THERMO 2000 VOLTMAX 45, VOLTMAX 30, VOLTMAX 36, VOLTMAX 41, VOLTMAX 50 Installation And Operation Manual

...
VOLTMAX Electric Boiler
Model: 22.5 kW to 180 kW:
208/240 Volts (single-phase) and
208/240/480
INSTALLATION AND OPERATION MANUAL
mo
Your
VOLTMAX Electric Boiler was carefully assembled and checked at the factory to ensure its pro
per
functioning for many years.
The following information and safety measures are provided to
enable
proper installation, operation, and maintenance of this product.
It is imperative that all persons who are expected to install, operate or adjust this boi
ler
should read
these instructions carefully.
Any questions regarding the operation, maintenance, service or warranty of this electric boiler should be directed to the supplier.
When all installation steps have been completed, keep this installation manu
al in a safe place (near
the
boiler) for future reference.
THERMO 2000 INC.
Printed in Canada
Revised: May 2017
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 2.
TABLE OF CONTENTS
SECTION 1 : TECHNICAL SPECIFICATIONS ............................................................................... 4
SECTION 2 : INTRODUCTION ....................................................................................................... 9
2.1 LOCAL INSTALLATION REGULATIONS ............................................................................. 9
2.2 CORROSIVE ENVIRONMENT.............................................................................................. 9
2.3 INSPECTION UPON RECEPTION ....................................................................................... 9
2.4 TO BE CHECKED ................................................................................................................. 9
SECTION 3 : INSTALLATION....................................................................................................... 10
3.1 SAFETY MEASURES .......................................................................................................... 10
3.2 LOCATION........................................................................................................................... 10
3.3 CLEARANCES .................................................................................................................... 10
3.4 PIPING INSTALLATION ...................................................................................................... 10
3.4.2 Drain faucet .................................................................................................................. 13
3.4.3 Pressure loss ................................................................................................................ 14
3.5 ELECTRICAL CONNECTIONS ........................................................................................... 20
3.5.1 Main electrical supply ................................................................................................... 20
3.5.2 Pump supply ................................................................................................................. 20
3.5.3 Connection of external signals to the controller ........................................................... 20
SECTION 4 : CONTROLLER OPERATION ................................................................................. 34
4.1 USER INTERFACE ............................................................................................................. 34
4.1.1 Symbol description ....................................................................................................... 34
4.1.2 Control panel ................................................................................................................ 35
4.1.3 Navigation and adjustements ....................................................................................... 35
4.1.4 Main menu navigation .................................................................................................. 36
4.1.5 Navigation in boiler setting ........................................................................................... 37
4.2 MAIN MENU ........................................................................................................................ 39
4.2.1 Boiler status .................................................................................................................. 39
4.2.2 Boiler configuration ....................................................................................................... 39
4.2.3 User setting .................................................................................................................. 39
4.2.4 Clock setting ................................................................................................................. 40
4.2.5 Consumption ................................................................................................................ 40
4.3 BOILER SETTINGS ............................................................................................................. 40
4.3.1 Heating mode W1 ......................................................................................................... 41
4.3.2 Heating mode W2/DHW ............................................................................................... 41
4.3.3 Pump setting................................................................................................................. 41
4.3.4 Capacity limiting ........................................................................................................... 42
4.3.5 Auxiliary boiler .............................................................................................................. 42
4.3.6 Limit setting .................................................................................................................. 43
4.3.7 Alarm ............................................................................................................................ 44
4.3.8 Communication............................................................................................................. 44
4.3.9 Occupation ................................................................................................................... 45
4.3.10 BOOST Mode ............................................................................................................. 46
4.3.11 Warm weather shutdown ............................................................................................ 46
4.3.12 Change password ...................................................................................................... 46
4.4 INTERNET ........................................................................................................................... 46
4.4.1 Website ......................................................................................................................... 47
4.4.2 Email ............................................................................................................................. 47
4.5 BOILER STATUS DISPLAY SETTINGS ............................................................................. 48
4.6 HEATING MODE W1 SETTINGS ....................................................................................... 50
4.6.1 FIXED MODE ............................................................................................................... 50
4.6.2 OUTDOOR RESET MODE .......................................................................................... 51
4.6.3 Mode : DDC 0-10VDC .................................................................................................. 52
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 3.
4.7 W2 MODE SET-POINT TEMPERATURE SETTINGS ........................................................ 53
4.7.1 W2 MODE .................................................................................................................... 53
4.7.2 DHW MODE ................................................................................................................. 53
4.8 PUMP CONFIGURATION MENU SETTINGS .................................................................... 53
4.8.1 PUMP 1 ........................................................................................................................ 53
4.8.2 PUMP 2 ........................................................................................................................ 53
SPECIFIC PARAMETERS FOR THE CAPACITY LIMITING MENU .................................... 54
4.8.3 MANUAL MODE ........................................................................................................... 54
4.8.4 MODE: 0-10 VDC ......................................................................................................... 54
4.9 POWER LIMITATION MENU SETTINGS ........................................................................... 55
4.9.1 MANUAL MODE ........................................................................................................... 55
4.9.2 0-10 VDC MODE .......................................................................................................... 55
4.9.3 T. ext MODE ................................................................................................................. 56
4.9.4 Schedule MODE ........................................................................................................... 57
4.10 AUXILIARY BOILER SETTINGS ....................................................................................... 58
4.10.1 BACKUP MODE ......................................................................................................... 58
4.10.2 EXTERNAL CONTACT MODE .................................................................................. 59
4.10.3 ManuAl MODE ........................................................................................................... 59
4.10.4 Bi-Energy MODE ........................................................................................................ 60
4.11 LIMIT CONFIGURATION MENU SETTINGS .................................................................... 61
4.12 CONFIG. ALARM MENU SETTINGS ................................................................................ 62
4.13 OCCUPATION MENU SETTINGS .................................................................................... 62
4.14 BOOST MENU SETTINGS................................................................................................ 63
4.15 WARM WEATHER SHUTDOWN MENU SETTINGS ....................................................... 63
SECTION 5 : BOILER START UP ................................................................................................ 64
5.1 FILLING THE BOILER ......................................................................................................... 64
5.2 ADJUSTEMENT OF THE CONTROLLER OPERATING PARAMETERS .......................... 64
5.3 STARTUP PROCEDURE .................................................................................................... 64
SECTION 6 : TROUBLESHOOTING ............................................................................................ 66
6.1 WARNING LIGHTS ............................................................................................................. 66
6.2 OPERATING PROBLEM IDENTIFICATION ....................................................................... 66
6.2.1 External HL / LWCO ............................................................................................... 66
6.2.2 Sensor ( SE ) .......................................................................................................... 66
6.2.3 Low limit ( LL ) ........................................................................................................ 66
6.2.4 Flow ( F ) ................................................................................................................ 66
6.2.5 Current ( A ) ............................................................................................................ 66
6.2.6 HL temperature ( HL ) ............................................................................................ 67
6.2.7 Low pressure ( P ) .................................................................................................. 67
6.2.8 High pressure ( P ) ................................................................................................. 67
6.2.9 Lock out .................................................................................................................. 67
SECTION 7 : MAINTENANCE ...................................................................................................... 68
7.1 BOILER WATER PIPING .................................................................................................... 68
7.2 PRESSURE RELIEF VALVE ............................................................................................... 68
7.3 AIR PURGE ......................................................................................................................... 68
7.4 ELECTRICAL INSPECTION................................................................................................ 68
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 4.
SECTION 1 : TECHNICAL SPECIFICATIONS
Table 1: VOLTMAX 208 VAC / 60 Hz / Single-Phase1
Capacity
STG
Series
SCR Series
Model
kW
BTU/h
Amp
s
Electrical
element(s) 240 V
Stage Relay
Stage Relay
SCR
Stage
VOLTMAX 23
22,5
76 770
108,4
6 x 5 kW
3 x 7,5 kW
2 x 7,5 kW
1 x 7,5 kW
VOLTMAX 27
27
92 124
130,1
6 x 6 kW
3 x 9 kW
2 x 9 kW
1 x 9 kW
VOLTMAX 30
30
102 360
144,5
8 x 5 kW
4 x 7,5 kW
3 x 7,5 kW
1 x 7,5 kW
VOLTMAX 36
36
122 832
173,4
8 x 6 kW
4 x 9 kW
3 x 9 kW
1 x 9 kW
VOLTMAX 41
41
139 892
198,7
5 x 5 kW + 5 x 6 kW
5 x 8,25 kW
4 x 8,25 kW
1 x 8,25 kW
VOLTMAX 45
45
153 540
216,8
10 x 6 kW
5 x 9 kW
4 x 9 kW
1 x 9 kW
VOLTMAX 50
49,5
168 894
238,4
6 x 5 kW + 6 x 6 kW
6 x 8,25 kW
5 x 8,25 kW
1 x 8,25 kW
VOLTMAX 54
54
184 248
260,1
12 x 6 kW
6 x 9 kW
5 x 9 kW
1 x 9 kW
1
Electrical supply 208 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
Table 2: VOLTMAX 240 VAC / 60 Hz / 1 Phase1
Capacity
STG
Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s) 240 V
Stage Relay
Stage Relay
SCR
Stage
VOLTMAX 30
30
102 360
125
6 x 5 kW
3 x 10 kW
2 x 10 kW
1 x 10 kW
VOLTMAX 36
36
122 832
150
6 x 6 kW
3 x 12 kW
2 x 12 kW
1 x 12 kW
VOLTMAX 40
40
136 480
166,7
8 x 5 kW
4 x 10 kW
3 x 10 kW
1 x 10 kW
VOLTMAX 48
48
163 776
200
8 x 6 kW
4 x 12 kW
3 x 12 kW
1 x 12 kW
VOLTMAX 55
55
187 660
229,2
5 x 5 kW + 5 x 6 kW
5 x 11 kW
4 x 11 kW
1 x 11 kW
VOLTMAX 60
60
204 720
250
10 x 6 kW
5 x 12 kW
4 x 12 kW
1 x 12 kW
VOLTMAX 66
66
225 192
275
6 x 5 kW + 6 x 6 kW
6 x 11 kW
5 x 11 kW
1 x 11 kW
VOLTMAX 72
72
245 664
300
12 x 6 kW
6 x 12 kW
5 x 12 kW
1 x 12 kW
1
Electrical supply 240 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
Table 3 : VOLTMAX 208 VAC / 60 Hz / 1 Phase1
Puissance
STG
Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s) 240 V
Stage Relay
Stage Relay
SCR
Stage
VOLTMAX 30
30
102 360
125
6 x 5 kW
3 x 10 kW
2 x 10 kW
1 x 10 kW
VOLTMAX 36
36
122 832
150
6 x 6 kW
3 x 12 kW
2 x 12 kW
1 x 12 kW
VOLTMAX 40
40
136 480
166,7
8 x 5 kW
4 x 10 kW
3 x 10 kW
1 x 10 kW
VOLTMAX 48
48
163 776
200
8 x 6 kW
4 x 12 kW
3 x 12 kW
1 x 12 kW
VOLTMAX 55
55
187 660
229,2
5 x 5 kW + 5 x 6 kW
5 x 11 kW
4 x 11 kW
1 x 11 kW
VOLTMAX 60
60
204 720
250
10 x 6 kW
5 x 12 kW
4 x 12 kW
1 x 12 kW
VOLTMAX 66
66
225 192
275
6 x 5 kW + 6 x 6 kW
6 x 11 kW
5 x 11 kW
1 x 11 kW
VOLTMAX 72
72
245 664
300
12 x 6 kW
6 x 12 kW
5 x 12 kW
1 x 12 kW
1
Electrical supply 208 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 5.
Table 4 : VOLTMAX 240 VAC / 60 Hz / 3 Phases
1
Capacity
STG
Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s) 240 V
Stage Relay
Model kW
VOLTMAX 30
30
102 360
72
6 x 5 kW
2 x 15 kW
1 x 15 kW
1 x 15 kW
VOLTMAX 36
36
122 832
86,6
6 x 6 kW
2 x 18 kW
1 x 18 kW
1 x 18 kW
VOLTMAX 45
45
153 540
108,3
9 x 5 kW
3 x 15 kW
2 x 15 kW
1 x 15 kW
VOLTMAX 54
54
184 248
129,9
9 x 6 kW
3 x 18 kW
2 x 18 kW
1 x 18 kW
VOLTMAX 60
60
204 720
144,3
12 x 5 kW
4 x 15 kW
3 x 15 kW
1 x 15 kW
VOLTMAX 72
72
245 664
173,2
12 x 6 kW
4 x 18 kW
3 x 18 kW
1 x 18 kW
VOLTMAX 75
75
255 900
180,4
15 x 5 kW
5 x 15 kW
4 x 15 kW
1 x 15 kW
1
Electrical supply 240 V - 1 phase (L1-L2) with 2 conductors 90°C with a ground.
Table 5 : VOLTMAX 480 VAC / 60 Hz / 3 Phases
1
Capacity
STG Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s)
240 V
Stage Relay
Model
kW
VOLTMAX 30
30
102 360
36,1
6 x 5 kW
2 x 15 kW
1 x 15 kW
1 x 15 kW
VOLTMAX 36
36
122 832
43,3
6 x 6 kW
2 x 18 kW
1 x 18 kW
1 x 18 kW
VOLTMAX 45
45
153 540
54,1
9 x 5 kW
3 x 15 kW
2 x 15 kW
1 x 15 kW
VOLTMAX 54
54
184 248
65
9 x 6 kW
3 x 18 kW
2 x 18 kW
1 x 18 kW
VOLTMAX 60
60
204 720
72,2
12 x 5 kW
4 x 15 kW
3 x 15 kW
1 x 18 kW
VOLTMAX 72
72
245 664
86,6
12 x 6 kW
4 x 18 kW
3 x 18 kW
1 x 18 kW
VOLTMAX 75
75
255 900
90,2
15 x 5 kW
5 x 15 kW
4 x 15 kW
1 x 15 kW
VOLTMAX 90
90
307 80
108,3
15 x 6 kW
5 x 18 kW
4 x 18 kW
1 x 18 kW
VOLTMAX 99
99
337 788
119,1
9 x 5 kW + 9 x 6 kW
3 x 33 kW
2 x 33 kW
1 x 33 kW
VOLTMAX 108
108
368 496
129,9
18 x 6 kW
3 x 36 kW
2 x 36 kW
1 x 36 kW
VOLTMAX 120
120
409 440
144,3
24 x 5 kW
4 x 30 kW
3 x 30 kW
1 x 30 kW
VOLTMAX 132
132
450 384
158,8
12 x 5 kW + 12 x 6 kW
4 x 33 kW
3 x 33 kW
1 x 33 kW
VOLTMAX 144
144
491 328
173,2
24 x 6 kW
4 x 36 kW
3 x 36 kW
1 x 36 kW
VOLTMAX 150
150
511 800
180,4
30 x 5 kW
5 x 30 kW
4 x 30 kW
1 x 30 kW
VOLTMAX 165
165
562 980
198,5
15 x 5 kW + 15 x 6 kW
5 x 33 kW
4 x 33 kW
1 x 33 kW
VOLTMAX 180
180
614 160
216,5
30 x 6 kW
5 x 36 kW
4 x 36 kW
1 x 36 kW
1
Electrical supply 480 V - 1 phase (L1-L2-L3) with 3 conductors 90°C with a ground.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 6.
Table 6 : VOLTMAX 600 VAC / 60 Hz / 3 Phases1
Capacity
STG Series
SCR Series
Model
kW
BTU/h
Amps
Electrical
element(s)
240 V
Stage Relay
Model
kW
VOLTMAX 30
30
102 360
28,9
6 x 5 kW
2 x 15 kW
1 x 15 kW
1 x 15 kW
VOLTMAX 36
36
122 832
34,6
6 x 6 kW
2 x 18 kW
1 x 18 kW
1 x 18 kW
VOLTMAX 45
45
153 540
43,3
9 x 5 kW
3 x 15 kW
2 x 15 kW
1 x 15 kW
VOLTMAX 54
54
184 248
52
9 x 6 kW
3 x 18 kW
2 x 18 kW
1 x 18 kW
VOLTMAX 60
60
204 720
57,7
12 x 5 kW
4 x 15 kW
3 x 15 kW
1 x 18 kW
VOLTMAX 72
72
245 664
69,3
12 x 6 kW
4 x 18 kW
3 x 18 kW
1 x 18 kW
VOLTMAX 75
75
255 900
72,2
15 x 5 kW
5 x 15 kW
4 x 15 kW
1 x 15 kW
VOLTMAX 90
90
307 80
86,6
15 x 6 kW
5 x 18 kW
4 x 18 kW
1 x 18 kW
VOLTMAX 99
99
337 788
95,3
9 x 5 kW +
9 x 6 kW
3 x 33 kW
2 x 33 kW
1 x 33 kW
VOLTMAX 108
108
368 496
103,9
18 x 6 kW
3 x 36 kW
2 x 36 kW
1 x 36 kW
VOLTMAX 120
120
409 440
115,5
24 x 5 kW
4 x 30 kW
3 x 30 kW
1 x 30 kW
VOLTMAX 132
132
450 384
127
12 x 5 kW +
12 x 6 kW
4 x 33 kW
3 x 33 kW
1 x 33 kW
VOLTMAX 144
144
491 328
138,6
24 x 6 kW
4 x 36 kW
3 x 36 kW
1 x 36 kW
VOLTMAX 150
150
511 800
144,3
30 x 5 kW
5 x 30 kW
4 x 30 kW
1 x 30 kW
VOLTMAX 165
165
562 980
158,8
15 x 5 kW +
15 x 6 kW
5 x 33 kW
4 x 33 kW
1 x 33 kW
VOLTMAX 180
180
614 160
173,2
30 x 6 kW
5 x 36 kW
4 x 36 kW
1 x 36 kW
1
Electrical supply 600 V - 1 phase (L1-L2-L3) with 3 conductors 90°C with a ground.
Tableau 7 : Maximal service pressure
VOLTMAX
90 kW and less
More than 90 kW
Maximum operating pressure
30 PSI
60 PSI
Optional maximum operating pressure
70 PSI*
125 PSI
* Model from 23 to 90 kW are available at a maximum operating pressure of 125 PSI, but size of the unit will be the same as model of more than 90 kW.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 7.
BOILER DIMENSIONS AND CHARACTERISTIC: MODELS 90KW OR LESS
* Return sensor available with the " SCR SERIES " configuration. ** Optional disconnect switch available on " THREE-PHASE " models. *** Solid state SCR relay available with the " SCR SERIES " configuration. **** Low water cut-off is optional.
BOILER CONNECTIONS
1
Boiler outlet
1 1/2" NPT M
2
Boiler inlet
1 1/2" NPT M
3
Pressure relief valve
3/4" NPT F
4
Drain valve
3/4" NPT F
5*
Access to the return sensor
1/2" NPT F
MIN. CLEARANCES FOR INSTALLATION &
MAINTENANCE
Left and Right sides
3"/ 76mm
Rear
3"/ 76mm
Front
24" / 610mm
Bottom
0" / 0mm
Top
32" / 813mm
GENERAL INFORMATIONS
Weight
310lbs / 141kg
Water Volume
11 Us gal. / 41.6 liters
Max. operating
pressure
STANDARD: 30psi
OPTION: 70 PSI *
*Available at 125PSI (See Shop Drawing 99-180KW)
COMPONENTS IDENTIFICATION
A
Electrical main supply
B
Boiler controller
C
"On/Off" switch
D**
Disconnect switch & rotary handle
E
Fuses for controls
F***
Solid state SCR relay
G****
Low water cut-off, test button and indicator lights
H
Electrical control access door
I
Door handle for electric access with lock
J
Electrical control wires access holes
K
Access door power circuit
L
Access cover to Heating elements
M
Heating elements
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 8.
BOILER DIMENSIONS AND CHARACTERISTIC: MODELS 90KW TO 180KW
* Return sensor available with the " SCR Series " configuration. ** Optional disconnect switch available on " THREE-PHASE" models. *** Solid state SCR relay available with the " SCR Series " configuration. **** Low water cut-off is standard for models more than 117kw.
BOILER CONNECTIONS
1
Boiler outlet
1 1/2" NPT M
2
Boiler inlet
1 1/2" NPT M
3
Pressure relief valve
3/4" NPT F
4
Drain valve
3/4" NPT F
5*
Access to the return sensor
1/2" NPT F
MIN. CLEARANCES FOR INSTALLATION &
MAINTENANCE
Left and Right sides
3"/ 76mm
Rear
3"/ 76mm
Front
24" / 610mm
Bottom
0" / 0mm
Top
32" / 813mm
GENERAL INFORMATIONS
Weight
550lbs / 250kg
Water Volume
30 gal. Us/ 113.5 liters
Max. operating
pressure
STANDARD: 60psi
OPTION: 125 PSI
COMPONENTS IDENTIFICATION
A
Electrical main supply
B
Boiler controller
C
"On/Off" switch
D**
Disconnect switch & rotary handle
E
Fuses for controls
F***
Solid state SCR relay
G****
Low water cut-off, test button and indicator lights
H
Electrical control access door
I
Door handle for electric access with lock
J
Electrical control wires access holes
K
Access door power circuit
L
Access cover to Heating elements
M
Heating elements
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 9.
General Safety Precautions
Be sure to read and understand the entire Installation & operation manual before attempting to install or to operate this water heater. Pay attention to the following General Safety Precautions. Failure to follow these warnings could cause property damage, bodily injury or death. Should you have any problems understanding the instructions in this manual, STOP, and get help from a qualified installer or technician
SECTION 2 : INTRODUCTION
These important safeguards and instruction appearing in this manual are not meant to cover all possible conditions and situations that may occur. Common sense, caution and care are factors that cannot be built into every product. These factors must be supplied by the person(s) caring for and operating the unit.
2.1 LOCAL INSTALLATION REGULATIONS
This electric boiler must be installed in accordance with these instructions and in conformity with local codes, or in the absence of local codes, with the National Plumbing Code and the National Electric Code, current edition. In any case where instructions in this manual differ from local or national codes, the local or national codes take precedence.
2.2 CORROSIVE ENVIRONMENT
The electric boiler must not be installed near an air duct supplying corrosive atmosphere or with high humidity content. When a boiler defect is caused by such conditions, the warranty will not apply.
2.3 INSPECTION UPON RECEPTION
Inspect the electric boiler for possible shipping
damage. The manufacturer’s responsibility
ceases upon delivery of goods to the carrier in good condition. The Consignee must file any claims for damage, shortage in shipments, or non-delivery immediately against the carrier.
2.4 TO BE CHECKED
Please refer to the rating plate on the unit to ensure that you have the correct model and voltage in hand.
List of components shipped with the unit:
• Pressure relief valve set at
30 PSI.
• Drain valve.
• Temperature & pressure indicator
• Outdoor temperature sensor
• Installation and operating manual
The electric boiler should not be installed where it may damage the adjacent structures or lower floors in the event of leakage of the tank or connections. If this cannot be avoided, install a non­flammable tray or bowl under the boiler to collect and drain water from leaks.
NOTE: Any tray or cuvette MUST conform to local codes.
!
AVERTISSEMENT
!
WARNING
!
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 10.
SECTION 3 : INSTALLATION
The manufacturer’s warranty does not cover any damage or defect caused by installation, or attachment, or use of any special attachment other than those authorized by the manufacturer into, onto, or in conjunction with the water heater. The use of such unauthorized devices may shorten the life of the boiler and may endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized devices
3.1 SAFETY MEASURES
Any commercial installation will be equipped with a safety valve that limits the maximum working pressure to the maximum design pressure of the tank. The maximum operating pressure of the VOLTMAX Boiler with a power of 90kW and less (5 elements) is 30 psi or 70 psi, depending on the options chosen. The maximum operating pressure of the VOLTMAX boiler with a power of more than 90kW (10 elements) is 60 psi or 125 psi, depending on the options selected. See boiler data sheet for maximum operating pressure.
The boiler is equipped with an automatic high limit temperature control set at 210°F (99°C) and a second manual high limit temperature settable.
This electric boiler is designed to operate at a maximum operating temperature of 200 ° F (93 ° C). The boiler is designed for use in a hot water heating system only.
The heat transfer fluid must be water or an antifreeze water / propylene glycol solution or an antifreeze water / ethylene glycol solution specially designed for heating systems. The maximum concentration of solution must be a maximum of 50%.
3.2 LOCATION
The electric boiler should be installed in a clean, dry location. Long hot water lines should be insulated to conserve water and energy. The electric boiler and water lines should be protected from exposure to freezing temperature.
The boiler can be mounted vertically or horizontally directly on a solid surface. Vertical supports are provided and allow installation on the floor; No wall bracket is included with the equipment.
The electric boiler must be located or protected to avoid risk of physical damage, such as from moving vehicles, flooding, etc.
The location must have sufficient ventilation to maintain an ambient temperature not exceeding 90°F (32°C).
3.3 CLEARANCES
For adequate inspection and servicing the following minimum clearance is necessary:
Table 8 : Boiler Clearances
Sides**
3 inches / 76 mm
Bottom
0 inches / 0 mm
Top*
32 inches / 813 mm
Front
24 inches / 610 mm
Back
3 inches / 76 mm
* A minimum clearance of 32 inches. For units equipped with 18 kW elements (25 in. For 15 kW elements) is required for possible replacement of heating elements.
** The left side of the control panel, where the boiler ON / OFF switch is located, must remain visible after installation. Otherwise, a label indicating its location must be affixed to the control panel indicating its position.
3.4 PIPING INSTALLATION
The location of the inlet and outlet piping shall conform to the various configurations shown in Figure 1. You will find typical connection diagrams to the Figure 3, the Figure 4 and the Figure 5.
MISE EN GARDE
!
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 11.
Figure 1 : Possible pipe flow configurations
3.4.1.1 Boiler piping connection
The boiler is equipped with two fittings on each side of the unit. One of the bottom connections must be used for the heating return (inlet) and one of the top connections must be used for supplying the heating system (outlet). The outlet and inlet size are 1½ "NPTM threaded steel pipes, for the VOLTMAX with a power of 90kW and less (5 elements) and 2½ "NPTM threaded steel pipes for the VOLTMAX with a power of More than 90kW (10 elements).
Installation of plugs on the inlet and exhaust ducts is recommended to facilitate the disconnection and maintenance of the boiler.
When connecting different types of pipes (galvanized steel and copper), use dielectric joints (insulation) to protect the boiler and piping.
Use only new and clean pipes as piping connection to the boiler. Local codes or regulations may dictate the exact type of material to be used.
Insulate all piping containing hot water, especially in an unheated environment.
Install faucets for easy maintenance.
Install a thermometer on the inlet and outlet duct(s).
Close the unused openings on the boiler. Do not block the safety valve, this may cause loss, damage or injury.
3.4.1.2 Auxiliary boiler piping connection
When an auxiliary boiler used as back up is twinned to the DTH Ultra boiler to act as a back-
up controlled by the DTH Ultra, the auxiliary boiler shall preferably be installed downstream of the electric boiler as shown on Figure 5.
3.4.1.3 Safety valve
The installation of a safety valve is an integral
part of the boiler’s installation. The trigger point of
the valve must not exceed the design pressure of the boiler as indicated on its registration and identification plate. The valve must comply with the ASME Boiler and Pressure Vessel Code and limit the boiler maximum operating pressure. The safety valve is a security component, not a control component.
The capacity of the safety valve expressed in BTU / hour must equal or exceed the rating on the nameplate of the boiler (s).
Connect the exhaust of the safety valve to a drain line. The lower end of this conduit shall be at least 6" (15 cm) from the floor drain away from any electrical component. The drain line must be directed downwards from the exhaust of the safety valve to ensure complete drainage by gravity. The diameter of the drainpipe must not be less than that of the exhaust of the valve. The end of the conduit must not be threaded or hidden and must be protected from freezing. No valves, valves or valves shall be installed on the pipe. The installation of the safety valves is governed by the local code.
3.4.1.4 System pressure control and expansion tank
Pressure control devices within the system ensure that each component operates within minimum and maximum allowable pressures and maintain minimum pressure for all normal operating temperatures. They also allow air
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 12.
bleeding, prevent cavitation at the pump inlet and prevent water from boiling within the system; all this is accomplished with minimal addition of new water.
The increase in boiler water volume resulting from higher temperature is stored in the expansion tank during periods of high operating temperature and is returned to the system when the temperature decreases.
The expansion tank must be able to store the required volume of boiler water during maximum design operating temperature without exceeding the maximum allowable operating pressure, and to maintain the required minimum pressure when the system is cold. Contact your installing contractor, plumbing supply house, or local plumbing inspector for assistance. The point where the expansion tank is connected should be carefully selected to avoid the possibility that normal operation of automatic check or manual valves will isolate the tank from a hot boiler or any part of the system.
The expansion tank should preferably be located on the suction or intake side of the pump.
3.4.1.5 Water pressure makeup regulator
Make-up systems must be employed as required by codes. An automatic fill valve (automatic pressure regulator) must be used with a backflow preventer as required, to maintain minimum system pressure by supplying water to make up for leakage.
3.4.1.6 Air bleeder
The air contained in the heated water must be removed from the system to prevent corrosion
Installation of manual or automatic air vents is required to eliminate all air from the boiler and the heating distribution system.
The main air eliminator must be installed near the outlet of the boiler on the highest point of the main supply piping. It is imperative to ensure that all air possibly located in the boiler be eliminated at all time.
Regularly purge air from the pipes and beware that the heated water does not cause injury or damage. If the boiler is located at a location higher than the heat distribution system such as a heated floor, an automatic air eliminator should be installed close to the boiler outlet.
3.4.1.7 Circulating pump
The pump can be located either just upstream or just downstream from the boiler. On installation where the operating pressure is high, the preferred location of the circulator pump is upstream of the boiler in such a way as to lower the pressure on the boiler when the pump will be in operation. The pump capacity required is determined in relation to the capacity of the boiler installed and the type of heating distribution system on which it will be connected.
They are generally designed for an operation at a differential of temperature (Delta T0) of 10 to 20F between the supply and return temperature to the boiler.
Use the following equation to determine the required water flow.
Pump flow rate = Boiler power ÷ Delta T ÷ 500
· Pump flow rate is expressed in US gallons per minute or GPM.
· The Boiler output (in net BTU per hour) is the maximum amount of heat to be transferred through the heating loop to meet the heating load.
· Delta T: The boiler water temperature drop
For example, an electric boiler rated at 180KW has an output capacity of 614 160 BTU per hour. The system is designed for a temperature drop of 20°F.
Required pump flow rate = 614,160 ¸ 20 ¸ 500 = 61,4 GPM
For example, an 180kW electric boiler has a power of 614,160 BTU/h. The system is designed for a drop-in temperature (Delta T) of 20°F.
Flow required = 614,160 ¸ 20 ¸ 500 = 61.4 GPM
The following table lists the required pump flow rate in relation to the boiler capacity and Delta T.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 13.
Table 9 : Temperature rise vs flow rate (GPM)
MODEL
DELTA T0
10oF
20oF
30oF
40oF
VOLTMAX 23
15.7
7.8
5.2
3.9
VOLTMAX 27
18.4
9.2
6.1
4.6
VOLTMAX 30
20.5
10.2
6.8
5.1
VOLTMAX 36
24.6
12.3
8.2
6.1
VOLTMAX 40
27.3
13.6
9.1
6.8
VOLTMAX 41
28.0
14.0
9.3
7.0
VOLTMAX 45
30.7
15.4
10.2
7.7
VOLTMAX 48
32.8
16.4
10.9
8.2
VOLTMAX 50
34.1
17.1
11.4
8.5
VOLTMAX 54
36.8
18.4
12.3
9.2
VOLTMAX 55
37.5
18.8
12.5
9.4
VOLTMAX 60
40.9
20.5
13.6
10.2
VOLTMAX 66
46.4
23.2
15.5
11.6
VOLTMAX 68
45.0
22.5
15.0
11.3
VOLTMAX 72
49.1
24.6
16.4
12.3
VOLTMAX 75
51.2
25.6
17.1
12.8
VOLTMAX 90
61.7
30.8
20.6
15.4
VOLTMAX 99
67.8
33.9
22.6
17.0
VOLTMAX 108
73.7
36.8
24.6
18.4
VOLTMAX 120
82.2
41.1
27.4
16.1
VOLTMAX 132
90.5
45.2
30.2
22.6
VOLTMAX 144
98.7
49.3
32.9
24.7
VOLTMAX 150
102.4
51.2
34.1
25.6
VOLTMAX 165
112.6
56.3
37.5
28.1
VOLTMAX 180
122.8
61.4
40.9
30.7
3.4.2 DRAIN FAUCET
A drain valve is installed behind the unit. It allows the boiler to be emptied, to make possible the replacement of defective components.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 14.
3.4.3 PRESSURE LOSS
The graph of pressure loss due to friction of water inside the VOLTMAX boiler is shown in the following
Figure 2 : Pressure loss (FTH) as a function of the flow rate of heated water (GPM)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 15.
Figure 3 : Basic installation
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 16.
Figure 4 : Basic installation with indirect water heater and radiator
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 17.
Figure 5 : Dual-Energy installation with a condensing boiler
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 18.
Figure 6 : Multiple boiler parallel installation
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 19.
Figure 7 : Basic installation with auxiliary boiler for production of domestic hot water and heating
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 20.
3.5 ELECTRICAL CONNECTIONS
Wiring must conform to the National Electrical Code and to state or local code requirements.
The electric boiler must be electrically grounded in accordance with local codes, or, in the absence of local codes, with the National Electrical Code.
3.5.1 MAIN ELECTRICAL SUPPLY
The power supply must be a 208 or 240-volt circuit (single-phase or three-phase, 60Hz), 480 volts (three-phase, 60 Hz) or 600 volts (three­phase, 60 Hz) protected by an appropriately sized breaker. The wiring rating (3 wires + ground) must be adequate. Refer to the boiler rating plate to select the breaker capacity and wiring rating
3.5.2 PUMP SUPPLY
The VOLTMAX Electric boiler (SCR models) can control 1 or 2 pumps of the distribution system. According to the working configuration of the pump, the contact of the controller will function differently.
During a heat demand on W1 or W2, the contact between Pc and P1 or Pc and P2 will be used to start an external pump relay (maximum of 3 amps.). Depending on the configurations selected in the controller (section Erreur ! Source du renvoi introuvable.), the pump P2 can have priority over the pump P1 and if this function is selected, the controller W2 and the pump P2 will be given priority by opening the pump contact P1.
N.B. The VOLTMAX boiler is not designed to heat without a water circulation in its tank. Therefore, if external pump controls are used, they must be interlocked with the operating authorization on W1 of the controller.
3.5.3 CONNECTION OF EXTERNAL SIGNALS TO THE CONTROLLER
The connection of all external signals is made directly on the boiler controller on terminals located on top of it. See the connection diagram on Figure 8 and Figure 9.
Cables used for the connections shall resist temperature up to 90 °C.
3.5.3.1 Connecting the building heat demand signal
Upon reception of a closed contact connected to terminals 24V+ and W1 or W2, the corresponding circulating pump P1 or P2 will start and the boiler will be allowed to operate.
If external controllers control the heating system pumps, they must provide the operating authorization signal. The boiler must not receive a heat demand without the circulation pumps running.
On heating systems when water circulation is continuous, the heat demand control can be connected to the 24V+ and W1 terminals. The heating elements will then be active and available only when there is a request (dry contact).
If the heating system is designed to keep water warm with continuous circulation, a jumper (jumper) must be installed on the 24V+ and W1 terminals to maintain the boiler in demand. The boiler will then attempt to maintain the water temperature at the set-point.
Operation with an upper fixed set-point W2 can be established by connecting the auxiliary heating demand signal (Dry contact) of a thermostat to the 24V+ and W2 of the terminal block.
In all operating modes of the controller, a heat demand on W1 and W2/DHW (close contact) must be present to DI1 or DI2 to allow the operation of the boiler. The only exception is in domestic hot water mode (DHW) with an indirect water heater where the minimum boiler temperature shall be maintained.
3.5.3.2 Connecting au auxiliary boiler
(Available only on SCR models)
The boiler controller is designed to allow the operation of a second boiler or an auxiliary gas or oil fired boiler according to two different mode of operation “Auxiliary Backup” or Dual-Energy”.
To do so, connect the TT terminals of the auxiliary boiler to terminals AUX of the VOLTMAX. The maximum capacity of this contact is 3A/120Vac.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 21.
3.5.3.3 Connection of an “Unoccupied signal”
of the building.
This function allows dropping the boiler temperature during periods where the building is not used and this without having to lower all the room thermostats of the building. To do so, a signal (dry contact) will have to be connected to terminal OCC. The contact shall be close during the periods of temperature drop. You can also manage the periods of temperature drop by setting the parameters from the internal clock of the controller.
3.5.3.4 Connection of an indirect domestic
hot water heater
The VOLTMAX electric boiler can be used not only to fill the heating requirements of the building but also to fill its domestic hot water needs using an indirect domestic hot water heater such as our TURBOMAX series. To do so, connect the signal (dry contact) of indirect water heater temperature control to the terminal 24V+ and W2/DHW. This will activate the circulating pump supplying the water heater (if properly installed).
3.5.3.5 Connection of a dual-energy signal
The VOLTMAX can be operated in a dual-energy mode with an auxiliary boiler.
To do so, connect the normally close contact of the dual energy controller to terminals 24V+ & BI- E to operate with the electric boiler. See section Erreur ! Source du renvoi introuvable. for more details on the sequence of operation in dual energy.
3.5.3.6 Connection of an outdoor temperature
sensor
If you wish to modulate the boiler water temperature according to the outdoor temperature (Outdoor Reset, ORST) and also wish to stop the operation of the boiler when the outdoor temp. reaches a selected value (See section Erreur ! Source du renvoi introuvable.), then the outdoor sensor supplied with the unit or a corresponding signal coming from the network system shall be connected to terminals S. Ext. of the controller. This sensor does not need to be connected if the boiler application is for a fixed set-point operation.
N.B. Do not install a jumper if the outside sensor is not used.
Outdoor sensor location
o Outside the building at a location that best
represents the heat demand of the building (a wall facing north for most of the buildings and on a south one on buildings with large windows facing south).
o It should not be exposed to external heat
sources (dryer outlet, window openings, non­insulated walls).
o It should not be installed in a location where it
could be covered with snow.
Installation:
1. Drill a 9/64” dia. hole through the wall and insert the sensor cable.
2. Fix the sensor cover to the wall using supplied screw.
3. With an electric cable (100ft max.) having 2 conductors 20ga. connect one end of this cable to the sensor cable using twist-on wire connectors and the other end to terminals S.
Ext (G. & AI2) of the boiler.
3.5.3.7 Remote controller used to determine
the target boiler temperature
An external controller (such as a central building energy management system) can be used to determine the boiler target temperature required for the building. To do so, the external controller shall give a 0 to 10VDC signal connected to terminals 0-10Vdc G & 0-10Vdc T° of the controller.
3.5.3.8 Power limiting device
An external controller providing a 0-10Vdc signal could be used to manage the capacity (kW) of the boiler. Example: An application where the main electrical service supply of the building is limited or when the electricity rate is billed according to the maximum peak loads of the building. To do so, the external controller shall be connected to terminals 0-10Vdc G & 0-10V cap. The capacity of the boiler could be manually limited by adjusting some of the controller parameters. See sections Erreur ! Source du renvoi introuvable. for more details
3.5.3.9 Alarm
An alarm signal (dry contact) is available on the boiler to advise the user of an alarm situation. The capacity of the contact is 3A resistive/1A inductive on terminal AL/AL
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 22.
Figure 8 : ELECTRICAL CONNECTIONS OF THE INPUT AND OUTPUT SIGNALS TO THE CONTROLLER (SCR MODEL)
Figure 9 : ELECTRICAL CONNECTIONS OF THE INPUT AND OUTPUT SIGNALS TO THE CONTROLLER (STG MODEL)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 23.
Figure 10: Control System Electrical Diagram (SCR model) (2 to 4 stages)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 24.
Figure 11: Control System Electrical Diagram (SCR model) (5 to 6 stages)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 25.
Figure 12: Control System Electrical Diagram (STG model) (2 to 6 stages)
Stage 1-1
SCR1
TITRE:
Diagramme électrique
VOLTMAX-SCR: 23 @ 72 kW
208-240V / 1ph
NOM DE FICHIER:
VOLTMAX-SCR: 72-208/
240/1PH
PAGE
1 de 1
DATE IMPRESSION:
No DESSIN:
THERMO 2000 inc.
500, 9e avenue Richmond (Québec)
J0B 2H0
REV. DESCRIPTION DATE Par/Verif
SCR-1
24
Com24VAC
-+
T1 L1
L1
L2
TX-1
240-208V
x120V
Alimentation 120V Supply
voir détails de contrôle/See control details
R: Relais de puissance / Power relay
Circuit 240 & 208 x 1 ph Circuit
Basse tension 120VAC Low voltage
L
1
N
120
VAC
de TX
-
1
LWCO
HL-MR HL-AR
1
CR1
CA
CB
CC
G
DO2-1
R-2
DO3-1
R-3
DO4-1
R-4
DO1-1
R-5
LWCO
(OPTION)
1/2A
24Vac
Extension
R14
Extension
R14
Extension
R14
Extension
R14
SCR
TX-2
120:24
40VA
Controler
TM171
Stage 2
Stage 3
Stage 4
Stage 5
Stage 6
CB
CC
SR-2
R-6
LWCO : Bas niveau d’eau / Low water cut off HL-MR: Haute limite manuel reset / High limit manual reset
HL-AR: Haute limite reset auto./ High limit automatic reset SCR: Relais de modulation / Modulating relay
C : Contacteur principal /Main contactor R: Relais de puissance / Power relay
Breaker
R2
R3
R4
R5
R6
Press.
T in
T out
RD
VT
GN
CR1- 2
HL&LWCO
W2/DHW
W1
120Vac
R2
stg-2R3stg-3R4stg-4
R5
stg-5
ALARM
POMPE
CHAUFF.
W1
POMPE
W2/
DHW
SCR
STATIC RELAY
OCC.
(On 5&6 stg models)
Note 1
COM.
Filage en usine Factory wiring
Filage au chantier Field wiring
CR-1
SR-1
0-10Vdc
AUX.
AUX.
24Vac+
24Vac-
Outdoor
T sensor
BACnet
MSTP
120 ohm
24Vac +
+
Sens. Ext.
RS485
Note 2
Note 2
24Vac-
24Vac
24Vac+
TM171PFE03
TM171EP14R
TM171EP14R
G DI4 DI3 DI2 DI1 AO2 AO1 G 24v+ 5v+ AI4 AI3 AI2 AI1 G 24VAC
DO1 DO2 DO3 DO4 N
DIP
SWITCH
CAN
24V:50mA 5V: 20mA
DO1 DO2 DO3 DO4 N
G DI4 DI3 DI2 DI1 AO2 AO1 G 24v+ 5v+ AI4 AI3 AI2 AI1 G 24VAC
24V:50mA 5V: 20mA
DIP
SWITCH
CAN
1 2 3 4 5 6 7
L H GS
1 2 3 4
1 2 3 4 5 6 7
L H GS
1 2 3 4
CAN
L H GS
G AI3 AI2
ETHERNET
GS
24Vac
BU
GN
GN
BK
BU
GY
TN
BK
WH
RD
BK
VT
BK
RD
VT
BN
BK
RD
WH
TN
BU
RD
BN
GY
YE
RD
GY
CT
GY
VT
YE
OG
YE
OG
24Vac+
GN
VT
GN
TN
RMSP
0-10Vdc
Cap.
T G
OG
BK
YE
BN
OG
YE
Bornes de raccordement de contrôles bas voltage Low voltage Control terminal strip
BU
BU
-
-
SR-2
120Vac
R6
NOTE 1: Ce contact est utilisé pour contrôler une chaudière auxiliaire sur les modèles ayant 4 stages et moins / This contact isused to control an auxiliary boiler on models having 4stages and less.
CA
BN
GN
TN
BK
BK
4 stg models
5 stg models
6 stg models
3 & 4 stg models
5 & 6 stg models
Stage 1
SCR
TITRE:
Diagramme électrique
VOLTMAX: 23 @ 75kW
208-240V/3ph
NOM DE FICHIER:
VOLTMAX
PAGE
1 de 1
DATE IMPRESSION:
No DESSIN:
THERMO 2000 inc.
500, 9e avenue Richmond (Québec)
J0B 2H0
REV. DESCRIPTION DATE Par/Verif
SCR
24
Com24VAC
-+
T1
L1
T2 L2
R2/B
R-4/B
L1 L2 L3
TX-1
208/240
x120V
Alimentation 120V Supply
voir détails de contrôle/See control details
CA
CB
CD
CE
Circuit 208V ou/or 240V x 3 ph Circuit
Basse tension 120VAC Low voltage
L
1
N
1
20
VAC
de TX
-
1
LWCO
HL-MR HL-AR
CR1
SCR
CA
CB
CC
CD
R-2A
R-4/A
G
DO2-1
R-2
R-5/B
R-5/A
DO3-1
R-3
DO4-1
R-4
DO1-1
R-5
CE
TDR
TDR
LWCO
24Vac
Extension
R14
Extension
R14
Extension
R14
Extension
R14
SCR
TX-2
120:24
Controler
TM171
LWCO : Bas niveau d’eau / Low water cut off HL-MR: Haute limite manuel reset / High limit manual reset
HL-AR: Haute limite reset auto./ High limit automatic reset SCR: Relais de modulation / Modulating relay C : Contacteur principal /Main contactor R: Relais de puissance / Power relay
Sectionneur /
disconnect
OPTION
R-3/B
R-3/A
Stage 2
Stage 3
EL#3
EL#2
EL#4
EL#5
CC
Fusible
(Voir note 1)
Remplacable par
un relais
standard 2 poles
Note 1: En Option sur les modèles dont l’ampérage max. est inférieure à 120A. / In option on models on models having an amperage of 120A and less.
Press.
T in
T out
RD
VT
GN
CR1- 2
HL&LWCO
W2/DHW
W1
120Vac
R2
stg-2R3stg-3R4stg-4
R5
stg-5
ALARM
POMPE
CHAUFF.
W1
POMPE
W2/
DHW
SCR
OCC.
(On 5 stg models)
Note 2
COM.
Filage en usine Factory wiring
Filage au chantier Field wiring
CR-1
SR-1
0-10Vdc
AUX.
AUX.
24Vac+
24Vac-
Outdoor
T sensor
BACnet
MSTP
120 ohm
24Vac +
+
Sens. Ext.
RS485
Note 2
Note 2
24Vac-
24Vac
24Vac+
TM171PFE03
TM171EP14R
TM171EP14R
G DI4 DI3 DI2 DI1 AO2 AO1 G 24v+ 5v+ AI4 AI3 AI2 AI1 G 24VAC
DO1 DO2 DO3 DO4 N
DIP
SWITCH
CAN
24V:50mA 5V: 20mA
DO1 DO2 DO3 DO4 N
G DI4 DI3 DI2 DI1 AO2 AO1 G 24v+ 5v+ AI4 AI3 AI2 AI1 G 24VAC
24V:50mA
5V: 20mA
DIP
SWITCH
CAN
1 2 3 4 5 6 7
L H GS
1 2 3 4
1 2 3 4 5 6 7
L H GS
1 2 3 4
CAN
L H GS
G AI3 AI2
ETHERNET
GS
24Vac
BU
GN
GN
BK
BU
GY
TN
BK
WH
RD
BK
VT
BK
RD
VT
BN
BK
RD
WH
TN
BU
RD
BN
GY
YE
RD
GY
CT
GY
VT
YE
OG
YE
OG
24Vac+
GN
VT
GN
TN
RMSP
0-10Vdc
Cap.
T G
OG
BK
YE
BN
OG
YE
Bornes de raccordement de contrôles bas voltage Low voltage Control terminal strip
BU
BU
-
-
BK
BK
Note 2: Ce contact est utilisé pour contrôler une chaudière auxiliaire sur les modèles ayant 4 stages et moins / This contact isused to control an auxiliary boiler on models having 4stages and less.
4 stg models
5 stg models
4 stg models
5 stg models
4 &5 stg models
Stage 1
SCR1
TITRE:
Diagramme élect. / Electrical dia.
VOLTMAX SCR 30@90 kW
480&600V / 3ph
NOM DE FICHIER:
VOLTMAX: 90- 480&600
PAGE
1 de 1
DATE IMPRESSION:
No DESSIN:
THERMO 2000 inc.
500, 9e avenue
Richmond (Québec)
J0B 2H0
REV. DESCRIPTION DATE Par/Verif
Stage 2
Stage 3
SCR-1
24
Com24VAC
-+
T1 L1
T2 L2
R2B
R3B
L1 L2 L3
TX-1
600:120
Alimentation 120V Supply
voir détails de contrôle/See control details
CA
CB
Circuit 480 ou 600V x 3 ph Circuit
Basse tension 120VAC Low voltage
L
1
N
120
VAC
de TX
-
1
LWCO
HL-MR HL-AR
1
CR1
E2
CA
CB
CC
R2/A
R3A
G
CC
DO2-1
Stage 5
R5B
R5A
Stage 4
R4B
R4A
DO3-1
R-3
DO4-1
R-4
DO1-1
R-5
LWCO
(Option)
24Vac
Extension
R14
Extension
R14
Extension
R14
Extension
R14
SCR
TX-2
120:24
40VA
Controler
TM171
LWCO : Bas niveau d’eau / Low water cut off HL-MR: Haute limite manuel reset / High limit manual reset HL-AR: Haute limite reset auto./ High limit automatic reset SCR: Relais de modulation / Modulating relay C : Contacteur principal /Main contactor R: Relais de puissance / Power relay
Sectionneur /
disconnect
OPTION
Fusible / Fuse
(note 2)
R-2
Fusible / Fuse
(note 2)
Fusible / Fuse
(note 2)
Note 1:
Lorsque le stage 5 n’est pas utilisé, ce contact sert au démarrage de la chaudière Auxiliaire / When stage 5 is not used, this contact will be used to control the Auxiliary boiler. Note 2:
Offert en Option sur les modèles dont le courant nominal est de 120A et moins / Optional on models having a nominal amperage less than 120A. Note 3:
La configuration des éléments peut être en « Delta » ou en « Y » / Heating element configuration could be in « Delta » or « Y ».
Press.
T in
T out
RD
VT
BK
CR1- 2
HL&LWCO
Bi-Energ.
W2/DHW
W1
120Vac
R2
stg-2R3stg-3R4stg-4
R5
stg-5
ALARM
POMPE
CHAUFF.
W1
POMPE
W2/
DHW
SCR
STATIC RELAY
OCCUPATION
30 @ 90 kW
(On 5 stg models)
Note 1
COM.
Filage en usine Factory wiring
Filage au chantier Field wiring
CR-1
SR
0-10Vdc
AUX.
AUX.
24Vac+
24Vac-
Outdoor
T sensor
BACnet
MSTP
120 ohm
24Vac +
+
Sens. Ext.
RS485
Note 2
Note 2
24Vac-
24Vac
24Vac+
TM171PFE03
TM171EP14R
TM171EP14R
G DI4 DI3 DI2 DI1 AO2 AO1 G 24v+ 5v+ AI4 AI3 AI2 AI1 G 24VAC
DO1 DO2 DO3 DO4 N
DIP
SWITCH
CAN
24V:50mA
5V: 20mA
DO1 DO2 DO3 DO4 N
G DI4 DI3 DI2 DI1 AO2 AO1 G 24v+ 5v+ AI4 AI3 AI2 AI1 G 24VAC
24V:50mA 5V: 20mA
DIP
SWITCH
CAN
1 2 3 4 5 6 7
L H GS
1 2 3 4
1 2 3 4 5 6 7
L H GS
1 2 3 4
CAN
L H GS
G AI3 AI2
ETHERNET
GS
24Vac
BU
GN
GN
BK
BU
GY
TN
BK
WH
RD
BK
VT
BK
RD
VT
BN
BK
RD
WH
TN
BU
RD
BN
GY
YE
RD
YE
CT
GY
VT
YE
OG
YE
OG
24Vac+
GN
VT
GN
TN
RMSP
0-10Vdc
Cap.
T G
OG
BK
YE
BN
OG
YE
Chaudière Aux.
Auxiliary boiler
Bornes de raccordement de contrôles bas voltage Low voltage Control terminal strip
BU
BU
-
-
30@90
30@90
45@90
60@90
75@90
Model 30@90
Model 45@90
Model 60@90
Model 75@90
Model 30@90
Model 45@90
Model 75@90
GN
(note 3)
(note 3)
(note 3)
(note 3)
(note 3)
Stage 1-1
SCR1
TITRE:
Diagramme électrique
VOLTMAX- SCR: 99 @ 180 kW
480 & 600V / 3PH
NOM DE FICHIER:
VOLTMAX 180KW/480-600
PAGE
1 de 1
DATE IMPRESSION:
No DESSIN:
REV. DESCRIPTION DATE Par/Verif
Stage 2-1
Stage 3-1
SCR-1
24
Com24VAC
-+
T1 L1
T2 L2
R-2/B
R-3/B
L1 L2 L3
TX-1
600:120
Alimentation 120V Supply
voir détails de contrôle/See control details
CA
CB
CC
CD
Circuit 480 ou 600V x 3 ph Circuit
Basse tension 120VAC Low voltage
L1
N
120
VA
C
de T
X
-
1
LWCO
HL-MR HL-AR
1
CR1
E2
SCR
CA
CB
CC
CD
R-2/A
R-3/A
G
E1
Stage 1-2
SCR1
Stage 2-2
Stage 3-2
CE
DO2-1
R-2
Stage 5-1
R-5/B
R-5/A
Stage 5-2
Stage 4-1
R-4/B
R-4/A
Stage 4-2
DO3-1
R-3
DO4-1
R-4
DO1-1
R-5
CE
TDR
TDR
LWCO
(Note 3)
24Vac
Extension
R14
Extension
R14
Extension
R14
Extension
R14
SCR
TX-2
120:24
Press.
T in
T out
RD
VT
GN
CR1- 2
HL&LWCO
Bi-Energ.
W2/DHW
W1
120Vac
R2
stg-2R3stg-3R4stg-4
R5
stg-5
ALARM
POMPE
CHAUFF.
W1
POMPE
W2/
DHW
SCR
STATIC RELAY
OCCUPATION
99 @ 180 kW
(On 5 stg models)
Note 2
COM.
Filage en usine Factory wiring
Filage au chantier Field wiring
Controler
TM171
CR-1
SR
0-10Vdc
AUX.
AUX.
24Vac+
24Vac-
LWCO : Bas niveau d’eau / Low water cut off HL-MR: Haute limite manuel reset / High limit manual reset HL-AR: Haute limite reset auto./ High limit automatic reset
SCR: Relais de modulation / Modulating relay
C : Contacteur principal /Main contactor
R: Relais de puissance / Power relay
Sectionneur /
disconnect
OPTION
Fusible /Fuse
(note 1)
Note 1:
En Option sur les modèles dont l’ampérage
max. est inférieure à 120A /Optional on models having an amperage less thant 120A. Note 2
: Ce contact est utilisé pour contrôler une chaudière auxiliaire sur les modèles ayant 4 stages et moins / This contact is used to control an auxiliary boiler on models having 4stages and less. Note 3:
En option sur les modèles de 120kW à 180 kW/ In option on models of 120 to 180kW Note 4:
La configuration des éléments peut être en « Delta » ou en « Y » / Heating element configuration could be in « Delta » or « Y ».
Outdoor
T sensor
BACnet
MSTP
120 ohm
24Vac +
+
Sens. Ext.
RS485
Note 2
Note 2
24Vac-
24Vac
24Vac+
TM171PFE03
TM171EP14R
TM171EP14R
G DI4 DI3 DI2 DI1 AO2 AO1 G 24v+ 5v+ AI4 AI3 AI2 AI1 G 24VAC
DO1 DO2 DO3 DO4 N
DIP
SWITCH
CAN
24V:50mA 5V: 20mA
DO1 DO2 DO3 DO4 N
G DI4 DI3 DI2 DI1 AO2 AO1 G 24v+ 5v+ AI4 AI3 AI2 AI1 G 24VAC
24V:50mA
5V: 20mA
DIP
SWITCH
CAN
1 2 3 4 5 6 7
L H GS
1 2 3 4
1 2 3 4 5 6 7
L H GS
1 2 3 4
CAN
L H GS
G AI3 AI2
ETHERNET
GS
24Vac
BU
GN
GN
BK
BU
GY
TN
BK
WH
RD
BK
VT
BK
RD
VT
BN
BK
RD
WH
TN
BU
RD
BN
GY
YE
RD
GY
CT
GY
VT
YE
OG
YE
OG
24Vac+
GN
VT
GN
TN
RMSP
0-10Vdc
Cap.
T G
OG
BK
YE
BN
OG
YE
Chaudière Aux. Auxiliary boiler
Bornes de raccordement de contrôles bas voltage Low voltage Control terminal strip
THERMO 2000 INC 500, 9e Ave Richmond, QC
BU
BU
-
-
Model 99@180
Model 120@180
Model 120@180
Model 99@144
Model 150@180
150@180
120@180
99@180
99@180
Model 99@108
Model 99@108
99@180
Model 99@180
Model 99@180
Model 99@180
BK
Note 4
Note 4
Note 4
Note 4
Note 4
TITRE:
Diagramme électrique
VOLTMA-STG: 23 @ 72 kW
208-240V / 1ph
NOM DE FICHIER:
VOLTMAX-SCR: 72-208/
240/1PH
PAGE
1 de 1
DATE IMPRESSION:
No DESSIN:
THERMO 2000 inc.
500, 9e avenue Richmond (Québec)
J0B 2H0
REV. DESCRIPTION DATE Par/Verif
L1
L2
TX-1
240-208V
x120V
Alimentation 120V Supply
voir détails de contrôle/See control details
R: Relais de puissance / Power relay
Circuit 240 & 208 x 1 ph Circuit
Basse tension 120VAC Low voltage
L
1
N
120
VAC
de TX
-
1
LWCO
HL-MR HL-AR
CR1
CA
CB
CC
G
DO2-1
R-1
DO3-1
R-2
DO4-1
R-3
DO1-1
R-4
LWCO
(OPTION)
24Vac
Extension
R14
SCR
TX-2
120:24
40VA
Controler
TM171
Stage 2
Stage 3
Stage 4
Stage 5
Stage 6
CB
CC
SR-1
R-5
LWCO : Bas niveau d’eau / Low water cut off
HL-MR: Haute limite manuel reset / High limit manual reset
HL-AR: Haute limite reset auto./ High limit automatic reset SCR: Relais de modulation / Modulating relay
C : Contacteur principal /Main contactor R: Relais de puissance / Power relay
Breaker
R2
R3
R4
R5
R6
CA
4 stg models
5 stg models
6 stg models
3 & 4 stg models
5 & 6 stg models
T out
RD
VT
BK
CR1- 2
HL&LWCO
W2/DHW
W1
120Vac
R5
stg-5
R2
stg-2R3stg-3
R4
stg-4
Filage en usine Factory wiring
Filage au chantier Field wiring
SR
24Vac+
Outdoor T sensor
BACnet
MSTP
24Vac
+
Sens. Ext.
RS485
Note 2
24Vac-
24Vac
TM171PFE03
TM171EP14R
G DI4 DI3 DI2 DI1 AO2 AO1 G 24v+ 5v+ AI4 AI3 AI2 AI1 G 24VAC
DO1 DO2 DO3 DO4 N
DIP
SWITCH
CAN
24V:50mA 5V: 20mA
1 2 3 4 5 6 7
L H GS
1 2 3 4
CAN
L H GS
G AI3 AI2
ETHERNET
GS
24Vac
GN
GN
BK
BU
GY
TN
BK
WH
RD
BK
TN
BU
RD
GY
YE
YE
OG
OG
BK
OG
YE
Bornes de raccordement de contrôles bas voltage Low voltage Control terminal strip
R1
stg-1
Stage 1
R1
3 stg models
SR-2
R-5
R6
stg-6
SR
TITRE:
Diagramme électrique
VOLTMAX- STG: 23 @ 75kW
208-240V/3ph
NOM DE FICHIER:
VOLTMAX
PAGE
1 de 1
DATE IMPRESSION:
No DESSIN:
THERMO 2000 inc.
500, 9e avenue Richmond (Québec)
J0B 2H0
REV. DESCRIPTION DATE Par/Verif
R2/B
R-4/B
L1 L2 L3
TX-1
208/240
x120V
Alimentation 120V Supply
voir détails de contrôle/See control details
CB
CD
CE
Circuit 208V ou/or 240V x 3 ph Circuit
Basse tension 120VAC Low voltage
L
1
N
1
20
VA
C
d
e
T
X
-
1
LWCO
HL-MR HL-AR
CR1
SCR
CA
CB
CC
CD
R-2A
R-4/A
G
DO2-1
R-1
R-5/B
R-5/A
DO3-1
R-2
DO4-1
R-3
DO1-1
R-4
CE
TDR
TDR
LWCO
(Option)
24Vac
Extension
R14
SCR
TX-2
120:24
Controler
TM171
LWCO : Bas niveau d’eau / Low water cut off HL-MR: Haute limite manuel reset / High limit manual reset
HL-AR: Haute limite reset auto./ High limit automatic reset SCR: Relais de modulation / Modulating relay C : Contacteur principal /Main contactor R: Relais de puissance / Power relay
Sectionneur /
disconnect
OPTION
R-3/B
R-3/A
Stage 2
Stage 3
EL#3
EL#2
EL#4
EL#5
CC
Fusible
(Voir note 1)
Note 1: En Option sur les modèles dont l’ampérage max. est inférieure à 120A. / In option on models on models having an amperage of 120A and less.
4 stg models
5 stg models
4 stg models
5 stg models
4 &5 stg models
T out
RD
VT
BK
CR1- 2
HL&LWCO
W2/DHW
W1
120Vac
R5
stg-5
R2
stg-2R3stg-3
R4
stg-4
Filage en usine Factory wiring
Filage au chantier Field wiring
SR
24Vac+
Outdoor T sensor
BACnet
MSTP
120 ohm
24Vac
+
Sens. Ext.
RS485
Note 2
24Vac-
24Vac
TM171PFE03
TM171EP14R
G DI4 DI3 DI2 DI1 AO2 AO1 G 24v+ 5v+ AI4 AI3 AI2 AI1 G 24VAC
DO1 DO2 DO3 DO4 N
DIP
SWITCH
CAN
24V:50mA
5V: 20mA
1 2 3 4 5 6 7
L H GS
1 2 3 4
CAN
L H GS
G AI3 AI2
ETHERNET
GS
24Vac
GN
GN
BK
BU
GY
TN
BK
WH
RD
BK
TN
BU
RD
GY
YE
YE
OG
OG
BK
OG
YE
Bornes de raccordement de contrôles bas voltage Low voltage Control terminal strip
R1
stg-1
R-1B
CB
R-1A
Stage 1
EL#1
SR-1
R-5
5 stg models
3 stg models
Stage 1
TITRE:
VOLTMAX -STG : 30@90 kW
480&600V / 3ph
NOM DE FICHIER:
VOLTMAX 90- 480&600V
PAGE
1 de 1
DATE IMPRESSION:
No DESSIN:
THERMO 2000 inc.
500, 9e avenue
Richmond (Québec)
J0B 2H0
REV. DESCRIPTION DATE Par/Verif
Stage 2
Stage 3
R-2/B
R-3/B
L1 L2 L3
TX-1
600:120
Alimentation 120V Supply
voir détails de contrôle/See control details
CA
CB
Circuit 480 ou 600V x 3 ph
Basse tension 120VAC Low voltage
L
1
N
1
20
VA
C
d
e
T
X
-
1
LWCO
HL-MR HL-AR
CR1
E2
CA
CB
CC
R-2/A
R-3/A
G
CC
DO2-1
Stage 5
R-5/B
R-5/A
Stage 4
R-4/B
R-4/A
DO3-1
R-2
DO4-1
R-3
DO1-1
R-4
LWCO
(Option)
24Vac
Extension
R14
TX-2
120:24
40VA
120Vac
Controler
TM171
LWCO : Bas niveau d’eau / Low water cut off (Option) HL-MR: Haute limite manuel reset / High limit manual reset HL-AR: Haute limite reset auto./ High limit automatic reset C : Contacteur principal /Main contactor R: Relais de puissance / Power relay
R-1
R-1A
R-1/B
SR-AO1-1
R-5
SR: Relais statique / Static relay
T out
RD
VT
BK
CR1- 2
HL&LWCO
W2/DHW
W1
120Vac
R5
stg-5
R2
stg-2R3stg-3
R4
stg-4
Filage en usine Factory wiring
Filage au chantier Field wiring
SR
24Vac+
Outdoor T sensor
BACnet
MSTP
120 ohm
24Vac
+
Sens. Ext.
RS485
Note 2
24Vac-
24Vac
TM171PFE03
TM171EP14R
G DI4 DI3 DI2 DI1 AO2 AO1 G 24v+ 5v+ AI4 AI3 AI2 AI1 G 24VAC
DO1 DO2 DO3 DO4 N
DIP
SWITCH
CAN
24V:50mA 5V: 20mA
1 2 3 4 5 6 7
L H GS
1 2 3 4
CAN
L H GS
G AI3 AI2
ETHERNET
GS
24Vac
GN
GN
BK
BU
GY
TN
BK
WH
RD
BK
TN
BU
RD
GY
YE
YE
OG
OG
BK
OG
YE
Bornes de raccordement de contrôles bas voltage Low voltage Control terminal strip
R1
stg-1
Fusible / Fuse
(note 1)
Fusible / Fuse
(note 1)
Note 1:
Offert en Option sur les modèles dont le courant nominal est de 120A et moins / Offered in option on models having a nominal amperage less than 120A.
Fusible / Fuse
(note 1)
45@90
30@90
60@90
75@90
3 STG MODELS
2 STG MODELS
4 STG MODELS
5 STG MODELS
3 &4 STG MODELS
5 STG MODELS
Note 2:
La configuration des éléments peut être en « Delta » ou en « Y » / Heating element configuration could be in « Delta » or « Y ».
(Note 2)
(Note 2)
(Note 2)
(Note 2)
(Note 2)
Stage 1-1
SCR1
TITRE:
VOLTMAX-STG: 99 @ 180 kW
480 & 600V / 3PH
NOM DE FICHIER:
VOLTMAX 180KW/480-600
PAGE
1 de 1
DATE IMPRESSION:
No DESSIN:
REV. DESCRIPTION DATE Par/Verif
Stage 2-1
Stage 3-1
R-2/B
R-3/B
L1 L2 L3
TX-1
600:120
Alimentation 120V Supply
voir détails de contrôle/See control details
CA
CB
CC
CD
Circuit 480 ou 600V x 3 ph Circuit
Basse tension 120VAC Low voltage
L1
N
120
VA
C
de T
X
-
1
LWCO
HL-MR HL-AR
CR1
CA
CB
CC
CD
1/2A
R-2/A
Model 150 à 180
G
Stage 1-2
SCR1
Stage 2-2
Stage 3-2
CE
DO2
R-1
Stage 5-1
R-5/B
R-5/A
Stage 5-2
Stage 4-1
R-4/B
R-4/A
Stage 4-2
DO3
R-2
DO4
R-3
DO1
R-4
CE
TDR
TDR
LWCO Note 2
24Vac
Extension
R14
TX-2
120:24
T out
RD
VT
GN
CR1- 2
HL&LWCO
W2/DHW
W1
120Vac
R5
stg-5
R2
stg-2R3stg-3
R4
stg-4
99 @ 180 kW
Filage en usine Factory wiring
Filage au chantier Field wiring
Controler
TM171
SR
24Vac+
LWCO : Bas niveau d’eau / Low water cut off HL-MR: Haute limite manuel reset / High limit manual reset HL-AR: Haute limite reset auto./ High limit automatic reset
SCR: Relais de modulation / Modulating relay
C : Contacteur principal /Main contactor
R: Relais de puissance / Power relay
Sectionneur /
disconnect
OPTION
Fusible /Fuse
(note 1)
Note 1
: En Option sur les modèles dont l’ampérage max. est inférieure à 120A / Optional on models having an amperage less thant 120A. Note 2:
En Option sur les modèles de moins de
120kW / Optional on models less than 120kW
1/2A
Outdoor T sensor
BACnet
MSTP
120 ohm
24Vac
+
Sens. Ext.
RS485
Note 2
24Vac-
24Vac
TM171PFE03
TM171EP14R
G DI4 DI3 DI2 DI1 AO2 AO1 G 24v+ 5v+ AI4 AI3 AI2 AI1 G 24VAC
DO1 DO2 DO3 DO4 N
DIP
SWITCH
CAN
24V:50mA 5V: 20mA
1 2 3 4 5 6 7
L H GS
1 2 3 4
CAN
L H GS
G AI3 AI2
ETHERNET
GS
24Vac
GN
GN
BK
BU
GY
TN
BK
WH
RD
BK
TN
BU
RD
GY
YE
YE
OG
OG
BK
OG
YE
Bornes de raccordement de contrôles bas voltage Low voltage Control terminal strip
THERMO 2000 INC 500, 9e Ave Richmond, QC
R1
stg-1
R-1/B
R-1/A
SR1
R-5
R-1
Model 99 à 144
Model 99 à 180
Model 120 à 180
Modèles 120 à 144
150 @ 180
120 @ 180
Modèles 150 à 180
99@180
99@180
99@180
Model 99@108
Model 99@108
Model 99@108
Model 99@108
Model 99@108
Model 99@108
Model 120 à 180
Note 3:
La configuration des éléments peut être en « Delta » ou en « Y » / Heating element configuration could be in « Delta » or « Y ».
(Note 3)
(Note 3)
(Note 3)
(Note 3)
(Note 3)
(Note 3)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 34.
SECTION 4 : CONTROLLER OPERATION
4.1 USER INTERFACE
The control of the boiler is ensured by a controller TM171PFE03 of the company Schneider Electric. The LCD display of the controller provides an interface for configuring and displaying the boiler parameters.
A communication module also allows you to integrate the controller with an intelligent building management system (BACnet protocol). It is also equipped with an Ethernet connection. Allowing the connection to the Internet network of the building allowing to read and modify locally or remotely the boiler setting. It can be configured to send alarm messages via e-mail.
Icons will also display to indicate the boiler’s current operating status. Temperature can be displayed in Celsius or Fahrenheit and text can be set to either English or French.
The controller has a backlight function. It is also equipped with three indicator lights (Green / Yellow / Red). The green light indicates normal operation of the unit; the yellow light indicates that the controller has diagnosed and anomaly which requires verification by a technician. The red light indicates that the unit is currently in a critical state (high temperature alarm) or in lock out mode. More detail is provided in Section 6: Troubleshooting. The controller can also be configured to activate an audible alarm and activate an external alarm signal when an alarm
condition occurs causing the boiler to fail.
Figure 13 : Illustration of the display
4.1.1 SYMBOL DESCRIPTION
The main display shows most the boiler operation status information. The explanation of the main display is shown below.
Boiler operating mode
W1
Heating request 1 : On
W2
Heating request 2 : On
P1
Pump 1 : On
P2
Pump 2 : On
BIE
Boiler in Bi-Energy mode
VOLTMAX Boiler : On
Bi-energy operation with auxiliary boiler
Boost mode
: On
Warm Weather Shut Down
: On
Alarm symbol
An alarm is active
The boiler is in lock
out mode
HL
High limit temperature is reached
LL
Low limit (Lack of capacity)
P
Alarm due to a pressure problem
A
Alarm due to an electrical problem
F
Alarm due to a flow problem
Se
Alarm due to a sensor problem
Operating state of the boiler
T° SET­POINT
Actual
set-point
temperature
T° BOILER
Water temperature at the outlet of the boiler
CAP
(%)
Percentage of power used according to boiler rated power
T° EXT
Outdoor temperature measured using the outdoor sensor
KW ACT
Actual power used by the boiler
PRESS.
Pressure inside the boiler
STAGE
Status of active stage
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 35.
4.1.2 CONTROL PANEL
Figure 14 : Control panel
On the left side of the appliance, an on / off switch (# 3) is used to operate the appliance and to reset the boiler.
An indicator light showing the status of the low water level cut off and a test button (# 1) is standard for models 120 kW and above. The control circuit fuses (# 2) are accessible from the left side of the unit.
4.1.3 NAVIGATION AND ADJUSTEMENTS
The navigation within the display is done with the five pushbuttons on the right of the screen.
Navigation between the elements is done with the up and down arrows. Use the right key to change the page in the menus. The return key will bring you to the previous menu. The return key returns you to the main display when it is pressed for 2 seconds or more.
The OK button confirms the selection and allows you to edit a parameter. Only highlighted box can be modified. To modify an option, select the box to modify with the arrow keys and press OK. Change the value of the option using the arrows and confirm the change by pressing OK.
1
2 3 4
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 36.
4.1.4 MAIN MENU NAVIGATION
Figure 15 : Main menu navigation
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 37.
4.1.5 NAVIGATION IN BOILER SETTING
Figure 16 : Navigation in boiler setting menu (1/2)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 38.
Figure 17 : Navigation in boiler setting menu (2/2)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 39.
4.2 MAIN MENU
The main menu is accessible to the user, no access code is required. The main menu is accessed by pressing one of the 5 pushbuttons. Navigation between menu is done with the arrows (up, down, left and right).
Menu
Contents
Boiler status
Detailed information on the boiler condition
Boiler setting
Configuration of the boiler operating mode.
User setting
Configuration of the controller display option
Clock setting
Configuration of the internal clock
Consumption
Power consumption of the boiler
4.2.1 BOILER STATUS
Detailed information on the boiler condition
This menu allows the display of data not included in the main display. The boiler status menu display the measurements of temperature, pressure, flow, alarm summary, version of the programme
The set of variables presented in this menu are presented in Section 4.5
4.2.2 BOILER CONFIGURATION
Configuration of the boiler operating mode
This menu is accessible only to the installer or to an authorized person.
The options in the Boiler setting menu are detailed in Section 4.3.
The Manufacturer access code gives access to advanced operating parameters that are not accessible to the installer and the user.
4.2.3 USER SETTING
Configuration of the controller display option
This menu allows the modification of different display parameters.
Parameters
Description
Language
Select English or French version
Temperature unit
Select the temperature units, either Celsius (C) or Fahrenheit (F)
Flow unit
Select the flow unit, either US gallons per minute (USgpm) or liters per second (L / sec)
Backlight
Setting the backlight mode
Internal buzzer
Setting of the internal buzzer
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 40.
4.2.4 CLOCK SETTING
Internal clock configuration
Use this menu to adjust the controller’s internal clock. To set the clock correctly, you must adjust the time, minutes, and date.
This adjustment is necessary in order for these modes to function properly:
- The boiler’s power consumption
- Limiting the boiler’s power capacity according to a schedule
- The boiler’s occupation mode
Battery life for the clock is at least 1 year when the controller is unpowered (at 25°C).
N.B. The date and day of the week must be set correctly to ensure the controller automatically changes to daylight savings time.
4.2.5 CONSUMPTION
Boiler consumption cycle report
This menu allows visualization of the boiler power consumption report. First, you must activate the beginning of the consumption cycle with the Start key. The consumption report can be saved using the Save key. And all saved report is available on the History tab. The beginning of the consumption cycles can be reset using the Reset button.
The controller records up to 30 consumption report.
N.B. For the STG model, the calculation of power consumption is based on a theoretical approach, there may be differences between the actual consumption of the boiler and the consumption displayed on the screen. For the SCR model, the amp meter is used to calculated the power consumption of the boiler.
4.3 BOILER SETTINGS
In order to be able to configure the boiler, it is necessary to authenticate yourself with an installer or manufacturer code.
The default "Installer" access code is 1111 and can be changed in the Change password menu.
HEATING
MODE W1
Boiler heating mode W1 configuration according to the type of application
HEATING
MODE
W2/DHW
Boiler heating mode W2 or DHW
configuration accor
ding
to the type of application
PUMP
SETTING
Pump contact configurations
CAPACITY
LIMITING
C
apacity limiting mode
configuration
AUXILIARY
BOILER
Auxiliary
boiler mode
configuration
(if needed)
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 41.
LIMIT SETTING
Configuration of the boiler operating limits
ALARM
Configuration of the alarms
COMMUNICATION
Configuration of the boiler communication parameter
OCCUPATION
Configuration of the occupation parameter mode
MODE BOOST
Enable Boost mode
WARM WEATHER
SHUTD.
Enable warm weather shut-down function
CHANGE
PASSWORD
Changing the Installer password
4.3.1 HEATING MODE W1 Selection of the operating mode
In this menu, you must select an operation mode depending on the application required by your installation. A heat demand must be present on W1 and/or W2/DHW so that the boiler can heat up. During a heat demand, the boiler activates (depending on a PID curve) the number of stages required in sequence so that the boiler output temperature is maintained at the approximate set-point temperature.
Here is the list of W1 heating modes:
FIXED
Fixed boiler set-point
DDC 0­10 VDC
Modulation of the boiler set-point using a 0-10VDC signal
OUTD RESET
Modulation of the boiler set-point using the outdoor temperature
STOP
No heating demand on W1
4.3.1.1 Fixe
This mode is used for an installation where it is desired to have a fixed set-point temperature. If the boiler is thermostat-controlled with a heat demand signal on W1, the boiler uses the corresponding set-point (T. Set-point W1) as the supply temperature.
4.3.1.2 DDC 0-10 VDC (Available only on SCR model)
This operating mode allows modulating the boiler set-point temperature according to a 0­10VDC signal applied the terminal 0-10VDC and G, produced by an external controller (Ex: Building Energy Management Controller).
The details of the parameters in this mode are presented in Section 4.6.3.
4.3.1.3 Outdoor reset
This operating mode makes it possible to modulate the boiler output set-point temperature as a function of the outdoor temperature. The outdoor temperature signal comes from the temperature sensor supplied with the boiler, which will be connected to the boiler controller.
The details of the parameters are presented in
Section 4.6.2 .
4.3.1.4 Stop
Select this mode when there is no boiler heating demand on W1.
4.3.2 HEATING MODE W2/DHW
This mode allows you to configure a second heating demand (W2) or a demand from an indirect domestic water heater (DHW). Select none if none of these functions are used. These modes are presented in detail in Section
4.7.
W2
This mode allows the W2-DHW input to be used to receive a signal (dry contact) from a 2nd stage of heating. When the contact on W2-DHW closes, the set­point temperature changes to the set value (T. Set-point W2), even if there is no demand on W1.
DHW
This mode allows you to configure the demand for an indirect domestic water heater. When the DHW mode is selected, the boiler is kept at a minimum temperature (T. Min Boiler) and when contact W2 closes (Dry contact) the set-point rises equivalent to T. DHW Set-point. In addition, the PID curve is more aggressive.
4.3.3 PUMP SETTING
Configuring pump contact activation (Available only on SCR model)
The system allows the control of up to two pumps. Each of these pumps can be activated using a contact (Max 3 Amp.). Each pump can be activated according to different modes.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 42.
Pump Configuration Options
On W1 Dem.
Contact of pump 1 is activated only when there is a demand on W1.
On W2 Dem.
Contact of pump 2 is activated only when there is a demand in W2.
Priority over P1
When there is a request on W2, contact of pump 2 is activated and contact of pump 1 is deactivated.
Always On
The selected pump is always on (contact is always on).
Stop
The selected pump is always deactivated (contact is always off).
Off
Delay
The delay in seconds before the contact of the pump is deactivated.
4.3.4 CAPACITY LIMITING
Adjusting the maximum authorized power
This menu allows you to configure the boiler output limit. The selection of the limit mode can be selected in the Capacity limiting menu
o None o Manual o DDC 0-10 VDC o T. Ext o Schedule
Details of each of these options are presented in Section 4.9 . N.B: It is not recommended to disconnect one of the power relays to accomplish this function.
4.3.4.1 NONE
The boiler is not limited in power, the maximum power it can deliver is equivalent to its maximum rated power.
4.3.4.2 MANUAL
The maximum capacity permitted of the boiler is configured in a fixed mode. Details of the variables in this mode are presented in Section 4.9.1
4.3.4.3 DCC 0-10 VDC
(Available only on SCR model)
A 0-10 VDC signal from a building management system can be used. The signal is treated as a function in order to limit the maximum power. In order to configure this mode, you must connect the 0-10 VDC signal to the terminal block 0-10Vdc Cap. and 0-10Vdc G. Details of the variables in this mode are presented in Section 4.9.2
4.3.4.4 T. EXT
The maximum permitted power can be adjusted according to the outside temperature sensor. The outdoor temperature is used in order to limit the maximum authorized power. Details of the variables in this mode are presented in Section 4.9.3 .
4.3.4.5 Schedule
The maximum authorized boiler power can be programmed according to a schedule. See section 4.9.4 for an explanation of how to modify a schedule.
4.3.5
AUXILIARY BOILER
(Available only on SCR model)
The controller program has been designed to allow the operation of a second boiler or auxiliary gas or oil boiler. In order for the VOLTMAX controller to be able to record a rise in temperature caused by the operation of the auxiliary boiler, the piping installation must be
carried out in series. The heating return must first pass through the auxiliary boiler before entering the boiler.
Back up boiler operation
In the event of a lack of capacity, the boiler is started to compensate. The lack of capacity is defined by the fact that the boiler output temperature is less than X degrees (Delta T. Start Aux.) relative to the set­point for duration of X min. (Auxiliary Start Delay). The auxiliary boiler will be deactivated
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 43.
when the temperature differential between the water outlet temperature and the set-point temperature is lower than Delta T. Off Aux. The operation of the auxiliary boiler is explained in detail in Section 4.10
The source of the set-point temperature control can be configured by selecting STPT source Aux. Consequently. The set-point temperature control can be dictated by the auxiliary boiler by selecting the External mode. The VOLTMAX boiler thus has no set temperature and is only used to activate the auxiliary boiler relay. The various configurations of the Aux boiler mode are the following :
None
No auxiliary boiler is present
Backup Aux.
This mode allows the adjustment of a second boiler to play a Backup role
Ext Contact
Select the heating source using electrical contact to the BI-E terminal.
BiE (BI­Energy)
Select the heating source using electrical contac
t to the BI-
E terminal
with the possibility of support mode of the auxiliary boiler.
Manual
Manually select the system operation mode (Electrical or Auxiliary).
N.B. The auxiliary boiler can only be switched on when a heat demand is present on W1 or / and W2 / DHW.
4.3.5.1 None
This mode must be active when there is no auxiliary boiler on the hydronic heating system.
4.3.5.2 Backup Aux.
The boiler will be activated according to the configuration of the lack of capacity. Details of the variables in this mode are presented in Section 4.10.1
4.3.5.3 Contact Ext.
This configuration mode makes it possible to operate the electric boiler or the auxiliary boiler according to a contact. During a close contact at
the BI-E terminals, the electric boiler (
) is
activated. When the contact is open, the auxiliary boiler ( ) will be on. The auxiliary
boiler will not be allowed to operate if the electric boiler lacks capacity. Details of the variables in this mode are presented in Section 0
4.3.5.4 BiE (BI-Energy)
The Bi-Energy mode allows the auxiliary boiler to operate when there is a lack of capacity. The auxiliary boiler will then be activated to help the electric boiler reach its set temperature according to the operating parameters
Upon receipt of an electrical signal (contact closed at Bi-E) and a request at the terminal of W1 or W2, the contact at the terminal of AUX
will be opened and thus the electric boiler ( ) is allowed to operate and the auxiliary boiler is deactivated.
When an electrical signal is absent (contact open at Bi-E) and a request is present at the terminals of W1 or W2, the contact will close at the terminal of AUX, in order to operate the
boiler Auxiliary ( ) and not the electric boiler. Details of the variables in this mode are presented in Section 4.10.4 .
4.3.5.5 Manual
Manual mode is used to manually select the operating mode of the system (Electrical or Auxiliary). Details of the variables in this mode are presented in Section 4.10.3
4.3.6 LIMIT SETTING
Configuring the boiler operating limits
Use this menu to adjust the permissible operating boiler limits for various parameters.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 44.
This menu’s configuration options are presented in detail in Section 4.11.
4.3.7 ALARM
Alarm Mode Configuration
When an alarm is active, it will be displayed on the main display as a symbol.
An alarm is active
The boiler is in lock mode
HL
The high limit temperature has been reached
LL
Low limit (Lack of capacity)
P
Pressure problem alarm
A
Electrical problem alarm
F
Flow problem alarm
Se
Sensor problem alarm
Ex: If P and Se are displayed at the same time, this indicates a pressure sensor problem
A summary of active alarms is also available in the Boiler status menu.
An alarm report is available under the Alarm log menu. Information about date, time and alarm code is available in this menu. The internal clock must be adjusted beforehand so that the alarm registers correctly. Section 6 - Troubleshooting details alarm codes and settings specific to this menu.
Details about this menu’s operation are available
in Section 4.12
4.3.8 COMMUNICATION
The boiler controller can be connected via an Ethernet network communication port or using a BACNet protocol. The boiler web portal can be accessed in a variety of ways. You will be able to modify the parameters remotely on a web portal and to visualize the anomalies.
Direct connection between the controller and a computer.
1. Connect the boiler controller to your local
network or directly to your computer in an internet port using an RJ45 network cable (located on the back of the controller). Refer to the wiring diagram, if you have any questions.
2. Open the Network and sharing center,
then Change adapter setting on a windows operating system. Open the Local area
connection properties, then Internet Protocole Version 4 (TCP/IPv4).
3. Replace the parameters by those show on
the following figure.
4. Open a web browser and enter the IP
address (available in the Communication menu / Ethernet) of the controller in the web address bar.
5. Enter your username and password.
Default
Address IP
10.0.0.100
User
Administrator
Password
password
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 45.
Remote connection using a boiler-specific wireless network.
If the boiler cannot be connected to the local network, a wireless router for remote connection can be installed. The configuration may differ depending on the model of the router being used. The methodology is presented with a TP­LINK model TL-WR810N.
1. Plug the router into an electrical outlet.
2. Connect the network cable to the RJ45 socket on the controller and the LAN / WAN jack on the router.
3. Use a computer to connect to the wireless network generated by TL-WR810N. (by default).
4. Open a web browser and your wireless
network’s web configuration page at
http://tplinkwifi.net, or use the router’s default address.
Default
IP address
192.168.0.1
User
Admin
Password
Admin
Remote connection using a network connection
1. Enter a compatible IP address and subnet mask compatible with the network you want to connect to. Note: Select a free IP address that is compatible with the network (pay attention to the IP addresses of printers and other modules.)
2. Restart the controller to apply the changes.
3. Plug the network cable into the controller and into an Ethernet port (wall outlet or directly into the router)
4. Open a web browser and enter the previously selected IP address.
4.3.8.1 BACnet
The BACnet menu allows you to view the configuration and change the BACnet parameters. In order to configure the VOLTMAX boiler to your BACnet management system, you must activate the function.
You must then enter the correct baud rate. Ex: For a BACnet MS / TP communication protocol with a Metasys system the default baud rate is
38400. You must enter the correct MS / TP
address. Ex : For a BACnet MS / TP
communication with a Metasys system, the address is 5.
For more information on the BACnet protocol, please refer to the appropriate documentation.
4.3.9 OCCUPATION
Setting the temperature-lowering period.
4.3.9.1 Occupation setting
This function allows the boiler water temperature to be lowered for defined periods without having to lower all the thermostats of the building. This function can be activated and deactivated within the menu Occupation under Occupation mode. This function allows the set-point temperature to be lowered when the boiler is within the hours specified in the Schedule Setting menu. The temperature drop in the set­point can be changed in the Occupation Setting menu.
The SCR model allows the connection of a contact (OCC Contact) on the controller allowing the use of an external timer to control the OCCUPATION function. The Contact OCC. option activates the operating mode using an external contact (switch). Ex: When the contact (switch) is open at the OCC terminal, then the boiler will be in temperature-lowering mode. (Night mode) When the contact (switch) is closed, it will be in normal occupancy mode (Day mode).
Force is used to force the boiler to operate normally (day mode).
A weekly schedule can be programmed under the Schedule setting to modify the occupation hours of the building.
4.3.9.2 SCHEDULE CONFIGURATION Changing a Schedule
Use this menu to configure the building’s
occupation schedule. The schedule works on a weekly schedule (Monday - Sunday). The first hour represents the start of the occupancy
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 46.
period and the second hour represents the innocupancy periods.
Ex: In the case currently displayed between 07:00 and 17:59, the set-point temperature will not be affected. On the other hand, from 18:00 to 06:59, the set temperature will be lowered.
When the building is not occupied for a full day, you must enter this information as follows, so that the boiler is not switched on.
4.3.10 BOOST MODE
Enable Boost Mode
This mode operates with the Fixed Set-point and Outdoor reset mode. This menu allows the Boost mode to be activated, this mode increase the set-point temperature when the heating load of the building exceeds the capacity generated by the current water temperature determined by the boiler. This mode is activated after a period of 30 min if the set-point temperature is not reached. After this period, the set temperature will start to rise until a predetermined maximum temperature is reached depending on the heating mode until the demand is filled. This temperature increase is temporary and has a maximum duration of 120 minutes or when the request is terminated on W1 and W2.
N.B. The BOOST mode is particularly interesting for applications such as:
o Applications with a programmable thermostat
with automatic lowering of the building temperature.
o Return to normal heat demand after a
prolonged period of sunshine where there have been no long-term demands and, therefore, heating floors will take a long time to provide heat at d Normal water.
4.3.11 WARM WEATHER SHUTDOWN Shuts down the boiler when the outside temperature reaches an established threshold.
This mode stops the boiler’s heating production when the outside temperature is higher than a pre-determined temperature (ex: 68°F).
Note: If the boiler is configured with DHW mode, it will continue to operate normally in order to meet the DHW heating demand.
4.3.12 CHANGE PASSWORD
Changing the password
This menu allows you to change the installer account password
4.4 INTERNET
The settings available on the controller are also available remotely on a web portal. This portal works only when the boiler is properly connected to an internet or Ethernet network. The various setting parameters and the protocol for connecting the boiler to a network are available in the Communication menu and Section
4.3.8.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 47.
4.4.1 WEBSITE
In order to access the boiler remotely via the internet, the boiler controller must be correctly connected.
The web portal has 3 main menus, the User, Installer and Manufacturer menu. The structure of the web portal is the same as the controller; please refer to the previous sections, if you have any questions.
Ex: The user can obtain information concerning the boiler status, in the menu Operations /
N.B. The password to acces the installater section of the website is 1111. He is independent of the boiler password.
4.4.2 EMAIL
In order to configure the alarm by e-mail, you must:
1. You must first ensure that you enter the correct information in the controller (depending on your network) under the following options:
a. IP address b. Default Gateway c. Subnet mask d. Primary DNS e. Secondary DNS
You must restart the device for the changes to take place.
2. Access the Boiler Web Portal.
3. Click on the Installer / Communication menu.
4. Enter your e-mail under Recipient. You can
also use your own mail server by entering the necessary data.
5. Then select the types of alarms you want to receive by e-mail.
If you want to send alarms to different e-mail addresses, simply enter a list of e-mails.
Personal Email Server (Type: Gmail)
The M171 controller does not support SSL encryption. Thus, your SMTP Email server must accept an unencrypted connection. Internet service providers usually have a specific server that accepts connections without encryptions. On-line messaging services, such as Hotmail, G-mail, do not accept unencrypted communications. In order to work around the
problem, there are relay services such as SMTP2GO: https://www.smtp2go.com, to relay between controller communication and your messaging system. This service is free for up to 1000 emails per month.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 48.
4.5 BOILER STATUS DISPLAY SETTINGS
Display
Description
BACnet Variable
BACnet Description
T.
Set point
The set-point temperature of the boiler. The boiler will
activate its elements accordingly in order to modulate its
water outlet temperature.
AV_T
Set-point ---
T. Out Boiler
The temperature at the outlet of the VOLTMAX boiler.
AV_BoilerTOut
---
T. In Boiler
The temperature at the inlet of the VOLTMAX boiler.
This sensor is only available on SCR models.
AV_BoilerTIn
---
T. Outdoor
This variable allows the outdoor temperature to be displayed
in real time when the outdoor temperature sensor is correctly
connected.
AV_OutdoorT
---
Boiler Pressure
This variable allows the reading of the pressure sensor inside
the boiler.
AV_SensorPressureSignal
---
Actual power
The actual power used in kilowatt
AV_ActualPower
---
% max
authorized
power
The maximum permissible power as a percentage of the
nominal power.
AV_CapLimitPrc
---
Consumption
The power consumption of the last cycle.
You must first begin a history cycle (MAIN MENU /
CONSUMPTION)
--- ---
Actual Current
(A)
This variable allows the reading of the current sensor inside
the boiler. This sensor is only available on SCR models.
AV_SigCaptCourant
---
Demand W1
When requesting heating on W1, allowing the operation of
the heating elements.
BV_HeatingW1
0 = No W1 demand
1 = W1 demand
Demand
W2/DHW
When requesting heating on W2 or DHW, allowing the
operation of the heating elements.
BV_HeatingW2
0 = No W2 demand
1 = W2 demand
Pump W1
During a closed contact of the terminal block of the pump 1
BV_ContactPump1
0 = Pump 1 open contact
1 = Pump 1 closed contact
Pump W2/DHW
During a closed contact of the terminal block of the pump 2
BV_ContactPump2
0 = Pump 2 open contact
1 = Pump 2 closed contact
Flow
The theoretical flow calculated according to the power used,
T. Out B
oiler and T. In BoilerT.
Available on SCR models only.
AV_WaterFlow
---
SCR Modulation
%
Percentages of the SCR relay utilisation.
(For SCR model only)
AV_ModSCR
Stage #1
Operation of stage #1 (For STG model only)
BV_RelStage1
0 = Stage 1 not working
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 49.
1 = Operation of stage 1
Stage #2
Operation of stage #2
BV_RelStage2
0 = Stage 2 not working
1 = Operation of stage 2
Stage #3
Operation of stage #3
BV_RelStage3
0 = Stage 3 not working
1 = Operation of stage 3
Stage #4
Operation of stage #4
BV_RelStage4
0 = Stage 4 not working
1 = Operation of stage 4
Stage #5
Operation of stage #5
BV_RelStage5
0 = Stage 5 not working
1 = Operation of stage 5
Stage #6
Operation of stage #6
BV_RelStage6
0 = Stage 6 not working
1 = Operation of stage 6
Alarm
HL/LWCO
Alarm
Alarm triggered because of a high limit and low water level
manual alarm.
BV_StatusAlarmHL/LW
0 = Normal operation 1 = Alarm activated
HL Alarm
Alarm triggered when the boiler’s internal temperature is
higher than the threshold.
BV_AlarmIntHL
0 = Normal operation
1 = Alarm activated
LL Alarm
Alarm triggered by the boiler’s lack of capacity.
BV_AlarmLL
0 = Normal operation
1 = Alarm activated
Low Pressure
Alarm
Alarm triggered by a low pressure.
BV_AlarmLowPressure
0 = Normal operation
1 = Alarm activated
High Pressure
Alarm
Alarm triggered by a high pressure.
BV_AlarmHighPressure
0 = Normal operation
1 = Alarm activated
Flow Alarm
Alarm triggered by a flow problem.
BV_AlarmLowFlow
0 = Normal operation
1 = Alarm activated
Current Alarm
Alarm triggere
d by a current problem.
BV_AlarmCurrent
0 = Normal operation
1 = Alarm activated
Sensor Alarm
Alarm triggered by a sensor problem.
BV_AlarmSensor
0 = Normal operation
1 = Alarm activated
Boiler model
The VOLTMAX boiler model.
---
---
Tension
The nominal voltage of the VOLTMAX boiler.
---
---
Firmware
version
The controller’s firmware version.
--- ---
Program name
The controller’s program name and version.
---
---
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 50.
4.6 HEATING MODE W1 SETTINGS
Display
BACnet variable
Description
Parameters
Default
Operating Mode
WP_HeatingMod
eW1
Selects the power limitation mode
between Stop,
Modulation T. Ext, DCC 0
-10VDC and Fixed.
0 = Stop
1 = Outdoor Reset 2 = DCC 0
-10VDC
3 = Fixed
Fixed
4.6.1 FIXED MODE
Configure the fixed set-point temperature
Display
BACnet Variable
Description
Selection
Default
W1 Set point
WP_FixedSTPT
W1
Selects the fixed set-point temperature when there is
demand on W1.
10 to 93
0
C
50 to 200
0
F
140
0
F
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 51.
4.6.2 OUTDOOR RESET MODE
Adjust the set-point temperature according to the outside temperature
This mode allows modulating the boiler output
set-point
temperature as a
function of the outdoor temperature. The outdoor temperature value
comes from a temperature sensor connected to the boiler controller.
If the outdoor sensor is not connected or if its circuit is open, an alarm
signal will be displayed on the display (SE). The boiler temperature set-
point
will become the set value at STPT Min T. Outdoor.
Figure 18 : Outdoor reset curve
Table 10 : OUTDOOR RESET MODE Settings
Display
BACnet
Variable
Description Parameters
Default
Calculated SPTP
AV_TBoilerSTP
TCalculatedOU
TRST
Current set-point temperature calculated based on the
adjustment curve
and the outside temperature
10 to 93
0
C
50 to
200
0
F
---
STPT at Min Outd T
WP_STPTatMin
OutdT
Boiler set-point temperature when the outside temperature
reaches the Min Outd T.
10 to 93
0
C
50 to 200
0
F
140
0
F
STPT at Max Outd T
WP_STPTatMa
xOutdT
Boiler set-point temperature when the outside temperature
reaches the Max Outd T.
10 to 93
0
C
50 to 200
0
F
80
0
F
Outdoor T.
AV_OutdoorT
Displays the outside temperature in real time when the
outdoor temperature sensor is properly connected.
-46 to 107 °C
-50 to 250 °F
---
Min Outd T.
WP_MinOutdRs
tT
Minimum outside temperature (Set to the area’s coldest
average temperature)
-46 to 107 °C
-50 to 250 °F
-10
0
F
Max Outd T.
WP_MaxOutdR
stT
Maximum outside temperature at which the building will need
heating
-46 to 107 °C
-50 to 250 °F
65
0
F
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 52.
4.6.3 MODE : DDC 0-10VDC
Modulation of the set-point temperature as a function of 0-10 VDC
(Available only on SCR model)
This operating mode allows to modulate the
set-point
temperature of
the water outlet of the boiler according to a 0
-
10VDC signal applied
to the ter
minal block 0-10Vdc T and 0-10Vdc G
from an external
controller (Ex: An energy management software).
A heat demand (closed contact W1 and / or W2
-
DHW) must be
present so that the boiler can heat up.
Figure 19 : Mode DDC 0-10 VDC
Table 11 : Specific parameters in DDC 0-10 VDC
Display BACnet variable
Description
Parameters
Default
T. STPT 0
-10VDC
AV_TBoilerSTPTCalculatedV
This variable represents the set-point temperature
based on the voltage of the building control system.
0
C
or
0
F
---
STPT at Min Volt
WP_STPTatMinRemote010V
Set-point of the boiler temperature corresponding to
the voltage level of Min Voltage.
0
C
or
0
F 80
0
F
STPT at Max Volt
WP_STPTatMaxRemote010V
Set-point of the boiler temperature corresponding to
the voltage level of Max Voltage.
0
C
or
0
F
140
0
F
Actual voltage
AV_Remote010VSTPT
Voltage emitted by the external controller in real
time
0
-10 V
---
Max Voltage
WP_MinRemoteVSTPT
The maximum voltage that the external controller
can send
0
-10 V
10
Min Voltage
WP_MaxRemoteVSTPT
The minimum voltage that the external controller
can send
0
-10 V
0
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 53.
4.7 W2 MODE SET-POINT TEMPERATURE SETTINGS
Display
BACnet Variable
Description
Selection Default
Operating Mode
WP_HeatingMod
eW2
Select the boile
r’s operating mode during demand on W2 (None
, W2
and
DHW)
0 = W2
1 = DHW 2 = None
None
4.7.1 W2 MODE
Configures the fixed set-point temperature during demand on W2
Display
BACnet Variable
Description
Selection Default
W2 Set point
WP_FixedSTPT
W2
Selects the
fixed set-point temperature during demand on W2.
10 to 93
0
C
50 to 200
0
F
175 deg F
0
4.7.2 DHW MODE
Configures the fixed set-point temperature during demand on DHW mode.
Display
BACnet Variable
Description
Selection Default
T.
Set-point
DHW
WP_FixedSTPT
W2
Selects the fixed set-point temperature during demand on W2
terminale
10 to 93
0
C
50 to 200
0
F
175
0
F
T. Min
Boiler
WP_FixedSTPT
W0
Selects the boiler’s minimum temperature.
The boiler’s heating elements will activate automatically
to keep the
hydronic system at the selected temperature.
10
to 93
0
C
50
to 200
0
F
150
0
F
4.8 PUMP CONFIGURATION MENU SETTINGS
4.8.1 PUMP 1
Display
BACnet Variable
Description
Selection
Default
Pump
configuration
WP_Pump1Mode
Selects the pump configuration mode (
pump contact switc
h)
0 = None
1 = Always Active 2 = On demand W1
Always
active
Purge delay
WP_Pump1Delay
Configures the pump purge delay (used in W1 On-Demand
mode)
0 to 600 sec
30 sec
4.8.2 PUMP 2
Display
BACnet Variable
Description
Selection
Default
Pump
Configuration
WP_Pump2Mode
Selects the pump configuration mode
(
pump contact switch)
0 = None
1 =
Always Active
2 =
On demand W1
3 = Priority on P1
Always
Active
Purge delay
WP_Pump2Delay
Configures the pump purge delay (used in W1 On-Demand
mode)
0 to 600 sec
30 sec
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 54.
SPECIFIC PARAMETERS FOR THE CAPACITY LIMITING MENU
The boiler authorizes a maximal power use. The configuration of these modes is shown below.
4.8.3 MANUAL MODE
The maximum power is determined manually
Display
BACnet variable
Description
Parameters
Default
Max capacity
(kW)
Configure the maximum electrical power the boiler will use.
0 to maximum
rated power
---
4.8.4 MODE: 0-10 VDC
(Only available on SCR model)
The modulation of the maximum power is carried out using an external control 0-10 VDC.
Display
BACnet variable
Description
Parameters
Default
Max capacity
(kW)
The calculated power value as a function of the current and the nominal
operating voltage of the boiler
0 to maximum
rated power
---
kW at Min Volt
The maximum permissible power of the boiler when the voltage of the
external controller is at Min Voltage
0 to maximum
rated power
0
kW at Max Volt
The maximum permissible power of the boiler when the voltage of the
external controller is at Min Voltage
0 to maximum
rated power
---
0-10V Current
Signal
Voltage emitted by the external controller in real time
0
-10 V
---
Max Voltage
The voltage representing the maximum set-point of the external
controller
0
-10 V
10
Min Voltage
The voltage representing the minimum set-point of the external controller
0-10 V
0
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 55.
4.9 POWER LIMITATION MENU SETTINGS
You can control the boiler power with different modes. Their configuration is below.
Display
BACnet Variable
Description
Selection
Default
Limitation Mode
WP_CapLimitMo
de
Select the power limitation between Non
e, Manual, DCC 0-10VDC,T. Ext
and Scheduled.
0 = None
1 =
Manual
2 = DCC 0
-10VDC
3 = T. Ext 4 = Scheduled
---
4.9.1 MANUAL MODE
The maximum power is set manually.
Display
BACnet Variable
Description
Selection
Default
Current
authorized max
kW
WP_ManualCapL
imit
Configures the maximum electrical power that the
boiler will use
.
0
to maximum rated power
---
4.9.2 0-10 VDC MODE
(Available on SCR models only)
An external 0-10 VDC controller is used to adjust the maximum power.
Display
BACnet Variable
Description
Selection Default
Current
authorized max
kW
AV_ActualCapLi
mitkW
The value of power calculated based on the current and the boiler’s
nominal
operating voltage
0 to maximum
rated power
(kW)
---
Minimum Power
Volt (kW)
WP_MinRemote
VCapLimit
The boiler’s maximum power when the external controller voltage is at
Min Voltage
0 to maximum
rated power
0
Maximum Power
Volt (kW)
WP_MaxRemote
VCapLimit
The boiler’s maximum power when the external controller voltage is at V
for max. cap.
0 to maximum
rated power
---
Current Signal 0-
10V
AV_Remote010V
Cap
Voltage emitted by the external controller in real time
0
-10 V
---
Min Voltage
(VDC)
WP_CapLimitatM
inRemote010V
The voltage representing the external controller’s minimum set-point
0
-10 V
0
Max Voltage
(VDC)
WP_CapLimitatM
axRemote010V
The voltage representing the external controller’s maximum set-point
0
-10 V
10
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 56.
4.9.3 T. EXT MODE
Maximum power modulation
is based on
the outside
temperature.
Power modulation is shown below.
If the external sensor is not connected or there is a problem with
the sensor, then the power will be
limited according to
Cap. At T.
Ext. Min.
Figure 20: Adjustment curve according to the T. ext mode
Display
BACnet Variable
Description
Parameters
Default
Max capacity
(kW)
AV_ActualCapLi
mitkW
The value of power calculated based on the current and the boiler’s
nominal operating voltage
0 to maximum rated
power
---
Cap. At T. Ext.
Min
WP_CapLimitatM
inOutdT
Maximum authorized capacity according to T. Ext. Min
Ex. Maximum power is 170 kW for T. Ext min
0 to maximum rated
power
---
Cap. At T. Ext.
Max
WP_CapLimitatM
axOutdT
Maximum authorized capacity according to T. Ext. Max
Ex. Maximum power is 120 kW for T. Ext min
0 to maximum rated
power
--­Actual T. Exterior
AV_Ou
tdoorT
This variable allows you to view the outside temperature in real time
when the outside temperature sensor is properly connected.
-46 to 107 °C
-50 to 250 °F
--­T. Ext. Min
WP_MinOutdTCa
pLimit
Minimal outside temperature used to adjust the maximum power
-46 to 107 °C
-50 to 250 °F
-
10 F T. Ext. Max
WP_MaxOutdTC
apLimit
Maximum outside temperature used to adjust the maximum power
-46 to 107 °C
-50 to 250 °F
65 F
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 57.
4.9.4 SCHEDULE MODE
Power can be modulated according to a fixed schedule. This can be programmed in the Schedule Setting menu.
Display
BACnet variable
Description Parameters
Default
Max capacity
(kW)
AV_ActualCapLi
mitkW
Maximum capacity allowed at present time.
0 to maximum rated
power
--­Cap In Schedule
WP_CapLimitDay
Mode
Power limitation when the boiler internal clock is within the power
limitation schedule.
0 to maximum rated
power
---
Cap Out
Schedule
WP_CapLimitNig
htMode
Power limitation when the boiler internal clock is outside the power
limitation schedule.
0 to maximum rated
power
--­Schedule
---
Configuring the boiler power limitation schedule. In order to operate
correctly, you must first adjust the internal boiler clock in the
Clock
Setting menu.
---
---
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 58.
4.10 AUXILIARY BOILER SETTINGS
(Only available on SCR model)
The system allows control of an auxiliary boiler to the system. The different configuration options are shown below.
In or
der for the boiler to start, two conditions must be met:
The water outlet temperature of the Voltmax boiler must be below the start-up
temperature
Aux.
(T. Out Boiler < (T Set-point - Delta T. Aux Start)
The water outlet temperature of the Voltmax boiler must be below the start-up
temperature Aux. for a period of X minutes (
Start Delay Aux), after the
Voltmax
boiler is at 100% of it
s authorized power.
In order for the auxiliary boiler to turn off, the water outlet temperature of the
Voltmax boiler must be above the Aux.
T Out Boiler > (T. Set-point - Delta T. Aux Stop)
4.10.1 BACKUP MODE
Configures a second boiler as a backup.
Display
BACnet variable
Description
Parameters
Default
STPT Source
WP_STPTSource
Aux
Selects the source used to control the set-point temperature.
Auxiliary
means that the set-point will be determined
by the auxiliary
boiler
. The VOLTMAX boiler therefore has no set-
point temperature and
is only used to activate the auxiliary boiler relay.
Voltmax
means that the set-
point temperature will be determined by the
VOLTMAX boiler.
Auxiliary or
VOLTMAX
0 = Auxilliary
1 = VOLTMAX
VOLTMAX
Delta T. Start
Aux.
WP_DeltaTStartA
ux
This option adjusts the temperature differential (set-point temperature –
Water outlet temperature) used to activate the auxiliary boiler.
0 to 55
0
C
0 to 100
0
F
20
0
F
Delta T. Stop
Aux.
WP_DeltaTStopA
ux
This option configures the temperature differential (set-point temperature
Water outlet temperature) in the VOLTMAX bo
iler used to deactivate
the auxiliary boiler.
0
to 55
0
C
0
to 100
0
F
5
0
F
Delay Start
Aux.
WP_DelayStartA
ux
This option adjusts the delay in minutes before activating the auxiliary
boiler.
Min
10
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 59.
4.10.2 EXTERNAL CONTACT MODE
This mode selects the hydronic system heating source (VOLTMAX boiler or auxiliary boiler) using the BI-E terminal’s electrical switch.
Display
BACnet
Variable
Description Settings
Default
STPT Source
WP_STPTSourc
eAux
Selects the source used to control the set-point temperature.
External
means that the set-
point will be determined by the auxiliary
boiler
. The VOLTMAX boiler therefore has no set-point temperature
and is
used only to activate the auxiliary boiler’s relay
.
Internal
means that the set-point temperature will be deter
mined by the
VOLTMAX boiler.
External or
internal
Internal
4.10.3 MANUAL MODE
Manual mode is used to select the system’s operating mode (Electric or auxiliary).
Display
BACnet Variable
Description
Selection Default
Active Boiler
WP_ActiveBoiler
This option selects which boiler is in operation; either the VOLTMAX
boiler
(electric) or the auxiliary boilder (auxiliary).
VOLTMAX ou
Auxiliary
0 = VOLTMAX
1 = Auxiliary
VOLTMAX
STPT Source
WP_STPTSource
Aux
Selects the source used to control the set-point temperature.
Auxiliary
means that the set-
point will be determined by the auxiliary
boiler. The VOLTMAX boiler therefore has no set
-
point temperature and
is only used to activate the auxiliary boiler relay
.
Voltmax
means that the set-point temperature wil
l be determined by the
VOLTMAX boiler.
Auxiliary or
VOLTMAX
0 = Auxiliary
1 = VOLTMAX
VOLTMAX
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 60.
4.10.4 BI-ENERGY MODE
This mode selects the hydronic system heating source (VOLTMAX boiler or auxiliary boiler) using the BI-E terminal’s electrical switch. The benefit of this
mode is that the system can operate the back-up boiler when needed.
Display
BACnet variable
Description
Parameters
Default
STPT Source
WP_STPTSource
Aux
Selects the source used to control the set-point temperature.
Auxiliary
means that the set-point
will be determined by the auxiliary
boiler
. The VOLTMAX boiler has no set-
point temperature and is only
used to activate the
auxiliary boiler relay.
Voltmax
means that the set-point temperature will be determined
by the
VOLTMAX boiler.
Auxiliary or
VOLTMAX
0 = Auxiliary
1 = VOLTMAX
VOLTMAX
Delta T. Start
Aux.
WP_DeltaTStartA
ux
This option adjusts the temperature differential (Set-point temperature –
Water outlet temperature) used to activate the auxiliary boiler.
0 to 55
0
C
0 to 100
0
F
20
0
F
Delta T. Stop
Aux.
WP_DeltaTStopA
ux
This option configures the temperature differential (Set-point temperature
Water outlet temperature) in the VOLTMAX boiler used to deactivate
the auxiliary boiler.
0 to 55
0
C
0 to 100
0
F
5
0
F
Delay Start Aux.
WP_DelayStartA
ux
This option adjusts the delay in minutes before activating the auxiliary
boiler.
Min
10
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 61.
4.11 LIMIT CONFIGURATION MENU SETTINGS
Display
BACnet variable
Description
Settings
Default
Haute Limite T
WP_HighLimitTemp
Adjusts the temperature high limit at which the alarm
triggers
. If the water temperature leaving the
boiler
exceeds the alarm’s high limit
, it will trigger an HL
alarm and the boiler’s heating elements will be
deactivated.
0 to 92 °C
0 to 199 °F
180 °F
Delta T. LL
WP_DeltaTLL
Adjusts the temperature differential to activate the LL
alarm.
0 to -55 °C
0 to -99 °F
-20 °F
Delay LL (min)
WP_DelayLL
Adjusts the LL alarm trigger delay .
0 to 180 min 60 min
Pressure sensor
WP_ActivatePressureSensor
Activates the boiler’s internal pressure sensor module.
OFF / ON
0 = Off ; 1 = On
ON
Actual pressure
AV_SensorPressureSignal
Reads the boiler’s internal pressure sensor.
---
---
Current sensor
WP_ActivateCurrentSensor
Activates the current sensor module.
This module is available on SCR models only
OFF / ON
0 = Off ; 1 = On
ON
Calculated
current
AV_CalculatedCurrentSignal
Used to view the VOLTMAX boiler’s theoretical
electric consumption current.
--- ---
Actual current
AV_SensorCurrentSignal
View current as measured by a sensor.
---
---
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 62.
4.12 CONFIG. ALARM MENU SETTINGS
Display
BACnet Variable
Description
Possible Settings
Default
Status: HL/LWCO
alarm
BV_StatusExtAlarm
Displays the external alarm status. The external
alarm contact
is activated only if a high limit or
low
water level alarm occurs.
0 = Off 1 = On
---
Silence Alarm
WP_SilenceAlarm
Temporarily suspends the alarm .
0 = Off
1 = On
Off
Reset
Lockdown
WP_ResetLockDown
Cancels the Lockdown mode without resetting the
unit
.
Resetting the unit is required
when it is in LOCK-
OUT
mode, following repeated alarms over a short period.
0 = Off 1 = On
Off
Internal buzzer
WP_ActivateInternalBuzzer
Activates the controller’s internal buzzer.
0 = Off
1 = On
On
Deactivate LL
alarm
WP_
DeactivateAlarmLL ()
Deactivates the LL alarm.
0 = Off 1 = On
Off
4.13 OCCUPATION MENU SETTINGS
Display
BACnet Variable
Description
Possible Settings
Default
Occupation
Mode
WP_ActivateOccupationMode
Activates the Occupation function.
0 = Off
1 = On
---
Source OCC
WP_SourceOccupation
Selects the source used to determine the building’s
occupation schedule.
0 = Schedule
1 = Contact OCC
Lowering T.
WP_LoweringTInnoccupation
Lowers the set-point temperature.
---
Off
Occupation
Status
BV_StatusOccupation
Displays the Occupation mode status.
Off
: Day mode; the set-
point temperature is not
lowered On:
Night mode; the set-point temperature
is lowered
according to the configuration
0 = Off 1 = On
On
Force Day
Mode
WP_ForceOccupationDay
Forces the Day mode. The set-point temperature will
not be lowered.
0 = Off ; 1 = On
Off
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 63.
4.14 BOOST MENU SETTINGS
Display
BACnet Variable
Description
Possible Settings
Default
Mode BOOST
WP_ActivateModeBoost
This option enables the BOOST functionality.
0 = Off
1 = On
Off
4.15 WARM WEATHER SHUTDOWN MENU SETTINGS
Display
BACnet Variable
Description
Possible Settings
Default
Warm Weather
Shutdown
WP_ActivateWarmWeatherSD
Shuts down the boiler when the outside temperature
reaches a specific temperature
.
This temperature can
be set in the Warm Weather Shutdown Temperature
box.
OFF / ON
0 = Off ; 1 = On
OFF
T. Ext Shutdown
WWSD
WP_WarmWeatherSDTemp
Sets the outside temperature that activates the Warm
Weather Shutdown, if it shuts down the boiler.
0 to 55 °C
0 to 99 °F
68 °F
Current Ext. T.
AV_OutdoorT
Shows
the outside temperature in real time.
-46 to 107 °C
-50 to 250 °F
---
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 64.
SECTION 5 : BOILER START UP
Before operating this boiler, be sure to read and follow these instructions, as well as the warnings printed in this manual. Failure to do so can result in unsafe operation of the boiler resulting in property damage, bodily injury, or death. Should you have any problems reading, following or difficulty in understanding the instructions in this manual, STOP, and get help from a qualified person. Do not turn on the boiler unless it is filled with water. Do not turn on the boiler if the cold-water supply shut-off valve is closed.
After the boiler, has been plumbed and wired, it is now ready to be set for automatic operation
5.1 FILLING THE BOILER
Open the service valves at the outlet of the boiler and the cold-water supply valve (fill or makeup water valve) to boiler.
Open the relief valve on top of the boiler in order to purge the air out of the boiler tank during the fill process
Leave all shutoff valves open.
Check system for leaks and repair. Purge air from all the heating distribution zones.
Bleed air from different areas of the heat distribution system.
Check boiler pressure gage reading. The indicated pressure should be lower than the pressure relief valve design rating.
5.2 ADJUSTEMENT OF THE CONTROLLER OPERATING PARAMETERS
After the system has been manually purged of air, and all components (valves, vents, controllers) have been set properly, the boiler can be started.
Never operate this boiler until this has been done.
Consider safety and energy-savings when adjusting the boiler’s water temperature. It is more energy-efficient to maintain a set-point as low as possible while still meeting heating needs.
Safety and energy conservation are factors to be considered when setting the boiler water
operating temperature. The most energy­efficient operation will result when the temperature setting of the controller is the lowest that satisfies the heating needs.
Make sure that the input of the operating parameters of the controller as well as the adjustable high mechanical limit control of the boiler corresponding to the values required for the application.
Adjusting the high limit is possible in the Limit Setting menu. The High temperature limit should be adjusted from 15 to 20F higher than the maximum operating temperature.
5.3 STARTUP PROCEDURE
Before starting the boiler, make sure that the heating distribution design is made so that the heating elements will come on only when water is circulating in the boiler.
1) Fill the boiler as described in Section 5.1.
2) Set the boiler operating temperature as described in Section 4.
3) Cancel all heating demand from the distribution system.
4) Turn on the boiler power breakers and switch.
5) The main contactors should be activated in sequence and the controller display shall be lighted. The heating elements shall not come on because there is no heat demand applied to the controller and if there is no water circulation in the unit.
6) Apply a heat demand. If the boiler target temperature is higher than the boiler water temperature, the heating elements shall come on in sequence more or less rapidly depending on the differential between the values.
N.B. It is normal that the elements be activated very rapidly during the boiler start-up since this temperature differential is generally high at this moment.
WARNING
!
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 65.
7) When the boiler capacity has reached 100% as displayed on the controller, measure the amperage and voltage values drawn by the unit. These values shall be close to those shown on the boiler name plate.
8) Slow down the heat demand from the heating system. The boiler temperature shall gradually increase and the boiler capacity shall drop gradually and stabilize when the boiler temperature will reach a temperature near the target temperature.
9) When the heating request is completed, the circulating pump can continue to operate (depending on the operating mode or the purge time) or switch off. The heating elements stop working.
10) Check the operation of the adjustable high­limit mechanical control.
11) Check the operation of the Low Water Cut OFF by pressing its test button during 5 sec.
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 66.
SECTION 6 : TROUBLESHOOTING
The troubleshooting section shows the various error messages that can occur during abnormal operation of the boiler.
It is possible to change the limits of some alarms on the controller in the Limit Setting.
6.1 WARNING LIGHTS
The LEDs above the navigation buttons indicate 3 different boiler states.
Active
warning
light
Boiler status
Green
Normal operation of the boiler
Yellow
One or more alarms are active. These alarms do not prevent the operation of the
boiler;
the boiler continues to operate in normal mode. Ex. The controller detects a problem with the amperage reading sensor.
Red
A critical alarm is active, accompanied by the buzzer (if active). Ex. A high limit alarm is active
6.2 OPERATING PROBLEM IDENTIFICATION
An alarm log is available in the BOILER CONFIG / ALARM / ALARM LOG. Each alarm
is recorded with its alarm code, the time and date. The register can record up to 30 alarms.
6.2.1 EXTERNAL HL / LWCO
When this alarm is present, the indicator light to the left of the boiler lights red. This alarm happens when one of the two external sensors (External fault Low Water Cut Off or External High limit) is triggered.
Look for the cause of this contact opening which normally occurs when there is a lack of water in the boiler according to the low water level sensor (Standard on 120 kW models and higher) or when the high temperature limit control detects a temperature higher than 210°F.
The external alarm contact will be activated immediately if it has been activated (Ext. Alarm Contact) in the Alarm menu. The heating elements stop working and will start again when the water level returns to normal. If this alarm happens 3 times in 1 hour, the boiler will be set in Lock out mode.
6.2.2 SENSOR ( SE )
The Sensor alarm is activated when the controller detects a problem with a sensor. This alarm usually appears with another alarm, for example the flow rate alarm (F) and the sensor alarm (SE), this help target a flow sensor problem, for example.
See Table 13 for comparison of Resistance measurements against temperature for the outdoor sensor.
6.2.3 LOW LIMIT ( LL )
The LL alarm is activated when the temperature differential between the set-point temperature and the boiler output temperature is higher than
Delta T.LL and this period is higher than the LL delay.
The heating elements remain in operation. The screen will automatically return to its normal state. When the temperature of the boiler approaches the set temperature.
6.2.4 FLOW ( F )
(Available only on SCR model)
The flow alarm is triggered when the theoretical flow calculation is below the manufacturer's authorized flow limit.
6.2.5 CURRENT ( A )
(Available only on SCR model)
The Current alarm is triggered when there is a difference of more than 20% between the measured current (Available only on SCR
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 67.
model) and the calculated theoretical current. This may indicate an electrical problem from a wrong connection.
6.2.6 HL TEMPERATURE ( HL )
The outlet temperature of the boiler is above the high limit allowed. This alarm triggers the deactivation of the heating elements of the boiler. The boiler is restarted when the temperature drops below the high limit (and the set-point) If the boiler is in this alarm state for more than 25 minutes, the boiler switches to Lock Out mode.
6.2.7 LOW PRESSURE ( P )
The Low Pressure alarm is activated when the pressure inside the boiler is below the allowed limit (default: 5 psi).
6.2.8 HIGH PRESSURE ( P )
The High Pressure alarm is activated when the pressure inside the boiler is above the allowed
limit (depending on the maximum boiler pressure)
6.2.9 LOCK OUT
Lock out mode is activated after 3 major alarms have been activated within one hour. When the lock mode is activated, the boiler is deactivated and can only be restarted by restarting the boiler (to the left of the control panel) or by using the reset Lock Out function (in the alarm setting menu).
Tableau 12 : Resistance (Ohm) according to the outdoor sensor measuring temperature
Temperature
Resistance
Temperature
Resistance
Temperature
Resistance
Temperature
Resistance
°F
°C Ω °F
°C Ω °F
°C Ω °F
°C
-50
-46
490 813
20
-7
46 218
90
32
7 334
160
71
1 689
-45
-43
405 710
25
-4
39 913
95
35
6 532
165
74
1 538
-40
-40
336 606
30
-1
34 558
100
38
5 828
170
77
1 403
-35
-37
280 279
35 2 29 996
105
41
5 210
175
79
1 281
-30
-34
234 196
40 4 26 099
110
43
4 665
180
82
1 172
-25
-32
196 358
45 7 22 763
115
46
4 184
185
85
1 073
-20
-29
165 180
50
10
19 900
120
49
3 760
190
88
983
-15
-26
139 402
55
13
17 436
125
52
3 383
195
91
903
-10
-23
118 018
60
16
15 311
130
54
3 050
200
93
829
-5
-21
100 221
65
18
13 474
135
57
2 754
205
96
763
0
-18
85 362
70
21
11 883
140
60
2 490
210
99
703
5
-15
72 918
75
24
10 501
145
63
2 255
215
102
648
10
-12
62 465
80
27
9 299
150
66
2 045
220
104
598
15
-9
53 658
85
29
8 250
155
68
1 857
225
107
553
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 68.
SECTION 7 : MAINTENANCE
Properly maintained, your boiler will provide years of dependable, trouble free service. It is recommended that a regular routine maintenance program be established and followed by the user. Components are subject to eventual failure that requires service. Failure to use the correct procedures or parts in these circumstances may make the unit unsafe or reduce the life of the boiler.
The owner should have the following inspection and maintenance procedures performed:
7.1 BOILER WATER PIPING
YEARLY VISUAL INSPECTION
Check all piping for signs of leakage near joints, unions and shut-off valves. Repair as needed.
7.2 PRESSURE RELIEF VALVE
TWICE A YEAR
Check for possible leak at the outlet of the safety relief valve. If a leak is detected and the pressure at the indicator is less than 28psi, change the safety relief valve with a new one having similar characteristics. If the pressure is higher than 28psi, ask your heating service agency to determine the cause of the high pressure and have it corrected rapidly. Do not plug the outlet of this valve if a dripping condition occurs.
7.3 AIR PURGE
TWICE A YEAR
Check for proper operation of the automatic air purgers and activate manual air vents to eliminate air present.
7.4 ELECTRICAL INSPECTION
ANNUALLY
It is recommended to perform a visual inspection of the boiler electric compartment annually, during the heating season, to ensure it is watertight and that there are no signs of component or wiring overheating. Repair as soon as possible if necessary. Defective components should always be replaced with the Original Manufacturer’s parts.
The inspection should also include a check of the main temperature controls in operation as well as an amperage reading to verify the proper operation of all the heating elements.
The manufacturer's warranty DOES NOT cover a tank breakage caused by improper installation or maintenance. If the boiler safety valve opens periodically, this may be caused by the expansion tank.
Immediately call a qualified technician to inspect and remedy the problem.
NOTE: To prevent premature tank failure, the air trapped inside the tank must be purged periodically.
Before manually operating the relief valve, make certain no one will be sprayed with the hot water released by its opening. The water may be hot enough to create a SCALD hazard. The water released should be directed to a suitable drain to prevent injury or damage.
DANGER
!
WARNING
!
VOLTMAX ELECTRIC BOILER Installation and Operation Manual (Revised June 2017), Page 69.
VOLTMAX LIMITED WARRANTY
Warranty Coverage for Commercial Installation
Thermo 2000 Inc. warrants to the original purchaser that the DTHUltra tank installed in a commercial setting for ten (10) years. Commercial setting shall mean use in other than residential setting stated above in the residential setting definition. In the event that a leak should develop and occur within this limited warranty period due to defective material or workmanship, such leak having been verified by an authorized company representative, Thermo 2000 Inc. will repair or replace at our sole option the failed unit with the nearest comparable model at the time of replacement.
The original purchaser is responsible for all costs associated with the removal and reinstallation, shipping and handling to and from Manufacturer. The replacement unit will be warranted for the remaining portion of the original Warranty.
Limited two-year warranty on all VOLTMAX components & parts
All other DTHUltra components & parts are warranted for a period of two (2) years against defects due to defective material or workmanship. The original purchaser is responsible for all costs associated with the removal and reinstallation, shipping and handling to and from Manufacturer. The components, repaired or replaced are warranted for the residual period of the initial warranty on the unit.
Limitations
Thermo 2000 shall not be responsible for any damage, loss, and inconvenience of any nature whatsoever, directly or indirectly, relating to the breakdown or malfunction of the unit. This warranty limits its
beneficiary’s rights. Nevertheless, the beneficiary may have other rights,
which vary from state to state.
This warranty replaces any other expressed or implicit warranty and constitutes the sole obligation of Thermo 2000 towards the consumer. The warranty does not cover cost of removal, reinstallation or shipping to repair or replace the unit, nor administration fees incurred by the original consumer purchaser.
Thermo 2000 reserves its rights to make changes in the details of design, construction, or material, as shall in its judgment constitute an improvement of former practices.
This warranty is valid only for installations made within the territorial limits of Canada and the United States.
Warranty service procedure
Only authorized VOLTMAX retailers may handle warranty claims. The owner or contractor must provide the defective equipment to Thermo 2000 with the following details: the model, the serial number, a copy of the original invoice and the owner identification certificate.
Exclusions
This warranty is void and shall not apply if:
A) Defects or malfunctions resulting from installation, repair,
maintenance and/or usage that are not done in conformity with the manufacturer’s installation manual; or
B) Defects or malfunctions resulting from installation, maintenance, or
repair that are not done in accordance with regulations in force; or
C) Defects or malfunctions resulting from improper installation,
maintenance or repair done carelessly or resulting from consumer damage (improper maintenance, misuse, abuse, accident or alteration); or
D) Installation in which a relief valve (pressure) is not installed or if it is
not functioning properly, or when it is not connected to a drain to avoid damage to the property; or
E) Installation in which liquid circulating in the tank does not remain in
closed circuit or installation in which piping is leaking; or
F) A polybutylene pipe or radiant panel installation without an oxygen
absorption barrier is used; or
G) Installation where the acidity of water is not within the normal
Environmental Protection Agency (EPA) (between pH 6.5 – 8.5) guidelines or the water contains abnormal levels of particulate matter or water exceeding 10.5 gpg; or
H) Your home contains any type of water softener system and the unit
is not installed and maintained in accordance with the manufacturer specifications; or
I) The DTH Ultra unit is being subject to non-authorized modifications;
or
J) Defects or malfunction resulting of storing or handling done
elsewhere than Thermo 2000’s manufacturing plant; or
K) Units on which the serial number is removed or obliterated.
THERMO 2OOO INC.
500, 9
ième
Avenue,
Richmond (Qc) Canada J0B 2H0
Tel: (819) 826
-5613 Fax: (819) 826-6370
www.thermo2000.com
Loading...