COMBOMAXMC Electric boiler Set-up, use and care guide
(revised Oct 2015)
, Page 8.
3.6.2 Expansion tank on the cold water
supply line
Determine if a flow check valve, a back flow
preventer, a pressure-reducing valve, a water
meter or a water softener is present on the cold
water supply line.
A flow check valve creates a closed system and
prevents the water, as it is being heated, from
expanding back into the cold water supply line.
Pressure can build up within the water heater,
causing the pressure relief valve to operate
during a heating cycle. This excessive operation
can cause premature failure of the relief valve
and possibly of the water heater itself.
Replacing the relief valve will not correct the
problem. One method of preventing pressure
build-up is to install an expansion tank on the
cold water supply line between the
COMBOMAXMC unit and flow check valve.
Contact your installing contractor, water
supplier, local plumbing inspector or plumbing
supply house for assistance.
3.6.3 Recirculation line (if applicable)
If a recirculation line is installed, the return
connection should be made to a tee close to the
inlet connection on the water heater. A check
valve should always be installed in the
recirculation line to prevent cold water from
entering.
3.6.4 Domestic hot water pressure relief
valve
An automatic pressure relief valve must be
installed on a tee installed on the domestic hot
water pipe coming out of the water heater. No
valve of any type should be placed between the
safety relief valve and the water heater. The
pressure rating of the relief valve must not
exceed 150 psi.
The BTU per hour rating of the relief valve must
equal or exceed the BTU per hour input of the
boiler(s) or heat source(s) as recorded on the
boiler(s) rating plate.
Connect the outlet of the relief valve to a
suitable open drain, with the discharge at most
6” above the floor, far from any live electrical
parts. The discharge line must pitch downward
from the valve to allow complete draining and be
no smaller than the outlet of the valve. The end
of the discharge line should not be threaded or
concealed and should be protected from
freezing. No valve of any type, restriction or
reducer coupling should be installed in the
discharge line. Local codes shall govern the
installation of relief valves.
3.6.5 Thermostatically controlled mixing
valve (included)
For general-purpose hot water requirements in a
domestic environment, a thermostatically
controlled mixing valve is recommended to
reduce the risk of scald injury. Contact a
licensed plumber or the local plumbing authority
for further information. Adjust the mixing valve to
the lowest required temperature setting.
3.7 BOILER WIRING
The boiler cabling and grounding must conform
to local codes or, in their absence, to the
National Electrical Code.
Power must be provided by a 120/240 volt
(single phase, 60 Hz) circuit, appropriately fused
and with 3-wire plus ground cabling of sufficient
gage. The fuse and cabling gauge may be
determined from the boiler rating plate.
3.8 CIRCULATOR WIRING
The COMBOMAXMC heating pump (120 Vac,
1/25 Hp) is connected to the C&C terminals on
the boiler electrical panel. The control circuit is
designed to start the pump upon receiving a
heating signal from the thermostat or priority
aquastat.
3.9 CONNECTING THE THERMOSTAT
3.9.1 Single heating zone
Connect the low-voltage thermostat to the T&T
terminals on the COMBOMAXMC electrical panel
(DO NOT apply current to these terminals).
(see figure 2&3).
3.9.2 Zone valve zoning
Connect the low-voltage thermostat to the zone
valve. The components must wired such that,
upon a heating signal from a thermostat, only
the corresponding zone valve will be actuated
and will in turn activate the COMBOMAXMC
circulator relay. Connect the zone valve switch
to the T&T terminals on the COMBOMAXMC
electrical panel (DO NOT apply current to
these terminals). See figures 8.