THERMO 2000 GTH 6, GTH 8, GTH 10, GTH 12, GTH 18 Use & Care Manual

...
GTH Electric Boilers
Models ranging from 6 kW to 36 kW :
240 Volts ( 1 phase ) & 600 Volts ( 3 phases ).
USE & CARE MANUAL
WITH INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR
It is imperative that all persons who are expected to install, operate or adjust this boiler should read these instructions carefully.
Any questions regarding the operation, maintenance, service or warranty of this electric boiler should be directed to the supplier.
When all installation steps have been completed, insert this installation manual in its original envelope, and keep in a safe place (close to the boiler) for future reference.
THERMO 2000 INCORPORATED revision : November 2005
Printed in Canada
Section 1: Dimensions & Specifications
Table 1: Electric Ratings for 240 VAC (1 phase) Electric Boilers:
Current
Model
GTH 6 6 25.0 34.0 2 X 3KW 2 2 2 1 8 50 GTH 8 8 33.3 42.3
GTH 10 10 41.6 50.6 2 X 5KW 2 2 2 1 6 70 GTH 12 12 50.0 59.0 4 X 3KW 4 4 4 1 4 100
GTH 15 15 62.5 71.5 GTH 18 18 75.0 84.0 4 X 4.5KW 4 4 4 1 3 110
GTH 20 20 83.4 92.4 4 X 5KW 4 4 4 1 2 125 GTH 24 24 100.0 109.0 4 X 6KW 4 4 4 1 1 150 GTH 27 27 112.5 121.5 6 X 4.5KW 6 6 6 2 1/0 175 GTH 30 30 125.0 134.0 6 X 5KW 6 6 6 2 2/0 200
GTH 33 33 138.0 147.0
* Current for circulator (9 Amp max)
P
KW
Heating
Elements
Table 2: Electric Ratings for 600 VAC (3 phases) Electric Boilers:
P
Model
GTH 9 9 8.7 3 X 3KW 1 1 1 2 14 15 GTH 13 13.5 13.1 3 X 4.5KW 1 1 1 2 12 20 GTH 18 18 17.5 6 X 3KW 2 2 2 3 10 30
GTH 22 22.5 22.0 GTH 27 27 26.0 6 X 4.5KW 2 2 2 3 8 40
GTH 30 30 29.1 6 X 5KW 2 2 2 3 8 40 GTH 36 36 35.0 6 X 6KW 2 2 2 3 8 50
KW
Current
Amp
Amp
Total
with
Circulator
Elements
1X 3KW
1 X 5KW
2 X 3KW
2 X 4.5KW
3 X 5KW 3 X 6KW
Elements Stage Aquastats Lights Contactors
3 X 3KW
3 X 4.5KW
2 2 2 3 10 30
Wires
Stages
2 2 2 1 6 70
4 4 4 1 3 110
6 6 6 2 2/0 200
Lights
Aquastats
CU
Contactors
Fuse
Wires
CU
A
Fuse
A
Table 3: Connections sizes & Boiler overall dimensions
Connections sizes Boiler overall dimensions
Boiler return 1 “ NPT M Height 12 3/16 inches
Boiler feed 1 “ NPT M Width 16 7/16 inches
Waterworks 1/2 “ NPT F Depth 28 ½ inches
Safety valve 3/4 “ NPT F Shipping weight 99 lbs.
Drain valve 1/2 “ NPT F
Drain valve (GTH
33,36)
Operating temperature : from 50°F to 190°F.; Maximum operating pressure: 30 p.s.i.
3/4 “ NPT M
DTH Electric Boilers USE & CARE MANUAL (Revision November/05), Page 2.
2
8
1
/
2
"
C
A
F
B
E
D
I
M
16"
G
H
K
L
16 7/16"
12 3/16"
N
Legeng/Légende: A) Boiler Water Supply Connection / Alimentation du chauffage (1" npt M) B) Boiler Water Return/ Retour du chauffage (1" npt M) C) Safety relief valve/ Soupape de sûreté (3/4" npt F.) D) Temperature and pressur e G age/ Indicateur de Tempéra tur e et pr ession (1/2'' npt. F) E) Drain Valve/ Valve de drainage (3/4'' npt M) F) Fill Water Connection/ Entrée d'eau aqueduc (1/2" npt F) G) Power supply wi r ing/Alimentation électrique H) Pilot Ligh ts/ Lampe témoin I) Electrical Compartments/ Co mpartiment électrique J) Wall Brackets/ Supports mural K) Circulator wiring/ Alimentation pompe L) Thermostat wiring/ Connection thermostat M) ON/OFF switch/ Interrupteur ON/OFF N) Elements Co mpartments/ Compartiment d es éléments
J
THERMO 2000 inc.
SIZE
DWG. NO.
A
REV.
DESSIN D'ATELIER GTH/ GENERAL DIMENSIONS GTH
TH2-ATELIER
0
Figure 1
Page 3
General Safety Precautions
!
Be sure to read and understand the entire Use & Care Manual before attempting to install or to operate this electric boiler. Pay particular attention to the following General Safety Precautions. Failure to follow these warnings could cause property damage, bodily injury or death. Should you have any problems understanding the instructions in this manual, STOP, and get help from a qualified installer or technician.
Section 2: Introduction
WARNING
!
The important safeguards and instructions appearing in this manual are not meant to cover all possible conditions and situations that may occur. It should be understood that common sense, caution and care are factors which cannot be built into every product. They are the responsibility of the person(s) caring for and operating the unit.
2.1 LOCAL INSTALLATION REGULATIONS
This electric boiler must be installed in accordance with these instructions and in conformity with local codes, or in the absence of local codes, with the National Plumbing Code and the National Electric Code current edition. In any case where instructions in this manual differ from local or national codes, the local or national codes take precedence.
2.2 CORROSIVE ATMOSPHERE
The electric boiler should not be located near an air vent containing a corrosive atmosphere or high humidity. The limited warranty is void when the failure of the electric boiler is due to a corrosive atmosphere.
2.3 INSPECT SHIPMENT
Inspect the electric boiler for possible shipping damage. The manufacturer’s responsibility ceases upon delivery of goods to the carrier in good condition. Consignee must file any claims for damage, shortage in shipments, or non­delivery immediately against carrier.
2.4 CHECK LIST
Please check the identification tag on the unit to make sure you have the right model.
List of components shipped with the unit :
Pressure relief valve set at 30 PSI.
Drain valve.
Tridicator (temperature & pressure
gage).
CAUTION
!
The electric boiler should not be located in an area where leakage of the tank or water connections will result in damage to the adjacent area or to lower floors of the structure. When such areas cannot be avoided, a suitable drain pan or non­flammable catch pan, adequately drained, must be installed under the boiler. The pan must be connected to a drain. NOTE: Auxiliary catch pan MUST conform to local codes.
DTH Electric Boilers USE & CARE MANUAL (Revision November/05), Page 4.
Section 3: Installation
WARNING
!
The manufacturer’s warranty does not cover any damage or defect caused by installation, or attachment, or use of any special attachment other than those authorized by the manufacturer into, onto, or in conjunction with the boiler. The use of such unauthorized devices may shorten the life of the boiler may endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized devices
3.1 SECURITY CONSIDERATIONS
Domestic and commercial installations have a maximum design operating pressure limited to 30 psi (207 kPa) by a safety relief valve.
Boiler maximum operating temperature is 190°F by design. This boiler is designed to be used
only in a hot water heating system.
The heat transfer medium must be water or other non-toxic fluid having a toxicity rating or class of 1, as listed in clinical Toxicology of Commercial products, 5
3.2 LOCATION
The electric boiler should be installed in a clean, dry location. Long hot water lines should be insulated to conserve water and energy. The electric boiler and water lines should be protected from exposure to freezing temperatures.
The electric boiler must be installed horizontally, directly on the wall. Use the wall mounting brackets to make the unit level. The wall mounting brackets are held by four 5/16’’ lag screws. The openings are located at 16’’ intervals (i.e. standard stud spacing). When the first bracket is installed you can hang the boiler on the wall (see figure 1). The lag screws must be suitably anchored to safely support the weight of the boiler including water content, piping and wiring.
CAUTION
!
th
edition
The electric boiler must be located or protected so as not to be subject to physical damage, for example, by moving vehicles, area flooding, etc. All models can be installed on combustible floors and in alcoves. Ambient temperature must not exceed 80°F or 27°C.
3.3 CLEARANCE
Minimum clearances for adequate inspection and servicing are listed in the following table:
Table 4: Boiler clearance
Left side 16 inches
Right side 6 inches
Top & Bottom of the boiler 6 inches
Front side of the boiler 24 inches
Back side of the boiler 0 inch
3.4 PIPING
The recommended piping arrangement is shown in figures 2, 3, 4 and 5, including the pump, expansion tank, drain valve, pressure relief valve, air vent, flow check valve and pressure­temperature gauge. Details about each item follow.
3.4.1 Boiler connections
This electric boiler may be connected individually or in parallel with other boilers. If two or more boilers are connected, the “reverse­return piping” method (whereby the boiler with the first return inlet also has the last supply outlet and so forth until the last return inlet corresponds to the first supply outlet) should be used to connect the boilers in parallel, to ensure an equal water flow rate through each boiler.
The BOILER WATER SUPPLY, located on the top side, and the BOILER WATER RETURN, located on the bottom side of the boiler are steel pipes (male NPT threaded connection) where supply and return line connections are to be made.
Installing a union is recommended on the boiler water supply and return lines to facilitate boiler disconnection for servicing.
Dielectric unions are required for protection of the boiler and piping if dissimilar pipe material such as galvanized steel and copper are present.
DTH Electric Boilers USE & CARE MANUAL (Revision November/05), Page 5.
Use only clean pipe for boiler water lines. Local codes or regulations shall govern the exact type of material to be used.
Insulate all pipes containing hot water, especially in unheated areas.
Install shutoff (ball) valves for servicing convenience. Thermometer(s) should be installed on the boiler water supply and return lines.
Cap or plug unused connections on the boiler. Do not cap the pressure relief valve on the boiler since it will damage and shorten the life of the boiler and may endanger life and property.
3.4.2 Flow check valve
If the heating system is pipe to use only a single pump, then to minimize flow by gravity & heat loss during non-draw periods, a flow check
must
be installed.
3.4.3 Pressure relief valve
An automatic pressure relief valve must be installed during boiler setup. The pressure rating of the relief valve must not exceed 30 psi. The safety relief valve must meet the requirements of the ASME Boiler and Pressure Vessel Code and limit the maximum operating boiler pressure. It is a safety device, not an operating control.
The BTU per hour rating of the relief valve must equal or exceed the BTU per hour input of the boiler(s) or heat source(s) as marked on the boiler(s) rating plate.
Connect the outlet of the relief valve to a discharge line with its lower tip at most 6” above a floor drain, well clear of any live electrical parts. The discharge line must pitch downward from the valve to allow complete draining by gravity of the relief valve and discharge line, and be of a diameter no smaller than that of the valve outlet. The tip of the discharge line should not be threaded or concealed and should be protected from freezing. No valve of any type, restriction or reducer coupling should be installed on the discharge line. Local codes shall govern the installation of relief valves.
3.4.4 Piping system pressurization: expansion tank
Pressure control devices within the system ensure that each component operates within minimum and maximum allowable pressures and maintain minimum pressure for all normal operating temperatures. They also allow air bleeding, prevent cavitation at the pump inlet and prevent water from boiling within the system; all this is accomplished with minimal addition of new water.
The increase in boiler water volume resulting from higher temperature is stored in the expansion tank during periods of high operating temperature and is returned to the system when the temperature decreases.
The expansion tank must be able to store the required volume of boiler water during maximum design operating temperature without exceeding the maximum allowable operating pressure, and to maintain the required minimum pressure when the system is cold. Contact your installing contractor, plumbing supply house, or local plumbing inspector for assistance. The point where the expansion tank is connected should be carefully selected to avoid the possibility that normal operation of automatic check or manual valves will isolate the tank from a hot boiler or any part of the system. Pre­charged diaphragm expansion tanks are preferable to air control (see section 3.4.6).
These tanks incorporate a balloon-like bladder or diaphragm. It is inflated, prior to filling the system, to a pressure equal to the setting of the water pressure makeup regulator.
The expansion tank should be located on the suction or intake side of the pump. The pump can be located either just upstream or just downstream from the boiler.
3.4.5 Water pressure makeup regulator
Make-up systems must be employed as required by codes. An automatic fill valve must be used with a backflow preventer as required, to maintain minimum system pressure by supplying water to make up for leakage.
3.4.6 Air bleeder
Oxygen should be excluded from the system to prevent corrosion. As hinted at in section 3.4.4,
DTH Electric Boilers USE & CARE MANUAL (Revision November/05), Page 6.
this precludes the use of air in direct contact with the boiler water as a pressurization means.
Installation of manual or automatic air vent devices prevents air from accumulating in the system. Air vents should be installed at all high points to remove trapped air during initial setup and to ensure that the system is tight. Regularly purge the air out of the system while taking care to avoid personal injuries or property damage caused by hot boiler water spray.
3.4.7 Circulator zoning recommendations
The preferred location of the circulator pump for each zone is on the boiler supply side, with the expansion tank between the boiler and the pump.
A flow check valve must be installed in each zone, preferably on the outlet side of each circulator pump, to prevent water flow to other zones where no heat is required.
3.4.8 Zone valve zoning recommandations
The preferred location of the circulator pump is on the boiler supply side, with the expansion tank between the boiler and the circulator. Use zone valves with low pressure drop.
3.4.9 Pump & pipe sizing
3.4.9.1 Boiler water temperature drop (BWTD) through the heating loop
A simplified design method based on a 20°F temperature drop (BWTD) between boiler outlet and inlet is commonly used. Although such a method is widely used and generates satisfactory system performance when applied properly, it does not determine the system operating point. The pipe size is often uneconomically large, and the actual system flow rate is likely to be much higher than intended. Such design methods seldom consider temperature drops higher than 20°F, which results in overdesign.
Another method by which the boiler water temperature drop (BWTD) could be calculated is to assume a constant supply boiler water temperature minus the return boiler water temperature. For example a boiler might have a return temperature of 140 °F. Assuming a constant supply boiler temperature of 180 °F, the BWTD would be 40 °F ( = 180 °F – 140 °F).
Second example: If the boiler water has a return temperature of 120 °F and the boiler supply is at 140 °F, then the temperature drop is 20 °F (=140 °F – 120 °F).
The following table suggests temperature drops (BWTD) to be used in calculating the pump flow rate.
Table 5: Temperature rise through the boiler
PROPOSED BOILER WATER
TEMPERATURE RISE THROUGH THE
BOILER (BWTD)
System
type
Baseboards
Cast Iron
Radiators
Radiant
In-Floor
Boiler water
Supply
tempera-
ture
190°F to
140°F
160°F to
130°F
130°F to
90°F
Boiler water
Return
tempera-
ture
170°F to
120°F
140°F to
110°F
110°F to
70°F
BWTD
20°F to
40°F
20°F to
40°F
20°F to
40°F
3.4.9.2 Pump flow rate calculation
The boiler output rating must correspond to the calculated heating load or be within the sizing guide recommendations. Use the equation below to calculate the pump flow rate.
Pump flow rate = Boiler output ÷ BWTD ÷ 500
Pump flow rate is express in U.S. gallons per minute or GPM.
The Boiler output ( in net BTU per hour) is the maximum heat to be transferred through the heating loop to meet the heating load.
BWTD is the boiler water temperature drop
For example, a 24KW electric boiler has a rated output of 81,888 BTU per hour. The system is designed for a temperature drop (BWTD) of 20°F.
Pump flow rate = 81,888 ÷ 20 ÷ 500 = 8,2 GPM.
DTH Electric Boilers USE & CARE MANUAL (Revision November/05), Page 7.
The following chart propose water temperature rise vs flow rate in GPM.
Table 6: Temperature rise vs flow rate (GPM)
Model KW
o
10
F 20oF 30oF 40oF
BWTD
GTH 6 6 4,1 2,0 1,4 1,0 GTH 8 8 5,5 2,7 1,8 1,4
GTH 9 9 6,1 3,1 2,0 1,5 GTH 10 10 6,8 3,4 2,3 1,7 GTH 12 12 8,2 4,1 2,7 2,0 GTH 13 13,5 9,2 4,6 3,1 2,3 GTH 15 15 10,2 5,1 3,4 2,6 GTH 18 18 12,3 6,1 4,1 3,1 GTH 20 20 13,7 6,8 4,6 3,4 GTH 22 22,5 15,4 7,7 5,1 3,8 GTH 24 24 16,4 8,2 5,5 4,1 GTH 27 27 18,4 9,2 6,1 4,6 GTH 30 30 20,5 10,2 6,8 5,1 GTH 33 33 22,5 11,3 7,5 5,6 GTH 36 36 24,6 12,3 8,2 6,1
3.4.9.3 Pipe sizing criteria
Proper selection of pipe size is important to efficient system operation. A large pipe size results in lower friction losses and may allow the selection of smaller, more economical pump. The increased pipe size, however, costs more initially and must be balanced against the cost savings realized be smaller pump. Likewise, small pipe costs less initially but must be balanced against the increased operating cost of pumping water through a system with high friction losses. An economical balance should be reached between pump size, operating costs, and pipe diameter.
The ASHRAE fundamentals handbook states the general range of pipe friction loss used for the design of hydraulic systems and upper limits of water velocity in piping.
A variety of upper limits of water velocity and/or pressure drop in piping and piping systems are used. One recommendation places a velocity limit of 4 feet per second for 2 inch pipe and smaller, and a pressure drop limit of 4 feet of water per hundred feet for piping over 2 inches. These limitations are imposed either to control the levels of pipe and valve noise, erosion and water hammer pressure or for economic reasons.
Please note that in the smaller pipe sizes, this velocity limit permits the use of friction loss rates higher than 4 feet per 100 feet.
Fluid velocity should be above 1-1/2 to 2 feet per second in order to carry entrained air along to a high point in the system where it can be purged.
It is generally accepted that if proper air control is provided to eliminate air and turbulence in the system, the maximum flow rate can be established by a piping friction loss rate of 4 feet of water per 100 feet. This allows velocities greater than 4 feet per second in pipe sizes 2 inches and larger.
As piping ages, friction losses increase. It is recommended that for most commercial design purposes a safety factor of 10 to 15 % be added to the values in the tables.
What is a “foot of water”? A column of water at 60°F, 5 feet tall, creates a constant pressure of 5 feet of water at the bottom of the column. If the water column is 2.31 feet tall, the mass of water creates a constant pressure (head) of one (1) psi (pound per square inch). Pressure losses are expressed either in “feet of water” or in psi. Pump manufacturers usually prefer feet of water units.
3.4.9.4 Pump or circulator selection
Performance characteristics of centrifugal pumps are described by pump curves, which plot flow versus head or pressure together with other information such as efficiency and power. Consult the manufacturer’s pump curves to select the proper model or ask your pump dealer or your HVAC wholesaler for a recommendation.
3.5 ELECTRIC POWER SUPPLY
Wiring must conform to the National Electrical Code and to state or local code requirements.
The electric boiler must be electrically grounded in accordance with local codes, or, in the absence of local codes, with the National Electrical Code.
3.5.1 240Vac models
Wiring must be from a 120/240 Volt (single phase, 60 Hz) circuit protected by a properly sized breaker. Wire gage (3 wires, ground) must be properly sized. Consult the boiler rating plate to select the proper breaker and wire gage
DTH Electric Boilers USE & CARE MANUAL (Revision November/05), Page 8.
3.5.2 600Vac models
Line wiring must be from a 600 Volt ( 3 phase, 60 Hz) circuit protected by a properly sized breaker. Wire gage (3 wires, ground) must be properly sized. Consult the boiler rating plate to select the proper breaker and wire gage.
3.6 PUMP POWER SUPPLY
3.6.1 240Vac models
Connect only a 120 Vac, 9 amp. (maximum) pump to terminals C and C on the electric pannel. Do not use a 600 Vac pump or one drawing more than 9 amps. The logic circuit is designed to activate the circulator based only on demand by the thermostat after a time delay.
3.6.2 600Vac models
Use a relay (Honeywell #RA-889, RA-89A) or the secondary contact of a zone valve (if the heating system is zoned using 4-wire zone valves). When a thermostat calls for heat: the relay will power either the boiler pump or the zone valve (the zone valve will power the boiler pump upon opening fully). See figure 6 for more details.
If the heating system is designed to use only a single pump, then to minimize flow by gravity and heat loss during non-draw periods, a flow
check must
be installed.
3.7 CONNECTING THE THERMOSTAT
3.7.1 For 240Vac model
3.7.1.1 Single heating zone Connect a low voltage thermostat to terminals T and T on the electric panel (DO NOT apply any power to these terminals!).
3.7.1.2 Multiple heating zones Connect the zone valve end switch to terminals T and T on the electric pannel (DO NOT apply
any power to these terminals!). See figure 6.
3.7.2 For 600Vac model
3.7.2.1 Single heating zone Connect the low voltage thermostat to a relay (Honeywell #RA-889, RA-89A). See figure 6.
3.7.2.2 Multiple heating zones
Zone valve zoning Connect the low voltage thermostat to the zone valve. Components must be wired to ensure that only the zone valve corresponding to the zone calling for heat is actuated and that the circulator is powered on a demand from any zone.The transformer used to power the zone valves must be sized for the load represented by all zone valves in the heating system. See figure 6.
Circulator zoning Connect the low voltage thermostat to the relay (Honeywell #RA-889, RA-89A). Components must be wired to ensure that only the circulator corresponding to the zone calling for heat is actuated. See figure 6.
DTH Electric Boilers USE & CARE MANUAL (Revision November/05), Page 9.
3.8 CBE-EM DUAL ENERGY INSTALLATION
In order to obtain a special rate from your electric utility for residential use, your GTH boiler can be hooked-up to an existing oil heater. Contact your electric utility to find out if your property is eligible for such rates and how to register for them. For installations instructions, refer to figure 12, 13 and 14.
The CBE-EM dual-energy control (an available option, three-way, motorized valve (1’’ NPT F standard) included) is specially designed to electric utility standards. The CBE-EM control selects the least expensive energy source based on outside temperature, user choice or a signal from your utility.
The CBE-EM dual-energy control will start up the oil burner upon receiving the appropriate signal, even if the thermostat in the house is not calling for heat. It will shut off when the temperature in the boiler reaches its target on the Limit Control. It is for this reason that the piping requires an anti-gravity valve (flow check valve) or motorized zone valves.
A three-way, motorized valve (1’’ NPT F standard) will direct the water flow either to the oil-fired heater or to your DTH electric boiler, depending on the signal received. This way, your oil heater will cool down and eliminate any energy loss, either through the chimney or by way of conduction in the boiler room.
DTH Electric Boilers USE & CARE MANUAL (Revision November/05), Page 10.
Section 4: Operation
SAFETY PRECAUTIONS !
Before operating this boiler, be sure to read and follow these instructions, as well as the warnings printed in this manual. Failure to do so can result in unsafe operation of the boiler resulting in property damage, bodily injury, or death. Should you have any problems reading, following or difficulty in understanding the instructions in this manual, STOP, and get help from a qualified person.
Do not turn on the boiler unless it is filled with water. Do not turn on the boiler if the cold water supply shut-off valve is closed.
After the boiler has been plumbed and wired, it is now ready to be set for automatic operation.
4.1 FILLING THE BOILER
Open the shutoff valve (and on a zone valve system, manually open zone valve) on the supply piping from the boiler.
Open cold water supply valve (fill or makeup water valve) to boiler.
To let the air out of the boiler tank during the fill process open the relief valve on top of the boiler.
Leave all shutoff valves open. Return zone valves to automatic operation.
Check system for leaks and repair. Purge air from the remaining zones, if
necessary. Check boiler pressure gage reading. 15 to 20 psi is normal for most installations.
4.2 AQUASTAT ADJUSTMENT
After the system has been manually purged of air, and all components (valves, vents, controllers) have been set properly, the boiler can be started. Never operate this boiler until this has been done.
Safety and energy conservation are factors to be considered when setting the boiler water temperature using the aquastats. The most energy-efficient operation will result when the temperature setting of each aquastat is the
lowest that satisfies the heating needs.
refer to table 5 for more details.
Each aquastat controls one stage (in the 240V model each electric element has it own aquastat; in the 600V model there is one aquastat per 3 elements). Set the temperature on the aquastat using the knob graduated in degrees Celsius and Fahrenheit.
Set the temperature on the first aquastat to the highest supply temperature required by the heating system.
Please
Set the temperature on the second aquastat from 1°F to 20°F below the setpoint of the first aquastat. Usually 5°F below the setpoint of the first aquastat is adequate if the boiler water temperature drop is 20°F.
Proceed in a similar manner for the 3rd, 4th and any supplementary aquastats, lowering the set point by 5°F each time.The elements will thus be activated (and de-activated) in the number required by the set points and the drop (or rise) in boiler water temperature.
On initial start up (on the first day of the heating season) with a cold tank, a considerable amount of time may be required for the tank to reach desired temperature. Check the temperature on the boiler temperature gage.
Adjust the boiler aquastats as needed. Note that setting the aquastat to a lower setting will not have an immediate effect. The stored boiler water heat will first have to be consumed. Additional checks of the water temperature should follow completion of a cycle. Further adjustments may be necessary as you use your boiler and space heating system.
Note: The maximum setting for the boiler water supply to the heating system is 190°F.
DTH Electric Boilers USE & CARE MANUAL (Revision November/05), Page 11.
4.3 STARTUP PROCEDURE
1. Fill the boiler as described in section
4.1.
2. Set the boiler operating temperature as described in section 4.2.
3. Turn down all room thermostats under room temperature
4. Turn on the boiler power breakers and switch.
5. The main contactor should close and all elements should be in operation. Pilot lights should be on.
6. Temperature inside the boiler should increase. Elements and pilot lights should turn off one by one as they reach their set point.
7. When all elements are off, turn up all room thermostats above room temperature.
8. The circulator should start up after a time delay.
9. The elements should turn on in sequence as the boiler water temperature drops below the aquastat set points. This could take many minutes.
10. The circulator stays on for as long as there is a demand for heating. When the circulator turns off,
11. Temperature inside the boiler should increase. Elements and pilot lights should turn off one by one at they reach their aquastat set point.
In this way, the power drawn by the boiler depends on the actual heating load of the building. If you need only one stage to heat your home, only one will be turned on; if you need two stages, two will be turned on. Excessive cycling and wear and tear of electric components will be avoided, thus increasing their life reducing heating cost.
DTH Electric Boilers USE & CARE MANUAL (Revision November/05), Page 12.
R
Section 5: Maintenance
Properly maintained, your boiler will provide years of dependable, trouble free service. It is recommended that a regular routine maintenance program be established and followed by the user. Components are subject to eventual failure that requires service. Failure to use the correct procedures or parts in these circumstances may make the unit unsafe or reduce the life of the boiler.
The owner should have the following inspection and maintenance procedures performed:
5.1 BOILER WATER PIPING:
Yearly visual inspection.
Check all piping for signs of leakage near joints, unions and shut-off valves. Repair as needed.
5.2 PRESSURE RELIEF VALVE ON TOP OF BOILER:
Monthly inspection.
Must be manually operated to ensure safe and proper operation. By opening the pressure relief valve, the air trapped inside the heater tank is purged.
Make sure that the discharged water is directed to a suitable drain or other collection device, and will not spray onto anyone. Use the lever on the pressure relief valve to open. A steady discharge of hot water should occur. After releasing this lever the safety relief valve should close and fully shut off this flow. If the pressure relief valve does not function properly, it must be replaced with the same model or its equivalent. Do not plug the outlet of this valve if a dripping condition occurs.
5.3 BOILER PURGE
Yearly.
It is recommended that the boiler be purged annually, in order to eliminate sediment and sludge which may have accumulated at the bottom of the boiler and covered the heating elements.
Procedure
1. Let the boiler cool down
2. Close the maintenance valves connected to the boiler inlet and outlet. N.B.: It is not recommended to drain the water from the whole heating system.
3. Hook-up a garden hose to the drain valve and place it close to a floor drain.
4. Open the purge valve until the water comes out clean and clear
5. Close the valve
It is recommended to perform a visual inspection of the boiler electrical compartment annually, during the heating season, to ensure it is watertight and that there are no signs of component or wiring overheating. Repair as soon as possible if necessary. Defective components should always be replaced with the Original Manufacturer’s parts.
The manufacturer’s warranties DO NOT cover tank failure due to improper installation or maintenance. If the pressure relief valve on the heater discharges periodically, this may be due to thermal expansion. Immediately call a qualified service technician to inspect and to remedy as needed.
NOTE: To prevent premature tank failure, the air trapped inside the tank must be purged periodically. Use the safety relief valve on top of the tank to perform this task.
Before manually operating the relief valve, make certain no one will be sprayed with the hot water released by its opening. The water may be hot enough to create a SCALD hazard. The water released should be directed to a suitable drain to prevent injury or damage.
WARNING
!
DANGE
!
1
2
3
4
5
6
7
8
9
10
11
12
13
L1 L2 N
T T
C C
Legeng/Légende:
1) Main water supply / Alimentation d'ea u
2) Maintenance valve/ Valve d'entretien
3) Check valve/ Clapet anti-retour
4) Pressure reducer/ Réducteur de pression
5) Expension tank/ Réservoir d'expansion
6) Circulating pump/ Pompe circulatrice
7) Purge valve/ Robinet élimination d'a ir
8) Drain valve/ Valve drainage
9) Safety valve/ Valve de sécurité
10) T & P Gage/ Tridicateur
11) Automatic air vent/ Purgeur d'air
12) Flow check valve/ C lapet antigravité (required on systems without motorised zone valves) (requise sur les systèmes n'ayant pas de valv es motorisées)
13) Thermostat/ Thermostat
Schéma d'installation général/ General installation
GTH 240V
Simple zone/ Single zone
THERMO 2000 inc. GTH
Raccordement de pompe G TH 600V/ Pump wiring GTH 600V
T T
1
2
3
4
L2 L1
Pompe/Pump
jumper
Thermostat
Relais/Relay
RA89A
120Vac
Figure 2
Figure 14
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
L1 L2 N
T T
C C
Legeng/Légende:
1) Main water supply / Alimentation d'ea u
2) Maintenance valve/ Valve d'entretien
3) Check valve/ Clapet anti-retour
4) Pressure reducer/ Réducteur de pression
5) Expension tank/ Réservoir d'expansion
6) Circulating pump/ Pompe circulatrice
7) Purge valve/ Robinet élimination d'a ir
8) Drain valve/ Valve drainage
9) Safety valve/ Valve de sécurité
10) T & P Gage/ Tridicateur
11) Automatic air vent/ Purgeur d'air
12) Flow check valve/ C lapet antigravité (required on systems without motorised zone valves) (requise sur les systèmes n'ayant pas de valv es motorisées)
13) Motorized zone va lve/ Soupape électrique de zone
14) Hot water baseboard/ Plinthes chauff age
15) Thermostat/ Thermostat
Schéma d'installation général/ General installation
THERMO 2000 inc. GTH 240V
Zonage de plinthes/ Valve zoning to baseboard
Figure 3
Page 15
1
2
3
4
5
6
7
8
9
10
11
12
15
L1 L2 N
T T
C C
Legeng/Légende:
1) Main water supply / Alimentation d'ea u
2) Maintenance valve/ Valve d'entretien
3) Check valve/ Clapet anti-retour
4) Pressure reducer/ Réducteur de pression
5) Expension tank/ Réservoir d'expansion
6) Circulating pump/ Pompe circulatrice
7) Purge valve/ Robinet élimination d'a ir
8) Drain valve/ Valve drainage
9) Safety valve/ Valve de sécurité
10) T & P Gage/ Tridicateur
11) Automatic air vent/ Purgeur d'air
12) Flow check valve/ C lapet antigravité
13) Return header/ Collecteur de retour
14) Radiant infloor piping/ Plancher chauffant
15) Thermostat/ Thermostat
16) Supply header/ Collecteur d'alimentation
14
13
16
T=105 F
T=90 F
Schéma d'installation général/ General installation
THERMO 2000 inc. GTH 240V
Plancher chauffant direct/ Direct radiant heating loop
Figure 4
Page 16
1
2
3
4
5
6
7
8
9
10
11
12
15
L1 L2 N
T T
C C
Legeng/Légende:
1) Main water supply / Alimentation d'eau
2) Maintenance valve/ Valve d'entretien
3) Check valve/ Clapet anti-retour
4) Pressure reducer/ Réducteur de pression
5) Expension tank/ Réservoir d'expansion
6) Circulating pump/ Pompe circulatrice
7) Purge valve/ Robinet élimination d'air
8) Drain valve/ Valve drainage
9) Safety valve/ Valve d e sécur ité
10) T & P Gage/ Tridicateur
11) Automatic air vent/ Purgeur d'air
12) Injection valve/ Valve d'injection
13) Return header/ Collecteur de retour
14) Radiant infloor piping/ Plancher chauffant
15) Thermostat/ Thermostat
16) Supply header/ Collecteur d'alimentation
17) Circuit balancing valve/ Valve de balancement
18) Indoor- Outdoor controller/ Conjtrôleur modulant Int.-Ext.
19)Boiler water temp. sensor/ Sonde de température d ' ea u
20)Exterior temperature sen s o r / Sonde de temperature ex tér ieur
21) Ambiant temperature sensor/ Sonde de températur e ambiante
14
13
16
T=90 F - 105F
T=85 F
17
20
21
18
19
T=150 F
T=85 F
Schéma d'installation général/ General installation
THERMO 2000 inc. GTH 240V
Plancher chauffant modul a n t/ Modulating radiant heating loop
Figure 5
Diagramme électrique/ Wiring diagram
Figure 6
Page 18
Raccordement de pompe GTH 600V/ Wiring pump for GTH 600V
Relais de pompe/pump relay
24 Vac
Thermostat
T T
2
L2 L1
120Vac
1
Relais/Relay
RA89A
jumper
3
Pompe/Pump
4
Diagramme électrique/ Wiring diagram
Raccordement de zone valves/ Wiring for zoned valves system
Zone
valves
Thermostat
Zone 1
22
4
1
Zone
valves
3
Thermostat
Zone 2
22
4
1
Thermostat
Zone 3
22
Zone
valves
3
4
1
3
Note 1 Block terminal thermostat /Thermostat termin al b l oc k GTH240V: sur panneau électrique GTH/
on GTH electric pannel
GTH 600V: sur relais RA89A/
on relay RA89A
120 Vac
Electrical servic e
Transfo
40Va Transfo (3 zones ) 20Va Transfo (3 zones )
Raccordement de multiples circulateurs/ Wiring for multiple circulators
Thermostat
Zone 1
T
Relais/Relay
RA845A
Diagramme électrique/ Wiring diagram
Thermostat
Zone 2
T
4
6
12
3
5
Circulateur/
circulator
Zone 1
T
Relais/Relay
RA845A
2
TT
T
4
6
3
1
5
Circulateur/
circulator
Zone 2
Note 1
L2L1
120Vac
electrical service
L1 G
C1
TH1
TH2
R1
HL
C1
V2E2
R1Relais de pompe
WR 24A05A-1
Thermostat
Diagramme électrique/ Wiring diagram
GTH 240V
Modèle/Model 6 - 10 KW
Légende/ Legend
Voir/see note 2
Note 1: Bloc terminal (24 VAC) pour une installation avec le controleur bi-énergie Thermo 2000 modèle: "CBE-EM"/ Terminal block (24 VAC) for an installation with Thermo 2000 dual energy controller model: "CBE-EM"
Note 2: Couper le cavalier lorsque vous utilisez le controleur bi-énergie Thermo 2000 modèle: "CBE-EM"/ Cut open this jumper when using Thermo 2000 dual energy controller model: "CBE-EM"
TH
C
R
HL
Aquastat
Élément chauffant/ Heating element
Commutateur ON/OFF ON/OFF switch
Contacteur de puissance Power relay
Relais
Relay Lampe témoin
Pilot light
Haute limite Hi-Limit
N
CCTT
Circulateur/
Circulator
Bleu/
Blue
Jaune/
Yellow
Noir/
Black
Blanc/White
Rouge/Red
F
Fusible Fuse
C1
L2
B1 B1
Voir/see note 3
OPTION
Disjoncteur Braker
Voir note 1
Note 3: Disjoncteur en option/ Braker in option
B2
EL1
EL2
Cablage en usine/ Factory wiring
Cablage par l'installateur/ Wiring by others
Figure 7
Page 19
L1 G
C1
TH1
TH2
R1
HL
C1
Diagramme électrique/ Wiring diagram GTH 240V
modèle/ model 12 - 24 KW
Voir/see note 1
Voir/see note 2
N
F
C1
L2
C1
TH3
TH4
C1
Note 1: Bloc terminal (24 VAC) pour une installation avec le controleur bi-énergie Thermo 2000 modèle: "CBE-EM"/ Terminal block (24 VAC) for an installation with Thermo 2000 dual energy controller model: "CBE-EM"
Note 2: Couper le cavalier lorsque vous utilisez le controleur bi-énergie Thermo 2000 modèle: "CBE-EM"/ Cut open this jumper when using Thermo 2000 dual energy controller model: "CBE-EM"
Note 3: Disjoncteur en option/ Braker in option
Légende/ Legend
TH
C
R
HL
Aquastat
Élément chauffant/ Heating element
Commutateur ON/OFF ON/OFF switch
Contacteur de puissance Power relay
Relais
Relay Lampe témoin
Pilot light
Haute limite Hi-Limit
Fusible Fuse
Disjoncteur Braker
V2E2
R1
Thermostat
CCTT
Circulateur/
Circulator
Bleu/
Blue
Jaune/
Yellow
Noir/
Black
Blanc/White
Rouge/ Red
Relais de pompe
WR 24A05A-1
B1 B2 B1 B2
Voir/see note 3
OPTION
Voir/see note 3
OPTION
B3
EL1
EL2
EL3
EL4
Cablage en usine/ Factory wiring
Cablage par l'installateur/ Wiring by others
Figure 8
Page 20
L1 G
C1
TH1
TH2
R1
HL
C1
Diagramme électrique/ Wiring diagram GTH 240V
modèle/ model 27-33 KW
N
F
C2
L2
C1
TH3
TH4
C2
C1
TH5
TH6
C2
C2
B1 B2 B3
V2E2
R1
CCTT
Circulateur/
Circulator
Bleu/
Blue
Jaune/
Yellow
Noir/
Black
Blanc/ White
Rouge/ Red
Note 1: Bloc terminal (24 VAC) pour une installation avec le controleur bi-énergie Thermo 2000 modèle: "CBE-EM"/ Terminal block (24 VAC) for an installation with Thermo 2000 dual energy controller model: "CBE-EM"
Note 2: Couper le cavalier lorsque vous utilisez le controleur bi-énergie Thermo 2000 modèle: "CBE-EM"/ Cut open this jumper when using Thermo 2000 dual energy controller model: "CBE-EM"
Note 3: Disjoncteur en option sur modèle 27KW/ Braker in option on model 27 KW
B1 B2 B3 B4
Voir/see note 3
OPTION
Voir/see note 3
OPTION
Voir/see note 2
Voir/see note 1
Relais de pompe
WR 24A05A-1
Légende/ Legend
TH
C
R
HL
Aquastat
Élément chauffant/ Heating element
Commutateur ON/OFF ON/OFF switch
Contacteur de puissance Power relay
Relais
Relay
Lampe témoin Pilot light
Haute limite Hi-Limit
Fusible Fuse
Disjoncteur Braker
EL1
EL2
EL3
EL4
EL5
EL6
Cablage en usine/ Factory wiring
Cablage par l'installateur/ Wiring by others
Figure 9
Page 21
EL1
Figure 10
Page 22
EL2
Diagramme électrique/ Wiring diagram GTH 600V
modèle/ model 9 - 13 KW
L1 L2
L3
C1 C1 C1
R1
G
HL
TH1
V2
Voir/see note 1
E2
EL3
Voir note 2
R3
R1
R3
F3
F1
F2
600 V
Transfo
F4
120 V
C1
R1
Note 1: Bloc terminal (24 VAC) pour une ins tallation avec le controleur bi-énergie Thermo 2000 modèle: "CBE-EM"/ Terminal block (24 VAC) for an installation with Thermo 2000 dual energy controller model: "CBE-EM"
Note 2: Couper le cavalier lorsque vous utilisez le controleur bi-énergie Thermo 2000 modèle: "CBE-EM"/ Cut open this jumper when using Thermo 2000 dual energy controller model: "CBE-EM"
TH
C
Aquastat
Élément chauffant/ Heating element
Contacteur de puissance Power relay
Légende/ Legend
R
Relais
Relay Lampe témoi n
Pilot light
Commutateur ON/OFF ON/OFF switch
HL
Disjoncteur Braker
Haute limite Hi-Limit
Fusible Fuse
EL1
Figure 11
Page 23
Diagramme électrique/ Wiring diagram GTH 600V
modèle/ model 18 - 36 KW
L1 L2
C1 C1 C1
R1
G
L3
R2R2EL4
HL
TH1
TH2
EL2
EL3
Voir note 2
R3
R1
F3
F1
EL5
EL6
F2
600 V
Transfo
F4
120 V
C1
R1
R2
V2
Voir/see note 1
E2
TH
C
R3
Aquastat
Élément chauffant/ Heating element
Contacteur de puissance Power relay
Note 1: Bloc terminal (24 VAC) pour une installation avec le controleur bi-énergie Thermo 2000 modèle: "CBE-EM"/ Terminal block (24 VAC) for an installation with Thermo 2000 dual energy controller model: "CBE-EM"
Note 2: Couper le cavalier lorsque vous utilisez le controleur bi-énergie Thermo 2000 modèle: "CBE-EM"/ Cut open this jumper when using Thermo 2000 dual energy controller model: "CBE-EM"
Légende/ Legend
R
Relais
Relay Lampe témoin
Pilot light
Commutateur ON/OFF ON/OFF switch
HL
Disjoncteur Braker
Haute limite Hi-Limit
Fusible Fuse
L1 Diagramme électrique/ Wiring diagram
Figure 12
Page 24
Contrôle Bi-énergy/ Dual control energy CBE-EM
120 Vac
Transfo
24 Vac
Lumière haut tarif/
High tarif light
N
H
Sonde extérieur/
Outdoor sensor
V1
120 Vac
H
Interrupteur DPDT
Switch ON-OFF-ON
Cablage en usine/ Factory wiring
Cablage par l'installateur/ Wiring by others
Transfo
Bi-energie/ Dual energy Electrique/ Electric Mazout/ Oil
SPDT
Relais/ Relay
V3
SPDT
Relais/ Relay
E2 E1
T2
T1
Noir/ Black
Brun/ Brown
Bleu/ Blue
Relais GTH/
E2
GTH Relay
T
Relais chaudière mazout/ Oil boiler Relay
T
Electrique/ Electric
Mazout/ Oil
Valve 3 voies optionnelle/
Optional 3-way valve
Interrupteur DPDT
Switch ON-OFF-ON
V2
V2
B
AB
A
24 Vac
Sonde extérieur/
Outdoor sensor
H H V1V2 V3 T1 T2 E1 E2
Noir/ Black
Bleu/ Blue
Brun/ Brown
Valve 3 voies optionnelle/
Optional 3-way valve
Bi-energie/ Dual energy Electrique/ Electric Mazout/ Oil
Lumière haut tarif/
High tarif light
Chaudière électrique GTH/BTH Electric boiler GTH/BTH ("E2 V2" bornier 24 Vac/ terminal E2-V2)
Chaudière mazout Oil boiler ("T T" relais de combustion/ oil boiler burner)
1
2
3
4
5
6
7
8
9
10
11
12
15
L1 L2 N
T T
C C
16
T=150 F
o o o o o o o o o H H V1 V2 V3 T1T2 E1E 2
E2V2
Legeng/Légende:
1) Main water supply / Alimentation d'ea u
2) Maintenance valve/ Valve d'entretien
3) Check valve/ Clapet anti-retour
4) Pressure reducer/ Réducteur de pression
5) Expension tank/ Réservoir d'expansion
6) Circulating pump/ Pompe circulatrice
7) Purge valve/ Robinet élimination d'a ir
8) Drain valve/ Valve drainage
9) Safety valve/ Valve d e sécur ité
10) T & P Gage/ Tridicateur
11) Automatic air vent/ Purgeur d'air
12) Flow check valve/ C lapet antigravité (required on systems without motorised zone valves) (requise sur les systèmes n'ayant pas de valv es motorisées)
14) Dual energy outside senso r / S o n d e ex t. Bi-energie
15) Thermostat/ Thermostat
16) Dual energy control C BE- EM/ C o n trô le Bi-énergie CBE-EM
14
T T
N
L1
jumper/ cavalier
Schéma d'installation général/ General installation
THERMO 2000 inc. GTH 240V
Bi-Énergie sans va lve 3 voies/ Dual-energy without 3-way valve
Figure 13
Page 25
1
2
3
4
5
6
7
8
9
10
11
12
15
L1 L2 N
T T
C C
16
T=150 F
o o o o o o o o o H H V1 V2 V3 T1 T2 E1 E 2
E2V2
Legeng/Légende:
1) Main water supply / Alimentation d'ea u
2) Maintenance valve/ Valve d'entretien
3) Check valve/ Clapet anti-retour
4) Pressure reducer/ Réducteur de pression
5) Expension tank/ Réservoir d'expansion
6) Circulating pump/ Pompe circulatrice
7) Purge valve/ Robinet élimination d'a ir
8) Drain valve/ Valve drainage
9) Safety valve/ Valve d e sécur ité
10) T & P Gage/ Tridicateur
11) Automatic air vent/ Purgeur d'air
12) Flow check valve/ C lapet antigravité (required on systems without motorised zone valves) (requise sur les systèmes n'ayant pas de valv es motorisées)
14) Dual energy outside senso r / S o n d e ex t. Bi-energie
15) Thermostat/ Thermostat
16) Dual energy control C BE- EM/ C o n trô le Bi-énergie CBE-EM
17) Motorised 3 way valve/ Valve motorisée 3 voies
14
T T
L1
N
17
jumper/ cavalier
Noir
Bleu
Brun
B
A
AB
Schéma d'installation général/ General installation
THERMO 2000 inc. GTH 240V
Bi-Énergie avec valve 3 voies/ Dual-energy with 3-way valve
Figure 14
1
2
5
4
6
7
8
9
11
12
13
14
16
15
17
19
20
10
32
33
3
18
21
22
23
24
25
26
27
30
28
29
31
THERMO 2000 inc. GTH 6-10 KW 240V
Liste des pièces/ Part list
ITEM DESCRIPTI ON NUMERO IT EM DESCRIPTION NUMERO ITEM DESC RIPT ION NUMERO
1 Chaudière/ Boiler 13 Isolation/ Insulation 25 Porte fusible/ Fuse holder 1 pole class midjet 2 Pui t Haute-limite/ Hi-limit well 14 Interrupteur/ Switch ON-OFF 26 Relais de pompe/ Pump relay WR 24 A05A-1 3 Pui t aquastat/ aquastat well 15 Dessus cabinet/ Cabinet top 27 Relais bi-énergie/ Dual energy relay 4 Haute-limite Ranco L6/ Hi-limit Ranco L6 16 Thermomanomètre/ Tridicator 0/60 psi 30/240F 28 Bloc terminal/ Terminals blocks 5 Bouchon 1/2'' NPT/ Plug 1/2'' NP T 17 Valve de sécûrité/ Safety valve, 30psi, 3/4''Mx 3/4''F 29 Bloc terminal/ Terminals blocks 6 Él éments/ Heating elements 3, 4.5 , 5Kw ; 240V 18 Support chaudière/ Boiler bracket 30 Disjoncteur 1 pôle/ 1 pole braker 15Am p 7 Porte gauche cabinet/ Cabinet left door 19 Lumière/ Pilot light 31 Aquastat G1-11781 8 Pl ancher cabinet/ Cabinet floor 20 Support mural/ Mounting bracket 32 Fusible/ Fuse 15A 250V class midjet Ferraz TRM15
9 Valve de drainage/ Drain valve 21 Bornier de mise à terre/ Grund connector 33 Plaque d'éléments/ Elem ent plate 10 Panneau électrique/ Electrical pannel 22 Bornier d'alimentation/ Power block 11 Porte devant cabinet/ Cabinet front door 23 Disjoncteur 2 pôles/ 2 poles braker 35,60,50Amp,240V 12 Porte droite cabinet/ Cabinet right door 24 Contacteur/ C ontactor 2poles, 50Amp res, 120V bobine
Figure 15
Page 27
1
2
5
4
6
7
8
9
11
12
13
14
16
15
17
19
20
10
32
3
18
21
22
23
24
25
26
27
30
28
29
31
THERMO 2000 inc. GTH 12-24 KW 240V
Liste des pièces/ Part list
ITEM DESCRI PTION NUMERO ITEM DESCRIPTION NUMERO ITEM DESCRIPTI ON NUM ERO
1 Chaudière/ Boiler 13 Isolation/ I nsulati on 25 Porte fusible/ Fuse holder 1 pole class midjet 2 Puit Haute-limite/ Hi-limit well 14 Interrupteur/ Sw itch ON-OFF 26 Relais de pompe/ Pump relay WR 24A05A-1 3 Puit aquastat/ aquastat well 15 Dessus cabinet/ Cabinet top 27 Relais bi-énergie/ Dual energy relay 4 Haute-limite Ranco L6/ Hi -li mit Ranco L6 16 Thermom a nomètre/ Tridicator 0/60 psi 30/240F 28 Bloc terminal/ Term inals blocks 5 Bouchon 1/2'' NP T/ Plug 1/2'' NPT 17 Valve de sécûrité/ Safety valve, 30psi, 3/4''Mx 3/4''F 29 Bloc terminal/ Terminals blocks 6 Éléments/ Heating elements 3, 4.5 , 5, 6Kw; 240V 18 Support chaudière/ Boiler bracket 30 Disjoncteur 1 pôle/ 1 pole braker 15Amp 7 Porte gauche cabinet/ Cabinet left door 19 Lumière/ Pilot light 31 Aquastat G1-11781 8 Plancher cabinet/ Cabinet floor 20 Support mural/ M o unting bracket 32 Fusible/ Fuse 15A 250V class midjet Ferraz TRM15
9 Valve de drainage/ Drain valve 21 Bornier de mise à terre/ Grund connector 10 Panneau électrique/ Electrical pannel 22 Bornier d'alimentation/ Power block 11 Porte devant cabinet/ Cabinet front door 23 Disjoncteur 2 pôles/ 2 poles braker 35,60,50Amp,240V 12 Porte droite cabinet/ Cabinet right door 24 Contacteur/ Contactor 4poles, 50Amp res, 120V bobine
Figure 16
Page 28
1
2
5
4
6
7
8
9
11
12
13
14
16
15
17
19
20
10
32
3
18
21
22
23
24
25
26
27
30
28
29
31
THERMO 2000 inc. GTH 27-33 KW 240V
Liste des pièces/ Part list
IT EM DESCRI PTION NUM ERO ITEM DESCRIPTION NUMERO ITEM DESCRI PTION NUM ERO
1 Chaudière/ Boile r 13 Isolation/ Insulation 25 Porte fusible/ Fuse holder 1 pole class midjet 2 Pui t Haute-limite/ Hi-limit well 14 Interrupteur/ Sw itch ON-OFF 26 Relais de pompe/ Pump relay WR 24A05A-1 3 Pui t aquastat/ aquastat well 15 Dessus cabinet/ Cabinet top 27 Relais bi-énergie/ Dual energy relay 4 Haute-limite Ranco L6/ Hi-limit R an co L6 16 Thermomanomètre/ Tridicator 0/60 psi 30/240F 28 Bloc terminal/ Terminals blocks 5 Bouchon 1/2'' NP T/ Plug 1/2'' NPT 17 Valve de sécûrité/ Safety valve, 30psi, 3/4''Mx 3/4''F 29 Bloc terminal/ Terminals blocks 6 Él éments/ Heating elements 4.5 , 5, 6Kw; 240V 18 Support chaudière/ Boiler bracket 30 Disjoncteur/ Braker 15Amp 7 Porte gauche cabinet/ Cabinet left door 19 Lumière/ P ilot light 31 Aquastat G1-11781 8 Pl ancher cabinet/ Cabinet floor 20 Support mural/ Mounting bracket 32 Fusible/ Fuse 15A 250V class midjet Ferraz TRM15
9 Valve de drainage/ Drain valve 21 Bornier de mise à terre/ Grund connector 10 Panneau électrique/ Electrical pannel 22 Bornier d'alimentation/ Power block 11 Porte devant cabinet/ Cabinet front door 23 Disjoncteur/ Braker 60,50Amp,240V 12 Porte droite cabinet/ Cabinet right door 24 Contacteur/ Contactor 3 poles, 50Amp res, 120V bobine
Figure 17
Page 29
1
2
5
4
6
7
8
9
11
12
13
14
16
15
17
19
20
10
32
33
30
3
18
21
22
23
24
25
26
27
28
29
31
THERMO 2000 inc. GTH 9-13 KW 600V
Liste des pièces/ Part list
ITEM DESCRIPTION NUMERO ITEM DESCRIPTION NUMERO ITEM DESCRIPTION NUMERO
1 Chaudière/ Boiler 13 Isolation/ Insulation 25 Porte fusible/ Fuse holder 2 poles class cc 2 Pui t Haute-limite/ Hi-limit well 14 Interrupteur/ Sw itch ON-OFF 26 Transfo 50VA 600V/120V 3 Pui t aqu astat/ aquastat well 15 Dessus cabinet/ Cabinet top 27 Porte fusible/ Fuse holder 2 poles migjet class 4 Haute-limite Ranco L6/ Hi-limit Ranco L6 16 Thermomanom ètre/ Tridicator 0/60 psi 30/240F 28 Relais bi-énergie/ Dual en ergy relay 5 Bouchon 1/2'' NPT/ Plug 1/2'' NP T 17 Valve de sécûrité/ Safety valve, 30psi, 3/4''Mx 3/4''F 29 Bloc terminal/ Terminals blocks 6 Él éments/ Heating elements 3, 4.5Kw; 347V 18 Support chaudière/ Boiler bracket 30 Fusible/ Fuse 6/10A 250V class midjet Ferraz TRM6/10 7 Porte gauche cabinet/ Cabinet left door 19 Lumière/ Pilot light 31 Aquastat G1-11781 8 Pl an cher cabinet/ Cabin et floor 20 Support mural/ Mounting bracket 32 Fusible/ Fuse 1/4A 600V class cc Ferraz ATQR 1/4
9 Valve de drainage/ Drain valve 21 Bornier de mise à terre/ Grund connector 33 Plaque élément/ Elem en ts plate 10 Panneau électrique/ Electrical pannel 22 Bornier d'alimentation/ Power block 11 Porte devant cabinet/ Cabinet front door 23 Contacteur/ Contactor 3poles, 50Amp res, 120V bobine 12 Porte droite cabinet/ Cabinet right door 24 Contacteur/ Contactor 2poles, 50Amp res, 120V bobine
Figure 18
Page 30
1
2
5
4
6
7
8
9
11
12
13
14
16
15
17
19
20
10
32
33
30
3
18
21
22
23
24
25
26
27
28
29
31
THERMO 2000 inc. GTH 18-36 KW 600V
Liste des pièces/ Part list
IT EM DESCRIPTI ON NUMERO ITEM DESC RIPTION NUM ERO IT EM DES CRIPTION NUMERO
1 Chaudière/ Boiler 13 Isolation/ Insulation 25 Porte fusible/ Fuse holder 2 poles class cc
2 Pui t Haute-limite/ Hi-limit well 14 Interrupteur/ Switch ON-OFF 26 Transfo 50VA 600V/120V
3 Pui t aquastat/ aquastat well 15 Dessus cabinet/ C abinet top 27 Porte fusible/ Fuse holder 2 poles migjet class
4 Haute-limite Ranco L6/ Hi-limit Ranco L6 16 Thermomanomètre/ Tridicator 0/60 psi 30/240F 28 Relais bi-énergie/ Dual energy relay
5 Bouchon 1/2'' NP T/ Plug 1/2'' NPT 17 Valve de sécûrité/ Safety valve, 30psi, 3/4''Mx 3/4''F 29 Bloc terminal/ Terminals blocks
6 Él éments/ Heating elements 3, 4.5Kw ; 347V 18 Support chaudière/ Boil er bracket 30 Fusible/ Fuse 6/10A 250V class midjet Ferraz TRM6/10
7 Porte gauche cabinet/ Cabinet left door 19 Lumière/ Pilot light 31 Aquastat G1-11781
8 Pl ancher cabinet/ Cabine t floor 20 Support mural/ Mounting bracket 32 Fusible/ Fuse 1/4A 600V class cc Ferraz ATQR 1/4
9 Valve de drainage/ Drain valve 21 Bornier de mise à terre/ Grund connector
10 Panneau électrique/ Electrical pannel 22 Bornier d'alimentation/ Pow er block 11 Porte devant cabinet/ Cabinet front door 23 Contacteur/ Contactor 3poles, 50Amp res, 120V bobine 12 Porte droite cabinet/ Cabinet right door 24 Contacteur/ Contactor 2poles, 50Amp res, 120V bobine
Figure 19
Page 31
GTH LIMITED WARRANTY
Warranty Coverage for Residential Installation.
Thermo 2000 Inc. hereby warrants to the original residential purchaser that the GTH tank installed in a residential setting shall be free of leaks during normal use and service for a period of ten (10) years from the date of purchase as long as the original residential purchaser owns the home in which the unit was originally installed, the first (5) years in full and years six (6) through ten (10) prorated 20% each year at suggested retail price. Residential setting shall mean usage in a single­family dwelling in which the consumer resides on a permanent basis. Also, residential setting shall mean use in multiple family dwellings in which one (1) GTH tank is to be use in only one (1) dwelling. In the event that a leak should develop and occur within this limited warranty period due to defective material or workmanship, such leak having been verified by an authorized company representative, Thermo 2000 inc. will repair or replace at our sole option the failed unit with the nearest comparable model at the time of replacement.
The original residential purchaser is responsible for all costs associated with the removal and reinstallation, shipping and handling to and from manufacturing plant. The replacement unit will be warranted for the remaining portion of the original Warranty.
Warranty Coverage for Commercial Installation.
Thermo 2000 Inc. warrants to the original purchaser that the GTH tank installed in a commercial setting for ten years, the first (5) years in full and years six (6) through ten (10) prorated 20% each year at suggested retail price
Commercial setting shall mean use in other than residential setting stated above in the residential setting definition. In the event that a leak should develop and occur within this limited warranty period due to defective material or workmanship, such leak having been verified by an authorized company representative, Thermo 2000 inc. will repair or replace at our sole option the failed unit with the nearest comparable model at the time of replacement.
The original purchaser is responsible for all costs associated with the removal and reinstallation, shipping and handling to and from Manufacturer. The replacement unit will be warranted for the remaining portion of the original Warranty.
Limited one year warranty on all GTH components & parts
All other GTH components & parts are warranted for a period of one (1) year against defects due to defective material or workmanship. The original purchaser is responsible for all costs associated with the removal and reinstallation, shipping and handling to and from Manufacturer. The components, repaired or replaced are warranted for the residual period of the initial warranty on the unit.
Exclusions.
This warranty is void and shall not apply if:
1. Defects or malfunctions resulting from installation, repair, maintenance and/or usage that are not done in conformity with the manufacturer’s installation manual; or
2. Defects or malfunctions resulting from installation, maintenance, or repair that are not done in accordance with regulations in force; or
3. Defects or malfunctions resulting from improper installation, maintenance or repair done carelessly or resulting from consumer damage (improper maintenance, misuse, abuse, accident or alteration); or
4. Installation in which a relief valve (pressure) is not installed or if it is not functioning properly, or when it is not connected to a drain to avoid damage to the property; or
5. Installation in which liquid circulating in the tank does not remain in closed circuit or installation in which piping is leaking; or
6. A polybutylene pipe or radiant panel installation without an oxygen absorption barrier is used; or
7. Installation where the acidity of water is not within the normal Environmental Protection Agency (EPA) (between pH 6.5 – 8.5) guidelines or the domestic water contains abnormal levels of particulate matter or water exceeding 10.5 gpg; or
8. Your home contains any type of water softener system and the unit is not installed and maintained in accordance with the manufacturer specifications; or
9. The GTH unit is being subject to non authorized modifications; or
10. Defects or malfunction resulting of storing or handling done elsewhere than Thermo 2000’s manufacturing plant; or
11. Units on which the serial number is removed or obliterated.
Limitations.
Thermo 2000 shall not be responsible for any damage, loss, and inconvenience of any nature whatsoever, directly or indirectly, relating to the breakdown or malfunction of the unit. This warranty limits its beneficiary’s rights. Nevertheless, the beneficiary may have other rights, which vary from state to state.
This warranty replaces any other expressed or implicit warranty and constitutes the sole obligation of Thermo 2000 towards the consumer. The warranty does not cover cost of removal, reinstallation or shipping to repair or replace the unit, nor administration fees incurred by the original consumer purchaser.
Thermo 2000 reserves its rights to make changes in the details of design, construction, or material, as shall in its judgment constitute an improvement of former practices.
This warranty is valid only for installations made within the territorial limits of Canada and the United States.
In order to receive the benefit of this warranty, the original consumer purchaser must fill in and return the attached registration card within thirty (30) days of date of purchase.
Warranty service procedure
Only authorized GTH dealers are permitted to perform warranty obligations. The owner or its contractor must provide Thermo 2000’s head office or authorized depot with defect unit together with the following information: GTH model and serial number, copy of the original sales receipt and owner’s identification certificate.
THERMO 2OOO INC.
500, 9th Avenue, Richmond (Qc) Canada J0B 2H0 Phone: (819) 826-5613 Fax: (819) 826-6370
www.thermo2000.com
Loading...