PID Controllers
Models 2404/2408
Installation and
Operation handbook
ENG
Installation and Operation Handbook Contents
MODELS 2408 and 2404 PID CONTROLLERS
INSTALLATION AND OPERATION HANDBOOK
Contents Page
Chapter 1 INSTALLATION…………….…………………………… 1-1
Chapter 2 OPERATION…………………………………………….. 2-1
Chapter 3 ACCESS LEVELS………………………………………. 3-1
Chapter 4 TUNING…………………………………………………... 4-1
Chapter 5 PROGRAMMER OPERATION………………………… 5-1
Chapter 6 CONFIGURATION………………………………………. 6-1
Chapter 7 USER CALIBRATION…………………………………... 7-1
Appendix A UNDERSTANDING THE ORDERING CODE………... A-1
Appendix B SAFETY and EMC INFORMATION…………………... B-1
Appendix C TECHNICAL SPECIFICATION………………………… C-1
Appendix D LOAD CURRENT MONITORING AND
DIAGNOSTICS…………………………………………... D-1
Appendix E PROFIBUS COMMUNICATIONS…………………….. E-1
Appendix F RoHS……………………………………………………… F-1
“This product is covered by one or more of the following US Patents:
5,484,206; Additional patents pending.
PDS and INSTANT ACCURACY are trademarks of Eurotherm.”
HA025132 Issue 11 Oct-07 Applies to 2408 and 2404 controller software version 4. 0 i
Contents Installation and Operation Handbook
Issue 11 of this handbook applies to software version 4 and includes
RoHS statement.
Enhancements to Software Version 4
The following enhancements have been added to software versions 4.
• Isolated Single Logic Output Module
• Transducer Power Supply Module to provide 5 or 10Vdc to an external transducer. (Not
intended for melt pressure control)
• DeviceNet communications
• Linear over range limits are +5% of high instrument range and –5% of low instrument
range for all process input ranges (i.e. 0-20mA, 4-20mA, 0-10V)
• Sensor break or input open circuit faults are detected on all analogue inputs (PV1.PV2
and remote input channels)
• PV2 alarm, full scale high and low limits default to maximum and minimum display
limits
• Deviation alarms are not inverted when direct acting control is sel ected. Alarm
behaviour when using reverse acting control is unchanged
• The PD track valve positioning parameter (Pd.tr) has been removed
Controllers Affected:-
Standard controllers – which include
Version 4.11 or later
programmers with up to 4 programs
Setpoint programming controllers with up to
Version 4.61 or later
20 programs
Profibus controllers – which include
Version 4.32 or later
programmers with up to 4 programs
• The 10Amp output relay in module 4 is not available on controllers supplied after Jan 04
Related Information
• DeviceNet Communications Handbook part no. HA027506 which includes the
parameter address map.
• Profibus Communications Handbook part no. HA026290
• EMC (Electromagnetic Compatibility) Installation Guide, part no. HA025464
These are available on www. eurotherm.co.uk.
ii HA025132 Issue 11 Oct-07 Applies to 2408 and 2404 controller software version 4. 0