Thermia Atria Optimum, Diplomat, Comfort Optimum, Diplomat Duo Optimum, Diplomat Duo Optimum G2/G3 User Manual

User Guide
Atria Optimum Atria Duo Optimum Comfort Optimum Diplomat Diplomat Duo Diplomat Duo Optimum Diplomat Duo Optimum G2/G3 Diplomat Optimum Diplomat Optimum G2/G3
Domestic heat pumps
www.thermia.com
The English language is used for the original instructions. Other languages are a translation of the original instructions. (Directive 2006/42/EC)
© Copyright Thermia Värmepumpar
User Guide Domestic heat pumps

Table of Contents

1 Foreword ............................................... 4
2 Safety precautions ......................................... 5
3 About your heat pump ....................................... 7
4 Control system ........................................... 11
5 Settings and adjustments ..................................... 14
6 Regular checks ........................................... 18
7 Default setting in the controller ................................. 22
8 Checklist ............................................... 23
9 Installation carried out by: .................................... 24
Thermia Värmepumpar VUGFD202
3
User Guide Domestic heat pumps

1 Foreword

Buying a heat pump from Thermia is an investment in a better future.
A Thermia heat pump is classed as a renewable energy source, which means that it is considerate of our envi­ronment. It is a safe and convenient solution that provides heating, hot water and, in certain cases, cooling for your home at a low cost.
We thank you for the confidence that you have shown in us by buying a heat pump from Thermia . We hope that you will benefit from it for many, many years to come.
With best wishes
Thermia heat pumps
4
VUGFD202 Thermia Värmepumpar
N
User Guide Domestic heat pumps

2 Safety precautions

2.1 Important information

Caution The front of the heat pump must only be opened by qualified installers.
Caution This product is not intended for use by persons (including children) with re-
duced physical, sensory or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instructions concern­ing the use of the product by a person responsible for their safety.
Children are not permitted to play with the product.
The system can be considered maintenance-free but certain checks are necessary.
Contact your installer for any service work.

2.2 Installation and maintenance

Caution Only qualified installers may install, operate and carry out maintenance and
repair work on the heat pump.
Caution Only qualified electricians may modify the electrical installation.
Caution Only qualified refrigeration technicians may work on the refrigerant circuit.
Thermia Värmepumpar VUGFD202
5
User Guide Domestic heat pumps

2.3 System modifications

Only qualified installers may carry out modifications on the following components:
The heat pump unit
The pipes for the refrigerant, brine and water
The power supply
The safety valves
Do not carry out construction installations that may affect the operational safety of the heat pump.

2.4 Safety valves

Never block the connection to a safety valve’s overflow pipe.
The following safety precautions apply to the hot water circuit’s safety valve with corresponding over-
flow pipe: Water expands when it is heated, which means that a small amount of water is released from the system via the overflow pipe. The water that exits the overflow pipe can be hot! Therefore, allow it to flow to a floor drain to prevent any risk of burning yourself.
6
VUGFD202 Thermia Värmepumpar
3
4
5
1
2
User Guide Domestic heat pumps

3 About your heat pump

3.1 Heat pump components

The heat pump is a complete heat pump installation for heating and hot water. Certain models have an inte­grated water heater. Using the TWS (Tap Water Stratification) technology, more effective heat transfer and effi­cient layering of the water in the water tank is achieved.
The heat pump is equipped with control equipment, which is operated using a control panel.
Heat is distributed throughout the house via a water-borne heating system. The heat pump supplies as much of the heat demand as possible before auxiliary heating is engaged and assists.
The heat pump consists of five basic units:
1 Heat pump unit with compressor, heat exchanger, circulation
pumps for brine and heating systems, valves and safety equip­ment.
2
Water heater
3 Exchange valve or shunt valve that the heated water either
passes through to the heating system or to the water heater depending on whether heating or hot water is to be produced.
4 Auxiliary heater with an electrical heater installed on the heat-
ing system’s supply line.
5 Control equipment.

3.2 Outdoor and defroster function

Applies to Atria.
Atria are equipped with an outdoor unit that uses air as a heat source down to -20°C. The outdoor unit has a coil that uses brine to recover energy from the outside air. During normal operation the coil becomes cold as energy is lost through the exchange of heat. In humid air conditions it may build up a layer of ice. Atria has an automatic function to defrost the coil by reusing the heat energy produced. When required, a defrosting se­quence is triggered. The defrosting sequence is described as follows:
Thermia Värmepumpar VUGFD202
7
User Guide Domestic heat pumps
The defrosting sequence starts when the temperature of the brine reaches its set parameter for defrost-
ing. The compressor is stopped so that the defrosting sequence does not load the compressor unnecessari-
ly. But the compressor is not stopped when it produces hot water because the water heater is cooled during the defrosting sequence. The fan on the outdoor unit is stopped to reduce the duration of the defrosting sequence.
The shunt valve in the heat pump opens so that warm brine from the defrosting tank is mixed with the
cold brine circulating to the outdoor unit. The mixture has an approximate temperature of 15°C. The brine, heated to 15°C, melts the ice layer on the coil. At the same time, the brine liquid cools due to
heat exchange. When the brine is no longer cooled to temperatures below 11°C the coil is assumed to be sufficiently
defrosted. The shunt valve closes the flow of warm brine from the defrosting tank.
Operation returns to normal.

3.3 Speed (rpm) controlled circulation pumps

Applies to certain heat pump models only.
A heat pump requires optimum conditions in both the heating system and brine circuit in order to run as effi­ciently as possible. The temperature difference between the heating system’s supply line and return line must be between 7 and 10°C. For the brine circuit a temperature difference of 3°C between the input and output line applies. If the differences are larger or smaller than the quoted values, the heat pump will not work at 100% efficiency and savings may be reduced.
A heat pump with speed-controlled circulation pumps ensures that the required temperature differences are maintained. The control equipment detects if the balance is wrong and increases or decreases the speed of the circulation pumps as necessary.

3.4 HGW technology

Applies to certain heat pump models only.
HGW technology is a new and unique method of water heating.
During heating of the heating system water, a small proportion is diverted through an additional heat ex­changer and is used to heat the domestic water in the water tank. A shunt valve controls the flow between the hot water and the heating system.
8
VUGFD202 Thermia Värmepumpar
1
2
3
4
5
7
8
6
User Guide Domestic heat pumps

3.5 Water heater

Thermia heat pumps Diplomat and Comfort are supplied with an integrated 180 litre water heater. They are equipped with a TWS coil, which results in more effective heat transfer and more efficient layering of the water in the water heater.
1 Tap hot water
Top temperature sensor
2 3 Water heater 4 TWS coil 5 Start temperature sensor 6 Supply line to TWS coil 7 Return line from TWS coil 8 Cold water line
Hot water production is prioritised over heat production.
The temperature of the hot water cannot be adjusted. Hot water production does not stop at a preset water temperature; it stops when the compressor’s operating pressure switch reaches its maximum pressure. This corresponds to a hot water temperature of approximately 50–55°C in normal conditions.
To prevent the build up of bacteria in the water tank, the temperature of the water is increased at regular inter­vals using the integrated electrical heater (anti-legionella function). The factory-set time interval is seven days (can be adjusted). When the anti-legionella function is active, the heat pump produces hot water until the tem­perature for the start temperature sensor (5) has reached 60°C.
In the control system’s TEMPERATURE menu, the temperatures that are measured and calculated for the hot water and heating system supply line are displayed. The current temperature of the top temperature sensor (2) and the temperature of the supply line during heating and hot water production are displayed. The tempera­ture of the supply line often exceeds the maximum permitted hot water temperature, usually during hot water production.
The hot water tanks for Atria differ from the other heat pumps as the function for defrosting the outdoor unit is different.
Thermia Värmepumpar VUGFD202
9
Loading...
+ 19 hidden pages