THERMO 2000 VoltMax80, VoltMax96, VoltMax84, VoltMax77, VoltMax105 Installation And Operation Manual

...
1
VoltMax 400
Electric Boiler
INSTALLATION AND OPERATION MANUAL
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 2.
TABLE OF CONTENTS
TECHNICAL SPECIFICATIONS .............................................................................................. 4
INTRODUCTION ....................................................................................................................... 8
LOCAL INSTALLATION REGULATIONS ............................................................................................. 8
CORROSIVE ENVIRONMENT ............................................................................................................ 8
INSPECTION UPON RECEPTION ...................................................................................................... 8
TO BE CHECKED ................................................................................................................................ 8
INSTALLATION ........................................................................................................................ 9
SAFETY MEASURES .......................................................................................................................... 9
LOCATION ........................................................................................................................................... 9
CLEARANCES ..................................................................................................................................... 9
PIPING INSTALLATION ....................................................................................................................... 9
Boiler piping connection ...................................................................................................... 10
Auxiliary boiler piping connection ........................................................................................ 10
Safety valve ........................................................................................................................ 10
System pressure control and expansion tank ..................................................................... 11
Water pressure makeup regulator ....................................................................................... 11
Air bleeder .......................................................................................................................... 11
Circulating pump ................................................................................................................. 11
Drain faucet......................................................................................................................... 12
Sieve ................................................................................................ ................................... 12
Pressure loss ...................................................................................................................... 13
ELECTRICAL CONNECTIONS .......................................................................................................... 19
Main electrical supply .......................................................................................................... 19
Pump supply ................................ ....................................................................................... 19
Connection of external signals to the controller .................................................................. 19
CONTROLLER OPERATION ................................................................................................. 23
USER INTERFACE ............................................................................................................................ 23
Symbol description .............................................................................................................. 23
Control panel....................................................................................................................... 24
Navigation and adjustements .............................................................................................. 24
Main menu navigation ................................................................ ................................ ......... 25
Navigation in boiler setting .................................................................................................. 26
MAIN MENU ....................................................................................................................................... 29
Boiler status ........................................................................................................................ 29
Boiler configuration ............................................................................................................. 29
User setting ......................................................................................................................... 29
Clock setting ....................................................................................................................... 30
Consumption ....................................................................................................................... 30
BOILER SETTINGS ........................................................................................................................... 30
Heating mode W1 ............................................................................................................... 31
Heating mode W2/DHW ...................................................................................................... 32
Capacity limiting .................................................................................................................. 32
Auxiliary boiler..................................................................................................................... 33
Limit setting ......................................................................................................................... 34
Alarm .................................................................................................................................. 34
Communication ................................................................................................................... 34
Config. BACnet ................................................................................................................... 35
Occupation .......................................................................................................................... 36
BOOST Mode ..................................................................................................................... 37
Warm weather shutdown .................................................................................................... 37
Change password ............................................................................................................... 37
ETHERNET ........................................................................................................................................ 37
Web PORTAL ..................................................................................................................... 37
Alarm notification Email ...................................................................................................... 37
BOILER STATUS DISPLAY SETTINGS ............................................................................................ 39
HEATING MODE W1 SETTINGS ...................................................................................................... 41
FIXED MODE...................................................................................................................... 41
OUTDOOR RESET MODE ................................................................................................. 42
MODE: DDC 0-10VDC ........................................................................................................ 43
W2 MODE SET-POINT TEMPERATURE SETTINGS ....................................................................... 44
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 3.
W2 MODE ........................................................................................................................... 44
DHW MODE........................................................................................................................ 44
POWER LIMITATION MENU SETTINGS .......................................................................................... 44
MANUAL MODE ................................................................................................................. 45
0-10 VDC MODE ................................................................................................................ 45
T. ext MODE ....................................................................................................................... 46
Schedule MODE ................................................................................................................. 47
AUXILIARY BOILER SETTINGS ........................................................................................................ 47
BACKUP MODE ................................................................................................................. 48
EXTERNAL CONTACT MODE ........................................................................................... 48
ManuAl MODE .................................................................................................................... 48
Bi-Energy MODE ................................................................................................................ 49
LIMIT CONFIGURATION MENU SETTINGS ................................................................................... 50
CONFIG. ALARM MENU SETTINGS ............................................................................................... 51
OCCUPATION MENU SETTINGS ................................................................................................... 51
BOOST MENU SETTINGS .............................................................................................................. 52
WARM WEATHER SHUTDOWN MENU SETTINGS ....................................................................... 52
BOILER START UP ................................................................................................................ 53
STARTUP PREPARATION ................................................................................................................ 53
ADJUSTEMENT OF THE CONTROLLER OPERATING PARAMETERS .......................................... 53
STARTUP PROCEDURE ................................................................................................................... 54
TROUBLESHOOTING ............................................................................................................ 55
WARNING LIGHTS ............................................................................................................................ 55
OPERATING PROBLEM IDENTIFICATION ...................................................................................... 55
External HL / LWCO ........................................................................................................... 55
Sensor (SE) ........................................................................................................................ 55
Low limit (LL)....................................................................................................................... 55
Flow (F) ............................................................................................................................... 56
Current (A) .......................................................................................................................... 56
HL temperature (HL) ........................................................................................................... 56
Low pressure (P) ................................................................................................................. 56
High pressure (P) ................................................................................................................ 56
Battery low level ................................................................................................................. 56
Lock out ............................................................................................................................. 56
FUSES ............................................................................................................................................... 58
CONTACTOR ..................................................................................................................................... 58
HEATING ELEMENTS ....................................................................................................................... 58
TEMPERATURE SENSOR ................................................................................................................ 58
EXTERNAL HIGH LIMIT CONTROL .................................................................................................. 58
INTERNAL CLOCK ............................................................................................................................ 58
MAINTENANce....................................................................................................................... 59
BOILER WATER PIPING ................................................................ ................................................... 59
PRESSURE RELIEF VALVE .............................................................................................................. 59
AIR PURGE ........................................................................................................................................ 59
ELECTRICAL INSPECTION .............................................................................................................. 59
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 4.
TECHNICAL SPECIFICATIONS
Table 1 : VoltMax 600 VAC / 60 Hz / 3 Phases
1
Model
BTU/h
kW
Amps
Elements 600V
Stage
2
max. power
supply
(MCM)3
VoltMax 192
655 104
192
185
8 x 15 kW 4 x 18 kW
4 x 48 kW
3 x 350
VoltMax 204
696 048
204
197
8 x 18 kW 4 x 15 kW
4 x 51 kW
3 x 350
VoltMax 216
736 996
216
208
12 x 18 kW
4 x 54 kW
3 x 350
VoltMax 225
767 700
225
217
15 x 15 kW
5 x 45 kW
3 x 350
VoltMax 240
818 880
240
231
10 x 15 kW
5 x 18 kW
5 x 48 kW
3 x 350
VoltMax 255
870 060
255
246
10 x 18 kW
5 x 15 kW
5 x 51 kW
3 x 350
VoltMax 270
921 240
270
260
15 x 18 kW
5 x 54 kW
3 x 500
VoltMax 288
982 656
288
277
12 x 15 kW
6 x 18 kW
6 x 48 kW
3 x 500
VoltMax 306
1 044 072
306
295
12 x 18 kW
6 x 15 kW
6 x 51 kW
3 x 500
VoltMax 315
1 074 780
315
303
21 x 15 kW
7 x 45 kW
3 x 500
VoltMax 324
1 105 488
324
312
18 x 18 kW
6 x 54 kW
3 x 500
VoltMax 336
1 146 432
336
324
14 x 15 kW
7 x 18 kW
7 x 48 kW
3 x 600
VoltMax 357
1 218 084
357
344
14 x 18 kW
7 x 15 kW
7 x 51 kW
3 x 600
VoltMax 378
1 289 736
378
364
21 x 18 kW
7 x 54 kW
6 x 300
VoltMax 384
1 310 208
384
370
16 x 15 kW
8 x 18 kW
8 x 48 kW
6 x 300
VoltMax 408
1 392 096
408
393
16 x 18 kW
8 x 15 kW
8 x 51 kW
6 x 300
1
Electrical supply 600 V 3 phase (L1-L2-L3) with 3 conductors Cu or AL ,90 °C with a ground.
2
The 45 kW stage is composed of three 15 kW elements. The 48 kW stage is composed of two 15 kW elements and one 18 kW element. The 51 kW stage is composed of one 15 kW element and two 18 kW elements. The 54 kW stage is composed of three 18 kW elements.
3
-Maximum capacity of the boilers connection terminals
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 5.
Table 2 : VoltMax 480 VAC / 60 Hz / 3 Phases
1
Model
BTU/h
kW
Amps
Elements 480V
Stage
2
max. power
supply
(MCM)3
VoltMax 192
655 104
192
231
8 x 15 kW 4 x 18 kW
4 x 48 kW
3 x 350
VoltMax 204
696 048
204
246
8 x 18 kW 4 x 15 kW
4 x 51 kW
3 x 500
VoltMax 225
767 700
225
271
15 x 15 kW
5 x 45 kW
3 x 500
VoltMax 240
818 880
240
289
10 x 15 kW
5 x 18 kW
5 x 48 kW
3 x 500
VoltMax 255
870 060
255
307
10 x 18 kW
5 x 15 kW
5 x 51 kW
3 x 500
VoltMax 288
982 656
288
347
12 x 15 kW
6 x 18 kW
6 x 48 kW
3 x600
VoltMax 306
1 044 072
306
368
12 x 18 kW
6 x 15 kW
6 x 51 kW
3 x600
VoltMax 315
1 074 780
315
379
21 x 15 kW
7 x 45 kW
6 x 300
VoltMax 336
1 146 432
336
405
14 x 15 kW
7 x 18 kW
7 x 48 kW
6 x 300
VoltMax 357
1 218 084
357
430
14 x 18 kW
7 x 15 kW
7 x 51 kW
6 x 300
VoltMax 384
1 310 208
384
462
16 x 15 kW
8 x 18 kW
8 x 48 kW
6 x 300
VoltMax 408
1 392 096
408
491
16 x 18 kW
8 x 15 kW
8 x 51 kW
6 x 500
1
Electrical supply 480 V 3 phase (L1-L2-L3) with 3 conductors Cu or AL ,90 °C with a ground.
2
The 45 kW stage is composed of three 15 kW elements. The 48 kW stage is composed of two 15 kW elements and one 18 kW element. The 51 kW stage is composed of one 15 kW element and two 18 kW elements.
3
-Maximum capacity of the boilers connection terminals
Table 3 : VoltMax 240 VAC / 60 Hz / 3 Phases
1
Model
BTU/h
kW
Amps
Elements 240V
Stage
max. power
supply
(MCM)2
VoltMax 105
358 260
105
253
7 x 15 kW
7 x 15 kW
3 x 500
VoltMax 120
409 440
120
289
8 x 15 kW
8 x 15 kW
3 x 500
VoltMax 126
429 912
126
303
7 X 18 kW
7 X 18 kW
3 x 500
VoltMax 144
491 328
144
347
8 x 18 kW
8 x 18 kW
3 x 500
1
Electrical supply 240 V 3 phase (L1-L2-L3) with 3 conductors Cu or AL ,90 °C with a ground.
2
-Maximum capacity of the boilers connection terminals
Table 4 : VoltMax 208 VAC / 60 Hz / 3 Phases
1
Model
BTU/h
kW
Amps
Elements 240V
2
Stage
max. power
supply
(MCM)3
VoltMax 79
268 695
78,75
219
7 x 15 kW
7 x 11,25 kW
3 x 350
VoltMax 90
307 080
90
250
8 x 15 kW
8 x 11,25 kW
3 x 500
VoltMax 95
322 434
94,5
263
7 X 18 kW
7 X 13,5 kW
3 x 500
VoltMax 108
368 496
108
300
8 x 18 kW
8 x 13,5 kW
3 x 500
1
Electrical supply 208 V 3 phase (L1-L2-L3) with 3 conductors Cu or AL ,90 °C with a ground.
2
240V electrical element operated at 208V
3
-Maximum capacity of the boilers connection terminals
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 6.
Table 5 : VoltMax 240 VAC / 60 Hz / 1 Phase
1
Model
BTU/h
kW
Amps
Elements 240V
Stage
2
max. power
supply
(MCM)3
VoltMax 77
262 724
77
321
7 x 5 kW 7 x 6 kW
7 x 11 kW
2 x 500
VoltMax 80
272 960
80
333
16 x 5 kW
8 x 10 kW
2 x 600
VoltMax 84
386 608
84
350
14 x 6 kW
7 X 12 kW
2 x 600
VoltMax 88
300 256
88
366
8 x 5 kW 8 x 6 kW
8 x 11 kW
4 x300
VoltMax 96
327 552
96
400
16 x 6 kW
8 x 12 kW
4 x 300
1
Electrical supply 240 V 2 phase (L1-L2) with 2 conductors Cu or AL ,90 °C with a ground.
2
The 10 kW stage is composed of two 5kW elements The 11 kW stage is composed of one 5 kW element et one 6 kW element The 12 kW stage is composed of two 6 kW elements.
3
-Maximum capacity of the boilers connection terminals
Table 6 : VoltMax 208 VAC / 60 Hz / 1 Phase
1
Model
BTU/h
kW
Amps
Elments 240V
2
Stage
3
max. power
supply
(MCM)4
VoltMax 58
197 043
57.75
278
7 x 5 kW 7 x 6 kW
7 x 8.25
kW
2 x 500
VoltMax 60
204 720
60
288
16 x 5 kW
8 x 7.5 kW
2 x 500
VoltMax 63
214 956
63
303
14 x 6 kW
7 X 9 kW
2 x 500
VoltMax 66
225 192
66
317
8 x 5 kW 8 x 6 kW
8 x 8.25
kW
2 x 500
VoltMax 72
245 664
72
346
16 x 6 kW
8 x 9 kW
2 x 600
1
Electrical supply 240 V 2 phase (L1-L2) with 2 conductors Cu or AL ,90 °C with a ground.
2
240 electrical element operated at 208V
3
The 7.5 kW stage is composed of two 5kW elements The 8.25 kW stage is composed of one 5 kW element et one 6 kW element The 9 kW stage is composed of two 6 kW elements.
4
- Maximum capacity of the boilers connection terminals
Table 7 : Maximum operating pressure
All models
1
Standard maximum operating pressure
160 PSI
1
Safety valeve pressure of 60 psi, 125 psi or 150 psi (Standard).
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 7.
BOILER DIMENSIONS AND CHARACTERISTICS
* Optional disconnect switch available on "THREE-PHASE" models.
BOILER CONNECTIONS
1
Boiler outlet
3 " NPT M
2
Boiler inlet
3 " NPT M
3
Pressure relief valve
3/4" NPT F
4
Drain valve
1 1/4 " NPT F
5*
Access to the return sensor
1/2 " NPT F
MIN. CLEARANCES FOR INSTALLATION &
MAINTENANCE
Left and Right sides
6"/ 152mm
Rear
6"/ 152mm
Front
24" / 610mm
Bottom
0" / 0mm
Top
32" / 813mm
GENERAL INFORMATIONS
Weight
1200 lbs / 545 kg
Water Volume
62 Us gal. / 235 liters
Max. operating
pressure
STANDARD: 160psi
COMPONENTS IDENTIFICATION
A
Electrical main supply
B
Boiler controller
C
"On/Off" switch
D*
Disconnect switch & rotary handle
E
Fuses for controls
F
Solid state SCR relay
G
Low water cut-off, test button and indicator lights
H
Electrical control access door
I
Door handle for electric access with lock
J
Electrical control wires access holes
K
Access door power circuit
L
Access cover to Heating elements
M
Heating elements
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 8.
General Safety Precautions
Be sure to read and understand the entire Installation & operation manual before attempting to install or to operate this water heater. Pay attention to the following General Safety Precautions. Failure to follow these warnings could cause property damage, bodily injury or death. Should you have any problems understanding the instructions in this manual, STOP, and get help from a qualified installer or technician
INTRODUCTION
These important safeguards and instruction appearing in this manual are not meant to cover all possible conditions and situations that may occur. Common sense, caution and care are factors that cannot be built into every product. These factors must be supplied by the person(s) caring for and operating the unit.
LOCAL INSTALLATION
REGULATIONS
This electric boiler must be installed in accordance with these instructions and in conformity with local codes, or in the absence of local codes, with the National Plumbing Code and the National Electric Code, current edition. In any case where instructions in this manual differ from local or national codes, the local or national codes take precedence.
CORROSIVE ENVIRONMENT
The electric boiler must not be installed near an air duct supplying corrosive atmosphere or with high humidity content. When a boiler defect is caused by such conditions, the warranty will not apply.
INSPECTION UPON RECEPTION
Inspect the electric boiler for possible shipping
damage. The manufacturer’s responsibility
ceases upon delivery of goods to the carrier in good condition. The Consignee must file any claims for damage, shortage in shipments, or non-delivery immediately against the carrier.
TO BE CHECKED
Please refer to the rating plate on the unit to ensure that you have the correct model and voltage in hand.
List of components shipped with the unit:
• Pressure relief valve
Drain valve
• Outdoor temperature sensor ¸
(Located inside the control panel of the unit)
The electric boiler should not be installed where it may damage the adjacent structures or lower floors in the event of leakage of the tank or connections. If this cannot be avoided, install a non­flammable tray or bowl under the boiler to collect and drain water from leaks.
NOTE: Any tray or cuvette MUST conform to local codes.
!
AVERTISSEMENT
!
WARNING
!
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 9.
INSTALLATION
The manufacturer’s warranty does not cover any damage or defect caused by installation, or attachment, or use of any special attachment other than those authorized by the manufacturer into, onto, or in conjunction with the water heater. The use of such unauthorized devices may shorten the life of the boiler and may endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized devices
SAFETY MEASURES
Any commercial installation will be equipped with a safety valve that limits the maximum working pressure to the maximum design pressure of the tank. The maximum operating pressure of the VoltMax Boiler with a power of 90kW and less is 30 psi or 70 psi, depending on the options chosen. The maximum operating pressure of the VoltMax boiler with a power of more than 90kW is 60 psi or 125 psi, depending on the options selected. See boiler data sheet for maximum operating pressure.
The boiler is equipped with an automatic high limit temperature control set at 210°F (99°C) and a second manual high limit temperature settable.
This electric boiler is designed to operate at a maximum operating temperature of 200 ° F (93 ° C). The boiler is designed for use in a hot water heating system only.
The heat transfer fluid must be water or an antifreeze water / propylene glycol solution or an antifreeze water / ethylene glycol solution specially designed for heating systems. The maximum concentration of solution must be a maximum of 50%.
LOCATION
The electric boiler should be installed in a clean, dry location. Long hot water lines should be insulated to conserve water and energy. The electric boiler and water lines should be protected from exposure to freezing temperature.
The boiler can be mounted vertically or horizontally directly on a solid surface.
The electric boiler must be located or protected to avoid risk of physical damage, such as from moving vehicles, flooding, etc.
The location must have sufficient ventilation to maintain an ambient temperature not exceeding 80°F (27°C).
To prevent condensation on the boiler walls, boiler temperature should not be maintained below the condensation temperature (dew­point temperature) of the ambient. The operating temperature of the boiler must not be lower than the condensation temperature (dew temperature) relative to the ambient humidity content.
CLEARANCES
For adequate inspection and servicing the following minimum clearance is necessary:
Table 8 : Boiler Clearances
Sides**
3 inches / 76 mm
Bottom
0 inches / 0 mm
Top*
32 inches / 813 mm
Front
24 inches / 610 mm
Back
3 inches / 76 mm
* A minimum clearance of 32 inches. For units equipped with 18 kW elements (25 in. For 15 kW elements) is required for possible replacement of heating elements.
** The left side of the control panel, where the boiler ON / OFF switch is located, must remain visible after installation. Otherwise, a label indicating its location must be affixed to the control panel indicating its position.
PIPING INSTALLATION
The location of the inlet and outlet piping shall conform to the various configurations shown in Figure 1. You will find typical connection diagrams to the Figure 3, Figure 4 and Figure 5.
The VoltMax boiler is designed to be operated on a closed-circuit piping system. Therefore, it should not be used to heat open air tanks
MISE EN GARDE
!
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 10.
Figure 1 : Possible pipe flow configurations
BOILER PIPING CONNECTION
The boiler is equipped with two fittings on each side of the unit. One of the bottom connections must be used for the heating return (inlet) and one of the top connections must be used for supplying the heating system (outlet). The outlet and inlet size are 1½ "NPTM threaded steel pipes, for the VoltMax with a power of 90kW and less and 2½ "NPTM threaded steel pipes for the VoltMax with a power of More than 90kW.
Installation of plugs on the inlet and exhaust ducts is required to facilitate the disconnection and maintenance of the boiler.
When connecting different types of pipes (galvanized steel and copper), use dielectric joints (insulation) to protect the boiler and piping.
Use only new and clean pipes as piping connection to the boiler. Local codes or regulations may dictate the exact type of material to be used.
Insulate all piping containing hot water, especially in an unheated environment.
Install faucets for easy maintenance. Install a thermometer on the inlet and outlet
duct(s). Close the unused openings on the boiler. Do not
block the safety valve, this may cause loss, damage or injury.
AUXILIARY BOILER PIPING
CONNECTION
When an auxiliary boiler used as back up is twinned to the VoltMax boiler to act as a back-up controlled by the VOTLMAX, the auxiliary
boiler shall be installed downstream of the electric boiler as shown on Figure 5 and 7.
SAFETY VALVE
The installation of a safety valve is an integral part
of the boiler’s installation. The trigger point of the
valve must not exceed the design pressure of the boiler as indicated on its registration and identification plate. The valve must comply with the ASME Boiler and Pressure Vessel Code and limit the boiler maximum operating pressure. The safety valve is a security component, not a control component.
The capacity of the safety valve expressed in BTU / hour must equal or exceed the rating on the nameplate of the boiler (s).
A safety valve adjusted to the maximum design pressure of the boiler has been installed at the factory. The latter can be replaced by a valve with a lower trigger pressure, but its BTU / hour capacity must not be lower than the maximum boiler power.
Connect the exhaust of the safety valve to a drain line. The lower end of this conduit shall be at least 6" (15 cm) from the floor drain away from any electrical component. The drain line must be directed downwards from the exhaust of the safety valve to ensure complete drainage by gravity. The diameter of the drainpipe must not be less than that of the exhaust of the valve. The end of the conduit must not be threaded or hidden and must
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 11.
be protected from freezing. No valves, valves or valves shall be installed on the pipe. The installation of the safety valves is governed by the local code.
SYSTEM PRESSURE CONTROL
AND EXPANSION TANK
Pressure control devices within the system ensure that each component operates within minimum and maximum allowable pressures and maintain minimum pressure for all normal operating temperatures. They also allow air bleeding, prevent cavitation at the pump inlet and prevent water from boiling within the system; all this is accomplished with minimal addition of new water.
The increase in boiler water volume resulting from higher temperature is stored in the expansion tank during periods of high operating temperature and is returned to the system when the temperature decreases.
The expansion tank must be able to store the required volume of boiler water during maximum design operating temperature without exceeding the maximum allowable operating pressure, and to maintain the required minimum pressure when the system is cold. Contact your installing contractor, plumbing supply house, or local plumbing inspector for assistance. The point where the expansion tank is connected should be carefully selected to avoid the possibility that normal operation of automatic check or manual valves will isolate the tank from a hot boiler or any part of the system. The expansion tank should preferably be located on the suction or intake side of the pump.
WATER PRESSURE MAKEUP
REGULATOR
Make-up systems must be employed as required by codes. An automatic fill valve (automatic pressure regulator) must be used with a backflow preventer as required, to maintain minimum system pressure by supplying water to make up for leakage.
A minimum pressure of 5psi (34kPa) must be maintained at all times.
A backflow prevention device that complies with local standards must be installed upstream of the pressure regulator.
AIR BLEEDER
The air contained in the heated water must be removed from the system to allow the proper functioning of the heating system and the boiler.
Installation of manual or automatic air vents is required to eliminate all air from the boiler and the heating distribution system.
The main air eliminator must be installed near the outlet of the boiler on the highest point of the main supply piping. It is imperative to ensure that all air possibly located in the boiler be eliminated at all time.
Regularly purge air from the pipes and beware that the heated water does not cause injury or damage.
If the boiler is located at a location higher than the heat distribution system such as a heated floor, an automatic air eliminator should be installed close to the boiler outlet.
CIRCULATING PUMP
The pump capacity required is determined in relation to the capacity of the boiler installed and the type of heating distribution system on which it will be connected.
They are generally designed for an operation at a differential of temperature (Delta T0) of 10 to 20F between the supplies and return temperature to the boiler.
Use the following equation to determine the required water flow.
Pump flow rate = Boiler power ÷ Delta T ÷ 500
Pump flow rate is expressed in US gallons per minute or GPM.
The Boiler output (in net BTU per hour) is the maximum amount of heat to be transferred through the heating loop to meet the heating load.
Delta T: The boiler water temperature drop
For example, an electric boiler rated at 180KW has an output capacity of 614 160 BTU per hour. The system is designed for a temperature drop of 20°F.
Required pump flow rate = 614,160 20 500 = 61,4 GPM
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 12.
For example, an 180kW electric boiler has a power of 614,160 BTU/h. The system is designed for a drop-in temperature (Delta T) of 20°F.
Flow required = 614,160 20 500 = 61.4 GPM N.B. To achieve proper operation, a minimum flow
must be present when a heating request is applied and the heating elements are in operation. In the table below, the column representing a differential of 50°F indicates the minimum recommended flow for each boiler output. Installation of a flow switch is not mandatory. If installed, its contact must be connected between 24V+ and W1 (operation authorization) The following table lists the required pump flow rate in relation to the boiler capacity and Delta T.
Table 9 : Temperature rise vs flow rate (GPM)
MODEL
DELTA T0
10oF
20oF
30oF
40oF
VoltMax 77
52,5
26,3
17,5
13,1
VoltMax 80
54,6
27,3
18,2
13,6
VoltMax 84
57,3
28,7
19,1
14,3
VoltMax 88
60,1
30,0
20,0
15,0
VoltMax 96
65,5
32,8
21,8
16,4
VoltMax 105
71,7
35,8
23,9
17,9
VoltMax 120
81,9
40,9
27,3
20,5
VoltMax 126
86,0
43,0
28,7
21,5
VoltMax 144
98,3
49,1
32,8
24,6
VoltMax 192
131,0
65,5
43,7
32,8
VoltMax 204
139,2
69,6
46,4
34,8
VoltMax 216
147,4
73,7
49,1
36,8
VoltMax 225
153,5
76,8
51,2
38,4
VoltMax 240
163,8
81,9
54,6
40,9
VoltMax 255
174,0
87,0
58,0
43,5
VoltMax 270
184,2
92,1
61,4
46,1
VoltMax 288
196,5
98,3
65,5
49,1
VoltMax 306
208,8
104,4
69,6
52,2
VoltMax 315
215,0
107,5
71,7
53,7
VoltMax 324
221,1
110,5
73,7
55,3
VoltMax 336
229,3
114,6
76,4
57,3
VoltMax 357
243,6
121,8
81,2
60,9
VoltMax 378
257,9
129,0
86,0
64,5
VoltMax 384
262,0
131,0
87,3
65,5
VoltMax 408
278,4
139,2
92,8
69,6
*Minimum flow
DRAIN FAUCET
A drain valve is installed behind the unit. It allows the boiler to be emptied, to make possible the replacement of defective components.
SIEVE
A sieve or other accessorie that collects sediments should be installed on systems where high particle concentration may existe. Sediments may eventually get to the elements and cause damage to the elements. The warranty does not cover damages in this case.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 13.
PRESSURE LOSS
The graph of pressure loss due to flow of water inside the VoltMax boiler is shown in the following figure.
Figure 2 : Pressure loss (FTH) as a function of the flow rate of heated water (GPM)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 14.
Figure 3 : Basic installation
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 15.
Figure 4 : Basic installation with indirect water heater and radiator
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 16.
Figure 5 : Dual-Energy installation with a condensing boiler
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 17.
Figure 6 : Multiple boiler parallel installation
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 18.
Figure 7 : Basic installation with auxiliary boiler for production of domestic hot water and heating
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 19.
ELECTRICAL CONNECTIONS
Wiring must conform to the National Electrical Code and to state or local code requirements.
The electric boiler must be electrically grounded in accordance with local codes, or, in the absence of local codes, with the National Electrical Code.
MAIN ELECTRICAL SUPPLY
The power supply must be a 208 or 240-volt circuit (single-phase or three-phase, 60Hz), 480 volts (three-phase, 60 Hz) or 600 volts (three-phase, 60 Hz) protected by an appropriately sized breaker.
Refer to the boiler rating plate to select the breaker capacity and wiring rating
Alimentation cables can be in copper or aluminium.
The used cable gauge shall not be greater than the maximum size allowed by the connection terminals. See tables 1 through 6 for the specific values.
PUMP SUPPLY
The VoltMax Electric boiler can control 1 or 2 pumps of the distribution system. According to the VoltMax configuration, the contact of the pump will function differently.
During a heat demand on W1 or W2, the contact between Pc and P1 or Pc and P2 will be used to start an external pump relay (maximum of 3 amps.). Depending on the configurations selected in the controller, the pump P2 can have priority over the pump P1.
N.B. The VoltMax boiler is not designed to heat without a water circulation in its tank. Therefore, if external pump controls are used, they must be interlocked with the operating authorization on W1 and/or W2 of the controller.
CONNECTION OF EXTERNAL
SIGNALS TO THE CONTROLLER
The connection of all external signals is made directly on the boiler controller on terminals located on top of it. See the connection diagram on Figure 8
Cables used for the connections shall resist temperature up to 90 °C.
Connecting the building heat demand
signal or running authorization
Upon reception of a closed contact connected to terminals 24V+ and W1 or W2, the corresponding circulating pump P1 or P2 will start and the boiler will be allowed to operate.
If external controllers control the heating system pumps, they must provide the operating authorization signal. The boiler must not receive a heat demand without the circulation pumps running.
On heating systems when water circulation is continuous, the heat demand control can be connected in series with the pumps interlocks to the 24V+ and W1 terminals. The heating elements will then be active and available only when there is a request (dry contact).
If the heating system is designed to keep water warm with continuous circulation, a dry contact from the pumps relay or a contact from a flow sensor must be connected on the 24V+ and W1 terminals to maintain the boiler in demand as long as the pumps are in function. The boiler will then attempt to maintain the water temperature at the set-point.
Operation with an upper fixed set-point W2 can be established by connecting the auxiliary heating demand signal (Dry contact) of a thermostat to the 24V+ and W2 of the terminal block.
In all operating modes of the controller, a heat demand on W1 and W2/DHW (close contact) must be present to DI1 or DI2 to allow the operation of the boiler. The only exception is in domestic hot water mode (DHW) with an indirect water heater where the minimum boiler temperature shall be maintained.
Connecting an auxiliary boiler
The boiler controller is designed to allow the operation of a second boiler or an auxiliary boiler according to two different mode of operation “Auxiliary Backup” or Dual-Energy”. To do so, connect the TT terminals of the auxiliary boiler to terminals AUX of the VoltMax. The maximum capacity of this contact is 3A/120Vac.
See section 4.3.4 for details.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 20.
Connection of an “Unoccupied signal”
of the building.
This function allows dropping the boiler temperature during periods where the building is not used and this without having to lower all the room thermostats of the building. To do so, a signal (dry contact) will have to be connected to terminal OCC. The contact shall be close during the periods of temperature drop. You can also manage the periods of temperature drop by setting a schedule in the controller.
Connection of an indirect domestic
hot water heater
The VoltMax electric boiler can be used not only to fill the heating requirements of the building but also to fill its domestic hot water needs using an indirect domestic hot water heater such as our TURBOMAX series. To do so, connect the signal (dry contact) of indirect water heater temperature control to the terminal 24V+ and W2/DHW This will activate the circulating pump supplying the water heater (if properly installed).
Connection of a dual-energy signal
The VoltMax can be operated in a dual-energy mode with an auxiliary boiler.
To do so, connect the normally close contact of the dual energy controller to terminals 24V+ & BI-E to operate with the electric boiler. See section
4.3.4.5 for more details on the sequence of operation in dual energy.
Connection of an outdoor temperature
sensor
If you wish to modulate the boiler water temperature according to the outdoor temperature (Outdoor Reset, ORST) and also wish to stop the operation of the boiler when the outdoor temp. reaches a selected value, then the outdoor sensor supplied with the unit or a corresponding signal coming from the network system shall be connected with a cable of minimum gauge 20 (max 100pi) to terminals S. Ext. of the controller. This probe does not need to be connected during an operation with a fixed setpoint temperature unless you want to use the Warm weather Shutdown function.
N.B. Do not install a jumper if the outside sensor is not used.
Outdoor sensor location
o Outside the building at a location that best
represents the heat demand of the building (a wall facing north for most of the buildings and on a south one on buildings with large windows facing south).
o It should not be exposed to external heat
sources (dryer outlet, window openings, non­insulated walls).
o It should not be installed in a location where it
could be covered with snow.
Remote controller used to determine
the target boiler temperature
An external controller (such as a central building energy management system) can be used to determine the boiler target temperature required for the building. On every model this can be done by a BACnet communication. Also, an external controller shall give a 0 to 10VDC signal connected to terminals 0-10Vdc G & 0-
10Vdc T° of the controller.
Limit Capacity 0-10VDC
On every model this can be done by a BACnet communication. An external controller providing a 0-10Vdc signal could be used to manage the capacity (kW) of the boiler. Example: An application where the main electrical service supply of the building is limited or when the electricity rate is billed according to the maximum peak loads of the building. To do so, the external controller shall be connected to terminals 0-10Vdc G & 0-10V cap. The capacity of the boiler could be manually limited by adjusting some of the controller parameters. See section 4.3.4 for more details.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 21.
External alarm contact
An alarm signal (dry contact) is available on the boiler to advise the user of an alarm situation. The capacity of the contact is 5A resistive/1A inductive on terminal AL/AL.
The dry contact between contactors AL/AL is normaly open and will close in the event that any of the following conditions appears:
A temperature high limit
A low level of water (if included)
Électric power loss or the control switch is
at OFF.
An internal audible alarm inside the controller is available on all models. Just activate it in the settings.
Connecting an external high
limit (EXT.HL)
An additional high limit control (pressure,
temperature, flow, water low level…) could be
required in a particular application. It shall be installed outside of the unit and its contact shall be connected the EXT. HL contactor of the terminal bloc after removing the current jumper. This contact is installed in series with the internal high limits of the boiler and will stop completetly the boiler and even engage a lock out if the contact persists. Consequently, this contact shall not be used to turn on the boiler. The heat demand or running authorization should be connected on W1 or W2.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 22.
Figure 8 : ELECTRICAL CONNECTIONS OF THE INPUT AND OUTPUT SIGNALS TO THE CONTROLLER
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 23.
CONTROLLER OPERATION
USER INTERFACE
The control of the boiler is ensured by a controller TM171PFE03 from the Schneider Electric company. The LCD display of the controller provides an interface for configuring and displaying the boiler parameters and status.
A communication module also allows you to integrate the controller with an intelligent building management system (BACnet protocol). It is also equipped with an Ethernet connection. Allowing the connection to the Internet network of the building allowing reading and modifying locally or remotely the boiler setting. It can be configured to send alarm messages via e-mail.
Icons will also display to indicate the boiler’s current operating status. Temperature can be displayed in Celsius or Fahrenheit and text can be set to either English or French.
The controller has a backlight function. It is also equipped with three indicator lights (Green / Yellow / Red). The green light indicates normal operation of the unit; the yellow light indicates that the controller has diagnosed and anomaly which requires verification by a technician. The red light indicates that the unit is currently in a critical state (high temperature alarm) or in lock out mode. More detail is provided in Section 6: Troubleshooting. The controller can also be configured to activate an internal buzzer and activate an external alarm signal when an alarm
condition occurs causing the boiler to fail.
Figure 9 : Illustration of the display
SYMBOL DESCRIPTION
The main display shows most the boiler operation status information. The explanation of the main display is shown below.
Boiler operating mode
W1
Heating request 1 : On
W2
Heating request 2 : On
BIE
Boiler in Bi-Energy mode
VoltMax Boiler : On
Auxiliary boiler : On
Boost mode : On
Warm Weather Shut Down : On
Alarm symbol
An alarm is active
The boiler is in lock out mode
HL
High temperature limit condition at the boiler outlet
LL
Low temperature limit conditions (lack of capacity)
P
Alarm due to a pressure problem
A
Alarm due to an electrical problem
F
Alarm due to a flow problem
Se
Alarm due to a sensor problem
The internal clock battery level is low
Operating state of the boiler
T° SET­POINT
Actual set-point temperature
T° BOILER
Water temperature at the outlet of the boiler
CAP (%)
Percentage of power used according to boiler rated power
T° EXT
Outdoor temperature measured using the outdoor sensor
KW ACT
Actual power calculated by the boiler
PRESS.
Pressure inside the boiler
STAGE
Status of active stage
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 24.
CONTROL PANEL
Figure 10 : Control panel
On the left side of the appliance, an on / off switch (# 3) is used to operate the appliance and to reset the boiler.
An indicator light showing the status of the low water level cut off and a test button (# 1). The control circuit fuses (# 2) are accessible from the left side of the unit.
NAVIGATION AND
ADJUSTEMENTS
The navigation within the display is done with the five pushbuttons on the right of the screen.
Navigation between the elements is done with the up and down arrows. Use the right key to change the page in the menus. The return key will bring you to the previous menu. The return key returns you to the main display when it is pressed for 2 seconds or more.
The OK button confirms the selection and allows you to edit a parameter. Only highlighted box can be modified. To modify an option, select the box to modify with the arrow keys and press OK. The black box or one of its values will flash and can be changed. Change the values using the arrows and confirm the change by pressing OK.
1 2 3
4
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 25.
MAIN MENU NAVIGATION
Press one of the 5 buttons on the main display to access the main menu
Figure 11 : Main menu navigation
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 26.
NAVIGATION IN BOILER SETTING
Figure 12 : Navigation in boiler setting menu (1/3)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 27.
You can switch from page by using the left or right arrow (Ex : 1/3 to 2/3 by using the right arrow)
Figure 13 : Navigation in boiler setting menu (2/3)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 28.
Figure 14 : Navigation in boiler setting menu (3/3)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 29.
MAIN MENU
The main menu is accessible to the user, no access code is required. The main menu is accessed by pressing one of the 5 pushbuttons. Navigation between menus is done with the arrows (up, down, left and right).
Menu
Contents
Boiler status
Detailed information on the boiler condition
Boiler setting
Configuration of the boiler operating mode and parameters.
User setting
Configuration of the controller display option
Clock setting
Configuration of the internal clock
Consumption
Power consumption of the boiler
BOILER STATUS
Detailed information on the boiler condition
This menu allows the display of data not included in the main display. The boiler status menu displays the measurements of temperature, pressure, flow, alarm summary, version of the programme and the status of the heating element.
The set of variables presented in this menu are presented in Section 4.5
BOILER CONFIGURATION
Configuration of the boiler operating mode
This menu is accessible only to the installer or to an authorized person.
The default installator password is 1111
To enter the password:
-Press up or down arrows until the “installer” rectangle becomes black, then press “OK”.
-Press the up arrow once the change from 0 to 1.
-Press left arrow and the second number will be selected. Press the up arrow to change from 0 to 1
-Proceed the same way the enter the other numbers. Press OK when done.
The options in the Boiler setting menu are detailed in Section 4.3.
The Manufacturer access code gives access to advanced operating parameters that are not accessible to the installer and the user.
USER SETTING
Configuration of the controller display option
This menu allows the modification of different display parameters.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 30.
Parameters
Description
Language
Select English or French version
Temperature unit
Select the temperature units, either Celsius (C) or Fahrenheit (F)
Flow unit
Select the flow unit, either US gallons per minute (USgpm) or liters per second (L / sec)
Backlight
Setting the backlight mode:
- Off
- 30 secondes
- Always On
Internal buzzer
ON/OFF setting of the internal buzzer
CLOCK SETTING
Internal clock configuration
Use this menu to adjust the controller’s internal clock. To set the clock correctly, you must adjust the time, minutes, and date.
This adjustment is necessary in order for these modes to function properly:
- The boiler’s power consumption
- Limiting the boiler’s power capacity according to a schedule
- The boiler’s occupation mode Battery life for the clock is at least 1 year when
the controller is unpowered (at 25°C). When the battery is low an indicator will appear on the screen. The battery shall be replaced to keep to clock active. Following a battery replacement, the internal clock must be reprogrammed to remove the indicator on the bottom of the screen.
CONSUMPTION
Boiler consumption cycle report
This menu allows visualization of the boiler power consumption report. First, you must activate the beginning of the consumption cycle with the Start key. The consumption report can be saved using the Save key. And all saved report is available on the History tab. The beginning of the consumption cycles can be reset using the Reset button.
The controller records up to 30 consumption report.
N.B The consumption values are approximate and should not be used as a comparison with actual consumption data charged by the electricity distributor.
BOILER SETTINGS
In order to be able to configure the boiler, it is necessary to authenticate yourself with an installer or manufacturer code.
The default "Installer" access code is
1111 and can be changed in the
Change password menu.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 31.
HEATING
MODE W1
Boiler heating mode W1 configuration according to the type of application
HEATING
MODE
W2/DHW
Boiler heating mode W2 or DHW configuration according to the type of application
CAPACITY
LIMITING
Capacity limiting mode configuration
AUXILIARY
BOILER
Auxiliary boiler mode configuration (if needed)
LIMIT
SETTING
Configuration of the boiler operating limits
ALARM
Configuration of the alarms
COMMUNICATION
Configuration of the boiler communication parameters (Web, Email, Bacnet)
OCCUPATION
Configuration of the occupation parameter mode
MODE BOOST
Enable Boost mode
WARM WEATHER
SHUTD.
Enable warm weather shut-down function
CHANGE
PASSWORD
Changing the Installer password
HEATING MODE W1
Selection of the operating mode
In this menu you must select an operating mode for selecting the desired setpoint temperature depending on the application. A heat demand or a demand must be present on W1 and/or W2/DHW so that the boiler can heat up. Otherwise the boiler will indicate “---
During a heat demand, the boiler activates (depending on a PID curve) the number of stages required in sequence so that the boiler output temperature is maintained at the approximate set-point temperature.
Here is the list of W1 heating modes:
FIXED
Fixed boiler set-point
DDC 0­10 VDC
Modulation of the boiler set-point using a 0-10VDC signal
OUTD RESET
Modulation of the boiler set-point using the outdoor temperature
STOP
No heating demand on W1
Fixe
This mode is used for an installation where it is desired to have a fixed set-point temperature. If the boiler is thermostat-controlled with a heat demand signal on W1, the boiler uses the corresponding set-point (T. Set-point W1) as the supply temperature.
DDC 0-10 VDC
This operating mode allows modulating the boiler set-point temperature according to a 0-10VDC signal applied the terminal 0-10VDC and bornier 0-10Vdc G et 0-10Vdc T, produced by an external controller (Ex: Building Energy Management Controller).
The details of the parameters in this mode are presented in Section 4.6.3.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 32.
Outdoor reset
This operating mode makes it possible to modulate the boiler output set-point temperature as a function of the outdoor temperature. The outdoor temperature signal comes from the temperature sensor supplied with the boiler, which will be connected to the boiler controller.
The details of the parameters are presented in
Section 4.6.2.
Stop
Select this mode to stop the boiler. The heating elements will not operate on a W1 demand.
HEATING MODE W2/DHW
This mode allows you to configure a second heating demand (W2) or a demand from an indirect domestic water heater (DHW). Select none if none of these functions are used. These modes are presented in detail in Section
4.7 .
W2
This mode allows the W2-DHW input to be used to receive a signal (dry contact) from a 2nd stage of heating. When the contact on W2-DHW closes, the set­point temperature changes to the set value (T.
Set-point W2), even if there is no demand on W1.
DHW
This mode allows you to configure the demand for an indirect domestic water heater. When the DHW mode is selected, the boiler is kept at a minimum temperature (T. Min Boiler) and when contact W2 closes (Dry contact) the set-point rises to T. DHW Set-point. In addition, the PID curve is more aggressive.
CAPACITY LIMITING
Adjusting the maximum authorized power
This menu allows you to configure the boiler output limit. The selection of the limit mode can be selected in the Capacity limiting menu
o None
o Manual o DDC 0-10 VDC o T. Ext o Schedule
Details of each of these options are presented in
Section 4.8 . N.B: It is not recommended to disconnect one of
the power relays inside the VoltMax boiler to accomplish this function.
None
The boiler is not limited in power, the maximum power it can deliver is equivalent to its maximum rated power.
Manual
The maximum capacity permitted of the boiler is configured in a fixed mode.
Details of the variables in this mode are presented in Section 4.8.1
DCC 0-10 VDC
A 0-10 VDC signal from a building management system can be used. The signal is treated as a function in order to limit the maximum power. In order to configure this mode, you must connect the 0-10 VDC signal to the terminal block 0- 10Vdc Cap. and 0-10Vdc G.
Details of the variables in this mode are presented in Section 4.8.2
T. ext
The maximum permitted power can be adjusted according to the outside temperature sensor. The outdoor temperature is used in order to limit the maximum authorized power.
Details of the variables in this mode are presented in Section 4.8.3.
This mode of operation is particularly advantageous in applications where the boiler is connected to an electrical network taking account of demand peaks in order to determine the cost of use (demand meter). Since the boiler will thus be limited to a maximum power which will have to be established as a function of the heating requirements of the building and the outside temperature, it will thus be possible to avoid peaks of power not required to satisfy the heating needs in periods of cold weather.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 33.
Schedule
The maximum authorized boiler power can be programmed according to a schedule. See section 4.8.4 for an explanation of how to modify a schedule.
AUXILIARY BOILER
The controller program has been designed to allow the operation of a second boiler or auxiliary boilier.
Select setpoint source for Auxiliary
Boiler
The source of the set-point temperature control can be configured by selecting STPT source Aux. consequently.
In the VoltMax mode, the terminal contact Aux closes when there is a request for W1 or W2/DHW and the VoltMax output temperature is below the setpoint temperature. In addition, the Aux contact is opened when the output temperature is higher than the setpoint temperature.
In AUXILARY mode, the Aux contact closes when there is a request on W1 or W2 / DHW regardless of the boiler output temperature VoltMax. The VoltMax boiler thus has no set temperature and is only used to activate the auxiliary boiler relay. The various configurations of the Aux boiler mode are the following:
None
No auxiliary boiler is present
Backup Aux.
This mode allows the adjustment of a second boiler to play a Backup role
Ext Contact
Select the heating source using external contact to the BI-E terminal.
BiE (BI-
Energy)
Select the heating source using external contact to the BI-E terminal
with the possibility of support mode of the auxiliary boiler.
Manual
Manually select the system operation mode (Electrical or Auxiliary).
N.B. The auxiliary boiler can only be switched on when a heat demand is present on W1 or / and W2 / DHW.
None
This mode must be active when there is no auxiliary boiler on the hydronic heating system.
Backup Aux.
The boiler will be activated according to the configuration of the lack of capacity of the VoltMax boiler.
In the event of a lack of capacity, the boiler is started to compensate. The lack of capacity is defined by the fact that the boiler output temperature is less than X degrees (Delta T. Start Aux.) relative to the set-point for duration of X min. (Auxiliary Start Delay). The auxiliary boiler will be deactivated when the temperature differential between the water outlet temperature and the set-point temperature is lower than Delta T. Off Aux. The calculation of the delay begins only when the electric boiler reaches its maximum power (or maximum power allowed).
The value of "Delta T." should be a negative value.
Details of the variables in this mode are presented in Section 4.9.1
Contact Ext.
This configuration mode makes it possible to operate the electric boiler or the auxiliary boiler according to a contact. During a close contact at
the BI-E terminals, the electric boiler ( ) is activated. When the contact is open, the auxiliary
boiler ( ) will be on. The auxiliary boiler will not be allowed to operate if the electric boiler lacks capacity. Details of the variables in this mode are presented in Section 4.9.2
BiE (BI-Energy)
The Bi-Energy mode allows the auxiliary boiler to operate when there is a lack of capacity.
Upon receipt of an electrical signal (contact closed at Bi-E) and a request at the terminal of W1 or W2, the contact at the terminal of AUX will
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 34.
be opened and thus the electric boiler ( ) is allowed to operate and the auxiliary boiler is deactivated.
When an electrical signal is absent (contact open at Bi-E) and a request is present at the terminals of W1 or W2, the contact will close at the terminal of AUX, in order to operate the boiler Auxiliary (
) and not the electric boiler.
If the electric boiler is turned off (lock out), the contact on the AUX contactor will close to authorize operation of the auxiliary boiler.
Manual
Manual mode is used to manually select the operating mode of the system (Electrical or Auxiliary). Details of the variables in this mode are presented in Section 4.9.3
LIMIT SETTING
Configuring the boiler operating limits
Use this menu to adjust the permissible operating boiler limits for various parameters.
This menu’s configuration options are presented in detail in Section 4.11.
ALARM
Alarm Mode Configuration
When an alarm is active, it will be displayed on the main display as a symbol.
An alarm is active
The boiler is in lock mode
HL
The high limit temperature has been reached
LL
Low limit (Lack of capacity)
P
Pressure problem alarm
A
Electrical problem alarm
F
Flow problem alarm
Se
Sensor problem alarm
The internal clock battery level is low
A summary of active alarms is also available in the Boiler status menu.
Section 6 - Troubleshooting details alarm codes and settings specific to this menu.
An alarm report is available under the Alarm log menu. Information about date, time and alarm code is available in this menu. The internal clock must be adjusted beforehand so that the alarm registers correctly.
Details about this menu’s operation are available
in Section 4.10
COMMUNICATION
The boiler controler can be connected by an ethernet connexion port or by RS485 (BACnet SMTP). The boilers web portal can be accessed by different means. It is then possible to modify parameters from distance on this web portal and to visualize the functioning status of the boiler.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 35.
IP Adresse
This menu permits to configure the connexion properties of the VoltMax boiler.
Direct connexion between the controler and a computer (Direct Ethernet cable).
1. Connect the boiler controler on the local network with the ethernet port (On the back of the controller) with a standard RJ45 cable. See electric diagrams if needed.
2. On your computer, open a command window (On widows opereating systems, type « cmd » in the program search bar).
3. In this command window, type « ipconfig » and write down your IPv4, subnet mask, and default gatway (as shown on the next figure).
4. Back on the controler, in the Communication/Ethernet section change the default IP adress (10.0.0.100) for an adresse that is compatible with the one that got written down. The last 3 numbers should be diffrent than your IP adress (make sure not tu use an already existing adress). For example, the IP adress 192.168.0.232 could of been used in this particular case.
5. In the same section, enter the written down default gatway and subnet mask. DNS servers may be left as default (8.8.8.8 and
8.8.4.4).
6. Reboot the controler to apply all changes.
7. On a web browser, you may now directly write the chosen IP adress in the navigation bar (as if it was a website) and you will be redirected to the controlers webpage. By the default, the username and password are as givien in the next table.
By default
Username
administrator
Password
password
Distant wireless connexion with a WI-FI rooter.
If the boiler cannot be directly connected to the network, a WI-FI rooter may be added to it to act as connexion between the boiler and the network. Connexion procedure may varie from one rooter to another. This exemple is for a tested TP-LINK TL-WR802N rooter.
1. Modify all the IP parameters as show in the last section so the controller is compatible with the network.
2. Connect the power to the rooter
3. Connect the network cable to the rooter in the LAN/WAN port and to the ethernet port on the controller.
4. Use a computer to connect to the temporary network of the rooter.
5. Open a web browser and go to the http://tplinkwifi.net web page or to the defalt rooter address.
6. Follow the instructions in the rooter manual to set it up as client mode.
7. The client mode will connect the controller to the WI-FI network and the boiler will then be accessible as same as the direct connection methode.
8. The boiler can be acessible from distance with a VPN if the computer is not connected to the local network.
By default
Rooter adress
192.168.0.1
Username
admin
Password
admin
9. Reboot the controler to apply all changes.
CONFIG. BACNET
The control of the boiler by an external BACnet controller can be activated or desactivated by selecting “local” or “BACnet”
The Config. BACnet menu allows you to view the configuration and change the BACnet parameters to establish the BACnet communication.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 36.
In order to configure the VoltMax boiler to your BACnet management system, you must activate the function.
The controller allows a BACnet IP or MSTP communication.
You must then enter the;
BAUDRATE. For a BACnet MS / TP communication protocol with a Metasys system the default baud rate is 38400.
MAC ID / MS/TP address. By default for a BACnet MS / TP communication with a Metasys system, the address is 5.
Device instance. To be adjusted with the client BACnet equipment.
SOURCE. Can be selected as “LOCAL” to control de boiler with its controller or as “BACnet” to control the operation parameters with an external controller.
If required the following informations can also be modified to adapt to the client controller.
DATA BIT : / PARITY /STOP BIT
The names of the BACnet variables used by the program are listed in the tables 4.5 through 4.15 below. Variables beginning with AV and BV
are read variables, while variables beginning with "W" are editable.
For more information on the BACnet protocol, please refer to the appropriate documentation.
OCCUPATION
Setting the temperature-lowering period.
Occupation setting
This function allows the boiler water temperature to be lowered for defined periods without having to lower all the thermostats of the building. This function can be activated and deactivated within the menu Occupation under Occupation mode. This function allows the set-point temperature to be lowered when the boiler is within the hours specified in the Schedule Setting menu. The temperature drop (the value should be negative) in the set-point can be changed in the Occupation Setting menu.
The SCR model allows the connection of a contact (OCC Contact) allowing the use of an external timer to control the OCCUPATION function. Ex: When the contact (switch) is open at the OCC terminal, then the boiler will be in temperature­lowering mode. (Night mode) When the contact (switch) is closed, it will be in normal occupancy mode (Day mode).
Force is used to force the boiler to operate normally (day mode).
A weekly schedule can be programmed under the Schedule setting to modify the occupation hours of the building.
N.B: The internal clock of the controller does not take in account the daylight-saving time changes.
Schedule Configuration
Changing a Schedule
Use this menu to configure the building’s
occupation schedule. The schedule works on a weekly schedule (Monday - Sunday) and allow only 1 lowering Set point periods. The first hour represents the start of the occupancy period and the second hour represents the innocupancy periods.
Ex: In the case currently displayed between 07:00 and 17:59, the set-point temperature will not be affected. On the other hand, from 18:00 to 06:59, the set temperature will be lowered.
When the building is not occupied for a full day, you must enter this information as follows, so that the stpt stay in the lowering mode.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 37.
BOOST MODE
Enable Boost Mode
This mode operates with the Fixed Set-point and Outdoor reset mode.
This menu allows the Boost mode to be activated, this mode increase the set-point temperature when the heating load of the building exceeds the capacity generated by the current water temperature determined by the boiler. This mode is activated after a period of 30 min if the heat demand is maintained for 30 consecutive minutes on W1. After this period, the set temperature will start to rise until a predetermined maximum temperature is reached depending on the heating mode until the demand is filled. This temperature increase is temporary and has a maximum duration of 120 minutes or when the request is terminated on W1.
N.B. The BOOST mode is particularly interesting for applications such as: o Applications with a programmable thermostat
with automatic lowering of the building temperature.
o Return to normal heat demand after a
prolonged period of sunshine where there have been no long-term demands and, therefore, heating floors will take a long time to provide heat at d Normal water.
WARM WEATHER SHUTDOWN
Shuts down the boiler when the outside temperature reaches an established threshold.
This mode stops the boiler’s heating production when the outside temperature is higher than a pre-determined temperature (ex: 68°F).
Note: If the boiler is configured with DHW mode, it will continue to operate normally in order to meet the DHW heating demand.
CHANGE PASSWORD
Changing the password
This menu allows you to change the installer account password
ETHERNET
The settings available on the controller are also available remotely on a web portal. This portal works only when the boiler is properly connected to an internet or Ethernet network. The various setting parameters and the protocol for connecting the boiler to a network are available in the Communication menu and Section 4.3.7.
WEB PORTAL
In order to access the boiler remotely via the internet, the boiler controller must be correctly connected.
The web portal has 3 main menus, the User, Installer and Manufacturer menu. The structure of the web portal is the same as the controller; please refer to the previous sections, if you have any questions.
Ex: The user can obtain information concerning the boiler status, in the menu Operations /
N.B. The password to acces the installater section of the website is 1111.
ALARM NOTIFICATION EMAIL
In order to configure the alarm by e-mail, you must:
1. You must first ensure that you enter the correct information in the controller (depending on your network) under the following options:
a. IP address b. Default Gateway c. Subnet mask d. Primary DNS e. Secondary DNS
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 38.
You must restart the device for the changes to take place.
2. Access the Boiler Web Portal.
3. Click on the Installer / Communication menu.
4. Enter your e-mail under Recipient. You can
also use your own mail server by entering the necessary data.
5. Then select the types of alarms you want to receive by e-mail.
If you want to send alarms to different e-mail addresses, simply enter a list of e-mails.
The parameters to enter on the web page are indicated on the screen shot below.
Personal Email Server (Type: Gmail)
The M171 controller does not support SSL encryption. Thus, your SMTP Email server must accept an unencrypted connection. Internet service providers usually have a specific server that accepts connections without encryptions. On-line messaging services, such as Hotmail, G-mail, do not accept unencrypted communications. In order to work around the problem, there are relay services such as SMTP2GO: https://www.smtp2go.com, to relay between controller communication and your messaging system. This service is free for up to 1000 emails per month.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 39.
BOILER STATUS DISPLAY SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
Display
Description
BACnet Variable
Instance
Tag
BACnet Description
T. Set point
The set-point temperature of the boiler. The boiler will activate its elements accordingly in order to modulate its water outlet temperature.
AV_TBoilerSTP
53
8388661
---
T. Out Boiler
The temperature at the outlet of the VoltMax boiler.
AV_BoilerTOut
0
8388608
---
T. In Boiler
The temperature at the inlet of the VoltMax boiler. This sensor is only available on SCR models.
AV_BoilerTIn
1
8388609
---
T. Outdoor
This variable allows the outdoor temperature to be displayed in real time when the outdoor temperature sensor is correctly connected.
AV_OutdoorT
2
8388610
---
Boiler Pressure
This variable allows the reading of the pressure sensor inside the boiler.
AV_SensorPressure Signal
6
8388614
---
Actual power
The actual power used in kilowatt
AV_ActualPowerkw
8
8388616
---
% max authorized power
The maximum permissible power as a percentage of the nominal power.
AV_CapLimitPrc
54
8388662
---
Consumption
The power consumption of the last cycle. You must first begin a history cycle (MAIN MENU / CONSUMPTION)
---
---
---
---
Actual Current (A)
This variable allows the reading of the current sensor inside the boiler.
This sensor is only available on SCR models.
Av_SensorCurrent_ Signal
6
8388614
---
Demand W1
When requesting heating on W1, allowing the operation of the heating elements.
BV_HeatingW1
0
20971520
0 = No W1 demand 1 = W1 demand
Demand W2/DHW
When requesting heating on W2 or DHW, allowing the operation of the heating elements.
BV_HeatingW2
1
20971521
0 = No W2 demand 1 = W2 demand
Flow
When no heating elements are active, the calculated flow rate will be equivalent to 0,
because the theoretical flow is calculated according to the power used, T. Out Boiler and T. In Boiler T.
Available on SCR models only.
AV_WaterFlow
10
8388618
---
SCR Modulation %
Percentages of the SCR relay utilisation. (For SCR model only)
AV_ModSCR
7
8388615
Stage #1
Status of stage #1 (For STG model only)
BV_RelStage1
13
20971533
0 = Stage 1 not working
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 40.
1 = Operation of stage 1
Stage #2
Status of stage #2
BV_RelStage2
5
20971525
0 = Stage 2 not working 1 = Operation of stage 2
Stage #3
Status of stage #3
BV_RelStage3
6
20971526
0 = Stage 3 not working 1 = Operation of stage 3
Stage #4
Status of stage #4
BV_RelStage4
7
20971527
0 = Stage 4 not working 1 = Operation of stage 4
Stage #5
Status of stage #5
BV_RelStage5
11
20971531
0 = Stage 5 not working 1 = Operation of stage 5
Stage #6
Status of stage #6
BV_RelStage6
12
20971532
0 = Stage 6 not working 1 = Operation of stage 6
Stage #7
Status of stage #7
BV_RelStage7
41
20971561
0 = Stage 7 not working 1 = Operation of stage 7
Stage #8
Status of stage #8
BV_RelStage8
42
20971562
0 = Stage 8 not working 1 = Operation of stage 8
Alarm HL/LWCO Alarm
Alarm triggered because of a high limit and low water level manual alarm.
BV_StatusAlarmHL/ LW
14
20971534
0 = Normal operation 1 = Alarm activated
HL Alarm
Alarm triggered when the boiler’s internal
temperature is higher than the threshold.
BV_AlarmIntHL
15
20971535
0 = Normal operation 1 = Alarm activated
LL Alarm
Alarm triggered by the boiler’s lack of capacity.
BV_AlarmLL
21
20971541
0 = Normal operation 1 = Alarm activated
Low Pressure Alarm
Alarm triggered by a low pressure.
BV_AlarmLowPress ure
16
20971536
0 = Normal operation 1 = Alarm activated
High Pressure Alarm
Alarm triggered by a high pressure.
BV_AlarmHighPress ure
17
20971537
0 = Normal operation 1 = Alarm activated
Flow Alarm
Alarm triggered by a flow problem.
BV_AlarmLowFlow
18
20971538
0 = Normal operation 1 = Alarm activated
Current Alarm
Alarm triggered by a current problem.
BV_AlarmCurrent
19
20971539
0 = Normal operation 1 = Alarm activated
Sensor Alarm
Alarm triggered by a sensor problem.
BV_AlarmSensor
20
20971540
0 = Normal operation 1 = Alarm activated
Boiler model
The VoltMax boiler model.
---
---
Tension
The nominal voltage of the VoltMax boiler.
---
---
Firmware version
The controller’s firmware version.
---
---
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 41.
Program name
The controller’s program name and version.
---
---
HEATING MODE W1 SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
Display
BACnet variable
Instance
Tag
Description
Parameters
Default
Head
demand W1
WP_HeatingW1
43
20971563
Allows to select W1 heating demand source. BACnet or Local
Local Bacnet
Local
Operating Mode
WP_HeatingMod eW1
11
8388619
Selects the power limitation mode between Stop, Modulation T. Ext, DCC 0-10VDC and Fixed.
0 = Stop 1 = Outdoor Reset 2 = DCC 0-10VDC 3 = Fixed
Fixed
FIXED MODE
Configure the fixed set-point temperature
Display
BACnet Variable
Instance
Tag
Description
Selection
Default
W1 Set point
WP_FixedSTPT W1
22
8388630
Selects the fixed set-point temperature when there is demand on W1.
10 to 93 0C 50 to 200 0F
140 0F
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 42.
OUTDOOR RESET MODE
Adjust the set-point temperature according to the outside temperature
This mode allows modulating the boiler output set-point temperature as a function of the outdoor temperature. The outdoor temperature value comes from a temperature sensor connected to the boiler controller.
If the outdoor sensor is not connected or if its circuit is open, an alarm signal will be displayed on the display (SE). The boiler temperature set-point will become the set value at STPT Min T. Outdoor.
Figure 15 : Outdoor reset curve
Table 10 : OUTDOOR RESET MODE Settings
Display
BACnet Variable
Instance
Tag
Description
Parameters
Default
Calculated SPTP
AV_TBoilerSTPT CalculatedOUTR ST
12
8388625
Current set-point temperature calculated based on the adjustment curve and the outside temperature
10 to 93 0C 50 to 200 0F
---
STPT at Min Outd T
WP_STPTatMinO utdT
13
8388621
Boiler set-point temperature when the outside temperature reaches the Min Outd T.
10 to 93 0C 50 to 200 0F
140 0F
STPT at Max Outd T
WP_STPTatMax OutdT
14
8388622
Boiler set-point temperature when the outside temperature reaches the Max Outd T.
10 to 93 0C 50 to 200 0F
80 0F
Outdoor T.
AV_OutdoorT
2
8388610
Displays the outside temperature in real time when the outdoor temperature sensor is properly connected.
-46 to 107 °C
-50 to 250 °F
---
Min Outd T.
WP_MinOutdRst T
15
8388623
Minimum outside temperature (Set to the area’s
coldest average temperature)
-46 to 107 °C
-50 to 250 °F
-10 0F
Max Outd T.
WP_MaxOutdRst T
16
8388624
Maximum outside temperature at which the building will need heating
-46 to 107 °C
-50 to 250 °F
65 0F
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 43.
MODE: DDC 0-10VDC
Modulation of the set-point temperature as a function of 0-10 VDC (Available only on SCR model)
This operating mode allows to modulate the set-point temperature of the water outlet of the boiler according to a 0-10VDC signal applied to the terminal block 0-10Vdc T and 0-10Vdc G from an external controller (Ex: An energy management software).
A heat demand (closed contact W1 and / or W2-DHW) must be present so that the boiler can heat up.
Figure 16 : Mode DDC 0-10 VDC
Table 11 : Specific parameters in DDC 0-10 VDC
Display
BACnet variable
Instance
Tag
Description
Parameters
Default
T. STPT 0­10VDC
AV_TBoilerSTPT CalculatedV
17
8388625
This variable represents the set-point temperature based on the voltage of the building control system.
0
C or 0F
---
STPT at Min Volt
WP_STPTatMinR emote010V
20
8388626
Set-point of the boiler temperature corresponding to the voltage level of Min Voltage.
0
C or 0F
80 0F
STPT at Max Volt
WP_STPTatMax Remote010V
21
8388627
Set-point of the boiler temperature corresponding to the voltage level of Max Voltage.
0
C or 0F
140 0F
Actual voltage
AV_Remote010V STPT
3
8388611
Voltage emitted by the external controller in real time
0-10 V
---
Max Voltage
WP_MinRemoteV STPT
18
8388626
The maximum voltage that the external controller can send
0-10 V
10
Min Voltage
WP_MaxRemote VSTPT
19
8388627
The minimum voltage that the external controller can send
0-10 V
0
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 44.
W2 MODE SET-POINT TEMPERATURE SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
Display
BACnet Variable
Instance
Tag
Description
Selection
Default
Heat demande W2/DHW
WP_HeatingW2
44
20971564
Allows to select W1 heating demand source. BACnet or Local
Local BACnet
Local
Operating Mode
WP_HeatingMod eW2
23
8388631
Select the boiler’s operating mode during demand on W2 (None, W2 and DHW)
0 = W2 1 = DHW 2 = None
None
W2 MODE
Configures the fixed set-point temperature during demand on W2
Display
BACnet Variable
Instance
Tag
Description
Selection
Default
W2 Set point
WP_FixedSTPT W2
24
8388632
Selects the fixed set-point temperature during demand on W2.
10 to 93 0C 50 to 200 0F
175 deg F0
DHW MODE
Configures the fixed set-point temperature during demand on DHW mode.
Display
BACnet Variable
Instance
Tag
Description
Selection
Default
T. Set-point DHW
WP_FixedSTPT W2
24
8388632
Selects the fixed set-point temperature during demand on W2 terminale
10 to 93 0C 50 to 200 0F
175 0F
T. Min Boiler
WP_FixedSTPT W0
26
8388634
Selects the boiler’s minimum temperature. The boiler’s heating elements will activate
automatically to keep the hydronic system at the selected temperature.
10 to 93 0C 50 to 200 0F
150 0F
POWER LIMITATION MENU SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
You can control the boiler power with different modes. Their configuration is below.
Display
BACnet Variable
Instance
Tag
Description
Selection
Default
Limitation Mode
WP_CapLimitMo de
31
8388639
Select the power limitation between None, Manual, DCC 0-10VDC,T. Ext and Scheduled.
0 = None 1 = Manual 2 = DCC 0-10VDC 3 = T. Ext 4 = Scheduled
---
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 45.
MANUAL MODE
The maximum power is set manually.
Display
BACnet Variable
Instance
Tag
Description
Selection
Default
Current authorized max kW
WP_ManualCapL imit
32
8388640
Configures the maximum electrical power that the boiler will use.
0 to maximum rated power
---
0-10 VDC MODE
An external 0-10 VDC controller is used to adjust the maximum power.
Display
BACnet Variable
Instance
Tag
Description
Selection
Default
Current authorized max power (%)
AV_CapLimitPrc
54
8388662
The value of power (%) calculated based on the current and the boiler’s nominal operating voltage
0 to maximum rated power (%)
---
Minimum Power Volt (kW)
WP_MinRemote VCapLimit
33
8388641
The boiler’s maximum power when the external
controller voltage is at Min Voltage
0 to maximum rated power
0
Maximum Power Volt (kW)
WP_MaxRemote VCapLimit
34
8388642
The boiler’s maximum power when the external
controller voltage is at V for max. cap.
0 to maximum rated power
---
Current Signal 0­10V
AV_Remote010V Cap
4
8388612
Voltage emitted by the external controller in real time
0-10 V
---
Min Voltage (VDC)
WP_CapLimitatM inRemote010V
35
8388628
The voltage representing the external controller’s
minimum set-point
0-10 V
0
Max Voltage (VDC)
WP_CapLimitatM axRemote010V
36
8388629
The voltage representing the external controller’s
maximum set-point
0-10
10
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 46.
T. EXT MODE
Maximum power modulation is based on the outside temperature. Power modulation is shown below.
If the external sensor is not connected or there is a problem with the sensor, then the power will be limited according to Cap. At T. Ext. Min.
Figure 17: Adjustment curve according to the T. ext mode
Display
BACnet Variable
Instance
Tag
Description
Parameters
Default
Current authorized max power (%)
AV_CapLimitPrc
54
8388662
The value of power (%) calculated based on the
current and the boiler’s nominal operating voltage
0 to maximum rated power (%)
---
Cap. At T. Ext. Min
WP_CapLimitatM inOutdT
37
8388645
Maximum authorized capacity according to T. Ext.
Min
Ex. Maximum power is 170 kW for T. Ext min
0 to maximum rated power
---
Cap. At T. Ext. Max
WP_CapLimitatM axOutdT
38
8388646
Maximum authorized capacity according to T. Ext. Max Ex. Maximum power is 120 kW for T. Ext min
0 to maximum rated power
---
Actual T. Exterior
AV_OutdoorT
2
8388610
This variable allows you to view the outside temperature in real time when the outside temperature sensor is properly connected.
-46 to 107 °C
-50 to 250 °F
---
T. Ext. Min
WP_MinOutdTCa pLimit
39
8388647
Minimal outside temperature used to adjust the maximum power
-46 to 107 °C
-50 to 250 °F
-10 F
T. Ext. Max
WP_MaxOutdTC apLimit
40
8388647
Maximum outside temperature used to adjust the maximum power
-46 to 107 °C
-50 to 250 °F
65 F
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 47.
SCHEDULE MODE
Power can be modulated according to a fixed schedule. This can be programmed in the Schedule Setting menu.
Display
BACnet variable
Instance
Tag
Description
Parameters
Default
Current authorized max power (%)
AV_CapLimitPrc
54
8388662
The value of power (%) calculated based on the
current and the boiler’s nominal operating voltage
0 to maximum rated power (%)
---
Cap In Schedule
WP_CapLimitDay Mode
41
8388649
Power limitation when the boiler internal clock is within the power limitation schedule.
0 to maximum rated power
---
Cap Out Schedule
WP_CapLimitNig htMode
42
8388650
Power limitation when the boiler internal clock is outside the power limitation schedule.
0 to maximum rated power
---
Schedule
---
Configuring the boiler power limitation schedule. In order to operate correctly, you must first adjust the internal boiler clock in the Clock Setting menu.
---
---
AUXILIARY BOILER SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
(Only available on SCR model)
The system allows control of an auxiliary boiler to the system. The different configuration options are shown below.
In order for the boiler to start, two conditions must be met: The water outlet temperature of the Voltmax boiler must be below the start-up
temperature Aux.
(T. Out Boiler < (T Set-point - Delta T. Aux Start)
The water outlet temperature of the Voltmax boiler must be below the start-up temperature Aux. for a period of X minutes (Start Delay Aux), after the Voltmax boiler is at 100% of its authorized power.
In order for the auxiliary boiler to turn off, the water outlet temperature of the Voltmax boiler must be above the Aux.
T Out Boiler > (T. Set-point - Delta T. Aux Stop)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 48.
BACKUP MODE
Configures a second boiler as a backup.
Display
BACnet variable
Instance
Tag
Description
Parameters
Default
STPT Source
WP_STPTSource Aux
22
20971542
Selects the source used to control the set-point temperature. Auxiliary means that the set-point will be determined by the auxiliary boiler. The VoltMax boiler therefore has no set-point temperature and is only used to activate the auxiliary boiler relay. Voltmax means that the set-point temperature will be determined by the VoltMax boiler.
Auxiliary or
VoltMax 0 = Auxilliary 1 = VoltMax
VoltMax
Delta T. Start Aux.
WP_DeltaTStartA ux
44
8388652
This option adjusts the temperature differential (set­point temperature – Water outlet temperature) used to activate the auxiliary boiler.
0 to 55 0C 0 to 100 0F
20 0F
Delta T. Stop Aux.
WP_DeltaTStopA ux
45
8388653
This option configures the temperature differential (set-point temperature – Water outlet temperature) in the VoltMax boiler used to deactivate the auxiliary boiler.
0 to 55 0C 0 to 100 0F
5 0F
Delay Start Aux.
WP_DelayStartA ux
46
8388654
This option adjusts the delay before activating the auxiliary boiler.
Min
10
EXTERNAL CONTACT MODE
This mode selects the hydronic system heating source (VoltMax boiler or auxiliary boiler) using the BI-E terminal’s electrical switch.
Display
BACnet Variable
Instance
Tag
Description
Settings
Default
STPT Source
WP_STPTSource Aux
22
20971542
Selects the source used to control the set-point temperature. External means that the set-point will be determined by the auxiliary boiler. The VoltMax boiler therefore has no set-point temperature and is used only to activate the auxiliary boiler’s relay. Internal means that the set-point temperature will be determined by the VoltMax boiler.
External or
internal
Internal
MANUAL MODE
Manual mode is used to select the system’s operating mode (Electric or auxiliary).
Display
BACnet Variable
Instance
Tag
Description
Selection
Default
Active Boiler
WP_ActiveBoiler
23
20971543
This option selects which boiler is in operation; either the VoltMax boiler (electric) or the auxiliary boilder (auxiliary).
VoltMax ou
Auxiliary
0 = VoltMax
VoltMax
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 49.
BI-ENERGY MODE
This mode selects the hydronic system heating source (VoltMax boiler or auxiliary boiler) using the BI-E terminal’s electrical switch. The benefit of this mode is that the system can operate the back-up boiler when needed.
Display
BACnet variable
Instance
Tag
Description
Parameters
Default
Bi-Energy Source
WP_SignalBiEne rgy
47
20971567
Allows to select Bi-energy activation contact source. BACnet or Local
Local BACnet
Local
STPT Source
WP_STPTSource Aux
22
20971542
Selects the source used to control the set-point temperature. Auxiliary means that the set-point will be determined by the auxiliary boiler. The VoltMax boiler has no set-point temperature and is only used to activate the auxiliary boiler relay. Voltmax means that the set-point temperature will be determined by the VoltMax boiler.
Auxiliary or
VoltMax 0 = Auxiliary 1 = VoltMax
VoltMax
Delta T. Start Aux.
WP_DeltaTStartA ux
44
8388652
This option adjusts the temperature differential (Set-point temperature – Water outlet temperature) used to activate the auxiliary boiler.
0 to 55 0C 0 to 100 0F
20 0F
Delta T. Stop Aux.
WP_DeltaTStopA ux
45
8388653
This option configures the temperature differential (Set-point temperature – Water outlet temperature) in the VoltMax boiler used to deactivate the auxiliary boiler.
0 to 55 0C 0 to 100 0F
5 0F
Delay Start Aux.
WP_DelayStartA ux
46
8388654
This option adjusts the delay in minutes before activating the auxiliary boiler.
Min
10
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 50.
LIMIT CONFIGURATION MENU SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
Display
BACnet variable
Instance
Tag
Description
Settings
Default
High Limit T
WP_HighLimitTe mp
47
8388655
Adjusts the temperature high limit at which the alarm triggers. If the water temperature leaving the
boiler exceeds the alarm’s high limit, it will trigger
an HL alarm and the boiler’s heating elements will be deactivated.
0 to 92 °C
0 to 199 °F
195 °F
Low Limit
ON/OFF
WP_Desactivate AlarmLL
31
20971551
Desactivates the low limit detection function (see* below)
0=OFF
1=ON
ON
Delta T. LL*
WP_DeltaTLL
48
8388656
Adjusts the temperature differential to activate the LL alarm.
0 to -55 °C 0 to -99 °F
-20 °F
Delay LL (min)*
WP_DelayLL
49
8388657
Adjusts the LL alarm trigger delay.
0 to 180 min
60 min
Pressure sensor
WP_ActivatePres sureSensor
24
20971544
Activates the boiler’s internal pressure sensor
module.
OFF / ON
0 = Off ; 1 =
On
ON
Actual pressure
AV_SensorPress ureSignal
6
8388614
Reads the boiler’s internal pressure sensor.
---
---
Current sensor
WP_ActivateCurr entSensor
25
20971545
Activates the current sensor module.
This module is available on SCR models only
OFF / ON
0 = Off ; 1 =
On
ON
Calculated current
AV_CalculatedCu rrentSignal
50
8388658
Used to view the VoltMax boiler’s theoretical electric consumption current.
---
---
Actual current
AV_SensorCurre ntSignal
5
8388613
View current as measured by a sensor.
---
---
*The LL (low limit) function aims to identify a potential anomaly of the boiler by detecting a potential lack of power that makes the temperature of the water at the boiler outlet to be anormaly lower than the set temperature during a predefined time period (see section 6.2.3).
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 51.
CONFIG. ALARM MENU SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
Display
BACnet Variable
Instance
Tag
Description
Settings
Default
Occupation mode
WP_Schedule_O n
46
20971566
Allows to select Bi-energy activation contact source. BACnet or Local
Local BACnet
Local
Status: HL/LWCO alarm
BV_StatusExtAlar m
28
20971548
Displays the external alarm status. The external alarm contact is activated only if a high limit or low water level alarm occurs.
0 = Off 1 = On
---
Silence Alarm
WP_SilenceAlar m
27
20971547
Temporarily suspends the alarm.
0 = Off 1 = On
Off
Reset Lockdown
WP_ResetLockD own
29
20971549
Cancels the Lockdown mode without resetting the unit. Resetting the unit is required when it is in LOCK- OUT mode, following high external temperature or low water level alarms over a short period.
0 = Off 1 = On
Off Internal buzzer
WP_ActivateInter nalBuzzer
30
20971550
Activates the controller’s internal buzzer.
0 = Off 1 = On
On
OCCUPATION MENU SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
Display
BACnet Variable
Instance
Tag
Description
Settings
Default
Occupation Mode
WP_ActivateOcc upationMode
33
20971553
Activates the Occupation function.
0 = Off 1 = On
---
Source OCC
WP_SourceOccu pation
34
20971554
Selects the source used to determine the building’s
occupation schedule.
0 = Schedule 1 = Contact OCC
Lowering T.
WP_LoweringTIn noccupation
52
8388660
Lowers the set-point temperature.
---
Off
Occupation Status
BV_StatusOccup ation
35
20971555
Displays the Occupation mode status. Off: Day mode; the set-point temperature is not lowered On: Night mode; the set-point temperature is lowered according to the configuration
0 = Off 1 = On
On Force Day Mode
WP_ForceOccup ationDay
36
20971556
Forces the Day mode. The set-point temperature will not be lowered.
0 = Off ; 1 = On
Off
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 52.
BOOST MENU SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
Display
BACnet Variable
Instance
Tag
Description
Settings
Default
Mode BOOST
WP_ActivateMod eBoost
37
20971557
This option enables the BOOST functionality.
0 = Off 1 = On
Off
WARM WEATHER SHUTDOWN MENU SETTINGS
(Variables beginning with AV and BV are read variables, while variables beginning with "W" are editable)
Display
BACnet Variable
Instance
Tag
Description
Settings
Default
Warm Weather Shutdown
WP_ActivateWar mWeatherSD
26
20971546
Shuts down the boiler when the outside temperature reaches a specific temperature. This temperature can be set in the Warm Weather Shutdown Temperature box.
OFF / ON
0 = Off ; 1 = On
OFF
T. Ext Shutdown WWSD
WP_WarmWeath erSDTemp
51
8388659
Sets the outside temperature that activates the Warm Weather Shutdown, if it shuts down the boiler.
0 to 55 °C 0 to 99 °F
68 °F
Current Ext. T.
AV_OutdoorT
2
8388610
Shows the outside temperature in real time.
-46 to 107 °C
-50 to 250 °F
---
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 53.
BOILER START UP
Before operating this boiler, be sure to read and follow these instructions, as well as the warnings printed in this manual. Failure to do so can result in unsafe operation of the boiler resulting in property damage, bodily injury, or death. Should you have any problems reading, following or difficulty in understanding the instructions in this manual, STOP, and get help from a qualified person. Do not turn on the boiler unless it is filled with water. Do not turn on the boiler if the cold-water supply shut-off valve is closed.
After the boiler, has been plumbed and wired, it is now ready to be set for automatic operation
STARTUP PREPARATION
Remove the lid of the boiler and install the temperature probe which is hanging outside the control pannel with a red label indicating the message “important “. This sensor is used to provide the outpout water temperature to the boiler controller. Therefore, it shall be installed in one of the two immersion wells indicated below. Insert in the immersion well located on the same side of the selected water outpout connection.
Open the service valves at the outlet of the boiler and the cold-water supply valve (fill or makeup water valve) to boiler.
Open the relief valve on top of the boiler in order to purge the air out of the boiler tank during the fill process
Leave all shutoff valves open.
Check system for leaks and repair. Purge air from all the heating distribution zones.
Bleed air from different areas of the heat distribution system.
Check boiler pressure gage reading. The indicated pressure should be lower than the pressure relief valve design rating.
ADJUSTEMENT OF THE CONTROLLER OPERATING PARAMETERS
After the system has been manually purged of air, and all components (valves, vents, and controllers) have been set properly, the boiler can be started.
Never operate this boiler until this has been done.
1) Make sure that there is no heat demand or
startup authorisation on W1 and W2 contactors and that the ON/OFF switch on the left side of the panel is at OFF.
2) Turn on the boiler alimentation circuit and the
disconnect switch (option).
3) Turn on the boiler ON/OFF switch. You
should hear the mains contactors engaging and see the controller screen turn on. The heating elements shall not come on as long as there is no W1 or W2 heat demand.
4) Enter the appropriate parameters in the
controller to obtain a proper operation of the heating system on wich to boiler is installed.
The acces the menu, press “OK”, then select “BOILER SETTING” and entre the password “1111”. Consult section four of this manual to
adjust the paramaters.
5) Make sure that the high limit parameters of
the boiler are set at the appropriate values for the application.
6) The high limit adjustment is possible trough
the “LIMIT setting” menu and should be
adjusted 10 to 15°F above the maximum
WARNING
!
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 54.
operation temperature selected. Proceed to the adjustment of the mechanical high limit control localized on the right in the low voltage electric compartiment. It shall be adjusted 10 to 15F higher than the controller high limit.
STARTUP PROCEDURE
Before starting the boiler, make sure that the heating distribution design is made so that the heating elements will come on only when water is circulating in the boiler.
1) Apply a heat demand. If the boiler target temperature is higher than the boiler water temperature, the heating elements shall come on in sequence more or less rapidly depending on the differential between the values. If the value indicated is “--- it is because the authorization or start up signal is not established.
2) When the boiler capacity has reached 100% as displayed on the controller, measure the amperage and voltage values drawn by the unit. These values shall be close to those shown on the boiler name plate.
3) Slow down the heat demand from the heating system. The boiler temperature shall gradually increase and the boiler capacity shall drop gradually and stabilize when the boiler temperature will reach a temperature near the target temperature.
4) When the heating request is completed, the circulating pump can continue to operate (depending on the operating mode or the purge time) or switch off. The heating elements stop working.
5) Check the operation of the adjustable high­limit mechanical control
6) Check the operation of the Low Water Cut OFF by pressing its test button during 5 sec. The button is located on the left side of the control panel
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 55.
TROUBLESHOOTING
The troubleshooting section shows the various error messages that can occur during abnormal operation of the boiler. It is possible to change the limits of some alarms on the controller in the
Limit Setting. Alarm menue Symbols
An alarm is active
The boiler is in lock mode
HL
The high limit temperature has been reached
LL
Low limit (Lack of capacity)
P
Pressure problem alarm
A
Electrical problem alarm
F
Flow problem alarm
Se
Sensor problem alarm
The internal clock battery level is low
WARNING LIGHTS
The LEDs above the navigation buttons indicate 3 different boiler states.
Active
warning
light
Boiler status
Green
Normal operation of the boiler
Yellow
One or more alarms are active. These alarms do not prevent the operation of the boiler; the boiler continues to operate in normal mode. Ex. The controller detects a problem with the amperage reading sensor.
Red
A critical alarm is active, accompanied by the buzzer (if active). Ex. A high limit alarm is active
OPERATING PROBLEM
IDENTIFICATION
An alarm log is available in the BOILER CONFIG / ALARM / ALARM LOG. Each alarm is recorded
with its alarm code, the time and date. The register can record up to 30 alarms.
EXTERNAL HL / LWCO
When this alarm is present, the indicator light to the left of the boiler lights red.
This alarm happens when one of the following contacts is open: the adjustable mechanical high limit, the manual reset high limit located in the heating elements compartiment, a low level of
water or an external contact connected to “EXT. HL” terminals.
The external alarm contact (SCR models only) will be activated immediately if it has been activated (Ext. Alarm Contact) in the Alarm menu. The heating elements will stop working and will start again when the water level or the other condition returns to normal. If this alarm happens 3 times in 1 hour or for 60 consecutives minutes, the boiler will be set in Lock out mode.
SENSOR (SE)
The Sensor alarm indicates that a courant, pressure or temperature sensor is defective. This alarm will also be triggered if the external temperature is not connected and an operating condition require this sensor. Generaly the alarm is coupled with the lettes A, P and F wich indicates the defective sensor. This condition does not turn off the boiler (except in the case of a defective water outlet temperature sensor). The yellow indicator light stays on as long as the alarm condition is active.
See Table 13 for comparison of Resistance measurements against temperature for the outdoor sensor.
LOW LIMIT (LL)
The LL alarm is activated when the temperature differential between the set-point temperature and the boiler output temperature is higher than
Delta T.LL and this period is higher than the LL delay.
The heating elements remain in operation. The screen will automatically return to its normal state when the temperature of the boiler approaches the set temperature.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 56.
This function can detect a possible lack of power from the boiler and therefore possible anomalies of certain componants. This function is generaly not activated when the power limitation function of the boiler is activated.
FLOW (F)
(Available only on SCR model)
The flow alarm is triggered when the theoretical flow calculated from the water input and output temperature differential (max.50F) is above the authorized flow limit. This condition triggered by a lack of flow does not turn off the boiler but activates a yellow indicator light as long as the condition is active.
CURRENT (A)
The Current alarm is triggered when there is a difference of more than 20% between the measured current and the calculated theoretical current. This may indicate an electrical problem from a wrong connection. This condition triggered by a lack of flow does not turn off the boiler but activates a yellow indicator light as long as the condition is active. If more than 50% of the stages are detected as defective, the alarm will then shut down the boiler and the red light will light up.
HL TEMPERATURE (HL)
The outlet temperature of the boiler is above the high limit allowed. This alarm triggers the deactivation of the heating elements of the boiler. The boiler is restarted when the temperature drops below the high limit (and the set-point) If the boiler is in this alarm state for more than 60 minutes or the condition occurs 3 times in an hour, the boiler switches to Lock Out mode.
LOW PRESSURE (P)
The Low-Pressure alarm P is activated when the pressure inside the boiler is below the allowed limit (default: 5 psi).
This condition triggered by a lack of flow does not turn off the boiler but activates a yellow indicator light as long as the condition is active.
HIGH PRESSURE (P)
The High-Pressure alarm is activated when the pressure inside the boiler is above the allowed limit (depending on the maximum boiler pressure)
BATTERY LOW LEVEL
The low-level battery alarm appears when the battery used by the internal clock is at a low level. The battery needs to be replaced. To get the replacement procedure, contact our technical service.
LOCK OUT
Lock out mode is activated after 3 major alarms (red indicator light) have been activated within one hour or when a major alarm (high limit output water temperature detected by the external temperature sensor or low water level condition) is maintained activated during the same time period. When the lock mode is activated, the boiler is deactivated and can only be restarted by restarting the boiler (to the left of the control panel) or by using the reset Lock Out function (in the alarm setting menu). The details of this menu can be found in section 4.12.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 57.
Tableau 12 : Resistance (Ohm) according to the outdoor sensor measuring temperature
Temperature
Resistance
Temperature
Resistance
Temperature
Resistance
Temperature
Resistance
°F
°C Ω °F
°C Ω °F
°C Ω °F
°C
-50
-46
490 813
20
-7
46 218
90
32
7 334
160
71
1 689
-45
-43
405 710
25
-4
39 913
95
35
6 532
165
74
1 538
-40
-40
336 606
30
-1
34 558
100
38
5 828
170
77
1 403
-35
-37
280 279
35 2 29 996
105
41
5 210
175
79
1 281
-30
-34
234 196
40 4 26 099
110
43
4 665
180
82
1 172
-25
-32
196 358
45 7 22 763
115
46
4 184
185
85
1 073
-20
-29
165 180
50
10
19 900
120
49
3 760
190
88
983
-15
-26
139 402
55
13
17 436
125
52
3 383
195
91
903
-10
-23
118 018
60
16
15 311
130
54
3 050
200
93
829
-5
-21
100 221
65
18
13 474
135
57
2 754
205
96
763
0
-18
85 362
70
21
11 883
140
60
2 490
210
99
703
5
-15
72 918
75
24
10 501
145
63
2 255
215
102
648
10
-12
62 465
80
27
9 299
150
66
2 045
220
104
598
15
-9
53 658
85
29
8 250
155
68
1 857
225
107
553
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 58.
FUSES
Delay fuses with the same capacity and voltage must be used when remplacing all of the boiler fuses except for the power fuses that are “fast acting” type T.
CONTACTOR
If one or more contactor must be replaced, make sure that the terminal screws are well tightened to avoid an overcharge. The required torque is indicated on the contactor label. A verification of the screw torque should be made annually particuliary on the first years of service.
HEATING ELEMENTS
If a heating element must be replaced, make sure that the replacement has identical power and voltage as the old one. The model number and technical caracteristics are indicated on the side of the mounting flange of the element. The sealing gasket must also be replaced by an identical model as the one procured by Thermo
2000. The torque for the bolts retaining the flange should be 6lb.ft. If the elements have been in contact with water or a very humid environnement, dry then completely before putting then under voltage. Verify the state of the electrical isolation of the element and the ground with a “Megger” test. If elements are blown at their extrimites, make sure there is no sediment deposits in the tank befor installing new elements. If deposites are present. A Sieve or other accessorie preventing sediment deposits shall be installed.
TEMPERATURE SENSOR
Water outlet sensor:
The sensor is located in an immersion well located in the heating elements compartiment on
the top of the boiler (illustration 5.1) and the resistance vs temperature value is indicated in table 12 above.
Water intake sensor (on SCR models only): The sensor is located in an immersion well in the back and at the bottom of the boiler. To acces it, remove the plastic plug located right above the drain valve.
EXTERNAL HIGH LIMIT CONTROL
Fix high limit control with manual arming
It is located in the heating elements compartiment and fixed in place by a metal plate fixed to one of the element’s flange. During the installation one must make sure that the surface of contact is clean and that the control is firmly locked in place.
Adjustable high limit automatic control
It is located on the right in the control compartiment of the boiler. It must always be adjusted at 10°F above the high limit temperature indicated in the operation parameter of the controller.
INTERNAL CLOCK
If the internal clock is used and it does not keep its reading (goes back de 0:00), the battery on the electronic controller needs to be changed. Contact thermo 2000 technical support for the battery replacement procedure.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 59.
MAINTENANCE
Properly maintained, your boiler will provide years of dependable, trouble free service. It is recommended that a regular routine maintenance program be established and followed by the user. Components are subject to eventual failure that requires service. Failure to use the correct procedures or parts in these circumstances may make the unit unsafe or reduce the life of the boiler.
The owner should have the following inspection and maintenance procedures performed:
BOILER WATER PIPING
VISUAL INSPECTION
Check all piping for signs of leakage near joints, unions and shut-off valves. Repair without delai to avoid new water to enter the closed circuit and cause corrosion.
PRESSURE RELIEF VALVE
TWICE A YEAR
Check for possible leak at the outlet of the safety relief valve. If a leak is detected and the pressure at the indicator is less than 28psi, change the safety relief valve with a new one having similar characteristics. If the pressure is higher than 28psi, ask your heating service agency to determine the cause of the high pressure and have it corrected rapidly. Do not plug the outlet of this valve if a dripping condition occurs.
AIR PURGE
TWICE A YEAR
Check for proper operation of the automatic air purgers and activate manual air vents to eliminate air present.
ELECTRICAL INSPECTION
ANNUALLY
It is recommended to perform a visual inspection of the boiler electric compartment annually, during the heating season, to ensure it is watertight and that there are no signs of component or wiring overheating. Repair as soon as possible if necessary. Defective components should always be replaced with the Original Manufacturer’s parts.
The inspection should also include a verification of the torque of all the terminals screws and particuliary the power contactors. The inspection should follow with a verification of the main temperature controls in operation as well as an amperage and voltage reading to verify the proper operation of all the heating elements.
The manufacturer's warranty DOES NOT cover a tank breakage caused by improper installation or maintenance. If the boiler safety valve opens periodically, this may be caused by the expansion tank.
Immediately call a qualified technician to inspect and remedy the problem.
NOTE: To prevent premature tank failure, the air trapped inside the system must be purged periodically.
Before manually operating the relief valve, make certain no one will be sprayed with the hot water released by its opening. The water may be hot enough to create a SCALD hazard. The water released should be directed to a suitable drain to prevent injury or damage.
DANGER
!
WARNING
!
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised March 2019), Page 60.
VoltMax LIMITED WARRANTY
Warranty Coverage for residential Installation
Thermo 2000 Inc. hereby warrants that the VoltMax tank installed in a normal residential service shall be exempt of any leak for ten (10) years from the purchase date. The warranty is effective as long as the original residential purchaser owns the home in wich the unit was originaly installed. Residential setting shall mean usage in a single-family dwelling in which the consumer resides on a permanent basis. Also, residential setting shall mean use in multiple family dwellings in which one (1) VoltMax boiler is to be use in only one (1) dwelling. In the event that a leak should develop and occur within this limited warranty period due to defective material or workmanship, such leak having been verified by an authorized company representative, Thermo 2000 Inc. will repair or replace at our sole option the failed unit with the nearest comparable model at the time of replacement.
The residential owner is responsible for all costs associated with the removal and reinstallation, shipping and handling to and from Manufacturer. The replacement unit will be warranted for the remaining portion of the original Warranty.
Warranty Coverage for Commercial Installation
Thermo 2000 Inc. warrants to the original purchaser that the VoltMax tank installed in a commercial setting shall be exempt of any leak for ten (10) years from the purchase date. Commercial setting shall mean use in other than residential setting stated above in the residential setting definition. In the event that a leak should develop and occur within this limited warranty period due to defective material or workmanship, such leak having been verified by an authorized company representative, Thermo 2000 Inc. will repair or replace at our sole option the failed unit with the nearest comparable model at the time of replacement.
The original purchaser is responsible for all costs associated with the removal and reinstallation, shipping and handling to and from Manufacturer. The replacement unit will be warranted for the remaining portion of the original Warranty.
Limited two-year warranty on all VoltMax components & parts
All other VoltMax components & parts are warranted for a period of two (2) years against defects due to defective material or workmanship. The original purchaser is responsible for all costs associated with the removal and reinstallation, shipping and handling to and from Manufacturer. The components, repaired or replaced are warranted for the residual period of the initial warranty on the unit.
Limitations
Thermo 2000 shall not be responsible for any damage, loss, and inconvenience of any nature whatsoever, directly or indirectly, relating to the breakdown or malfunction of the unit. This warranty limits its beneficiary’s rights. Nevertheless, the beneficiary may have other rights, which vary from state to state.
This warranty replaces any other expressed or implicit warranty and constitutes the sole obligation of Thermo 2000 towards the consumer. The warranty does not cover cost of removal, reinstallation or shipping to repair or replace the unit, nor administration fees incurred by the original consumer purchaser.
Thermo 2000 reserves its rights to make changes in the details of design, construction, or material, as shall in its judgment constitute an improvement of former practices.
This warranty is valid only for installations made within the territorial limits of Canada and the United States.
Warranty service procedure
Only authorized VoltMax retailers may handle warranty claims. The owner or contractor must provide the defective equipment or components to Thermo 2000 with the following details: the model, the serial number, a copy of the original invoice and the owner identification certificate.
Exclusions
This warranty is void and shall not apply if:
A) Defects or malfunctions resulting from installation, repair,
maintenance and/or usage that are not done in conformity with the manufacturer’s installation manual; or
B) Defects or malfunctions resulting from installation, maintenance, or
repair that are not done in accordance with regulations in force; or
C) Defects or malfunctions resulting from improper installation,
maintenance or repair done carelessly or resulting from consumer damage (improper maintenance, misuse, abuse, accident or alteration); or
D) Installation in which a relief valve (pressure) is not installed or if it is
not functioning properly, or when it is not connected to a drain to avoid damage to the property; or
E) Installation in which liquid circulating in the tank does not remain in
closed circuit or installation in which piping is leaking; or
F) A polybutylene pipe or radiant panel installation without an oxygen
absorption barrier is used; or
G) Installation where the acidity of water is not within the normal
Environmental Protection Agency (EPA) (between pH 6.5 – 8.5) guidelines or the water contains abnormal levels of particulate matter or water exceeding 10.5 gpg; or
H) Element failure due to low water level, sediment accumulation in the
tank or by anormally high deposits at the surface of the elements; or
I) The VoltMax unit is being subject to non-authorized modifications; or J) Defects or malfunction resulting of storing or handling done elsewhere
than Thermo 2000’s manufacturing plant; or
K) Units on which the serial number is removed or obliterated.
THERMO 2OOO INC.
500, 9
ième
Avenue, Richmond (Qc) Canada J0B 2H0
Tel: (819) 826-5613 Fax: (819) 826-6370
www.thermo2000.com
Loading...