THERMO 2000 VOLTMAX 36, VOLTMAX 27, VOLTMAX 30, VOLTMAX 41, VOLTMAX 50 Installation And Operation Manual

...
1
VOLTMAX Electric Boiler
It is imperative that all persons who are expected to install, operate or adjust this boiler should read these instructions carefully.
Any questions regarding the operation, maintenance, service or warranty of this electric boiler should be directed to the installer or to a skilled technician.
When all installation steps have been completed, keep this installation manual in a safe place (near the boiler) for future reference.
THERMO 2000 INC. Printed in Canada Revised: August 2017
INSTALLATION AND OPERATION MANUAL
mo
TABLE OF CONTENTS
SECTION 1 : TECHNICAL SPECIFICATIONS ............................................................... 4
SECTION 2 : INTRODUCTION ....................................................................................... 9
2.1 LOCAL INSTALLATION REGULATIONS ............................................................................. 9
2.2 CORROSIVE ENVIRONMENT.............................................................................................. 9
2.3 INSPECTION UPON RECEPTION ....................................................................................... 9
2.4 TO BE CHECKED ................................................................................................................. 9
SECTION 3 : INSTALLATION ...................................................................................... 10
3.1 SAFETY MEASURES .......................................................................................................... 10
3.2 LOCATION........................................................................................................................... 10
3.3 CLEARANCES .................................................................................................................... 10
3.4 PIPING INSTALLATION ...................................................................................................... 10
3.4.1 Boiler piping connection ............................................................................................... 11
3.4.2 Auxiliary boiler piping connection ................................................................................. 11
3.4.3 Safety valve .................................................................................................................. 11
3.4.4 System pressure control and expansion tank .............................................................. 12
3.4.5 Water pressure makeup regulator ................................................................................ 12
3.4.6 Air bleeder .................................................................................................................... 12
3.4.7 Circulating pump .......................................................................................................... 12
3.4.8 Drain faucet .................................................................................................................. 13
3.4.9 Pressure loss ................................................................................................................ 14
3.5 ELECTRICAL CONNECTIONS ........................................................................................... 20
3.5.1 Main electrical supply ................................................................................................... 20
3.5.2 Pump supply ................................................................................................................. 20
3.5.3 Connection of external signals to the controller ........................................................... 20
SECTION 4 : CONTROLLER OPERATION ................................................................. 23
4.1 USER INTERFACE ............................................................................................................. 23
4.1.1 Symbol description ....................................................................................................... 23
4.1.2 Control panel ................................................................................................................ 24
4.1.3 Navigation and adjustements ....................................................................................... 24
4.1.4 Main menu navigation .................................................................................................. 25
4.1.5 Navigation in boiler setting ........................................................................................... 26
4.2 MAIN MENU ........................................................................................................................ 29
4.2.1 Boiler status .................................................................................................................. 29
4.2.2 Boiler configuration ....................................................................................................... 29
4.2.3 User setting .................................................................................................................. 29
4.2.4 Clock setting ................................................................................................................. 30
4.2.5 Consumption ................................................................................................................ 30
4.3 BOILER SETTINGS ............................................................................................................. 30
4.3.1 Heating mode W1 ......................................................................................................... 31
4.3.2 Heating mode W2/DHW ............................................................................................... 31
4.3.3 Pump setting................................................................................................................. 32
4.3.4 Capacity limiting ........................................................................................................... 32
4.3.5 Auxiliary boiler .............................................................................................................. 33
4.3.6 Limit setting .................................................................................................................. 34
4.3.7 Alarm ............................................................................................................................ 34
4.3.8 Communication............................................................................................................. 35
4.3.9 Occupation ................................................................................................................... 36
4.3.10 BOOST Mode ............................................................................................................. 36
4.3.11 Warm weather shutdown ............................................................................................ 37
4.3.12 Change password ...................................................................................................... 37
4.4 INTERNET ........................................................................................................................... 37
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 2.
4.4.1 Website ......................................................................................................................... 37
4.4.2 Email ............................................................................................................................. 37
4.5 BOILER STATUS DISPLAY SETTINGS ............................................................................. 39
4.6 HEATING MODE W1 SETTINGS ....................................................................................... 41
4.6.1 FIXED MODE ............................................................................................................... 41
4.6.2 OUTDOOR RESET MODE .......................................................................................... 42
4.6.3 Mode : DDC 0-10VDC .................................................................................................. 43
4.7 W2 MODE SET-POINT TEMPERATURE SETTINGS ........................................................ 44
4.7.1 W2 MODE .................................................................................................................... 44
4.7.2 DHW MODE ................................................................................................................. 44
4.8 PUMP CONFIGURATION MENU SETTINGS .................................................................... 44
4.8.1 PUMP 1 ........................................................................................................................ 44
4.8.2 PUMP 2 ........................................................................................................................ 44
SPECIFIC PARAMETERS FOR THE CAPACITY LIMITING MENU .................................... 45
4.8.3 MANUAL MODE ........................................................................................................... 45
4.8.4 MODE: 0-10 VDC ......................................................................................................... 45
4.9 POWER LIMITATION MENU SETTINGS ........................................................................... 46
4.9.1 MANUAL MODE ........................................................................................................... 46
4.9.2 0-10 VDC MODE .......................................................................................................... 46
4.9.3 T. ext MODE ................................................................................................................. 47
4.9.4 Schedule MODE ........................................................................................................... 48
4.10 AUXILIARY BOILER SETTINGS ....................................................................................... 49
4.10.1 BACKUP MODE ......................................................................................................... 49
4.10.2 EXTERNAL CONTACT MODE .................................................................................. 50
4.10.3 ManuAl MODE ........................................................................................................... 50
4.10.4 Bi-Energy MODE ........................................................................................................ 50
4.11 LIMIT CONFIGURATION MENU SETTINGS .................................................................... 51
4.12 CONFIG. ALARM MENU SETTINGS ................................................................................ 52
4.13 OCCUPATION MENU SETTINGS .................................................................................... 52
4.14 BOOST MENU SETTINGS................................................................................................ 53
4.15 WARM WEATHER SHUTDOWN MENU SETTINGS ....................................................... 53
SECTION 5 : BOILER START UP ................................................................................ 54
5.1 FILLING THE BOILER ......................................................................................................... 54
5.2 ADJUSTEMENT OF THE CONTROLLER OPERATING PARAMETERS .......................... 54
5.3 STARTUP PROCEDURE .................................................................................................... 54
SECTION 6 : TROUBLESHOOTING ............................................................................ 56
6.1 WARNING LIGHTS ............................................................................................................. 56
6.2 OPERATING PROBLEM IDENTIFICATION ....................................................................... 56
6.2.1 External HL / LWCO ............................................................................................... 56
6.2.2 Sensor ( SE ) .......................................................................................................... 56
6.2.3 Low limit ( LL ) ........................................................................................................ 56
6.2.4 Flow ( F ) ................................................................................................................ 56
6.2.5 Current ( A ) ............................................................................................................ 56
6.2.6 HL temperature ( HL ) ............................................................................................ 57
6.2.7 Low pressure ( P ) .................................................................................................. 57
6.2.8 High pressure ( P ) ................................................................................................. 57
6.2.9 Lock out .................................................................................................................. 57
SECTION 7 : MAINTENANCE ...................................................................................... 58
7.1 BOILER WATER PIPING .................................................................................................... 58
7.2 PRESSURE RELIEF VALVE ............................................................................................... 58
7.3 AIR PURGE ......................................................................................................................... 58
7.4 ELECTRICAL INSPECTION................................................................................................ 58
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 3.
Capacity
STG
Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s) 240 V
Stage Relay
Stage Relay
SCR
Stage
VOLTMAX 23
22,5
76 770
108,4
6 x 5 kW
3 x 7,5 kW
2 x 7,5 kW
1 x 7,5 kW
VOLTMAX 27
27
92 124
130,1
6 x 6 kW
3 x 9 kW
2 x 9 kW
1 x 9 kW
VOLTMAX 30
30
102 360
144,5
8 x 5 kW
4 x 7,5 kW
3 x 7,5 kW
1 x 7,5 kW
VOLTMAX 36
36
122 832
173,4
8 x 6 kW
4 x 9 kW
3 x 9 kW
1 x 9 kW
VOLTMAX 41
41
139 892
198,7
5 x 5 kW + 5 x 6 kW
5 x 8,25 kW
4 x 8,25 kW
1 x 8,25 kW
VOLTMAX 45
45
153 540
216,8
10 x 6 kW
5 x 9 kW
4 x 9 kW
1 x 9 kW
VOLTMAX 50
49,5
168 894
238,4
6 x 5 kW + 6 x 6 kW
6 x 8,25 kW
5 x 8,25 kW
1 x 8,25 kW
VOLTMAX 54
54
184 248
260,1
12 x 6 kW
6 x 9 kW
5 x 9 kW
1 x 9 kW
Capacity
STG
Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s) 240 V
Stage Relay
Stage Relay
SCR
Stage
VOLTMAX 30
30
102 360
125
6 x 5 kW
3 x 10 kW
2 x 10 kW
1 x 10 kW
VOLTMAX 36
36
122 832
150
6 x 6 kW
3 x 12 kW
2 x 12 kW
1 x 12 kW
VOLTMAX 40
40
136 480
166,7
8 x 5 kW
4 x 10 kW
3 x 10 kW
1 x 10 kW
VOLTMAX 48
48
163 776
200
8 x 6 kW
4 x 12 kW
3 x 12 kW
1 x 12 kW
VOLTMAX 55
55
187 660
229,2
5 x 5 kW + 5 x 6 kW
5 x 11 kW
4 x 11 kW
1 x 11 kW
VOLTMAX 60
60
204 720
250
10 x 6 kW
5 x 12 kW
4 x 12 kW
1 x 12 kW
VOLTMAX 66
66
225 192
275
6 x 5 kW + 6 x 6 kW
6 x 11 kW
5 x 11 kW
1 x 11 kW
VOLTMAX 72
72
245 664
300
12 x 6 kW
6 x 12 kW
5 x 12 kW
1 x 12 kW
Puissance
STG Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s)
240 V
Stage Relay
Stage Relay
SCR Stage
VOLTMAX 23
22,5
76 770
62,6
6 x 5 kW
2 x 11,25 kW
1 x 11,25 kW
1 x 11,25 kW
VOLTMAX 27
27
92 124
75,1
6 x 6 kW
2 x 13,5 kW
1 x 13,5 kW
1 x 13,5 kW
VOLTMAX 34
34
116 008
93,9
9 x 5 kW
3 x 11,25 kW
2 x 11,25 kW
1 x 11,25 kW
VOLTMAX 41
40,5
138 186
112,6
9 x 6 kW
3 x 13,5 kW
2 x 13,5 kW
1 x 13,5 kW
VOLTMAX 45
45
153 540
125,1
12 x 5 kW
4 x 11,25 kW
3 x 11,25 kW
1 x 11,25 kW
VOLTMAX 54
54
184 248
150,2
12 x 6 kW
4 x 13,5 kW
3 x 13,5 kW
1 x 13,5 kW
VOLTMAX 56
56
191 072
156,4
15 x 5 kW
5 x 11,25 kW
4 x 11,25 kW
1 x 11,25 kW
VOLTMAX 68
67,5
230 310
187,7
15 x 6 kW
5 x 13,5 kW
4 x 13,5 kW
1 x 13,5 kW
SECTION 1 : TECHNICAL SPECIFICATIONS
Table 1: VOLTMAX 208 VAC / 60 Hz / Single-Phase1
1
Electrical supply 208 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
Table 2: VOLTMAX 240 VAC / 60 Hz / 1 Phase1
1
Electrical supply 240 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
Table 3 : VOLTMAX 208 VAC / 60 Hz / 3 Phase1
1
Electrical supply 208 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 4.
Capacity
STG
Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s) 240 V
Stage Relay
Model
kW
VOLTMAX 30
30
102 360
72
6 x 5 kW
2 x 15 kW
1 x 15 kW
1 x 15 kW
VOLTMAX 36
36
122 832
86,6
6 x 6 kW
2 x 18 kW
1 x 18 kW
1 x 18 kW
VOLTMAX 45
45
153 540
108,3
9 x 5 kW
3 x 15 kW
2 x 15 kW
1 x 15 kW
VOLTMAX 54
54
184 248
129,9
9 x 6 kW
3 x 18 kW
2 x 18 kW
1 x 18 kW
VOLTMAX 60
60
204 720
144,3
12 x 5 kW
4 x 15 kW
3 x 15 kW
1 x 15 kW
VOLTMAX 72
72
245 664
173,2
12 x 6 kW
4 x 18 kW
3 x 18 kW
1 x 18 kW
VOLTMAX 75
75
255 900
180,4
15 x 5 kW
5 x 15 kW
4 x 15 kW
1 x 15 kW
Capacity
STG Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s)
240 V
Stage Relay
Model
kW
VOLTMAX 30
30
102 360
36,1
6 x 5 kW
2 x 15 kW
1 x 15 kW
1 x 15 kW
VOLTMAX 36
36
122 832
43,3
6 x 6 kW
2 x 18 kW
1 x 18 kW
1 x 18 kW
VOLTMAX 45
45
153 540
54,1
9 x 5 kW
3 x 15 kW
2 x 15 kW
1 x 15 kW
VOLTMAX 54
54
184 248
65
9 x 6 kW
3 x 18 kW
2 x 18 kW
1 x 18 kW
VOLTMAX 60
60
204 720
72,2
12 x 5 kW
4 x 15 kW
3 x 15 kW
1 x 18 kW
VOLTMAX 72
72
245 664
86,6
12 x 6 kW
4 x 18 kW
3 x 18 kW
1 x 18 kW
VOLTMAX 75
75
255 900
90,2
15 x 5 kW
5 x 15 kW
4 x 15 kW
1 x 15 kW
VOLTMAX 90
90
307 80
108,3
15 x 6 kW
5 x 18 kW
4 x 18 kW
1 x 18 kW
VOLTMAX 99
99
337 788
119,1
9 x 5 kW + 9 x 6 kW
3 x 33 kW
2 x 33 kW
1 x 33 kW
VOLTMAX 108
108
368 496
129,9
18 x 6 kW
3 x 36 kW
2 x 36 kW
1 x 36 kW
VOLTMAX 120
120
409 440
144,3
24 x 5 kW
4 x 30 kW
3 x 30 kW
1 x 30 kW
VOLTMAX 132
132
450 384
158,8
12 x 5 kW + 12 x 6 kW
4 x 33 kW
3 x 33 kW
1 x 33 kW
VOLTMAX 144
144
491 328
173,2
24 x 6 kW
4 x 36 kW
3 x 36 kW
1 x 36 kW
VOLTMAX 150
150
511 800
180,4
30 x 5 kW
5 x 30 kW
4 x 30 kW
1 x 30 kW
VOLTMAX 165
165
562 980
198,5
15 x 5 kW + 15 x 6 kW
5 x 33 kW
4 x 33 kW
1 x 33 kW
VOLTMAX 180
180
614 160
216,5
30 x 6 kW
5 x 36 kW
4 x 36 kW
1 x 36 kW
Table 4 : VOLTMAX 240 VAC / 60 Hz / 3 Phases1
1
Electrical supply 240 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
Table 5 : VOLTMAX 480 VAC / 60 Hz / 3 Phases1
1
Electrical supply 480 V - 1 phase (L1-L2-L3) with 3 conductors 90°C with a ground.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 5.
Capacity
STG Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s)
240 V
Stage Relay
Model
kW
VOLTMAX 30
30
102 360
28,9
6 x 5 kW
2 x 15 kW
1 x 15 kW
1 x 15 kW
VOLTMAX 36
36
122 832
34,6
6 x 6 kW
2 x 18 kW
1 x 18 kW
1 x 18 kW
VOLTMAX 45
45
153 540
43,3
9 x 5 kW
3 x 15 kW
2 x 15 kW
1 x 15 kW
VOLTMAX 54
54
184 248
52
9 x 6 kW
3 x 18 kW
2 x 18 kW
1 x 18 kW
VOLTMAX 60
60
204 720
57,7
12 x 5 kW
4 x 15 kW
3 x 15 kW
1 x 18 kW
VOLTMAX 72
72
245 664
69,3
12 x 6 kW
4 x 18 kW
3 x 18 kW
1 x 18 kW
VOLTMAX 75
75
255 900
72,2
15 x 5 kW
5 x 15 kW
4 x 15 kW
1 x 15 kW
VOLTMAX 90
90
307 80
86,6
15 x 6 kW
5 x 18 kW
4 x 18 kW
1 x 18 kW
VOLTMAX 99
99
337 788
95,3
9 x 5 kW +
9 x 6 kW
3 x 33 kW
2 x 33 kW
1 x 33 kW
VOLTMAX 108
108
368 496
103,9
18 x 6 kW
3 x 36 kW
2 x 36 kW
1 x 36 kW
VOLTMAX 120
120
409 440
115,5
24 x 5 kW
4 x 30 kW
3 x 30 kW
1 x 30 kW
VOLTMAX 132
132
450 384
127
12 x 5 kW +
12 x 6 kW
4 x 33 kW
3 x 33 kW
1 x 33 kW
VOLTMAX 144
144
491 328
138,6
24 x 6 kW
4 x 36 kW
3 x 36 kW
1 x 36 kW
VOLTMAX 150
150
511 800
144,3
30 x 5 kW
5 x 30 kW
4 x 30 kW
1 x 30 kW
VOLTMAX 165
165
562 980
158,8
15 x 5 kW +
15 x 6 kW
5 x 33 kW
4 x 33 kW
1 x 33 kW
VOLTMAX 180
180
614 160
173,2
30 x 6 kW
5 x 36 kW
4 x 36 kW
1 x 36 kW
VOLTMAX
90 kW and less
More than 90 kW
Maximum operating pressure
30 PSI
60 PSI
Optional maximum operating pressure
70 PSI*
125 PSI
Table 6 : VOLTMAX 600 VAC / 60 Hz / 3 Phases1
1
Electrical supply 600 V - 1 phase (L1-L2-L3) with 3 conductors 90°C with a ground.
Tableau 7 : Maximal service pressure
* Model from 23 to 90 kW are available at a maximum operating pressure of 125 PSI, but size of the unit will be the same as model of more than 90 kW.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 6.
BOILER CONNECTIONS
1
Boiler outlet
1 1/2" NPT M
2
Boiler inlet
1 1/2" NPT M
3
Pressure relief valve
3/4" NPT F
4
Drain valve
3/4" NPT F
5*
Access to the return sensor
1/2" NPT F
MIN. CLEARANCES FOR INSTALLATION &
MAINTENANCE
Left and Right sides
3"/ 76mm
Rear
3"/ 76mm
Front
24" / 610mm
Bottom
0" / 0mm
Top
32" / 813mm
GENERAL INFORMATIONS
Weight
310lbs / 141kg
Water Volume
11 Us gal. / 41.6 liters
Max. operating
pressure
STANDARD: 30psi
OPTION: 70 PSI *
COMPONENTS IDENTIFICATION
A
Electrical main supply
B
Boiler controller
C
"On/Off" switch
D**
Disconnect switch & rotary handle
E
Fuses for controls
F***
Solid state SCR relay
G****
Low water cut-off, test button and indicator lights
H
Electrical control access door
I
Door handle for electric access with lock
J
Electrical control wires access holes
K
Access door power circuit
L
Access cover to Heating elements
M
Heating elements
BOILER DIMENSIONS AND CHARACTERISTIC: MODELS 90KW OR LESS
* Return sensor available with the " SCR SERIES " configuration. ** Optional disconnect switch available on " THREE-PHASE " models. *** Solid state SCR relay available with the " SCR SERIES " configuration. **** Low water cut-off is optional.
*Available at 125PSI (See Shop Drawing 99-180KW)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 7.
BOILER CONNECTIONS
1
Boiler outlet
1 1/2" NPT M
2
Boiler inlet
1 1/2" NPT M
3
Pressure relief valve
3/4" NPT F
4
Drain valve
3/4" NPT F
5*
Access to the return sensor
1/2" NPT F
MIN. CLEARANCES FOR INSTALLATION &
MAINTENANCE
Left and Right sides
3"/ 76mm
Rear
3"/ 76mm
Front
24" / 610mm
Bottom
0" / 0mm
Top
32" / 813mm
GENERAL INFORMATIONS
Weight
550lbs / 250kg
Water Volume
30 gal. Us/ 113.5 liters
Max. operating
pressure
STANDARD: 60psi
OPTION: 125 PSI
COMPONENTS IDENTIFICATION
A
Electrical main supply
B
Boiler controller
C
"On/Off" switch
D**
Disconnect switch & rotary handle
E
Fuses for controls
F***
Solid state SCR relay
G****
Low water cut-off, test button and indicator lights
H
Electrical control access door
I
Door handle for electric access with lock
J
Electrical control wires access holes
K
Access door power circuit
L
Access cover to Heating elements
M
Heating elements
BOILER DIMENSIONS AND CHARACTERISTIC: MODELS 90KW TO 180KW
* Return sensor available with the " SCR Series " configuration. ** Optional disconnect switch *** Solid state SCR relay available with the " SCR Series " configuration. **** Low water cut-off is standard for models 120 kW and more.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 8.
List of components shipped with the unit:
• Pressure relief valve
Drain valve
• Outdoor temperature sensor ¸
(Located inside the control panel of the unit)
!
AVERTISSEMENT
!
WARNING
!
General Safety Precautions
Be sure to read and understand the entire Installation & operation manual before attempting to install or to operate this water heater. Pay attention to the following General Safety Precautions. Failure to follow these warnings could cause property damage, bodily injury or death. Should you have any problems understanding the instructions in this manual, STOP, and get help from a qualified installer or technician
SECTION 2 : INTRODUCTION
These important safeguards and instruction appearing in this manual are not meant to cover all possible conditions and situations that may occur. Common sense, caution and care are factors that cannot be built into every product. These factors must be supplied by the person(s) caring for and operating the unit.
2.1 LOCAL INSTALLATION REGULATIONS
This electric boiler must be installed in accordance with these instructions and in conformity with local codes, or in the absence of local codes, with the National Plumbing Code and the National Electric Code, current edition. In any case where instructions in this manual differ from local or national codes, the local or national codes take precedence.
2.2 CORROSIVE ENVIRONMENT
The electric boiler must not be installed near an air duct supplying corrosive atmosphere or with high humidity content. When a boiler defect is caused by such conditions, the warranty will not apply.
2.3 INSPECTION UPON RECEPTION
Inspect the electric boiler for possible shipping
damage. The manufacturer’s responsibility
ceases upon delivery of goods to the carrier in good condition. The Consignee must file any claims for damage, shortage in shipments, or non-delivery immediately against the carrier.
2.4 TO BE CHECKED
Please refer to the rating plate on the unit to ensure that you have the correct model and voltage in hand.
The electric boiler should not be installed where it may damage the adjacent structures or lower floors in the event of leakage of the tank or connections. If this cannot be avoided, install a non­flammable tray or bowl under the boiler to collect and drain water from leaks.
NOTE: Any tray or cuvette MUST conform to local codes.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 9.
Sides**
3 inches / 76 mm
Bottom
0 inches / 0 mm
Top*
32 inches / 813 mm
Front
24 inches / 610 mm
Back
3 inches / 76 mm
MISE EN GARDE
!
SECTION 3 : INSTALLATION
The manufacturer’s warranty does not cover any damage or defect caused by installation, or
attachment, or use of any special attachment other than those authorized by the manufacturer into, onto, or in conjunction with the water heater. The use of such unauthorized devices may shorten the life of the boiler and may endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized devices
3.1 SAFETY MEASURES
Any commercial installation will be equipped with a safety valve that limits the maximum working pressure to the maximum design pressure of the tank. The maximum operating pressure of the VOLTMAX Boiler with a power of 90kW and less is 30 psi or 70 psi, depending on the options chosen. The maximum operating pressure of the VOLTMAX boiler with a power of more than 90kW is 60 psi or 125 psi, depending on the options selected. See boiler data sheet for maximum operating pressure.
The boiler is equipped with an automatic high limit temperature control set at 210°F (99°C) and a second manual high limit temperature settable.
This electric boiler is designed to operate at a maximum operating temperature of 200 ° F (93 ° C). The boiler is designed for use in a hot water heating system only.
The heat transfer fluid must be water or an antifreeze water / propylene glycol solution or an antifreeze water / ethylene glycol solution specially designed for heating systems. The maximum concentration of solution must be a maximum of 50%.
3.2 LOCATION
The electric boiler should be installed in a clean, dry location. Long hot water lines should be insulated to conserve water and energy. The electric boiler and water lines should be protected from exposure to freezing temperature.
The boiler can be mounted vertically or horizontally directly on a solid surface.
The electric boiler must be located or protected to avoid risk of physical damage, such as from moving vehicles, flooding, etc.
The location must have sufficient ventilation to maintain an ambient temperature not exceeding 80°F (27°C).
To prevent condensation on the boiler walls, boiler temperature should not be maintained below the condensation temperature (dew­point temperature) of the ambient. The operating temperature of the boiler must not be lower than the condensation temperature (dew temperature) relative to the ambient humidity content.
3.3 CLEARANCES
For adequate inspection and servicing the following minimum clearance is necessary:
Table 8 : Boiler Clearances
* A minimum clearance of 32 inches. For units equipped with 18 kW elements (25 in. For 15 kW elements) is required for possible replacement of heating elements.
** The left side of the control panel, where the boiler ON / OFF switch is located, must remain visible after installation. Otherwise, a label indicating its location must be affixed to the control panel indicating its position.
3.4 PIPING INSTALLATION
The location of the inlet and outlet piping shall conform to the various configurations shown in Figure 1. You will find typical connection diagrams to the Figure 3, Figure 4 and Figure 5.
The VOLTMAX boiler is designed to be operated on a closed circuit piping system. Therefore, it should not be used to heat open air tanks
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 10.
Figure 1 : Possible pipe flow configurations
3.4.1 BOILER PIPING CONNECTION
The boiler is equipped with two fittings on each side of the unit. One of the bottom connections must be used for the heating return (inlet) and one of the top connections must be used for supplying the heating system (outlet). The outlet and inlet size are 1½ "NPTM threaded steel pipes, for the VOLTMAX with a power of 90kW and less and 2½ "NPTM threaded steel pipes for the VOLTMAX with a power of More than 90kW.
Installation of plugs on the inlet and exhaust ducts is required to facilitate the disconnection and maintenance of the boiler.
When connecting different types of pipes (galvanized steel and copper), use dielectric joints (insulation) to protect the boiler and piping.
Use only new and clean pipes as piping connection to the boiler. Local codes or regulations may dictate the exact type of material to be used.
Insulate all piping containing hot water, especially in an unheated environment.
Install faucets for easy maintenance. Install a thermometer on the inlet and outlet
duct(s). Close the unused openings on the boiler. Do not
block the safety valve, this may cause loss, damage or injury.
3.4.2 AUXILIARY BOILER PIPING CONNECTION
When an auxiliary boiler used as back up is twinned to the VOLTMAX boiler to act as a back­up controlled by the VOTLMAX, the auxiliary
boiler shall be installed downstream of the electric boiler as shown on Figure 5 and 7.
3.4.3 SAFETY VALVE
The installation of a safety valve is an integral part of the boiler’s installation. The trigger point of the valve must not exceed the design pressure of the boiler as indicated on its registration and identification plate. The valve must comply with the ASME Boiler and Pressure Vessel Code and limit the boiler maximum operating pressure. The safety valve is a security component, not a control component.
The capacity of the safety valve expressed in BTU / hour must equal or exceed the rating on the nameplate of the boiler (s).
A safety valve adjusted to the maximum design pressure of the boiler has been installed at the factory. The latter can be replaced by a valve with a lower trigger pressure, but its BTU / hour capacity must not be lower than the maximum boiler power.
Connect the exhaust of the safety valve to a drain line. The lower end of this conduit shall be at least 6" (15 cm) from the floor drain away from any electrical component. The drain line must be directed downwards from the exhaust of the safety valve to ensure complete drainage by gravity. The diameter of the drainpipe must not be less than that of the exhaust of the valve. The end of the conduit must not be threaded or hidden and must be protected from freezing. No
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 11.
valves, valves or valves shall be installed on the pipe. The installation of the safety valves is governed by the local code.
3.4.4 SYSTEM PRESSURE CONTROL AND EXPANSION TANK
Pressure control devices within the system ensure that each component operates within minimum and maximum allowable pressures and maintain minimum pressure for all normal operating temperatures. They also allow air bleeding, prevent cavitation at the pump inlet and prevent water from boiling within the system; all this is accomplished with minimal addition of new water.
The increase in boiler water volume resulting from higher temperature is stored in the expansion tank during periods of high operating temperature and is returned to the system when the temperature decreases.
The expansion tank must be able to store the required volume of boiler water during maximum design operating temperature without exceeding the maximum allowable operating pressure, and to maintain the required minimum pressure when the system is cold. Contact your installing contractor, plumbing supply house, or local plumbing inspector for assistance. The point where the expansion tank is connected should be carefully selected to avoid the possibility that normal operation of automatic check or manual valves will isolate the tank from a hot boiler or any part of the system.
The expansion tank should preferably be located on the suction or intake side of the pump.
3.4.5 WATER PRESSURE MAKEUP REGULATOR
Make-up systems must be employed as required by codes. An automatic fill valve (automatic pressure regulator) must be used with a backflow preventer as required, to maintain minimum system pressure by supplying water to make up for leakage.
A minimum pressure of 5psi (34kPa) must be maintained at all times.
A backflow prevention device that complies with local standards must be installed upstream of the pressure regulator.
3.4.6 AIR BLEEDER
The air contained in the heated water must be removed from the system to allow the proper functioning of the heating system and the boiler.
Installation of manual or automatic air vents is required to eliminate all air from the boiler and the heating distribution system.
The main air eliminator must be installed near the outlet of the boiler on the highest point of the main supply piping. It is imperative to ensure that all air possibly located in the boiler be eliminated at all time.
Regularly purge air from the pipes and beware that the heated water does not cause injury or damage.
If the boiler is located at a location higher than the heat distribution system such as a heated floor, an automatic air eliminator should be installed close to the boiler outlet.
3.4.7 CIRCULATING PUMP
The pump capacity required is determined in relation to the capacity of the boiler installed and the type of heating distribution system on which it will be connected.
They are generally designed for an operation at a differential of temperature (Delta T0) of 10 to 20F between the supplies and return temperature to the boiler.
Use the following equation to determine the required water flow.
Pump flow rate = Boiler power ÷ Delta T ÷ 500
Pump flow rate is expressed in US gallons
per minute or GPM.
The Boiler output (in net BTU per hour) is the
maximum amount of heat to be transferred through the heating loop to meet the heating load.
Delta T: The boiler water temperature drop For example, an electric boiler rated at 180KW
has an output capacity of 614 160 BTU per hour. The system is designed for a temperature drop of 20°F.
Required pump flow rate = 614,160 20 500 = 61,4 GPM
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 12.
MODEL
DELTA T0
10oF
20oF
30oF
40oF
VOLTMAX 23
15.7
7.8
5.2
3.9
VOLTMAX 27
18.4
9.2
6.1
4.6
VOLTMAX 30
20.5
10.2
6.8
5.1
VOLTMAX 36
24.6
12.3
8.2
6.1
VOLTMAX 40
27.3
13.6
9.1
6.8
VOLTMAX 41
28.0
14.0
9.3
7.0
VOLTMAX 45
30.7
15.4
10.2
7.7
VOLTMAX 48
32.8
16.4
10.9
8.2
VOLTMAX 50
34.1
17.1
11.4
8.5
VOLTMAX 54
36.8
18.4
12.3
9.2
VOLTMAX 55
37.5
18.8
12.5
9.4
VOLTMAX 60
40.9
20.5
13.6
10.2
VOLTMAX 66
46.4
23.2
15.5
11.6
VOLTMAX 68
45.0
22.5
15.0
11.3
VOLTMAX 72
49.1
24.6
16.4
12.3
VOLTMAX 75
51.2
25.6
17.1
12.8
VOLTMAX 90
61.7
30.8
20.6
15.4
VOLTMAX 99
67.8
33.9
22.6
17.0
VOLTMAX 108
73.7
36.8
24.6
18.4
VOLTMAX 120
82.2
41.1
27.4
16.1
VOLTMAX 132
90.5
45.2
30.2
22.6
VOLTMAX 144
98.7
49.3
32.9
24.7
VOLTMAX 150
102.4
51.2
34.1
25.6
VOLTMAX 165
112.6
56.3
37.5
28.1
VOLTMAX 180
122.8
61.4
40.9
30.7
For example, an 180kW electric boiler has a power of 614,160 BTU/h. The system is designed for a drop-in temperature (Delta T) of 20°F.
Flow required = 614,160 20 500 = 61.4 GPM N.B. To achieve proper operation, a minimum
flow must be present when a heating request is applied and the heating elements are in operation. See the table below for the recommended minimum flow depending on the boiler output. Installation of a flow switch is not mandatory
The following table lists the required pump flow rate in relation to the boiler capacity and Delta T.
Table 9 : Temperature rise vs flow rate (GPM)
3.4.8 DRAIN FAUCET
A drain valve is installed behind the unit. It allows the boiler to be emptied, to make possible the replacement of defective components.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 13.
3.4.9 PRESSURE LOSS
The graph of pressure loss due to flow of water inside the VOLTMAX boiler is shown in the following figure.
Figure 2 : Pressure loss (FTH) as a function of the flow rate of heated water (GPM)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 14.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 15.
Figure 3 : Basic installation
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 16.
Figure 4 : Basic installation with indirect water heater and radiator
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 17.
Figure 5 : Dual-Energy installation with a condensing boiler
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 18.
Figure 6 : Multiple boiler parallel installation
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 19.
Figure 7 : Basic installation with auxiliary boiler for production of domestic hot water and heating
3.5 ELECTRICAL CONNECTIONS
Wiring must be conform to the National Electrical Code and to state or local code requirements.
The electric boiler must be electrically grounded in accordance with local codes, or, in the absence of local codes, with the National Electrical Code.
3.5.1 MAIN ELECTRICAL SUPPLY
The power supply must be a 208 or 240-volt circuit (single-phase or three-phase, 60Hz), 480 volts (three-phase, 60 Hz) or 600 volts (three­phase, 60 Hz) protected by an appropriately sized breaker.
Refer to the boiler rating plate to select the breaker capacity and wiring rating
3.5.2 PUMP SUPPLY
The VOLTMAX Electric boiler (SCR models) can control 1 or 2 pumps of the distribution system. According to the VOLTMAX configuration, the contact of the pump will function differently.
During a heat demand on W1 or W2, the contact between Pc and P1 or Pc and P2 will be used to start an external pump relay (maximum of 3 amps.). Depending on the configurations selected in the controller, the pump P2 can have priority over the pump P1.
N.B. The VOLTMAX boiler is not designed to heat without a water circulation in its tank. Therefore, if external pump controls are used, they must be interlocked with the operating authorization on W1or W2 of the controller.
3.5.3 CONNECTION OF EXTERNAL SIGNALS TO THE CONTROLLER
The connection of all external signals is made directly on the boiler controller on terminals located on top of it. See the connection diagram on Figure 8 and Figure 9.
Cables used for the connections shall resist temperature up to 90 °C.
3.5.3.1 Connecting the building heat demand signal
Upon reception of a closed contact connected to terminals 24V+ and W1 or W2, the corresponding circulating pump P1 or P2 will start and the boiler will be allowed to operate.
If external controllers control the heating system pumps, they must provide the operating authorization signal. The boiler must not receive a heat demand without the circulation pumps running.
On heating systems when water circulation is continuous, the heat demand control can be connected to the 24V+ and W1 terminals. The heating elements will then be active and available only when there is a request (dry contact).
If the heating system is designed to keep water warm with continuous circulation, a jumper (jumper) must be installed on the 24V+ and W1 terminals to maintain the boiler in demand. The boiler will then attempt to maintain the water temperature at the set-point.
Operation with an upper fixed set-point W2 can be established by connecting the auxiliary heating demand signal (Dry contact) of a thermostat to the 24V+ and W2 of the terminal block.
In all operating modes of the controller, a heat demand on W1 and W2/DHW (close contact) must be present to DI1 or DI2 to allow the operation of the boiler. The only exception is in domestic hot water mode (DHW) with an indirect water heater where the minimum boiler temperature shall be maintained.
3.5.3.2 Connecting au auxiliary boiler
(Available only on SCR models)
The boiler controller is designed to allow the operation of a second boiler or an auxiliary boiler according to two different mode of operation “Auxiliary Backup” or Dual-Energy”.
To do so, connect the TT terminals of the auxiliary boiler to terminals AUX of the VOLTMAX. The maximum capacity of this contact is 3A/120Vac.
See section 3.4.5 for details.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 20.
3.5.3.3 Connection of an “Unoccupied signal”
of the building.
This function allows dropping the boiler temperature during periods where the building is not used and this without having to lower all the room thermostats of the building. To do so, a signal (dry contact) will have to be connected to terminal OCC. (SCR model only) The contact shall be close during the periods of temperature drop. You can also manage the periods of temperature drop by setting a schedule in the controller.
3.5.3.4 Connection of an indirect domestic
hot water heater
The VOLTMAX electric boiler can be used not only to fill the heating requirements of the building but also to fill its domestic hot water needs using an indirect domestic hot water heater such as our TURBOMAX series. To do so, connect the signal (dry contact) of indirect water heater temperature control to the terminal 24V+ and W2/DHW (SCR model only. This will activate the circulating pump supplying the water heater (if properly installed).
On STG models, the pumps can be controlled by an external pump controller with the same characteristics
3.5.3.5 Connection of a dual-energy signal
(SCR model only)
The VOLTMAX can be operated in a dual-energy mode with an auxiliary boiler.
To do so, connect the normally close contact of the dual energy controller to terminals 24V+ & BI-
E to operate with the electric boiler. See section
4.3.4.5 for more details on the sequence of
operation in dual energy.
3.5.3.6 Connection of an outdoor temperature
sensor
If you wish to modulate the boiler water temperature according to the outdoor temperature (Outdoor Reset, ORST) and also wish to stop the operation of the boiler when the outdoor temp. reaches a selected value, then the outdoor sensor supplied with the unit or a corresponding signal coming from the network system shall be connected with a cable of minimum gauge 20 (max 100pi) to terminals S. Ext. of the controller. This probe does not need to be connected during an operation with a fixed setpoint temperature
unless you want to use the Warm weather Shutdown function.
N.B. Do not install a jumper if the outside sensor is not used.
Outdoor sensor location
o Outside the building at a location that best
represents the heat demand of the building (a wall facing north for most of the buildings and on a south one on buildings with large windows facing south).
o It should not be exposed to external heat
sources (dryer outlet, window openings, non­insulated walls).
o It should not be installed in a location where it
could be covered with snow.
3.5.3.7 Remote controller used to determine the target boiler temperature (SCR model only)
An external controller (such as a central building energy management system) can be used to determine the boiler target temperature required for the building. To do so, the external controller shall give a 0 to 10VDC signal connected to terminals 0-10Vdc G & 0-10Vdc T° of the controller.
3.5.3.8 Limit Capacity 0-10VDC (SCR model only)
An external controller providing a 0-10Vdc signal could be used to manage the capacity (kW) of the boiler. Example: An application where the main electrical service supply of the building is limited or when the electricity rate is billed according to the maximum peak loads of the building. To do so, the external controller shall be connected to terminals 0-10Vdc G & 0-10V cap. The capacity of the boiler could be manually limited by adjusting some of the controller parameters. See
section 4.3.4 for more details.
3.5.3.9 External alarm contact (SCR model only)
An alarm signal (dry contact) is available on the boiler to advise the user of an alarm situation. The capacity of the contact is 3A resistive/1A inductive on terminal AL/AL.
An internal audible alarm inside the controller is available on all models. Just activate it in the settings.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 21.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 22.
Figure 8 : ELECTRICAL CONNECTIONS OF THE INPUT AND OUTPUT SIGNALS TO THE CONTROLLER (SCR MODEL)
Figure 9 : ELECTRICAL CONNECTIONS OF THE INPUT AND OUTPUT SIGNALS TO THE CONTROLLER (STG MODEL)
W1
Heating request 1 : On
W2
Heating request 2 : On
P1
Pump 1 : On
P2
Pump 2 : On
BIE
Boiler in Bi-Energy mode
VOLTMAX Boiler : On
Auxiliary boiler : On
Boost mode : On
Warm Weather Shut Down : On
An alarm is active
The boiler is in lock out mode
HL
High temperature limit condition at the boiler outlet
LL
Low temperature limit conditions (lack of capacity)
P
Alarm due to a pressure problem
A
Alarm due to an electrical problem
F
Alarm due to a flow problem
Se
Alarm due to a sensor problem
T° SET­POINT
Actual set-point temperature
T° BOILER
Water temperature at the outlet of the boiler
CAP (%)
Percentage of power used according to boiler rated power
T° EXT
Outdoor temperature measured using the outdoor sensor
KW ACT
Actual power calculated by the boiler
PRESS.
Pressure inside the boiler
STAGE
Status of active stage
SECTION 4 : CONTROLLER OPERATION
4.1 USER INTERFACE
The control of the boiler is ensured by a controller TM171PFE03 of the company Schneider Electric. The LCD display of the controller provides an interface for configuring and displaying the boiler parameters.
A communication module also allows you to integrate the controller with an intelligent building management system (BACnet protocol). It is also equipped with an Ethernet connection. Allowing the connection to the Internet network of the building allowing to read and modify locally or remotely the boiler setting. It can be configured to send alarm messages via e-mail.
Icons will also display to indicate the boiler’s current operating status. Temperature can be displayed in Celsius or Fahrenheit and text can be set to either English or French.
The controller has a backlight function. It is also equipped with three indicator lights (Green / Yellow / Red). The green light indicates normal operation of the unit; the yellow light indicates that the controller has diagnosed and anomaly which requires verification by a technician. The red light indicates that the unit is currently in a critical state (high temperature alarm) or in lock out mode. More detail is provided in Section 6: Troubleshooting. The controller can also be configured to activate an internal buzzer and activate an external alarm signal (SCR only)
when an alarm condition occurs causing the boiler to fail.
Boiler operating mode
Alarm symbol
Operating state of the boiler
Figure 10 : Illustration of the display
4.1.1 SYMBOL DESCRIPTION
The main display shows most the boiler operation status information. The explanation of the main display is shown below.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 23.
1
2 3 4
4.1.2 CONTROL PANEL
Figure 11 : Control panel
On the left side of the appliance, an on / off switch (# 3) is used to operate the appliance and to reset the boiler.
An indicator light showing the status of the low water level cut off and a test button (# 1) is standard for models 120 kW and above. The control circuit fuses (# 2) are accessible from the left side of the unit.
4.1.3 NAVIGATION AND ADJUSTEMENTS
The navigation within the display is done with the five pushbuttons on the right of the screen.
Navigation between the elements is done with the up and down arrows. Use the right key to change the page in the menus. The return key will bring you to the previous menu. The return key returns you to the main display when it is pressed for 2 seconds or more.
The OK button confirms the selection and allows you to edit a parameter. Only highlighted box can be modified. To modify an option, select the box to modify with the arrow keys and press OK. The black box or one of its values will flash and can be changed. Change the values using the arrows and confirm the change by pressing OK.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 24.
4.1.4 MAIN MENU NAVIGATION
Press one of the 5 buttons on the main display to access the main menu
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 25.
Figure 12 : Main menu navigation
4.1.5 NAVIGATION IN BOILER SETTING
Figure 13 : Navigation in boiler setting menu (1/3)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 26.
You can switch from page by using the left or right arrow (Ex : 1/3 to 2/3 by using the right arrow)
Figure 14 : Navigation in boiler setting menu (2/3)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 27.
Figure 15 : Navigation in boiler setting menu (3/3)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 28.
Menu
Contents
Boiler status
Detailed information on the boiler condition
Boiler setting
Configuration of the boiler operating mode and parameters.
User setting
Configuration of the controller display option
Clock setting
Configuration of the internal clock
Consumption
Power consumption of the boiler
Parameters
Description
Language
Select English or French version
Temperature unit
Select the temperature units, either Celsius (C) or Fahrenheit (F)
Flow unit
Select the flow unit, either US gallons per minute (USgpm) or liters per second (L / sec)
Backlight
Setting the backlight mode:
- Off
- 30 secondes
- Always On
Internal buzzer
Setting of the internal buzzer
4.2 MAIN MENU
The main menu is accessible to the user, no access code is required. The main menu is accessed by pressing one of the 5 pushbuttons. Navigation between menu is done with the arrows (up, down, left and right).
4.2.2 BOILER CONFIGURATION
Configuration of the boiler operating mode
This menu is accessible only to the installer or to an authorized person.
The options in the Boiler setting menu are detailed in Section 4.3.
The Manufacturer access code gives access to advanced operating parameters that are not accessible to the installer and the user.
4.2.3 USER SETTING
Configuration of the controller display option
This menu allows the modification of different display parameters.
4.2.1 BOILER STATUS
Detailed information on the boiler condition
This menu allows the display of data not included in the main display. The boiler status menu display the measurements of temperature, pressure, flow, alarm summary, version of the programme and the status of the heating element.
The set of variables presented in this menu are presented in Section 4.5
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 29.
HEATING
MODE W1
Boiler heating mode W1 configuration according to the type of application
HEATING
MODE
W2/DHW
Boiler heating mode W2 or DHW configuration according to the type of application
PUMP
SETTING
Pump contact configurations
CAPACITY
LIMITING
Capacity limiting mode configuration
AUXILIARY
BOILER
Auxiliary boiler mode configuration (if needed)
4.2.4 CLOCK SETTING
Internal clock configuration
Use this menu to adjust the controller’s internal clock. To set the clock correctly, you must adjust the time, minutes, and date.
This adjustment is necessary in order for these modes to function properly:
- The boiler’s power consumption
- Limiting the boiler’s power capacity according to a schedule
- The boiler’s occupation mode Battery life for the clock is at least 1 year when
the controller is unpowered (at 25°C). N.B. The date and day of the week must be set
correctly to ensure the controller automatically changes to daylight savings time.
4.2.5 CONSUMPTION
Boiler consumption cycle report
N.B. For the STG model, the calculation of
power consumption is based on a theoretical approach, there may be differences between the actual consumption of the boiler and the consumption displayed on the screen.
N.B The consumption values are approximate and should not be used as a comparison with actual consumption data charged by the electricity distributor.
4.3 BOILER SETTINGS
In order to be able to configure the boiler, it is necessary to authenticate yourself with an installer or manufacturer code.
The default "Installer" access code is
1111 and can be changed in the
Change password menu.
This menu allows visualization of the boiler power consumption report. First, you must activate the beginning of the consumption cycle with the Start key. The consumption report can be saved using the Save key. And all saved report is available on the History tab. The beginning of the consumption cycles can be reset using the Reset button.
The controller records up to 30 consumption report.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 30.
LIMIT SETTING
Configuration of the boiler operating limits
ALARM
Configuration of the alarms
COMMUNICATION
Configuration of the boiler communication parameter (Web, Email, Bacnet)
OCCUPATION
Configuration of the occupation parameter mode
MODE BOOST
Enable Boost mode
WARM WEATHER
SHUTD.
Enable warm weather shut-down function
CHANGE
PASSWORD
Changing the Installer password
FIXED
Fixed boiler set-point
DDC 0­10 VDC
Modulation of the boiler set-point using a 0-10VDC signal
OUTD RESET
Modulation of the boiler set-point using the outdoor temperature
STOP
No heating demand on W1
4.3.1 HEATING MODE W1 Selection of the operating mode
In this menu you must select an operating mode for selecting the desired setpoint temperature depending on the application. A heat demand or a demand must be present on W1 and/or W2/DHW so that the boiler can heat up. During a heat demand, the boiler activates (depending on a PID curve) the number of stages required in sequence so that the boiler output temperature is maintained at the approximate set-point temperature.
Here is the list of W1 heating modes:
4.3.1.1 Fixe
This mode is used for an installation where it is desired to have a fixed set-point temperature. If the boiler is thermostat-controlled with a heat demand signal on W1, the boiler uses the
corresponding set-point (T. Set-point W1) as the supply temperature.
4.3.1.2 DDC 0-10 VDC
(Available only on SCR model)
This operating mode allows modulating the boiler set-point temperature according to a 0­10VDC signal applied the terminal 0-10VDC and bornier 0-10Vdc G et 0-10Vdc T, produced by an external controller (Ex: Building Energy Management Controller).
The details of the parameters in this mode are presented in Section 4.6.3.
4.3.1.3 Outdoor reset
This operating mode makes it possible to modulate the boiler output set-point temperature as a function of the outdoor temperature. The outdoor temperature signal comes from the temperature sensor supplied with the boiler, which will be connected to the boiler controller.
The details of the parameters are presented in
Section 4.6.2 .
4.3.1.4 Stop
Select this mode to stop the boiler. The heating elements will not operate on a W1 demand.
4.3.2 HEATING MODE W2/DHW
This mode allows you to configure a second heating demand (W2) or a demand from an indirect domestic water heater (DHW). Select none if none of these functions are used. These modes are presented in detail in Section
4.7.
W2
This mode allows the W2-DHW input to be used to receive a signal (dry contact) from a 2nd stage of heating. When the contact on W2-DHW closes, the set­point temperature changes to the set value (T. Set-point W2), even if there is no demand on W1.
DHW
This mode allows you to configure the demand for an indirect domestic water heater. When the DHW mode is selected, the boiler is kept at a minimum temperature (T. Min Boiler) and when contact W2 closes (Dry contact) the set-point rises to T. DHW Set-point. In addition, the PID curve is more aggressive.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 31.
On W1 Dem.
Contact of pump 1 is activated only when there is a demand on W1.
On W2 Dem.
Contact of pump 2 is activated only when there is a demand in W2.
Priority over P1
When there is a request on W2, contact of pump 2 is activated and contact of pump 1 is deactivated.
Always On
The selected pump is always on (contact is always on).
Stop
The selected pump is always deactivated (contact is always off).
Off Delay
The delay in seconds before the contact of the pump is deactivated.
4.3.3 PUMP SETTING
Configuring pump contact activation (Available only on SCR model)
The system allows the control of up to two pumps. Each of these pumps can be activated using a contact. Each pump can be activated according to different modes.
If the amperage of each of the pumps exceeds
3A, external pump relays must be used.
Pump Configuration Options
N.B. External pump relays can also be used as
an alternative to the boiler pump controller. If this alternative is used, a dry contact of this controller must be connected to W1 or / and W2 to allow the boiler to operate only when there is a flow of water present.
4.3.4 CAPACITY LIMITING
Adjusting the maximum authorized power
This menu allows you to configure the boiler output limit. The selection of the limit mode can be selected in the Capacity limiting menu
o None o Manual o DDC 0-10 VDC o T. Ext o Schedule
Details of each of these options are presented in
Section 4.9 . N.B: It is not recommended to disconnect one of
the power relays inside the VOLTMAX boiler to accomplish this function.
N.B: On the STG models, the maximum power chosen must correspond to the power of the stages of the boiler since there is no power modulation relay on these models.
4.3.4.1 NONE
The boiler is not limited in power, the maximum power it can deliver is equivalent to its maximum rated power.
4.3.4.2 MANUAL
The maximum capacity permitted of the boiler is configured in a fixed mode.
Details of the variables in this mode are presented in Section 4.9.1
4.3.4.3 DCC 0-10 VDC
(Available only on SCR model)
A 0-10 VDC signal from a building management system can be used. The signal is treated as a function in order to limit the maximum power. In order to configure this mode, you must connect the 0-10 VDC signal to the terminal block 0-10Vdc Cap. and 0-10Vdc G.
Details of the variables in this mode are presented in Section 4.9.2
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 32.
None
No auxiliary boiler is present
Backup Aux.
This mode allows the adjustment of a second boiler to play a Backup role
Ext Contact
Select the heating source using electrical contact to the BI-E terminal.
BiE (BI-
Energy)
Select the heating source using electrical contact to the BI-E terminal
with the possibility of support mode of the auxiliary boiler.
Manual
Manually select the system operation mode (Electrical or Auxiliary).
4.3.4.4 T. EXT
The maximum permitted power can be adjusted according to the outside temperature sensor. The outdoor temperature is used in order to limit the maximum authorized power.
Details of the variables in this mode are presented in Section 4.9.3 .
This mode of operation is particularly advantageous in applications where the boiler is connected to an electrical network taking account of demand peaks in order to determine the cost of use (demand meter). Since the boiler will thus be limited to a maximum power which will have to be established as a function of the heating requirements of the building and the outside temperature, it will thus be possible to avoid peaks of power not required to satisfy the heating needs in periods of cold weather.
4.3.4.5 Schedule
The maximum authorized boiler power can be programmed according to a schedule. See section 4.9.4 for an explanation of how to modify a schedule.
4.3.5 AUXILIARY BOILER (Available only on SCR model)
The controller program has been designed to allow the operation of a second boiler or auxiliary boilier.
4.3.5.1 Select setpoint source for Auxiliary Boiler
The source of the set-point temperature control can be configured by selecting STPT source Aux. consequently.
In the Internal mode, the terminal contact Aux closes when there is a request for W1 or W2/DHW and the VOLTMAX output temperature is below the setpoint temperature. In addition, the Aux contact is opened when the output
temperature is higher than the setpoint temperature.
In External mode, the Aux contact closes when there is a request on W1 or W2 / DHW regardless of the boiler output temperature VOLTMAX. The VOLTMAX boiler thus has no set temperature and is only used to activate the auxiliary boiler relay.The various configurations of the Aux boiler mode are the following:
N.B. The auxiliary boiler can only be switched on when a heat demand is present on W1 or / and W2 / DHW.
4.3.5.2 None
This mode must be active when there is no auxiliary boiler on the hydronic heating system.
4.3.5.3 Backup Aux.
The boiler will be activated according to the configuration of the lack of capacity of the VOLTMAX boiler.
In the event of a lack of capacity, the boiler is started to compensate. The lack of capacity is defined by the fact that the boiler output temperature is less than X degrees (Delta T. Start Aux.) relative to the set­point for duration of X min. (Auxiliary Start Delay). The auxiliary boiler will be deactivated when the temperature differential between the water outlet temperature and the set-point temperature is lower than Delta T. Off Aux. The calculation of the delay begins only when the electric boiler reaches its maximum power (or maximum power allowed).
The value of "Delta T." should be a negative value.
Details of the variables in this mode are presented in Section 4.10.1
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 33.
An alarm is active
The boiler is in lock mode
HL
The high limit temperature has been reached
LL
Low limit (Lack of capacity)
P
Pressure problem alarm
A
Electrical problem alarm
F
Flow problem alarm
Se
Sensor problem alarm
4.3.5.4 Contact Ext.
This configuration mode makes it possible to operate the electric boiler or the auxiliary boiler according to a contact. During a close contact at
the BI-E terminals, the electric boiler ( ) is activated. When the contact is open, the
auxiliary boiler ( ) will be on. The auxiliary boiler will not be allowed to operate if the electric boiler lacks capacity. Details of the variables in this mode are presented in Section 0
4.3.5.5 BiE (BI-Energy)
The Bi-Energy mode allows the auxiliary boiler to operate when there is a lack of capacity.
Upon receipt of an electrical signal (contact closed at Bi-E) and a request at the terminal of W1 or W2, the contact at the terminal of AUX
will be opened and thus the electric boiler ( ) is allowed to operate and the auxiliary boiler is deactivated.
When an electrical signal is absent (contact open at Bi-E) and a request is present at the terminals of W1 or W2, the contact will close at the terminal of AUX, in order to operate the
boiler Auxiliary ( ) and not the electric boiler. Details of the variables in this mode are presented in Section 0.
4.3.5.6 Manual
Manual mode is used to manually select the operating mode of the system (Electrical or Auxiliary). Details of the variables in this mode are presented in Section 4.10.3
4.3.6 LIMIT SETTING Configuring the boiler operating limits
Use this menu to adjust the permissible operating boiler limits for various parameters.
This menu’s configuration options are presented in detail in Section 4.11.
4.3.7 ALARM
Alarm Mode Configuration
When an alarm is active, it will be displayed on the main display as a symbol.
Ex: If P and Se are displayed at the same time, this indicates a pressure sensor problem
A summary of active alarms is also available in the Boiler status menu. An alarm report is available under the Alarm log menu. Information about date, time and alarm code is available in this menu. The internal clock must be adjusted beforehand so that the alarm registers correctly. Section 6 - Troubleshooting details alarm codes and settings specific to this menu.
Details about this menu’s operation are available
in Section 4.12
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 34.
Address IP
10.0.0.100
User
administrator
Password
password
IP address
192.168.0.1
User
admin
Password
admin
4.3.8 COMMUNICATION
The boiler controller can be connected via an Ethernet network communication port and using a RS485 (BACnet)l. The boiler web portal can be accessed in a variety of ways. You will be able to modify the parameters remotely on a web portal and to visualize the boiler status.
Direct connection between the controller and a computer.
1. Connect the boiler controller to your local network or directly to your computer in an internet port using an RJ45 network cable. The communication port is located on the back of the controller. Refer to the wiring diagram, if you have any questions.
2. Open the Network and sharing center, then Change adapter setting on a windows operating system. Open the Local area
connection properties, then Internet Protocole Version 4 (TCP/IPv4).
3. Replace the parameters by those show on the following figure.
4. Open a web browser and enter the IP address (available in the Communication
menu / Ethernet) of the controller in the web address bar.
5. Enter your username and password.
Default
Remote connection using a boiler-specific wireless network.
If the boiler cannot be connected to the local network, a wireless router for remote connection can be installed. The configuration may differ depending on the model of the router being used. The methodology is presented with a TP­LINK model TL-WR810N.
1. Plug the router into an electrical outlet.
2. Connect the network cable to the RJ45 socket on the controller and the LAN / WAN jack on the router.
3. Use a computer to connect to the wireless network generated by TL-WR810N. (by default).
4. Open a web browser and your wireless
network’s web configuration page at
http://tplinkwifi.net, or use the router’s default address.
Default
Remote connection using a network connection
1. Enter a compatible IP address and subnet mask compatible with the network you want to connect to. Note: Select a free IP address that is compatible with the network (pay attention to the IP addresses of printers and other modules.)
2. Restart the controller to apply the
changes.
3. Plug the network cable into the controller and into an Ethernet port (wall outlet or directly into the router)
4. Open a web browser and enter the previously selected IP address.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 35.
4.3.8.1 BACnet
The BACnet menu allows you to view the configuration and change the BACnet parameters. In order to configure the VOLTMAX boiler to your BACnet management system, you must activate the function.
You must then enter the correct baud rate. Ex: For a BACnet MS / TP communication protocol with a Metasys system the default baud rate is
38400. You must enter the correct MS / TP address. Ex : For a BACnet MS / TP communication with a Metasys system, the address is 5.
The names of the BACnet variables used by the program are listed in the tables below. Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable.
For more information on the BACnet protocol, please refer to the appropriate documentation.
4.3.9 OCCUPATION
Setting the temperature-lowering period.
Ex: When the contact (switch) is open at the OCC terminal, then the boiler will be in temperature-lowering mode. (Night mode) When the contact (switch) is closed, it will be in normal occupancy mode (Day mode).
Force is used to force the boiler to operate normally (day mode).
A weekly schedule can be programmed under the Schedule setting to modify the occupation hours of the building.
4.3.9.2 SCHEDULE CONFIGURATION
Changing a Schedule
Use this menu to configure the building’s
occupation schedule. The schedule works on a weekly schedule (Monday - Sunday) and allow only 1 lowering Set point periods. The first hour represents the start of the occupancy period and the second hour represents the innocupancy periods.
4.3.9.1 Occupation setting
This function allows the boiler water temperature to be lowered for defined periods without having to lower all the thermostats of the building. This function can be activated and deactivated within the menu Occupation under Occupation mode. This function allows the set-point temperature to be lowered when the boiler is within the hours specified in the Schedule Setting menu. The temperature drop (the value should be negative) in the set-point can be changed in the Occupation Setting menu.
The SCR model allows the connection of a contact (OCC Contact) on the controller allowing the use of an external timer to control the OCCUPATION function. The Contact OCC. option activates the operating mode using an external contact (switch).
Ex: In the case currently displayed between 07:00 and 17:59, the set-point temperature will not be affected. On the other hand, from 18:00 to 06:59, the set temperature will be lowered.
When the building is not occupied for a full day, you must enter this information as follows, so that the stpt stay in the lowering mode.
4.3.10 BOOST MODE
Enable Boost Mode
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 36.
This mode operates with the Fixed Set-point and Outdoor reset mode. This menu allows the Boost mode to be activated, this mode increase the set-point temperature when the heating load of the building exceeds the capacity generated by the current water temperature determined by the boiler. This mode is activated after a period of 30 min if the heat demand is maintained for 30 consecutive minutes on W1. After this period, the set temperature will start to rise until a predetermined maximum temperature is reached depending on the heating mode until the demand is filled. This temperature increase is temporary and has a maximum duration of 120 minutes or when the request is terminated on W1.
N.B. The BOOST mode is particularly interesting for applications such as: o Applications with a programmable thermostat
with automatic lowering of the building temperature.
o Return to normal heat demand after a
prolonged period of sunshine where there have been no long-term demands and, therefore, heating floors will take a long time to provide heat at d Normal water.
4.3.11 WARM WEATHER SHUTDOWN Shuts down the boiler when the outside temperature reaches an established threshold.
This mode stops the boiler’s heating production when the outside temperature is higher than a pre-determined temperature (ex: 68°F).
Note: If the boiler is configured with DHW mode, it will continue to operate normally in order to meet the DHW heating demand.
4.3.12 CHANGE PASSWORD
Changing the password
This menu allows you to change the installer account password
4.4 INTERNET
The settings available on the controller are also available remotely on a web portal. This portal works only when the boiler is properly connected to an internet or Ethernet network. The various setting parameters and the protocol for connecting the boiler to a network are available in the Communication menu and Section
4.3.8.
4.4.1 WEBSITE
In order to access the boiler remotely via the internet, the boiler controller must be correctly connected.
The web portal has 3 main menus, the User, Installer and Manufacturer menu. The structure of the web portal is the same as the controller; please refer to the previous sections, if you have any questions.
Ex: The user can obtain information concerning the boiler status, in the menu Operations /
N.B. The password to acces the installater section of the website is 1111. He is independent of the boiler password.
4.4.2 EMAIL
In order to configure the alarm by e-mail, you must:
1. You must first ensure that you enter the correct information in the controller (depending on your network) under the following options:
a. IP address
You must restart the device for the changes to take place.
2. Access the Boiler Web Portal.
3. Click on the Installer / Communication
b. Default Gateway c. Subnet mask d. Primary DNS e. Secondary DNS
menu.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 37.
4. Enter your e-mail under Recipient. You can
also use your own mail server by entering the necessary data.
5. Then select the types of alarms you want to receive by e-mail.
If you want to send alarms to different e-mail addresses, simply enter a list of e-mails.
Personal Email Server (Type: Gmail)
The M171 controller does not support SSL encryption. Thus, your SMTP Email server must accept an unencrypted connection. Internet service providers usually have a specific server that accepts connections without encryptions. On-line messaging services, such as Hotmail, G-mail, do not accept unencrypted communications. In order to work around the problem, there are relay services such as SMTP2GO: https://www.smtp2go.com, to relay between controller communication and your messaging system. This service is free for up to 1000 emails per month.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 38.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 39.
4.5 BOILER STATUS DISPLAY SETTINGS
Display
Description
BACnet Variable
BACnet Description
T. Set point
The set-point temperature of the boiler. The boiler will activate its elements accordingly in order to modulate its water outlet temperature.
AV_TSet-point
---
T. Out Boiler
The temperature at the outlet of the VOLTMAX boiler.
AV_BoilerTOut
---
T. In Boiler
The temperature at the inlet of the VOLTMAX boiler. This sensor is only available on SCR models.
AV_BoilerTIn
---
T. Outdoor
This variable allows the outdoor temperature to be displayed in real time when the outdoor temperature sensor is correctly connected.
AV_OutdoorT
---
Boiler Pressure
This variable allows the reading of the pressure sensor inside the boiler.
AV_SensorPressureSignal
---
Actual power
The actual power used in kilowatt
AV_ActualPower
---
% max authorized power
The maximum permissible power as a percentage of the nominal power.
AV_CapLimitPrc
---
Consumption
The power consumption of the last cycle. You must first begin a history cycle (MAIN MENU / CONSUMPTION)
---
---
Actual Current (A)
This variable allows the reading of the current sensor inside the boiler.
This sensor is only available on SCR models.
AV_SigCaptCourant
---
Demand W1
When requesting heating on W1, allowing the operation of the heating elements.
BV_HeatingW1
0 = No W1 demand 1 = W1 demand
Demand W2/DHW
When requesting heating on W2 or DHW, allowing the operation of the heating elements.
BV_HeatingW2
0 = No W2 demand 1 = W2 demand
Pump W1
During a closed contact of the terminal block of the pump 1
BV_ContactPump1
0 = Pump 1 open contact 1 = Pump 1 closed contact
Pump W2/DHW
During a closed contact of the terminal block of the pump 2
BV_ContactPump2
0 = Pump 2 open contact 1 = Pump 2 closed contact
Flow
The theoretical flow calculated according to the power used, T. Out Boiler and T. In BoilerT. Available on SCR models only.
AV_WaterFlow
---
SCR Modulation %
Percentages of the SCR relay utilisation. (For SCR model only)
AV_ModSCR
Stage #1
Operation of stage #1 (For STG model only)
BV_RelStage1
0 = Stage 1 not working
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 40.
1 = Operation of stage 1
Stage #2
Operation of stage #2
BV_RelStage2
0 = Stage 2 not working 1 = Operation of stage 2
Stage #3
Operation of stage #3
BV_RelStage3
0 = Stage 3 not working 1 = Operation of stage 3
Stage #4
Operation of stage #4
BV_RelStage4
0 = Stage 4 not working 1 = Operation of stage 4
Stage #5
Operation of stage #5
BV_RelStage5
0 = Stage 5 not working 1 = Operation of stage 5
Stage #6
Operation of stage #6
BV_RelStage6
0 = Stage 6 not working 1 = Operation of stage 6
Alarm HL/LWCO Alarm
Alarm triggered because of a high limit and low water level manual alarm.
BV_StatusAlarmHL/LW
0 = Normal operation 1 = Alarm activated
HL Alarm
Alarm triggered when the boiler’s internal temperature is
higher than the threshold.
BV_AlarmIntHL
0 = Normal operation 1 = Alarm activated
LL Alarm
Alarm triggered by the boiler’s lack of capacity.
BV_AlarmLL
0 = Normal operation 1 = Alarm activated
Low Pressure Alarm
Alarm triggered by a low pressure.
BV_AlarmLowPressure
0 = Normal operation 1 = Alarm activated
High Pressure Alarm
Alarm triggered by a high pressure.
BV_AlarmHighPressure
0 = Normal operation 1 = Alarm activated
Flow Alarm
Alarm triggered by a flow problem.
BV_AlarmLowFlow
0 = Normal operation 1 = Alarm activated
Current Alarm
Alarm triggered by a current problem.
BV_AlarmCurrent
0 = Normal operation 1 = Alarm activated
Sensor Alarm
Alarm triggered by a sensor problem.
BV_AlarmSensor
0 = Normal operation 1 = Alarm activated
Boiler model
The VOLTMAX boiler model.
---
---
Tension
The nominal voltage of the VOLTMAX boiler.
---
---
Firmware version
The controller’s firmware version.
---
---
Program name
The controller’s program name and version.
---
---
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 41.
4.6 HEATING MODE W1 SETTINGS
Display
BACnet variable
Description
Parameters
Default
Operating Mode
WP_HeatingMod eW1
Selects the power limitation mode between Stop, Modulation T. Ext, DCC 0-10VDC and Fixed.
0 = Stop 1 = Outdoor Reset 2 = DCC 0-10VDC 3 = Fixed
Fixed
4.6.1 FIXED MODE
Configure the fixed set-point temperature
Display
BACnet Variable
Description
Selection
Default
W1 Set point
WP_FixedSTPT W1
Selects the fixed set-point temperature when there is demand on W1.
10 to 93 0C 50 to 200 0F
140 0F
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 42.
4.6.2 OUTDOOR RESET MODE Adjust the set-point temperature according to the outside temperature
This mode allows modulating the boiler output set-point temperature as a function of the outdoor temperature. The outdoor temperature value comes from a temperature sensor connected to the boiler controller.
If the outdoor sensor is not connected or if its circuit is open, an alarm signal will be displayed on the display (SE). The boiler temperature set­point will become the set value at STPT Min T. Outdoor.
Figure 16 : Outdoor reset curve
Table 10 : OUTDOOR RESET MODE Settings
Display
BACnet Variable
Description
Parameters
Default
Calculated SPTP
AV_TBoilerSTP TCalculatedOU TRST
Current set-point temperature calculated based on the adjustment curve and the outside temperature
10 to 93 0C 50 to 200 0F
---
STPT at Min Outd T
WP_STPTatMin OutdT
Boiler set-point temperature when the outside temperature reaches the Min Outd T.
10 to 93 0C 50 to 200 0F
140 0F
STPT at Max Outd T
WP_STPTatMa xOutdT
Boiler set-point temperature when the outside temperature reaches the Max Outd T.
10 to 93 0C 50 to 200 0F
80 0F
Outdoor T.
AV_OutdoorT
Displays the outside temperature in real time when the outdoor temperature sensor is properly connected.
-46 to 107 °C
-50 to 250 °F
---
Min Outd T.
WP_MinOutdRs tT
Minimum outside temperature (Set to the area’s coldest average temperature)
-46 to 107 °C
-50 to 250 °F
-10 0F
Max Outd T.
WP_MaxOutdR stT
Maximum outside temperature at which the building will need heating
-46 to 107 °C
-50 to 250 °F
65 0F
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 43.
4.6.3 MODE : DDC 0-10VDC Modulation of the set-point temperature as a function of 0-10 VDC (Available only on SCR model)
This operating mode allows to modulate the set-point temperature of the water outlet of the boiler according to a 0-10VDC signal applied to the terminal block 0-10Vdc T and 0-10Vdc G from an external controller (Ex: An energy management software).
A heat demand (closed contact W1 and / or W2-DHW) must be present so that the boiler can heat up.
Figure 17 : Mode DDC 0-10 VDC
Table 11 : Specific parameters in DDC 0-10 VDC
Display
BACnet variable
Description
Parameters
Default
T. STPT 0-10VDC
AV_TBoilerSTPTCalculatedV
This variable represents the set-point temperature based on the voltage of the building control system.
0
C or 0F
---
STPT at Min Volt
WP_STPTatMinRemote010V
Set-point of the boiler temperature corresponding to the voltage level of Min Voltage.
0
C or 0F
80 0F
STPT at Max Volt
WP_STPTatMaxRemote010V
Set-point of the boiler temperature corresponding to the voltage level of Max Voltage.
0
C or 0F
140 0F
Actual voltage
AV_Remote010VSTPT
Voltage emitted by the external controller in real time
0-10 V
---
Max Voltage
WP_MinRemoteVSTPT
The maximum voltage that the external controller can send
0-10 V
10
Min Voltage
WP_MaxRemoteVSTPT
The minimum voltage that the external controller can send
0-10 V
0
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 44.
4.7 W2 MODE SET-POINT TEMPERATURE SETTINGS
Display
BACnet Variable
Description
Selection
Default
Operating Mode
WP_HeatingMod eW2
Select the boiler’s operating mode during demand on W2 (None, W2 and DHW)
0 = W2 1 = DHW 2 = None
None
4.7.1 W2 MODE
Configures the fixed set-point temperature during demand on W2
Display
BACnet Variable
Description
Selection
Default
W2 Set point
WP_FixedSTPT W2
Selects the fixed set-point temperature during demand on W2.
10 to 93 0C 50 to 200 0F
175 deg F0
4.7.2 DHW MODE
Configures the fixed set-point temperature during demand on DHW mode.
Display
BACnet Variable
Description
Selection
Default
T. Set-point DHW
WP_FixedSTPT W2
Selects the fixed set-point temperature during demand on W2 terminale
10 to 93 0C 50 to 200 0F
175 0F
T. Min Boiler
WP_FixedSTPT W0
Selects the boiler’s minimum temperature. The boiler’s heating elements will activate automatically to keep the
hydronic system at the selected temperature.
10 to 93 0C 50 to 200 0F
150 0F
4.8 PUMP CONFIGURATION MENU SETTINGS
4.8.1 PUMP 1
Display
BACnet Variable
Description
Selection
Default
Pump configuration
WP_Pump1Mode
Selects the pump configuration mode (pump contact switch)
0 = None 1 = Always Active 2 = On demand W1
Always
active
Purge delay
WP_Pump1Delay
Configures the pump purge delay (used in W1 On-Demand mode)
0 to 600 sec
30 sec
4.8.2 PUMP 2
Display
BACnet Variable
Description
Selection
Default
Pump Configuration
WP_Pump2Mode
Selects the pump configuration mode (pump contact switch)
0 = None 1 = Always Active 2 = On demand W1 3 = Priority on P1
Always
Active
Purge delay
WP_Pump2Delay
Configures the pump purge delay (used in W1 On-Demand mode)
0 to 600 sec
30 sec
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 45.
SPECIFIC PARAMETERS FOR THE CAPACITY LIMITING MENU
The boiler authorizes a maximal power use. The configuration of these modes is shown below.
4.8.3 MANUAL MODE
The maximum power is determined manually
Display
BACnet variable
Description
Parameters
Default
Max capacity (kW)
Configure the maximum electrical power the boiler will use.
0 to maximum rated power
---
4.8.4 MODE: 0-10 VDC (Only available on SCR model)
The modulation of the maximum power is carried out using an external control 0-10 VDC.
Display
BACnet variable
Description
Parameters
Default
Max capacity (kW)
The calculated power value as a function of the current and the nominal operating voltage of the boiler
0 to maximum rated power
---
kW at Min Volt
The maximum permissible power of the boiler when the voltage of the external controller is at Min Voltage
0 to maximum rated power
0
kW at Max Volt
The maximum permissible power of the boiler when the voltage of the external controller is at Min Voltage
0 to maximum rated power
---
0-10V Current Signal
Voltage emitted by the external controller in real time
0-10 V
---
Max Voltage
The voltage representing the maximum set-point of the external controller
0-10 V
10
Min Voltage
The voltage representing the minimum set-point of the external controller
0-10 V
0
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 46.
4.9 POWER LIMITATION MENU SETTINGS
You can control the boiler power with different modes. Their configuration is below.
Display
BACnet Variable
Description
Selection
Default
Limitation Mode
WP_CapLimitMo de
Select the power limitation between None, Manual, DCC 0-10VDC,T. Ext and Scheduled.
0 = None 1 = Manual 2 = DCC 0-10VDC 3 = T. Ext 4 = Scheduled
---
4.9.1 MANUAL MODE
The maximum power is set manually.
Display
BACnet Variable
Description
Selection
Default
Current authorized max kW
WP_ManualCapL imit
Configures the maximum electrical power that the boiler will use.
0 to maximum rated power
---
4.9.2 0-10 VDC MODE (Available on SCR models only)
An external 0-10 VDC controller is used to adjust the maximum power.
Display
BACnet Variable
Description
Selection
Default
Current authorized max kW
AV_ActualCapLi mitkW
The value of power calculated based on the current and the boiler’s nominal operating voltage
0 to maximum rated power (kW)
---
Minimum Power Volt (kW)
WP_MinRemote VCapLimit
The boiler’s maximum power when the external controller voltage is at Min Voltage
0 to maximum rated power
0
Maximum Power Volt (kW)
WP_MaxRemote VCapLimit
The boiler’s maximum power when the external controller voltage is at V for max. cap.
0 to maximum rated power
---
Current Signal 0­10V
AV_Remote010V Cap
Voltage emitted by the external controller in real time
0-10 V
---
Min Voltage (VDC)
WP_CapLimitatM inRemote010V
The voltage representing the external controller’s minimum set-point
0-10 V
0
Max Voltage (VDC)
WP_CapLimitatM axRemote010V
The voltage representing the external controller’s maximum set-point
0-10 V
10
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 47.
4.9.3 T. EXT MODE
Maximum power modulation is based on the outside temperature. Power modulation is shown below.
If the external sensor is not connected or there is a problem with the sensor, then the power will be limited according to Cap. At T. Ext. Min.
Figure 18: Adjustment curve according to the T. ext mode
Display
BACnet Variable
Description
Parameters
Default
Max capacity (kW)
AV_ActualCapLi mitkW
The value of power calculated based on the current and the boiler’s nominal operating voltage
0 to maximum rated power
---
Cap. At T. Ext. Min
WP_CapLimitatM inOutdT
Maximum authorized capacity according to T. Ext. Min Ex. Maximum power is 170 kW for T. Ext min
0 to maximum rated power
---
Cap. At T. Ext. Max
WP_CapLimitatM axOutdT
Maximum authorized capacity according to T. Ext. Max Ex. Maximum power is 120 kW for T. Ext min
0 to maximum rated power
---
Actual T. Exterior
AV_OutdoorT
This variable allows you to view the outside temperature in real time when the outside temperature sensor is properly connected.
-46 to 107 °C
-50 to 250 °F
---
T. Ext. Min
WP_MinOutdTCa pLimit
Minimal outside temperature used to adjust the maximum power
-46 to 107 °C
-50 to 250 °F
-10 F
T. Ext. Max
WP_MaxOutdTC apLimit
Maximum outside temperature used to adjust the maximum power
-46 to 107 °C
-50 to 250 °F
65 F
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 48.
4.9.4 SCHEDULE MODE
Power can be modulated according to a fixed schedule. This can be programmed in the Schedule Setting menu.
Display
BACnet variable
Description
Parameters
Default
Max capacity (kW)
AV_ActualCapLi mitkW
Maximum capacity allowed at present time.
0 to maximum rated power
---
Cap In Schedule
WP_CapLimitDay Mode
Power limitation when the boiler internal clock is within the power limitation schedule.
0 to maximum rated power
---
Cap Out Schedule
WP_CapLimitNig htMode
Power limitation when the boiler internal clock is outside the power limitation schedule.
0 to maximum rated power
---
Schedule
---
Configuring the boiler power limitation schedule. In order to operate correctly, you must first adjust the internal boiler clock in the Clock Setting menu.
---
---
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 49.
4.10 AUXILIARY BOILER SETTINGS (Only available on SCR model)
The system allows control of an auxiliary boiler to the system. The different configuration options are shown below.
In order for the boiler to start, two conditions must be met: The water outlet temperature of the Voltmax boiler must be below the start-up
temperature Aux.
(T. Out Boiler < (T Set-point - Delta T. Aux Start)
The water outlet temperature of the Voltmax boiler must be below the start-up temperature Aux. for a period of X minutes (Start Delay Aux), after the Voltmax boiler is at 100% of its authorized power.
In order for the auxiliary boiler to turn off, the water outlet temperature of the Voltmax boiler must be above the Aux.
T Out Boiler > (T. Set-point - Delta T. Aux Stop)
4.10.1 BACKUP MODE
Configures a second boiler as a backup.
Display
BACnet variable
Description
Parameters
Default
STPT Source
WP_STPTSource Aux
Selects the source used to control the set-point temperature. Auxiliary means that the set-point will be determined by the auxiliary boiler. The VOLTMAX boiler therefore has no set-point temperature and is only used to activate the auxiliary boiler relay. Voltmax means that the set-point temperature will be determined by the VOLTMAX boiler.
Auxiliary or
VOLTMAX 0 = Auxilliary 1 = VOLTMAX
VOLTMAX Delta T. Start
Aux.
WP_DeltaTStartA ux
This option adjusts the temperature differential (set-point temperature – Water outlet temperature) used to activate the auxiliary boiler.
0 to 55 0C 0 to 100 0F
20 0F
Delta T. Stop Aux.
WP_DeltaTStopA ux
This option configures the temperature differential (set-point temperature – Water outlet temperature) in the VOLTMAX boiler used to deactivate the auxiliary boiler.
0 to 55 0C 0 to 100 0F
5 0F
Delay Start Aux.
WP_DelayStartA ux
This option adjusts the delay in minutes before activating the auxiliary boiler.
Min
10
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 50.
4.10.2 EXTERNAL CONTACT MODE
This mode selects the hydronic system heating source (VOLTMAX boiler or auxiliary boiler) using the BI-E terminal’s electrical switch.
Display
BACnet
Variable
Description
Settings
Default
STPT Source
WP_STPTSourc eAux
Selects the source used to control the set-point temperature. External means that the set-point will be determined by the auxiliary boiler. The VOLTMAX boiler therefore has no set-point temperature and is used only to activate the auxiliary boiler’s relay. Internal means that the set-point temperature will be determined by the VOLTMAX boiler.
External or
internal
Internal
4.10.3 MANUAL MODE
Manual mode is used to select the system’s operating mode (Electric or auxiliary).
Display
BACnet Variable
Description
Selection
Default
Active Boiler
WP_ActiveBoiler
This option selects which boiler is in operation; either the VOLTMAX boiler (electric) or the auxiliary boilder (auxiliary).
VOLTMAX ou
Auxiliary 0 = VOLTMAX 1 = Auxiliary
VOLTMAX
4.10.4 BI-ENERGY MODE
This mode selects the hydronic system heating source (VOLTMAX boiler or auxiliary boiler) using the BI-E terminal’s electrical switch. The benefit of this mode is that the system can operate the back-up boiler when needed.
Display
BACnet variable
Description
Parameters
Default
STPT Source
WP_STPTSource Aux
Selects the source used to control the set-point temperature. Auxiliary means that the set-point will be determined by the auxiliary boiler. The VOLTMAX boiler has no set-point temperature and is only used to activate the auxiliary boiler relay. Voltmax means that the set-point temperature will be determined by the VOLTMAX boiler.
Auxiliary or
VOLTMAX 0 = Auxiliary 1 = VOLTMAX
VOLTMAX Delta T. Start
Aux.
WP_DeltaTStartA ux
This option adjusts the temperature differential (Set-point temperature – Water outlet temperature) used to activate the auxiliary boiler.
0 to 55 0C 0 to 100 0F
20 0F
Delta T. Stop Aux.
WP_DeltaTStopA ux
This option configures the temperature differential (Set-point temperature – Water outlet temperature) in the VOLTMAX boiler used to deactivate the auxiliary boiler.
0 to 55 0C 0 to 100 0F
5 0F
Delay Start Aux.
WP_DelayStartA ux
This option adjusts the delay in minutes before activating the auxiliary boiler.
Min
10
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 51.
4.11 LIMIT CONFIGURATION MENU SETTINGS
Display
BACnet variable
Description
Settings
Default
Haute Limite T
WP_HighLimitTemp
Adjusts the temperature high limit at which the alarm triggers. If the water temperature leaving the boiler exceeds the alarm’s high limit, it will trigger an HL alarm and the boiler’s heating elements will be deactivated.
0 to 92 °C
0 to 199 °F
180 °F
Delta T. LL
WP_DeltaTLL
Adjusts the temperature differential to activate the LL alarm.
0 to -55 °C
0 to -99 °F
-20 °F
Delay LL (min)
WP_DelayLL
Adjusts the LL alarm trigger delay .
0 to 180 min
60 min
Pressure sensor
WP_ActivatePressureSensor
Activates the boiler’s internal pressure sensor module.
OFF / ON
0 = Off ; 1 = On
ON
Actual pressure
AV_SensorPressureSignal
Reads the boiler’s internal pressure sensor.
---
---
Current sensor
WP_ActivateCurrentSensor
Activates the current sensor module.
This module is available on SCR models only
OFF / ON
0 = Off ; 1 = On
ON
Calculated current
AV_CalculatedCurrentSignal
Used to view the VOLTMAX boiler’s theoretical
electric consumption current.
---
---
Actual current
AV_SensorCurrentSignal
View current as measured by a sensor.
---
---
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 52.
4.12 CONFIG. ALARM MENU SETTINGS
Display
BACnet Variable
Description
Possible Settings
Default
Status: HL/LWCO alarm
BV_StatusExtAlarm
Displays the external alarm status. The external alarm contact is activated only if a high limit or low water level alarm occurs.
0 = Off 1 = On
---
Silence Alarm
WP_SilenceAlarm
Temporarily suspends the alarm .
0 = Off 1 = On
Off
Reset Lockdown
WP_ResetLockDown
Cancels the Lockdown mode without resetting the unit. Resetting the unit is required when it is in LOCK-OUT mode, following repeated alarms over a short period.
0 = Off 1 = On
Off
Internal buzzer
WP_ActivateInternalBuzzer
Activates the controller’s internal buzzer.
0 = Off 1 = On
On
Deactivate LL alarm
WP_DeactivateAlarmLL ()
Deactivates the LL alarm.
0 = Off 1 = On
Off
4.13 OCCUPATION MENU SETTINGS
Display
BACnet Variable
Description
Possible Settings
Default
Occupation Mode
WP_ActivateOccupationMode
Activates the Occupation function.
0 = Off 1 = On
---
Source OCC
WP_SourceOccupation
Selects the source used to determine the building’s occupation schedule.
0 = Schedule 1 = Contact OCC
Lowering T.
WP_LoweringTInnoccupation
Lowers the set-point temperature.
---
Off
Occupation Status
BV_StatusOccupation
Displays the Occupation mode status. Off: Day mode; the set-point temperature is not lowered On: Night mode; the set-point temperature is lowered according to the configuration
0 = Off 1 = On
On
Force Day Mode
WP_ForceOccupationDay
Forces the Day mode. The set-point temperature will not be lowered.
0 = Off ; 1 = On
Off
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 53.
4.14 BOOST MENU SETTINGS
Display
BACnet Variable
Description
Possible Settings
Default
Mode BOOST
WP_ActivateModeBoost
This option enables the BOOST functionality.
0 = Off 1 = On
Off
4.15 WARM WEATHER SHUTDOWN MENU SETTINGS
Display
BACnet Variable
Description
Possible Settings
Default
Warm Weather Shutdown
WP_ActivateWarmWeatherSD
Shuts down the boiler when the outside temperature reaches a specific temperature. This temperature can be set in the Warm Weather Shutdown Temperature box.
OFF / ON
0 = Off ; 1 = On
OFF
T. Ext Shutdown WWSD
WP_WarmWeatherSDTemp
Sets the outside temperature that activates the Warm Weather Shutdown, if it shuts down the boiler.
0 to 55 °C 0 to 99 °F
68 °F
Current Ext. T.
AV_OutdoorT
Shows the outside temperature in real time.
-46 to 107 °C
-50 to 250 °F
---
WARNING
!
SECTION 5 : BOILER START UP
Before operating this boiler, be sure to read and follow these instructions, as well as the warnings printed in this manual. Failure to do so can result in unsafe operation of the boiler resulting in property damage, bodily injury, or death. Should you have any problems reading, following or difficulty in understanding the instructions in this manual, STOP, and get help from a qualified person. Do not turn on the boiler unless it is filled with water. Do not turn on the boiler if the cold-water supply shut-off valve is closed.
After the boiler, has been plumbed and wired, it is now ready to be set for automatic operation
5.1 FILLING THE BOILER
Open the service valves at the outlet of the boiler and the cold-water supply valve (fill or makeup water valve) to boiler.
Open the relief valve on top of the boiler in order to purge the air out of the boiler tank during the fill process
Leave all shutoff valves open. Check system for leaks and repair. Purge air
from all the heating distribution zones. Bleed air from different areas of the heat
distribution system. Check boiler pressure gage reading. The
indicated pressure should be lower than the pressure relief valve design rating.
5.2 ADJUSTEMENT OF THE CONTROLLER OPERATING PARAMETERS
After the system has been manually purged of air, and all components (valves, vents, controllers) have been set properly, the boiler can be started.
Never operate this boiler until this has been done.
Consider safety and energy-savings when adjusting the boiler’s water temperature. It is more energy-efficient to maintain a set-point as low as possible while still meeting heating needs.
Safety and energy conservation are factors to be considered when setting the boiler water
operating temperature. The most energy­efficient operation will result when the temperature setting of the controller is the lowest that satisfies the heating needs.
Make sure that the input of the operating parameters of the controller as well as the adjustable high mechanical limit control of the boiler corresponding to the values required for the application.
Adjusting the high limit is possible in the Limit Setting menu. The High temperature limit should be adjusted from 15 to 20F higher than the maximum operating temperature.
5.3 STARTUP PROCEDURE
Before starting the boiler, make sure that the heating distribution design is made so that the heating elements will come on only when water is circulating in the boiler.
1) Fill the boiler as described in Section 5.1.
2) Set the boiler operating temperature as described in Section 4.
3) Cancel all heating demand from the distribution system.
4) Turn on the boiler power breakers and switch.
5) The main contactors should be activated in sequence and the controller display shall be lighted. The heating elements shall not come on because there is no heat demand applied to the controller and if there is no water circulation in the unit.
6) Apply a heat demand. If the boiler target temperature is higher than the boiler water temperature, the heating elements shall come on in sequence more or less rapidly depending on the differential between the values.
N.B. It is normal that the elements be activated very rapidly during the boiler start-up since this temperature differential is generally high at this moment.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 54.
7) When the boiler capacity has reached 100% as displayed on the controller, measure the amperage and voltage values drawn by the unit. These values shall be close to those shown on the boiler name plate.
8) Slow down the heat demand from the heating system. The boiler temperature shall gradually increase and the boiler capacity shall drop gradually and stabilize when the boiler temperature will reach a temperature near the target temperature.
9) When the heating request is completed, the circulating pump can continue to operate (depending on the operating mode or the purge time) or switch off. The heating elements stop working.
10) Check the operation of the adjustable high­limit mechanical control.
11) Check the operation of the Low Water Cut OFF by pressing its test button during 5 sec.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 55.
Active
warning
light
Boiler status
Green
Normal operation of the boiler
Yellow
One or more alarms are active. These alarms do not prevent the operation of the boiler; the boiler continues to operate in normal mode. Ex. The controller detects a problem with the amperage reading sensor.
Red
A critical alarm is active, accompanied by the buzzer (if active). Ex. A high limit alarm is active
SECTION 6 : TROUBLESHOOTING
The troubleshooting section shows the various error messages that can occur during abnormal operation of the boiler.
It is possible to change the limits of some alarms on the controller in the Limit Setting.
6.1 WARNING LIGHTS
The LEDs above the navigation buttons indicate 3 different boiler states.
6.2 OPERATING PROBLEM IDENTIFICATION
An alarm log is available in the BOILER CONFIG / ALARM / ALARM LOG. Each alarm
is recorded with its alarm code, the time and date. The register can record up to 30 alarms.
6.2.1 EXTERNAL HL / LWCO
When this alarm is present, the indicator light to the left of the boiler lights red. This alarm happens when one of the two external sensors (External fault Low Water Cut Off or External High limit) is triggered.
Look for the cause of this contact opening which normally occurs when there is a lack of water in the boiler according to the low water level sensor (Standard on 120 kW models and higher) or when the high temperature limit control detects a temperature higher than 210°F.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 56.
The external alarm contact will be activated immediately if it has been activated (Ext. Alarm Contact) in the Alarm menu. The heating elements stop working and will start again when the water level returns to normal. If this alarm happens 3 times in 1 hour, the boiler will be set in Lock out mode.
6.2.2 SENSOR ( SE )
The Sensor alarm is activated when the controller detects a problem with a sensor. This alarm usually appears with another alarm, for example the flow rate alarm (F) and the sensor alarm (SE), this help target a flow sensor problem, for example.
See Table 13 for comparison of Resistance measurements against temperature for the outdoor sensor.
6.2.3 LOW LIMIT ( LL )
The LL alarm is activated when the temperature differential between the set-point temperature and the boiler output temperature is higher than
Delta T.LL and this period is higher than the LL delay.
The heating elements remain in operation. The screen will automatically return to its normal state. When the temperature of the boiler approaches the set temperature.
6.2.4 FLOW ( F )
(Available only on SCR model)
The flow alarm is triggered when the theoretical flow calculation is below the manufacturer's authorized flow limit.
6.2.5 CURRENT ( A )
(Available only on SCR model)
The Current alarm is triggered when there is a difference of more than 20% between the measured current (Available only on SCR
Temperature
Resistance
Temperature
Resistance
Temperature
Resistance
Temperature
Resistance
°F
°C Ω °F
°C Ω °F
°C Ω °F
°C
-50
-46
490 813
20
-7
46 218
90
32
7 334
160
71
1 689
-45
-43
405 710
25
-4
39 913
95
35
6 532
165
74
1 538
-40
-40
336 606
30
-1
34 558
100
38
5 828
170
77
1 403
-35
-37
280 279
35 2 29 996
105
41
5 210
175
79
1 281
-30
-34
234 196
40 4 26 099
110
43
4 665
180
82
1 172
-25
-32
196 358
45 7 22 763
115
46
4 184
185
85
1 073
-20
-29
165 180
50
10
19 900
120
49
3 760
190
88
983
-15
-26
139 402
55
13
17 436
125
52
3 383
195
91
903
-10
-23
118 018
60
16
15 311
130
54
3 050
200
93
829
-5
-21
100 221
65
18
13 474
135
57
2 754
205
96
763
0
-18
85 362
70
21
11 883
140
60
2 490
210
99
703
5
-15
72 918
75
24
10 501
145
63
2 255
215
102
648
10
-12
62 465
80
27
9 299
150
66
2 045
220
104
598
15
-9
53 658
85
29
8 250
155
68
1 857
225
107
553
model) and the calculated theoretical current. This may indicate an electrical problem from a wrong connection.
limit (depending on the maximum boiler pressure)
6.2.9 LOCK OUT
6.2.6 HL TEMPERATURE ( HL )
The outlet temperature of the boiler is above the high limit allowed. This alarm triggers the deactivation of the heating elements of the boiler. The boiler is restarted when the temperature drops below the high limit (and the set-point) If the boiler is in this alarm state for more than 25 minutes, the boiler switches to Lock Out mode.
6.2.7 LOW PRESSURE ( P )
The Low Pressure alarm is activated when the pressure inside the boiler is below the allowed limit (default: 5 psi).
6.2.8 HIGH PRESSURE ( P )
The High Pressure alarm is activated when the pressure inside the boiler is above the allowed
Lock out mode is activated after 3 major alarms have been activated within one hour. When the lock mode is activated, the boiler is deactivated and can only be restarted by restarting the boiler (to the left of the control panel) or by using the reset Lock Out function (in the alarm setting menu).
Tableau 12 : Resistance (Ohm) according to the outdoor sensor measuring temperature
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 57.
DANGER
!
WARNING
!
SECTION 7 : MAINTENANCE
Properly maintained, your boiler will provide years of dependable, trouble free service. It is recommended that a regular routine maintenance program be established and followed by the user. Components are subject to eventual failure that requires service. Failure to use the correct procedures or parts in these circumstances may make the unit unsafe or reduce the life of the boiler.
The owner should have the following inspection and maintenance procedures performed:
7.1 BOILER WATER PIPING
YEARLY VISUAL INSPECTION
Check all piping for signs of leakage near joints, unions and shut-off valves. Repair as needed.
7.2 PRESSURE RELIEF VALVE
TWICE A YEAR
Check for possible leak at the outlet of the safety relief valve. If a leak is detected and the pressure at the indicator is less than 28psi, change the safety relief valve with a new one having similar characteristics. If the pressure is higher than 28psi, ask your heating service agency to determine the cause of the high pressure and have it corrected rapidly. Do not plug the outlet of this valve if a dripping condition occurs.
7.3 AIR PURGE
TWICE A YEAR
Check for proper operation of the automatic air purgers and activate manual air vents to eliminate air present.
7.4 ELECTRICAL INSPECTION
ANNUALLY
It is recommended to perform a visual inspection of the boiler electric compartment annually, during the heating season, to ensure it is watertight and that there are no signs of component or wiring overheating. Repair as soon as possible if necessary. Defective components should always be replaced with the Original Manufacturer’s parts.
The inspection should also include a check of the main temperature controls in operation as well as an amperage reading to verify the proper operation of all the heating elements.
The manufacturer's warranty DOES NOT cover a tank breakage caused by improper installation or maintenance. If the boiler safety valve opens periodically, this may be caused by the expansion tank.
Immediately call a qualified technician to inspect and remedy the problem.
NOTE: To prevent premature tank failure, the air trapped inside the tank must be purged periodically.
Before manually operating the relief valve, make certain no one will be sprayed with the hot water released by its opening. The water may be hot enough to create a SCALD hazard. The water released should be directed to a suitable drain to prevent injury or damage.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 58.
THERMO 2OOO INC.
500, 9
ième
Avenue, Richmond (Qc) Canada J0B 2H0
Tel: (819) 826-5613 Fax: (819) 826-6370
www.thermo2000.com
VOLTMAX LIMITED WARRANTY
Warranty Coverage for Commercial Installation
Thermo 2000 Inc. warrants to the original purchaser that the DTHUltra tank installed in a commercial setting for ten (10) years. Commercial setting shall mean use in other than residential setting stated above in the residential setting definition. In the event that a leak should develop and occur within this limited warranty period due to defective material or workmanship, such leak having been verified by an authorized company representative, Thermo 2000 Inc. will repair or replace at our sole option the failed unit with the nearest comparable model at the time of replacement.
The original purchaser is responsible for all costs associated with the removal and reinstallation, shipping and handling to and from Manufacturer. The replacement unit will be warranted for the remaining portion of the original Warranty.
Limited two-year warranty on all VOLTMAX components & parts
All other DTHUltra components & parts are warranted for a period of two (2) years against defects due to defective material or workmanship. The original purchaser is responsible for all costs associated with the removal and reinstallation, shipping and handling to and from Manufacturer. The components, repaired or replaced are warranted for the residual period of the initial warranty on the unit.
Limitations
Thermo 2000 shall not be responsible for any damage, loss, and inconvenience of any nature whatsoever, directly or indirectly, relating to the breakdown or malfunction of the unit. This warranty limits its beneficiary’s rights. Nevertheless, the beneficiary may have other rights, which vary from state to state.
This warranty replaces any other expressed or implicit warranty and constitutes the sole obligation of Thermo 2000 towards the consumer. The warranty does not cover cost of removal, reinstallation or shipping to repair or replace the unit, nor administration fees incurred by the original consumer purchaser.
Thermo 2000 reserves its rights to make changes in the details of design, construction, or material, as shall in its judgment constitute an improvement of former practices.
This warranty is valid only for installations made within the territorial limits of Canada and the United States.
Warranty service procedure
Only authorized VOLTMAX retailers may handle warranty claims. The owner or contractor must provide the defective equipment to Thermo 2000 with the following details: the model, the serial number, a copy of the original invoice and the owner identification certificate.
Exclusions
This warranty is void and shall not apply if:
A) Defects or malfunctions resulting from installation, repair,
maintenance and/or usage that are not done in conformity with the manufacturer’s installation manual; or
B) Defects or malfunctions resulting from installation, maintenance, or
repair that are not done in accordance with regulations in force; or
C) Defects or malfunctions resulting from improper installation,
maintenance or repair done carelessly or resulting from consumer damage (improper maintenance, misuse, abuse, accident or alteration); or
D) Installation in which a relief valve (pressure) is not installed or if it is
not functioning properly, or when it is not connected to a drain to avoid damage to the property; or
E) Installation in which liquid circulating in the tank does not remain in
closed circuit or installation in which piping is leaking; or
F) A polybutylene pipe or radiant panel installation without an oxygen
absorption barrier is used; or
G) Installation where the acidity of water is not within the normal
Environmental Protection Agency (EPA) (between pH 6.5 – 8.5) guidelines or the water contains abnormal levels of particulate matter or water exceeding 10.5 gpg; or
H) Your home contains any type of water softener system and the unit
is not installed and maintained in accordance with the manufacturer specifications; or
I) The DTH Ultra unit is being subject to non-authorized modifications;
or
J) Defects or malfunction resulting of storing or handling done
elsewhere than Thermo 2000’s manufacturing plant; or
K) Units on which the serial number is removed or obliterated.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised August 2017), Page 59.
Loading...