Thermasol PRO-84, PRO-750, PRO-395, PRO-240, PRO-140 User Manual

...
Installation Operation Manual thermasol.com/solutions
PRO-84, PRO-140, PRO-240, PRO-395, PRO-575, PRO-750, PRO-1000
OVER 60 YEARS OF STEAM SHOWER INNOVATION
PRO Series Generator
PRO Series Generator Installation Instructions
1 Important Information Before You Install
Make sure the walls, ceiling and oor materials are suitable for use with steam. If using acrylic walls, they must be steam rated from their manufacturer. ThermaSol only recommends specic generators for acrylic modules. Ensure electrical power is turned off for the duration of the installation.
PLEASE REVIEW WARNINGS BELOW AND LEAVE THIS MANUAL WITH HOMEOWNER
DO NOT USE THIS PRODUCT UNLESS YOU HAVE CONSULTED WITH YOUR DOCTOR AND RECEIVED WRITTEN PERMISSION TO DO SO. USE OF THIS PRODUCT MAY BE HAZARDOUS TO YOUR HEALTH.
PLEASE CONSULT YOUR PHYSICIAN BEFORE USING. IF YOU ARE PREGNANT, ELDERLY, HAVE HIGH BLOOD PRESSURE, DIABETES, SUFFER FROM HEART DISEASE, AND INTOXICATED, OR NOT IN GOOD HEALTH, DO NOT USE THIS STEAM BATH.
STEAM IS HOT! DO NOT TOUCH OR GO NEAR THE STEAMHEAD FROM THE TIME THE UNIT IS “ON”, UP TO ONE HOUR AFTER IT HAS SHUT OFF. SEVERE BURNS WILL OCCUR IF YOU COME IN CONTACT WITH THE STEAMHEAD OR STEAM EMITTING FROM THE STEAMHEAD.
NEVER ATTEMPT TO FILL AROMA RESERVOIR ON THE STEAMHEAD WHEN UNIT IS IN THE ON POSITION. SEVERE BURNS WILL OCCUR.
DO NOT USE THERMASOL AROMATHERAPY OILS OR SKIN CARE PRODUCTS OR ANY PRODUCT ASSOCIATED WITH YOUR THERMASOL UNIT WITHOUT CONSULTING WITH YOUR ALLERGIST OR DOCTOR BEFORE USE. THESE PRODUCTS MAY BE HAZARDOUS TO YOUR HEALTH.
DO NOT USE STEAM ROOM WHILE UNDER THE INFLUENCE OF ALCOHOL OR DRUGS, AS THIS CAN BE HAZARDOUS TO YOUR HEALTH.
YOUR SHOWER MAY BE A SLIP-AND-FALL HAZARD. CHECK WITH YOUR CONTRACTOR OR FLOORING MANUFACTURER REGARDING THE SAFE USE OF YOUR FLOORING IN A STEAM APPLICATION. SLIPPING AND FALLING INTO THE STEAMHEAD ITSELF OR INTO THE STREAM EMITTING FROM THE STEAMHEAD WILL CAUSE SERIOUS BURNS OR PHYSICAL INJURY.
IF YOU ARE FEELING UNCOMFORTABLE, DIZZY, FAINT, OR STARTING TO FALL ASLEEP IMMEDIATELY EXIT THE STEAM ROOM.
DO NOT USE STEAM ROOM IF YOU ARE UNDER THE AGE OF 16 UNLESS SUPERVISED BY AN ADULT.
THERMASOL STEAM BATH GENERATORS ARE NOT DESIGNED TO BE USED FOR SPACE HEATING PURPOSES.
THERMASOL STEAM BATH GENERATORS ARE FOR INDOOR USE ONLY. THEY SHOULD NEVER BE LOCATED OUTSIDE THE HOME.
All products must be installed in accordance with installation instructions provided. Failure to do so may invalidate warranty at manufacturer’s discretion. ©2016 ThermaSol.
2 Tools and Materials
Steam generator Installation instructions,
Materials needed:
qBrass ball valve 3/8" NPT or
brass shut-off valve (for water supply shut-off)
Pipe compound
q Copper or brass ttings & nipples
(sizes and quantities per instructions)
q Wire (see page 3) q Copper tube or pipe qWire cap nuts qFlex conduit
(for units 12kW and above)
3/8" Hose & Fitting
(Items 02-8239 & 04-1810)
Parts enclosed with the generator:
In-line water screen kit
warranty, static cling
warning label
qBrass or copper tee connection and plug qSilicone qOther materials as required
Materials recommended:
q In-line water lter (recommended) q PRO-750 and PRO-1000:
(2) 1/2" - 3/4” drop elbow/adapters
Tools needed:
qPipe wrench qTubing cutter
(comes pre-installed from the
factory) Item 04-8457
Steamhead Housing and
Cable Kit (10-8034-1)
qWire cutters or wire strippers qAdjustable wrench qScrewdriver (Phillips and regular) qSolder and ux q1-1/16" inch masonry drill bit q1-1/8" inch hole saw for ThermaSol
SteamVection steamhead rough-in
qDrill motor qPropane torch qOther tools as required
Read warnings on page 2. For illustrative purposes only. Consult with qualied professional for steam room construction details.
2
THERMASOL.COM I 800.776.0711
PRO Series Generator Installation Instructions
3 Sizing or Double Checking the Unit Specied
If you are installing the unit or thinking of adding one on your next project, you will need to make sure the unit is sized properly.
Calculate the shower area (Length x Width x Height = Cubic Feet)
The set of numbers in the generator model number represents the maximum capacity.
Example: Generator model PRO-240 will be sufcient up to 240 cubic feet (with a ceiling not exceeding 8 feet in height). Up-size 1 Unit size for every foot
over 8 foot to a maximum of 10 foot.
Model number can be found on the box or generator.
Installation note
We do not recommend a
ceiling height exceeding
10 feet.
Lowering ceiling
height to 8 feet helps
create a more efcient
steam room.
ThermaSol’s generators can be placed up to 50 feet from the shower; in an attic, closet or below a sink are ideal locations. Make sure the walls, ceiling and oor materials are suitable for use with steam.
q All the electrical wiring must be done per National/Local Electrical Codes.
4 Electrical Wiring
The size of the shower will determine the size of the generator. The size of the generator will determine electrical requirements.
qRun 240V Power source to the generator.
qUse copper wire only.
qWire sizes recommended by NEC (2002 Version). Minimum wire
temperature rating 90°C. Type THHN.
q Each generator should be wired to their own separate breaker
8'
4'
5'
qTurn off all electricity to the working area at the main breaker panel!
qLeave power OFF during installation process.
MODEL INPUT VOLTAGE KW RATING AMPS PHASE WIRE BREAKER ELECTRICAL MAX. ROOM SIZE
PRO-84 208-240VAC 6.0 28 1 10 30 NEMA 6-30P 84 CU.FT. PRO-140 208-240VAC 8.0 37 1 8 40 NEMA 6-50P 140 CU.FT. PRO-240 208-240VAC 10 46 1 8 50 NEMA 6-50P 240 CU.FT. PRO-395 208-240VAC 11 55 1 6 60 Hardwire 395 CU.FT. PRO-575 208-240VAC 15 69 1 4 90 Hardwire 575 CU.FT. PRO-750 208-240VAC 20 92 1 0 100 Hardwire 750 CU.FT. PRO-1000 208-240VAC 24 110 1 0 120 Hardwire 1000 CU.FT.
ThermaSol requires that a licensed electrician perform all electrical work.
Read warnings on page 2. For illustrative purposes only. Consult with qualied professional for steam room construction details.
THERMASOL.COM I 800.776.0711
3
PRO Series Generator Installation Instructions
5 Placing the Generator
Select a location as near as practical to the steam shower.
Typical locations include: closet, vanity cabinet, climate controlled attic or basement.
Be sure to install unit in a location that offers easy accessibility for servicing of generator. (Power Flush maintenance is recommended every 1000 minutes of use.)
DO NOT install generator inside steam room.
DO NOT install generator or plumbing lines in unheated
attic or any locations where water could freeze.
DO NOT install generator outdoors or wherever environmental conditions may affect the safety and/or performance of the generator.
Generator may be installed up to 50 feet away from steam shower and must be in a dry, non-combustible, well ventilated space with 6" clearance around generator.
When constructing the ceiling add slope of 1"/foot. The control cable provided with the generator is 50 feet in length (Item 03-6152-050).
When locating the control unit, place it as far as possible away from the steam head and as close as is practical to where the user will be sitting.
The generator must be upright, accessible and on a level surface with all connections on top. Access panel must be unobstructed and allow for easy access.
Example of different generator locations.
4
Read warnings on page 2. For illustrative purposes only. Consult with qualied professional for steam room construction details.
THERMASOL.COM I 800.776.0711
PRO Series Generator Installation Instructions
6 Water Supply and Drain Pan
Once you select the generator location, you will need to run water to the unit.
Use copper or brass ttings only!
DO NOT use galvanized ttings.
DO NOT use PEX or PVC tubing.
DO NOT plumb the pressure relief valve into the steam line.
Plumbing the pressure relief valve into the steam line can be hazardous, should the steam outlet be capped off or obstructed.
Recommend installing unions on all rigid pipe lines for ease of removal and serviceability (if required).
Use 3/8" NPT line to connect to supplied 3/8" braided hose.
A
B
The drain pan is required for installation.
Plumb the 3/4" drain connection on pan to an approved
C
drain. generator installations.
All plumbing shall be performed by a qualied licensed plumber and in accordance with applicable national and local codes.
Drain Pan must be installed on all
Connect a tee to the existing cold water line.
D
Install copper pipe from the tee to create inlet line for unit.
Install a brass shut off valve on the water inlet line
E
in an accessible area in front of the brass union (and recommended in-line water lter). A stainless steel water supply ex connector may be used.
Pre-Installed water line debris screen (included) in the
F
water inlet on the generator.
Before making the water connection, ush the water line
into a ve-gallon pail to remove any silt or other materials that may be in the water inlet line.
 Make nal connection but DO NOT turn the water
or power on yet.
Water Inlet Line
(3/8" NPT with brass
shut-off valve)
3/4" Drain Line
E
AD
Steam Line
F
B
C
Read warnings on page 2. For illustrative purposes only. Consult with qualied professional for steam room construction details.