THERMO 2000 THERMO 2000, TURBOMAX 23, TURBOMAX 24, TURBOMAX 33, TURBOMAX 34 Use & Care Manual

...
®
TURBOMAX
Instantaneous Indirect Water Heater
USE & CARE MANUAL
WITH INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR
Your TURBOMAX® Instantaneous Indirect Water Heater has been carefully assembled and factory tested to provide years of trouble-free service. In order to insure the service intended, the following information is provided to enable proper installation, operation, safety precautions and maintenance of this product.
It is imperative that all persons who are expected to install, operate or adjust this water heater read the instructions carefully so that they may understand how to do so.
Any questions regarding the operation, maintenance, service or warranty of this water heater should be directed to the entity from whom it was purchased. If additional information is required, refer to the section How to Obtain Service Assistance
When all installation steps have been completed, replace this installation manual in its original envelope, and keep in a safe place for future reference.
Revision : December 2005
THERMO 2000 INCORPORATED
Specifications
The hot water heater for domestic hot water purposes shall be a TURBOMAX
as manufactured by THERMO 2000 Inc. The hot water heater shall have an all-copper domestic waterways made of multiple helical copper tubes operating in parallel with a 150 p.s.i. maximum operating pressure rating. All copper components shall meet the NSF 61 standard of NSF International Standard Drinking Water Systems Components Health Effects. All copper components shall be joined at high temperature by a Sillfoss silver brazing containing no lead. The hot water heater shall have a patented steel injector through which the boiler water or the primary circuit fluid enters the top side of the tank and a steel collector through which the boiler water or primary circuit fluid exits at the bottom of the tank. The tank shall be made of high carbon steel. All the steel joints must be welded by the MIG/Argon gas process. The tank shall be hydrostatically tested to a pressure of 300 p.s.i. and shall have a maximum operating pressure of 150 p.s.i. The tank shall have a fiberglass insulation jacket reducing the tank heat loss to less than ½°F per hour. The outer steel jacket shall be protected by baked epoxy. The hot water heater shall have a temperature controller (aquastat) that makes contact when the temperature falls 9°F below the tank water temperature set point and breaks contact when the temperature rises over the set point. The tank shall have a drain (ball) valve made of brass, which have a maximum working pressure of 150 p.s.i. 3 adjustable feet support the water heater for leveling. The hot water heater shall be shipped from the factory with an ASME rated pressure relief valve set at 30 p.s.i., a thermometer/pressure gage (except #23, 33) and an automatic air vent (except #23, #24, #33, #34). The water heater is backed by a 10-year warranty (consult the terms of the warranty shipped with the water heater).
®
model _______,
Connection Domestic Hot Water Outlet
Safety valve set at 30 psi
Aquastat
Connection Cold Domestic Water Inlet
Connection Boiler Water Return Outlet
Specifications:
Model Tank
Volume
TURBOMAX® 109
TURBOMAX® 65 TURBOMAX® 45 TURBOMAX® 44 TURBOMAX® 34 TURBOMAX® 33 TURBOMAX® 24
TURBOMAX® 23
Note: Copyright 2005. Thermo 2000 Inc. All rights reserved. Turbomax® is a registered trademark of Thermo 2000 Inc. Thermo 2000 reserves the right to modify at any time and without notice colors, components, materials, specifications or model described in or shown in this document.
119 US gal. 58.9 ft² 2’’ Sweat M 2’’ NPT M 74’’ 29’’ 555 lbs
72 US gal. 32.7 ft² 1-1/2’ Sweat M 1-1/2’’ NPT M 67’’ 24’’ 250 lbs 48 US gal. 32.7 ft² 1-1/2’’ Sweat M 1-1/4’’ NPT M 55’’ 22’’ 235 lbs 48 US gal. 26.2 ft² 1-1/2’’ Sweat M 1-1/4’’ NPT M 55’’ 22’’ 210 lbs 36 US gal. 26.2 ft² 1-1/2’’ Sweat M 1-1/4’’ NPT M 65“ 18“ 195 lbs 36 US gal. 19.6 ft² 1-1/4’’ Sweat M 1-1/4’’ NPT M 65“ 18“ 170 lbs 26 US gal. 26.2 ft² 1-1/2’’ Sweat M 1-1/4’’ NPT M 49’’ 18’’ 175 lbs 26 US gal. 19.6 ft² 1-1/4’’ Sweat M 1-1/4’’ NPT M 49’’ 18’’ 150 lbs
Heat transfer area (sq. ft.)
Utility connection
Boiler connection
Height
Connection Boiler Water Supply Inlet
Manometer/ thermometer
Height
Drain Valve (right side)
r
e
t
e
m
ia
D
Diameter Shipping
weight
TURBOMAX Use and Care Manual with Installation Instructions (December 2005) Page 2
R
!
General Safety Precautions
Be sure to read and understand the entire Use & Care Manual before attempting to install or operate this water heater. Pay particular attention to the following General Safety Precautions. Failure to follow these warnings could cause property damage, bodily injury or death. Should you have any problems understanding the instructions in this manual, STOP, and get help from a qualified installer or technician.
To meet commercial water use needs, the aquastat on this water heater is adjustable up to 190°F. However water temperatures over 125°F can cause severe burns instantly or death from scalds. 125°F is the preferred starting point for setting the control to supply general-purpose hot water.
Safety and energy conservation are factors to be considered when setting the water temperature on the aquastat. The most energy efficient operation will result when the temperature setting is the lowest that satisfied the needs consistent with the application.
Maximum water temperature occurs just after burner or the energy source has shut off. To find hot water temperature being delivered, turn on a hot water faucet and place a thermometer in the hot water stream and read the thermometer.
The following chart details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications.
TIME VS TEMPERATURE
RELATIONSHIPS IN SCALDS
Temperature
120°F More than 5 minutes 125°F 1-1/2 to 2 minutes 130°F About 30 seconds 135°F About 10 Seconds 140°F Less than 5 seconds 145°F Less than 3 seconds 150°F About 1-1/2 seconds 155°F About 1 second
Table courtesy of Shriners Burn Institute
The temperature of the water in the heater can be regulated by setting the temperature dial in front of the aquastat. To comply with safety regulations the aquastat was set at its lowest setting before water heater was shipped from the factory.
There is a Hot Water Scald Potential if the aquastat is set too high. When this water heater is supplying general purpose hot water requirements for use by individuals, a thermostatically controlled mixing valve for reducing point-of-use water temperature is recommended to reduce the risk of scald injury. Contact a licensed plumber or local plumbing authority for further information.
!
DANGE
Time to Produce Serious
Burn
TURBOMAX Use and Care Manual with Installation Instructions (December 2005) Page 3
Introduction
WARNING
!
The important safeguards and instructions appearing in this manual are not meant to cover all possible conditions and situations that may occur. It should be understood that common sense, caution and care are factors, which cannot be built into every product. These factors must be supplied by the person(s) caring for and operating the unit.
LOCAL INSTALLATION REGULATIONS
This water heater must be installed in accordance with these instructions and must conform to local, or in the absence of local codes, with the current edition of the National Plumbing Code and the National Electric Code. In any case where instructions in this manual differ from local or national codes, the local or national codes take precedence.
DECISIONS REQUIRED BEFORE INSTALLATION
In some jusrisdictions the boiler’s operating pressure must be limited to 30 psi (200 kPa) by a safety relief valve. When a higher operating pressure level is needed, select a boiler which is certified to operate at the required pressure.
The boiler’s output rating must be within the heater’s recommended sizing guide specifications. Too low an output rating may cause excessive condensation in the boiler. Too high an output rating may cause a boiler short cycling condition. Either of these conditions could be detrimental to the life and performance of the system.
Where the boiler’s output is used to supply space heating and domestic water heating, two options are available when wiring the controls. The first option uses a priority relay. When the aquastat of the water heater calls for heat, the relay shuts off the space heating zones, giving priority to producing domestic hot water. Any demand for space heating is postponed until the water heater has reached a preset level. This delay in supplying the space heating zones is usually not noticed by those occupying the living space. The water heater gets adequate hot water flow from the boiler to maintain the full rated delivery of domestic hot water.
In the second option, the water heater will be supplied as just another heating zone. This means that if all space heating zones call for hot boiler water at the same time, the water heater may not be supplied with enough hot boiler water to “recover” adequately. The delivery of domestic hot water will be diminished. This is not a problem when the boiler output is sized adequately for both loads.
The flow of hot boiler water to the water heater can be controlled with either a pump or a motorized valve. If a zone valve is to be used, the space heating system circulator must have an adequate flow rate to allow proper heat transfer of BTUs from the hot boiler water stored in the tank to the domestic water flowing inside the water heater’s heat exchanger. Be sure the space heating zone valve chosen has maximum pressure drop to insure proper boiler water flow to the heater. The recommended way to provide adequate boiler water flow through the water heater is to use a separate dedicated circulator. This option may be used even though the heating system utilizes zone valves.
CAUTION
!
The heat transfer medium must be water or other non-toxic fluid having a toxicity rating or class of 1, as listed in Clinical Toxicology of Commercial Products, 5
th
edition
LOCATION
The water heater should be installed in a clean, dry location as close as practical to the boiler or the heat source. Long hot water lines should be insulated to conserve water and energy. The water heater and water lines should be protected from exposure to freezing temperatures.
TURBOMAX
vertically. Use the adjustable feet to level the unit.
The water heater must be located or protected so it is not subject to physical damage, for example, by moving vehicles, area flooding, etc.
®
water heaters must be installed
TURBOMAX Use and Care Manual with Installation Instructions (December 2005) Page 4
All models can be installed on combustible floors and in alcoves. Minimum clearance from combustible construction is 0 inches on all sides. A minimum 3 inch clearance on both sides and in the rear and a minimum 24 inch clearance in front and on top should be available for adequate inspection and servicing.
CAUTION
!
The water heater should not be located in an area where leakage from the tank or water connections will result in damage to the adjacent area or to lower floors of the structure. When such areas cannot be avoided, a suitable drain pan or non­flammable catch pan, adequately drained, must be installed under the water heater. The pan must be connected to a drain.
NOTE: Auxiliary catch pan MUST conform to local codes.
Catch pan or drain pan kits made of metal are available in 16”, 19”, 22”, 24” and 26-1/2” diameters from the distributor or store where the water heater was purchased.
RESTAURANTS
If the water heater is to be installed in a restaurant or other location where the floor is frequently cleaned, it must be elevated to provide at least 6 inches of clearance from the floor to comply with NSF International recommendations. A factory-designed leg extension kit is available for this purpose from the distributor or store where the water heater was purchased.
CORROSIVE ATMOSPHERES
The heater should not be located near an air supply containing halogenated hydrocarbons or high humidity. For example, The air in beauty salons, dry cleaning establishments, photo processing labs and storage areas for liquid and powder bleaches or swimming pool chemicals often contains such hydrocarbons.
The limited warranty is voided when failure of the water heater is due to a corrosive atmosphere. TURBOMAX designed for corrosive atmospheres are available from the distributor or store where the water heater was purchased.
®
water heaters
Check List of Mechanical Components for Proper Installation
NON-PRIORITY SYSTEM
A) If separate circulator for each zone
1 circulator per zone
1 flow check per zone
B) If only one circulator used by the
heating system
1 zone valve per zone
C) Common Components:
4 x unions
4 x ball valves minimum
1 x vacuum breaker (if required)
1 x temperature & pressure relief valve
with probe of sufficient length.
1 x thermostatic mixing valve
copper pipe & copper pipe fittings
steel pipe & steel pipe fittings
PRIORITY SYSTEM
A) If separate circulator for each zone
1 circulator per zone
1 flow check
B) If only one circulator used by the
heating system
1 – 3 way zone valve
1 x potable water expansion tank if
necessary. See the “Domestic water connections” section.
1 x pressure reducing valve (boiler water)
1 x pneumatic expansion tank
2 x automatic air vents at least.
Switching relays or zone controller
And any other necessary components.
TURBOMAX Use and Care Manual with Installation Instructions (December 2005) Page 5
Installation
WARNING
!
The manufacturer’s warranty does not cover any damage or defect caused by installation or attachment or use of any special attachment other than those authorized by the manufacturer into, onto, or in conjunction with the water heater. The use of such unauthorized devices may shorten the life of the water heater and may endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized devices
INSPECT SHIPMENT
Inspect the water heater for possible shipping damage. The manufacturer’s responsibility ceases upon delivery of goods to the carrier in good condition. Consignee must file any claims for damage, shortage in shipments, or non­delivery immediately against carrier.
DOMESTIC WATER CONNECTIONS
This water heater may be connected individually, in multiples with others, or with an external hot water storage tank. If two TURBOMAX are installed, the piping method to be used to connect the TURBOMAX “reverse-return piping”, so domestic water flow rate through each TURBOMAX
®
in parallel should be
®
is equal.
The HOT WATER OUTLET and the COLD WATER INLET connections are clearly marked. Inlet water connections (COLD WATER INLET) are to be made to the copper pipe (sweat connection) at the bottom of the heater. Outlet water connections (HOT WATER OUTLET) are to be made to the copper pipe (sweat connection) at the top of the heater.
The installation of copper unions or copper alloy unions is recommended on the HOT and COLD water lines, so that the water heater may be easily disconnected for servicing if necessary.
Dielectric unions are required for protection of the water heater if dissimilar pipe material like galvanized pipe is used.
Install shutoff (ball) valves for servicing convenience.
®
or more
Use only clean copper or approved plastic pipe for water connections. Local codes or regulations shall govern the exact type of material to be used.
To minimize heat loss during non-draw periods, a heat trap formed from piping can be used. Insulate all pipes containing hot water, especially in unheated areas.
Cap or plug unused connections. If the water heater is replacing a tankless coil in the boiler, do not cap tube outlets in the tankless coil after disconnecting from plumbing.
Thermometer(s) should be installed to indicate the temperature of the water at or near the outlet of the water heater and storage tank(s), if provided.
EXPANSION TANK FOR POTABLE WATER
Determine if there is a check valve, a back flow preventer, a pressure-reducing valve, a water meter or a water softener in the cold water supply line.
A check valve creates a closed system and prevents the water, as it is being heated, from expanding back into the cold water supply line. Pressure can build up within the water heater, causing the relief valve to operate during a heating cycle. This excessive operation can cause premature failure of the relief valve and possibly of the water heater itself.
Replacing the relief valve will not correct the problem. One method of preventing pressure build-up is to install an expansion tank for potable water in the cold water supply line between the heater and check valve. Contact your installing contractor, water supplier, local plumbing inspector or plumbing supply house for assistance.
RECIRCULATION LINE (IF APPLICABLE)
If a recirculation line is installed, the return connection should be made to a tee close to the inlet connection on the water heater. A check valve should always be installed in the recirculation line to prevent cold water from entering.
TURBOMAX Use and Care Manual with Installation Instructions (December 2005) Page 6
Basic Piping Schematic
Zone Valve Zoning
Requirements:
1. The installation must conform to local, state, provincial and national codes. In any case where instructions conflict with the above, let those codes take precedence.
2. This is a basic piping schematic. Please consult the installation manual.
3. Install a safety valve (temperature & pressure) on the domestic hot water line, as near as possible to the hot water heater connection and before any shut off valve.
4. Pipe all the safety valves and drain valves to the drain or accordingly to the code.
5. When a back flow preventer or water meter or a pressure reducing valve is used on the domestic cold water supply line, then a thermal expansion tank must be installed between the water heater and this device.
TURBOMAX Use and Care Manual with Installation Instructions (December 2005) Page 7
Basic Piping Schematic
Circulator Zoning
Requirements:
1. The installation must conform to local, state, provincial and national codes. In any case where instructions conflict with the above, let those codes take precedence.
2. This is a basic piping schematic. Please consult the installation manual.
3. Install a safety valve (temperature & pressure) on the domestic hot water line, as near as possible to the hot water heater connection and before any shut off valve.
4. Pipe all the safety valves and drain valves to the drain or accordingly to the code.
5. When a back flow preventer or water meter or a pressure reducing valve is used on the domestic cold water supply line, then a thermal expansion tank must be installed between the water heater and this device.
TURBOMAX Use and Care Manual with Installation Instructions (December 2005) Page 8
DOMESTIC HOT WATER TEMPERATURE & PRESSURE RELIEF VALVE
An automatic temperature & pressure relief valve with a temperature probe of sufficient length must be installed at the time of the installation. No valve of any type should be placed between the T&P relief valve and the water heater. Use a tee to install the relief valve onto the hot water outlet. The pressure rating of the relief valve must not exceed 150 psi.
The BTU per hour rating of the relief valve must equal or exceed the BTU per hour input of the boiler(s) or heat source(s) as marked on the boiler(s) rating plate.
For a circulating tank installation, the separate storage tank(s) must have similar protection.
Connect the outlet of the relief valve to a suitable open drain, so discharge can exit only 6” above the structural floor; and cannot contact any live electrical parts. The discharge line must pitch downward from the valve to allow complete draining (by gravity) of the relief valve and discharge line, and be no smaller than the outlet of the valve. The end of the discharge line should not be threaded or concealed and should be protected from freezing. No valve of any type, restriction or reducer coupling should be installed in the discharge line. Local codes shall govern the installation of relief valves.
THERMOSTATIC MIXING VALVE
When this water heater is supplying general­purpose hot water requirements for use by individuals, a thermostatically controlled mixing valve is recommended to reduce the risk of scald injury. Contact a licensed plumber or the local plumbing authority for further information.
Keep temperature control of the mixing valve at the lowest setting which is satisfactory.
When installing a mixing valve, locate it at the bottom of anti-thermosiphon loop at least 24” high to prevent excessive hot water from entering mixed water supply.
VACUUM BREAKER (IF REQUIRED)
Install a vacuum breaker (or vacuum relief valve) for water heater protection. Prevents siphoning of the water from the system and collapse of the water heater.
BOILER WATER CONNECTIONS
This water heater may be connected individually, in multiples with others, or with an external storage tank containing boiler water. If two TURBOMAX method to be used to connect the TURBOMAX parallel should be “reverse-return piping”, so boiler water flow rate through each TURBOMAX
®
or more are installed, the piping
®
is
®
in
equal. The BOILER WATER SUPPLY and BOILER
WATER RETURN connections are clearly marked. Boiler water supply connections are to be made to the steel pipe (threaded connection) at the top of the heater. Boiler water return connections are to be made to the steel pipe (threaded connection) at the bottom of the heater.
The installation of unions is recommended on the BOILER WATER SUPPLY and BOILER WATER RETURN lines, so that the water heater may be easily disconnected for servicing if necessary.
Dielectric unions are required for protection of the water heater and the pipes, if dissimilar pipe material like galvanized pipe, copper and steel is used.
Use only clean pipe for boiler water lines. Local codes or regulations shall govern the exact type of material to be used. Install shutoff (ball) valves for servicing convenience. Thermometer(s) should be installed to indicate the temperature of the boiler water supply and return lines.
Circulator zoning recommendations
The preferred location of the circulator pumps for each zone is on the boiler supply, with an expansion tank between the boiler and the circulators.
A flow check valve must be installed on each zone, preferably at the outlet side of each circulator pump, to prevent water flow to other zones when they are not demanding flow
Zone valve zoning recommandations
The preferred location of the circulator pump is on the boiler supply, with the expansion tank between the boiler and the circulator.
Use zone valves with low pressure drop specifications, particularly on the water heater zone.
TURBOMAX Use and Care Manual with Installation Instructions (December 2005) Page 9
PUMP & PIPE SIZING
Boiler water temperature drop (TD) through the water heater
Simplified design methods based on a 20°F temperature drop (TD) of boiler water going through the water heater to heat up domestic water are commonly used. Although such methods are widely used and generate satisfactory system performance when applied properly, they do not determine the system operating point. The pipe size is often uneconomically large, and the actual system flow rate is likely to be much higher than intended. Such design methods seldom consider temperature drops higher than 20°F, which results in over-design.
Another method by which the boiler water temperature drop (TD) could be calculated is to assume a constant supply boiler water temperature minus the domestic water final temperature. For example a domestic water heater might have a final temperature of 140 °F. Assuming a constant supply boiler temperature of 180 °F, the TD would be 40 °F ( = 180 °F – 140 °F). Second example: If the domestic water heater has a final temperature of 180 °F and the boiler supply is at 200 °F, then temperature drop is 20 °F (= 200 °F – 180 °F).
Precautions should be taken so that the boiler return is above the boiler manufacturer’s lowest recommended temperature. Most hot water heating systems use standard, non-condensing boilers (cast iron or steel), which must be operated above 140°F in order to prevent the corrosion that is associated with flue gas condensation.
Alternatively, when the boiler surfaces are hot due to previous loads such as domestic hot water generation, the large temperature difference between the boiler and its return water can cause the boiler to become thermally shocked.
An experienced designer could work with other values than those proposed by looking into the TURBOMAX performance tables and use the guidelines stated above to design a state of the art system.
The following chart proposes a temperature drop (TD) that should be used to calculate the pump flow rate.
Proposed boiler water temperature drop
through the water heater (TD)
Boiler water
supply
temperature
200 °F 180 °F 20 °F 200 °F 160 °F 40 °F 180 °F 160 °F 20 °F 180 °F 140 °F 20 °F to 40 °F 180 °F 125 °F 20 °F to 40 °F 180 °F 110 °F 20 °F to 40 °F 160 °F 140 °F 20 °F 160 °F 125 °F 20 °F 160 °F 110 °F 20 °F
NOTE: The boiler water in TURBOMAX
Domestic water
final
temperature
TD
®
constitutes a store of heat energy ready to heat fresh domestic water. The volume of boiler water stored in TURBOMAX
®
tank provides enough heat to keep your domestic hot water hot while the boiler heats up. In fact, it acts as a buffer, which prevents domestic hot water, or boiler water temperature swings.
Pump flow rate calculation
The boiler’s output rating must be within the heater’s the heat loads calculation or the sizing guide recommendations. Use the equation below to calculate the pump flow rate.
Pump flow rate = Boiler output ÷ TD ÷ 500
Pump flow rate is express in U.S. gallons
per minute or GPM.
The Boiler output ( in net BTU per hour) is
the maximum heat to be transferred through the water heater to meet the hot water demand.
TD is the boiler water temperature drop
through the TURBOMAX®.
For example, a cast iron boiler has an output rated at 90,000 BTU per hour. The system is designed for a temperature drop (TD) of 20°F.
Pump flow rate = 90,000 ÷ 20 ÷ 500 = 9 GPM.
TURBOMAX Use and Care Manual with Installation Instructions (December 2005) Page 10
Pipe sizing criteria
Proper selection of pipe size is important to efficient system operation. A large pipe size results in lower friction losses and may allow the selection of smaller, more economical pump. The larger pipe, however, costs more initially and must be balanced against the cost savings realized by a smaller pump. Likewise, small pipe costs less initially but must be balanced against the increased operating cost of pumping water through a system with high friction losses. An economical balance should be reached between pump size, operating costs, and pipe diameter.
The ASHRAE fundamentals handbook states the general range of pipe friction loss used for the design of hydronic systems and upper limits of water velocity in piping.
A variety of upper limits of water velocity and/or pressure drop in piping and piping systems are used. One recommendation places a velocity limit of 4 feet per second for 2 inch pipe and smaller, and a pressure drop limit of 4 feet of water per hundred feet for piping over 2 inches. These limitations are imposed either to control the levels of pipe and valve noise, erosion and water hammer pressure or for economic reasons.
Please note that in the smaller pipe sizes, this velocity limit allows the use of friction loss rates higher than 4 feet per 100 feet.
Fluid velocity should be above 1-1/2 to 2 feet per second in order to carry entrained air along with the flowing water to the point of air separation where the air can then be separated from the water and purged.
Velocities greater than 4 feet per second are often used on piping larger than 2 inches.
It is generally accepted that if proper air control is provided to eliminate air and turbulence in the system, the maximum flow rate can be established by the piping friction loss rate at 4 feet of water per 100 feet. This allows the use of velocities higher than 4 feet per second in pipe sized 2 inches and larger.
Tables 1 and 2 provide friction loss values for new pipe. It should be taken into consideration that as the pumping system ages, friction losses increase. It is recommended that for most
TURBOMAX Use and Care Manual with Installation Instructions (December 2005) Page 11
commercial design purposes a safety factor of 10 to 15 % be added to the values in the tables.
What is a “foot of water”? A mass of water at 60°F standing inside a vertical column or a vertical pipe 5 feet tall creates a constant pressure of “5 feet of water” at the bottom of the column or pipe. If the water column is 2.31 feet tall, the mass of water creates a constant pressure (head) of one (1) p.s.i. (pound per square inch). Pressure losses are expressed either in “feet of water” or in p.s.i.. Usually, pump manufacturers use feet of water units.
Pressure loss from water flow in pipes
To get the proper boiler water flow through the water heater tank, the pump must overcome the pressure loss from water flow in pipes, valves, fittings and components in the piping circuit. Friction is a resistance to flow.
Pressure loss (or pressure drop) from friction in straight pipe, in Tables 1 and 2, are in feet of water per 100 feet of pipe length.
Example 1: What is the pressure drop caused by water flowing at a rate of 25 GPM (gallons per minute) through a 1-1/2 inch diameter copper tube which has a length of 100 feet?
Answer: by looking at the data in Table 1, you notice that the pressure loss is 5.46 feet of water for a tube of 100 feet.
Example 2: What if the pipe has a length of 40 feet for the same flow rate?
Answer: the pressure loss is 40% (= 40 feet / 100 feet) of 5.46 feet of water per 100 feet. The calculated pressure loss is 2.18 feet of water (= 40% X 5.46 ft water).
Pressure loss from water flow in pipe fittings and valves
In addition to the pressure loss in straight pipe, there will be pressure losses from turbulence and change of direction through fittings and valves. These pressure losses are shown in Table 3.
The pressure losses are expressed in Table 3 in a way that is called the “equivalent length”. The listings for a particular fitting of a given size show the “equivalent length” (E.L.) of straight pipe that would have the same pressure drop.
After finding the “equivalent length” (E.L.) from Table 3, the appropriate friction loss table (Table 1 or Table 2) is used to find the actual pressure drop through the fitting.
Example 3: What is the pressure loss through a 1-1/2 inch 90° copper standard elbow in a piping system through which 25 GPM of water is flowing.
Answer: from Table 3 find the equivalent length of the fitting = 4.5 feet. From Table 1 find the pressure loss for a 1-1/2 inch copper tube, through which 25 GPM of water is flowing = 5.46 feet of water per 100 feet. The pressure loss through the fitting is 4.5% (= 4.5 feet E.L./ 100 feet) of a straight 1-1/2 inch diameter copper tube. The calculated result is 0.25 feet of water (= 4.5% of 5.46 feet of water)
Pressure loss from water flow in TURBOMAX tank.
There will be pressure losses from turbulence and change of direction through TURBOMAX tank. These pressure losses are shown in Table 4. The pressure losses through the boiler water’s side (or tank‘s side) are expressed in feet of water. The pressure losses, through the domestic water’s side (or copper coil system’s side) are expressed in p.s.i..
Example 4: What is the pressure loss of boiler water flowing through a TURBOMAX
®
#109 at 60 GPM? Answer: the pressure loss is 2 feet of water.
Pressure loss from boiler or other equipment
Information on pressure drops (losses) through a boiler or other equipment is obtained from the manufacturer.
Piping system pressure drop calculation.
The pressure loss from friction in a closed piping system is required to determine the required pump head. The system pressure drop is simply the sum of the losses through each item in one circuit from pump discharge to pump suction, including piping, fittings, valves, TURBOMAX
®
tank, boiler and other equipment. To find the system pressure drop, therefore:
First inspect the piping layout. Second, note all the elements through which
pressure loss occurs in the circuit from pump discharge to pump suction. Write down the size of the fitting.
Third, measure pipe length and note the pipe diameter and material of the circuit.
Fourth, calculate for each element (pipes, fittings, valves, TURBOMAX tank, boiler and other equipment) the pressure loss at the boiler water flow rate calculated earlier.
It should be taken into consideration that, as the piping system ages, friction losses increase. It is recommended that for most commercial design purposes a safety factor of 15 to 20 % be added to the values in Tables 1 and 2.
Fifth, sum all the pressure losses of each item in the circuit
Pump or circulator selection
Consult pump manufacturer’s pump curves to select the proper pump model. Performance characteristics of centrifugal pumps are described by pump curves, which plot flow versus head or pressure together with other information such as efficiency and power.
To select the proper pump that fits your needs, ask your pump dealer or your HVAC wholesaler for a recommendation.
TURBOMAX Use and Care Manual with Installation Instructions (December 2005) Page 12
Loading...
+ 25 hidden pages