THERMO 2000 DTH 45, DTH 54, DTH 72, DTH 78, DTH 60 Use & Care Manual

...
DTH
Electric Boilers
M
odels ranging from 42 kW to 144 kW :
USE & CARE MANUAL
WITH INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR
Your DTH’s Electric Boiler has been carefully assembled and factory tested to provide years of trouble-free service. In order to ensure performance, the following information and safety precautions are provided to enable proper installation, operation, and maintenance of this product.
It is imperative that all persons who are expected to install, operate or adjust this electric boiler should read these instructions carefully to fully understand how to do so.
Any questions regarding the operation, maintenance, service or warranty of this electric boiler should be directed to the supplier.
When all installation steps have been completed, insert this installation manual in its original envelope, and keep in a safe place (close to the boiler) for future reference.
THERMO 2000 INC. Revision June 2014
Printed in Canada
DTH Electric Boilers USE & CARE MANUAL
(Revision June 2014)
, Page 2.
Section 1 : Dimensions & Specifications
Table 1: Electric Ratings for 240 VAC (1 phase) Electric Boilers:
Model
P
Kw
Current
Amp
Heating
Elements
Elements
Stages
Aquastats
Lights
Contactors
Sequencers
DTH 42 42 175 7 X 6KW 7 7 7 2 1 DTH 48 48 200 8 X 6KW 8 8 8 2 1 DTH 54 54 225 9 X 6KW 9 9 9 3 2 DTH 60 60 250 10 X 6KW 10 10 10 3 2 DTH 66 66 275 11 X 6KW 11 11 11 3 2 DTH 72 72 300 12 X 6KW 12 12 12 3 2 DTH 78 78 325 13 X 6KW 13 13 13 4 3 DTH 84 84 350 14 X 6KW 14 14 14 4 3 DTH 90 90 375 15 X 6KW 15 15 15 4 3 DTH 96 96 400 16 X 6KW 16 16 16 4 3
Table 2: Electric Ratings for 480 VAC (3 phases) Electric Boilers:
Model
P
Kw
Current
Amp
Élements
(277V)
Stages Aquastats Lights
Power
contactors
Secondary contactors
Sequencers
DTH 45 45 54 9 X 5KW 3 3 3 2 3 1 DTH 54 54 65 9 X 6KW 3 3 3 2 3 1 DTH 60 60 72 12 X 5KW 4 4 4 2 4 1 DTH 72 72 87 12 X 6KW 4 4 4 2 4 1
DTH 78 78 94
12 X 5KW
3 X 6KW
5 5 5 3 5 2 DTH 90 90 108 15 X 6KW 5 5 5 3 5 2 DTH 99 99 119
9 X 5KW 9 X 6KW
6 6 6 3 6 2
DTH 102 102 123
12 x 6KW
6 x 5Kw
6 6 6 3 6 2
DTH 108 108 130 18 x 6 KW
6 6 6 3 6 2
DTH 120 120 144 24 X 5KW 8 8 8 4 8 3 DTH 132 132 159
12 X 5KW 12 X 6KW
8 8 8 4 8 3
DTH 144 144 173 24 X 6KW 8 8 8 4 8 3
DTH Electric Boilers USE & CARE MANUAL
(Revision June 2014)
, Page 3.
Table 3: Electric Ratings for 600 VAC (3 phases) Electric Boilers:
Model
P
Kw
Current
Amp
Élements
(347V)
Stages Aquastats Lights
Power
contactors
Secondary contactors
Sequencers
DTH 45 45 43 9 X 5KW 3 3 3 2 3 1 DTH 54 54 52 9 X 6KW 3 3 3 2 3 1 DTH 60 60 58 12 X 5KW 4 4 4 2 4 1 DTH 72 72 69 12 X 6KW 4 4 4 2 4 1
DTH 78 78 75
12 X 5KW
3 X 6KW
5 5 5 3 5 2 DTH 90 90 87 15 X 6KW 5 5 5 3 5 2 DTH 99 99 95
9 X 5KW 9 X 6KW
6 6 6 3 6 2
DTH 102 102
98
12 x 6KW
6 x 5Kw
6 6 6 3 6 2
DTH 108 108 104 18 x 6 KW 6 6 6 3 6 2 DTH 120 120 115 24 X 5KW 8 8 8 4 8 3
DTH 132 132 127
12 X 5KW 12 X 6KW
8 8 8 4 8 3
DTH 144 144 139 24 X 6KW 8 8 8 4 8 3
Table 4: Connections sizes & Boiler overall dimensions
Connections sizes Boiler overall dimensions
Boiler inlet 2 “ NPT M Height 33 po Boiler outlet 2 “ NPT M Depth 46 po Waterworks 1/2 “ NPT M Width 22 po Safety valve 3/4 “ NPT F Shipping weight 395lbs
Drain valve 3/4 “ NPT M Volume 35.6 Gal US.
Operating temperature : from 50°F to 190°F.; Maximum operating pressure:
Models at 480 & 600V :
45 to 72 kW : 30 psi. or 60psi
(See boiler identification plate)
78 to144kW :: 60psi
Models at 240V/1ph :
42 & 48kW : 30 psi ou 60lpsi
(See boiler identification plate)
54 to 96kW : 60 psi
DTH Electric Boilers USE & CARE MANUAL
(Revision June 2014)
, Page 4.
Figure 1 : Component identification
DTH Electric Boilers USE & CARE MANUAL
(Revision June 2014)
, Page 5.
General Safety Precautions
Be sure to read and understand the entire Use & Care Manual before attempting to install or to operate this electric boiler. Pay particular attention to the following General Safety Precautions. Failure to follow these warnings could cause property damage, bodily injury or death. Should you have any problems understanding the instructions in this manual, STOP, and get help from a qualified installer or technician.
Section 2 : Introduction
The important safeguards and instructions appearing in this manual are not meant to cover all possible conditions and situations that may occur. It should be understood that common sense, caution and care are factors which cannot be built into every product. They are the responsibility of the person(s) caring for and operating the unit.
2.1 LOCAL INSTALLATION REGULATIONS
This electric boiler must be installed in accordance with these instructions and in conformity with local codes, or in the absence of local codes, with the National Plumbing Code and the National Electric Code current edition. In any case where instructions in this manual differ from local or national codes, the local or national codes take precedence.
2.2 CORROSIVE ATMOSPHERE
The electric boiler should not be located near an air vent containing a corrosive atmosphere or high humidity. The limited warranty is void when the failure of the electric boiler is due to a corrosive atmosphere.
2.3 SHIPMENT INSPECTION
Inspect the electric boiler for possible shipping damage. The manufacturer’s responsibility ceases upon delivery of goods to the carrier in good condition. Consignee must file any claims for damage, shortage in shipments, or non­delivery immediately against carrier.
2.4 CHECK LIST
Please check the identification tag on the unit to make sure you have the right model, voltage and pressure rating.
List of components shipped with the unit :
Pressure relief valve.
Drain valve.
Tridicator (temperature & pressure
gage).
The electric boiler should not be located in an area where leakage of the tank or water connections will result in damage to the adjacent area or to lower floors of the structure. When such areas cannot be avoided, a suitable drain pan or non­flammable catch pan, adequately drained, must be installed under the boiler. The pan must be connected to a drain. NOTE: Auxiliary catch pan MUST conform to local codes.
!
CAUTION
!
WARNING
!
DTH Electric Boilers USE & CARE MANUAL
(Revision June 2014)
, Page 6.
Section 3 : INSTALLATION
The manufacturer’s warranty does not cover any damage or defect caused by installation, or attachment, or use of any special attachment other than those authorized by the manufacturer, into, onto, or in conjunction with the boiler. The use of such unauthorized devices may shorten the life of the boiler and may endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized devices
3.1 SECURITY CONSIDERATIONS
Domestic and commercial installations have a maximum design operating pressure limited to 30 psi (207 kPa) or 60psi (414kPa) by a safety relief valve.
Boiler maximum operating temperature is 190°F by design. This boiler is designed to be used
only in a hot water heating system.
The heat transfer medium must be water or other non-toxic fluid. An antifreeze solution with propylene glycol specially formulated for heating system could be used up to a maximum concentration of 50%
3.2 LOCATION
The electric boiler should be installed in a clean, dry location. Long hot water lines should be insulated to conserve energy. The electric boiler and water lines should be protected from exposure to freezing temperatures.
The electric boiler must be installed horizontally directly on the floor or wall. Supporting legs are included but wall mounting brackets are not.
The electric boiler must be located or protected so as not to be subject to physical damage, for example, by moving vehicles, area flooding, etc. All models can be installed on combustible floors and in alcoves. Ambient temperature must not exceed 80°F or 27°C.
3.3 CLEARANCE
Minimum clearances for adequate inspection and servicing are listed in the following table:
Table 4: Boiler clearance
Left side 14 inches Right side 14 in.(78to144kW 480&600v)
(54to96kWx 240v)
0in. Other models Top & bottom of the boiler
12 inches Front side of the
boiler
24 inches Back side of the
boiler
0 inch
3.4 SYSTEM SETUP
The recommended piping arrangement is shown in Figure 4, 5 and 6 including the pump, expansion tank, drain valve, pressure relief valve, air vent, flow check valve and pressure­temperature gauge. Details about each item follow.
3.4.1 Boiler connections
This electric boiler may be connected individually or in parallel with other boilers. If two or more boilers are connected, the “reverse­return piping” method (whereby the boiler with the first return inlet also has the last supply outlet and so forth until the last return inlet corresponds to the first supply outlet) should be used to connect the boilers in parallel, to ensure an equal water flow rate through each boiler.
The boiler water supply, located on the top side, and the boiler water return, located on the bottom side of the boiler are steel pipes (male NPT threaded connection) where supply and return line connections are to be made.
Installing a union is recommended on the boiler water supply and return lines to facilitate boiler disconnection for servicing.
Dielectric unions are required for protection of the boiler and piping if dissimilar pipe material such as galvanized steel and copper are present.
WARNING
!
CAUTION
!
DTH Electric Boilers USE & CARE MANUAL
(Revision June 2014)
, Page 7.
Use only clean, new piping for boiler water lines. Local codes or regulations shall govern the exact type of material to be used. Insulate all pipes containing hot water, especially in unheated areas. Install shutoff (ball) valves for servicing convenience. Thermometer(s) should be installed on the boiler water supply and return lines. Cap or plug unused connections on the boiler. Do not cap the pressure relief valve on the boiler since it will damage and shorten the life of the boiler and may endanger life and property.
3.4.2 Flow check valve
If the heating system includes a single pump, then to minimize flow by gravity and heat loss during non-draw periods, a flow check valve
must be installed.
3.4.3 Pressure relief valve
An automatic pressure relief valve must be installed during boiler setup. The pressure rating of the relief valve must not exceed the pressure design of the boiler as shown on the pressure vessel name plate. The safety relief valve must meet the requirements of the ASME Boiler and Pressure Vessel Code and limit the maximum operating boiler pressure. It is a safety device, not an operating control. The BTU per hour rating of the relief valve must equal or exceed the BTU per hour input of the boiler(s) or heat source(s) as marked on the boiler(s) rating plate. Connect the outlet of the relief valve to a discharge line with its lower tip at most 6” above a floor drain, well clear of any live electrical parts. The discharge line must pitch downward from the valve to allow complete draining by gravity of the relief valve and discharge line, and be of a diameter no smaller than that of the valve outlet. The tip of the discharge line should not be threaded or concealed and should be protected from freezing. No valve of any type, restriction or reducer coupling should be installed on the discharge line. Local codes shall govern the installation of relief valves.
3.4.4 System pressure control and expansion tank
Pressure control devices within the system ensure that each component operates within minimum and maximum allowable pressures and maintain minimum pressure for all normal operating temperatures. They also allow air
bleeding, prevent cavitation at the pump inlet and prevent water from boiling within the system; all this is accomplished with minimal addition of new water.
The increase in boiler water volume resulting from higher temperature is stored in the expansion tank during periods of high operating temperature and is returned to the system when the temperature decreases.
The expansion tank must be able to store the required volume of boiler water during maximum design operating temperature without exceeding the maximum allowable operating pressure, and to maintain the required minimum pressure when the system is cold. Contact your installing contractor, plumbing supply house, or local plumbing inspector for assistance. The point where the expansion tank is connected should be carefully selected to avoid the possibility that normal operation of automatic check or manual valves will isolate the tank from a hot boiler or any part of the system. Pre­charged diaphragm expansion tanks are preferable to air control (see section 3.4.6). These tanks incorporate a balloon-like bladder or diaphragm. It is inflated, prior to filling the system, to a pressure equal to the setting of the water pressure makeup regulator. The expansion tank should be located on the suction or intake side of the pump. The pump can be located either just upstream or just downstream from the boiler.
3.4.5 Water pressure makeup regulator
Make-up systems must be employed as required by codes. An automatic fill valve must be used with a backflow preventer as required, to maintain minimum system pressure by supplying water to make up for leakage.
3.4.6 Air bleeder
Oxygen should be excluded from the system to prevent corrosion. As hinted at in section 3.4.4, this precludes the use of air in direct contact with the boiler water as a pressurization means.
Installation of manual or automatic air vent devices prevents air from accumulating in the system. Air vents should be installed at all high points to remove trapped air during initial setup and to ensure that the system is tight. Regularly purge the air out of the system while taking care to avoid personal injuries or property damage caused by hot boiler water spray.
DTH Electric Boilers USE & CARE MANUAL
(Revision June 2014)
, Page 8.
3.4.7 Circulator zoning recommendations
The preferred location of the circulator pump for each zone is on the boiler supply side, with the expansion tank between the boiler and the pump.
A flow check valve must be installed in each zone, preferably on the outlet side of each circulator pump, to prevent water flow to other zones where no heat is required.
3.4.8 Zone valve zoning recommendations
The preferred location of the circulator pump is on the boiler supply side, with the expansion tank between the boiler and the circulator. Use zone valves with low pressure drop.
3.4.9 Pump & pipe sizing
3.4.9.1 Boiler water temperature drop (BWTD) through the heating loop A simplified design method based on a 20°F temperature drop (BWTD) between boiler outlet and inlet is commonly used. Although such a method is widely used and generates satisfactory system performance when applied properly, it does not determine the system operating point. The pipe size is often uneconomically large, and the actual system flow rate is likely to be much higher than intended. Such design methods seldom consider temperature drops higher than 20°F, which results in overdesign.
Another method by which the boiler water temperature drop (BWTD) could be calculated is to assume a constant supply boiler water temperature minus the return boiler water temperature. For example a boiler might have a return temperature of 140 °F. Assuming a constant supply boiler temperature of 180 °F, the BWTD would be 40 °F ( = 180 °F – 140 °F). Second example: If the boiler water has a return temperature of 120 °F and the boiler supply is at 140 °F, then the temperature drop is 20 °F (=140 °F – 120 °F).
The following table suggests temperature drops (BWTD) to be used in calculating the pump flow rate.
Table 5: Temperature rise through the boiler
PROPOSED BOILER WATER
TEMPERATURE RISE THROUGH THE
BOILER (BWTD)
System
type
Boiler water
Supply
tempera-
ture
Boiler water
Return
tempera-
ture
BWTD
Baseboards
190°F to
140°F
170°F to
120°F
20°F to
40°F
Cast Iron
Radiators
160°F to
130°F
140°F to
110°F
20°F to
40°F
Radiant
In-Floor
130°F to
90°F
110°F to
70°F
10°F to
20°F
3.4.9.2 Pump flow rate calculation The boiler output rating must correspond to the calculated heating load. Use the equation below to calculate the pump flow rate.
Pump flow rate = Boiler output ÷÷÷÷ BWTD ÷÷÷÷ 500
Pump flow rate is expressed in US gallons per minute or GPM.
The Boiler output ( in net BTU per hour) is the maximum amount of heat to be transferred through the heating loop to meet the heating load.
BWTD is the boiler water temperature drop
For example, an electric boiler rated at 144KW has a power output of 491,328 BTU per hour. The system is designed for a temperature drop (BWTD) of 20°F.
Required pump flow rate = 491,328 ÷ 20 ÷ 500 =
49.1 GPM
The following table lists the required pump flow rate as a function of boiler power and BWTD.
Loading...
+ 16 hidden pages