Thermo-Dynamics Boiler THERMOTRON OTF, THERMOTRON ITF Operation, Maintenance, And Installation Instructions

THERMOTRON
ROUTE 61 • P.O. BOX 325 • SCHUYLKILL HAVEN, PA 17972 • (570) 385-0731 • FAX (570) 385-5304
Operation
Thermo-Dynamics
www.thermodynami c s b o i ler.com
Maintenance and Installation Instructions
Models OTF / ITF
Contents
Assembly Diagrams
General Information ......................................................................................................1
Service Policy ................................................................................................................1
Installation Instructions .................................................................................................2
Filling Instructions .........................................................................................................2
Winterizing .....................................................................................................................3
Start-Up and Operation ................................................................................................3
Piping/Connection Diagrams .......................................................................................4
......................................................................................................5
Trouble Shooting ..........................................................................................................6
Care and Maintenance .................................................................................................6
Pool Coil Diagram .........................................................................................................7
Wiring Diagrams ...........................................................................................................8
Parts List ........................................................................................................................9
Specifications ..........................................................................................................10
Home Owner Information .......................................................................................11
Set-Up and Service Records ..................................................................................12
Warranty Information ..............................................................................................12
1
General Information
nance. Proper care and maintenance of your pool heater will allow you to enjoy the benefits of your
with a high quality trouble free product that will be part of your family for many years to come.
1) Please read all instructions and review all diagrams prior to proceeding with installation.
2) Instructions and diagrams are intended only as guidelines.
3) Installations must conform with all applicable national, state and local codes.
4) Additional guidelines are available from National Fire Protection Association (NFPA), American society of Mechanical Engineers (ASME) and Building Officials and Code Administrators (BOCA).
Service Policy
Congratulations on the purchase of your new pool heater. Here at Thermo-Dynamics Boiler Company we pride ourselves on the design and construction of our product. Our intent is to furnish you with a high quality appliance that will provide you and your family with years of trouble free service.
In order to maintain peak performance of your pool heater, it is recommended that the unit be win­terized at the end of the season and that the burner/boiler be serviced annually. Servicing of your appliance must be performed by a qualified heating technician. You should utilize a qualified heat­ing technician familiar with your installation to manage your heater and perform periodic mainte-
new purchase as well as extend its long useful life. In the event that your serviceman encounters difficulty with the pool heater, he/she shall contact
the distributor from which the product was purchased. The distributor shall, in turn, contact the Thermo-Dynamics sales representative for your area. By adhering to this protocol, Thermo­Dynamics wishes to provide you with responsive and unparalleled service. We realize the impor­tance that our product means to you and your family and our goal is to get your heater up and run­ning as quickly as possible.
Thank you for purchasing the Thermo-Dynamics pool heater. Again, it is our intent to provide you Please consider Thermo-Dynamics Boiler Company in the future for all of your home heating
needs.
2
Section I. Installation Instructions Control of combustion draft.
(1)
Locating The Heater:
pool circulation lines are at the back of
component to obtaining optimum
open take temperature readings for
(B)
ITF Series (Indoor Units)
two (2) feet higher than any portion of
pitched upward at least one-quarter
joint should be securely fastened with
effect the shortest possible run of
an indirect heater using primary water
water
Therefore the pool heater, or boiler
Before uncrating the unit prepare the location. It should be placed upon a good level concrete floor or pad. Care should be taken to locate the unit for easy accessibility. Please maintain the following clearances to combustible materials:
OTF
(Outdoor Pool Heaters)
Front 24 inches Back 24 inches
Sides 12 inches
ITF
(Indoor Pool Heaters)
Front 24 inches Back 12 inches
Sides 12 inches
In addition, the air openings in the cabinet shall have adequate clearance to allow for sufficient air intake to the burner. Uncrate the unit as close to its permanent location as possible to prevent handling damage.
(2) Connections:
Do not run any piping along the front access panel of heater as they may interfere with servicing. The tap­pings for connecting the unit to the
the heater. These connections are 1­1/2" NPT. Connections should be made as per the piping illustration on page 4. Install unions at the heat exchanger so it can be readily removed for service. If plastic pipe is used, make connection to the unit with metal piping and run metal piping to the floor line before joining to plastic
pipe. This will act as a “heat-trap” and
reduce possible damage to the plastic pipes from overheating. Install posi­tive check valve on inlet side. Install a Tee joint at the coil where the PIPING FROM the pool filter/pump ENTERS the coil. Install the copper well provid­ed into the piping Tee and insert the remote sensing bulb from the L-4031 pool thermostat.
An adjustable by-pass around the heat-exchanger is required. The by­pass is an important and necessary
performance (see piping diagram on page 4). In order to properly adjust the flowrate through the system, please adhere to the following steps: By-Pass Set-Up
a) Use piping and full-size valve
to connect the “In” and “Out” streams
of the pool coil.
b) With the bypass valve wide open take a pressure reading at the gauge on the pool filter.
c) Pressure reading with bypass valve full open is the baseline pressure.
d) Slowly close the bypass valve so that the pressure increases.
e) Stop when pressure reaches 2 to 4 psi above the baseline at the filter.
Alternatively, flowrate may be set by comparing the temperature differ-
ence between the “In” and “Out”
streams of the pool coil.
a) Use full size piping and valve
to connect the “In” and “Out” streams
of the pool coil.
b) Allow the boiler to fire contin­uously for a period of ten (10) to fif­teen (15) minutes.
c) With the bypass valve wide
the coil.
d) Note: surface temperature readings taken on a cold day will vary significantly from test data.
e) Slowly close the bypass valve and continue to take temperature readings.
f) Stop when the temperature
difference between the “In” and “Out”
streams reaches forty-five (45) to fifty (50) degrees Fahrenheit.
g) Flowrate should correspond to six (6) gallons per minute. (See chart page 7).
(3) Flue Connections:
(A) OTF Series (Outdoor Units)
The OTF heaters are provided with an outdoor vent cap to be installed directly on top of the cabinet at the flue outlet. This vent cap provides for a waterproof unit as well as proper con-
(a) General:
Oil fired units must be connected to a flue having sufficient draft at all times to assure proper operation.
(b) Draft:
A draft regulator should be installed in accordance with the man-
ufacturer’s instructions. Set the draft to a negative –.01 to –.02 max. WC
over the fire.
(c) Roof Clearances:
The flue gas exit of the venting system should be at least three (3) feet above the outside point where it passes through the roof and at least
a building within ten (10) feet of the venting system.
(d) Chimney Connections:
The horizontal length of a chim­ney connector should not exceed ten (10) feet unless a draft booster is used. The connector should be
(1/4) inch to the foot. Use only high quality lock seam smoke pipe. Each
sheet metal screws. Chimney con­nections should be positioned to
smoke pipe to the chimney.
(e) Vent Cap:
Install a UL listed vent cap where the possibility of down draft exists.
Section II Filling Instructions
The Thermotron Pool Heater is
in the boiler shell to act as a heat transfer medium to the pool flowing through the separate all copper/bronze heat exchanger coil.
section, MUST be filled with fresh city water. DO NOT FILL WITH CHLO­RINATED OR WATER FROM THE SWIMMING POOL.
3
(1) Do not turn on electrical
garden hose to the hose adapter of
Open the vent at the top of
When water flows out of
pipe systems as soon as the burner
also be caused by too high a “lift” or
the air band to allow just sufficient air
on the air shutter and closing the air
reading of
power to heater until boiler is properly filled with water.
(2) * Connect the male end of a
the heater drain valve.
(3) the boiler section location as shown on page 4.
(4) Turn on water and open drain valve, allow water to flow into boiler section.
(5) boiler vent, close vent and leave heater drain valve open until pressure gauge reads approximately 10 PSI.
(6) Close drain valve and dis­connect hose.
(7) Pool temperature control should be set at desired temperature.
(8) Burner can now be operated as per specified instructions.
*You may choose to install permanent pip­ing...filling instructions would be the same.
IMPORTANT NOTICE Winterizing The Heater:
If the pool heater is installed in an area known to have a freezing climate it is necessary to COMPLETELY drain both the primary boiler and indirect heat exchanger (pool coil).
Connect a hose to the boiler drain at the bottom of the boiler section. Open the vent at the top of the boiler, as well as the drain valve and drain the boiler section completely. Disconnect the unions and the piping at the pool coil heat exchanger. Remove the 1/8" pipe plugs in the bot­tom of the pool coil heat exchanger header (to be completely certain that all water is out of the indirect heat exchanger, it may be advisable to remove the pool coil completely or force an anti-freeze solution into the pool coil.)
Section III Start Up and Operation
A Start Up:
(1) Make sure the electrical
power is turned off.
(2) Check the Oil Burner ignition electrodes carefully and adjust if nec­essary.
(3) Check to be certain oil tank is full.
(4) Be certain unit is filled with water as per filling instructions.
(5) Turn on pool filter pump.
(6) Set limit control at 180°.
(7) Install pressure gauge in the nozzle port of the fuel pump. Do not take reading at the bleed port. The pressure gauge should have a mini­mum range of 100 PSI. Consult Fuel Pump specification sheet (shipped with Oil Burner).
(8) Turn on burner power switch.
(9) Push the safety reset button on the primary control and release.
(10)Bleed the fuel unit on one-
motor starts. To bleed, attach a piece of 1/4" OD clear plastic tubing to the end of the bleed port. Loosen same and purge oil of air for at least 15 sec­onds after oil appears to be clear. If oil stream does not become clear and free of air bubbles or foam, check all fittings, filter and valve connections. Foam can also be caused by kinks in the oil line, causing an oil vacuum condition. High vacuum readings can
too small diameter tubing. Consult Fuel Pump specification sheet.
B Equipment Adjustments:
Equipment Required: (1) CO2Analyzer (absorption type) (2) Draft Gauge (3) Fuel Pressure
Gauge/Vacuum Gauge
(4) Stack Thermometer (5) Smoke Tester (Bacharach
Type)
Allow the burner to operate continu­ously for at least 15 minutes and then make adjustments:
(a) Combustion Samples:
Should be taken through the observation port above the burner, directly over the fire.
(b) Draft:
Take a draft reading over the fire (OTF outdoor equipment will range
from “0” to –.01 negative minimum).
(ITF indoor equipment should be
adjusted to a –.01 draft minimum to a –.02 max.)
(c) Pump Pressure:
Adjust the pump discharge pres­sure to 100 PSI. Vacuum must not exceed 6" on one pipe and 10" on a two-pipe system.
(d) Combustion Settings/CO
2
Reduce the air supply by closing
for clean combustion. This is accom­plished by loosening the lock screws
shutter until a TRACE of smoke is recorded. Take a CO2sample, which should be approximately 12%. Open the air shutter and lower CO2reading approximately by 1-1/2 to 2% from the above reading. A “0” smoke reading should result with a CO
2
approximately 10%.
(e) Stack Temperature: (ITF
only)
Check to see that the stack tem­perature is approximately 500° above the ambient temperature.
(f) Turn LIMIT CONTROL to the lowest setting; burner should shut down. Turn back to the desired set­ting, (normally 180°) burner should operate.
(g) Turn POOL TEMPERATURE CONTROL down to lowest setting;
Loading...
+ 10 hidden pages