THERMO 2000 BTH 8, BTH 12, BTH 10, BTH 18, BTH 15 Use & Care Manual

...
BTH Electric Boilers
Models ranging from 8 kW to 36 kW :
240 Volts ( 1 phase ) & 600 Volts ( 3 phases ).
USE & CARE MANUAL
WITH INSTALLATION INSTRUCTIONS FOR THE CONTRACTOR
It is imperative that all persons who are expected to install, operate or adjust this boiler should read these instructions carefully.
Any questions regarding the operation, maintenance, service or warranty of this electric boiler should be directed to the supplier.
When all installation steps have been completed, insert this installation manual in its original envelope, and keep in a safe place (close to the boiler) for future reference.
THERMO 2000 INCORPORATED revision:August/06
Printed in Canada
Ratings & Specifications
Electric Ratings for 240 VAC (1 phase) Electric Boilers:
Model
No.
BTH 8 5 000 3 000 ------ ------ 8 000 33.3 27 296 8 6 50 50 41.3
BTH 10 5 000 5 000 ------ ------ 10 000 41.6 34 120 6 6 60 60 52 BTH 12 3 000 3 000 3 000 3 000 12 000 50 40 944 6 4 70 70 62.5 BTH 15 3 000 4 500 3000 4 500 15 000 62.5 51 180 4 3 100 80 78.2 BTH 18 4 500 4 500 4500 4 500 18 000 75 61 416 3 2 100 100 93.8 BTH 20 5 000 5 000 5000 5 000 20 000 83.4 68 240 3 1 125 110 104 BTH 24 6 000 6 000 6000 6 000 24 000 100 81 888 1 0 125 125 125 BTH 27 3 x 4 500 3 x 4 500 27 000 112.5 92 124 1 0 150 150 140 BTH 30 3 x 5 000 3 x 5 000 30 000 125 102 360 2/0 3/0 200 175 156
BTH 33 3 x 5 000 3 x 6 000 33 000 138 112 596 2/0 3/0 200 200 172
Electric Elements
(in Watts)
A B C D Watts Amp. BTU CU AL Amp. Amp. Amp.
Total Wires Breakers Fuse
Electric Ratings for 600 VAC (3 phases) Electric Boilers:
Model
No. Quantity Watts Quantity Watts kW Amp. BTU RW-90 HRC “D”
BTH 9 3 3 000 ------- ------ 9 8.7 30 708 14 15 A BTH 13 3 4 500 ------- ------ 13.5 13 46 062 12 20 A BTH 18 6 3 000 ------- ------- 18 17 61 416 10 30 A BTH 22 3 3 000 3 4 500 22.5 22 76 770 10 30 A BTH 27 6 4 500 ------- ------- 27 26 92 124 8 40 A BTH 30 6 5 000 ------- ------- 30 29 102 360 8 40 A BTH 36 6 6 000 ------- ------- 36 35 122 832 8 50 A
Electric Elements Electric Elements Total Wires Fuse
Note: 1 kW =3,412Btu
Connections sizes & overall dimensions
125%
Connections sizes Boiler overall dimensions
Boiler return 1 “ NPT M Height 12 inches
Boiler feed 1 “ NPT M Width 12 inches Waterworks 1/2 “ NPT F Depth 34 inches Safety valve 3/4 “ NPT F Shipping weight 99 lbs.
Drain valve 1/2 “ NPT F Drain valve
(BTH 33,36)
3/4 “ NPT M
Operating temperature : from 50°F to 190°F. Maximum operating pressure: 30 p.s.i.
BTH Electric Boilers USE & CARE MANUAL (Revision August /06), Page 2.
Unit description:
Legend :
A. Boiler Water Supply Connection ( 1 inch diameter, NPT male) B. Boiler Water Return Connection ( 1 inch diameter, NPT male) C. Safety Relief Valve ( ¾ inch NPT female ) D. Temperature & Pressure Gage (1/2 inch NPT female ) E. Drain Valve (1/2 inch NPT female ) F. Fill Water Connection (1/2 inch NPT female ) G. Electric Line Knock-Out ( 1 inch ) H. Pilot Light I. Boiler Wall Hanging Brackets
J. Electrical Compartment
BTH Electric Boilers USE & CARE MANUAL (Revision August /06), Page 3.
General Safety Precautions
!
Be sure to read and understand the entire Use & Care Manual before attempting to install or to operate this water heater. Pay particular attention to the following General Safety Precautions. Failure to follow these warnings could cause property damage, bodily injury or death. Should you have any problems understanding the instructions in this manual, STOP, and get help from a qualified installer or technician.
Introduction
WARNING
!
These important safeguards and instruction appearing in this manual are not meant to cover all possible conditions and situations that may occur. It should be understood that common sense, caution and care are factors which cannot be built into every product. These factors must be supplied by the person(s) caring for and operating the unit.
LOCAL INSTALLATION REGULATIONS
This electric boiler must be installed in accordance with these instructions and in conformity with local codes, or in the absence of local codes, with the National Plumbing Code and the National Electric Code, current edition. In any case where instructions in this manual differ from local or national codes, the local or national codes take precedence.
SECURITY CONSIDERATIONS
Domestic and commercial installations have a maximum design operating pressure limited to 30 psi by a safety relief valve.
Boiler maximum operating temperature is 190°F by design. This boiler is designed to be used
only in a hot water heating system.
CAUTION
!
The heat transfer medium must be water or other non-toxic fluid having a toxicity rating or class of 1, as listed in clinical Toxicology of Commercial products, 5
th
edition
LOCATION
The electric boiler should be installed in a clean, dry location. Long hot water lines should be insulated to conserve water and energy. The electric boiler and water lines should be protected from exposure to freezing temperature.
The electric boiler must be installed horizontally directly on the wall. Use the hanging brackets for leveling the unit The electric boiler must be located or protected so as not to be subject to physical damage, for example, by moving vehicles, area flooding, etc. All models can be installed on combustible floors and in alcoves. Ambient temperature must not exceed 80°F.
CLEARANCE
For adequate inspection and servicing the following minimum clearance is necessary:
Right side 2 inches
Left side 14 inches
Top & Bottom of the boiler 6 inches
Front side of the boiler 24 inches
Back side of the boiler 1 inch
CAUTION
!
The electric boiler should not be located in an area where leakage of the tank or water connections will result in damage to the adjacent area or to lower floors of the structure. When such areas cannot be avoided, a suitable drain pan or non­flammable catch pan, adequately drained, and must be installed under the boiler. The pan must be connected to a drain. NOTE: Auxiliary catch pan MUST conform to local codes.
BTH Electric Boilers USE & CARE MANUAL (Revision August /06), Page 4.
CORROSIVE ATMOSPHERE
The electric boiler should not be located near an air vent blowing a corrosive atmosphere or high humidity. The limited warranty is void when the failure of the electric boiler is due to a corrosive atmosphere.
CHECK LIST
Please check the identification tag on the unit to make sure you have the right model.
List of components shipped with the unit :
Pressure relief valve set at 30 PSI.
Drain valve.
Tridicator (temperature & pressure
gage).
SHIPMENT INSPECTION
Inspect the electric boiler for possible shipping damage. The manufacturer’s responsibility ceases upon delivery of goods to the carrier in good condition. Consignee must file any claims for damage, shortage in shipments, or non­delivery immediately against carrier.
BTH Electric Boilers USE & CARE MANUAL (Revision August /06), Page 5.
Installation
The manufacturer’s warranty does not cover any damage or defect caused by installation, or attachment, or use of any special attachment other than those authorized by the manufacturer into, onto, or in conjunction with the water heater. The use of such unauthorized devices may shorten the life of the boiler may endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized devices
WIRING
Wiring must conform to the National Electrical Code and to state or local code requirements.
The electric boiler must be electrically grounded in accordance with local codes, or, in the absence of local codes, with the National Electrical Code.
240Vac models
Wiring must be from a 240 Volt (single phase, 60 Hz) circuit protected by a properly sized breaker. Wire gage (3 wires, ground) must be properly sized. Consult the boiler rating plate to select the proper breaker and wire gage.
600Vac models
Line wiring must be from a 600 Volt ( 3 phase, 60 Hz) circuit protected by a properly sized breaker. Wire gage (3 wires, ground) must be properly sized. Consult the boiler rating plate to select the proper breaker and wire gage.
Circulator zoning wiring
Components must be wired to ensure that only the circulator corresponding to the zone calling for heat is actuated.
Zone valve zoning wiring
Connect the low voltage thermostat to the zone valve. Components must be wired to ensure that only the zone valve corresponding to the zone calling for heat is actuated and that the circulator is powered on a demand from any zone. The transformer used to power the zone valves must be sized for the load represented by all zone valves in the heating system.
WARNING
!
BOILER WATER CONNECTIONS
This electric boiler may be connected individually or in parallel with other boilers. If two or more boilers are connected, the “reverse-return piping” method (whereby the boiler with the first return inlet also has the last supply outlet and so forth until the last return inlet corresponds to the first supply outlet) should be used to connect the boilers in parallel, to ensure an equal water flow rate through each boiler.
The boiler water supply, located on the top side, and the boiler water return, located on the bottom side of the boiler are steel pipes (male NPT threaded connection) where supply and return line connections are to be made.
Installing a union is recommended on the boiler water supply and return lines to facilitate boiler disconnection for servicing.
Dielectric unions are required for protection of the boiler and piping if dissimilar pipe material such as galvanized steel and copper are present.
Use only clean, new piping for boiler water lines. Local codes or regulations shall govern the exact type of material to be used.
Insulate all pipes containing hot water, especially in unheated areas.
Install shutoff (ball) valves for servicing convenience. Thermometer(s) should be installed on the boiler water supply and return lines.
Cap or plug unused connections on the boiler. Do not cap the pressure relief valve on the boiler since it will damage and shorten the life of the boiler and may endanger life and property.
Flow check valve
If the heating system includes a single pump, then to minimize flow by gravity and heat loss during non-draw periods, a flow check valve must
installed.
be
Pressure relief valve
An automatic pressure relief valve must be installed during boiler setup. The pressure rating of the relief valve must not exceed 30 psi. The safety relief valve must meet the requirements of
BTH Electric Boilers USE & CARE MANUAL (Revision August /06), Page 6.
the ASME Boiler and Pressure Vessel Code and limit the maximum operating boiler pressure. It is a safety device, not an operating control.
The BTU per hour rating of the relief valve must equal or exceed the BTU per hour input of the boiler(s) or heat source(s) as marked on the boiler(s) rating plate.
Connect the outlet of the relief valve to a discharge line with its lower tip at most 6” above a floor drain, well clear of any live electrical parts. The discharge line must pitch downward from the valve to allow complete draining by gravity of the relief valve and discharge line, and be of a diameter no smaller than that of the valve outlet. The tip of the discharge line should not be threaded or concealed and should be protected from freezing. No valve of any type, restriction or reducer coupling should be installed on the discharge line. Local codes shall govern the installation of relief valves.
SYSTEM PRESSURE CONTROL Expansion tank
Pressure control devices within the system ensure that each component operates within minimum and maximum allowable pressures and maintain minimum pressure for all normal operating temperatures. They also allow air bleeding, prevent cavitation at the pump inlet and prevent water from boiling within the system; all this is accomplished with minimal addition of new water.
The increase in boiler water volume resulting from higher temperature is stored in the expansion tank during periods of high operating temperature and is returned to the system when the temperature decreases.
The expansion tank must be able to store the required volume of boiler water during maximum design operating temperature without exceeding the maximum allowable operating pressure, and to maintain the required minimum pressure when the system is cold. Contact your installing contractor, plumbing supply house, or local plumbing inspector for assistance.
The point where the expansion tank is connected should be carefully selected to avoid the possibility that normal operation of automatic check or manual valves will isolate the tank from a hot boiler or any part of the system. Pre-charged diaphragm expansion tanks are preferable to air control.
These tanks incorporate a balloon-like bladder or diaphragm. It is inflated, prior to filling the system, to a pressure equal to the setting of the water pressure makeup regulator.
The expansion tank should be located on the suction or intake side of the pump. The pump can be located either just upstream or just downstream from the boiler.
BTH Electric Boilers USE & CARE MANUAL (Revision August /06), Page 7.
Water pressure makeup regulator
Make-up systems must be employed as required by codes. An automatic fill valve must be used with a backflow preventer as required, to maintain minimum system pressure by supplying water to make up for leakage.
Air bleeder
Oxygen should be excluded from the system to prevent corrosion. As mentioned in the expansion tank paragraph above, this precludes the use of air in direct contact with the boiler water as a pressurization means.
Installation of manual or automatic air vent devices prevents air from accumulating in the system. Air vents should be installed at all high points to remove trapped air during initial setup and to ensure that the system is tight. Regularly purge the air out of the system while taking care to avoid personal injuries or property damage caused by hot boiler water spray.
Circulator zoning recommendations
The preferred location of the circulator pump for each zone is on the boiler supply side, with the expansion tank between the boiler and the pump.
A flow check valve must be installed in each zone, preferably on the outlet side of each circulator pump, to prevent water flow to other zones where no heat is required.
Zone valve zoning recommendations
The preferred location of the circulator pump is on the boiler supply side, with the expansion tank between the boiler and the circulator. Use zone valves with low pressure drop.
Dual energy installation
In order to obtain a special rate from your electric utility for residential use, your BTH boiler can be hooked-up to an existing oil heater. Contact your electric utility to find out if your property is eligible for such rates and how to register for them.
The CBE-EM dual-energy control (an available option, three-way, motorized valve (1’’ NPT F standard) included) is specially designed to electric utility standards. The CBE-EM control selects the least expensive energy source based on outside temperature, user choice or a signal from your utility.
The CBE-EM dual-energy control will start up the oil burner upon receiving the appropriate signal, even if the thermostat in the house is not calling for heat. It will shut off when the temperature in the boiler reaches its target on the Limit Control. It is for this reason that the piping requires an anti­gravity valve (flow check valve) or motorized zone valves.
A three-way, motorized valve (1’’ NPT F standard) will direct the water flow either to the oil-fired heater or to your DTH electric boiler, depending on the signal received. This way, your oil heater will cool down and eliminate any energy loss, either through the chimney or by way of conduction in the boiler room.
BTH Electric Boilers USE & CARE MANUAL (Revision August /06), Page 8.
Loading...
+ 17 hidden pages