Your VOLTMAX Electric Boiler was carefully assembled and checked at the factory to ensure its proper
functioning for many years. The following information and safety measures are provided to enable
proper installation, operation, and maintenance of this product.
It is imperative that all persons who are expected to install, operate or adjust this boiler should read
these instructions carefully.
Any questions regarding the operation, maintenance, service or warranty of this electric boiler should be
directed to the installer or to a skilled technician.
When all installation steps have been completed, keep this installation manual in a safe place (near the
boiler) for future reference.
THERMO 2000 INC.
Printed in Canada Revised: August 2017
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 3.
Capacity
STG
Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s) 240 V
Stage
Relay
Stage
Relay
SCR
Stage
VOLTMAX 23
22,5
76 770
108,4
6 x 5 kW
3 x 7,5 kW
2 x 7,5 kW
1 x 7,5 kW
VOLTMAX 27
27
92 124
130,1
6 x 6 kW
3 x 9 kW
2 x 9 kW
1 x 9 kW
VOLTMAX 30
30
102 360
144,5
8 x 5 kW
4 x 7,5 kW
3 x 7,5 kW
1 x 7,5 kW
VOLTMAX 36
36
122 832
173,4
8 x 6 kW
4 x 9 kW
3 x 9 kW
1 x 9 kW
VOLTMAX 41
41
139 892
198,7
5 x 5 kW + 5 x 6 kW
5 x 8,25 kW
4 x 8,25 kW
1 x 8,25 kW
VOLTMAX 45
45
153 540
216,8
10 x 6 kW
5 x 9 kW
4 x 9 kW
1 x 9 kW
VOLTMAX 50
49,5
168 894
238,4
6 x 5 kW + 6 x 6 kW
6 x 8,25 kW
5 x 8,25 kW
1 x 8,25 kW
VOLTMAX 54
54
184 248
260,1
12 x 6 kW
6 x 9 kW
5 x 9 kW
1 x 9 kW
Capacity
STG
Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s) 240 V
Stage
Relay
Stage
Relay
SCR
Stage
VOLTMAX 30
30
102 360
125
6 x 5 kW
3 x 10 kW
2 x 10 kW
1 x 10 kW
VOLTMAX 36
36
122 832
150
6 x 6 kW
3 x 12 kW
2 x 12 kW
1 x 12 kW
VOLTMAX 40
40
136 480
166,7
8 x 5 kW
4 x 10 kW
3 x 10 kW
1 x 10 kW
VOLTMAX 48
48
163 776
200
8 x 6 kW
4 x 12 kW
3 x 12 kW
1 x 12 kW
VOLTMAX 55
55
187 660
229,2
5 x 5 kW + 5 x 6 kW
5 x 11 kW
4 x 11 kW
1 x 11 kW
VOLTMAX 60
60
204 720
250
10 x 6 kW
5 x 12 kW
4 x 12 kW
1 x 12 kW
VOLTMAX 66
66
225 192
275
6 x 5 kW + 6 x 6 kW
6 x 11 kW
5 x 11 kW
1 x 11 kW
VOLTMAX 72
72
245 664
300
12 x 6 kW
6 x 12 kW
5 x 12 kW
1 x 12 kW
Puissance
STG Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s)
240 V
Stage Relay
Stage
Relay
SCR Stage
VOLTMAX 23
22,5
76 770
62,6
6 x 5 kW
2 x 11,25 kW
1 x 11,25 kW
1 x 11,25 kW
VOLTMAX 27
27
92 124
75,1
6 x 6 kW
2 x 13,5 kW
1 x 13,5 kW
1 x 13,5 kW
VOLTMAX 34
34
116 008
93,9
9 x 5 kW
3 x 11,25 kW
2 x 11,25 kW
1 x 11,25 kW
VOLTMAX 41
40,5
138 186
112,6
9 x 6 kW
3 x 13,5 kW
2 x 13,5 kW
1 x 13,5 kW
VOLTMAX 45
45
153 540
125,1
12 x 5 kW
4 x 11,25 kW
3 x 11,25 kW
1 x 11,25 kW
VOLTMAX 54
54
184 248
150,2
12 x 6 kW
4 x 13,5 kW
3 x 13,5 kW
1 x 13,5 kW
VOLTMAX 56
56
191 072
156,4
15 x 5 kW
5 x 11,25 kW
4 x 11,25 kW
1 x 11,25 kW
VOLTMAX 68
67,5
230 310
187,7
15 x 6 kW
5 x 13,5 kW
4 x 13,5 kW
1 x 13,5 kW
SECTION 1 :TECHNICAL SPECIFICATIONS
Table 1: VOLTMAX 208 VAC / 60 Hz / Single-Phase1
1
Electrical supply 208 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
Table 2: VOLTMAX 240 VAC / 60 Hz / 1 Phase1
1
Electrical supply 240 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
Table 3 : VOLTMAX 208 VAC / 60 Hz / 3 Phase1
1
Electrical supply 208 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 4.
Capacity
STG
Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s) 240 V
Stage
Relay
Model
kW
VOLTMAX 30
30
102 360
72
6 x 5 kW
2 x 15 kW
1 x 15 kW
1 x 15 kW
VOLTMAX 36
36
122 832
86,6
6 x 6 kW
2 x 18 kW
1 x 18 kW
1 x 18 kW
VOLTMAX 45
45
153 540
108,3
9 x 5 kW
3 x 15 kW
2 x 15 kW
1 x 15 kW
VOLTMAX 54
54
184 248
129,9
9 x 6 kW
3 x 18 kW
2 x 18 kW
1 x 18 kW
VOLTMAX 60
60
204 720
144,3
12 x 5 kW
4 x 15 kW
3 x 15 kW
1 x 15 kW
VOLTMAX 72
72
245 664
173,2
12 x 6 kW
4 x 18 kW
3 x 18 kW
1 x 18 kW
VOLTMAX 75
75
255 900
180,4
15 x 5 kW
5 x 15 kW
4 x 15 kW
1 x 15 kW
Capacity
STG Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s)
240 V
Stage Relay
Model
kW
VOLTMAX 30
30
102 360
36,1
6 x 5 kW
2 x 15 kW
1 x 15 kW
1 x 15 kW
VOLTMAX 36
36
122 832
43,3
6 x 6 kW
2 x 18 kW
1 x 18 kW
1 x 18 kW
VOLTMAX 45
45
153 540
54,1
9 x 5 kW
3 x 15 kW
2 x 15 kW
1 x 15 kW
VOLTMAX 54
54
184 248
65
9 x 6 kW
3 x 18 kW
2 x 18 kW
1 x 18 kW
VOLTMAX 60
60
204 720
72,2
12 x 5 kW
4 x 15 kW
3 x 15 kW
1 x 18 kW
VOLTMAX 72
72
245 664
86,6
12 x 6 kW
4 x 18 kW
3 x 18 kW
1 x 18 kW
VOLTMAX 75
75
255 900
90,2
15 x 5 kW
5 x 15 kW
4 x 15 kW
1 x 15 kW
VOLTMAX 90
90
307 80
108,3
15 x 6 kW
5 x 18 kW
4 x 18 kW
1 x 18 kW
VOLTMAX 99
99
337 788
119,1
9 x 5 kW +
9 x 6 kW
3 x 33 kW
2 x 33 kW
1 x 33 kW
VOLTMAX 108
108
368 496
129,9
18 x 6 kW
3 x 36 kW
2 x 36 kW
1 x 36 kW
VOLTMAX 120
120
409 440
144,3
24 x 5 kW
4 x 30 kW
3 x 30 kW
1 x 30 kW
VOLTMAX 132
132
450 384
158,8
12 x 5 kW +
12 x 6 kW
4 x 33 kW
3 x 33 kW
1 x 33 kW
VOLTMAX 144
144
491 328
173,2
24 x 6 kW
4 x 36 kW
3 x 36 kW
1 x 36 kW
VOLTMAX 150
150
511 800
180,4
30 x 5 kW
5 x 30 kW
4 x 30 kW
1 x 30 kW
VOLTMAX 165
165
562 980
198,5
15 x 5 kW +
15 x 6 kW
5 x 33 kW
4 x 33 kW
1 x 33 kW
VOLTMAX 180
180
614 160
216,5
30 x 6 kW
5 x 36 kW
4 x 36 kW
1 x 36 kW
Table 4 : VOLTMAX 240 VAC / 60 Hz / 3 Phases1
1
Electrical supply 240 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
Table 5 : VOLTMAX 480 VAC / 60 Hz / 3 Phases1
1
Electrical supply 480 V - 1 phase (L1-L2-L3) with 3 conductors 90°C with a ground.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 5.
Capacity
STG Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s)
240 V
Stage Relay
Model
kW
VOLTMAX 30
30
102 360
28,9
6 x 5 kW
2 x 15 kW
1 x 15 kW
1 x 15 kW
VOLTMAX 36
36
122 832
34,6
6 x 6 kW
2 x 18 kW
1 x 18 kW
1 x 18 kW
VOLTMAX 45
45
153 540
43,3
9 x 5 kW
3 x 15 kW
2 x 15 kW
1 x 15 kW
VOLTMAX 54
54
184 248
52
9 x 6 kW
3 x 18 kW
2 x 18 kW
1 x 18 kW
VOLTMAX 60
60
204 720
57,7
12 x 5 kW
4 x 15 kW
3 x 15 kW
1 x 18 kW
VOLTMAX 72
72
245 664
69,3
12 x 6 kW
4 x 18 kW
3 x 18 kW
1 x 18 kW
VOLTMAX 75
75
255 900
72,2
15 x 5 kW
5 x 15 kW
4 x 15 kW
1 x 15 kW
VOLTMAX 90
90
307 80
86,6
15 x 6 kW
5 x 18 kW
4 x 18 kW
1 x 18 kW
VOLTMAX 99
99
337 788
95,3
9 x 5 kW +
9 x 6 kW
3 x 33 kW
2 x 33 kW
1 x 33 kW
VOLTMAX 108
108
368 496
103,9
18 x 6 kW
3 x 36 kW
2 x 36 kW
1 x 36 kW
VOLTMAX 120
120
409 440
115,5
24 x 5 kW
4 x 30 kW
3 x 30 kW
1 x 30 kW
VOLTMAX 132
132
450 384
127
12 x 5 kW +
12 x 6 kW
4 x 33 kW
3 x 33 kW
1 x 33 kW
VOLTMAX 144
144
491 328
138,6
24 x 6 kW
4 x 36 kW
3 x 36 kW
1 x 36 kW
VOLTMAX 150
150
511 800
144,3
30 x 5 kW
5 x 30 kW
4 x 30 kW
1 x 30 kW
VOLTMAX 165
165
562 980
158,8
15 x 5 kW +
15 x 6 kW
5 x 33 kW
4 x 33 kW
1 x 33 kW
VOLTMAX 180
180
614 160
173,2
30 x 6 kW
5 x 36 kW
4 x 36 kW
1 x 36 kW
VOLTMAX
90 kW and less
More than 90 kW
Maximum operating pressure
30 PSI
60 PSI
Optional maximum operating pressure
70 PSI*
125 PSI
Table 6 : VOLTMAX 600 VAC / 60 Hz / 3 Phases1
1
Electrical supply 600 V - 1 phase (L1-L2-L3) with 3 conductors 90°C with a ground.
Tableau 7 : Maximal service pressure
* Model from 23 to 90 kW are available at a maximum operating pressure of 125 PSI, but size of the unit will be the
same as model of more than 90 kW.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 6.
BOILER CONNECTIONS
1
Boiler outlet
1 1/2" NPT M
2
Boiler inlet
1 1/2" NPT M
3
Pressure relief valve
3/4" NPT F
4
Drain valve
3/4" NPT F
5*
Access to the return sensor
1/2" NPT F
MIN. CLEARANCES FOR INSTALLATION &
MAINTENANCE
Left and Right sides
3"/ 76mm
Rear
3"/ 76mm
Front
24" / 610mm
Bottom
0" / 0mm
Top
32" / 813mm
GENERAL INFORMATIONS
Weight
310lbs / 141kg
Water Volume
11 Us gal. / 41.6 liters
Max. operating
pressure
STANDARD: 30psi
OPTION: 70 PSI *
COMPONENTS IDENTIFICATION
A
Electrical main supply
B
Boiler controller
C
"On/Off" switch
D**
Disconnect switch & rotary handle
E
Fuses for controls
F***
Solid state SCR relay
G****
Low water cut-off, test button and indicator
lights
H
Electrical control access door
I
Door handle for electric access with lock
J
Electrical control wires access holes
K
Access door power circuit
L
Access cover to Heating elements
M
Heating elements
BOILER DIMENSIONS AND CHARACTERISTIC: MODELS 90KW OR LESS
* Return sensor available with the " SCR SERIES " configuration.
** Optional disconnect switch available on " THREE-PHASE " models.
*** Solid state SCR relay available with the " SCR SERIES " configuration.
**** Low water cut-off is optional.
*Available at 125PSI (See Shop Drawing 99-180KW)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 7.
BOILER CONNECTIONS
1
Boiler outlet
1 1/2" NPT M
2
Boiler inlet
1 1/2" NPT M
3
Pressure relief valve
3/4" NPT F
4
Drain valve
3/4" NPT F
5*
Access to the return sensor
1/2" NPT F
MIN. CLEARANCES FOR INSTALLATION &
MAINTENANCE
Left and Right sides
3"/ 76mm
Rear
3"/ 76mm
Front
24" / 610mm
Bottom
0" / 0mm
Top
32" / 813mm
GENERAL INFORMATIONS
Weight
550lbs / 250kg
Water Volume
30 gal. Us/ 113.5 liters
Max. operating
pressure
STANDARD: 60psi
OPTION: 125 PSI
COMPONENTS IDENTIFICATION
A
Electrical main supply
B
Boiler controller
C
"On/Off" switch
D**
Disconnect switch & rotary handle
E
Fuses for controls
F***
Solid state SCR relay
G****
Low water cut-off, test button and indicator
lights
H
Electrical control access door
I
Door handle for electric access with lock
J
Electrical control wires access holes
K
Access door power circuit
L
Access cover to Heating elements
M
Heating elements
BOILER DIMENSIONS AND CHARACTERISTIC: MODELS 90KW TO 180KW
* Return sensor available with the " SCR Series " configuration.
** Optional disconnect switch
*** Solid state SCR relay available with the " SCR Series " configuration.
**** Low water cut-off is standard for models 120 kW and more.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 8.
List of components shipped with the unit:
• Pressure relief valve
• Drain valve
• Outdoor temperature sensor ¸
(Located inside the control panel of the
unit)
!
AVERTISSEMENT
!
WARNING
!
General Safety Precautions
Be sure to read and understand the entire Installation & operation manual before attempting to install or to operate this water
heater. Pay attention to the following General Safety Precautions. Failure to follow these warnings could cause property damage,
bodily injury or death. Should you have any problems understanding the instructions in this manual, STOP, and get help from a
qualified installer or technician
SECTION 2 : INTRODUCTION
These important safeguards and instruction appearing in this manual are not meant to cover all
possible conditions and situations that may occur. Common sense,
caution and care are factors that cannot be built into every product. These factors must be
supplied by the person(s) caring for and operating the unit.
2.1 LOCAL INSTALLATION
REGULATIONS
This electric boiler must be installed in
accordance with these instructions and in
conformity with local codes, or in the absence of
local codes, with the National Plumbing Code
and the National Electric Code, current edition.
In any case where instructions in this manual
differ from local or national codes, the local or
national codes take precedence.
2.2 CORROSIVE ENVIRONMENT
The electric boiler must not be installed near an
air duct supplying corrosive atmosphere or with
high humidity content. When a boiler defect is
caused by such conditions, the warranty will not
apply.
2.3 INSPECTION UPON RECEPTION
Inspect the electric boiler for possible shipping
damage. The manufacturer’s responsibility
ceases upon delivery of goods to the carrier in
good condition. The Consignee must file any
claims for damage, shortage in shipments, or
non-delivery immediately against the carrier.
2.4 TO BE CHECKED
Please refer to the rating plate on the unit to
ensure that you have the correct model and
voltage in hand.
The electric boiler should not be installed where it may damage the adjacent structures or lower
floors in the event of leakage of the tank or connections. If this cannot be avoided, install a nonflammable tray or bowl under the boiler to collect and drain water from leaks.
NOTE: Any tray or cuvette MUST conform to local codes.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 9.
Sides**
3 inches / 76 mm
Bottom
0 inches / 0 mm
Top*
32 inches / 813 mm
Front
24 inches / 610 mm
Back
3 inches / 76 mm
MISE EN GARDE
!
SECTION 3 : INSTALLATION
The manufacturer’s warranty does not cover any damage or defect caused by installation, or
attachment, or use of any special attachment other than those authorized by the manufacturer
into, onto, or in conjunction with the water heater. The use of such unauthorized devices may
shorten the life of the boiler and may endanger life and property. The manufacturer disclaims any
responsibility for such loss or injury resulting from the use of such unauthorized devices
3.1 SAFETY MEASURES
Any commercial installation will be equipped with
a safety valve that limits the maximum working
pressure to the maximum design pressure of the
tank. The maximum operating pressure of the
VOLTMAX Boiler with a power of 90kW and less
is 30 psi or 70 psi, depending on the options
chosen. The maximum operating pressure of the
VOLTMAX boiler with a power of more than 90kW is 60 psi or 125 psi, depending on the
options selected. See boiler data sheet for
maximum operating pressure.
The boiler is equipped with an automatic high
limit temperature control set at 210°F (99°C) and
a second manual high limit temperature settable.
This electric boiler is designed to operate at a
maximum operating temperature of 200 ° F (93 °
C). The boiler is designed for use in a hot water
heating system only.
The heat transfer fluid must be water or an
antifreeze water / propylene glycol solution or
an antifreeze water / ethylene glycol solution
specially designed for heating systems. The
maximum concentration of solution must be a
maximum of 50%.
3.2 LOCATION
The electric boiler should be installed in a clean,
dry location. Long hot water lines should be
insulated to conserve water and energy. The
electric boiler and water lines should be protected
from exposure to freezing temperature.
The boiler can be mounted vertically or
horizontally directly on a solid surface.
The electric boiler must be located or protected
to avoid risk of physical damage, such as from
moving vehicles, flooding, etc.
The location must have sufficient ventilation to
maintain an ambient temperature not exceeding
80°F (27°C).
To prevent condensation on the boiler walls,
boiler temperature should not be maintained
below the condensation temperature (dewpoint temperature) of the ambient. The
operating temperature of the boiler must not
be lower than the condensation temperature
(dew temperature) relative to the ambient
humidity content.
3.3 CLEARANCES
For adequate inspection and servicing the
following minimum clearance is necessary:
Table 8 : Boiler Clearances
* A minimum clearance of 32 inches. For units
equipped with 18 kW elements (25 in. For 15 kW
elements) is required for possible replacement of
heating elements.
** The left side of the control panel, where the
boiler ON / OFF switch is located, must
remain visible after installation. Otherwise, a
label indicating its location must be affixed to
the control panel indicating its position.
3.4 PIPING INSTALLATION
The location of the inlet and outlet piping shall
conform to the various configurations shown in
Figure 1. You will find typical connection
diagrams to the Figure 3, Figure 4 and Figure 5.
The VOLTMAX boiler is designed to be
operated on a closed circuit piping system.
Therefore, it should not be used to heat open
air tanks
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 10.
Figure 1 : Possible pipe flow configurations
3.4.1 BOILER PIPING CONNECTION
The boiler is equipped with two fittings on each
side of the unit. One of the bottom connections
must be used for the heating return (inlet) and
one of the top connections must be used for
supplying the heating system (outlet).
The outlet and inlet size are 1½ "NPTM threaded
steel pipes, for the VOLTMAX with a power of
90kW and less and 2½ "NPTM threaded steel
pipes for the VOLTMAX with a power of More than 90kW.
Installation of plugs on the inlet and exhaust
ducts is required to facilitate the disconnection
and maintenance of the boiler.
When connecting different types of pipes
(galvanized steel and copper), use dielectric
joints (insulation) to protect the boiler and piping.
Use only new and clean pipes as piping
connection to the boiler. Local codes or
regulations may dictate the exact type of material
to be used.
Insulate all piping containing hot water, especially
in an unheated environment.
Install faucets for easy maintenance.
Install a thermometer on the inlet and outlet
duct(s).
Close the unused openings on the boiler. Do not
block the safety valve, this may cause loss,
damage or injury.
3.4.2 AUXILIARY BOILER PIPING
CONNECTION
When an auxiliary boiler used as back up is
twinned to the VOLTMAX boiler to act as a backup controlled by the VOTLMAX, the auxiliary
boiler shall be installed downstream of the
electric boiler as shown on Figure 5 and 7.
3.4.3 SAFETY VALVE
The installation of a safety valve is an integral
part of the boiler’s installation. The trigger point of
the valve must not exceed the design pressure of
the boiler as indicated on its registration and
identification plate. The valve must comply with
the ASME Boiler and Pressure Vessel Code and
limit the boiler maximum operating pressure. The
safety valve is a security component, not a
control component.
The capacity of the safety valve expressed in
BTU / hour must equal or exceed the rating on
the nameplate of the boiler (s).
A safety valve adjusted to the maximum design
pressure of the boiler has been installed at the
factory. The latter can be replaced by a valve with
a lower trigger pressure, but its BTU / hour
capacity must not be lower than the maximum
boiler power.
Connect the exhaust of the safety valve to a drain
line. The lower end of this conduit shall be at
least 6" (15 cm) from the floor drain away from
any electrical component. The drain line must be
directed downwards from the exhaust of the
safety valve to ensure complete drainage by
gravity. The diameter of the drainpipe must not
be less than that of the exhaust of the valve. The
end of the conduit must not be threaded or
hidden and must be protected from freezing. No
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 11.
valves, valves or valves shall be installed on the
pipe. The installation of the safety valves is
governed by the local code.
3.4.4 SYSTEM PRESSURE CONTROL
AND EXPANSION TANK
Pressure control devices within the system
ensure that each component operates within
minimum and maximum allowable pressures and
maintain minimum pressure for all normal
operating temperatures. They also allow air
bleeding, prevent cavitation at the pump inlet and
prevent water from boiling within the system; all
this is accomplished with minimal addition of new
water.
The increase in boiler water volume resulting
from higher temperature is stored in the
expansion tank during periods of high operating
temperature and is returned to the system when
the temperature decreases.
The expansion tank must be able to store the
required volume of boiler water during maximum
design operating temperature without exceeding
the maximum allowable operating pressure, and
to maintain the required minimum pressure when
the system is cold. Contact your installing
contractor, plumbing supply house, or local
plumbing inspector for assistance. The point
where the expansion tank is connected should be
carefully selected to avoid the possibility that
normal operation of automatic check or manual
valves will isolate the tank from a hot boiler or
any part of the system.
The expansion tank should preferably be located
on the suction or intake side of the pump.
3.4.5 WATER PRESSURE MAKEUP
REGULATOR
Make-up systems must be employed as required
by codes. An automatic fill valve (automatic
pressure regulator) must be used with a backflow
preventer as required, to maintain minimum
system pressure by supplying water to make up
for leakage.
A minimum pressure of 5psi (34kPa) must be
maintained at all times.
A backflow prevention device that complies with
local standards must be installed upstream of the
pressure regulator.
3.4.6 AIR BLEEDER
The air contained in the heated water must be
removed from the system to allow the proper
functioning of the heating system and the boiler.
Installation of manual or automatic air vents is
required to eliminate all air from the boiler and the
heating distribution system.
The main air eliminator must be installed near the
outlet of the boiler on the highest point of the
main supply piping. It is imperative to ensure that
all air possibly located in the boiler be eliminated
at all time.
Regularly purge air from the pipes and beware
that the heated water does not cause injury or
damage.
If the boiler is located at a location higher than
the heat distribution system such as a heated
floor, an automatic air eliminator should be
installed close to the boiler outlet.
3.4.7 CIRCULATING PUMP
The pump capacity required is determined in
relation to the capacity of the boiler installed and
the type of heating distribution system on which it
will be connected.
They are generally designed for an operation at a
differential of temperature (Delta T0) of 10 to 20F
between the supplies and return temperature to
the boiler.
Use the following equation to determine the
required water flow.
Pump flow rate = Boiler power ÷ Delta T ÷ 500
Pump flow rate is expressed in US gallons
per minute or GPM.
The Boiler output (in net BTU per hour) is the
maximum amount of heat to be transferred
through the heating loop to meet the heating
load.
Delta T: The boiler water temperature drop
For example, an electric boiler rated at 180KW
has an output capacity of 614 160 BTU per hour.
The system is designed for a temperature drop of
20°F.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 12.
MODEL
DELTA T0
10oF
20oF
30oF
40oF
VOLTMAX 23
15.7
7.8
5.2
3.9
VOLTMAX 27
18.4
9.2
6.1
4.6
VOLTMAX 30
20.5
10.2
6.8
5.1
VOLTMAX 36
24.6
12.3
8.2
6.1
VOLTMAX 40
27.3
13.6
9.1
6.8
VOLTMAX 41
28.0
14.0
9.3
7.0
VOLTMAX 45
30.7
15.4
10.2
7.7
VOLTMAX 48
32.8
16.4
10.9
8.2
VOLTMAX 50
34.1
17.1
11.4
8.5
VOLTMAX 54
36.8
18.4
12.3
9.2
VOLTMAX 55
37.5
18.8
12.5
9.4
VOLTMAX 60
40.9
20.5
13.6
10.2
VOLTMAX 66
46.4
23.2
15.5
11.6
VOLTMAX 68
45.0
22.5
15.0
11.3
VOLTMAX 72
49.1
24.6
16.4
12.3
VOLTMAX 75
51.2
25.6
17.1
12.8
VOLTMAX 90
61.7
30.8
20.6
15.4
VOLTMAX 99
67.8
33.9
22.6
17.0
VOLTMAX 108
73.7
36.8
24.6
18.4
VOLTMAX 120
82.2
41.1
27.4
16.1
VOLTMAX 132
90.5
45.2
30.2
22.6
VOLTMAX 144
98.7
49.3
32.9
24.7
VOLTMAX 150
102.4
51.2
34.1
25.6
VOLTMAX 165
112.6
56.3
37.5
28.1
VOLTMAX 180
122.8
61.4
40.9
30.7
For example, an 180kW electric boiler has a
power of 614,160 BTU/h. The system is designed
for a drop-in temperature (Delta T) of 20°F.
Flow required = 614,160 20 500 = 61.4 GPM
N.B. To achieve proper operation, a minimum
flow must be present when a heating request is
applied and the heating elements are in
operation. See the table below for the
recommended minimum flow depending on the
boiler output. Installation of a flow switch is not
mandatory
The following table lists the required pump flow
rate in relation to the boiler capacity and Delta T.
Table 9 : Temperature rise vs flow rate
(GPM)
3.4.8 DRAIN FAUCET
A drain valve is installed behind the unit. It allows
the boiler to be emptied, to make possible the
replacement of defective components.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 13.
3.4.9 PRESSURE LOSS
The graph of pressure loss due to flow of water inside the VOLTMAX boiler is shown in the following figure.
Figure 2 : Pressure loss (FTH) as a function of the flow rate of heated water (GPM)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 14.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 15.
Figure 3 : Basic installation
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 16.
Figure 4 : Basic installation with indirect water heater and radiator
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 17.
Figure 5 : Dual-Energy installation with a condensing boiler
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 18.
Figure 6 : Multiple boiler parallel installation
Loading...
+ 41 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.