ThermoFLUX ENplus-A1, ENplus-A2, EN-B Installation And Operation Manual

TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
Pellet burning boiler BioFlux series
EN
TECHNISCHES DATENBLATT MONTAGE- und BEDIENUNGSANLEITUNG
Pelletkessel Serie BioFlux
MANUEL TECHNIQUE INSTRUCTIONS pour L’INSTALLATION et L’EXPLOITATION
DE
FR
model:
serial number:
Version p0.8.1
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
Table of contents
1. EXPLANATION OF SYMBOLS AND SAFETY INSTRUCTIONS ..................................................................... 3
EN
1.1. Explanation of symbols .......................................................................................................................... 3
1.2. Requirements to boiler installation room .............................................................................................. 3
1.2.1. Instructions to boiler installer ................................................................................................................. 3
1.2.2. Instructions to installation user ............................................................................................................. 3
1.2.3. Minimum clearances for installation. Combustibility of construction materials ................................... 4
2. PRODUCT DESCRIPTION ......................................................................................................................... 4
3. FUELS ..................................................................................................................................................... 6
4. TRANSPORTATION .................................................................................................................................. 7
5. DELIVERY OF THE BOILER ................................................................................................................... 7
6. INSTALLATION OF THE HEATING BOILER ................................................................................................ 8
7. SETUP OF THE HEATING BOILER ............................................................................................................. 8
7.1. Connecng the boiler to a chimney ....................................................................................................... 8
7.2. Pellet boiler connecon to the pellet burner, auger and fuel hopper ................................................... 8
7.3. Connecng the boiler to the mains power supply .................................................................................. 9
7.4. Connecting the boiler to the heating installation ................................................................................... 9
7.5. Connection diagrams ............................................................................................................................ 11
8. FILLING THE HEATING INSTALLATION ................................................................................................ 11
9. OPERATION OF BOILER ...................................................................................................................... 11
10. CONTROLLER UNIT ............................................................................................................................... 14
10.1. Controller view. Explanation of buttons and indicators ....................................................................... 14
10.2. User menu ............................................................................................................................................ 16
11. MOUNTING OF FUEL HOPPER FH 500 .................................................................................................. 17
12. WARRANTY TERMS .............................................................................................................................. 17
13. TECHNICAL FEATURES .......................................................................................................................... 17
13.1. Technical features of PelleBurn pellet boiler ........................................................................................ 17
13.2. Technical parameters of Pell pellet burner ........................................................................................... 18
13.3. Technical features of fuel hoper FH 500 ............................................................................................... 19
14. RECYCLING ............................................................................................................................................ 20
APPENDIX - DIAGRAMS ........................................................................................................................ 59
2
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
1. EXPLANATION OF SYMBOLS AND SAFETY
1.1. Explanation of symbols CAUTION! - Important recommendation or
warning concerning safety conditions during installation and operation of boiler.
DANGER! - fault or improper use may cause
injury or be hazardous to life of humans or
animals.
FIRE HAZARD! - fault or improper installation
and operation may cause fire.
INFORMATION – Important information on
the proper operation of the product.
1.2. Requirements to boiler installation room
This manual contains important information for the safe and correct installation, start-up and trouble­free operation and maintenance of the boiler. The Pellet boiler can be used for heating rooms only in the manner described in this manual. The application and any other was the area of operation is not recommended by the manufacturer and is not responsible for the occurrence of defects
or failures.
Note the boiler type data on the factory rating label and the technical data provided in chapter 13 in order to ensure proper operation of the product.
1.2.1. Instructions to boiler installer
During installation and operation, the country-
specific requirements and regulations must be observed:
• Local construction regulations on installation,
air supply and exhaust gas extraction as well as chimney connection.
• Regulations and norms concerning the fitting of the
heating installation with safety devices.
• Required installation of a smoke detector in the
boiler room.
Use only original BURNiT parts
i
WARNING! Installation and setup of the boiler should be done by an authorized specialist / service shop and must follow the safety instructions and rules of operation.
INSTRUCTIONS
It is mandatory to assure a backup power generator of corresponding rated power!
(see table 1)
DANGER of intoxication, suffocation. Inadequate inflow of fresh air to the boiler room may result in dangerous leak of exhaust gases during boiler operation.
- Make sure the air inlets and exhaust gas outlets are not clogged or closed.
- If faults are not remedied immediately, the
!
1.2.2. Instructions to installation user
$
3
boiler must not be operated.
- The user must be provided with written instructions on the fault and the hazard it entails.
DANGER of fire when burning flammable materials or liquids.
- Flammable materials/liquids must not be left in close proximity of the burner and heating boiler.
- Instruct system user of the allowed minimum clearances from surrounding objects.
Customer must undergo boiler operation/ maintenance training by authorized installer/service shop.
Table 1.
Electricity consumpon of the boiler
Maximum electrical input 780 W
Electrical input at nominal heat output 80 W Electrical input at minimum heat output 60 W
DANGER of intoxication or explosion
Toxic gases may be discharged when burning waste, plastics, liquids.
- Use only the fuels indicated in this manual.
- In case of danger of explosion, ignition or discharge of exhaust gases in the room, stop the pellet burner from operation.
CAUTION! Danger of injury / damage of system due to incompetent operation.
- The boiler must be serviced only by persons familiar with the operation manual.
- As user, you are only allowed to start the boiler up, adjust the temperature of the boiler, shut the boiler down and clean it.
- Unattended children must not be allowed access to premises with running boiler inside.
It is mandatory to assure a backup power generator of corresponding rated power! (see table 1)
EN
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
Customer must undergo boiler operation/ maintenance training by authorized
installer/service shop.
EN
- Operate the pellet burner on recommended fuel only, and to that end you must regularly inspect the
boiler room.
- Do not use flammable liquids for ignition or increase
of burner output.
- Clean the burner surface using non-flammable agents only.
- Do not place flammable objects onto the burner housing and heating boiler cabinet or in their proximity. (see diagram 1 for the minimum
clearances)
- Do not store flammable materials in the boiler room.
- It is mandatory to strictly observe instructions for connecting the burner to power network as well as to all peripherals.
- Structural changes to Dual-chamber boiler by user can cause damage to equipment or injury.
- Do not allow contact transmission of electrical wire or touch any part of the boiler, where the surface temperature can exceed 70°C.
- This manual should be kept throughout the lifetime of the boiler.
1.2.3. Minimum clearances for installation and
flammability of construction materials
The applicable minimum clearances in your country may differ from the ones specified below. Please,
consult your installer.
The minimum distance from the burner, heating boiler or exhaust gas pipe to objects or walls must be
at least 200 mm.
Safety rules for user operation:
CAUTION! Hot surface! Risk of burns if you touch the running system. Burner housing, body and flange are hot surfaces during burner operation.
It is strictly prohibited to open boiler inspection doors with the burner running. The hopper hatch cover is not allowed to remain open for longer periods of time. Also, exercise caution when touching the observation port for monitoring the burning process. It may be hot.
Table 2. Flammability of construction materials
Class А – non-
flammable
Class B – hardly
flammable
Class С1/
С2 – Medium
flammable
Class C3 – easy
flammable
For general safety considerations, we recommend that the boiler be placed on a foundation made of class A material, see table 2.
Diagram 1. Recommended clearances
between boiler and walls /see page 59/
Ecological and highly-efficient pellet boiler PelleBurn is designed for firing wood pellets. The mantle fully covers the combustion chamber. Efficiency rate reaching 91%. Approved in accordance with EN 303­5, class 5. Set includes pellet boiler, pellet burner, auger and pellet fuel hopper (option).
2.1. Design structure of boiler PelleBurn.
Cylindrical body design is made of high-quality boiler steel sheets with thickness of 4 mm for the combustion chamber and 3 mm for the water mantle.
Ecological. A high-end pellet boiler. The wood pellets used for fueling the boiler are a renewable fuel with minimum carbon emissions and ultimate burning efficiency.
Automated. Owing to an improved algorithm with optional adjustment of a wide variety of parameters, the system may befinely tuned to any particular heating system to achieve optimum efficiencyand fuel consumption.
1) fully automated ignion and pellet feed;
2) exhaust fan ensures stable operaon of the boiler;
3) boiler-and-burner self-cleaning funcon;
4) controls the operaon of central heang circulaon pump;
5) controls the operaon of DHW (domesc hot water) pump;
6) controls by room thermostat;
7) ue gas sensor
4
Stone, bricks, ceramic tiles, baked clay, solutions, plaster free of organic additives.
Gypsum board panels, basalt fiber needled felt, fiberglass board, AKUMIN, Izomin, Rajolit, Lignos, Velox, Heraklit.
Wood beech, oak. Wood softwood, layered wood
Asphalt, cardboard, cellulose, tar, fiberboard, cork, polyurethane, polyethylene.
2. PRODUCT DESCRIPTION
Controller functions:
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
Efficient. To keep from losing heat into the ambience, the boiler is insulated on the outside by 100 mm high-temperature wool. With its state-of-the-art combustion control system and cylindrical body design construction the PelleBurn boiler achieves efficiency rate of as much as 91%.
2.2. Design of pellet burner Pell
The burner is made of high-quality stainless steel able to withstand temperatures of up to 1150°С. The burner must be installed on a heating boiler. The burner consists of two parts: combustion chamber tube and external tube with sheet metal mantle. Longitudinally, under the housing, there are blow chamber, fuel ignition heater, fan and power supply. On the upper part of the burner there is a feeder chute to which the pellet auger is attached. The combustion chamber consists of two tubes: Ember resistant steel tube inside the burner with holes for air intake along its entire length, opening for the hot air from the fuel ignition heater, opening for photosensor. Outer stainless steel tube. Between the two tubes there is a gap which provides for free circulation of the air necessary both for cooling and oxygen supply into the combustion chamber. The feeder chute allows 360° rotation for its best convenient positioning when connecting the pellet auger to the hopper.
Diagram 2. Design of Pellet Burner Pell
/see page 59/
Other elements of the burner are
Internal auger.
Dry contactless resistance heater assuring ignion of fuel.
Pneumac cleaning system of the combuson
chamber.
Feed fan, smooth regulaon (0% to 100 %).
Telescopic pull-out system of burner Pell for easy
maintenance.
2.3. Safety devices of pellet boiler-and-burner
A complex of safety devices provide for the safety of the appliance. Air-feed fan, step –regulated, controls the combustion according to energy needs and is maintained in optimal working order. Independent STB thermostat shut-off the burner and shut off the air feeding in the combustion chamber in case of rising boiler temperature.
Elbow-shape feeder chute. The geometrical shape of burner feeder chute prevents backfire entry from burner into pellet hopper. The flexible tube is melted at a temperature above 80°C. Thus prevent access to the hopper of the fire.
Thermostatic protection (80°С). The thermostatic protection is fitted on the feeder chute. When the surface of the feeder chute reaches 80°С, the control stops the feeding of pellets into the burner and signals for fault (BB Alarm).
Fuse. In case of electrical fault in the system of the burner (short circuit, current overload, etc.), the overload is borne by the electrical fuse fitted on the main control panel of the burner (10 А).
Power interruption. Innovative controller. In case
of power interruption, all parameter settings are stored in the memory of the controller. Upon the subsequent restart of the burner, the controller resumes the execution of the program from the point when the power interruption occurred.
2.4. Design of pellet auger
The auger transports pellets from fuel hopper to burner. Auger elements are: auger pipe, auger hose, motor, conveyor belt for moving the pellets.
D i a g ram 3 . D es ig n of pellet auger
/see page 59/
2.5. Design of fuel hopper FH 500
Pellet hopper, designated to serve biomass pellet-fired boilers. Pellet hopper design allowing installation by choice on either side of boiler. Made of cold-rolled steel sheets with PVC coating. Comfortable pellet charging hatch. Pellets inside hopper are fed into auger in order of reception. Precision leveling of hopper possible via screw-in legs. Elevated foundation with drain holes and container for separation and removal of pellet powder. The hopper capacity is determined using as calculation base the daily or weekly fuel consumption rate of burner. The pellet hopper usable volume of 500 litters allows charging of 280-300 kg of pellets with diameter 6 mm, and top-up/refill once a week (for burner of rated power up to 40 kW).
Diagram 4. Design of fuel hopper FH 500
/see page 59/
5
EN
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
All pellets are biomass manufactured from common
3. FUEL
low-growing plants and trees. The most common household type pellets are made of sawdust and
EN
milled wood chippings which are waste material from wood used in the production of logs, furniture and other products. Wood is the richest raw material which does not have any impact on the production costs of food products or ethyl alcohol (ethanol). The raw material is processed under high-pressure and temperature and is pressed to produce small­size cylindrical pellets. The production process may utilize soft wood material (such as softwood, pine), hardwood (oak) as well as recycled waste wood. Wood pellets are produced in hammer mills or wood
pellet plants.
Advantages of wood pellets:
Convenient storage.
Pellet bags can be stored on a small area in a dry garage, basement, service room or shed.
Easy loading.
In most cases the boiler hopper needs loading only once a week – this depends on the hopper capacity.
Better control of fuel quantity.
The small size of the pellets allows for precise fuel feeding. On the other hand, the supply of air for reaching optimal combustion efficiency is easier to adjust since the fuel quantity in the combustion chamber remains constant and predictable.
Fuel efficiency.
by consistently low moister content of pellets (consistently under 10% as opposed to 20% to 60% moisture content of the logs). Low moisture content, controlled fuel portions and precise air setting means high combustion efficiency and very low carbon oxides in the flue gases.
When purchasing pellets, ask for conformity declaration and certificate issued by an accredited laboratory and make sure the fuel meets the requirements indicated in the manual. If you purchase large amount of pellets
i
(bulk supply for the entire heating season for example), ask your supplier to provide accurate and true information about the storage conditions.
We recommend to use pellet with size of 6 - 8 mm. Density 600 - 750 kg/m3 heating value 4.7-5.5 kWh/ kg. Ash content – less than 1% and moisture content up to 8%., EN 14961-2:2011. The optimal density of the pellets which guarantees their quality is 605-700 kg per cubic meter. Pellet moisture content must not exceed 10%. Make sure you store your fuel in a dry and well-ventilated
place.
The optimal pellet ash content is ≤ 1%. This also provides for less frequent cleaning intervals for the
burner.
The table below contains the parameters which we recommend that you take into consideration when choosing fuel for your Pell burner.
High combustion efficiency is also determined
Table 3. European Certification of Wood Pellets for Heating Purposes
Parameters Units ENplus-A1 ENplus-A2 EN-B
Diameter mm
6 (± 1) 8 (± 1)
Length mm 15 ≤ L ≤ 40 Bulk density kg / m
2
≥ 600 ≥ 600 ≥ 600
1)
6 (± 1) 8 (± 1)
15 ≤ L ≤ 40
1)
Caloric/heang value MJ / kg ≥ 16,5-19 ≥ 16,3-19 ≥ 16,0-19 Humidity /moisture Ма .-% ≤ 10 ≤ 10 ≤ 10 Dust Ма .-% ≤ 1 Mechanical durability Ма .-% ≥ 97,5 Ash Ма .-%
2)
≤ 0,7 ≤ 1,5 ≤ 3,5
3)
4)
≤ 1
≥ 97,5
3)
4)
Melng point of ash °C ≥ 1200 ≥ 1100 ­Chlorine content Ма .-% Sulfur content Ма .-% Nitrogen content Ма .-%
Copper content mg / kg
2)
2)
2)
2)
≤ 0,02 ≤ 0,02 ≤ 0,03 ≤ 0,03 ≤ 0,03 ≤ 0,04
≤ 0,3 ≤ 0,3 ≤ 1,0
≤ 10 ≤ 10 ≤ 10
6 (± 1) 8 (± 1)
15 ≤ L ≤ 40
3)
≤ 1
≥ 96,5
1)
4)
6
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
Chromium content mg / kg Arsenic content mg / kg Cadmium content mg / kg Mercury content mg / kg Lead content mg / kg Nickel content mg / kg Zinc content mg / kg
1)
not more than 1% of the pellets may be longer than 40 mm, max. length 45 mm;
2)
dry weight;
3)
particles <3.15 mm, particulate matter, before handing over the goods;
4)
measurements with Ligno-Tester limit value ≥ 97,7% by weight.
4. TRANSPORTATION OF THE BOILER
We recommend to transport the heating boiler to the installation site in its packaging placed on the pallet. During transport and installation, depending on the weight, suitable safety devices should be used in accordance with Directive 2006/42/EC. When transporting items weighing more than 30 kg, the use of pallet jack, fork truck or other hoisting devices is a must. Product must be in original packaging following
2)
2)
2)
2)
2)
2)
2)
≤ 10 ≤ 10 ≤ 10 ≤ 1,0 ≤ 1,0 ≤ 1,0 ≤ 0,5 ≤ 0,5 ≤ 0,5 ≤ 0,1 ≤ 0,1 ≤ 0,1
≤ 10 ≤ 10 ≤ 10
≤ 10 ≤ 10 ≤ 10
≤ 100 ≤ 100 ≤ 100
motor drive (noise, friction) or failure of high-tech elements such as broken controller-screen, contact your nearest authorized service center for repairs and maintenance. The boiler is securely fastened with fasteners to a wooden pallet.
Important: When installing the boiler, the wooden pallet onto which the boiler is placed must be removed by unscrewing the bolted connections using flat ring
wrench S13.
the instructions on the label - to be protected from adverse weather conditions (snow, rain and dust) from the shocks, and other activities likely to cause
Diagram 5. Indications dimensions /see
page 59/
damage. In case of malfunction of the fan or the
Table 4. Overall dimensions of Set Pellet boiler PelleBurn, Pellet burner Pell and Fuel Hopper FH 500
PelleBurn 15 25 40
A1, mm A2, mm A3, mm B1, mm B2, mm B3, mm
C, mm D1, mm D2, mm D3, mm
Weight, kg
Pellet boiler, burner and pallet
Auger, box
Fuel Hopper, box
Pellet boiler, burner and pallet
Auger, box
Fuel Hopper, box Pellet boiler, burner and pallet Pellet boiler, burner and pallet
Auger, box
Fuel Hopper, box Pellet boiler, burner and pallet
Auger, box
Fuel Hopper, box
710 710 810 120 120 120 840 840 840
1100 1100 1320
260 260 260 810 810 810
125 125 125 1430 1630 1775 1700 1700 1700 1220 1220 1220
185 200 325
8 8 8
48 48 48
EN
5. DELIVERY OF THE BOILER
Inspect the integrity of the packaging upon delivery.
• Check whether all components have been delivered to you.
Boiler consignment package includes:
1) Pellet boiler PelleBurn with pellet burner Pell
2) Auger
3) Fuel hopper FH 500 (opon)
4) Safety valve 3 bar.
5) Fire irons
6) Technical passport. Installaon and operaon
manual
7) Service booklet and Warranty card
If any of the above items are missing, contact your
supplier.
7
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
6. INSTALLATION OF THE HEATING BOILER
The assembly, installation and set-up of the
EN
boiler must be performed by a technician authorized for such operations. Installer must indicate to the user of the installation the minimum clearances from flammable materials and liquids.
Requirements:
- Boiler room must be frost-proof;
- Boiler room must allow for continuous access of air
necessary to maintain combustion;
- Boilers must not be placed in inhabitable rooms;
- All boiler rooms must have correctly calculated vent depending on the boiler output. The vent must be protected by means of a net or grate.
The size of the vent is calculated according to the formula:
А=6,02*Q - where: А – area of the vent in cm2, Q – boiler output in kW
- Remove the packaging without polluting the
environment;
- Observe building supervision instructions, in particular the existing Ordinance on combustion devices and storage of combustion materials, on building requirements applicable to installation sites and on ventilation;
- The boiler must be placed on a foundation whose surface area is larger than the base of the heating boiler according to diagram 1;
- The boiler must be placed in a position which allows for the easiest possible cleaning and servicing;
- Installation must be carried out according to installation diagram 1 which shows the boiler housing;
- No objects made of flammable materials or liquids may be placed on/near the boiler;
7. SETUP OF THE HEATING BOILER
7.1. Connecng the boiler to a chimney
Boiler-to-chimney connecon must always comply with the exisng standards and rules. The chimney must provide sucient draught for evacuaon of the smoke under any condions. The proper funconing of the chimney requires adequate sizing of the chimney itself since the draught it produces aects combuson, boiler’s output and life span. The draught created by the chimney is in funconal relaon to its cross-secon, height and the roughness of its interior walls. No other appliance may be connected to the chimney serving the boiler. Chimney
diameter must not be smaller than the ue outlet of the boiler. Flue outlet must be connected to the chimney opening. In terms of mechanical properes, the ue outlet must be sturdy and properly sealed (to avoid gas leak) and allow for easy access for cleaning on the inside. The inner secon of the ue outlet must not be greater than the eecve secon of the chimney and must not narrow. Avoid using elbow
joints.
The chimney cleaning opening has to be in its lowest part. The chimney’s wall has to be three plied where the medium layer is from mineral wool. The thickness of the insulaon is not less than 30 mm when the chimney is seng up inside the house and the thickness is 50 mm, when the seng up is outside. Please entrust choosing a chimney and its installaon by a qualied professional. The required distance between the boiler and the chimney is 300-600 mm. Draught regulator (1) must be installed at least 600 mm from the joint (connecon).
Diagram 5.1. Boiler size and chimney
parameters /see page 60/
Table 5. Recommended minimum sizes and chimney
Boiler
output
15 kW Ø 130 10-20 25 kW Ø 130 10-20 40 kW Ø 150 10-20
Data in the tables are for indicative purposes. Draught depends on the diameter, height, uneven sections along the chimney surface and differences in temperature of
i
combustion products and outside air. We recommend that you use chimney fitted with flue terminal. Heating specialist must calculate the precise sizing of the chimney.
7.2. Pellet boiler connecon to the pellet burner,
auger and fuel hopper
- Take the auger hose (from the auger set). Using a bracket, clamp one end of the hose onto the motor­end outlet of the pellet auger.
- Using a bracket, clamp other end onto the feeding chute of burner
- Remember pellet auger must be installed at 45° angle to the ground horizontal surface.
- Fill the hopper with fuel (see table 2 for parameters of the fuel types used)
8
dra
Chimney
diameter, mm
Chimney
dra, Pа
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
- Plug the power cord of the pellet auger into the indicated Schuko-type boiler socket on the le side of the boiler housing.
Diagram 6. Pellet burner Pell and Fuel
Hopper FH connected to Pellet boiler
PelleBurn /see page 60/
1. Pellet boiler PelleBurn;
2. Pellet burner Pell;
3. Auger hose;
4. Auger;
5. Fuel Hopper FH.
7.3. Connecng the boiler to the mains power
supply
Such connecon must be performed by a
technician / service shop authorized for
such operaons.
Cauon! ELECTRIC SHOCK HAZARD!
- Before opening the unit: switch o the
voltage and secure the unit against accidental restart.
- Observeinstallaoninstrucons.
Improper cable connecons may damage
the regulator!
The device may be damaged if struck by a lightning. Make sure it is unplugged during the storms.
It is mandatory to assure a backup power generator of corresponding rated power!
(see table 1)
Legend /Diagrams 7 and 8/
To bring into exploitaon the boiler and auger must be connected to the electricity network 220V/50Hz with power cord. Create ght connecon with the electrical mains which complies with the local regulaons.
Diagram 7. Wiring diagram of connecon
of boiler elements to the controller
/see page 61/
Diagram 8. Wiring diagram of connecon
of burner elements to the controller
and connecng socket /see page 62-63/
7.4. Connecng the boiler to the heang installaon.
Such connecon must be performed by a
technician / service shop authorized for
such operaons.
When the boiler is connected to a heang system, it is mandatory to install a 3 bar relief valve and expansion vessel. No shut-o ngs may be installed between the relief valve, expansion vessel and boiler.
It is mandatory to install a three-way valve (Laddomat or similar) or a four-way mixing valve which to ensure that the temperature
of the heang medium fed into the boiler from the heang installaon is at least 65°С.
Elements INPUTS Symbol
Room thermostat I02 RT Boiler sensor I03 B
STB termostat of the burner I04 RB Sensor water heater I05 WH Sensor exhaust I06 PT Temperature sensor at the top of the buffer I08 AT Temperature sensor at the bottom of the buffer I17 NA1
EN
Elements OUTPUTS Symbol
Fan smoke gases О 01 FSG Ignitor О 03 IGN Fan cleaning of the burner О 04 FC Screw fuel О 05 SF Screw burner О 06 SB Pump heang О 07 PH Pump water heater О 08 PHW Electric motor of self-cleaning system О 10 CS
Electric motor of clean ash О 11 CA
9
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
Table 6. TROUBLE-SHOOTING TABLE
Cause Solution
EN
Duetounsealedconnecons Installtheconnecngpipingstrain-freetotheboilerconnecons.
Due to freezing
Boiler water too hot, heang bodies too cold
1. Hydraulic resistance is too high.
2. Air in the system
3.Inoperablecirculaonpump
The STB safety thermostat has been triggered.
Unable to reach normal temperature mode of 65°-85° С
Inadequate sizing and/or
combinaonofheangappliances
Ejecon of unburned pellets into the combuson chamber of the boiler
Poor adjustment of the fuel-to-air
raofromtheburnercontroller
Ulizaonoflow-qualitypellets
Formaon of clinkers and noncombusble inclusions inside burner body
Ulizaonoflow-quality pellets(see secon3.Fuel) Low performance of the automac
cleaning system Impropersengoffuel-airmixture Adjust using gas analyzer
Poor chimney draught or high internal resistance of the boiler
combusonchamber Blockage of burner combuson
chamber due to build-up of
noncombusblematerials Impropersengoffuel-airmixture Adjust using gas analyzer
Dust on the photosensor It is necessary to clean the photosensor. Refer to the manual for the
Boiler temperature too high. Controller failure.
Gridpoweructuaons
Power failure High temperature of exhaust gases.
High temperature alarm is turning on High temperature in boiler water jacket and low temperature in the
buertank.
Installaon damage
Ifthe heang installaon,including thepipingnetwork, hasnotbeen built frost-proof,we recommend that you llthe heanginstallaon withaliquidwhichhaslowfreezingpointandcorrosionproteconand anfreezeagent.
Make sure the circulaon pump has been properly selected and the heanginstallaonisoftheproperdimensions.(Youmustcontactyour
installer.)
Uponreachingatemperatureof95°С,thethermostacsafetyprotecon device is triggered and the fan is turned o. To resume protecon,
remove the black cap on the front panel of the boiler and press the
buonon theSTB-thermostat.Contactyourinstallertodeterminethe causeofprotecontriggering.
Low boiler temperature.
Immediately consult your installer about the problem.
Contactyour installer.It is necessarytoset the burnerproperlyusing
gas analyzer
Use only fuelwhichmeetstherequirementsspecied in the manual. (seesecon3.Fuel)
Useonlyfuelwhichmeetstherequirementsspeciedinthemanual.
Increaseturn-onfrequencyoftheautomaccleaningsystem.
Smoke in the pellet hopper
Immediately consult your installer about the problem.
Itisnecessarytocleantheburnercombusonchamberusingbrush
cleaning procedure.
It is mandatory to assure a backup power generator of corresponding
ratedpower!(seetable1)
Fume exhaust tubes of boiler water jacket are clogged with soot. Reduced heat transfer. The boiler should be cleaned. Please contact an authorized specialist / service shop to clean the boiler.
1.IncorrectON/OFFtemperaturesengsofpumps.
2.Incorrectsizingofheangsystem.
10
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
7.5. Connection diagrams
Such connecons must be performed by
a technician / service shop authorized for
such operaons.
Diagram 9. Connecon of boiler PelleBurn to three-way valve/see page 64/
Diagram 10. Connecon of boiler PelleBurn to P type buer tank
Diagram 11. Connecon of boiler PelleBurn to combi tank KSC2,
at plate solar collector PK and three-way valve/see page 65/
Diagram 12. Connecon of boiler PelleBurn to solar tank SON, buer thank P,
at plate solar collector PK and three-way valve /see page 65/
Problem Prevenon
Possible installaon damage due to strains in the material caused by temperature dierences
Danger of installaon damage due to accumulaon of deposits Condensate formaon and tar deposits may shorten boiler’s operaonal life.
and three-way valve /see page 64/
8. FILLING THE HEATING INSTALLATION
Table 6
Fill the heang installaon only in cold condions (inlet temperature must not exceed 40°C).
- Do not operate the heang boiler for a long period of me in paral load mode
- The temperature at the boiler inlet must not be less than 65°C, boiler water temperature must be between 80°C and 85°C.
- Use the boiler for a short period to heat warm water in the
summer.
EN
9. OPERATION OF BOILER
Failure to observe the installation and operating requirements described in the manual and the service booklet voids the warranty.
9.1. Operaon of pellet boiler PelleBurn with pellet
burner Pell
Ignion. Aer starng the burner up from the control panel, the main pellet auger conveys certain amount of fuel from the pellet hopper to the burner. This specic amount of pellets is set by the installer and depends on the fuel characteriscs. The fed­in quanty of pellets is conveyed from the auger conveyor built in the burner to the combuson chamber where it is being ignited using hot air.
Burning. The burning process takes place in the combuson chamber and, aer it has been fed into the combuson chamber, the fuel is then transported from the internal auger conveyor to the combuson chamber in porons. This allows for constant and opmal burning rate of the fuel. The boiler is controlled and operated by sensor exhaust. This sensor measures the temperature of exhaust gases and provides informaon to the control unit ignion or disconnuaon of combuson. The output of the
burner is determined by the intervals preset on the control panel taking into account the heang value, size and density of the pellets.
Automac cleaning system. The pellet boiler is equipped with innovave automac cleaning system for combuson chambers of both devices. A powerful cleaning motor built in the burner body, air is being blown in at high speed and rate thus removing all residues – ash, noncombusble inclusions, etc. built up into the combuson chamber of the boiler. At the same me the boiler turns on automac ash removal which is transported to the ash container through screw located in the lower part. These automac cleaning cycles last several seconds and can be addionally adjusted as well as their repeat rate depending on the load of the burner.
9.2. Important recommendaons for long-lasng and correct operaon of the boiler
- For assembly and installaon of the burner follow the requirements in this manual.
- Use only recommended in this manual fuel.
- Disassemble the burner from the boiler body before clean it. Depending on fuel and burner sengs, clean the pellet burner once a month.
- User`s training for operaon and maintenance of
11
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
burner is performed by an authorized installer or service shop.
Failure to observe the installation and
EN
9.3. Requirements for the cleaning and maintenance of PelleBurn pellet boiler with pellet burner.
- It is mandatory to clean the ashes from the container once a week. Unhook the buckles on both sides of ash container. Pull ash container out of the boiler and clean it. Once you have emped the container of ashes, please make sure you close the container cover ghtly, buckle-lock it to the container buckles, then buckle-lock the container to the boiler buckles.
- It is mandatory to clean once a month the
Before the start of the heang season it is mandatory to check and clean the following components of the boiler:
9.3.1 Cleaning and maintenance of sucon fan
operating requirements described in the manual and the service booklet voids the warranty.
Attention! Important instructions regarding cleaning of boiler.
Caution! Hot surfaces. Before cleaning the boiler, make sure the fire in it has died out and the boiler has
cooled down.
Diagram 13
combuson chamber of the burner.
Attention! Cleaning and maintenance of the boiler should be carried out only by an authorised installer/service shop.
- Remove the two parts of the boiler top cover by liing them upwards
2
- Remove the cover of the inner boiler body (2) using wrench S13.
- Clean the fan blade (1) and the dust and soot deposits. Use a brush. If the fan is not properly cleaned, this will aect the boiler performance.
- Check the nut holding the fan blade (2) to be well ghtened. Aenon: the nut is le threaded!
- Upon assembling the gasket of the fan must t well in place. If necessary, change the fan gasket.
- Mount back the top cover
9.3.2. Cleaning and maintenance of the cleaning
system:
- Remove the top cover (9.3.1).
- Cleaning system (1). Clean the ash deposits using a vacuum cleaner and/or a brush.
1
Diagram 15
Diagram 16
Diagram 14
- Hold a visual inspecon of the condion of the
Diagram 17
12
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
enre cleaning system. Also check the drive mechanism, located outside the combuson chamber.
- Upon detecon of worn piece/part, it is recommended to have it replaced with a new one.
- Dismantle ue pipes from the cleaning system of the boiler and clean them well. For this purpose: remove the upper ring of the automac cleaning system (2). Use wrench S10. Use a brush to clean the ue pipes thoroughly one by one. Mount back the ue pipes and the upper ring of the cleaning
system.
- Check silicone gasket mounted on the edge of the boiler. Replace if cracked or hardened.
- Mount back the top cover.
- The ashes from the cleaning system are collected in a drawer container for ash and soot. Upon compleon of the cleaning procedure, empty the
container.
9.3.3. Servicing of the burner:
- Remove the burner casing from the boiler cabinet body – using the handles (1) li it up then pull it towards yourself (Diagram18).
- The rail itself is hinge-xed to the boiler body, swing it to the right to withdraw the burner from the boiler body. Unscrew the marked bolts to dismount the burner from the ange holding it xed to the
rail.
EN
Diagram 20
- Remove connector (2) housing the wire connecons
Diagram 18
between the burner and the controller. Unscrew the 2 marked plasc head bolts (1) to release the slide rail onto which the burner is mounted.
Diagram 19
- Carefully slide out the rail with the burner mounted
on.
- Disassemble the burner combuson chamber.
Diagram 21
- Clean the inside of the burner chamber thoroughly from residues. Use a bodkin to release all clogged orices along the combuson chamber.
- Remove the ashes from inside the burner. Use a vacuum cleaner and a brush.
- Inspect and clean the motors and sensors in the
boiler.
- When mounng the burner back onto the boiler, replace the seal between the burner ange and the
boiler.
9.3.4. Feeding auger:
- Completely empty the pellet hopper.
- Dismantle the auger from the pellet hopper: release the top of the exible hose (1) from the auger tube; extract the auger (2) by pulling it out of the hopper.
13
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
EN
Diagram 22
- Clean the Auger from the ashes of the transport of pellets: Dust o (3) and clean the ashes from the collected (4)
- Mount the feeding auger back to the pellet hopper.
Important! Fill Auger and calibrate it. If auger remain without fuel for transportation will deteriorate normal boiler operation.
9.3.5. Pellet hopper:
- Completely empty the pellet hopper
- Clean the pellet ash residues from the boom of the hopper. Use the scraper and a vacuum cleaner.
10. CONTROLLER UNIT
10.1. Controller view. Explanaon of buons and
indicators.
LCD screen:
The controller screen displays the informaon for the operaon of the
facility.
Explanaon of buons:
When logging into a menu, use arrow keys
UP and DOWN
to move from
one page to another.
Enter buon permits adjustment of the page. When adjustment is enabled, use arrow keys UP
and DOWN to adjust the parameter.
Press ENTER to change the parameters.
Press F to exit the menu. Conrm with Enter buon .
Display symbols explanaon:
Auto Clean symbol appears in right upper part of display. Acve auto cleaning symbol means boiler automac cleaning mode.
Crossed-out ame symbol appears in upper right part of display. Means that the boiler enters into Exnguish mode.
CH priority /Radiator /symbol appears in upper part of display. Means than Central Heang priority is set to heat up the central
heang.
Domesc Hot Water /shower/ priority symbol appears in upper part of display. Means than
DHW priority is set to heat up the domesc hot water. When set DHW temperature is reached, DHW pump stops and CH pump is acvated.
Parallel pumps /shower and radiator/ symbol appears in upper part of display. Means that is set equal priority to both pumps. They work in parallel and are
controlled by temperature sensors.
Summer mode /shower and sun/ symbol means than is set Summer heang mode. Only DHW pump is acve.
Burner ame symbol appears in upper right part of display. Means that burner is acvated. Burner goes into Ignion mode
and upcoming boiler re up.
Flame 2 symbol means Maximum output
mode of boiler. In this mode the boiler
operates at maximum output.
Flame 1 symbol means Low output mode of
boiler. In this mode the boiler operates at
minimum output.
The noce “Hi” appearance on the screen where the boiler temperature is displayed means that the measured boiler body
temperature is above 120°C. Flashing and beeping alarm is acvated. When the issue is corrected, nocaon can be deleted. Disconnect fuel auger from boiler plug-in socket. Upon any such occurrence please contact immediately your installer for system checkup.
Boiler increased temperature. Those two
symbols appearance on the screen where the
boiler temperature is displayed means that
boiler temperature has increased up to 99°C. In such a case, please contact immediately to your installer to check the system.
14
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
Error symbol appears in right upper part of display. Flashing and beeping error symbol mean error or fault in boiler operaon. Use
Enter“ buon to move to next screen with error nocaon in lower le part of display. When the issue is corrected, error nocaon can be deleted. When disconnect the boiler from electrical supply for few seconds and then switch on it again, boiler goes back to normal operaon (error nocaon is deleted).
Cleaning system of exhaust gas tubes is activated.
S
Ash cleaning system is activated.
A
Factory seng - Alarms
BB ALARM
SENSOR E1
SENSOR E2
IGNITION FAIL Failure ignion
BURNOUT
DHW E1
DHW E2
Cleanup
TE Alarm
TE E1
TE E2
CH btm E1
CH btm E2
CH top E1
CH top E2
When restarng the controller alarm is deacvated.
Reverse re Alarm (when the thermostat contact RB input is
open) Boiler Temperature Sensor is
missing (input B) Boiler Temperature Sensor Short
circuit ( input B)
Exhaust gas temparature is too low in Operation mode. If the exhaust gases temperature drops below 85°C the boiler will shift into extinguishing mode.
Water Heater Temperature Sensor
is missing (input WH)
Water Heater Temperature Sensor
Short circuit (input WH) This alarm appears when gas temperature rises above 180°C This alarm appears when gas temperature rises above 220°С Temperature sensor of exhaust gases is missing Short circuit of temperature sensor of exhaust gases Temperature sensor of lower part of buffer tank is missing (when in chosen scheme with buffer tank) Short circuit of temperature sensor of lower part of buffer tank (when in chosen scheme with buffer tank)
Temperature sensor of upper part
of buffer tank is missing (when in chosen scheme with buffer tank) Short circuit of temperature sensor of upper part of buffer tank (when in chosen scheme with buffer tank)
Notify the authorized installer/ service to be performed immediately inspection of the boiler and heating installation.
”С” symbol means that the motor of automac cleaning system is acvated.
The symbol “T” indicates that a room thermostat is connected to the controller
In “CH Priority” mode the room thermostat controls the burner by starng and stopping it. In “DHW Priority” mode the room thermostat controls the heang installaon pump by starng it when the temperature of the domesc hot water has reached the maximum preset temperature. In “Parallel Pumps” mode the room thermostat controls the heang installaon pump regardless of the temperature of domesc hot water. In “Summer Mode” the room thermostat is disabled.
Lights for operang:
- Pump heang system
- Pump Domesc hot water.
10.2. User menu
10.2.1. Inial (start-up screen) „Standby“
buon you can browse the quick menu (boom le) where the following read-only data is displayed:
Maximum set temperature t=85oC, temperature of domesc hot water where such heang circuit
is connected); Light intensity in the burner; Burner status (detected errors, if any); Date.
the facility for any reason will be displayed as an
error.
temperature of domesc hot water inside the water heater.
15
of the burner (the boiler).
The burner is in standby mode. The display shows: Temperature in the boiler (23 degrees), me, and by pressing the Enter
Error message. If there is an emergency in the operaon of
Мaximum set boiler
temperature.
Current date.
Parameter t
indicates
DHW
EN
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
Parameter tСН indicates the
temperature at upper and boom part of the buer tank.
EN
This screen is acve only when has been selected the menu opon for boiler control according to buer
temperature.
set the follow parameters:
Navigaon arrow Up” and “Navigaon arrow Down”. Aer entering the correct value press buon “Enter”.
. From this menu you can
scheme (with buer tank included) is selected, whereas the two sensors reading these temperatures are mounted in the upper, respecvely lower part of the buer tank (cf. boiler connecon schemes).
down and using the Enter buon you can change the parameters. You can adjust the maximum domesc hot water temperature inside the storage tank, as well as the switch-on hysteresis for the circulaon pump aer a drop of DHW temperature inside the storage tank.
value of instantaneous
Parameter tE indicates exhaust
gases temperature.
Set maximum
temperature of the boiler through navigaon arrows. Press buon F and hold for 3 seconds to
Possibility for forced turn on of ash and soot transport screw. Time seng of screw operaon. To set start and operang me use buons
Use this menu to adjust switch-
on temperature of central
heang pump.
preset buer tank circulaon pump switch-on and switch­o temperatures provided such heang installaon
From this menu you can adjust the maximum temperature in the domesc hot water storage tank, whereas by navigang from the arrow keys up and
Use UP and DOWN arrow keys in Set Time menu to set the unit’s built-in mer/clock.
Use UP and DOWN arrow keys in Set Date menu to set the date.
Use UP and DOWN arrow keys in Contrast menu to adjust the LCD display backlight level. Conrm sengs by shiing to next submenu through a single
pressing of the funconal key F.
Use this menu to choose the language of the controller. Choose a language by pressing navigation arrows and button “Enter”.
10.2.2. Burner start-up „Switch mode“
Burner start-up. Aer pressing the “F” buon and using the navigaon arrows, the “Auto or „Standby” menu is selected.
Set the priority mode of the burner through “navigaon arrows.”
- CH + DHW – Both pumps /CH-central heang pump and DHW – domesc hot water pump /are acve.
- CH only – In this mode of operaon the only acve pump is the CH circulaon pump for the heang installaon (CH pump). In this mode, the boiler can be managed via a room thermostat or be temperature-controlled by the temperature inside the connected buer tank to it (depending on the connecon scheme)
- Summer Mode – Boiler works for heang of domesc hot water only.
If you have selected the (CH + DHW) opon, upon conrmaon of command via the F buon you may navigate to the next screen.
From this menu you can set up and adjust DHW pump acvity periods. Use the arrow keys to set me (HH:MM). Use “Enter
buon to checkmark desired me period opon. If no opon is check-marked, the controller will maintain DHW temperature as a
16
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
priority. Only when its preset value is reached, the CH circulaon pump will start.
Important – The use of “External room thermostat for the burner” option
(Thermostat) is active only if option is selected (CH Priority – priority of central
heating installation pump).
10.2.3. Burner shut-down „Standby“
Pressing the “F” buon will take you to the main menu and by using the navigaon arrows
menu and conrm the selecon by pressing “F”. The burner goes into exnguishing mode. Set the temperature to start heang pump.
11. MOUNTING OF FUEL HOPPER FH 500
Fuel hopper FH 500 has a capacity of 500 liters pellets. Its design allowing installation by choice on either side of boiler. An important condition is to be leveled. Before loading the pellets, make sure that the hopper is clean. Empty the container for pellet powder and dust. Fuel hopper hatch-cover must be closed during operation. Detailed description for the assembly of a fuel hopper FH 500 will find the User manual for assembling the fuel hopper FH 500.
you can select the “Standby
12. WARRANTY TERMS
The warranty terms are described in the Service booklet included in the supply.
EN
13. TECHNICAL FEATURES
13.1. Technical features of PelleBurn pellet boiler
13.1.1. Elements of PelleBurn pellet boiler
Diagram 23. Elements of PelleBurn pellet
boiler /see page 66/
1. Housing
2. High efficiency thermal insulation
3. Chimney
4. Flue gas extraction fan
5. Fume exhaust tube
6. Automatic cleaning system
7. Water mantle
8. Combustion chamber
9. Ash-and-soot container
10. Burner housing
11. Pellet burner
12. Burner flange
13. Controller unit
14. Ash and soot transport screw with stirring mechanism
13.1.2. Technical parameters of PelleBurn pellet boiler
PelleBurn 15 PelleBurn 25 PelleBurn 40
Nominal heat output
Min / Max heat output
Height H
Width L / Depth D
Mantle volume
Combuson chamber volume
Combuson chamber resistance
Water side pressure drop (ΔT = 20°C) Pa/mH2O 480/0,048 850/0,085 1350/0,135
Required chimney draught
Insulaon
Electric power supply
Recommended fuel
Operang temperature range
Operang pressure
Pellet burner Pell Power kW 5÷15 8÷25 10÷40
Boiler Doors
Weight
kW 15 25 40 kW 5÷15 8÷25 10÷40
mm 1290 1430 1700 mm 640/1120 640/1120 700/1120 l 55 70 101 l 43 53 73
Pa/mbar 10/0,10 11/0,11 12/0,12
Pa 10÷20 10÷20 10÷20
100 mm high-eciency thermal wool
lined with aluminum foil
20 mm high-eciency black veil rockwood
V/Hz/A 230/50/10 230/50/10 230/50/10
wood-pellets, diameter 6÷8 mm
°C 65-85 65-85 65-85
bar 3 3 3 kg 220 240 358
17
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
EN
Pellet fuel hopper
Cold water inlet
Hot water outlet
Safety line sleeve
Air vent
Cleaning opening
Combuson viewer
Boiler ue gas extracon fan
Burner air-feed fan
Automac cleaning device
Cleaning device motor
Burner ange
Ash and soot transport motor
Ash-and-soot container
Control unit
L 500 500 500
A, mm R ¾’’/100 R ¾’’/100 R ¾’’/100 B, mm R ¾’’/980 R ¾’’/1120 R ¾’’/1417 К
I
F,
Flue
J, O, mm 140/300 140/300 140/300
Drain
E V
W1,
mm
W2,
mm P, mm 950 1090 1390
M Z
N, mm 170 170 170 Т
U
Diagram 23.1 /see page 66/
13.2. Technical features of Pell pellet burner
13.2.1. Elements of Pell pellet burner
ø mm mm
133
1280
320
1220
510
 
133
1480
320
1385
510
150
1700
350
1665
565
Diagram 24. Elements of Pell pellet burner /see page 67/
1. Pellet burner Pell;
2. Auger hose;
3. Auger motor;
4. Automatic pellet auger;
6. Burner (inner) auger;
7. Combustion chamber corps;
8. Combustion chamber;
9. Automatic cleaning system;
5. Feeder chute;
13.2.2. Spare parts for Pell pellet burner
Diagram 25. Spare parts for BURNiT Pell pellet burner /see page 67/
Part Number Model PEll 25 Model PEll 40
1 82801300000002 х 1 82801300000003 х 2 82801300000010 Х 2 82801300000011 х 3 89801300000006 х 3 89801300000024 Х 4 89800000000005 Х Х 5 89801381000001 Х
18
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
5 89801381000002 Х 6 78801100000001 Х Х 7 32800032000001 Х Х 8 89080000000006 Х Х
9 89801200000006 Х Х 10 89800000000004 Х Х 11 32590000000092 Х Х 12 89080000000007 Х Х 13 32640000000004 Х 13 32640000000003 Х 14 32800000000006 x(C130) x(C130)
13.3. Technical features of fuel hoper FH 500
13.3.1. Elements of fuel hopper FH 500
Diagram 26. Elements of fuel hopper FH 500 /see page 67/
1. Pellets loading hatch-cover
2. Side panels
3. Auger mounting side-panel opening
4. Auger holder
5. Pellet-guide plates
6. Drainage holes
13.3.2. Technical parameters of fuel hopper FH 500
Capacity l 500
Max/Min wood pellets load ø, 6÷8 mm kg 280÷300 / 15
Height H mm 1260
Width L / Depth D mm 772 / 730
Foundaon B, mm 53
Auger mounng opening C, ø mm 76
Auger holder E
Pellet-load hatch F, mm 400 / 772
Hinges G
Drainage holes J
Dust container X
Inclinaon of guide plates P 45°
Pellet-colecng boom R, mm 300 / 300
Leveling feet Z
Guide plate seal
Weight kg 82
7. Leveling feet
8. Dust container cover
9. Dust container
10. Pellet-collecting bottom
11. Foundation
12. Guide plate seal
EN
FH 500
  
 
Diagram 27 /see page 67/
19
TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL
14. RECYCLING
Submit all packaging material for recycling according to the local regulations and requirements. At the end of life cycle of each product its
EN
components are due to be disposed of in conformity with regulatory prescriptions. Obsolete equipment shall be collected separately from other recyclable waste containing materials with adverse effect on health and environment. According to Directive 2002/96/EC regarding electrical and electronic equipment waste, disposal thereof is required separately from the normal flow of solid household waste.
Expired appliances must be collected separately from other recyclable waste containing substances hazardous to health and environment. Both metal and non-metal parts are sold out to licensed organizations for recyclable metal or non-metal waste collection. In any case they should not be treated as household waste.
20
TECHNISCHES DATENBLATT MONTAGE- und BEDIENUNGSANLEITUNG
INHALT
1. ERLÄUTERUNG DER SYMBOLEN UND SICHERHEITSHINWEISE .............................................................. 22
1.1. Erläuterung der Symbolen .................................................................................................................... 22
1.2. Hinweise für den Raum der der Kesselaufstellung ................................................................................ 22
1.2.1. Hinweise für den Installateur ................................................................................................................ 22
1.2.2. Hinweise für Anlagebenutzer ................................................................................................................ 22
1.2.3. Mindestabstände bei der Montage und Brennbarkeit der Baumaterialien .. ........................................ 23
2. BESCHREIBUNG VOM ERZEUGNIS ..................................................................................................... 23
2.1. Konstruktion des Pelletkessels .............................................................................................................. 23
2.2. Konstruktion von Pelletbrenner ............................................................................................................ 24
2.3. Sicherheitsschutz des Pelletkessels und des Brenners ......................................................................... 24
2.4. Schneckeneinrichtungen für Beförderung von Pellets .......................................................................... 25
2.5. Einrichtungen für Pelletsbunker FH 500 ................................................................................................ 25
3. BRENNSTOFFE ....................................................................................................................................... 25
4. BEFÖRDERUNG VON KESSEL ................................................................................................................. 26
5. KESSELLIEFERUNG ............................................................................................................................... 27
6. MONTAGE VOM HEIZKESSEL ............................................................................................................. 27
7. MONTAGE DES HEIZKESSELS .............................................................................................................. 27
7.1. Anschluss des Kessels an einen Schornstein ......................................................................................... 27
7.2. Anschluss des Kessels an Bunker und Schnecke .................................................................................... 28
7.3. Anschluss des Kessels und Brenner an das Stromnetz .......................................................................... 28
7.4. Kessel - Anschluss an das Heizsystem ................................................................................................... 29
7.5. Schema Zusammenfügung .................................................................................................................... 31
8. FÜLLEN DER HEIZANLAGE ................................................................................................................... 31
9. NUTZUNG VOM KESSEL ......................................................................................................................... 31
DE
10. MIKROPROZESSORSTEUERUNG ............................................................................................................ 34
10.1. Ansicht vom Kontroller. Erläuterung der Druckknöpfe und der Indikatoren ........................................ 34
10.2. Benutzermenü ..................................................................................................................................... 35
11. MONTAGE VON PELLETBUNKER ........................................................................................................... 37
12. GARANTIEBEDINGUNGEN ..................................................................................................................... 37
13. TECHNISCHE CHARATERISTIKEN ............................................................................................................ 37
13.1. Technische Charakteristiken des Pelletskessels PelleFlux .................................................................... 37
13.2. Technische Parameter für Pelletbrenner BioFlux ........................................................................................ 38
13.3. Technische Charakteristiken des Pelletsbunker FH500 ......................................................................... 39
14. RECYCLING UND AUSWURF ............................................................................................................... 39
ANHANG - Diagramme .................................................................................................................................... 59
21
Loading...
+ 47 hidden pages