Thermal Solutions SOLARIS Installation, Operating And Service Instructions

INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
SOLARIS
Gas-Fired Boiler
Boiler Model Number SOL __ __ __ __ - __ __ __
Heating Contractor Phone Number
Address
814SOL0010-8/09
Boiler Serial Number 6 __ __ __ __ __ __ __
Installation Date
Price - $5.00
1
IMPORTANT INFORMATION - READ CAREFULLY
NOTE: The equipment shall be installed in accordance with those installation regulations enforced in the area where the
installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or local regulations.
All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or local regulations.
The Commonwealth of Massachusetts requires this product to be installed by a licensed Plumber or Gas Fitter.
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial property dam-
Indicates a potentially hazardous situation which, if not avoided, may result in moder­ate or minor injury or property damage.
CAUTION
age.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death, serious injury or substantial property dam­age.
Indicates specic instructions on installa­tion, operation, or maintenance which are important but not related to personal injury hazards.
NOTICE
DANGER
DO NOT store or use gasoline or other ammable vapors or liquids in the vicinity of this or any
other appliance. If you smell gas vapors, DO NOT try to operate any appliance - DO NOT touch any electrical switch or use any phone in the building. Immediately, call the gas supplier from a remotely lo­cated phone, Follow the gas supplier’s instructions or if the supplier is unavailable, contact the
re department.
Manufacturer’s Contact Information: Thermal Solutions 1175 Manheim Pike Lancaster, PA 17601 717-239-7642 www.thermalsolutions.com
2
WARNING
This boiler requires regular maintenance and service to operate safely. Follow the instructions
contained in this manual. Improper installation, adjustment, alteration, service or maintenance can cause property dam-
age, personal injury or loss of life. Read and understand the entire manual before attempting installation, start-up operation, or service. Installation and service must be performed only by an experienced, skilled, and knowledgeable installer or service agency.
This boiler must be properly vented. This boiler needs fresh air for safe operation and must be installed so there are provisions for
adequate combustion and ventilation air.
The interior of the venting system must be inspected and cleaned before the start of the heating season and should be inspected periodically throughout the heating season for any obstructions. A clean and unobstructed venting system is necessary to allow noxious fumes that could cause
injury or loss of life to vent safely and will contribute toward maintaining the boiler’s efciency.
Installation is not complete unless a pressure relief valve is installed into the tapping located on top of appliance. - See the Water Piping and Trim Section of this manual for details.
This boiler is supplied with safety devices which may cause the boiler to shut down and not re­start without service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the boiler is inoperative.
This boiler contains very hot water under high pressure. Do not unscrew any pipe ttings nor
attempt to disconnect any components of this boiler without positively assuring the water is cool
and has no pressure. Always wear protective clothing and equipment when installing, starting
up or servicing this boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the boiler. This boiler contains compo­nents which become very hot when the boiler is operating. Do not touch any components unless they are cool.
Boiler materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful sub­stances which can cause death or serious injury and which are known to the state of California to cause cancer, birth defects and other reproductive harm. Always use proper safety clothing,
respirators and equipment when servicing or working nearby the appliance.
Failure to follow all instructions in the proper order can cause personal injury or death. Read all instructions, including all those contained in component manufacturers manuals which are pro­vided with the boiler before installing, starting up, operating, maintaining or servicing.
Keep boiler area clear and free from combustible materials, gasoline and other ammable va­pors or liquids.
All cover plates, enclosures and guards must be in place at all times. This product must be installed by a licensed plumber or gas tter when installed within the Com-
monwealth of Massachusetts.
This boiler has a limited warranty, a copy of which is printed on the back of this manual. It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating properly when the installation is complete.
NOTICE
3
Table of Contents
I. Pre-Installation ................................................. 6
II. Unpack Boiler ...................................................7
III. Venting/Air Intake Piping ................................ 8
A. Vent Guidelines Due to Removal of an
Existing Boiler .............................................8
B. General Guidelines ..................................... 9
C. Supplemental Vent Terminal Location
Instructions ................................................10
D. Separate Horizontal Venting
System ........................................................ 11
E. Optional Horizontal Vent Terminal
Mounting .................................................... 14
F. Conventional Venting........ ........................15
G. Air Intake Piping ......................................15
H. Separate Vertical Venting System ...........17
IV. Water Piping and Trim .................................. 20
V. Gas Piping .......................................................24
VI. Electrical .........................................................26
VII. Modular Installations ....................................29
VIII. System Start-up ...........................................39
IX. Service and Maintenance ............................... 46
A. Periodic Maintenance ..............................46
B. Safety & Operating Controls .................... 49
C. Trouble Shooting ........................................50
X. Sage Boiler ControlTM (SBCTM)......................52
A. Introduction ............................................... 52
B. Front Panel Display ...................................53
C. Setup Menu ................................................54
D.BoilerCongurationMenu ......................56
E. SystemCongurationMenu ....................57
F. Setpoints Menu ..........................................58
G. Communication Menu ..............................59
H. Manual Mode Menu .................................. 59
I. Security Menu............................................60
XI. Repair Parts ....................................................61
XII. Service Record .............................................. 71
XIII. Refractory Ceramic Fiber ..........................74
XIV. Warranty .......................................................75
Minimum Clearance to Combustible Materials
Left Side Right Side Front Rear Top Flue Connector
1” 1” 24” 3” 1” 6”
Recommended Clearance for Service
Model Left Side or Right
Front Rear Top
Side SOL-300 24” 24” 24” 16” SOL-750 24” 24” 24” 16” SOL-1000 24” 24” 24” 19” SOL-1250 24” 24” 24” 31” SOL-1500 24”
Note: Verify clearance with jurisdiction having authority and local codes.
4
(Amps)
REAR VIEW
TOP VIEW
SIDE VIEW
L
(TYP.)
L
(TYP.)
C
2.71
E
D
B
K
A
13.00
H
M VENT
OUTLET
F OULET
WATER
F INLET
WATER
G INLET GAS
J
M VENT
INLET
Amp Draw
Rated Blower
(HP)
Rated Motor
Horse Power
Electrical Supply
(Voltz/Hertz/Phase)
Wet
(lbs.)
Weight
Dry
(lbs.)
Weight
Water
Volume
(Gallons)
BTU
(MBH)
Output
General Ratings and Capacities
(MBH)
BTU Input
Boiler
Model
SOL-300 300 252 1.1 288.5 297.7 3/4 8.5
SOL-500 500 420 1.3 316.0 326.8 3/4 8.5
SOL-750 750 637.5 2.4 508.5 528.5 120/60/1 3/4 8.0
SOL-1000 1000 850 2.6 548.5 570.2 3/4 8.0
SOL-1250 1250 1062.5 2.9 620.0 644.2 1-1/8 12
SOL-1500 1500 1275 3.3 713.0 740.5 1-1/8 12
Dimensions
‘A’ ‘B’ ‘C’ ‘D’ ‘E’ ‘F’ ‘G’ ‘H’ ‘J’ ‘K’ ‘L’ ‘M’
Boiler
Model
SOL-300 27.8 32.6 28.1 25.9 15.0 2.0 1.00 4.1 29.3 17.0 4.1 4.0
SOL-500 42.6 32.6 28.1 28.0 15.0 2.0 1.00 7.2 27.8 17.0 4.1 6.0
SOL-750 41.4 36.9 31.8 32.4 13.0 3.0 1.00 3.5 32.1 23.6 6.2 8.0
SOL-1000 49.4 36.9 31.8 32.4 13.0 3.0 1.25 3.5 32.1 21.6 6.2 8.0
SOL-1250 61.6 36.9 31.8 32.4 13.0 3.0 1.25 3.5 32.1 26.5 6.2 10.0
Figure 1: Dimensions
SOL-1500 73.9 36.9 31.8 32.4 13.0 3.0 1.50 3.5 32.1 25.6 6.2 10.0
5
I. Pre-Installation
WARNING
If you do not follow these instructions ex-
actly, a re or explosion may result causing
property damage or personal injury.
DANGER
Do not install boiler where gasoline or other
ammable vapors or liquids, or sources
of hydrocarbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used or stored.
NOTICE
E. Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, condensate trap, control replacement, etc.).
F. Provide combustion and ventilation air in accordance
with sections 5.3 of the National Fuel Gas code, ANSIZ223.1/NFPA 54, or sections 7.2, 7.3, or 7.4 of CAN/CSA B149.1, Natural Gas and Propane Installa­tion code, or applicable provisions of the local building codes.
WARNING
Adequate combustion and ventilation air
must be provided to assure proper combus­tion.
Due to the low water content of the boiler, mis-sizing of the boiler with regard to the heating system load will result in excessive boiler cycling and accelerated component failure. Thermal Solutions DOES NOT warrant failures caused by mis-sized boiler applications. DO NOT oversize the boiler to the system. Modular boiler installations greatly reduce the likelihood of boiler over­sizing.
A. Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such requirements, installation must conform to the Na- tional Fuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/CGA B149 Installation Codes. Where required the installation must conform to the standard for con-
trols and safety devices for automatically red boilers,
ANSI/ASME CSD-1.
B. Appliance is design certied for installation on combus-
tible ooring. Do not install boiler on carpeting.
C. Provide clearance between boiler jacket and combus-
tible material in accordance with local re ordinance.
Refer to Figure 1 for minimum listed clearance from combustible material. Recommended service clearance is 24 inches from left side, right side and front. Rec­ommended service clearance is 36” at rear of unit. Ser­vice clearances may be reduced to minimum clearances to combustible materials.
The following guideline is based on the National Fuel Gas Code, NFPA 54/ANSI Z223.1.
1. Determine volume of space (boiler room). Rooms communicating directly with space (through open­ings not furnished with doors) are considered part of space.
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]
2. Determine Total Input of all appliances in space. Round result to nearest 1,000 Btu per hour (Btuh).
3. Determine type of space. Divide Volume by Total Input.
a. If result is greater than or equal to 50 ft³ per
1,000 Btuh, space is considered an unconned space.
b. If result is less than 50 ft³ per 1,000 Btuh, space
is considered a conned space.
4. Determine building type. A building of unusually tight construction has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed, and;
b. Weather-stripping has been added on openable
windows and doors, and;
c. Caulking or sealants applied in joints around
window and door frames, between sill plates and
oors, between wall-ceiling joints, between wall
panels, at plumbing and electrical penetrations, and at other openings.
D. Install on level oor. Floor must be able to support
weight of boiler, water and all additional system com­ponents.
6
5. For boiler located in an unconned space in a
building of other than unusually tight construc­tion, adequate combustion and ventilation air
is normally provided by fresh air inltration
through cracks around windows and doors.
6. For boiler located within unconned space in
building of
within equate conned space, provide outdoor air through two permanent openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely commu­ nicating with the outdoors. Locate one opening within twelve (12) inches of top of space. Locate remaining opening within twelve (12) inches of bottom of space. Minimum dimension of air opening is three (3) inches. Size each opening per following:
a. Direct communication with outdoors. Minimum
free area of one (1) square inch per 4,000 Btu per hour input of all equipment in space.
b. Vertical ducts. Minimum free area of one (1)
square inch per 4,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
c. Horizontal ducts. Minimum free area of one (1)
square inch per 2,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
unusually tight construction, or
Alternate method for boiler located within
conned space. Use indoor air if two permanent
openings communicate directly with additional
space(s) of sufcient volume such that combined volume of all spaces meet criteria for unconned
space. Size each opening for minimum free area of one (1) square inch per 1,000 Btu per hour input of all equipment in spaces, but not less than 100 square inches.
7. Combustion Air/Ventilation Duct Louvers and Grilles. Equip outside openings with louvers to prevent entrance of rain and snow, and screens to prevent entrance of insects and rodents. Louvers and
grilles must be xed in open position or interlocked
with equipment to open automatically before burner operation. Screens must not be smaller than ¼ inch mesh.
Consider the blocking effect of louvers, grilles and
screens when calculating the opening size to provide the required free area. If free area of louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.
CAUTION
Avoid operating this boiler in an environment where saw dust, loose insulation bers, dry wall
dust, etc. are present. If boiler is operated under these conditions, the burner interior and ports must be cleaned and inspected daily to insure proper operation.
II. Unpack Boiler
CAUTION
Do not drop boiler. Do not bump boiler
jacket against the oor.
A. Move boiler to approximate installed position.
B. Remove all crate fasteners.
C. Lift and remove outside container. Save two of the
wooden slats from the container sleeve for use in Steps E and F.
D. Remove all boiler hold-down fasteners.
Installation of this boiler should be under­taken only by trained and skilled personnel
from a qualied service agency.
E. Tilt the boiler to its front side or back side and slide a
wooden slat under the raised feet.
F. Tilt the boiler in the opposite direction and slide another
wooden slat under the raised feet.
G. Slide the boiler left or right off the skid using the two
wooden slats as runners.
H. Move boiler to its permanent location.
WARNING
7
III. Venting / Air Intake Piping
WARNING
Do not use this boiler with galvanized, non metallic or any other venting material that is not de-
signed for condensing ue gas applications.
Do not use a drafthood with this appliance. Do not use vent dampers with this boiler. Moisture and ice may form on surfaces around termination. To prevent deterioration, surfaces
should be in good repair (sealed, painted, etc.). This appliance needs fresh air for safe operation and must be installed so there are provisions
for adequate combustion and ventilation air.
Do not reduce size of air intake pipe. Read, understand and follow combustion air instruction restrictions contained in the Pre-Installa-
tion instructions of this manual.
Do not operate appliance where gasoline or other ammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used, stored and/or present in the air.
When installing vent pipe through chimney, no other appliance can be vented into the chimney. Do not exceed maximum vent/air intake lengths. Refer to Table 1.
A. Vent Guidelines Due to Removal of an Ex-
isting Boiler
For installations not involving the replacement of an
existing boiler, proceed to Step B.
When an existing boiler is removed from a common
venting system, the common venting system is likely to be too large for proper venting of the remaining appli­ances. At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remain­ing connected to the common venting system are not in operation:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, and
other deciencies which could cause an unsafe
condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range-hoods and bathroom exhausts, so they will operate at
8
maximum speed. Do not operate a summer exhaust
fan. Close replace dampers.
4. Place in operation the appliance being inspected. Follow the Lighting (or Operating) Instructions. Adjust thermostat so appliance will operate continuously.
5. Test for spillage at the draft hood relief opening
after ve (5) minutes of main burner operation. Use the ame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined
above, return doors, windows, exhaust fans, re
place dampers and any other gas burning appliance to their previous conditions of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or CAN/CSA B149.1 Natural Gas and Propane Installation Code. When resizing any portion of the common venting system, the common venting system should be resized to ap­proach the minimum size as determined using the appropriate tables in Part 11 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1 Natural Gas and Propane Installation Code.
B. General Guidelines
1. Vent system installation must be in accordance with Part 7, Venting of Equipment of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Section 7, Venting Systems and Air Supply for Appliances of the CAN/CSA B149.1, Natural Gas and Propane In­stallation Code, or applicable provisions of the local building codes.
2. Contact local building or re ofcials about restric­tions and installation inspection in your area.
3. Refer to the appropriate drawings in this section of
this manual to determine the proper conguration of
venting system. Figures 2 thru 11. The vent system shall be installed in accordance with the instructions listed in this manual.
4. This appliance requires a Special Gas Vent. The product is designed to use AL 29-4C® Stainless Steel or other Stainless Steel material approved for
condensing ue gas applications. The boilers are
shipped with AL 29-4C® vent adapter to directly connect to Heat Fab Saf-T-Vent. The use of alter­nate manufacturer’s venting systems will require adapters and vent terminal. These adapters are not supplied with this unit and should be obtained from the supplier of alternate venting system.
5. The venting system must be installed so as to prevent accumulation of condensate. Horizontal vent pipe must maintain a minimum ¼ inch per foot slope down towards boiler.
a. Do not manifold condensate drains.
b. A common condensate pump/sump may be used.
Run separate condensate piping from each vent drain to the sump. A common drain may be used to discharge condensate from the sump.
Consult pump/sump manufacturer for compat-
ibility of materials of construction with ue gas
condensate. If a common pump/sump is used, individual vent drain lines must be connected such that one drain pipe cannot back feed into another vent drain.
c. Consult local authorities regarding disposal of
ue gas condensate into public waste water sys­tem. Some jurisdictions require that the conden­sate be buffered before discharge. this buffering is commonly achieved by draining the conden­sate through a limestone bed. Consult chemical treatment company for buffering systems.
6. Use noncombustible ¾ inch pipe strap to support horizontal runs and maintain vent location and slope while preventing sags in pipe. Do not restrict thermal expansion or movement of vent system.
Maximum support spacing is ve (5) feet. Do not
penetrate any part of the vent system with fasteners.
7. Vent length restrictions are based on equivalent length of vent/air pipe (total length of straight
pipe plus equivalent length of ttings). Maximum
vent/air lengths are listed in Table 1. Do not exceed
Table 1: Vent & Air Intake Length
Vent/Air Intake
Pipe Dia.Min Max
Boiler Model
SOL-300 5 50 4
SOL-500 5 78 6
SOL-750 5 50 8
SOL-1000 5 50 8
SOL-1250 5 50 10
SOL-1500 5 50 10
maximum vent/air intake lengths. Refer to vent manufacturer’s recommendations for the equivalent
length of ttings.
8. Provide and maintain vent pipe minimum clearances to combustible materials. Vent pipe minimum clear­ance to combustible material is four (4) inches when vent is installed in a fully enclosed (chase) applica­tion or three (3) inches when vent is installed with at least one side open, similar to a joist bay applica­tion. Use double wall thimble when penetrating a combustible wall. Some examples of Wall thimble manufactures are American Metal Products, Hart & Cooley, and Metal Fab.
9. Do not install venting system components on the ex-
terior of the building except as specically required
by these instructions. The vent termination location is restricted as follows:
a. The minimum distance from adjacent public
walkways, adjacent buildings, openable win dows and building openings shall not be less
than those values specied in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/ CSA B149.1, Natural Gas and Propane Installa tion Code.
b. Minimum twelve (12) inches above grade plus
normally expected snow accumulation level, or seven (7) feet above grade if located adjacent to public walkway. Do not install over public walk­way where local experience indicates appliance
ue gas vapor or condensate creates a nuisance
or hazard.
c. Minimum three (3) feet above any forced air
inlet located within ten (10) feet.
d. Power Vent - Minimum four (4) feet below, four
(4) feet horizontally from, or four (4) feet above any door, window, or gravity air inlet.
ft. ft. In.
9
e. Minimum of four (4) feet horizontally from, and
in no case above or below, unless a 4 foot hori­zontal distance is maintained from electric me­ters, gas meters, regulators and relief equipment. This distance may be reduced if equipment is protected from damage due to condensation or vapor by enclosure, overhangs, etc.
f. Minimum twelve (12) inches from overhang or
corner of building.
g. The vent termination shall be located such that
no damage to building materials will occur from
Figure 2: Vent Therminal Location
NOTICE
Cut must be square with pipe and led or
sanded smooth before joining. Carefully ensure roundness of cut pipe by hand with gloves before installing. Seal joint with RTV
specied in this manual.
ue gasses degradation.
10. Enclose vent passing through occupied or unoccu pied spaces above the boiler with material having a
re resistance rating of at least equal to the rating of the adjoining oor or ceiling. Maintain minimum
clearances to combustible materials. See page 4.
11. Plan venting system to avoid possible contact with plumbing or electrical wires. Start at vent connector on top of boiler and work towards vent terminal.
12. Once a vent pipe manufacturer and system is cho­sen never mix and match vent systems.
13. Field Supplied Vent Terminations (One per boiler) a. Horizontal - Use Saf-T Vent mitered termination with screen or equivalent
b. Vertical - Use Saf-T Vent rain cap or equivalent
C. Supplemental Vent Terminal Location In-
structions (Massachusetts Code Only)
The Commonwealth of Massachusetts requires compli-
ance with regulation 248 CMR 4.00 and 5.00 for instal­lation of side-wall vented gas appliances as follows:
(a) For all side wall horizontally vented gas fueled equip-
ment installed in every dwelling, building or structure used in whole or in part for residential purposes, includ­ing those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above nished grade in the area of the
venting, including but not limited to decks and porches,
the following requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE DETEC­TORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing
plumber or gastter shall observe that a hard wired
carbon monoxide detector with an alarm and battery
back-up is installed on the oor level where the gas
equipment is to be installed. In addition, the install-
ing plumber or gastter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building, or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the ser­vices of qualied licensed professionals for the installa­tion of hard wired carbon monoxide detectors.
a. In the even that the side wall horizontally vented
gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next
adjacent oor level.
b. In the event that the requirements of this subdivision
can not be met at the time of completion of installa­tion, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, how­ever, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in ac­cordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certi-
ed.
3. SIGNAGE. A metal or plastic identication plate shall be
permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizon­tally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW,
KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection,
10
the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt
from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equip­ment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS
EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufac­turer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the vent­ing system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS
EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not
provide the parts for venting the ue gasses, but identi­es “special venting systems”, the following require­ments shall be satised by the manufacturer:
1. The referenced “special venting system” instruc­tions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instruc­tions shall remain with the appliance or equipment at
the completion of the installation.
D. Separate Horizontal Venting System. See
Figures 3, 4 and 5.
1. Vent Piping
a. Do not exceed maximum vent/air intake
lengths. Refer to Table 1.
b. Recommended horizontal installation consists
of vent being sloped down ¼ inch per foot toward boiler.
c. Use appropriate designed thimbles when
passing through combustible walls (thimble use optional for noncombustible walls). Insert thimble through wall from outside. Secure
outside ange to wall with nails or screws, and
seal ID, OD and vent holes with sealant
material. Install inside ange to inside wall,
secure with nails or screws, and seal with sealant material.
d. For noncombustible wall application when thimble is not used, size opening such that bell with locking band attached cannot pass through. e. Join vent terminal to vent pipe. Locate vent pipe such that vent terminal is between six (6) inches and twenty-four (24) inches from wall when joined to inside vent piping. See Figure 3 or 4. f. Insert vent pipe through thimble/opening from outside and join to vent system. Apply seal­ ant between vent pipe and opening/thimble to provide weathertight seal.
2. Side Vent Installation. See gure 5.
a. Horizontal vent/air intake runs with no vertical rise in piping allowed. b. Do not exceed maximum vent/air intake lengths. Refer to Table 1. c. Recommended Horizontal Installation only consists of vent/air intake sloped down 1/4 inch per foot toward termination. d. Thimbles, same as “C” above in section D.1 e. same as “D” above in section D.1 f. same as “E” above in section D.1 g. same as “F” above in section D.1
Figure 3: Side Top Vent
11
12
Figure 4: Recommended Separate Horizontal - Vent/Air Intake Installation
Figure 5: Side Vent
13
E. Optional Separate Horizontal Vent Terminal Mounting – See Figure 6
1. Do not exceed maximum vent/air intake lengths.
Refer to Table 1.
2. This installation will allow a maximum of ve (5)
feet vertical exterior run of the vent/air intake piping to be installed on separate horizontal venting and indoor air horizontal venting.
Note: Exterior run to be included in equivalent vent/
air intake lengths.
3. Install vent piping.
a. Install vent piping for desired venting system.
Refer to specic section for details for vent pipe
installation.
b. After penetrating wall/thimble, install a 90°
elbow so that elbow leg is in the up direction.
c. Install maximum of ve (5) feet of vent pipe.
Refer to Sections C through E for proper proce-
dures for joining vent pipe and ttings.
d. At top of vent pipe length install a 90° elbow so
that elbow leg is opposite the building’s exterior surface.
e. Install 45° elbow to upper 90° elbow so that leg
of 45° is in down direction (see Figure 6). If not using indoor air, proceed to Step f.
f. Install horizontal vent terminal.
g. Brace piping if required.
4. Air Intake Piping (not required for indoor air).
a. Install air intake piping for desired venting sys-
tem. Refer to specic section for details for air
intake installation.
b. After penetrating wall, install a corrosion re-
sistant 90o elbow so that elbow leg is in the up direction.
c. Install maximum of ve (5) feet of corrosion
resistant air intake pipe.
d. At top of air intake pipe install air intake termi
nal (provided with boiler).
e. Brace piping if required.
-
14
Figure 6: Optional Indoor Air – Vent Terminal Installation
F. Conventional Venting (Negative Draft) – See Figure 7
a. The minimum chimney height is 15 feet.
b. The chimney must be protected from down
drafts, rain and debris by using a chimney cap or star.
c. Start installing vent at vent cap and continue
installation toward the boiler.
d. The ue connector and chimney ue diameter
may need to be increased or decreased depend ing on the dimensions of the boiler. Consult the National Fuel Gas Code or Local Codes for siz-
ing. Boiler input, ue connector lateral distance and chimney height affect the ue connector or chimney ue diameters.
e. A double acting barometric damper with integral
ue spillage interlock switch must be used when
the boiler is vented conventionally.
f. The chimney and ue connector must be sized
and congured to provide a minimum - 0.04 inch
w.c. draft at the vent outlet of the boiler.
g. Maintain a minimum vertical pitch of one (1)
inch in four (4) feet of vent connector run.
G. Air Intake Piping - See Figure 4 & 8
1. Locate air intake termination on the same wall as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler may be installed with verti­cal venting and sidewall combustion air inlet or vice versa, if installation conditions do not allow alternate arrangement.
2. Do not exceed maximum air intake length. See Table 1.
3. Use single wall metal pipe and ttings or thin wall PVC
available at most heating distributors.
4. Air intake termination must be located: Horizontal - At least twelve (12) inches above grade plus the expected snow accumulation.
5. Start at collar on burner enclosure (inside boiler jacket) and work towards the air intake terminal.
6. Maintain minimum of 1/4 inch per foot slope on horizontal runs. Slope towards air inlet terminal when possible. If not, slope towards boiler.
7. The air intake pipe must be adequately supported with
straps or supports no less than ve (5) feet apart on
horizontal runs. The complete air intake piping system must be rigid and able to withstand minor impacts with­out collapse.
8. Inlet air pipe penetration: Horizontal - Size wall pen­etration to allow easy insertion of air inlet piping. Seal around pipe with sealant to form weathertight exterior joint.
9. Seal all joints airtight, using silicone caulk or self-adhe­sive aluminum tape.
10. Install Air Intake Terminal.
Figure 7: Conventional Venting (Negative Draft)
15
16
SEE TABLE 1.
Figure 8: Separate Horizontal – Vent/Air Intake Terminal Conguration
H. Separate Vertical Venting System - See Figures 9, 10, and 11.
Vertical Venting
1. Do not exceed maximum vent lengths. Refer to Table 1.
2. Slope horizontal runs minimum ¼ inch per foot down towards boiler.
3. Install re stops where vent passes through oors, ceilings or framed walls. The re stop must close
the opening between the vent pipe and the structure. Fire stop manufacturers are Air-Jet, American Metal Products, Metal-Fab, and Simpson Dura-Vent.
4. Whenever possible, install vent straight through the roof. Refer to Figure 9 if offset is necessary. Main­tain minimum clearance to combustible materials.
5. Install Vent Terminal.
a. Size roof opening to maintain minimum clear-
ance from combustible materials.
b. Extend vent pipe to maintain minimum vertical
and horizontal distance of twelve (12) inches from roof surface. Allow additional vertical dis­tance for expected snow accumulation. Provide brace as required. Refer to Figure 11.
c. Vertical venting requires use of the roof ashing
and storm collar to prevent moisture from enter­ing the structure.
d. Install storm collar on vent pipe immediately
above ashing. Apply Dow Corning Silastic 732
RTV Sealant between vent pipe and storm collar to provide weathertight seal.
e. Attach vent terminal.
Vertical Air Intake Piping
1. Do not exceed maximum air intake length. Refer to Table 1.
2. Locate air intake termination on the same roof loca tion as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler may be installed with vertical venting and sidewall combus­tion air inlet or vica versa, if installation conditions do not allow alternate arrangement.
-
8. Inlet air pipe penetration:
9. Seal all joints airtight, using silicone caulk or self - adhesive aluminum tape.
10. Install Air Intake Terminal: Vertical - Insert intake piping into intake terminal collar. Secure terminal to intake piping and seal joint with silicone caulk.
with straps or supports no less than ve (5) feet
apart on horizontal runs. The complete air intake piping system must be rigid and able to withstand minor impacts without collapse.
Vertical - Size roof opening to allow easy insertion of inlet piping and allow proper installation of ash­ing and storm collar.
a. Use appropriately designed vent ashing when
passing through roofs. Follow ashing manufac-
turers’ instructions for installation procedures. Flashing manufacturers are Air-Jet, American Metal Products, Metal Fab, and Simpson Dura­Vent.
b. Extend air intake pipe to maintain minimum
vertical and horizontal distance of twelve (12) inches from roof surface. Allow additional verti­cal distance for expected snow accumulation. Provide brace as required. Refer to Figure 11.
c. Vertical air intake requires ashing and a storm
collar to prevent moisture from entering the structure.
d. Install storm collar on air intake pipe immediate-
ly above ashing. Apply Dow Corning Silastic
732 RTV Sealant between air intake pipe and storm collar to provide weathertight seal.
3 Use single wall metal pipe and ttings or thin wall
PVC available at most heating distributors.
4. Air intake termination must be located: Vertical - At least twelve (12) inches above the roof surface plus the expected snow accumulation.
5. Start at collar on burner enclosure (inside boiler jacket) and work towards the air intake terminal.
6. Maintain minimum of 1/4 inch per foot slope on horizontal runs. Slope down towards boiler.
7. The air intake pipe must be adequately supported
17
18
Figure 9: Vertical Vent Installation
Figure 10: Attic Offset
Figure 11: Indoor Air - Horizontal / Vertical Vent Terminal Installation
Extend Vent/Air Intake Piping to maintain minimum vertical (“X”) and minimum horizontal (“Y”) distance of twelve (12) inches from roof surface. Allow additional vertical (“X”) distance for expected snow accumulation.
19
IV. Water Piping and Trim
CAUTION
iii. Oxygen permeable materials in the distribu-
tion system.
Failure to properly pipe boiler may result in improper operation and damage to boiler or structure.
1. Design and install boiler and system piping to prevent oxygen contamination of boiler water and frequent water additions.
CAUTION
Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, and can lead to boiler fail­ure. Thermal Solutions Standard Warranty does not cover problems caused by oxy­gen contamination of boiler water or scale
(lime) build-up cause by frequent addition of
water.
CAUTION
All piping either new or existing must be cleaned with a tri sodium phosphate (TSP) solution to remove mill scale and oils from the system. Failure to do so could result in premature failure of the heat exchanger (not covered by Thermal Solutions warranty.)
CAUTION
On an existing or retrot system, a lter or
strainer must be installed on the system return prior to the boilers.
b. In order to insure long product life, oxygen
sources must be eliminated. This can be accom­plished by taking the following measures:
i. Repairing system leaks to eliminate the need
for addition of make-up water.
ii. Eliminating and/or repairing ttings which
allow oxygen absorption.
iii. Using non-permeable materials in the distri-
bution system.
iv. Isolating the boiler from the system water by
installing a heat exchanger.
vi. Using properly designed and operating air
elimination devices in water piping.
2. Design and install system piping to prevent return water temperatures below 130°F. Refer to Table 2
for boiler ow and pressure drop requirements.
3. Connect system supply and return piping to boiler. Refer to Figure 12. Also consult I=B=R Installation
CAUTION
Return water temperature below 130°F
will cause ue gas condensation inside the
boiler. Flue gas condensate can lead to boiler failure. Thermal Solutions Standard Warranty does not cover problems caused
by ue gas condensation.
WARNING
CAUTION
When using Glycol products, all Glycol
manufacturers’ requirements, including
rust inhibitors, must be adhered. Max 50% Glycol.
a. There are many possible causes of oxygen con-
tamination such as:
i. Addition of excessive make-up water as a
result of system leaks.
ii. Absorption through open tanks and ttings.
20
Supply and return water temperature differ­ences greater than 40°F can lead to boiler failure. Thermal Solutions Standard War­ranty does not cover problems caused by temperature difference greater than 40°F.
and Piping Guides. Maintain ½” minimum distance between water piping and combustible material. Consult Thermal Solutions for unusual system requirements.
4. A pressure relief valve is supplied with each appli­ance. No valve is to be placed between the relief valve and appliance. No reducing coupling or other restriction shall be installed in the discharge line.
See Figure 13.
compatible with local environmental regulations.
a. Pipe the safety relief discharge to a suitable place
for disposal when relief occurs.
b. Do not install reducing couplings for other
restrictive devices in the safety relief discharge line.
c. The safety relief discharge line must allow for
complete drainage of both the valve and line.
5. If the relief valve discharges periodically, this may be due to thermal expansion in a closed water supply system. Contact the water supplier or local plumbing inspector on how to correct this situation. DO NOT PLUG THE RELIEF VALVE.
6. Install the drain valve provided with the appliance at the lowest elevation. See Figure 13.
7. If this boiler is used in connection with refrigera­tion systems, the boiler must be installed so that the chilled medium is piped in parallel with the boiler using appropriate valves to prevent the chilled
medium from entering the boiler, see gure 13A.
Also consult I=B=R Installation and Piping Guides. If this boiler is connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation, the boiler piping must be equipped with ow control valves or other auto­matic means to prevent gravity circulation of boiler water during operation of the cooling system.
8. Install water ow switch. Water ow switch must be located such that water ow disruptions do not
affect switch operation. Maintain maximum practi-
cal straight piping before and after ow switch to
minimize water disruptions. Refer to manufactures’ instructions for proper paddle length.
9. A low water cutoff is required to protect a hot water boiler when any connected heat distributor (radia­tion) is installed below the top of the hot water
boiler (i.e. baseboard on the same oor level as the
boiler). In addition, some jurisdictions require the use of a LWCO with a hot water boiler. If a low water cutoff is required, it must be mounted in the system piping above the boiler. The minimum safe water level of a hot water boiler is just above the highest water containing cavity of the boiler; that is, a hot water boiler must be full of water to operate safely.
10. Oil, grease, and other foreign materials which accumulate in new hot water boilers and a new or reworked system should be boiled out, and then
thoroughly ushed. A local qualied water
treatment chemical specialist is a suggested source for recommendations regarding appropriate chemical compounds and concentrations which are
11. After the boiler and system have been cleaned and
ushed, and before relling the entire system add
appropriate water treatment chemicals, if necessary, to bring the pH between 8.8 and 9.2.
12. If it is required to perform a long term pressure
test of the hydronic system, the boiler should rst
be isolated to avoid a pressure loss due to the escape of air trapped in the boiler.
To perform a long term pressure test including the
boiler, ALL trapped air must rst be removed from
the boiler.
A loss of pressure during such a test, with no
visible water leakage, is an indication that the boiler contained trapped air.
WARNING
Failure to operate the unit with the proper
water ow rate can lead to appliance failure. Always install water ow switch so that the unit stops operating if improper water ow
is present. Safety relief valve discharge piping must
be piped such that the potential of severe burns is eliminated. DO NOT pipe in any area where freezing could occur. DO NOT install any shut-off valves, plugs or caps. Consult Local Codes for proper discharge piping arrangement.
Do not operate boiler with ow rates in excess of the maximum ow rates listed in
Table 2. Boiler tube erosion and pitting will occur. Thermal Solutions Standard War­ranty does not cover problems caused by
excessive water ow rates.
If a high head system pump is installed, as­sure that the boiler relief valve and system piping are capable of operating properly
at the combined pressure of the system ll
pressure plus the pump static head pres­sure.
21
Table 2 - Solaris Boiler Flow and Pressure Drop
20° ΔT (max) 40° ΔT (min)
Boiler
Model
SOL-300 0.8 24 0.5 12 2
SOL-500 6.9 41 1.4 20 2
SOL-750 6.5 64 1.5 32 3
SOL-1000 16.1 85 3.7 43 3
SOL-1250 23.5 106 6.9 53 3
SOL-1500 29.1 128 10.6 64 3
Flow
(GPM) Δ P (ft)
Flow
(GPM)
Supply/Return
Pipe (in. dia.)Δ P (ft)
Figure 12: Water Piping (Single Boiler)
22
Figure 13: Safety & Drain Valve Installation
Figure 13 A: Recommended Piping for Combination
Heating & Cooling (Refrigeration) System
23
Loading...
+ 52 hidden pages