Thermix KPH 1800-LV, KPH 2100-LV Installation & User Manual

1
Installation & User Guide
Kitchen Plinth Heater models
KPH 1800-LV and KPH 2100-LV
Low Voltage Models
Introduction
This heater is intended to install behind the plinth in the space under the kitchen cupboards. However, it can be installed in similar kind of application.
This unit is made for two pipe pumped central heating systems. Flow and return and pipes should be connected as per drawing mentioned in page 2.This unit should not be installed in one pipe system. To allow enough airflow a minimum clearance 0f 20-25mm from the top of the unit to the any shelving. This unit must be installed of flat surface to avoid vibration.
Isolating valves (not supplied) should be fitted to both pipes (flow & return) to allow easy servicing. The flexible hose should be fitted to both pipe (flow & return) to allow easy servicing.
This unit operate with low voltage DC power supply hence suitable to be installed in bath room or high humid areas.
The following items should be in the carton:
DC power supply. Flexible connecting Hoses Fitted Grille Fixing screws (2)
In the event of any items missing or visibly damaged, please contact us on email.
2
Installation:
1. The heater should be installed by a qualified plumber. We recommend the use of a knee pad when installing this product. Cut the opening in the plinth to the size shown in the table. Use method A or B.
Model
Width
A
Height
B*
KPH 1800 LV & 2100 LV
462mm
97mm
* The overall height of the grille is 100mm. Use care when cutting the opening.
A
A
B
B
2. Fit isolating valves (not supplied) to the system flow and return pipes. Failure to fit isolating valves may mean that the product is not serviceable in the event of failure. Remove and discard the two protection bung in the copper pipes and connect the flexible hoses between system pipework and heater. Open the isolating valves and check for leaks.
3. Vent air through bleed screw if necessary.
Flate heat screw driver
Bleed Valve
I
O
II
4. Please use the supplied DC power
supply unit to operate the fans. Power supply should be located in right location to comply with electrical regulations (please consult your electrician)
Power supply has preset at 5 V
to keep the keep the fan noise lower.
If you prefer to run at higher
fan speed you can select 6V.
I O II
Fused Spur
Flow
Return