Thermal Solutions SOLARIS Installation, Operating And Service Instructions

Page 1
INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
SOLARIS
Gas-Fired Boiler
Boiler Model Number SOL __ __ __ __ - __ __ __
Heating Contractor Phone Number
Address
814SOL0010-8/09
Boiler Serial Number 6 __ __ __ __ __ __ __
Installation Date
Price - $5.00
1
Page 2
IMPORTANT INFORMATION - READ CAREFULLY
NOTE: The equipment shall be installed in accordance with those installation regulations enforced in the area where the
installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or local regulations.
All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or local regulations.
The Commonwealth of Massachusetts requires this product to be installed by a licensed Plumber or Gas Fitter.
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial property dam-
Indicates a potentially hazardous situation which, if not avoided, may result in moder­ate or minor injury or property damage.
CAUTION
age.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death, serious injury or substantial property dam­age.
Indicates specic instructions on installa­tion, operation, or maintenance which are important but not related to personal injury hazards.
NOTICE
DANGER
DO NOT store or use gasoline or other ammable vapors or liquids in the vicinity of this or any
other appliance. If you smell gas vapors, DO NOT try to operate any appliance - DO NOT touch any electrical switch or use any phone in the building. Immediately, call the gas supplier from a remotely lo­cated phone, Follow the gas supplier’s instructions or if the supplier is unavailable, contact the
re department.
Manufacturer’s Contact Information: Thermal Solutions 1175 Manheim Pike Lancaster, PA 17601 717-239-7642 www.thermalsolutions.com
2
Page 3
WARNING
This boiler requires regular maintenance and service to operate safely. Follow the instructions
contained in this manual. Improper installation, adjustment, alteration, service or maintenance can cause property dam-
age, personal injury or loss of life. Read and understand the entire manual before attempting installation, start-up operation, or service. Installation and service must be performed only by an experienced, skilled, and knowledgeable installer or service agency.
This boiler must be properly vented. This boiler needs fresh air for safe operation and must be installed so there are provisions for
adequate combustion and ventilation air.
The interior of the venting system must be inspected and cleaned before the start of the heating season and should be inspected periodically throughout the heating season for any obstructions. A clean and unobstructed venting system is necessary to allow noxious fumes that could cause
injury or loss of life to vent safely and will contribute toward maintaining the boiler’s efciency.
Installation is not complete unless a pressure relief valve is installed into the tapping located on top of appliance. - See the Water Piping and Trim Section of this manual for details.
This boiler is supplied with safety devices which may cause the boiler to shut down and not re­start without service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the boiler is inoperative.
This boiler contains very hot water under high pressure. Do not unscrew any pipe ttings nor
attempt to disconnect any components of this boiler without positively assuring the water is cool
and has no pressure. Always wear protective clothing and equipment when installing, starting
up or servicing this boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the boiler. This boiler contains compo­nents which become very hot when the boiler is operating. Do not touch any components unless they are cool.
Boiler materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful sub­stances which can cause death or serious injury and which are known to the state of California to cause cancer, birth defects and other reproductive harm. Always use proper safety clothing,
respirators and equipment when servicing or working nearby the appliance.
Failure to follow all instructions in the proper order can cause personal injury or death. Read all instructions, including all those contained in component manufacturers manuals which are pro­vided with the boiler before installing, starting up, operating, maintaining or servicing.
Keep boiler area clear and free from combustible materials, gasoline and other ammable va­pors or liquids.
All cover plates, enclosures and guards must be in place at all times. This product must be installed by a licensed plumber or gas tter when installed within the Com-
monwealth of Massachusetts.
This boiler has a limited warranty, a copy of which is printed on the back of this manual. It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating properly when the installation is complete.
NOTICE
3
Page 4
Table of Contents
I. Pre-Installation ................................................. 6
II. Unpack Boiler ...................................................7
III. Venting/Air Intake Piping ................................ 8
A. Vent Guidelines Due to Removal of an
Existing Boiler .............................................8
B. General Guidelines ..................................... 9
C. Supplemental Vent Terminal Location
Instructions ................................................10
D. Separate Horizontal Venting
System ........................................................ 11
E. Optional Horizontal Vent Terminal
Mounting .................................................... 14
F. Conventional Venting........ ........................15
G. Air Intake Piping ......................................15
H. Separate Vertical Venting System ...........17
IV. Water Piping and Trim .................................. 20
V. Gas Piping .......................................................24
VI. Electrical .........................................................26
VII. Modular Installations ....................................29
VIII. System Start-up ...........................................39
IX. Service and Maintenance ............................... 46
A. Periodic Maintenance ..............................46
B. Safety & Operating Controls .................... 49
C. Trouble Shooting ........................................50
X. Sage Boiler ControlTM (SBCTM)......................52
A. Introduction ............................................... 52
B. Front Panel Display ...................................53
C. Setup Menu ................................................54
D.BoilerCongurationMenu ......................56
E. SystemCongurationMenu ....................57
F. Setpoints Menu ..........................................58
G. Communication Menu ..............................59
H. Manual Mode Menu .................................. 59
I. Security Menu............................................60
XI. Repair Parts ....................................................61
XII. Service Record .............................................. 71
XIII. Refractory Ceramic Fiber ..........................74
XIV. Warranty .......................................................75
Minimum Clearance to Combustible Materials
Left Side Right Side Front Rear Top Flue Connector
1” 1” 24” 3” 1” 6”
Recommended Clearance for Service
Model Left Side or Right
Front Rear Top
Side SOL-300 24” 24” 24” 16” SOL-750 24” 24” 24” 16” SOL-1000 24” 24” 24” 19” SOL-1250 24” 24” 24” 31” SOL-1500 24”
Note: Verify clearance with jurisdiction having authority and local codes.
4
Page 5
(Amps)
REAR VIEW
TOP VIEW
SIDE VIEW
L
(TYP.)
L
(TYP.)
C
2.71
E
D
B
K
A
13.00
H
M VENT
OUTLET
F OULET
WATER
F INLET
WATER
G INLET GAS
J
M VENT
INLET
Amp Draw
Rated Blower
(HP)
Rated Motor
Horse Power
Electrical Supply
(Voltz/Hertz/Phase)
Wet
(lbs.)
Weight
Dry
(lbs.)
Weight
Water
Volume
(Gallons)
BTU
(MBH)
Output
General Ratings and Capacities
(MBH)
BTU Input
Boiler
Model
SOL-300 300 252 1.1 288.5 297.7 3/4 8.5
SOL-500 500 420 1.3 316.0 326.8 3/4 8.5
SOL-750 750 637.5 2.4 508.5 528.5 120/60/1 3/4 8.0
SOL-1000 1000 850 2.6 548.5 570.2 3/4 8.0
SOL-1250 1250 1062.5 2.9 620.0 644.2 1-1/8 12
SOL-1500 1500 1275 3.3 713.0 740.5 1-1/8 12
Dimensions
‘A’ ‘B’ ‘C’ ‘D’ ‘E’ ‘F’ ‘G’ ‘H’ ‘J’ ‘K’ ‘L’ ‘M’
Boiler
Model
SOL-300 27.8 32.6 28.1 25.9 15.0 2.0 1.00 4.1 29.3 17.0 4.1 4.0
SOL-500 42.6 32.6 28.1 28.0 15.0 2.0 1.00 7.2 27.8 17.0 4.1 6.0
SOL-750 41.4 36.9 31.8 32.4 13.0 3.0 1.00 3.5 32.1 23.6 6.2 8.0
SOL-1000 49.4 36.9 31.8 32.4 13.0 3.0 1.25 3.5 32.1 21.6 6.2 8.0
SOL-1250 61.6 36.9 31.8 32.4 13.0 3.0 1.25 3.5 32.1 26.5 6.2 10.0
Figure 1: Dimensions
SOL-1500 73.9 36.9 31.8 32.4 13.0 3.0 1.50 3.5 32.1 25.6 6.2 10.0
5
Page 6
I. Pre-Installation
WARNING
If you do not follow these instructions ex-
actly, a re or explosion may result causing
property damage or personal injury.
DANGER
Do not install boiler where gasoline or other
ammable vapors or liquids, or sources
of hydrocarbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used or stored.
NOTICE
E. Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, condensate trap, control replacement, etc.).
F. Provide combustion and ventilation air in accordance
with sections 5.3 of the National Fuel Gas code, ANSIZ223.1/NFPA 54, or sections 7.2, 7.3, or 7.4 of CAN/CSA B149.1, Natural Gas and Propane Installa­tion code, or applicable provisions of the local building codes.
WARNING
Adequate combustion and ventilation air
must be provided to assure proper combus­tion.
Due to the low water content of the boiler, mis-sizing of the boiler with regard to the heating system load will result in excessive boiler cycling and accelerated component failure. Thermal Solutions DOES NOT warrant failures caused by mis-sized boiler applications. DO NOT oversize the boiler to the system. Modular boiler installations greatly reduce the likelihood of boiler over­sizing.
A. Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such requirements, installation must conform to the Na- tional Fuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/CGA B149 Installation Codes. Where required the installation must conform to the standard for con-
trols and safety devices for automatically red boilers,
ANSI/ASME CSD-1.
B. Appliance is design certied for installation on combus-
tible ooring. Do not install boiler on carpeting.
C. Provide clearance between boiler jacket and combus-
tible material in accordance with local re ordinance.
Refer to Figure 1 for minimum listed clearance from combustible material. Recommended service clearance is 24 inches from left side, right side and front. Rec­ommended service clearance is 36” at rear of unit. Ser­vice clearances may be reduced to minimum clearances to combustible materials.
The following guideline is based on the National Fuel Gas Code, NFPA 54/ANSI Z223.1.
1. Determine volume of space (boiler room). Rooms communicating directly with space (through open­ings not furnished with doors) are considered part of space.
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]
2. Determine Total Input of all appliances in space. Round result to nearest 1,000 Btu per hour (Btuh).
3. Determine type of space. Divide Volume by Total Input.
a. If result is greater than or equal to 50 ft³ per
1,000 Btuh, space is considered an unconned space.
b. If result is less than 50 ft³ per 1,000 Btuh, space
is considered a conned space.
4. Determine building type. A building of unusually tight construction has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed, and;
b. Weather-stripping has been added on openable
windows and doors, and;
c. Caulking or sealants applied in joints around
window and door frames, between sill plates and
oors, between wall-ceiling joints, between wall
panels, at plumbing and electrical penetrations, and at other openings.
D. Install on level oor. Floor must be able to support
weight of boiler, water and all additional system com­ponents.
6
Page 7
5. For boiler located in an unconned space in a
building of other than unusually tight construc­tion, adequate combustion and ventilation air
is normally provided by fresh air inltration
through cracks around windows and doors.
6. For boiler located within unconned space in
building of
within equate conned space, provide outdoor air through two permanent openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely commu­ nicating with the outdoors. Locate one opening within twelve (12) inches of top of space. Locate remaining opening within twelve (12) inches of bottom of space. Minimum dimension of air opening is three (3) inches. Size each opening per following:
a. Direct communication with outdoors. Minimum
free area of one (1) square inch per 4,000 Btu per hour input of all equipment in space.
b. Vertical ducts. Minimum free area of one (1)
square inch per 4,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
c. Horizontal ducts. Minimum free area of one (1)
square inch per 2,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
unusually tight construction, or
Alternate method for boiler located within
conned space. Use indoor air if two permanent
openings communicate directly with additional
space(s) of sufcient volume such that combined volume of all spaces meet criteria for unconned
space. Size each opening for minimum free area of one (1) square inch per 1,000 Btu per hour input of all equipment in spaces, but not less than 100 square inches.
7. Combustion Air/Ventilation Duct Louvers and Grilles. Equip outside openings with louvers to prevent entrance of rain and snow, and screens to prevent entrance of insects and rodents. Louvers and
grilles must be xed in open position or interlocked
with equipment to open automatically before burner operation. Screens must not be smaller than ¼ inch mesh.
Consider the blocking effect of louvers, grilles and
screens when calculating the opening size to provide the required free area. If free area of louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.
CAUTION
Avoid operating this boiler in an environment where saw dust, loose insulation bers, dry wall
dust, etc. are present. If boiler is operated under these conditions, the burner interior and ports must be cleaned and inspected daily to insure proper operation.
II. Unpack Boiler
CAUTION
Do not drop boiler. Do not bump boiler
jacket against the oor.
A. Move boiler to approximate installed position.
B. Remove all crate fasteners.
C. Lift and remove outside container. Save two of the
wooden slats from the container sleeve for use in Steps E and F.
D. Remove all boiler hold-down fasteners.
Installation of this boiler should be under­taken only by trained and skilled personnel
from a qualied service agency.
E. Tilt the boiler to its front side or back side and slide a
wooden slat under the raised feet.
F. Tilt the boiler in the opposite direction and slide another
wooden slat under the raised feet.
G. Slide the boiler left or right off the skid using the two
wooden slats as runners.
H. Move boiler to its permanent location.
WARNING
7
Page 8
III. Venting / Air Intake Piping
WARNING
Do not use this boiler with galvanized, non metallic or any other venting material that is not de-
signed for condensing ue gas applications.
Do not use a drafthood with this appliance. Do not use vent dampers with this boiler. Moisture and ice may form on surfaces around termination. To prevent deterioration, surfaces
should be in good repair (sealed, painted, etc.). This appliance needs fresh air for safe operation and must be installed so there are provisions
for adequate combustion and ventilation air.
Do not reduce size of air intake pipe. Read, understand and follow combustion air instruction restrictions contained in the Pre-Installa-
tion instructions of this manual.
Do not operate appliance where gasoline or other ammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used, stored and/or present in the air.
When installing vent pipe through chimney, no other appliance can be vented into the chimney. Do not exceed maximum vent/air intake lengths. Refer to Table 1.
A. Vent Guidelines Due to Removal of an Ex-
isting Boiler
For installations not involving the replacement of an
existing boiler, proceed to Step B.
When an existing boiler is removed from a common
venting system, the common venting system is likely to be too large for proper venting of the remaining appli­ances. At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remain­ing connected to the common venting system are not in operation:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, and
other deciencies which could cause an unsafe
condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range-hoods and bathroom exhausts, so they will operate at
8
maximum speed. Do not operate a summer exhaust
fan. Close replace dampers.
4. Place in operation the appliance being inspected. Follow the Lighting (or Operating) Instructions. Adjust thermostat so appliance will operate continuously.
5. Test for spillage at the draft hood relief opening
after ve (5) minutes of main burner operation. Use the ame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined
above, return doors, windows, exhaust fans, re
place dampers and any other gas burning appliance to their previous conditions of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or CAN/CSA B149.1 Natural Gas and Propane Installation Code. When resizing any portion of the common venting system, the common venting system should be resized to ap­proach the minimum size as determined using the appropriate tables in Part 11 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1 Natural Gas and Propane Installation Code.
Page 9
B. General Guidelines
1. Vent system installation must be in accordance with Part 7, Venting of Equipment of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Section 7, Venting Systems and Air Supply for Appliances of the CAN/CSA B149.1, Natural Gas and Propane In­stallation Code, or applicable provisions of the local building codes.
2. Contact local building or re ofcials about restric­tions and installation inspection in your area.
3. Refer to the appropriate drawings in this section of
this manual to determine the proper conguration of
venting system. Figures 2 thru 11. The vent system shall be installed in accordance with the instructions listed in this manual.
4. This appliance requires a Special Gas Vent. The product is designed to use AL 29-4C® Stainless Steel or other Stainless Steel material approved for
condensing ue gas applications. The boilers are
shipped with AL 29-4C® vent adapter to directly connect to Heat Fab Saf-T-Vent. The use of alter­nate manufacturer’s venting systems will require adapters and vent terminal. These adapters are not supplied with this unit and should be obtained from the supplier of alternate venting system.
5. The venting system must be installed so as to prevent accumulation of condensate. Horizontal vent pipe must maintain a minimum ¼ inch per foot slope down towards boiler.
a. Do not manifold condensate drains.
b. A common condensate pump/sump may be used.
Run separate condensate piping from each vent drain to the sump. A common drain may be used to discharge condensate from the sump.
Consult pump/sump manufacturer for compat-
ibility of materials of construction with ue gas
condensate. If a common pump/sump is used, individual vent drain lines must be connected such that one drain pipe cannot back feed into another vent drain.
c. Consult local authorities regarding disposal of
ue gas condensate into public waste water sys­tem. Some jurisdictions require that the conden­sate be buffered before discharge. this buffering is commonly achieved by draining the conden­sate through a limestone bed. Consult chemical treatment company for buffering systems.
6. Use noncombustible ¾ inch pipe strap to support horizontal runs and maintain vent location and slope while preventing sags in pipe. Do not restrict thermal expansion or movement of vent system.
Maximum support spacing is ve (5) feet. Do not
penetrate any part of the vent system with fasteners.
7. Vent length restrictions are based on equivalent length of vent/air pipe (total length of straight
pipe plus equivalent length of ttings). Maximum
vent/air lengths are listed in Table 1. Do not exceed
Table 1: Vent & Air Intake Length
Vent/Air Intake
Pipe Dia.Min Max
Boiler Model
SOL-300 5 50 4
SOL-500 5 78 6
SOL-750 5 50 8
SOL-1000 5 50 8
SOL-1250 5 50 10
SOL-1500 5 50 10
maximum vent/air intake lengths. Refer to vent manufacturer’s recommendations for the equivalent
length of ttings.
8. Provide and maintain vent pipe minimum clearances to combustible materials. Vent pipe minimum clear­ance to combustible material is four (4) inches when vent is installed in a fully enclosed (chase) applica­tion or three (3) inches when vent is installed with at least one side open, similar to a joist bay applica­tion. Use double wall thimble when penetrating a combustible wall. Some examples of Wall thimble manufactures are American Metal Products, Hart & Cooley, and Metal Fab.
9. Do not install venting system components on the ex-
terior of the building except as specically required
by these instructions. The vent termination location is restricted as follows:
a. The minimum distance from adjacent public
walkways, adjacent buildings, openable win dows and building openings shall not be less
than those values specied in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/ CSA B149.1, Natural Gas and Propane Installa tion Code.
b. Minimum twelve (12) inches above grade plus
normally expected snow accumulation level, or seven (7) feet above grade if located adjacent to public walkway. Do not install over public walk­way where local experience indicates appliance
ue gas vapor or condensate creates a nuisance
or hazard.
c. Minimum three (3) feet above any forced air
inlet located within ten (10) feet.
d. Power Vent - Minimum four (4) feet below, four
(4) feet horizontally from, or four (4) feet above any door, window, or gravity air inlet.
ft. ft. In.
9
Page 10
e. Minimum of four (4) feet horizontally from, and
in no case above or below, unless a 4 foot hori­zontal distance is maintained from electric me­ters, gas meters, regulators and relief equipment. This distance may be reduced if equipment is protected from damage due to condensation or vapor by enclosure, overhangs, etc.
f. Minimum twelve (12) inches from overhang or
corner of building.
g. The vent termination shall be located such that
no damage to building materials will occur from
Figure 2: Vent Therminal Location
NOTICE
Cut must be square with pipe and led or
sanded smooth before joining. Carefully ensure roundness of cut pipe by hand with gloves before installing. Seal joint with RTV
specied in this manual.
ue gasses degradation.
10. Enclose vent passing through occupied or unoccu pied spaces above the boiler with material having a
re resistance rating of at least equal to the rating of the adjoining oor or ceiling. Maintain minimum
clearances to combustible materials. See page 4.
11. Plan venting system to avoid possible contact with plumbing or electrical wires. Start at vent connector on top of boiler and work towards vent terminal.
12. Once a vent pipe manufacturer and system is cho­sen never mix and match vent systems.
13. Field Supplied Vent Terminations (One per boiler) a. Horizontal - Use Saf-T Vent mitered termination with screen or equivalent
b. Vertical - Use Saf-T Vent rain cap or equivalent
C. Supplemental Vent Terminal Location In-
structions (Massachusetts Code Only)
The Commonwealth of Massachusetts requires compli-
ance with regulation 248 CMR 4.00 and 5.00 for instal­lation of side-wall vented gas appliances as follows:
(a) For all side wall horizontally vented gas fueled equip-
ment installed in every dwelling, building or structure used in whole or in part for residential purposes, includ­ing those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above nished grade in the area of the
venting, including but not limited to decks and porches,
the following requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE DETEC­TORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing
plumber or gastter shall observe that a hard wired
carbon monoxide detector with an alarm and battery
back-up is installed on the oor level where the gas
equipment is to be installed. In addition, the install-
ing plumber or gastter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building, or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the ser­vices of qualied licensed professionals for the installa­tion of hard wired carbon monoxide detectors.
a. In the even that the side wall horizontally vented
gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next
adjacent oor level.
b. In the event that the requirements of this subdivision
can not be met at the time of completion of installa­tion, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, how­ever, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in ac­cordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certi-
ed.
3. SIGNAGE. A metal or plastic identication plate shall be
permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizon­tally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW,
KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection,
10
Page 11
the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt
from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equip­ment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS
EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufac­turer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the vent­ing system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS
EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not
provide the parts for venting the ue gasses, but identi­es “special venting systems”, the following require­ments shall be satised by the manufacturer:
1. The referenced “special venting system” instruc­tions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instruc­tions shall remain with the appliance or equipment at
the completion of the installation.
D. Separate Horizontal Venting System. See
Figures 3, 4 and 5.
1. Vent Piping
a. Do not exceed maximum vent/air intake
lengths. Refer to Table 1.
b. Recommended horizontal installation consists
of vent being sloped down ¼ inch per foot toward boiler.
c. Use appropriate designed thimbles when
passing through combustible walls (thimble use optional for noncombustible walls). Insert thimble through wall from outside. Secure
outside ange to wall with nails or screws, and
seal ID, OD and vent holes with sealant
material. Install inside ange to inside wall,
secure with nails or screws, and seal with sealant material.
d. For noncombustible wall application when thimble is not used, size opening such that bell with locking band attached cannot pass through. e. Join vent terminal to vent pipe. Locate vent pipe such that vent terminal is between six (6) inches and twenty-four (24) inches from wall when joined to inside vent piping. See Figure 3 or 4. f. Insert vent pipe through thimble/opening from outside and join to vent system. Apply seal­ ant between vent pipe and opening/thimble to provide weathertight seal.
2. Side Vent Installation. See gure 5.
a. Horizontal vent/air intake runs with no vertical rise in piping allowed. b. Do not exceed maximum vent/air intake lengths. Refer to Table 1. c. Recommended Horizontal Installation only consists of vent/air intake sloped down 1/4 inch per foot toward termination. d. Thimbles, same as “C” above in section D.1 e. same as “D” above in section D.1 f. same as “E” above in section D.1 g. same as “F” above in section D.1
Figure 3: Side Top Vent
11
Page 12
12
Figure 4: Recommended Separate Horizontal - Vent/Air Intake Installation
Page 13
Figure 5: Side Vent
13
Page 14
E. Optional Separate Horizontal Vent Terminal Mounting – See Figure 6
1. Do not exceed maximum vent/air intake lengths.
Refer to Table 1.
2. This installation will allow a maximum of ve (5)
feet vertical exterior run of the vent/air intake piping to be installed on separate horizontal venting and indoor air horizontal venting.
Note: Exterior run to be included in equivalent vent/
air intake lengths.
3. Install vent piping.
a. Install vent piping for desired venting system.
Refer to specic section for details for vent pipe
installation.
b. After penetrating wall/thimble, install a 90°
elbow so that elbow leg is in the up direction.
c. Install maximum of ve (5) feet of vent pipe.
Refer to Sections C through E for proper proce-
dures for joining vent pipe and ttings.
d. At top of vent pipe length install a 90° elbow so
that elbow leg is opposite the building’s exterior surface.
e. Install 45° elbow to upper 90° elbow so that leg
of 45° is in down direction (see Figure 6). If not using indoor air, proceed to Step f.
f. Install horizontal vent terminal.
g. Brace piping if required.
4. Air Intake Piping (not required for indoor air).
a. Install air intake piping for desired venting sys-
tem. Refer to specic section for details for air
intake installation.
b. After penetrating wall, install a corrosion re-
sistant 90o elbow so that elbow leg is in the up direction.
c. Install maximum of ve (5) feet of corrosion
resistant air intake pipe.
d. At top of air intake pipe install air intake termi
nal (provided with boiler).
e. Brace piping if required.
-
14
Figure 6: Optional Indoor Air – Vent Terminal Installation
Page 15
F. Conventional Venting (Negative Draft) – See Figure 7
a. The minimum chimney height is 15 feet.
b. The chimney must be protected from down
drafts, rain and debris by using a chimney cap or star.
c. Start installing vent at vent cap and continue
installation toward the boiler.
d. The ue connector and chimney ue diameter
may need to be increased or decreased depend ing on the dimensions of the boiler. Consult the National Fuel Gas Code or Local Codes for siz-
ing. Boiler input, ue connector lateral distance and chimney height affect the ue connector or chimney ue diameters.
e. A double acting barometric damper with integral
ue spillage interlock switch must be used when
the boiler is vented conventionally.
f. The chimney and ue connector must be sized
and congured to provide a minimum - 0.04 inch
w.c. draft at the vent outlet of the boiler.
g. Maintain a minimum vertical pitch of one (1)
inch in four (4) feet of vent connector run.
G. Air Intake Piping - See Figure 4 & 8
1. Locate air intake termination on the same wall as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler may be installed with verti­cal venting and sidewall combustion air inlet or vice versa, if installation conditions do not allow alternate arrangement.
2. Do not exceed maximum air intake length. See Table 1.
3. Use single wall metal pipe and ttings or thin wall PVC
available at most heating distributors.
4. Air intake termination must be located: Horizontal - At least twelve (12) inches above grade plus the expected snow accumulation.
5. Start at collar on burner enclosure (inside boiler jacket) and work towards the air intake terminal.
6. Maintain minimum of 1/4 inch per foot slope on horizontal runs. Slope towards air inlet terminal when possible. If not, slope towards boiler.
7. The air intake pipe must be adequately supported with
straps or supports no less than ve (5) feet apart on
horizontal runs. The complete air intake piping system must be rigid and able to withstand minor impacts with­out collapse.
8. Inlet air pipe penetration: Horizontal - Size wall pen­etration to allow easy insertion of air inlet piping. Seal around pipe with sealant to form weathertight exterior joint.
9. Seal all joints airtight, using silicone caulk or self-adhe­sive aluminum tape.
10. Install Air Intake Terminal.
Figure 7: Conventional Venting (Negative Draft)
15
Page 16
16
SEE TABLE 1.
Figure 8: Separate Horizontal – Vent/Air Intake Terminal Conguration
Page 17
H. Separate Vertical Venting System - See Figures 9, 10, and 11.
Vertical Venting
1. Do not exceed maximum vent lengths. Refer to Table 1.
2. Slope horizontal runs minimum ¼ inch per foot down towards boiler.
3. Install re stops where vent passes through oors, ceilings or framed walls. The re stop must close
the opening between the vent pipe and the structure. Fire stop manufacturers are Air-Jet, American Metal Products, Metal-Fab, and Simpson Dura-Vent.
4. Whenever possible, install vent straight through the roof. Refer to Figure 9 if offset is necessary. Main­tain minimum clearance to combustible materials.
5. Install Vent Terminal.
a. Size roof opening to maintain minimum clear-
ance from combustible materials.
b. Extend vent pipe to maintain minimum vertical
and horizontal distance of twelve (12) inches from roof surface. Allow additional vertical dis­tance for expected snow accumulation. Provide brace as required. Refer to Figure 11.
c. Vertical venting requires use of the roof ashing
and storm collar to prevent moisture from enter­ing the structure.
d. Install storm collar on vent pipe immediately
above ashing. Apply Dow Corning Silastic 732
RTV Sealant between vent pipe and storm collar to provide weathertight seal.
e. Attach vent terminal.
Vertical Air Intake Piping
1. Do not exceed maximum air intake length. Refer to Table 1.
2. Locate air intake termination on the same roof loca tion as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler may be installed with vertical venting and sidewall combus­tion air inlet or vica versa, if installation conditions do not allow alternate arrangement.
-
8. Inlet air pipe penetration:
9. Seal all joints airtight, using silicone caulk or self - adhesive aluminum tape.
10. Install Air Intake Terminal: Vertical - Insert intake piping into intake terminal collar. Secure terminal to intake piping and seal joint with silicone caulk.
with straps or supports no less than ve (5) feet
apart on horizontal runs. The complete air intake piping system must be rigid and able to withstand minor impacts without collapse.
Vertical - Size roof opening to allow easy insertion of inlet piping and allow proper installation of ash­ing and storm collar.
a. Use appropriately designed vent ashing when
passing through roofs. Follow ashing manufac-
turers’ instructions for installation procedures. Flashing manufacturers are Air-Jet, American Metal Products, Metal Fab, and Simpson Dura­Vent.
b. Extend air intake pipe to maintain minimum
vertical and horizontal distance of twelve (12) inches from roof surface. Allow additional verti­cal distance for expected snow accumulation. Provide brace as required. Refer to Figure 11.
c. Vertical air intake requires ashing and a storm
collar to prevent moisture from entering the structure.
d. Install storm collar on air intake pipe immediate-
ly above ashing. Apply Dow Corning Silastic
732 RTV Sealant between air intake pipe and storm collar to provide weathertight seal.
3 Use single wall metal pipe and ttings or thin wall
PVC available at most heating distributors.
4. Air intake termination must be located: Vertical - At least twelve (12) inches above the roof surface plus the expected snow accumulation.
5. Start at collar on burner enclosure (inside boiler jacket) and work towards the air intake terminal.
6. Maintain minimum of 1/4 inch per foot slope on horizontal runs. Slope down towards boiler.
7. The air intake pipe must be adequately supported
17
Page 18
18
Figure 9: Vertical Vent Installation
Page 19
Figure 10: Attic Offset
Figure 11: Indoor Air - Horizontal / Vertical Vent Terminal Installation
Extend Vent/Air Intake Piping to maintain minimum vertical (“X”) and minimum horizontal (“Y”) distance of twelve (12) inches from roof surface. Allow additional vertical (“X”) distance for expected snow accumulation.
19
Page 20
IV. Water Piping and Trim
CAUTION
iii. Oxygen permeable materials in the distribu-
tion system.
Failure to properly pipe boiler may result in improper operation and damage to boiler or structure.
1. Design and install boiler and system piping to prevent oxygen contamination of boiler water and frequent water additions.
CAUTION
Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, and can lead to boiler fail­ure. Thermal Solutions Standard Warranty does not cover problems caused by oxy­gen contamination of boiler water or scale
(lime) build-up cause by frequent addition of
water.
CAUTION
All piping either new or existing must be cleaned with a tri sodium phosphate (TSP) solution to remove mill scale and oils from the system. Failure to do so could result in premature failure of the heat exchanger (not covered by Thermal Solutions warranty.)
CAUTION
On an existing or retrot system, a lter or
strainer must be installed on the system return prior to the boilers.
b. In order to insure long product life, oxygen
sources must be eliminated. This can be accom­plished by taking the following measures:
i. Repairing system leaks to eliminate the need
for addition of make-up water.
ii. Eliminating and/or repairing ttings which
allow oxygen absorption.
iii. Using non-permeable materials in the distri-
bution system.
iv. Isolating the boiler from the system water by
installing a heat exchanger.
vi. Using properly designed and operating air
elimination devices in water piping.
2. Design and install system piping to prevent return water temperatures below 130°F. Refer to Table 2
for boiler ow and pressure drop requirements.
3. Connect system supply and return piping to boiler. Refer to Figure 12. Also consult I=B=R Installation
CAUTION
Return water temperature below 130°F
will cause ue gas condensation inside the
boiler. Flue gas condensate can lead to boiler failure. Thermal Solutions Standard Warranty does not cover problems caused
by ue gas condensation.
WARNING
CAUTION
When using Glycol products, all Glycol
manufacturers’ requirements, including
rust inhibitors, must be adhered. Max 50% Glycol.
a. There are many possible causes of oxygen con-
tamination such as:
i. Addition of excessive make-up water as a
result of system leaks.
ii. Absorption through open tanks and ttings.
20
Supply and return water temperature differ­ences greater than 40°F can lead to boiler failure. Thermal Solutions Standard War­ranty does not cover problems caused by temperature difference greater than 40°F.
and Piping Guides. Maintain ½” minimum distance between water piping and combustible material. Consult Thermal Solutions for unusual system requirements.
4. A pressure relief valve is supplied with each appli­ance. No valve is to be placed between the relief valve and appliance. No reducing coupling or other restriction shall be installed in the discharge line.
Page 21
See Figure 13.
compatible with local environmental regulations.
a. Pipe the safety relief discharge to a suitable place
for disposal when relief occurs.
b. Do not install reducing couplings for other
restrictive devices in the safety relief discharge line.
c. The safety relief discharge line must allow for
complete drainage of both the valve and line.
5. If the relief valve discharges periodically, this may be due to thermal expansion in a closed water supply system. Contact the water supplier or local plumbing inspector on how to correct this situation. DO NOT PLUG THE RELIEF VALVE.
6. Install the drain valve provided with the appliance at the lowest elevation. See Figure 13.
7. If this boiler is used in connection with refrigera­tion systems, the boiler must be installed so that the chilled medium is piped in parallel with the boiler using appropriate valves to prevent the chilled
medium from entering the boiler, see gure 13A.
Also consult I=B=R Installation and Piping Guides. If this boiler is connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation, the boiler piping must be equipped with ow control valves or other auto­matic means to prevent gravity circulation of boiler water during operation of the cooling system.
8. Install water ow switch. Water ow switch must be located such that water ow disruptions do not
affect switch operation. Maintain maximum practi-
cal straight piping before and after ow switch to
minimize water disruptions. Refer to manufactures’ instructions for proper paddle length.
9. A low water cutoff is required to protect a hot water boiler when any connected heat distributor (radia­tion) is installed below the top of the hot water
boiler (i.e. baseboard on the same oor level as the
boiler). In addition, some jurisdictions require the use of a LWCO with a hot water boiler. If a low water cutoff is required, it must be mounted in the system piping above the boiler. The minimum safe water level of a hot water boiler is just above the highest water containing cavity of the boiler; that is, a hot water boiler must be full of water to operate safely.
10. Oil, grease, and other foreign materials which accumulate in new hot water boilers and a new or reworked system should be boiled out, and then
thoroughly ushed. A local qualied water
treatment chemical specialist is a suggested source for recommendations regarding appropriate chemical compounds and concentrations which are
11. After the boiler and system have been cleaned and
ushed, and before relling the entire system add
appropriate water treatment chemicals, if necessary, to bring the pH between 8.8 and 9.2.
12. If it is required to perform a long term pressure
test of the hydronic system, the boiler should rst
be isolated to avoid a pressure loss due to the escape of air trapped in the boiler.
To perform a long term pressure test including the
boiler, ALL trapped air must rst be removed from
the boiler.
A loss of pressure during such a test, with no
visible water leakage, is an indication that the boiler contained trapped air.
WARNING
Failure to operate the unit with the proper
water ow rate can lead to appliance failure. Always install water ow switch so that the unit stops operating if improper water ow
is present. Safety relief valve discharge piping must
be piped such that the potential of severe burns is eliminated. DO NOT pipe in any area where freezing could occur. DO NOT install any shut-off valves, plugs or caps. Consult Local Codes for proper discharge piping arrangement.
Do not operate boiler with ow rates in excess of the maximum ow rates listed in
Table 2. Boiler tube erosion and pitting will occur. Thermal Solutions Standard War­ranty does not cover problems caused by
excessive water ow rates.
If a high head system pump is installed, as­sure that the boiler relief valve and system piping are capable of operating properly
at the combined pressure of the system ll
pressure plus the pump static head pres­sure.
21
Page 22
Table 2 - Solaris Boiler Flow and Pressure Drop
20° ΔT (max) 40° ΔT (min)
Boiler
Model
SOL-300 0.8 24 0.5 12 2
SOL-500 6.9 41 1.4 20 2
SOL-750 6.5 64 1.5 32 3
SOL-1000 16.1 85 3.7 43 3
SOL-1250 23.5 106 6.9 53 3
SOL-1500 29.1 128 10.6 64 3
Flow
(GPM) Δ P (ft)
Flow
(GPM)
Supply/Return
Pipe (in. dia.)Δ P (ft)
Figure 12: Water Piping (Single Boiler)
22
Page 23
Figure 13: Safety & Drain Valve Installation
Figure 13 A: Recommended Piping for Combination
Heating & Cooling (Refrigeration) System
23
Page 24
V. Gas Piping
WARNING
Failure to properly pipe gas supply to boiler may result in improper operation and dam­age to the boiler or structure. Always assure gas piping is absolutely leak free and of the proper size and type for the connected load. An additional gas pressure regulator may be needed. Consult gas supplier.
A. Size gas piping. Design system to provide adequate gas
supply to boiler. Consider these factors:
1. Allowable pressure drop from point of delivery to boiler. Maximum allowable system pressure is ½ psig. Actual point of delivery pressure may be less; contact gas supplier for additional information. The minimum and maximum gas valve inlet pressure is stamped on the rating label and can be found in table
3.
2. Maximum gas demand. Refer to the boiler’s input found in Figure 1 or as printed on it’s rating label. Also consider existing and expected future gas utilization equipment (i.e. water heater, cooking equipment).
3. Length of piping and number of ttings. Refer to
Table 5 for maximum capacity of Schedule 40 pipe. Table 6 lists equivalent pipe length for standard t­tings.
Table 3: Gas Ratings
Maximum
Boiler
Model
SOL-300 14 4.5 3.5
SOL-500 14 4.5 1.3
SOL-750 14 4.5 2.3
SOL-1000 14 4.5 1.9
SOL-1250 14 4.5 1.5
SOL-1500 14 4.5 1.3
Gas Pressure
(in. w.c.)
Minimum
Gas Pressure
(in. w.c.)
Manifold
Pressure
(in. w.c.)
4. Specic gravity of gas. Gas piping systems for gas with a specic gravity of 0.70 or less can be
sized directly from Table 5, unless authority having
jurisdiction species a gravity factor be applied. For specic gravity greater than 0.70, apply gravity factor from Table 4. If exact specic gravity is not
shown choose next higher value.
Table 4: Specic Gravity Correction Factors
Specic
Gravity
0.50 1.10 1.10 0.74
0.55 1.04 1.20 0.71
0.60 1.00 1.30 0.68
0.65 0.96 1.40 0.66
0.70 0.93 1.50 0.63
0.75 0.90 1.60 0.61
0.80 0.87 1.70 0.59
0.85 0.84 1.80 0.58
0.90 0.82 1.90 0.56
1.00 0.78 2.00 0.55
For materials or conditions other than those listed above, re-
fer to National Fuel Gas Code, NFPA54/ANSI Z223.1, or size system using standard engineering methods acceptable to authority having jurisdiction.
Correction
Factor
Specic
Gravity
Correction
Factor
B. Connect boiler gas valve to gas supply system.
1. Use methods and materials in accordance with local plumbing codes and requirements of gas supplier. In absence of such requirements, follow National Fuel Gas Code, NFPA 54/ANSI Z223.1.
2. Use thread (joint) compounds (pipe dope) resistant
to action of liqueed petroleum gas.
3. Install sediment trap, ground-joint union and manual shut-off valve upstream of boiler gas control valve and outside jacket. See Figure 14.
4. All above ground gas piping upstream from manual shut-off valve must be electrically continuous and bonded to a grounding electrode. Do not use gas piping as grounding electrode. Refer to National Electrical Code, NFPA 70.
USA boilers built for installation at altitudes greater than 2,000 feet above sea level have been
specically oriced to reduce gas input rate 4 percent per 1,000 feet above sea level per the
National Fuel Gas Code, NFPA 54/ANSI Z223.1.
24
C. Pressure test. The boiler and its gas connection must be
NOTICE
Page 25
Table 5: Maximum Capacity of Schedule 40 Pipe in CFH* for Gas Pressures of 0.5 psig or Less
MANUAL SHUT-OFF VALVE
GROUND-JOINT
UNION
TEE
CAP
3" MIN.
0.3 inch w.c. Pressure Drop 0.5 inch w.c. Pressure Drop
Length (Feet)
3/4 1 1-1/4 1-1/2 3/4 1 1-1/4 1-1/2
10 273 514 1060 1580 360 678 1390 2090
20 188 353 726 1090 247 466 957 1430
30 151 284 583 873 199 374 768 1150
40 129 243 499 747 170 320 657 985
50 114 215 442 662 151 284 583 873
60 104 195 400 600 137 257 528 791
70 95 179 368 552 126 237 486 728
80 89 167 343 514 117 220 452 677
90 83 157 322 482 110 207 424 635
100 79 148 304 455 104 195 400 600
* 1 CFH of Natural Gas is approximately equal to 1 MBH.
leak tested before placing boiler in operation.
1. Protect boiler gas control valve. For all testing over
DANGER
½ psig, boiler and its individual shutoff valve must be disconnected from gas supply piping. For test­ing at ½ psig or less, isolate boiler from gas supply
Do not use matches, candles, open ames
or other ignition source to check for leaks.
piping by closing boiler’s individual manual shutoff valve.
2. Locate leaks using approved combustible gas detec­tor, soap and water, or similar nonammable solu­tion.
WARNING
Failure to use proper thread compounds on all gas connectors may result in leaks of
ammable gas.
WARNING
Gas supply to boiler and system must be absolutely shut off prior to installing or ser­vicing boiler gas piping.
Table 6: Equivalent Lengths of Standard Pipe Fittings & Valves
VALVES FULLY OPEN
Figure 14: Recommended Gas Piping
Pipe Size I.D. Gate Globe Angle Swing 90° Elbow 45° Elbow 90° Tee, Flow 90° Tee, Flow
1/2” 0.622 0.35 18.6 9.3 4.3 1.6 0.78 1.0 3.1
3/4” 0.824 0.44 23.1 11.5 5.3 2.1 0.97 1.4 4.1
1” 1.049 0.56 29.4 14.7 6.8 2.6 1.23 1.8 5.3
1-1/4” 1.380 0.74 38.6 19.3 8.9 3.5 1.60 2.3 6.9
25
Page 26
VI. Electrical
DANGER
Positively assure all electrical connections are unpowered before attempting installation or ser­vice of electrical components or connections of the boiler or building. Lock out all electrical boxes with padlock once power is turned off.
WARNING
Failure to properly wire electrical connections to the boiler may result in serious physical harm. Electrical power may be from more than one source. Make sure all power is off before attempt-
ing any electrical work. Each boiler must be protected with a properly sized over-current device. Never jump out or make inoperative any safety or operating controls. The wiring diagrams contained in this manual are for reference purposes only. Each boiler is
shipped with a wiring diagram attached to the front door. Refer to this diagram and the wiring diagram of any controls used with the boiler. Read, understand and follow all wiring instructions supplied with the controls.
A. General. Install wiring and electrically ground boiler
in accordance with authority having jurisdiction or, in the absence of such requirements, follow the National Electrical Code, NFPA 70, and/or CSA C22.1 Electrical
Code.
B. A separate electrical circuit must be run from the main
electrical service with an over-current device/discon­nect in the circuit. A service switch is recommended and may be required by some local jurisdictions. Install the service switch in the line voltage “Hot” leg of the power supply. Locate the service switch such that the boiler can be shut-off without exposing personnel to danger in the event of an emergency. Connect the main power supply and ground to the three (3) boiler wires (black, white and green) located in the junction box at the back of the boiler jacket.
C. Refer to Figures 15 and 16 for details on the internal
boiler wiring.
D. When installed, the boiler must be electrically bonded
to ground in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the National Electric Code, ANSI/ NFPA70 and/or the Canadian Electrical Code Part 1, CSA C22.1, Electrical Code.
NOTICE
This boiler is equipped with a high water temperature limit located inside the internal wiring of the
boiler. This limit provides boiler shutdown in the event the boiler water temperature exceeds the
set point of the limit control. Certain Local Codes require an additional water temperature limit. In
addition, certain types of systems may operate at temperatures below the minimum set point of the limit contained in the boiler.
If this occurs, install an additional water temperature limit (Honeywell L4006 Aquastat) located in
the system piping as shown in the Water Piping and Trim Section of this manual. Wire as indi­cated in the Electrical Section of this manual.
26
Page 27
SAGE
CONTROLLER
Solaris
Ladder Diagram
LOW WATER
CUTOFF OPTION
(SEE NOTE 1)
WATER FLOW SWITCH
BURNER ON/OFF SWITCH
HIGH LIMIT AND OPERATING TEMPERATURE SWITCHES
HIGH AND LOW GAS PRESSURE SWITCHES
CNO
CNC
CC
CNO
MM 750-
MT-120
IGNITION PILOT
IGNITION XFMR
IGN
.
LEAD
2
1
P
GR
INTERMITTENT PILOT GAS VALVE
3
5
COMBUSTION AIR FLOW SWITCH
CNO
BLOCKED VENT
GN
RD
10
18
17
20
19
22
21
237
K1 K1
26
27
FUSE
G
2
10 28
8
9
11
12
13
14
16
15
7
8
9
11
10
3
2
5
SENSE
MAIN FUEL VALVE
6
SENSE
COMBUSTION AIR
FLOW
SENSE
HIGH LIMIT
SENSE
GAS PRESS SWITCHES
SENSE
WATER FLOW SWITCH
SENSE
BURNER ON/OFF
SWITCH
SENSE
LOW WATER CUTOFF
6
2
2
2
L1
L2
G
TO DISCONNECT (BY
OTHERS). GROUND
UNIT TO TECHNICAL
EARTH GROUND
120V-1PH-60HZ
43
31
32
34
35
33
36
K5
K5
29
37
38
K3
2
40
39
K4
41
4
4
5
3
K3
K5
K2
K3
SENSE
ALARM RELAY K2
K4
K6
51
52
1
2
1
4
1
5
0-10 VDC
TO
135 OHM
(+)
(-)
HONEYWELL Q7800H
FLAME SAFEGUARD SUBBASE
AND
PROGRAMMER CONTROL
RM7897A-1002
CALL FOR
HEAT
LC
CA
42
47
48
49
K2
2
3
3
2
3
50
2
0
30
K6
45
46
3
2
44
Flame
Rod
F
O+
O-
R+
R-
DP
LR
RO
SI
C
OUTSIDE AIR SENSOR
REMOTE SYSTEM SENSOR
OUTSIDE AIR
RESET OPTION
SYSTEM
TEMPERATURE
CONTROL OPTION
OUTLET
SENSOR
INLET
SENSOR
RJ45
MULTIPLE BOILER OUTSIDE AIR AND REMOTE SYSTEM TEMPERATURE SENSOR SHARING
C
SP
BP
VI
LO
SO
SYSTEM PUMP
COLD AIR DAMPER,
SYSTEM PUMP BACKUP
OR ALARM
BOILER PUMP
SPARE
LOCKOUT INDICATOR
CONTROL RELAY OPTIONS
MIXING VALVE
ACTUATOR
C-
C+
MR
MS
OR
1-9 VDC
24VAC +
24VAC -
2
12
7
5
4
6
8
9
1
11
10
3
K1
CS
AL
PR
C
LC
CH
FUSE
24VAC +
24VAC -
2
3
7
5
4
6
8
9
1
10
OO V
- V+
P-P
+
CA HL GP WF
Pin 6
Pin 1
Pin 7
Pin 1
BC
BO
BI
V+
V-
COMBUSTION BLOWER SPEED CONTROL CIRCUIT (0-10VDC)
COMBUSTION BLOWER
120 VAC CIRCUIT
GND TO
CHASSIS
GND TO
CHASSIS
2
1
3
GND TO
CHASSIS
2
1
3
GND TO
CHASSIS
MAIN GAS VALVE
115V TO 24V
TRANSFORMER
L2
L1
C
C
C
O+
O-
R+
R-
RJ11
SAGE CONTROLLER PEER-TO-PEER
COMMUNICATION
GND TO
CHASSIS
CNC
NC NC
LINE VOLTAGE ALARM
BLOWER MOTOR
AUXILIARY RELAY
AUXILIARY RELAY
MAIN FUEL VALVE(S)
20
HIGH LIMIT OPERATING LIMIT
HIGH LOW
GND TO CHASSIS
FACTORY WIRING, LINE VOLTAGE
LINE TYPES:
FIELD WIRING, LINE VOLTAGE
FACTORY WIRING, LOW VOLTAGE(SEE NOTE 3)
FACTORY WIRING, SPECIAL IGNITER
FIELD WIRING, LOW VOLTAGE
25
24
CS AL CH C PR
OO WF GP HL
THERMAL FUSE
(SEE NOTE 2)
BOILER
STATUS
12 VDC
0.5A MAX TOTAL FOR SO, SP, BP, V1, & LO
REMOTE ON/OFF
(ENABLE/DISABLE)
SPARE INPUT
DOMESTIC HOT WATER PRIORITY
LOCAL/REMOTE
(REMOVE JUMPER IF USED)
12 VDC
REMOTE CONTROL
REMOTE SETPOINT
OPTIONAL WIRING
CRA1
CRA2
CRA3
CRA4
CRA5
NOTES:
1. IF LOW WATER CUTOFF (LWCO) IS NOT USED, WIRE #P2 10/THERMAL FUSE MUST BE WIRED FROM TERMINAL TO THE THERMAL FUSE.
2. IF THE HIGH AND LOW GAS PRESSURE SWITCHES ARE NOT USED, A WIRE MUST BE INSTALLED BETWEEN TERMINAL AND .
3. FACTORY WIRING, LOW VOLTAGE IS 24VAC UNLESS OTHERWISE INDICATED.
10
16
17
GND TO
CHASSIS
Figure 15: Internal Boiler Wiring Ladder Diagram
27
Page 28
E. System Controls and Wiring
E1
W7W6W5W4W3W2W1
250V T5A
SIZE 3AG
W15
W14 W11
W10 W12
W13
W8
W9
K2
K6
K4K3
K5
K1
24V
COIL
CAUTION
HAZARD OF ELECTRIC SHOCK.
MORE THAN ONE DISCONNECT
SWITCH MAY BE REQUIRED TO
DE-ENERGIZE THE DEVICE
FOR SERVICING.
GND
L2 L1
120VAC POWER
SUPPLY
2
3 10
11 12
13
14
15 16
17
18 19 20
21 2
28
2272
2625
24
23
22
2923031323334353637383940414243444546
32323
3
4748492505152
P8
176
12
RJ11
RJ45
BC
BO
BI
CCC
SO
SP
BPVILO
MR
MS
C-
C+
LC
CH
O+
O+
O-
O-
R+
R+
R-
R-
DP
LR
RO
SI
C
C
CPRALCS
WF
P+P-V+V-OO
CA HL GP
HLPR
C
CHWF
GP
AL
CS
CA
LC
OO
G
L2
3456789
10
F
1213141516171819202122
3 5
SWITCH
ON/OFF
BURNER
NO
NC
C
CNO CNC
GAS PRESSURE SWITCH
LOW HIGH
MANUAL
SWITCH
AIR FLOW
COMBUSTION
TRANSFORMER
IGNITION
PILOT
INGITION
FLAME ROD
OR ALARM
SYSTEM PUMP BACKUP
COLD AIR DAMPER,
SYSTEM PUMP
BOILER PUMP
SPARE
LOCKOUT INDICATOR
AUXILIARY EQUIPMENT
AIR SENSOR
OUTSIDE
SYSTEM TEMPERATURE CONTROL OPTION
OUTSIDE AIR RESET OPTION
WATER PRIORITY
DOMESTIC HOT
(ENABLE/DISABLE)
REMOTE ON/OFF
SPARE INPUT
^WE
^WE
^BK
^BK
WE
BNBNBNBNBN
YW
BN
^BK
^WE
WE
BK
GN
WE
BK
WE
BK
YW
OE
OE
BN
WE
BN
WE
BN
WE
BE
YWYWYWYWYWYWYWYWYW
YW
NC C
NC C
RESET HIGH LIMIT
AUTO
TRANSFORMER
NEC
LOAD
R
C
YW
YW
YW
YW
YW
YW
YW
YW
YW
YW
YW
BE
YW
BE
YW
YW
BE
BE
YW
YW
YW
^WE
^BK
YW
YW
YW
YW
IGN LEAD
SWITCH OPTION
LOCAL REMOTE
(SEE NOTE 3)
BLOCKED
VENT
SWITCH
P1 P2
P3
P5
P4
P6
P7
104 GN
YW
OE
SWITCH
FLOW
WATER
LOW
F1
F2
125V T5A
SIZE 5MM X 20MM
CHASSIS
GND TO
GROUND
L2
L1
TO DISCONECT,
(BY OTHERS)
GROUND UNIT TO
TECHINCAL EARTH GND.
208/230/460V-3PH-60HZ
GN
WE
BK
CHASSIS
GND TO
OE
2
1
3
CHASSIS
GND TO
2
1
3
CHASSIS
GND TO
GAS VALVE
IGNITION PILOT
GAS VALVE
MAIN
WIRE COLORS:
BE = BLUE
BK = BLACK
BN = BROWN
GN = GREEN
OE = ORANGE
PK = PINK
RD = RED
VT = VIOLET
WT = WHITE
YW = YELLOW
RELAY/SWITCH TERMINALS:
C = COMMON
NC = NORM. CLOSED
NO = NORM. OPEN
WIRE TYPES:
(BLACK COLOR SHOWN, TYPICAL FOR ALL COLORS)
FACTORY WIRING, LINE VOLTAGE, 12 AWG, 105°C
FACTORY WIRING, LINE VOLTAGE, 18 AWG, 105°C
FACTORY WIRING, LOW VOLTAGE, 18 AWG, 105°C
FACTORY WIRING, LOW VOLTAGE, 18 AWG, SHIELDED
FACTORY WIRING, SPECIAL IGNITER, NOT IN HARNESS
OPTIONAL WIRING, LINE VOLTAGE, NOT IN HARNESS, 18AWG, 105°C
OPTIONAL WIRING, LOW VOLTAGE, NOT IN HARNESS
^BK
BK
BK
*BK
WE
BK
CHASSIS
GND TO
BLOWER
VARIABLE SPEED
PIN 6
PIN 1
PIN 7
PIN 1
BK
WE
(SEE NOTE 2)
(CRA1)
(CRA2)
(CRA3)
(CRA4)
(CRA5)
STANDARD FACTORY WIRING, LINE VOLTAGE, NOT IN HARNESS, 18AWG, 105°C
STANDARD FACTORY WIRING, LOW VOLTAGE, NOT IN HARNESS
STANDARD FACTORY WIRING, NOT IN HARNESS, 16AWG, 200°C
FUSE
^BK
^WE
NO
C
C
NC
THERMAL FUSE
(SEE NOTE 1)
(INSTALL IGNITION TERMINAL,
RAJAH MODEL AEBF)
(REMOVE)
(REMOVE)
(REMOVE)
(REMOVE)
(REMOVE)
(REMOVE JUMPERS 11, 12, & 15)
NOTES:
1. IF THE LOW WATER CUTOF F(LWCO) IS USED, DISCONNECT WIRE LABELED
P2 10/THERMAL FUSE FROM THE THERMAL FUSE AND CONNECT IT TO
LWCO TERMINAL 3. ALSO, CONNECT LWCO TERMINAL 5 TO THE THERMAL FUSE.
2. IF GAS PRESSURE SWITCHS ARE USED, INSTALL WIRING BETWEEN P16 AND
P17 TO INCLUDE THE PRESSURE SWITCH(S) AS SHOWN. IF NO GAS PRESSURE
SWITCH IS REQUIRED, INSTALL A JUMPER BETWEEN TERMINALS P16 AND
P17 AS SHOWN.
3. IF THE REMOTE ON/OFF FUNCTION IS DESIRED, REMOVE JUMPER WIRE BETWEEN
TERMINALS RO & C AND WIRE AS SHOWN. NOT TO BE DONE AT FACTORY.
THERMAL SOLUTIONS SAGE CONTROLLER (SBC)
PART NO. 801SOL0001
(BACK VIEW)
P12
LOW WATER
CUTOFF (LWCO)
OPTION
WE
GN
HONEYWELL
PROGRAMMER CONTROL
RM789A-1002
HONEYWELL Q7800H
PART NO. 101182-01
CHASSIS
GND TO
1. Refer to National Electric Code or Local Electric Codes for proper size and type of wire required. Follow Code.
2. Use anti-short bushings on all wiring passing through boiler jacket, junction boxes and/or control boxes.
3. Use armored cable (BX) over all exposed line voltage wiring.
28
Figure 16: Schematic Diagram
Page 29
VII. Modular Installation
A. General Guidelines
1. Read and follow all venting, combustion air, water piping, gas piping and electrical instructions con­tained in this manual unless otherwise instructed in this section.
2. Consult Local Building Codes or National Fuel Gas Code, NFPA 54/ANSI Z222.3 for restrictions and instructions on modular boiler installations.
3. Modular systems are complex. Design and installa­tion of modular systems should only be undertaken by skilled and knowledgable engineers and contrac­tors.
4. Use stainless steel vent material approved for con-
densing ue gass applications.
B. Module Sizing
Thermal Solutions recommends sizing each boiler in a
modular system to provide 20 % of the combined heat­ing load where ever possible. If the combined load ex-
ceeds the output of ve (5) boilers, install the minimum
number of boilers to meet the load requirements.
C. Venting
1. Horizontal/Vertical Venting a. Use Stainless Steel vent material approved for
condensing ue gas applications.
WARNING
CAUTION
Installing multiple vent terminations close together promotes frost buildup on build­ings. To minimize this possibility, extend the distance from the building to the end of the vent termination and increase the horizontal distance between terminations.
f. Refer to the cautions, notices, and warnings in
Section III.
2. Conventional Venting (Negative Draft)
a. Refer to Figure 17 for conventional venting
guideline for modular boilers.
b. Refer to National Fuel Gas Code to determine
required chimney diameter and common vent­ing diameter. Note that combined input, lateral length and chimney height affect vent diameter.
c. A single double acting barometric damper can
be utilized on the common venting when venting according to Figure 17.
d. Slope common venting a minimum of one (1)
inch in four feet of run towards boilers.
e. Locate boiler(s) with lowest input closest to
chimney.
f. Refer to cautions, notices, and warnding in Sec-
tion III.
Do not manifold vent components of a boiler without correcting to negative draft.
b. See Table 1 for the maximum vent length of each
size boiler.
c. Refer to Section III of this manual for guidelines
on venting of modular boilers individually. Each boiler requires an individual vent pipe.
d. The minimum horizontal distance between vent
terminations is one (1) foot. Additional horizon­tal distance is desirable to avoid frost damage to the building. Vent terminations must be at least twelve (12) inches above the ground plus the expected snow accumulation.
e. Multiple vertical vent pipes may be piped
through a common conduit or chase so that one roof penetration may be made. Each vent termi­nation must be one (1) foot from other termina­tions. A minimum of at least six (6) inches from the common conduit to combustible material must be maintained unless otherwise instructed by the conduit manufacturer.
D. Air Intake Piping
1. Locate air intake termination on the same wall as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler may be installed with vertical venting and sidewall combustion air inlet (or visa versa) if installation conditions do not allow alternate arrangement.
2. Refer to Figures 18 and 19 for common air intake guidelines for modular water heaters.
3. Individual air intake pipes may be used in lieu of common air intake piping. If so desired, refer to Figures 4 and 8.
4. Refer to Table 1 for the maximum air intake length.
Common air intake straight lengths and ttings
should be assumed to have the equivalent length the same as an individual air intake pipe used for a given boiler intake pipe diameter.
5. Position horizontal air intake termination center line below horizontal vent termination’s center line.
6. Vertical air intake pipe must terminate at least two (2) feet above teh closest portion of the roof.
7. Refer to the cautions, notices, and warnings in the Combustion Air Section of this manual.
29
Page 30
E. Water Piping
1. Refer to Figures 20 through 25 for typical water pip ing installation details for modular boilers.
2. Installing a low water cutoff in the system is highly recomended and may be required by code.
3. Refer to Table 2 for pressure drop and ow require­ments for each boiler.
4. Refer to the instructions, cautions, notices, and warnings in Section IV.
F. Gas Piping
1. Refer to National Fuel Gas Code, Local Codes and Tables 5 and 6 for gas pipe sizing.
2. Each boiler must be piped as shown in Figure 14.
3. Refer to the instructions, catuions, notices, and
warnings in Section V.
G. Electrical
WARNING
If gas pressure in the building is above 1/2 psig, an additional gas pressure regulator is
required. Using one additional regulator for
multiple boilers may result in unsafe boiler operation. The additional regulator must be able to properly regulate gas pressure at the input of the smallest boiler. If the regula­tor cannot do this, two or more additional
regulators are required. Consult regulator
manufacturer and/or local gas supplier for
instructions and equipment ratings.
-
1. Each boiler must be provided with a fused discon nect and service switch.
2. Install wiring in accordance with requirements of authority having jurisdiction. In the absence of such requirements, follow the National Electric Code, NFPA 70 and/or CSA C22.1 Electric Code.
3. Refer to Figure 2 for electrical data for each boiler size.
4. Refer to the instructions, cautions, notices, and warnings found in Section VI.
30
-
Page 31
Figure 17: Modular Boiler Conventional Venting
Figure 18: Modular Boiler Horizontal Air Intake Piping
31
Page 32
LISTED IN TABLE 1.
Figure 19: Modular Boiler Vertical Air Intake Piping
32
Page 33
Figure 20: Modular System: Typical One Pipe Water Piping
33
Page 34
34
Figure 21: Modular System: Typical Primary/Secondary Water Piping
Page 35
Figure 22: Modular System: Typical Primary/Secondary without System Pump
35
Page 36
36
Figure 23: Modular System: Typical Reverse - Return Water Piping
Page 37
Figure 24: Modular System Reverse - Return with System Pump Only
37
Page 38
38
Figure 25: Modular System: Typ Primary/Secondary with Reverse-Return
Page 39
VIII. System Start-up
A. Safe operation and other performance criteria were met
with gas manifold and control assembly provided on
boiler when boiler underwent tests specied in Ameri­can National Standard for Gas-Fired Low-Pressure
Steam and Hot Water Boilers, ANSI Z21.13.
B. Verify that the venting, water piping, gas piping and
electrical system are installed properly. Refer to instal­lation instructions contained in this manual.
C. Conrm all electrical, water and gas supplies are turned
off at the source and that vent is clear of obstructions.
D. Conrm that all manual shut-off gas valves between the
boiler and gas source are closed.
WARNING
Completely read, understand and follow all instructions in this manual before attempt­ing start up.
E. FILL ENTIRE HEATING SYSTEM WITH WATER
and vent air from system. Use the following procedure on a Series Loop or multi-zoned system installed to
remove air from the system while lling.
WARNING
3. Attach a hose to the vertical hose bib located prior to the full port ball valve in the system supply piping.
(Note - Terminate hose in ve gallon bucket at a suitable oor drain or outdoor area).
4. Starting with one circuit at a time, open zone valve or shut-off valve in system supply and return piping.
5. Open hose bib.
6. Open ll valve (Make-up water line should be locat­ed directly after full port ball valve in system supply piping between air scoop and expansion tank).
7. Allow water to overow from bucket until discharge
from hose is bubble free for 30 seconds.
8. Close the opened zone valve or shut-off valve for the zone being purged of air, then open the zone valve or shut-off valve for the next zone to be purged. Repeat this step until all zones have been purged. At completion, open all zone valves or shut-off valves.
9. Close hose bib, continue lling the system until the
pressure gauge indicates required system operating
pressure. Close ll valve.
(Note - If make-up water line is equipped with
pressure reducing valve, system will automatically
ll to set pressure. Follow ll valve manufacturer’s
instructions).
10. Open isolation valve in boiler supply piping.
The maximum operating pressure of this boiler is 150 psig. Never exceed this pres­sure. Do not plug or change pressure relief valve.
NOTICE
If it is required to perform a long term pres­sure test of the hydronic system, the boiler
should rst be isolated to avoid a pressure
loss due to the escape of air trapped in the boiler. To perform a long term pressure test includ-
ing the boiler, ALL trapped air must rst be
removed from the boiler. A loss of pressure during such a test, with no viable water leakage, is an indication that the boiler contained trapped air.
1. Close full port ball valve in boiler supply piping.
2. Isolate all zones by closing zone valves or shut-off valves in supply and return of each zone(s).
11. Remove hose from hose bib.
F. Conrm that the water ow switch is operating prop-
erly.
G. Turn on the electrical supply to the boiler and circula-
tion system at the fused disconnect.
H. Conrm that water ow switch is operating properly.
I. Prepare to check operation.
1. Obtain the gas heating value (in Btu per cubic feet) from the gas supplier.
2. Connect a monometer to the pressure taping upstream V1 on the main gas valve. Use the G 1/8
test nipple provided. Reference item 7 on gure 28.
3. Temporarily turn off all other gas-red appliances.
4. Turn on gas supply to the boiler gas piping.
5. Purge the gas line of air.
6. Reset the low gas pressure switch.
7. Conrm that the supply pressure to the gas valve is
14 in. w.c. or less. Refer to Table 3 for the minimum supply pressure.
39
Page 40
DANGER
Do not use matches, candles, open ames
or other ignition source to check for leaks.
8. Open the eld installed manual gas shut-off valve
located upstream of the gas valve on the boiler.
9. Check that boiler gas piping, valves, and all other components are leak free using a soap solution or a similar non-combustible solution, electronic leak detector or other approved method. Eliminate any leaks.
J. Follow the operating instructions to place the boiler
into operation. Reference Figure 27.
K. Sequence of operation. See Figure 29. If boiler fails to
operate properly, see Trouble shooting Guide in Section IX.
L. Select Desired Operating Mode. Refer to the Sage
Boiler Control ™ (SBC ™) instructional manual sup­plied with the boiler.
M. Set operating limits. Refer to the (SBC ™) instructional
manual supplied with the boiler.
Figure 26: Pilot Burner/Main Burner Flame
N. Check Ignition control module shut-off.
1. Rotate the manual gas shut-off valves clockwise from “ON” to “OFF” position.
2. Turn on the boiler-operating switch located on the left side of the unit.
3. Allow boiler to complete prepurge and pilot trial for
ignition (PTIF) sequence. Conrm that the ame control locks out on pilot ame failure.
4. Rotate the manual shut off valve for the pilot to al-
low gas ow to the pilot valve.
5. Allow the boiler to complete the pre-purge, PTIF,
and main trial for ignition (MTFI). Conrm that the ame control locks out on main ame failure.
6. Rotate the manual shut off valves for the main gas
valve to allow gas ow to the main gas valve. Con­rm that the ame control locks out on main ame
failure.
7. Disconnect the pilot lead wires from the pilot gas valve. If the burners do not shutdown, determine the cause of the malfunction. Replace necessary items and check operation.
40
Page 41
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING:
A.
This appliance is equipped with an ignition device, which automatically lights the pilot. Do not try to light the pilot by hand.
B.
BEFORE OPERATING smell all around the appliance area
forgas.Besuretosmellnexttotheoorbecausesomegasis heavierthanairandwillsettleontheoor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
Ifyoudonotfollowtheseinstructionsexactly,areorexplosionmayresult
causing property damage, personal injury, or loss of life.
OPERATING INSTRUCTIONS
1.
STOP! Read the safety information above on this label.
2.
Set the thermostat to lowest setting.
3.
Turn off all electric power to the appliance.
4.
This appliance is equipped with an ignition device, which automatically lights the pilot. Do not try to light the pilot by hand.
Inlet Gas
5.
Remove front door.
•Ifyoucannotreachyourgassupplier,calltheredepart­ment.
C.
Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand,
don’ttrytorepairit,callaqualiedservicetechnician. Forceorattemptedrepairmayresultinareorexplosion.
D.
Do not use this appliance if any part has been under water.
Immediatelycallaqualiedservicetechniciantoinspectthe
appliance and to replace any part of the control system and any gas control which has been under water.
7.
Rotate gas shutoff valves clockwise from “ON” position to “OFF”. Make sure handle rests against stop.
8.
Waitve(5)minutestoclearoutanygas.Thensmellfor gas,includingneartheoor.Ifyousmellgas,STOP!Follow
“B” in the safety information above on this label. If you do not smell gas, go to the next step.
9.
Rotate gas shutoff valves counterclockwise from “OFF” to “ON”. Make sure handle rest against stop. Do not force.
6.
Locate the gas pilot & main shutoff valves at the end of the gas supply pipe inside the boiler.
Gas Shut Off Valves
TO TURN OFF GAS TO APPLIANCE
1.
Set the thermostat to lowest setting.
2.
Turn off all electric power to the appliance if service is to be performed.
3.
Remove front door.
Figure 27: Operating Instructions
10.
Replace front door.
11.
Turn on all electric power to the appliance.
12.
Set thermostat to desired setting.
13.
If the appliance will not operate, follow the instructions “TO TURN OFF GAS TO APPLIANCE” and call your service technician or gas supplier.
4.
Rotate gas shutoff valves clockwise from “ON” position to “OFF”. Make sure handle rests against stop.
5.
Replace front door.
814SOL0001
41
Page 42
1 Electrical connection for valves (DIN EN 175 301-803) 10 Setting screw Ratio V
2 Input ange 11 Vent nozzle G 1/8
3 Pressure connection G 1/8 upstream of lter 12 G 1/8 pressure connection Burner pressure p
4 Filter 13 Output ange
Test point connection G 1/8 upstream of V1, possible
5 Type plate 14
both sides
6 Cover 15 G 1/8 pressure connection blower pressure p
Test point connection G 1/8 upstream of V1, possible
7
on both sides 16 G 1/8 pressure connection for pF furnace pressure
Test point connection G 1/8 downstream of V2
8
possible on both sides 17 Optional: Pulse line pBr
9 Setting screw Zero point adjustment N * G 1/8: 1/8” Iso Parallel Threads
Figure 28: Main Gas Valve
Br
L
42
Page 43
Figure 29: Sequence of Operation
43
Page 44
O.Checkthepilotandmainburnerames.Allow the
boiler to complete pre-purge, PTIF, and MTFI. Look through the boiler sight glass and check the pilot and
main burner ames. Reference Figure 26 for ame ap­pearance. The ames should have a clearly dened in-
ner cone with no yellow tipping. Orange-yellow streaks should not be confused with true yellow tipping. If the
ames do not meet the criteria in gure 26, adjust the
gas valve settings as described in step R.
WARNING
c. Use the N setting (Item 9 on Figure 28) on the
main gas valve to adjust the gas manifold pres-
sure at low re. Turn the screw setting clockwise
to increase counterclockwise to decrease the manifold pressure.
3. Clock the gas meter for at least 30 seconds. Use
table 7 to determine the gas ow rate in cubic feet
per hour.
4. Determine the input rate. Multiply the gas ow rate
by the gas heating value.
Failure to properly adjust gas input rate will result in over ring or under ring of the ap­pliance. Improper and unsafe boiler opera­tion may result.
P. Check low water cut-off (if so equipped).
1. Adjust setpoint to highest setting.
2. With boiler operating, open the drain valve and slowly drain the boiler.
3. Main burners and pilot burner will extinguish and blower will stop when the water level drops below the low water cutoff probe. Verify limit, thermostat or other controls have not shut off the boiler.
4. Adjust the setpoint to the desired value and rell
the boiler.
Q. Verify that all safety and operating limits are operat-
ing properly. These controls and limits include differ-
ential air switch, water temperature operating control, manual reset water temperature safety limit, and the high and low gas pressure switches (if provided). Refer to the individual manuals, provided with the boiler, for these components to obtain proper start-up and operat­ing instructions. Follow all instructions contained in these manuals. Refer to section IX to view a description of the safety and operating controls.
R. Adjust the gas input rate to the boiler.
1. Administer a call for heat and allow the boiler to operate.
2. Check the manifold pressure at high re and low re. See table 3 or the rating label located in the
boiler’s vestibule compartment.
a. Connect manometer to pressure tapping
downstream V1 on main gas valve. See item 8 on Figure 28.
b. Use the V setting (Item 10 on Figure 28) on
the main gas valve to adjust the gas manifold
pressure at high re. Turn the screw setting
clockwise to increase and counterclockwise to decrease the manifold pressure.
WARNING
Failure to properly adjust gas input will
result in over ring or under ring of the
appliance. Improper and unsafe operation may result.
5. Compare the measured input rate to the input rate stated on the rating plate.
a. The boiler must not be over red. Reduce the
input rate by decreasing the manifold pressure as described in step R. Do not reduce more than 0.3
inch w.c. If the boiler is still over red, contact
your Thermal Solutions representative.
b. If the measured value is less than 98% of the
rating plate input, increase the input rate by increasing the manifold gas pressure described in step R. Do not increase the manifold pressure more than 0.3 inch w.c. Contact your Thermal Solutions representative if the measured rate is still less than 98% of the rated input.
WARNING
Failure to properly adjust excess air will result in unsafe levels of carbon monoxide. Variations in venting or combustion air pres­sure and temperature will change excess air. Adjust excess air levels so that variation in venting or combustion air pressures and temperatures caused by change of sea­sons, wind conditions, opening or closing of boiler room doors or windows do not cause the boiler to operate with carbon monoxide concentrations above 400 parts per million.
6. Measure the percent oxygen (%O2), the carbon
monoxide concentrations in the ue gas (CO ppm), and the ue gas temperature. Compare the results
44
Page 45
with the values given on the factory re test report
supplied with the boiler.
7. Return gas red appliances to previous conditions of
use.
S. Review user’s information manual and system Op-
eration with owner or operator.
Table 7: Gas Flow Rate in Cubic Feet Per Hour
Size of Gas Meter Dial
Seconds
for One
30 60 120 240
32 56 113 225
34 53 106 212
36 50 100 200
38 47 95 189
40 45 90 180
42 43 86 172
44 41 82 164
46 39 78 157
48 37 75 150
50 36 72 144
52 35 69 138
54 33 67 133
56 32 64 129
58 31 62 124
60 30 60 120
One-Half
Cu. Ft.
One
Cu. Ft. Two Cu. Ft.
45
Page 46
IX. Service and Maintenance
DANGER
This boiler uses ammable gas, high voltage electricity, moving parts, and very hot water under
high pressure. Assure that all gas and electric power supplies are off and that the water tempera­ture is cool before attempting any disassembly or service.
Do not attempt any service work if gas is present in the air in the vicinity of the boiler. Never modify, remove or tamper with any control device.
WARNING
This boiler must only be serviced and repaired by skilled and experienced service technicians. If any controls are replaced, they must be replaced with identical models. Read, understand and follow all the instructions and warnings contained in all the sections of this
manual. If any electrical wires are disconnected during service, clearly label the wires and assure that the
wires are reconnected properly. Never jump out or bypass any safety or operating control or component of this boiler. Read, understand and follow all the instructions and warnings contained in ALL of the compo-
nent instruction manuals. Assure that all safety and operating controls and components are operating properly before plac-
ing the boiler back in service.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
ATTENTION
Au moment de l’entretien des commandes, étiqueteztous les ls avant de les débrancher. Des erreurs de câblage peuvent entraîner un fonetionnement inadéquat et dangereux.
S’assurer que l’appariel fonctionne adéquatement une fois l’entretien terminé.
A. Periodic Maintenance. Inspection and service should
be conducted periodically. Turn off electrical power and gas supply while conducting service or maintenance. Follow instructions TO TURN OFF GAS TO APPLI­ANCE. See Figure 27.
1. General
a. Keep the area around the boiler free from com-
bustible materials, gasoline and other ammable
vapors and liquids.
b. Keep the area around the combustion air inlet
terminal free from contaminates.
c. Keep the boiler room ventilation openings open
and unobstructed.
2. Low water cutoff (if so equipped).
a. Probe Type (Annual Service). Probe type
LWCO should be removed once a year, exam­ined and cleaned of any dirt accumulations to as­sure proper operations. Do not attempt to repair
mechanisms in the eld. Complete replacement
mechanisms, including necessary gaskets and installation instructions, are available from the manufacturer.
3. Vent/Air Intake System. Inspect for obstructions,
soot accumulation, proper support, deterioration of
46
Page 47
pipe, ttings, and joints.
a. Clean terminal screens. Terminals must be free
of obstruction, undamaged, with screens securely in place.
b. Inspect and clean the air lter as needed. The
lter can be cleaned using water. See Figure 39,
Item 11, for location.
c. Terminal Wall thimbles (if used) must be weath-
ertight.
d. Pipe must be full round shape, and show no dam-
age from impact or excessive temperature.
e. Ensure that there is nothing obstructing the ow
of combustion air and/or ue gas.
f. Inspect and clean piping with soft bristle brush
and vacuum to remove any lint, soot, or other dirt.
g. Replace immediately if any signs of deterioration
or corrosion are present.
h. Pipe must be supported at minimum ve (5) foot
intervals and must not sag.
i. All vent joints must be secure and watertight.
j. All air intake joints must be secure and airtight.
k. Horizontal vent tee drain or vertical vent tee
drain (if used) must have minimum 6 inch trap
and allow condensate to ow freely. To Clean:
i. Disconnect drain tube from drain tting.
ii. Flush drain tube with water. Fill trap with
water.
iii. Securely fasten drain tube to drain tting,
providing gas-tight and watertight seal.
1/2 inch of sensing probe. If ame is yellow and
lazy, follow instructions TO TURN OFF GAS TO APPLIANCE (see Figure 27), and contact
qualied agency.
e. Check main burner ames. See Figure 26. Flame
should have clearly dened inner cone with no
yellow tipping. Orange-yellow streaks caused by dust should not be confused with true yellow
tipping. If yellow ames are observed, follow
instructions TO TURN OFF GAS TO APPLI-
ANCE (see Figure 27), and contact qualied
service agency.
6. Combustion Chamber/Burners . Inspect for
blockage or soot accumulation (annually).
a. Remove Main Burners. See Figure 30.
1. Remove front door.
2. Remove air box cover.
3. Disconnect ignition wire, sensor wire, ground wire and gas valve wiring.
4. Disconnect manifold unions at pilot valve and main gas inlet on right side of air box.
5. Remove attachment screws holding air box to front of combustion chamber.
6. Remove burner/fuel train assembly from combustion chamber.
7. Inspect and clean burners with soft bristle brush and vacuum to remove any dirt and lint.
l. If pipe must be disassembled for removal of
obstructions or resealing of joint, see Section III, Paragraph B.
4. Inspect Condensate Drain Trap and Drain Line (Monthly)
a. Inspect condensate trap water level. If low, add
water to bring level to trap discharge.
b. Ensure condensate can ow freely to drain.
5. Inspect Pilot and Main Burner Flames
(Monthly).
a. Remove jacket front panel.
b. View ames through Flame Observation Port.
c. Adjust thermostat to highest setting.
d. Check pilot ame. See Figure 26. The pilot pro-
duces three (3) ames. The center ame should
be steady, medium hard blue enveloping 3/8 to
8. If burners show signs of deterioration or cor­rosion, replace immediately.
9. Check gas orices for dirt and lint. Clean as
necessary.
10. Inspect heat exchanger and combustion chamber. Clean heat exchanger with straight handle wire brush and vacuum heat exchanger and combustion chamber.
1. Exercise care during vacuuming to avoid damaging base insulation.
11. Inspect combustion chamber/burner assem­bly gaskets and replace if required.
12. Install burner/fuel train assembly and secure with original fasteners.
13. Connect manifold unions, ignition wire, sen-
47
Page 48
sor wire, ground wire and gas valve wiring.
WIRE BRUSH
SOFT BRISTLE BRUSH
14. Install air box cover and attachment hard­ware.
15. Install front door.
6. Check Operation . Follow steps from Section VIII for system start-up.
Figure 30: Cleaning Boiler Flue Passages
48
Page 49
B. Safety and Operating Controls. Operation and Shut Down
Component Function
Circuit Board Fuse
Power Switch
Operating Aquastat
Manual Reset High
Limit Aquastat
Flow Switch
Pressure (Safety) Relief Valve
Mixer Fuseable Link
If the power draw of the control circuit exceeds approximately 5 amps, the circuit board fuse trips and prevents the boiler from operating until the fuse is replaced.
If this switch is in the off position, power is interrupted to the control circuit of the boiler, which prevents the boiler from operating. If the switch is in the on position, power is sup­plied to the control circuit.
If the boiler water temperature exceeds the adjustable set point, power is interrupted to the control circuit of the boiler, which prevents the boiler from operating. When the boiler wa­ter temperature drops below the set point minus the adjustable differential setting, power is again supplied to the control circuit.
If the boiler water temperature exceeds the adjustable set point, power is interrupted to the control circuit of the boiler, which prevents the boiler from operating. Power is interrupted until the control is manually reset by pressing the control’s reset button. When the button is depressed, power will again be supplied to the control circuit.
If the water ow through the boiler drops below the xed ow rate required to move the
control’s paddle enough to close the controls contacts, power is interrupted to the control
circuit, which prevents the boiler from operating. When the water ow rate is increased,
the paddle closes the control’s contacts and power is supplied to the control circuit.
If the pressure inside the appliance exceeds the xed set point, the valve opens mechani­cally and discharges water. The valve remains open until the pressure inside the appliance drops below the set point.
If the temperature in the interior of the burner exceeds the xed set point. The contacts of
the switch open and power is interrupted to the control circuit, which prevents the boiler from operating. Power is interrupted until the switch is replaced.
Vestibule Fuseable Link
High and Low Gas Pressure Switches
Combustion Air Flow Switch
Flame Safeguard Control
Variable Frequency
Drive (VFD)
Thermal Solutions Sage Boiler Control™ (SBC)™
If the temperature in the interior of the vestibule enclosure exceeds the xed set point, the
contacts of the switch open and power is interrupted to the control circuit, which prevents the boiler from operating. Power is interrupted until the switch is replaced.
If the gas pressure reaches a point below the adjustable set point, or above the adjustable set point, the contacts of the switch open and power is interrupted to the control circuit, which prevents the boiler from operating. Power is interrupted until gas pressure is be­tween the high and low set points and the control is manually reset by moving the switch to the reset position. The switches will not reset until the gas pressure is within the set point parameters.
If the differential air pressure drops below the xed set point, the contacts of the switch
open and power is interrupted to the control circuit, which prevents the boiler from operat-
ing. Power is interrupted until air ow increases so that the contacts close.
Refer to the manual supplied with the boiler.
The variable frequency drive’s primary function is to vary the rotational speed of the blower fan based on the air requirements of the boiler combustion process. The VFD on Modulat-
ing boilers responds to a 0-10 VDC or 4-20 ma signal from the Digital Temperature Control­ler.
The Thermal Solutions Sage Boiler Control™ (SBC™) is a complete boiler and automa­tion system. It provides advanced boiler modulation control, operating control, diagnostics, multiple boiler lead lag and auxiliary device control. Refer to the SBC manual shipped with the boiler to learn more about these features and functions.
49
Page 50
C. Trouble Shooting Guide
Alarm Messages are shown one at a time in priority order. The message closes to the top of this list is displayed rst. Following
messages are not show until the higher priority message has cleared. All alarm messages are also stored in the fault history.
LCD Display Alarm Message
Low Water Level
Off Switch Turn Burner Switch On
Low Water Flow
Fuel Limit
High Temp Limit
Low Air Flow
FSG Fault
Outlet Temp Fail
Inlet Temp Fail
OA Temp Fail
Remote Temp Fail
Recommended Action
Manually Reset the Low
Water Cutoff
Ensure Boiler Pump is
Running and Boiler
Water Flow is Unobstructed
Manually Reset the Fuel
Pressure Switch
Manually Reset the
High Temperature
Aquastat
Check Combustion Air
Blower and Air
Pressure Switch
Settings and Wiring
Manually Reset
Required, Refer to
Flame Safeguard
Manual
Corrective Actions
Check Wiring and
Sensor
Check Wiring and
Sensor
Check Wiring and
Sensor
Check Wiring and
Sensor
Explanation
Low Water Cutoff Switch
When this option is congured and an instrument is installed, the manual reset
low water safety relay is preventing the boiler from starting. If terminal (LC) does not receive power and the Call For Heat output (CH) is powered the “Low Water Level” Message is displayed.
Burner Switch is Off
Control switch is in the OFF position and is preventing the boiler from starting. If terminal (OO) does not receive power and the Call For Heat output (CH) is pow­ered the “OFF Switch” Message is displayed.
Low Water Flow Switch
Low water ow is preventing the boiler from starting. If terminal (WF) does not
receive power and the Call For Heat output (CH) is powered the “Low Water Flow” Message is displayed.
Low or High Gas Pressure Switch
The low or high gas pressure switch is preventing the boiler from starting. If terminal (GP) does not receive power and the Call For Heat output (CH) is powered the “Fuel Limit” Message is displayed.
High Limit Temperature
The high temperature limit (HL) (and operational temperature limit when
provided) aquastat is preventing a boiler start. If terminal (HL) does not receive
power and the Call For Heat output (CH) is powered the “High Temp Limit” Message is displayed.
Low Air Flow or Blocked Vent Switch Not Made
The air ow (and blocked vent switch when provided) is preventing a boiler start.
If terminal (CA) does not receive power and the Call For Heat output (CH) is powered the “Low Air Flow” Message is displayed.
Flame Safeguard Fault
The Flame Safeguard is preventing a boiler start. If terminal (AL) receives power at any time, the “Flame Failure” Message is displayed.
Boiler Outlet Temperature Sensor Fail
The boiler outlet temperature sensor is not connected or is reading above or below a valid range. When the boiler outlet sensor fails and the Outlet Sensor mode was selected the control will transfer to Lost Sensor Blind Mode.
Boiler Inlet Temperature Sensor Fail
The boiler inlet temperature sensor is not connected or is reading above or below a valid range. When the boiler inlet sensor fails the mixing valve output will drive to 0% and low temperature alarm and maximum water differential (boiler outlet minus boiler inlet) temperature hold are disabled.
Outside Air Temperature Sensor Fail
The outside air sensor is congured and is not connected or is reading above or
below a valid range. When the outside air sensor fails the warm weather shut­down (WWSD) and outside air reset control logics are disabled.
Remote System Temperature Sensor Fail
The remote system temperature sensor is congured and is not connected or is
reading above or below a valid range. If Remote System Temperature Sensor mode was selected the control will transfer to Boiler Outlet Sensor Mode.
50
Page 51
Trouble Shooting Guide (continued)
LCD Display Alarm Message
Remote Input Fail
Comm Failure
Recommended Action
Check Wiring and
Remote System
Check Wiring and
Remote System
Conrm each boiler has
a unique address
Explanation
Remote Control Input Fail
The Remote Control Input is congured and is not connected or is above or be­low a valid range. When the remote control input fails the following control mode changes are taken automatically:
Selected Modes Resulting Control Mode Remote Mod Outlet Sensor and Local Setpoint Remote Mod & Remote Sensor Remote Sensor and Local Setpoint Remote SP Outlet Sensor and Local Setpoint Remote SP & Remote Sensor Remote Sensor and Local Setpoint
Communication Failure
The Modbus or Peer-To-Peer network has failed. When the Modbus network fails the following control mode changes are taken automatically:
Selected Modes Resulting Control Mode Modbus Mod Outlet Sensor and Local Setpoint Modbus Mod & Remote Sensor Remote Sensor and Local Setpoint Modbus SP Outlet Sensor and Local Setpoint Modbus SP & Remote Sensor Remote Sensor and Local Setpoint After a Modus communication failure, the ‘Comm Failure’ alarm is not cleared until communication is restored and successfully writes to both the Remote On / Off Modbus Command (00004) and Remote Firing Rate or Remote Setpoint (40006) points have been completed, power is cycled or the protocol parameter is changed to Peer-To-Peer and then back to Modbus.
Low Inlet Temp
Memory Failure
Check wiring and
sensor
Check return water
temperature. Consider
system or operational
changes to avoid low
temperature events
Call Factory Reset
all memories in
System menu:
Clr BIT History
Clr Alarm Hist
Clr Run Time Cnt
Clr Cycle Cnt
Factory Defaults
(Factory Level
Password is required)
When a Peer-To-Peer network has failed the boilers begin operation as stand alone boilers using the selected parameters.
After a Peer-To-Peer communication failure the ‘Comm Failure’ alarm is not cleared until communication is restored and the boiler rejoins a network with at least one other boiler, power is cycled or the protocol parameter is changed to Modbus and then back to Peer-To-Peer.
Low Boiler Inlet Temperature If the boiler inlet temperature is below the low boiler inlet temperature setpoint, the “Low Inlet Temp” Message is displayed and the boiler inlet temperature history is stored. See following page for additional information on low boiler inlet temperature history storage and retrieval.
Memory Failure
New software has been installed in the SBC™ or a power interruption has caused a memory failure. The Call For Heat will be prevented until the condition is cleared.
51
Page 52
X. Sage Boiler ControlTM (SBCTM)
A. INTRODUCTION: The intent of this section is to briey
summarize the controllers capabilities, familiarize the user with its basic features and to list factory supplied default settings. Read the additionally supplied Factory Instruction Manual for the SBC to learn more about the controllers features and capabilities.
1. Sage Boiler Control Overview The Sage Boiler Control (SBC) is a complete boiler monitoring and automation system. The SBC pro­vides advanced boiler modulation, operating control, diagnostics, multiple boiler lead-lag and auxiliary device control. The SBC provides advanced control features in an easy to use package.
Flexible, Field Selectable Control.
2. Control modules, water system, boiler auxiliary and modulating lead/lag control features are menu se­lectable without the need for external programmers, laptops or downloads. Every boiler is shipped with factory defaults that make eld menu selections un­necessary unless you are applying additional control features.
3.
Boiler Monitoring and Diagnostic Displays The SBC’s two line by sixteen character LCD display may be used for monitoring boiler inlet and outlet, remote system and outside air temperatures, modulation rate setpoint and modulating percent and mixing valve demand percent. Additionally, the dis­play automatically presents boiler sequence messag­es, alarms, hold and lockout messages. A diagnostic menu is included that provides the last 10 alarm messages and boiler inlet temperature alarm history. Boiler inlet temperature alarm history includes time and date, the lowest inlet temperature reached and the amount of time the water temperature dropped below the alarm setpoint.
Modulation Rate and On/Off Modes
4. The SBC may simply control boiler modulation and on/off output based on the boiler water out­let temperature and an operator adjusted setpoint. However, using parameter selections, the SBC allows the boiler modulation and on/off output to respond to remove system water and outside air temperatures, Domestic Hot Water Priority (DHWP) input or Energy Domestic Hot Water Priority (EMS) modulation rate demand, remote setpoint or remote start/stop commands. Parameter selections of remote system water temperature and remote mode deter­mining the choice of one of six different control modes.
5. Advanced Availability The above control modes are menu selectable op­tions. However, if a selected sensor rails, the SBC automatically changes to a control mode that will allow continued automatic operation of the boiler. For example, in the event of a remote system tem-
52
perature sensor failure, the SBC will automatically switch to boiler outlet temperature sensor based control.
6. Outdoor Air Reset When selected the modulation rate setpint is auto­matically adjusted based on outside air temperature. Outdoor air “reset” setpoint saves fuel by adjusting the water temperature of a heating boiler lower as the outside air temperature increases.
7. Warm Weather Shutdown (WWSD) Some boilers are used primarily for heating build­ings, and the boilers can be automatically shut­down when the outdoor air temperature is warm. When outside air temperature is above the WWSD setpoint, this function will prevent the boiler, boiler pump and/or the system pump from starting.
8. Domestic Hot Water Priority (DHWP) Some boilers are used primarily for building space heating, but also provide heat for the domestic hot water users. When the outdoor temperature is warm, the outdoor reset setpoint may drop lower than a desirable domestic hot water temperature. When enabled and a DHWP contact input is detected, the hot water setpoint is adjusted to be greater than a
eld adjustable DHWP Setpoint.
9. Water Side Control Outputs In order to maximize the life and availability of a hot water system it may be desirable to automate mixing valves, boiler pumps, system pumps, and standby system pumps. The SBC makes this type of automation totally integrated and cost effective. The
control of these devices is eld selectable through
simple yes/no menu selections.
10. Combustion Air Side Control Outputs Boiler room combustion air dampers (fresh air
dampers) and vent inducer control outputs are eld
selectable options.
11. Peer-To-Peer Network The SBC includes state-of-the-art modulating lead­lag sequencer for up to eight (8) boilers capable of auto rotation, outdoor reset and peer-to-peer com­munication. The peer-to-peer network is truly “plug and play”. Communication is activated by simply connecting a RJ11 telephone line between boilers. The SBC provides precise boiler coordination by sequencing boilers based on both remote system water temperature and boiler modulation rate. For
example, the lead boiler can be congured to start
a lag boiler after operating above 90% modulation rate for longer than an adjustable time. The boilers are modulated in “unison” (parallel) modulation rate to ensure even heat distribution.
12. Modbus Communication Interface
Page 53
A factory congured RS485 Modbus interface is
available for Energy Management System (EMS) or SCADA system monitoring and control.
B. FRONT PANEL DISPLAY
POWER LED (Steady On Green LED) indicates power is available down stream of the Electronic Control Module’s on board fuse. (Flashing On Green LED) indicates manual mode operation for boiler modulation, Call For Heat, and/or mixing valve modula tion. ALARM LED (Steady On Red LED) indicates an alarm is active. (Flashing On Red LED) indicates a lockout alarm is active and a manual
reset may be required.
SCREEN 2 line by 16 character display provides operational, alarm,
sequence status, conguration and diagnostic user interface
ENTER The ENTER key has no function in display mode. The ENTER key is used to select menus, menu items and save edited pa rameters as follows: Select Mode (steady text): Press ENTER to change into Edit Mode or select a menu or menu item Edit Mode (blinking text): Press ENTER to save the current value. Press MENU to cancel the current editing operation.
UP, DOWN Select Mode (steady text): Press UP, DOWN to change the selected display and move up and down menu items. Edit Mode (blinking text): Press UP, DOWN to increase or de crease the value of the number being edited, or scrolls through a list of choices.
MENU Press and hold MENU to change to the Main Menu screen. When in a sub menu screen, press MENU to move to the next higher menu. When in Edit Mode (blinking text) Press MENU to cancel the current editing operation.
53
Page 54
C. SETUP MENU
Display
WWSD Off
LL Start
Trigger
LL Stop
Trigger
Boiler On
Delay
Boiler Off
Delay
High Fire
Limit
Rotation Disable
Rotation
After
Outdoor
Sensor
Outdoor
Set Up
Boiler Set
Up
Outdoor
Design
Boiler
Design
Local
PID P
Factory
Settings
90 50 to 100
25 0 to 50
120 0 to 900
30 0 to 900
100 40 to 100
168 8 to 720
No
55°F 40°F to 100°F
140°F 80°F to 180°F
30°F -20°F to 50°F
180°F 80°F to 220°F
20 0 to 10000
Range/Choices
Off Ignores Warm Weather setpoint
WWSD of Boiler When Outside Air Temperature (OAT) is higher than the WWSD setpoint, inhibits boiler start
WWSD of Sys
Pump
Both
Disable Enable
No Outside Air Input (O+O-) is ignored.
Display Only Do Not Calculate setpoint based on outdoor temperature, Display Outside Air Temperature
Outdoor Reset
Description
WWSD
Species Warm Weather Shut-Down (WWSD) control of boiler and/or system pump:
When OAT is higher than the WWSD setpoint de-energize System Pump output (SO)
When OAT is higher than the WWSD setpoint, inhibit Call for Heat and de-energized system pump output (SO)
LL Start Trigger
Species the percent of maximum modulation rate the running boiler(s) must reach before calling
upon additional boilers for help.
LL Stop Trigger
Species the percent of modulation rate that the running boiler(s) must be below before shutting
down a lag boiler.
Boiler On Delay Time Delay after the On Point setpoint before starting the next boiler. Short time delay to prevent nuisance starts due to momentary temperature and modulation rate swings.
Boiler Off Delay Time Delay after the Off Point setpoint before stopping the next boiler. Short time delay to prevent nuisance stops due to momentary temperature and modulation rate swings.
High Fire Limit High modulation rate limit for all boilers on the peer-to-peer network as long as at least one boiler is still not running. After the last boiler has started the modulation rate is released up to 100%.
Rotation
Species number of hours (cumulative) a lead boiler runs before passing the lead to another boiler.
Lead rote will be surrendered earlier if the lead boiler is placed into manual mode, is running remotely
(mode 6), fails to start, is “blind” (all input sensors failed), or is satisfying a DHWP request.
Rotate After
Species number of hours (cumulative) a lead boiler runs before passing the lead to another boiler.
Outdoor Sensor Enables the Outside Air Temperature sensor and display and control logic:
Calculate the temperature setpoint based on outdoor temperature using a reset curve dened by
Outdoor Set Up, Boiler Set Up, Outdoor Design and boiler Design parameters.
Outdoor Set Up The Outdoor Set Up temperature is the outdoor temperature at which the Boiler Set Up temperature is supplied. Only visible when Outdoor Sensor is set to Outdoor Reset.
Boiler Set Up The Boiler Set Up temperature is the starting boiler water temperature of the reset ratio. If the build­ing feels cool during mild outdoor conditions, the Boiler Set Up setting should be increased. Only visible when Outdoor Sensor is set to Outdoor Reset.
Outdoor Design The Outdoor Design temperature is the outdoor temperature at which the Boiler Design temperature is supplied. Only visible when Outdoor Sensor is set to Outdoor Reset
Boiler Design
The Boiler Design setting is the water temperature required to satisfy the building heat loss during
the Outdoor Design temperature. If the building feels cool during cold outside conditions, the Boiler Design setting should be increased. Only visible when Outdoor Sensor is set to Outdoor Reset.
Local PID P Promotional gain value for boiler outlet temperature sensor control Modes. A larger gain value results in tighter, more active, PID control. Gain is the primary PID modulation rate tuning adjustment and provides the immediate modulation rate response.
54
Page 55
C. Setup Menu (Continued)
Display
Local PID I
Local
PID D
Remote
PID P
Remote
PID I
Remote
PID D
Mixing
Valve P
Mixing Valve I
Mixing
Valve D
Max ΔT P 10 0 to 10000
Max ΔT I 60 0 to 10000
Max ΔT D 0 0 to 10000
Factory
Settings
30 0 to 10000
20 0 to 10000
30 0 to 10000
10 0 to 10000
60 0 to 10000
Range/Choices Description
0 0 to 10000
0 0 to 10000
0 0 to 10000
Local PID I Integral Gain value for boiler outlet temperature sensor control Modes. A smaller value makes the Integral ramp in less time (i.e.., faster). Integral is a secondary PID modulation rate tuning adjustment that ramps the output over time (typically minutes).
Local PID D The Derivative Gain value for boiler outlet temperature sensor control Modes. A larger Derivative gain value produces a larger PID output contribution proportional to the rate of change of the error
(Setpoint - Boiler Outlet Temperature). When set equal to zero it has no effect on the output.
Remote PID P Proportional Gain value for Remote System Temperature sensor control Modes. Refer to Local PID P for explanation.
Remote PID I Integral Gain term for Remote System Temperature sensor control Modes. Refer to Local PID I for explanation.
Remote PID D Derivative Gain term for Remote System Temperature sensor control Modes. Refer to Local PID D for explanation
Mixing Valve P Proportional Gain value for boiler Inlet Temperature sensor control mode. A larger gain value results in tighter, more active, PID control. Gain is the primary PID modulation rate tuning adjustment and provides the immediate mixing valve modulation response. Only visible when mixing valve = yes.
Mixing Valve I Integral Gain value for boiler inlet Temperature sensor control mode. A smaller value makes the Inte­gral ramp in less time (i.e., faster). Integral is a secondary PID modulation rate tuning adjustment that ramps the output over time (typically minuets).
Mixing Valve D The Derivative Gain value for boiler Inlet Temperature sensor control mode. A larger Derivative gain value produces a larger PID output contribution proportional to the rate of change of the error (Set­point - Boiler Inlet Temperature)
When set equal to zero it has no effect on the output.
Max ΔT P
Promotional Gain value for boiler differential (boiler outlet minus inlet temperature sensor) tempera­ture control mode. Refer to Local PID P for explanation. Only Visible when mixing valve = yes.
Max ΔT I
Integral Gain value for boiler differential (boiler outlet minus inlet temperature sensor) temperature control mode. Refer to Local PID I for explanation. Only visible when mixing valve = yes.
Max ΔT D
Derivative gain term for boiler differential (boiler outlet minus inlet temperature sensor) temperature control mode. Refer to Local PID D for explanation. Only visible when mixing valve = yes.
55
Page 56
D. Boiler Conguration Menu
Display
Display
Units
Boiler
Pump
Pump
Prepurge
Postpurge
ΔT
Inlet Sen-
sor
Mixing
Valve
Set Time/
Date
Spare
Input
Spare
Output
Factory
Setting
°F
None
15 0 to 600
Yes
No
____
Off
Off
Range/Choices Description
Always On Pump Runs Continuously.
Purge Pump Runs during pump pre/post purge operations and during call for heat and then turns off.
Lead On
5 0 to 20
hour : minute Month / day /
Sys Pump FB
Low Fire
System Pump BUCloses when System Pump output is activated but the System Pump Feedback indicates the Primary
Soft Alarm Close when any alarm is active.
°F °C
None No Boiler Pump.
No
Yes
No
Yes
year
Off Ignore
Off Never close output (SO).
CAD
Display Units Selects how temperature parameter values are displayed.
Boiler Pump
Lead boiler’s pump runs continuously when the boiler is the lead boiler and revers to “Purge” opera­tion when it is a lag boiler.
Pump Prepurge Sets length of time the boiler pump will be run prior to closing the “Call for Heat” relay (CH).
Only visible when Boiler Pump does not equal None.
Postpurge ΔT Denes the temperature above BIT that BOT must be at or below before turning off the boiler pump
during pump post purge (Pump Cooldown State).
Only visible when Boiler Pump does not equal None.
Inlet Sensor Enables the inlet temperature display and control logic.
Mixing Valve Enables the mixing valve control output and user display.
Set Time/Date Sets the time and date of the boiler’s real time clock. This item also displays the time and date.
Spare Input Set the function of the Spare Input Terminal (SL):
Input (SI) should be wired to a ow switch inserted in the ow of the of the primary system pump. In­put (SI) indicates the primary system pump is operating. If output (SO) is set to System Backup Pump, system pump output (SO) is energized and System Pump Feedback is de-energized the System Backup Pump output (SO) is energized.
When the Fuel Valve Energized input (SC) is not energized and input (SI) is energized the modulation rate is set to the “Low Fire Spd” setpoint. When input (SI) is not energized the modulation rate is set to “Fan Purge Spd” setpoint. When the fuel valve energized input (CS) is energized input (SI) is ignored.
Spare Output Sets the function of the Spare Output Terminal (SO):
Closes SO relay with a call for heat, Opens SO relay 2 minutes after call for heat has been deacti­vated.
System Pump is not operating.
56
Page 57
E. System Conguration Menu
Display
DHWP Off
Remote
Control
Remote
1.0 volt =
Remote
9.0 volt =
Remote
Sensor
System
Pump
LWC or
CAD
Alarm
Message
Factory
Setting
140°F 60°F to 170°F
220°F 150°F to 220°F
16 Text
Charac-
Range/Choices Description
Off No DHWP.
Isolated
Demand
Shared Demand
No No
No Remote Sensor Input (R+,R-) is ignored.
No
No
No
ters
Display Only Remote Sensor Input (R+,R-) is used for display only.
Control
No
Yes
No
Yes
“Low Water
Level”
DHWP Enables Domestic Hot Water Priority (DHWP) control feature. When input (DP) is energized DHWP becomes active as selected:
Boiler that received the input (DP) drops off the Peer-To-Peer network and its temperature setpoint is adjusted above the DHWP setpoint. The PID output is based on boiler outlet temperature and set­point. If Remote SP or Remote System temperature sensor were selected, control is switched to the Boiler Outlet Sensor.
If the lead boiler receives the input (DP) the temperature setpoint for all boilers on the peer-to-peer network is adjusted above the DHWP setpoint.
Remote Control Sets the remote (Energy Management System) control mode as follows:
Local setpoint and modulation rate is used. Modbus and remote input (C+,C-) are ignored.
Remote 1.0 Volt = Sets the temperature corresponding to the input (C+,C-) 1 Volt. Voltage below 1V is considered invalid, (failed or miswired sensor.)
Remote 9.0 Volt = Sets the temperature corresponding to the input (C+,C-) 9 volts. Voltage above 9V is considered invalid (failed or miswired sensor.)
Remote Sensor Enables the Remote System Temperature sensor display and control logic:
Control Remote Sensor Input (R+,R-) is compared with the temperature setpoint to establish a modu­lation rate.
System Pump Enables the System Pump Output (SO)
LWC or CAD
Species a Low Water Cut-off Switch or Combustion Air Damper (Fresh Air Damper). Open switch
is connected to input (LC). Enables Limit Hold and alarm messages. Limit hold display message is described by parameter 28.
Alarm Message Limit Hold and alarm message displayed corresponding to sensor connected to input (LC). The “ENTER” key and “up” and “Down” arrow keys are used to change the text message.
Only visible when parameter 27 equals Yes.
57
Page 58
F. Setpoints Menu
Display
Opera-
tional SP
On Point -5°F 0°F to -99°F
Off Point 15°F 0°F to 99°F
High
Temp
Stop
DHWP
Setpoint
WWSD
Setpoint
Max SP 230°F 140°F to 230°F
Min SP 140°F 60°F to 230°F
Min In
H2O
Temp
Max H2O
Delta T
Max
Delta T
Hold
Factory
Setting
180°F 60°F to 230°F
200°F 60°F to 230°F
180°F 140°F to 230°F
70°F 40°F to 90°F
130°F 110°F to 180°F
40°F 20°F to 50°F
50°F 20°F to 50°F
Range/Choices Description
Operational SP Setpoint used in Local Setpoint Mode when not servicing a Domestic Hot Water Priority (DHWP)
request.
On Point The boiler starts when the water temperature drops “On Point” degrees below the setpoint.
Off Point The boiler stops when the water temperature rises “Off Point” degrees above the setpoint.
High Temp Stop The boiler stops when water temperature is above the High Temperature Stop setpoint. This setpoint is active in every control mode.
DHWP Setpoint The Domestic How Water Priority (DHWP) Setpoint is active when DHW Input (DP) closes and “DHWP” parameter is set to “yes” and Local SP Mode is selected. When the contact is closed, the boiler outlet is maintained at, or above, the DHW Setpoint.
WWSD Setpoint The Warm Weather Shutdown (WWSD) Setpoint used to disable boiler and/or system pump opera­tion when enabled by setting the “WWSD” parameter to “WWSD of Boiler”, “WWSD of Sys Pump” or “Both”
Max SP The Maximum Operational Setpoint for all possible Local and Remote Modes.
Min SP The Minimum Operational Setpoint is the lower limit for all Local and Remote modes.
Min In H2O Temp. Minimum Inlet Water Temperature Setpoint used as the Mixing Valve inlet temperature setpoint.
Only visible when Mixing Valve equals Yes.
Max H2O Delta T Maximum Water Differential (Boiler Outlet minus Boiler Inlet) temperature setpoint used as the Mixing Valve differential temperature setpoint.
Only visible when Mixing Valve equals yes.
Max Delta T Hold Maximum Water differential (Boiler Outlet minus Boiler Inlet) Temperature used to hold modulation
rate at low re.
58
Page 59
G. Communication Menu
Display
Protocol
Modbus Address
Baud
Rate
Parity Odd
Timeout 30 1 - 120
Messag-
es Rcvd
Messag-
es Sent
Boiler
Address
Online Status
Factory
Setting
Peer-To-
Peer
19.2
Range/Choices Description
Peer-To-Peer
1 1 - 247
1 1 to 8
Modbus
9.6
19.2
38.4
Odd
Even
None
XXXXXXXX
Protocol Selects between Peer-To-Peer (Multiple boiler lead/lag control network) and a Modbus slave commu­nication.
Modbus Address
Each boiler must be given a unique address. Only visible when Protocol equals Modbus.
Baud Rate Units are 1000 Bits Per Second (KBPS).
Only visible when Protocol Equals Modbus.
Parity
Only visible when Protocol equals Modbus.
Timeout
Only visible when Protocol equals Modbus.
Messages Rcvd
Diagnostic tool used to conrm wiring and Modbus master conguration. Only visible when Protocol equals Modbus.
Messages Sent
Diagnostic tool used to conrm wiring and Modbus master conguration. Only visible when Protocol equals Modbus.
Boiler Address
Each Boiler must be given a unique address. The boiler address assignment determines the boiler sequencing order. A value of 0 disables the network communications. Only visible when Protocol equals Peer-To-Peer.
Online Status Each space can be either the boiler address or a “-” depending on whether there is a boiler of that address online. Example: _ _ 6 _ _ _ 321 indicates that boilers 6, 3,2, and 1 are online.
Only visible when Protocol equals Peer-To-Peer
H. Manual Mode Menu
Display
101 Auto
102 Varies 0 to 100
103 Varies
104 Auto
105 Varies 0 to 100
Factory
Setting
Range/Choices Description
Man
Auto
On Off
Man
Auto
Boiler Man/Auto Man: Remain in Manual Mode
Auto: Return to Boiler Mode specied by parameter/boiler conditions.
Activated only when in Supervisor Mode.
Modulation Rate Sets the modulation rate to be sued for boiler when in Manual Mode. Activated only when in Supervisor Mode and Boiler Man/Auto = Man.
Boiler On/Off Sets the boiler start/stop status when in Manual Mode. No: Turn of boiler if running, otherwise remain off. Yes: Turn on boiler if off, otherwise remain on. Activated only when in Supervisor Mode and Boiler Man/Auto = Man.
Mixing Valve M/A Man: Remain in Manual Mode
Auto: Return to Control Mode specied by parameter/boiler conditions
Activated only when in Supervisor Mode.
Mixing Valve Sets the Mixing Valve % Open to be used for valve when in Manual Mode.
Activated only when in Supervisor Mode and Mixing Valve M/A equals Man.
59
Page 60
I. Security Menu
Passwords There are three Access Levels in the system: Basic, Supervisor, and Factory.
At the BASIC Access Level, the user can view many parameters, but is only allowed to edit a
• small sub-set of the parameters that are visible. At the SUPERVISOR Access Level, the user can view and edit most parameters that are vis-
• ible. Not all parameters will be visible at the Supervisor Access Level. At the FACTORY Access Level, all relevant internal parameters in the system will be visible
• and programmable.
The Basic Access Level is the access level at power-up if the system password parameter is not
equal to zero. The Supervisor Access Level is the access level at power-up if the system pass­word parameter is equal to zero. If the system password is non-zero, the Supervisor Access Level
may be reached by entering the correct password in the Enter Password parameter.
The Factory Access Level can be reached by entering the factory password in the Enter Password parameter and holding the Enter key for at least two seconds when accepting the value entered. The display will jump to the Access Level parameter menu when the system has entered the Fac­tory Access Level. Note that the Access Level parameters value will indicate “Supervisor”.
To exit either of the privileged access levels (Factory or Supervisor), change the value of the Ac­cess Level parameter from “Supervisor” to “Basic”. Also, if no key is pressed for ~ 1 hour, the ac­cess level will automatically revert to Basic.
Factory
No.
Setting Range/Choices Parameter and Description
Access Level
Basic
Supervisor
Basic: Select Basic Level Access to parameters/variables Supervisor: Select Password Level Access to parameters/ variables.
Enter Password
0 to 9999
Allows user to enter password to gain access to both Su­pervisor Access and Factory Access Levels.
Set Password
15 0 to 9999
Holds the user-dened password for the boiler. A password
= ) means no password protection. Access Level will de­fault to Supervisor Level at power-up.
60
Page 61
XI. Repair Parts
2
3
10
7
7
9
1
6
5
4
8
All Solaris® Series Repair Parts may be obtained through your local Thermal Solutions
representative. Should you require assistance in locating a Thermal Solutions representative in your area, or have questions regarding the availability of Thermal Solutions products or repair parts,
please contact Thermal Solutions Customer Service at (717) 239-7642 or Fax (877) 501-5212.
Figure 31: Combustion Chamber
Key No. Description Part Number
1. Combustion Chamber SOL-300 SOL-500 SOL-750 SOL-1000 SOL-1250 SOL-1500
1 Base/Bottom Panel 618SOL0204 618SOL0504 618SOL0704 618SOL1004 618SOL1204 618SOL1504
2 Left Side Panel Assembly 618SOL0021 618SOL00211
3 Right Side Panel Assembly 618SOL0031 618SOL00311
4 Air Box Cover 718SOL0203 718SOL0503 718SOL0703 718SOL1003 718SOL1203 718SOL1503
5 Air Box Assembly 618SOL02051 618SOL05051 618SOL07051 618SOL10051 618SOL12051 618SOL15051
6 Canopy Assembly 618SOL0210 618SOL0510 618SOL0710 618SOL1010 618SOL1210 618SOL1510
7 Side Insulation 820SOL0020 820SOL0021
8 Front Insulation 820SOL0203 820SOL0503 820SOL0703 820SOL1003 820SOL1203 820SOL1503
9 Bottom Insulation 820SOL0200 820SOL0500 820SOL0700 820SOL1000 820SOL1200 820SOL1500
10 Back Insulation 820SOL0202 820SOL0502 102504-01 102504-02 102504-03 102504-04
61
Page 62
Figure 32: Burner Tray
2
1
3
4
Key
No. Description Part Number
1. Burner Tray
1 3 Burner Assembly 102017-01
2 Ignitor Assembly 812SOL0010
3 Gasket, Burner Mounting Plate 820SOL0004
4 Gasket, Ignitor Assembly 820SOL0005
62
Page 63
6
3
5
4
2
1
3
7
Figure 33: Gas Train (SOL-300)
(Reference Table 8)
63
Page 64
3
9
6
5
4
7
1
10
8
3
SIDE VIEW OF
GAS VALVE
2 2
11
Figure 34: Gas Trains (SOL-500 through SOL-1500)
64
(Reference Table 8)
Page 65
Gas Trains: Reference Figures 33 & 34
SOL-300 SOL-500 SOL-750 SOL-1000 SOL-1250 SOL-1500
Main Gas Valve Flange(s) 3/4” NPT (1) 102281-01
Main Gas Valve Body (1)816SOL0006 (1)816SOL0510 (1) 816SOL0005
Key Description (Quantity) Part Number
1
Main Gas Valve Flange(s) 1” NPT (2) 816SOL0503 (2) 102281-02
Main Gas Valve Flange(s) 1-1/4” NPT (2) 102281-03
Main Gas Valve Flange(s) 1-1/2” NPT (2) 102281-04
2
Manual Gas Valve 1” NPT (2) 816SOL0015
Manual Gas Valve 1-1/4” NPT (2) 816SOL0016
Manual Gas Valve 1-1/2” NPT (2) 816SOL0017
3
4 Pilot Gas Valve (1) 816SOL0501
5 Pilot Gas Valve Flange 1/2” NPT (1) 816SOL0502
6 Manual Gas Valve 1/2” NPT (1) 816SOL0010
7 Insulation Grommet (1) 820SOL0001
8 High Gas Pressure Switch (Optional) (1) 816SOL0005
9 Low Gas Pressure Switch (Optional) (1) 816SOL0006
10 G18 Test Nipple (2) 816SOL0001
Table 8: Gas Train Components
11 Hose Barb (2) 816SOL0002
65
Page 66
1
2
Manifold Orice Assembly
Key
No. Description
1 Manifold Orice Assembly 812SOL0200 812SOL0500 812SOL0700 812SOL1000 812SOL1200 812SOL1500
2a Natural Gas Prejet 812SOL0034
2b Liquid Propane (LP) Gas Prejet 812SOL0001
Figure 35: Manifold Orice Assembly
66
Boiler Model
SOL-300 SOL-500 SOL-750 SOL-1000 SOL-1250 SOL-1500
Page 67
3
5
2
3
4
1
6
Heat Exchanger Assembly (SOL-300 & 500)
Key No. Description Quantity
1 Heat Exchanger 1 603SOL0210 603SOL0510
2 Immersion Well 2 80160456
3 Inlet/Outlet Temp. Sensor 2 801SOL0010
4A Temp/Pressure Gauge 0-100PSI 1 8056248
4B Temp/Pressure Gauge 0-200PSI 1 8056249
4C Temp/Pressure Gauge 0-240PSI 1 8056250
5 Water Flow Switch 1 80160175
6 Tube Bafes 10 718SOL0219 718SOL0519
Part Number
SOL-300 SOL-500
Figure 36: Heat Exchanger Assembly (SOL-300 & 500)
67
Page 68
Key No. Description
1 Heat Exchanger 102499-01 102499-02 102499-03 102499-04
2 Tube Bafe 718SOL0719 718SOL1019 718SOL1219 718SOL1519
3 Inlet/Outlet Temp Sensor 801SOL0010
4 Hose Banding 924660281
5 Hose Clamp 80860491
6 Fiberglass Tape Gasket 9206032
Figure 37: Heat Exchanger Assembly (SOL-750 through 1500)
68
Part Number
SOL-750 SOL-1000 SOL-1250 SOL-1500
Page 69
7
9
6
5
3
4
1
2
8
Key No. Description Quantity Part Number
1. Electrical Panel
1 Q7800H1009 Electrical Side Panel 1 704SOL0006
Q7800H1009 Honeywell Relay Module Circuit
2
board 1 101182-01
3 Relay Module Honeywell RM7897A1002 1 801602121
4 Flame Rectication Amplier 1 80160207
5 Purge Card 1 8136362
6 Keyboard Display Module 1 80160640
7 Transformer, 120V Primary, 24V Secondary 1 801600502
8 Combustion Airow Switch 1 102382-03
Figure 38: Electrical Panel
69
Page 70
SOL-300 SOL-500 SOL-750 SOL-1000 SOL-1250 SOL-1500
7
4
10
1
2
5
9
11
6
3
8
12
Part Number
Figure 39: Boiler Jacket Assembly
1 Base Panel Assembly 604SOL0211 604SOL0511 604SOL0711 604SOL1011 604SOL1211 604SOL1511
2 Jacket, Rear Panel Assembly 604SOL0203 604SOL0503 604SOL0703 604SOL1003 604SOL1203 604SOL1503
3 Exhaust CV Assembly 618SOL0000 618SOL0001 618SOL0701 618SOL1001 618SOL1201 618SOL1501
4 Jacket, Right Side Panel Assembly 604SOL0204 604SOL0504 604SOL0704 604SOL1004 604SOL1204 604SOL1504
5 Jacket, Left Side Panel Assembly 604SOL0205 604SOL0505 604SOL0705 604SOL1005 608SOL1205 604SOL1505
No. Description
Key
6 Jacket, Top Panel Assembly 604SOL0206 604SOL0506 604SOL0706 604SOL1006 604SOL1206 604SOL1506
7A Jacket. Front Panel (Left Side SOL-1250 & 1500) 704SOL0202 704SOL0502 604SOL0702 604SOL1002 704SOL0090 704SOL0091
8 Insulation Box 820SOL0032 820SOL0032 820SOL0033 820SOL0033 820SOL0033 820SOL0033
9 Intake Corner Vent Assembly 604SOL0208 604SOL0508 604SOL0708 604SOL0708 604SOL1208 604SOL1208
7B Jacket, Front Panel (Right Side SOL-1250 & 1500) 704SOL0092 704SOL0093
10 Exhaust Corner Vent 704SOL0207 704SOL0507 704SOL0707 704SOL0707 704SOL1207 704SOL1207
11 Air Inlet Filter 811SOL0020 811SOL0020 811SOL0022 811SOL0022 811SOL0022 811SOL0022
70
Page 71
SERVICE RECORD
Date Service Performed
71
Page 72
SERVICE RECORD
Date Service Performed
72
Page 73
SERVICE RECORD
Date Service Performed
73
Page 74
Important Product Safety Information
Refractory Ceramic Fiber Product
Warning:
This product contains refractory ceramic bers (RCF). RCF has been classied as a pos­sible human carcinogen. After this product is red, RCF may, when exposed to extreme-
ly high temperature (>1800F), change into a known human carcinogen. When disturbed as a result of servicing or repair, RCF becomes airborne and, if inhaled, may be hazard­ous to your health.
AVOID Breathing Fiber Particulates and Dust
Precautionary Measures:
Do not remove or replace previously red RCF (combustion chamber insulation, tar­get walls, canopy gasket, ue cover gasket, etc.) or attempt any service or repair work
involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH) approved respirator
2. Long sleeved, loose tting clothing
3. Gloves
4. Eye Protection
• Take steps to assure adequate ventilation.
• Wash all exposed body areas gently with soap and water after contact.
• Wash work clothes separately from other laundry and rinse washing machine
after use to avoid contaminating other clothes.
• Discard used RCF components by sealing in an air tight plastic bag.
First Aid Procedures:
• If contact with eyes: Flush with water for at least 15 minutes. Seek immedi­ate medical attention if irritation persists.
• If contact with skin: Wash affected area gently with soap and water. Seek immediate medical attention if irritation persists.
• If breathing difculty develops: Leave the area and move to a location with clean fresh air. Seek immediate medical attention if breathing difculties
persist.
74
Page 75
Thermal Solutions
(seller)
LIMITED WARRANTY
LIMITED WARRANTY
Subject to the terms and conditions herein and except as pro­vided below with respect to products or parts not manufactured by Thermal Solutions, Seller warrants to the original owner at the original installation site that products manufactured by Seller (“Products”) comply, at the time of manufacture, the heat exchanger with recognized hydronics industry regulatory agency standards and requirements then in effect and will be free from defects in materials and workmanship for a period of 3 years from date of shipment (the “Warranty Period”). The burner is also covered under the limited warranty for 1 year from date of shipment (the “Warranty” Period). SPECIAL NOTE: The warranty of any boiler found to be operating as a “Water Heater” shall revert back to Thermal Solution’s stan­dard water heater warranty.
For products or parts not manufactured by Thermal Solutions, the warranty obligations of Thermal Solutions shall, in all respects, be limited to one year.
REMEDY
A. The sole remedy for breach of this warranty is expressly
limited to the repair or replacement of any part found to be defective under conditions of normal use within the War­ranty Period. Labor for removal and/or installation is not included.
B. Warranty - The owner must notify the original installer of
the Product and Seller (Attention: Thermal Solutions, P.O. Box 3244, Lancaster, PA 17604-3244), in writing, within the Warranty Period, providing a detailed description of all claimed defects. Transportation to a factory or other des­ignated facility for repairs of any products or items alleged defective shall, in all events, be the responsibility and at the cost of the owner.
EXCLUSIONS
Seller shall have no liability for and this warranty does not cover:
A. Incidental, special or consequential damages, such as loss
of the use of products, facilities or production, inconve­nience, loss of time or labor expense involved in repairing or replacing the alleged defective Product.
B. The performance of any Product under conditions varying
materially from those under which such Product is usually tested under industry standards as of the time of shipment.
C. Any damage to the Product due to abrasion, erosion, corro
sion, deterioration, abnormal temperatures or the inuence
of foreign matter or energy.
D. The design or operation of owner’s plant or equipment
or of any facility or system of which any Product may be made a part.
E. The suitability of any Product for any particular applica
tion.
-
F. Any failure resulting from misuse, modication not
authorized by Seller in writing, improper installation or
lack of or improper maintenance.
G. Equipment furnished by the owner, either mounted or
unmounted, or when contracted for by the owner to be installed or handled.
H. Leakage or other malfunction caused by:
1. Defective installations in general and specically, any
installation which is made:
a. in violation of applicable state or local plumbing
housing or building codes,
b. without a certied ASME, pressure relief valve, or
c. contrary to the written instructions furnished with
the unit
2. Adverse local conditions in general and, specically,
sediment or lime precipitation in the tubes and/or head­ers or corrosive elements in the atmosphere.
3. Misuse in general and, specically, operation and
maintenance contrary to the written instructions furnished with the unit, disconnection, alteration or addition of components or apparatus, not approved by seller, operation with fuels or settings other than those set forth on the rating plate or accidental or exterior damage.
I. Production of noise, odors, discoloration or rusty water.
J. Damage to surrounding area or property caused by leakage
or malfunction.
K. Costs associated with the replacement and/or repair of the
unit including: any freight, shipping or delivery charges, any removal, installation or reinstallation charges, any ma­terial and/or permits required for installation reinstallation or repair, charges to return the boiler and or components.
Seller’s liability under this warranty shall not in any case ex­ceed the amount paid for the Product found to be defective.
THIRD-PARTY WARRANTIES
For goods or components not manufactured by Seller, the war­ranty obligations of Seller shall, in all respects, conform and be limited to one year from the date of shipment
SEVERABILITY
To the extent that any provision of this warranty would be void
-
or prohibited under applicable law, such provisions shall be limited in effect to the minimum extent necessary to render the remaining provisions hereof enforceable.
75
Loading...