THERMO 2000 VOLTMAX 45, VOLTMAX 30, VOLTMAX 36, VOLTMAX 41, VOLTMAX 50 Installation And Operation Manual

...
VOLTMAX Electric Boiler
Model: 22.5 kW to 180 kW:
208/240 Volts (single-phase) and
208/240/480
INSTALLATION AND OPERATION MANUAL
mo
Your
VOLTMAX Electric Boiler was carefully assembled and checked at the factory to ensure its pro
per
functioning for many years.
The following information and safety measures are provided to
enable
proper installation, operation, and maintenance of this product.
It is imperative that all persons who are expected to install, operate or adjust this boi
ler
should read
these instructions carefully.
Any questions regarding the operation, maintenance, service or warranty of this electric boiler should be directed to the supplier.
When all installation steps have been completed, keep this installation manu
al in a safe place (near
the
boiler) for future reference.
THERMO 2000 INC.
Printed in Canada
Revised: May 2017
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 2.
TABLE OF CONTENTS
SECTION 1 : TECHNICAL SPECIFICATIONS ............................................................................... 4
SECTION 2 : INTRODUCTION ....................................................................................................... 9
2.1 LOCAL INSTALLATION REGULATIONS ............................................................................. 9
2.2 CORROSIVE ENVIRONMENT.............................................................................................. 9
2.3 INSPECTION UPON RECEPTION ....................................................................................... 9
2.4 TO BE CHECKED ................................................................................................................. 9
SECTION 3 : INSTALLATION....................................................................................................... 10
3.1 SAFETY MEASURES .......................................................................................................... 10
3.2 LOCATION........................................................................................................................... 10
3.3 CLEARANCES .................................................................................................................... 10
3.4 PIPING INSTALLATION ...................................................................................................... 10
3.4.2 Drain faucet .................................................................................................................. 13
3.4.3 Pressure loss ................................................................................................................ 14
3.5 ELECTRICAL CONNECTIONS ........................................................................................... 20
3.5.1 Main electrical supply ................................................................................................... 20
3.5.2 Pump supply ................................................................................................................. 20
3.5.3 Connection of external signals to the controller ........................................................... 20
SECTION 4 : CONTROLLER OPERATION ................................................................................. 34
4.1 USER INTERFACE ............................................................................................................. 34
4.1.1 Symbol description ....................................................................................................... 34
4.1.2 Control panel ................................................................................................................ 35
4.1.3 Navigation and adjustements ....................................................................................... 35
4.1.4 Main menu navigation .................................................................................................. 36
4.1.5 Navigation in boiler setting ........................................................................................... 37
4.2 MAIN MENU ........................................................................................................................ 39
4.2.1 Boiler status .................................................................................................................. 39
4.2.2 Boiler configuration ....................................................................................................... 39
4.2.3 User setting .................................................................................................................. 39
4.2.4 Clock setting ................................................................................................................. 40
4.2.5 Consumption ................................................................................................................ 40
4.3 BOILER SETTINGS ............................................................................................................. 40
4.3.1 Heating mode W1 ......................................................................................................... 41
4.3.2 Heating mode W2/DHW ............................................................................................... 41
4.3.3 Pump setting................................................................................................................. 41
4.3.4 Capacity limiting ........................................................................................................... 42
4.3.5 Auxiliary boiler .............................................................................................................. 42
4.3.6 Limit setting .................................................................................................................. 43
4.3.7 Alarm ............................................................................................................................ 44
4.3.8 Communication............................................................................................................. 44
4.3.9 Occupation ................................................................................................................... 45
4.3.10 BOOST Mode ............................................................................................................. 46
4.3.11 Warm weather shutdown ............................................................................................ 46
4.3.12 Change password ...................................................................................................... 46
4.4 INTERNET ........................................................................................................................... 46
4.4.1 Website ......................................................................................................................... 47
4.4.2 Email ............................................................................................................................. 47
4.5 BOILER STATUS DISPLAY SETTINGS ............................................................................. 48
4.6 HEATING MODE W1 SETTINGS ....................................................................................... 50
4.6.1 FIXED MODE ............................................................................................................... 50
4.6.2 OUTDOOR RESET MODE .......................................................................................... 51
4.6.3 Mode : DDC 0-10VDC .................................................................................................. 52
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 3.
4.7 W2 MODE SET-POINT TEMPERATURE SETTINGS ........................................................ 53
4.7.1 W2 MODE .................................................................................................................... 53
4.7.2 DHW MODE ................................................................................................................. 53
4.8 PUMP CONFIGURATION MENU SETTINGS .................................................................... 53
4.8.1 PUMP 1 ........................................................................................................................ 53
4.8.2 PUMP 2 ........................................................................................................................ 53
SPECIFIC PARAMETERS FOR THE CAPACITY LIMITING MENU .................................... 54
4.8.3 MANUAL MODE ........................................................................................................... 54
4.8.4 MODE: 0-10 VDC ......................................................................................................... 54
4.9 POWER LIMITATION MENU SETTINGS ........................................................................... 55
4.9.1 MANUAL MODE ........................................................................................................... 55
4.9.2 0-10 VDC MODE .......................................................................................................... 55
4.9.3 T. ext MODE ................................................................................................................. 56
4.9.4 Schedule MODE ........................................................................................................... 57
4.10 AUXILIARY BOILER SETTINGS ....................................................................................... 58
4.10.1 BACKUP MODE ......................................................................................................... 58
4.10.2 EXTERNAL CONTACT MODE .................................................................................. 59
4.10.3 ManuAl MODE ........................................................................................................... 59
4.10.4 Bi-Energy MODE ........................................................................................................ 60
4.11 LIMIT CONFIGURATION MENU SETTINGS .................................................................... 61
4.12 CONFIG. ALARM MENU SETTINGS ................................................................................ 62
4.13 OCCUPATION MENU SETTINGS .................................................................................... 62
4.14 BOOST MENU SETTINGS................................................................................................ 63
4.15 WARM WEATHER SHUTDOWN MENU SETTINGS ....................................................... 63
SECTION 5 : BOILER START UP ................................................................................................ 64
5.1 FILLING THE BOILER ......................................................................................................... 64
5.2 ADJUSTEMENT OF THE CONTROLLER OPERATING PARAMETERS .......................... 64
5.3 STARTUP PROCEDURE .................................................................................................... 64
SECTION 6 : TROUBLESHOOTING ............................................................................................ 66
6.1 WARNING LIGHTS ............................................................................................................. 66
6.2 OPERATING PROBLEM IDENTIFICATION ....................................................................... 66
6.2.1 External HL / LWCO ............................................................................................... 66
6.2.2 Sensor ( SE ) .......................................................................................................... 66
6.2.3 Low limit ( LL ) ........................................................................................................ 66
6.2.4 Flow ( F ) ................................................................................................................ 66
6.2.5 Current ( A ) ............................................................................................................ 66
6.2.6 HL temperature ( HL ) ............................................................................................ 67
6.2.7 Low pressure ( P ) .................................................................................................. 67
6.2.8 High pressure ( P ) ................................................................................................. 67
6.2.9 Lock out .................................................................................................................. 67
SECTION 7 : MAINTENANCE ...................................................................................................... 68
7.1 BOILER WATER PIPING .................................................................................................... 68
7.2 PRESSURE RELIEF VALVE ............................................................................................... 68
7.3 AIR PURGE ......................................................................................................................... 68
7.4 ELECTRICAL INSPECTION................................................................................................ 68
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 4.
SECTION 1 : TECHNICAL SPECIFICATIONS
Table 1: VOLTMAX 208 VAC / 60 Hz / Single-Phase1
Capacity
STG
Series
SCR Series
Model
kW
BTU/h
Amp
s
Electrical
element(s) 240 V
Stage Relay
Stage Relay
SCR
Stage
VOLTMAX 23
22,5
76 770
108,4
6 x 5 kW
3 x 7,5 kW
2 x 7,5 kW
1 x 7,5 kW
VOLTMAX 27
27
92 124
130,1
6 x 6 kW
3 x 9 kW
2 x 9 kW
1 x 9 kW
VOLTMAX 30
30
102 360
144,5
8 x 5 kW
4 x 7,5 kW
3 x 7,5 kW
1 x 7,5 kW
VOLTMAX 36
36
122 832
173,4
8 x 6 kW
4 x 9 kW
3 x 9 kW
1 x 9 kW
VOLTMAX 41
41
139 892
198,7
5 x 5 kW + 5 x 6 kW
5 x 8,25 kW
4 x 8,25 kW
1 x 8,25 kW
VOLTMAX 45
45
153 540
216,8
10 x 6 kW
5 x 9 kW
4 x 9 kW
1 x 9 kW
VOLTMAX 50
49,5
168 894
238,4
6 x 5 kW + 6 x 6 kW
6 x 8,25 kW
5 x 8,25 kW
1 x 8,25 kW
VOLTMAX 54
54
184 248
260,1
12 x 6 kW
6 x 9 kW
5 x 9 kW
1 x 9 kW
1
Electrical supply 208 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
Table 2: VOLTMAX 240 VAC / 60 Hz / 1 Phase1
Capacity
STG
Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s) 240 V
Stage Relay
Stage Relay
SCR
Stage
VOLTMAX 30
30
102 360
125
6 x 5 kW
3 x 10 kW
2 x 10 kW
1 x 10 kW
VOLTMAX 36
36
122 832
150
6 x 6 kW
3 x 12 kW
2 x 12 kW
1 x 12 kW
VOLTMAX 40
40
136 480
166,7
8 x 5 kW
4 x 10 kW
3 x 10 kW
1 x 10 kW
VOLTMAX 48
48
163 776
200
8 x 6 kW
4 x 12 kW
3 x 12 kW
1 x 12 kW
VOLTMAX 55
55
187 660
229,2
5 x 5 kW + 5 x 6 kW
5 x 11 kW
4 x 11 kW
1 x 11 kW
VOLTMAX 60
60
204 720
250
10 x 6 kW
5 x 12 kW
4 x 12 kW
1 x 12 kW
VOLTMAX 66
66
225 192
275
6 x 5 kW + 6 x 6 kW
6 x 11 kW
5 x 11 kW
1 x 11 kW
VOLTMAX 72
72
245 664
300
12 x 6 kW
6 x 12 kW
5 x 12 kW
1 x 12 kW
1
Electrical supply 240 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
Table 3 : VOLTMAX 208 VAC / 60 Hz / 1 Phase1
Puissance
STG
Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s) 240 V
Stage Relay
Stage Relay
SCR
Stage
VOLTMAX 30
30
102 360
125
6 x 5 kW
3 x 10 kW
2 x 10 kW
1 x 10 kW
VOLTMAX 36
36
122 832
150
6 x 6 kW
3 x 12 kW
2 x 12 kW
1 x 12 kW
VOLTMAX 40
40
136 480
166,7
8 x 5 kW
4 x 10 kW
3 x 10 kW
1 x 10 kW
VOLTMAX 48
48
163 776
200
8 x 6 kW
4 x 12 kW
3 x 12 kW
1 x 12 kW
VOLTMAX 55
55
187 660
229,2
5 x 5 kW + 5 x 6 kW
5 x 11 kW
4 x 11 kW
1 x 11 kW
VOLTMAX 60
60
204 720
250
10 x 6 kW
5 x 12 kW
4 x 12 kW
1 x 12 kW
VOLTMAX 66
66
225 192
275
6 x 5 kW + 6 x 6 kW
6 x 11 kW
5 x 11 kW
1 x 11 kW
VOLTMAX 72
72
245 664
300
12 x 6 kW
6 x 12 kW
5 x 12 kW
1 x 12 kW
1
Electrical supply 208 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 5.
Table 4 : VOLTMAX 240 VAC / 60 Hz / 3 Phases
1
Capacity
STG
Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s) 240 V
Stage Relay
Model kW
VOLTMAX 30
30
102 360
72
6 x 5 kW
2 x 15 kW
1 x 15 kW
1 x 15 kW
VOLTMAX 36
36
122 832
86,6
6 x 6 kW
2 x 18 kW
1 x 18 kW
1 x 18 kW
VOLTMAX 45
45
153 540
108,3
9 x 5 kW
3 x 15 kW
2 x 15 kW
1 x 15 kW
VOLTMAX 54
54
184 248
129,9
9 x 6 kW
3 x 18 kW
2 x 18 kW
1 x 18 kW
VOLTMAX 60
60
204 720
144,3
12 x 5 kW
4 x 15 kW
3 x 15 kW
1 x 15 kW
VOLTMAX 72
72
245 664
173,2
12 x 6 kW
4 x 18 kW
3 x 18 kW
1 x 18 kW
VOLTMAX 75
75
255 900
180,4
15 x 5 kW
5 x 15 kW
4 x 15 kW
1 x 15 kW
1
Electrical supply 240 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
Table 5 : VOLTMAX 480 VAC / 60 Hz / 3 Phases
1
Capacity
STG Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s)
240 V
Stage Relay
Model
kW
VOLTMAX 30
30
102 360
36,1
6 x 5 kW
2 x 15 kW
1 x 15 kW
1 x 15 kW
VOLTMAX 36
36
122 832
43,3
6 x 6 kW
2 x 18 kW
1 x 18 kW
1 x 18 kW
VOLTMAX 45
45
153 540
54,1
9 x 5 kW
3 x 15 kW
2 x 15 kW
1 x 15 kW
VOLTMAX 54
54
184 248
65
9 x 6 kW
3 x 18 kW
2 x 18 kW
1 x 18 kW
VOLTMAX 60
60
204 720
72,2
12 x 5 kW
4 x 15 kW
3 x 15 kW
1 x 18 kW
VOLTMAX 72
72
245 664
86,6
12 x 6 kW
4 x 18 kW
3 x 18 kW
1 x 18 kW
VOLTMAX 75
75
255 900
90,2
15 x 5 kW
5 x 15 kW
4 x 15 kW
1 x 15 kW
VOLTMAX 90
90
307 80
108,3
15 x 6 kW
5 x 18 kW
4 x 18 kW
1 x 18 kW
VOLTMAX 99
99
337 788
119,1
9 x 5 kW + 9 x 6 kW
3 x 33 kW
2 x 33 kW
1 x 33 kW
VOLTMAX 108
108
368 496
129,9
18 x 6 kW
3 x 36 kW
2 x 36 kW
1 x 36 kW
VOLTMAX 120
120
409 440
144,3
24 x 5 kW
4 x 30 kW
3 x 30 kW
1 x 30 kW
VOLTMAX 132
132
450 384
158,8
12 x 5 kW + 12 x 6 kW
4 x 33 kW
3 x 33 kW
1 x 33 kW
VOLTMAX 144
144
491 328
173,2
24 x 6 kW
4 x 36 kW
3 x 36 kW
1 x 36 kW
VOLTMAX 150
150
511 800
180,4
30 x 5 kW
5 x 30 kW
4 x 30 kW
1 x 30 kW
VOLTMAX 165
165
562 980
198,5
15 x 5 kW + 15 x 6 kW
5 x 33 kW
4 x 33 kW
1 x 33 kW
VOLTMAX 180
180
614 160
216,5
30 x 6 kW
5 x 36 kW
4 x 36 kW
1 x 36 kW
1
Electrical supply 480 V - 1 phase (L1-L2-L3) with 3 conductors 90°C with a ground.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 6.
Table 6 : VOLTMAX 600 VAC / 60 Hz / 3 Phases1
Capacity
STG Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s)
240 V
Stage Relay
Model
kW
VOLTMAX 30
30
102 360
28,9
6 x 5 kW
2 x 15 kW
1 x 15 kW
1 x 15 kW
VOLTMAX 36
36
122 832
34,6
6 x 6 kW
2 x 18 kW
1 x 18 kW
1 x 18 kW
VOLTMAX 45
45
153 540
43,3
9 x 5 kW
3 x 15 kW
2 x 15 kW
1 x 15 kW
VOLTMAX 54
54
184 248
52
9 x 6 kW
3 x 18 kW
2 x 18 kW
1 x 18 kW
VOLTMAX 60
60
204 720
57,7
12 x 5 kW
4 x 15 kW
3 x 15 kW
1 x 18 kW
VOLTMAX 72
72
245 664
69,3
12 x 6 kW
4 x 18 kW
3 x 18 kW
1 x 18 kW
VOLTMAX 75
75
255 900
72,2
15 x 5 kW
5 x 15 kW
4 x 15 kW
1 x 15 kW
VOLTMAX 90
90
307 80
86,6
15 x 6 kW
5 x 18 kW
4 x 18 kW
1 x 18 kW
VOLTMAX 99
99
337 788
95,3
9 x 5 kW +
9 x 6 kW
3 x 33 kW
2 x 33 kW
1 x 33 kW
VOLTMAX 108
108
368 496
103,9
18 x 6 kW
3 x 36 kW
2 x 36 kW
1 x 36 kW
VOLTMAX 120
120
409 440
115,5
24 x 5 kW
4 x 30 kW
3 x 30 kW
1 x 30 kW
VOLTMAX 132
132
450 384
127
12 x 5 kW +
12 x 6 kW
4 x 33 kW
3 x 33 kW
1 x 33 kW
VOLTMAX 144
144
491 328
138,6
24 x 6 kW
4 x 36 kW
3 x 36 kW
1 x 36 kW
VOLTMAX 150
150
511 800
144,3
30 x 5 kW
5 x 30 kW
4 x 30 kW
1 x 30 kW
VOLTMAX 165
165
562 980
158,8
15 x 5 kW +
15 x 6 kW
5 x 33 kW
4 x 33 kW
1 x 33 kW
VOLTMAX 180
180
614 160
173,2
30 x 6 kW
5 x 36 kW
4 x 36 kW
1 x 36 kW
1
Electrical supply 600 V - 1 phase (L1-L2-L3) with 3 conductors 90°C with a ground.
Tableau 7 : Maximal service pressure
VOLTMAX
90 kW and less
More than 90 kW
Maximum operating pressure
30 PSI
60 PSI
Optional maximum operating pressure
70 PSI*
125 PSI
* Model from 23 to 90 kW are available at a maximum operating pressure of 125 PSI, but size of the unit will be the same as model of more than 90 kW.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 7.
BOILER DIMENSIONS AND CHARACTERISTIC: MODELS 90KW OR LESS
* Return sensor available with the " SCR SERIES " configuration. ** Optional disconnect switch available on " THREE-PHASE " models. *** Solid state SCR relay available with the " SCR SERIES " configuration. **** Low water cut-off is optional.
BOILER CONNECTIONS
1
Boiler outlet
1 1/2" NPT M
2
Boiler inlet
1 1/2" NPT M
3
Pressure relief valve
3/4" NPT F
4
Drain valve
3/4" NPT F
5*
Access to the return sensor
1/2" NPT F
MIN. CLEARANCES FOR INSTALLATION &
MAINTENANCE
Left and Right sides
3"/ 76mm
Rear
3"/ 76mm
Front
24" / 610mm
Bottom
0" / 0mm
Top
32" / 813mm
GENERAL INFORMATIONS
Weight
310lbs / 141kg
Water Volume
11 Us gal. / 41.6 liters
Max. operating
pressure
STANDARD: 30psi
OPTION: 70 PSI *
*Available at 125PSI (See Shop Drawing 99-180KW)
COMPONENTS IDENTIFICATION
A
Electrical main supply
B
Boiler controller
C
"On/Off" switch
D**
Disconnect switch & rotary handle
E
Fuses for controls
F***
Solid state SCR relay
G****
Low water cut-off, test button and indicator lights
H
Electrical control access door
I
Door handle for electric access with lock
J
Electrical control wires access holes
K
Access door power circuit
L
Access cover to Heating elements
M
Heating elements
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 8.
BOILER DIMENSIONS AND CHARACTERISTIC: MODELS 90KW TO 180KW
* Return sensor available with the " SCR Series " configuration. ** Optional disconnect switch available on " THREE-PHASE" models. *** Solid state SCR relay available with the " SCR Series " configuration. **** Low water cut-off is standard for models more than 117kw.
BOILER CONNECTIONS
1
Boiler outlet
1 1/2" NPT M
2
Boiler inlet
1 1/2" NPT M
3
Pressure relief valve
3/4" NPT F
4
Drain valve
3/4" NPT F
5*
Access to the return sensor
1/2" NPT F
MIN. CLEARANCES FOR INSTALLATION &
MAINTENANCE
Left and Right sides
3"/ 76mm
Rear
3"/ 76mm
Front
24" / 610mm
Bottom
0" / 0mm
Top
32" / 813mm
GENERAL INFORMATIONS
Weight
550lbs / 250kg
Water Volume
30 gal. Us/ 113.5 liters
Max. operating
pressure
STANDARD: 60psi
OPTION: 125 PSI
COMPONENTS IDENTIFICATION
A
Electrical main supply
B
Boiler controller
C
"On/Off" switch
D**
Disconnect switch & rotary handle
E
Fuses for controls
F***
Solid state SCR relay
G****
Low water cut-off, test button and indicator lights
H
Electrical control access door
I
Door handle for electric access with lock
J
Electrical control wires access holes
K
Access door power circuit
L
Access cover to Heating elements
M
Heating elements
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 9.
General Safety Precautions
Be sure to read and understand the entire Installation & operation manual before attempting to install or to operate this water heater. Pay attention to the following General Safety Precautions. Failure to follow these warnings could cause property damage, bodily injury or death. Should you have any problems understanding the instructions in this manual, STOP, and get help from a qualified installer or technician
SECTION 2 : INTRODUCTION
These important safeguards and instruction appearing in this manual are not meant to cover all possible conditions and situations that may occur. Common sense, caution and care are factors that cannot be built into every product. These factors must be supplied by the person(s) caring for and operating the unit.
2.1 LOCAL INSTALLATION REGULATIONS
This electric boiler must be installed in accordance with these instructions and in conformity with local codes, or in the absence of local codes, with the National Plumbing Code and the National Electric Code, current edition. In any case where instructions in this manual differ from local or national codes, the local or national codes take precedence.
2.2 CORROSIVE ENVIRONMENT
The electric boiler must not be installed near an air duct supplying corrosive atmosphere or with high humidity content. When a boiler defect is caused by such conditions, the warranty will not apply.
2.3 INSPECTION UPON RECEPTION
Inspect the electric boiler for possible shipping
damage. The manufacturer’s responsibility
ceases upon delivery of goods to the carrier in good condition. The Consignee must file any claims for damage, shortage in shipments, or non-delivery immediately against the carrier.
2.4 TO BE CHECKED
Please refer to the rating plate on the unit to ensure that you have the correct model and voltage in hand.
List of components shipped with the unit:
• Pressure relief valve set at
30 PSI.
• Drain valve.
• Temperature & pressure indicator
• Outdoor temperature sensor
• Installation and operating manual
The electric boiler should not be installed where it may damage the adjacent structures or lower floors in the event of leakage of the tank or connections. If this cannot be avoided, install a non­flammable tray or bowl under the boiler to collect and drain water from leaks.
NOTE: Any tray or cuvette MUST conform to local codes.
!
AVERTISSEMENT
!
WARNING
!
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 10.
SECTION 3 : INSTALLATION
The manufacturer’s warranty does not cover any damage or defect caused by installation, or attachment, or use of any special attachment other than those authorized by the manufacturer into, onto, or in conjunction with the water heater. The use of such unauthorized devices may shorten the life of the boiler and may endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized devices
3.1 SAFETY MEASURES
Any commercial installation will be equipped with a safety valve that limits the maximum working pressure to the maximum design pressure of the tank. The maximum operating pressure of the VOLTMAX Boiler with a power of 90kW and less (5 elements) is 30 psi or 70 psi, depending on the options chosen. The maximum operating pressure of the VOLTMAX boiler with a power of more than 90kW (10 elements) is 60 psi or 125 psi, depending on the options selected. See boiler data sheet for maximum operating pressure.
The boiler is equipped with an automatic high limit temperature control set at 210°F (99°C) and a second manual high limit temperature settable.
This electric boiler is designed to operate at a maximum operating temperature of 200 ° F (93 ° C). The boiler is designed for use in a hot water heating system only.
The heat transfer fluid must be water or an antifreeze water / propylene glycol solution or an antifreeze water / ethylene glycol solution specially designed for heating systems. The maximum concentration of solution must be a maximum of 50%.
3.2 LOCATION
The electric boiler should be installed in a clean, dry location. Long hot water lines should be insulated to conserve water and energy. The electric boiler and water lines should be protected from exposure to freezing temperature.
The boiler can be mounted vertically or horizontally directly on a solid surface. Vertical supports are provided and allow installation on the floor; No wall bracket is included with the equipment.
The electric boiler must be located or protected to avoid risk of physical damage, such as from moving vehicles, flooding, etc.
The location must have sufficient ventilation to maintain an ambient temperature not exceeding 90°F (32°C).
3.3 CLEARANCES
For adequate inspection and servicing the following minimum clearance is necessary:
Table 8 : Boiler Clearances
Sides**
3 inches / 76 mm
Bottom
0 inches / 0 mm
Top*
32 inches / 813 mm
Front
24 inches / 610 mm
Back
3 inches / 76 mm
* A minimum clearance of 32 inches. For units equipped with 18 kW elements (25 in. For 15 kW elements) is required for possible replacement of heating elements.
** The left side of the control panel, where the boiler ON / OFF switch is located, must remain visible after installation. Otherwise, a label indicating its location must be affixed to the control panel indicating its position.
3.4 PIPING INSTALLATION
The location of the inlet and outlet piping shall conform to the various configurations shown in Figure 1. You will find typical connection diagrams to the Figure 3, the Figure 4 and the Figure 5.
MISE EN GARDE
!
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 11.
Figure 1 : Possible pipe flow configurations
3.4.1.1 Boiler piping connection
The boiler is equipped with two fittings on each side of the unit. One of the bottom connections must be used for the heating return (inlet) and one of the top connections must be used for supplying the heating system (outlet). The outlet and inlet size are 1½ "NPTM threaded steel pipes, for the VOLTMAX with a power of 90kW and less (5 elements) and 2½ "NPTM threaded steel pipes for the VOLTMAX with a power of More than 90kW (10 elements).
Installation of plugs on the inlet and exhaust ducts is recommended to facilitate the disconnection and maintenance of the boiler.
When connecting different types of pipes (galvanized steel and copper), use dielectric joints (insulation) to protect the boiler and piping.
Use only new and clean pipes as piping connection to the boiler. Local codes or regulations may dictate the exact type of material to be used.
Insulate all piping containing hot water, especially in an unheated environment.
Install faucets for easy maintenance.
Install a thermometer on the inlet and outlet duct(s).
Close the unused openings on the boiler. Do not block the safety valve, this may cause loss, damage or injury.
3.4.1.2 Auxiliary boiler piping connection
When an auxiliary boiler used as back up is twinned to the DTH Ultra boiler to act as a back-
up controlled by the DTH Ultra, the auxiliary boiler shall preferably be installed downstream of the electric boiler as shown on Figure 5.
3.4.1.3 Safety valve
The installation of a safety valve is an integral
part of the boiler’s installation. The trigger point of
the valve must not exceed the design pressure of the boiler as indicated on its registration and identification plate. The valve must comply with the ASME Boiler and Pressure Vessel Code and limit the boiler maximum operating pressure. The safety valve is a security component, not a control component.
The capacity of the safety valve expressed in BTU / hour must equal or exceed the rating on the nameplate of the boiler (s).
Connect the exhaust of the safety valve to a drain line. The lower end of this conduit shall be at least 6" (15 cm) from the floor drain away from any electrical component. The drain line must be directed downwards from the exhaust of the safety valve to ensure complete drainage by gravity. The diameter of the drainpipe must not be less than that of the exhaust of the valve. The end of the conduit must not be threaded or hidden and must be protected from freezing. No valves, valves or valves shall be installed on the pipe. The installation of the safety valves is governed by the local code.
3.4.1.4 System pressure control and expansion tank
Pressure control devices within the system ensure that each component operates within minimum and maximum allowable pressures and maintain minimum pressure for all normal operating temperatures. They also allow air
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 12.
bleeding, prevent cavitation at the pump inlet and prevent water from boiling within the system; all this is accomplished with minimal addition of new water.
The increase in boiler water volume resulting from higher temperature is stored in the expansion tank during periods of high operating temperature and is returned to the system when the temperature decreases.
The expansion tank must be able to store the required volume of boiler water during maximum design operating temperature without exceeding the maximum allowable operating pressure, and to maintain the required minimum pressure when the system is cold. Contact your installing contractor, plumbing supply house, or local plumbing inspector for assistance. The point where the expansion tank is connected should be carefully selected to avoid the possibility that normal operation of automatic check or manual valves will isolate the tank from a hot boiler or any part of the system.
The expansion tank should preferably be located on the suction or intake side of the pump.
3.4.1.5 Water pressure makeup regulator
Make-up systems must be employed as required by codes. An automatic fill valve (automatic pressure regulator) must be used with a backflow preventer as required, to maintain minimum system pressure by supplying water to make up for leakage.
3.4.1.6 Air bleeder
The air contained in the heated water must be removed from the system to prevent corrosion
Installation of manual or automatic air vents is required to eliminate all air from the boiler and the heating distribution system.
The main air eliminator must be installed near the outlet of the boiler on the highest point of the main supply piping. It is imperative to ensure that all air possibly located in the boiler be eliminated at all time.
Regularly purge air from the pipes and beware that the heated water does not cause injury or damage. If the boiler is located at a location higher than the heat distribution system such as a heated floor, an automatic air eliminator should be installed close to the boiler outlet.
3.4.1.7 Circulating pump
The pump can be located either just upstream or just downstream from the boiler. On installation where the operating pressure is high, the preferred location of the circulator pump is upstream of the boiler in such a way as to lower the pressure on the boiler when the pump will be in operation. The pump capacity required is determined in relation to the capacity of the boiler installed and the type of heating distribution system on which it will be connected.
They are generally designed for an operation at a differential of temperature (Delta T0) of 10 to 20F between the supply and return temperature to the boiler.
Use the following equation to determine the required water flow.
Pump flow rate = Boiler power ÷ Delta T ÷ 500
· Pump flow rate is expressed in US gallons per minute or GPM.
· The Boiler output (in net BTU per hour) is the maximum amount of heat to be transferred through the heating loop to meet the heating load.
· Delta T: The boiler water temperature drop
For example, an electric boiler rated at 180KW has an output capacity of 614 160 BTU per hour. The system is designed for a temperature drop of 20°F.
Required pump flow rate = 614,160 ¸ 20 ¸ 500 = 61,4 GPM
For example, an 180kW electric boiler has a power of 614,160 BTU/h. The system is designed for a drop-in temperature (Delta T) of 20°F.
Flow required = 614,160 ¸ 20 ¸ 500 = 61.4 GPM
The following table lists the required pump flow rate in relation to the boiler capacity and Delta T.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 13.
Table 9 : Temperature rise vs flow rate (GPM)
MODEL
DELTA T0
10oF
20oF
30oF
40oF
VOLTMAX 23
15.7
7.8
5.2
3.9
VOLTMAX 27
18.4
9.2
6.1
4.6
VOLTMAX 30
20.5
10.2
6.8
5.1
VOLTMAX 36
24.6
12.3
8.2
6.1
VOLTMAX 40
27.3
13.6
9.1
6.8
VOLTMAX 41
28.0
14.0
9.3
7.0
VOLTMAX 45
30.7
15.4
10.2
7.7
VOLTMAX 48
32.8
16.4
10.9
8.2
VOLTMAX 50
34.1
17.1
11.4
8.5
VOLTMAX 54
36.8
18.4
12.3
9.2
VOLTMAX 55
37.5
18.8
12.5
9.4
VOLTMAX 60
40.9
20.5
13.6
10.2
VOLTMAX 66
46.4
23.2
15.5
11.6
VOLTMAX 68
45.0
22.5
15.0
11.3
VOLTMAX 72
49.1
24.6
16.4
12.3
VOLTMAX 75
51.2
25.6
17.1
12.8
VOLTMAX 90
61.7
30.8
20.6
15.4
VOLTMAX 99
67.8
33.9
22.6
17.0
VOLTMAX 108
73.7
36.8
24.6
18.4
VOLTMAX 120
82.2
41.1
27.4
16.1
VOLTMAX 132
90.5
45.2
30.2
22.6
VOLTMAX 144
98.7
49.3
32.9
24.7
VOLTMAX 150
102.4
51.2
34.1
25.6
VOLTMAX 165
112.6
56.3
37.5
28.1
VOLTMAX 180
122.8
61.4
40.9
30.7
3.4.2 DRAIN FAUCET
A drain valve is installed behind the unit. It allows the boiler to be emptied, to make possible the replacement of defective components.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 14.
3.4.3 PRESSURE LOSS
The graph of pressure loss due to friction of water inside the VOLTMAX boiler is shown in the following
Figure 2 : Pressure loss (FTH) as a function of the flow rate of heated water (GPM)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 15.
Figure 3 : Basic installation
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 16.
Figure 4 : Basic installation with indirect water heater and radiator
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 17.
Figure 5 : Dual-Energy installation with a condensing boiler
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 18.
Figure 6 : Multiple boiler parallel installation
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 19.
Figure 7 : Basic installation with auxiliary boiler for production of domestic hot water and heating
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 20.
3.5 ELECTRICAL CONNECTIONS
Wiring must conform to the National Electrical Code and to state or local code requirements.
The electric boiler must be electrically grounded in accordance with local codes, or, in the absence of local codes, with the National Electrical Code.
3.5.1 MAIN ELECTRICAL SUPPLY
The power supply must be a 208 or 240-volt circuit (single-phase or three-phase, 60Hz), 480 volts (three-phase, 60 Hz) or 600 volts (three­phase, 60 Hz) protected by an appropriately sized breaker. The wiring rating (3 wires + ground) must be adequate. Refer to the boiler rating plate to select the breaker capacity and wiring rating
3.5.2 PUMP SUPPLY
The VOLTMAX Electric boiler (SCR models) can control 1 or 2 pumps of the distribution system. According to the working configuration of the pump, the contact of the controller will function differently.
During a heat demand on W1 or W2, the contact between Pc and P1 or Pc and P2 will be used to start an external pump relay (maximum of 3 amps.). Depending on the configurations selected in the controller (section Erreur ! Source du renvoi introuvable.), the pump P2 can have priority over the pump P1 and if this function is selected, the controller W2 and the pump P2 will be given priority by opening the pump contact P1.
N.B. The VOLTMAX boiler is not designed to heat without a water circulation in its tank. Therefore, if external pump controls are used, they must be interlocked with the operating authorization on W1 of the controller.
3.5.3 CONNECTION OF EXTERNAL SIGNALS TO THE CONTROLLER
The connection of all external signals is made directly on the boiler controller on terminals located on top of it. See the connection diagram on Figure 8 and Figure 9.
Cables used for the connections shall resist temperature up to 90 °C.
3.5.3.1 Connecting the building heat demand signal
Upon reception of a closed contact connected to terminals 24V+ and W1 or W2, the corresponding circulating pump P1 or P2 will start and the boiler will be allowed to operate.
If external controllers control the heating system pumps, they must provide the operating authorization signal. The boiler must not receive a heat demand without the circulation pumps running.
On heating systems when water circulation is continuous, the heat demand control can be connected to the 24V+ and W1 terminals. The heating elements will then be active and available only when there is a request (dry contact).
If the heating system is designed to keep water warm with continuous circulation, a jumper (jumper) must be installed on the 24V+ and W1 terminals to maintain the boiler in demand. The boiler will then attempt to maintain the water temperature at the set-point.
Operation with an upper fixed set-point W2 can be established by connecting the auxiliary heating demand signal (Dry contact) of a thermostat to the 24V+ and W2 of the terminal block.
In all operating modes of the controller, a heat demand on W1 and W2/DHW (close contact) must be present to DI1 or DI2 to allow the operation of the boiler. The only exception is in domestic hot water mode (DHW) with an indirect water heater where the minimum boiler temperature shall be maintained.
3.5.3.2 Connecting au auxiliary boiler
(Available only on SCR models)
The boiler controller is designed to allow the operation of a second boiler or an auxiliary gas or oil fired boiler according to two different mode of operation “Auxiliary Backup” or Dual-Energy”.
To do so, connect the TT terminals of the auxiliary boiler to terminals AUX of the VOLTMAX. The maximum capacity of this contact is 3A/120Vac.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 21.
3.5.3.3 Connection of an “Unoccupied signal”
of the building.
This function allows dropping the boiler temperature during periods where the building is not used and this without having to lower all the room thermostats of the building. To do so, a signal (dry contact) will have to be connected to terminal OCC. The contact shall be close during the periods of temperature drop. You can also manage the periods of temperature drop by setting the parameters from the internal clock of the controller.
3.5.3.4 Connection of an indirect domestic
hot water heater
The VOLTMAX electric boiler can be used not only to fill the heating requirements of the building but also to fill its domestic hot water needs using an indirect domestic hot water heater such as our TURBOMAX series. To do so, connect the signal (dry contact) of indirect water heater temperature control to the terminal 24V+ and W2/DHW. This will activate the circulating pump supplying the water heater (if properly installed).
3.5.3.5 Connection of a dual-energy signal
The VOLTMAX can be operated in a dual-energy mode with an auxiliary boiler.
To do so, connect the normally close contact of the dual energy controller to terminals 24V+ & BI- E to operate with the electric boiler. See section Erreur ! Source du renvoi introuvable. for more details on the sequence of operation in dual energy.
3.5.3.6 Connection of an outdoor temperature
sensor
If you wish to modulate the boiler water temperature according to the outdoor temperature (Outdoor Reset, ORST) and also wish to stop the operation of the boiler when the outdoor temp. reaches a selected value (See section Erreur ! Source du renvoi introuvable.), then the outdoor sensor supplied with the unit or a corresponding signal coming from the network system shall be connected to terminals S. Ext. of the controller. This sensor does not need to be connected if the boiler application is for a fixed set-point operation.
N.B. Do not install a jumper if the outside sensor is not used.
Outdoor sensor location
o Outside the building at a location that best
represents the heat demand of the building (a wall facing north for most of the buildings and on a south one on buildings with large windows facing south).
o It should not be exposed to external heat
sources (dryer outlet, window openings, non­insulated walls).
o It should not be installed in a location where it
could be covered with snow.
Installation:
1. Drill a 9/64” dia. hole through the wall and insert the sensor cable.
2. Fix the sensor cover to the wall using supplied screw.
3. With an electric cable (100ft max.) having 2 conductors 20ga. connect one end of this cable to the sensor cable using twist-on wire connectors and the other end to terminals S.
Ext (G. & AI2) of the boiler.
3.5.3.7 Remote controller used to determine
the target boiler temperature
An external controller (such as a central building energy management system) can be used to determine the boiler target temperature required for the building. To do so, the external controller shall give a 0 to 10VDC signal connected to terminals 0-10Vdc G & 0-10Vdc T° of the controller.
3.5.3.8 Power limiting device
An external controller providing a 0-10Vdc signal could be used to manage the capacity (kW) of the boiler. Example: An application where the main electrical service supply of the building is limited or when the electricity rate is billed according to the maximum peak loads of the building. To do so, the external controller shall be connected to terminals 0-10Vdc G & 0-10V cap. The capacity of the boiler could be manually limited by adjusting some of the controller parameters. See sections Erreur ! Source du renvoi introuvable. for more details
3.5.3.9 Alarm
An alarm signal (dry contact) is available on the boiler to advise the user of an alarm situation. The capacity of the contact is 3A resistive/1A inductive on terminal AL/AL
Loading...
+ 48 hidden pages