Theben theLuxa P300 KNX WH operation manual

Motion detector theLuxa P300 KNX
theLuxa P300 KNX 1019610 (white) theLuxa P300 KNX 1019611 (black)
theLuxa P300 KNX
Updated: Nov-17 (subject to changes) Page 1 of 65
Motion detector theLuxa P300 KNX
Contents
1 Contents
2 FUNCTIONAL CHARACTERISTICS ................................................................................... 4
2.1 OPERATION .................................................................................................................... 5
2.1.1 Test mode................................................................................................................... 5
2.2 IMPORTANT INFORMATION ABOUT UNLOAD OR RESET. ................................................... 6
3 TECHNICAL DATA .............................................................................................................. 7
4 THE “THELUXA P300” APPLICATION PROGRAMME ................................................... 8
4.1 SELECTION IN THE PRODUCT DATABASE ......................................................................... 8
4.2 COMMUNICATION OBJECTS ............................................................................................ 9
4.2.1 General objects ....................................................................................................... 19
4.2.2 Objects for motion channels C1-C4 ........................................................................ 20
4.2.3 Objects for universal channels C5-C8 .................................................................... 23
4.2.4 Objects for logic modules C9-C12 .......................................................................... 24
4.2.5 Objects for the remote control ................................................................................ 25
4.3 PARAMETERS ............................................................................................................... 26
4.3.1 Parameter pages ..................................................................................................... 26
4.3.2 General parameter page ......................................................................................... 27
4.3.3 Measurement values parameter page ..................................................................... 29
4.3.4 Motion channel C1..C4: Function - parameter pages. ........................................... 31
4.3.5 Brightness settings parameter page ........................................................................ 34
4.3.6 Time settings parameter page ................................................................................. 36
4.3.7 Dimming parameter page........................................................................................ 39
4.3.8 Switching times parameter page ............................................................................. 40
4.3.9 Presets parameter page ........................................................................................... 41
4.3.10 Scenes parameter page........................................................................................ 43
4.3.11 Universal channel C5..C8: function - parameter pages ..................................... 45
4.3.12 Objects parameter page ...................................................................................... 47
4.3.13 Objects parameter page ...................................................................................... 52
4.3.14 Remote control parameter page .......................................................................... 55
5 TYPICAL APPLICATIONS ................................................................................................. 56
5.1 SIMPLE MOTION DETECTOR AS A LIGHT SWITCH ........................................................... 56
5.1.1 Devices: ................................................................................................................... 56
5.1.2 Overview.................................................................................................................. 56
5.1.3 Objects and links ..................................................................................................... 57
5.1.4 Important parameter settings .................................................................................. 57
5.2 CARK PARK LIGHTING WITH TIME SWITC H P ROGRAM ................................................... 58
5.2.1 Devices: ................................................................................................................... 58
5.2.2 Overview.................................................................................................................. 58
5.2.3 Objects and links ..................................................................................................... 59
5.2.4 Important parameter settings .................................................................................. 60
5.3 STAIRC ASE LIGHTING W ITH STANDBY LIGHT ................................................................ 62
5.3.1 Devices: ................................................................................................................... 62
5.3.2 Overview.................................................................................................................. 62
5.3.3 Objects and links ..................................................................................................... 63
5.3.4 Important parameter settings .................................................................................. 64
Updated: Nov-17 (subject to changes) Page 2 of 65
Motion detector theLuxa P300 KNX
6 APPENDIX .......................................................................................................................... 65
6.1 CONVERSION OF PERCENTAGES TO HEXADECIMA L AN D D ECIMAL VALUES ................... 65
Updated: Nov-17 (subject to changes) Page 3 of 65
Motion detector theLuxa P300 KNX

2 Functional characteristics

Motion detector (PIR)
Automatic lighting control depending on presence
and brightness
Can be integrated into KNX building system technology
For outdoor use
For wall and ceiling installation
• Integrated temperature sensor
For larger, commercial outdoor properties such as
administration buildings, hotels, schools, underground car parks and warehouses
Easy to program with ETS software for KNX
Adjustable brightness switching value and time delay
• Sensitivity can be reduced
Area limitation via cover clip
• Mixed light measurement
Teach-in of current brightness value
Pulse function
Test function for checking the detection area
Installation on flush -mounted box (60 mm) possible
Single-handed plug-in installation
Instant start-up possible thanks to presetting
• Protected adjusters
Spacer frame and corner installation bracket included in the scope of supply
Updated: Nov-17 (subject to changes) Page 4 of 65
Motion detector theLuxa P300 KNX

2.1 Operation

2.1.1 Test mode

The test mode is used to test the detection area and to restrict it if necessary.
The test mode can be activated via a telegram (test mode object), or via the time potentiometer (Min).
Perform walking test:
Set the time potentiometer (Min) to test. The motion detector now only reacts to movements (independent of brightness). Walk through the detection area at a right angle. After the motion detector has detected a movement, it switches on for 2 s. The LED for test lights up. Pay attention to the direction of motion during the test.
Figure 1
Important:
If the device has been discharged using ETS, the red LED will remain lit up constantly to report this.
Updated: Nov-17 (subject to changes) Page 5 of 65
Motion detector theLuxa P300 KNX

2.2 Important information about unload or reset.

Any error notification that appears following download can be ignored, provided that the LED
remains lit as described above.
The remote control does not work after downloading the application.
Following (bus) reset the device initially always sends 0 to the movement object (C1 .. C4).
If motion has been detected, 1 is sent immediately.
Until the first download of an application the device transmits to the following group addresses:
- 15/1/0: Obj. 6 (C1 motion)
- 15/1/1: Obj. 22 (C2 motion)
- 15/1/2: Obj. 38 (C3 motion)
- 15/1/3: Obj. 54 (C4 motion)
- 15/2/0: Obj. 2 (brightness value)
- 15/2/1: Obj. 3 (Temperature value)
- 15/3/0: Obj. 116 (Software version)
Updated: Nov-17 (subject to changes) Page 6 of 65
Motion detector theLuxa P300 KNX
Brightness setting range
1 – 3000 lx
Type of installation
Wall and ceiling installation
Lighting time delay
1 s – 60 min.
Protection class
III
Protection rating
IP 55

3 Technical data

Operating vo ltage KNX Bus current < 10 mA
Bus voltage
Detection angle Creep under protection
Type of light measurement Ambient temperature
300° Ø 6 m
Mixed light measurement
-25 °C … +45 °C
Updated: Nov-17 (subject to changes) Page 7 of 65
Motion detector theLuxa P300 KNX
Manufacturer
Theben AG
Product family
Physical sensors
Product type
Motion detector
Program name
theLuxa P300 KNX
Number of communication objects:
116
Number of group addresses:
254
Number of associations:
254

4 The “theLuxa P300” application programme

4.1 Selection in the product database

The ETS database can be found on our website: www.theben.de/en/downloads_en
Table 1
Updated: Nov-17 (subject to changes) Page 8 of 65
Motion detector theLuxa P300 KNX
3 byte
10.001
1 bit
1.001
2 byte
9.004
2 byte
9.001
1 bit
1.001
1 byte
5.004
1 bit
1 byte
5.001
2 byte
9.004
1 bit
2 byte
9.004
1 bit
1.001
1 bit
1.003
2 byte
2 byte
7.005
1 bit
1.003
1 bit
1 bit
1.003
1 bit
1.001
1 bit

4.2 Communication objects

Table 2
No. Name Function Length Flags
0 Time Receive
1 Time query Send
2 Brightness value Physical value
3 Temperature value Physical value
4 Dismounting Report
5 Sensitivity Receive
6 C1 Motion Switching
7 C1 Dimming Dimming value
8 C1 Brightness threshold Receive
9 C1 Brightness threshold Teach in
10 C1 Alt. Brightness threshold Receive
1.001
1.001
C R W -
C R - T
C R - T
C R - T
C R - T
C R W -
C R - T
C R - T
C R W -
C R W -
C R W -
11 C1 Alt. Brightness threshold Teach in
12 C1 Alt. Brightness threshold Selection
13 C1 Time delay Receive
14 C1 Alternative time delay Receive
15 C1 Alternative time delay Selection
Block = 0
16 C1 Block
Block = 1
Duration = 0
17 C1 Perm ON
Duration = 1
7.005
1.003
1.001
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
Updated: Nov-17 (subject to changes) Page 9 of 65
Motion detector theLuxa P300 KNX
1 bit
1.001
1 bit
1 bit
1.003
2 byte
9.004
1 byte
17.001
1 bit
1.001
1 byte
2 byte
9.004
1 bit
1.001
2 byte
9.004
1 bit
1.001
1 bit
2 byte
7.005
2 byte
7.005
1 bit
1.003
1 bit
1.003
1 bit
1 bit
1.001
1 bit
1.001
1 bit
1.001
1 bit
1.001
1 bit
Continuation:
No. Name Function Length Flags
Send
18 C1 Parallel switching
Send / Receive
19 C1 Test mode 1= active, 0 = not active
20 C1 External brightness value Receive
21 C1 Scene Receive
22 C2 Motion Switching
23 C2 Dimming Dimming value
24 C2 Brightness threshold Receive
25 C2 Brightness threshold Teach in
26 C2 Alt. Brightness threshold Receive
27 C2 Alt. Brightness threshold Teach in
1.001
5.001
C R - T
C R W T
C R W -
C R W -
C R W -
C R - T
C R - T
C R W -
C R W -
C R W -
C R W -
28 C2 Alt. Brightness threshold Selection
29 C2 Time delay Receive
30 C2 Alternative time delay Receive
31 C2 Alternative time delay Selection
Block = 0
32 C2 Block
Block = 1
Duration = 0
33 C2 Perm ON
Duration = 1
Send
34 C2 Parallel switching
Send / Receive
35 C2 Test mode 1= active, 0 = not active
1.003
1.003
1.003
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R - T
C R W T
C R W -
Updated: Nov-17 (subject to changes) Page 10 of 65
Motion detector theLuxa P300 KNX
2 byte
9.004
1 byte
17.001
1 bit
1.001
1 byte
5.001
2 byte
1 bit
1.001
2 byte
9.004
1 bit
1 bit
1.003
2 byte
7.005
2 byte
1 bit
1.003
1 bit
1.003
1 bit
1 bit
1.001
1 bit
1.001
1 bit
1.001
1 bit
1.001
1 bit
1.003
2 byte
9.004
1 byte
17.001
1 bit
Continuation:
No. Name Function Length Flags
36 C2 External brightness value Receive
37 C2 Scene Receive
38 C3 Motion Switching
39 C3 Dimming Dimming value
40 C3 Brightness threshold Receive
41 C3 Brightness threshold Teach in
42 C3 Alt. Brightness threshold Receive
43 C3 Alt. Brightness threshold Teach in
44 C3 Alt. Brightness threshold Selection
45 C3 Time delay Receive
46 C3 Alternative time delay Receive
9.004
1.001
7.005
C R W -
C R W -
C R - T
C R - T
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
47 C3 Alternative time delay Selection
Block = 0
48 C3 Block
Block = 1
Duration = 0
49 C3 Perm ON
Duration = 1
Send
50 C3 Parallel switching
Send / Receive
51 C3 Test mode 1= active, 0 = not active
52 C3 External brightness value Receive
53 C3 Scene Receive
54 C4 Motion Switching
1.003
1.001
C R W -
C R W -
C R W -
C R W -
C R W -
C R - T
C R W T
C R W -
C R W -
C R W -
C R - T
Updated: Nov-17 (subject to changes) Page 11 of 65
Motion detector theLuxa P300 KNX
Continuation:
No. Name Function Length Flags
55 C4 Dimming Dimming value
56 C4 Brightness threshold Receive
57 C4 Brightness threshold Teach in
58 C4 Alt. Brightness threshold Receive
59 C4 Alt. Brightness threshold Teach in
60 C4 Alt. Brightness threshold Selection
61 C4 Time delay Receive
62 C4 Alternative time delay Receive
63 C4 Alternative time delay Selection
Block = 0
64 C4 Block
Block = 1
Duration = 0
65 C4 Perm ON
Duration = 1
Send
66 C4 Parallel switching
Send / Receive
67 C4 Test mode 1= active, 0 = not active
68 C4 External brightness value Receive
69 C4 Scene Receive
Switching
70 C5.1 Universal channel
Priority
Valuator
1 byte
5.001
2 byte
9.004 1 bit
1.001
2 byte
9.004 1 bit
1.001 1 bit
1.003
2 byte
7.005
2 byte
7.005 1 bit
1.003 1 bit
1.003 1 bit
1.003 1 bit
1.001 1 bit
1.001 1 bit
1.001 1 bit
1.001 1 bit
1.003
2 byte
9.004
1 byte
17.001 1 bit
1.001 2 bit
2.001
1 byte
5.010
C R - T
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R - T
C R W T
C R W -
C R W -
C R W -
C R - T
C R - T
C R - T
Updated: Nov-17 (subject to changes) Page 12 of 65
Motion detector theLuxa P300 KNX
Continuation:
No. Name Function Length Flags
71 C5.2 Universal channel
72 C5 lock
73 C5 Brightness threshold
74 C6.1 Universal channel
Switching
Priority
Valuator
Block = 0
Block = 1
check
Specify/check
Switching
Priority
1 bit
1.001 2 bit
2.001
1 byte
5.010 1 bit
1.003 1 bit
1.003
2 byte
9.004
2 byte
9.004 1 bit
1.001 2 bit
2.001
C R - T
C R - T
C R - T
C R W -
C R W -
C R - T
C R W T
C R - T
C R - T
75 C6.2 Universal channel
76 C6 lock
77 C6 Brightness threshold
Valuator
Switching
Priority
Valuator
Block = 0
Block = 1
check
Specify/check
1 byte
5.010 1 bit
1.001 2 bit
2.001
1 byte
5.010 1 bit
1.003 1 bit
1.003
2 byte
9.004
2 byte
9.004
C R - T
C R - T
C R - T
C R - T
C R W -
C R W -
C R - T
C R W T
Updated: Nov-17 (subject to changes) Page 13 of 65
Motion detector theLuxa P300 KNX
Continuation:
No. Name Function Length Flags
78 C7.1 Universal channel
79 C7.2 Universal channel
80 C7 lock
81 C7 Brightness threshold
Switching
Priority
Valuator
Switching
Priority
Valuator
Block = 0
Block = 1
check
Specify/check
1 bit
1.001 2 bit
2.001
1 byte
5.010 1 bit
1.001 2 bit
2.001
1 byte
5.010 1 bit
1.003 1 bit
1.003
2 byte
9.004
2 byte
9.004
C R - T
C R - T
C R - T
C R - T
C R - T
C R - T
C R W -
C R W -
C R - T
C R W T
82 C8.1 Universal channel
83 C8.2 Universal channel
84 C8 lock
Switching
Priority
Valuator
Switching
Priority
Valuator
Block = 0
Block = 1
1 bit
1.001 2 bit
2.001
1 byte
5.010 1 bit
1.001 2 bit
2.001
1 byte
5.010 1 bit
1.003 1 bit
1.003
C R - T
C R - T
C R - T
C R - T
C R - T
C R - T
C R W -
C R W -
Updated: Nov-17 (subject to changes) Page 14 of 65
Motion detector theLuxa P300 KNX
Continuation:
No. Name Function Length Flags
85 C8 Brightness threshold
86 C9 Logic module
87 C9 Logic module
88 C9 Logic module
check
Specify/check
Logic input 1 in OR gate
Logic input 1 in AND gate
Logic input 1 in XOR gate
Logic input 2 in OR gate
Logic input 2 in AND gate
Logic input 2 in XOR gate
Logic input 3 in OR gate
Logic input 3 in AND gate
2 byte
9.004
2 byte
9.004 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002
C R - T
C R W T
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
89 C9 Logic module
90 C9 Logic module
91 C9. 1 Logic module
92 C9. 2 Logic module
Logic input 4 in OR gate
Logic input 4 in AND gate
Block = 0
Block = 1
Switching
Priority
Valuator
Switching
Priority
Valuator
1 bit
1.002 1 bit
1.002 1 bit
1.003 1 bit
1.003 1 bit
1.001 2 bit
2.001
1 byte
5.010 1 bit
1.001 2 bit
2.001
1 byte
5.010
C R W -
C R W -
C R W -
C R W -
C R - T
C R - T
C R - T
C R - T
C R - T
C R - T
Updated: Nov-17 (subject to changes) Page 15 of 65
Motion detector theLuxa P300 KNX
Continuation:
No. Name Function Length Flags
93 C10 Logic module
94 C10 Logic module
95 C10 Logic module
96 C10 Logic module
Logic input 1 in OR gate
Logic input 1 in AND gate
Logic input 1 in XOR gate
Logic input 2 in OR gate
Logic input 2 in AND gate
Logic input 2 in XOR gate
Logic input 3 in OR gate
Logic input 3 in AND gate
Logic input 4 in OR gate
Logic input 4 in AND gate
1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
97 C10 Logic module
98 C10. 1 Logic module
99 C10. 2 Logic module
100 C11 Logic module
Block = 0
Block = 1
Switching
Priority
Valuator
Switching
Priority
Valuator
Logic input 1 in OR gate
Logic input 1 in AND gate
1 bit
1.003 1 bit
1.003 1 bit
1.001 2 bit
2.001
1 byte
5.010 1 bit
1.001 2 bit
2.001
1 byte
5.010 1 bit
1.002 1 bit
1.002
C R W -
C R W -
C R - T
C R - T
C R - T
C R - T
C R - T
C R - T
C R W -
C R W -
Updated: Nov-17 (subject to changes) Page 16 of 65
Logic input 1 in XOR gate
1 bit
1.002
C R W -
Motion detector theLuxa P300 KNX
Continuation:
No. Name Function Length Flags
101 C11 Logic module
102 C11 Logic module
103 C11 Logic module
104 C11 Logic module
Logic input 2 in OR gate
Logic input 2 in AND gate
Logic input 2 in XOR gate
Logic input 3 in OR gate
Logic input 3 in AND gate
Logic input 4 in OR gate
Logic input 4 in AND gate
Block = 0
Block = 1
Switching
1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.003 1 bit
1.003 1 bit
1.001
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R - T
105 C11. 1 Logic module
106 C11. 2 Logic module
107 C12 Logic module
108 C12 Logic module
Priority
Valuator
Switching
Priority
Valuator
Logic input 1 in OR gate
Logic input 1 in AND gate
Logic input 1 in XOR gate
Logic input 2 in OR gate
Logic input 2 in AND gate
2 bit
2.001
1 byte
5.010 1 bit
1.001 2 bit
2.001
1 byte
5.010 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002
C R - T
C R - T
C R - T
C R - T
C R - T
C R W -
C R W -
C R W -
C R W -
C R W -
Updated: Nov-17 (subject to changes) Page 17 of 65
Logic input 2 in XOR gate
1 bit
1.002
C R W -
Motion detector theLuxa P300 KNX
Continuation:
No. Name Function Length Flags
109 C12 Logic module
110 C12 Logic module
111 C12 Logic module
112 C12. 1 Logic module
Logic input 3 in OR gate
Logic input 3 in AND gate
Logic input 4 in OR gate
Logic input 4 in AND gate
Block = 0
Block = 1
Switching
Priority
Valuator
Switching
1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.002 1 bit
1.003 1 bit
1.003 1 bit
1.001 2 bit
2.001
1 byte
5.010 1 bit
1.001
C R W -
C R W -
C R W -
C R W -
C R W -
C R W -
C R - T
C R - T
C R - T
C R - T
113 C12. 2 Logic module
114 Remote control button 1 Send scene
115 Remote control button 2 Send scene
116 Software version Send
Priority
Valuator
2 bit
2.001
1 byte
5.010
1 byte
17.001 1 byte
17.001
14 byte
16.001
C R - T
C R - T
C R - T
C R - T
C R - T
Updated: Nov-17 (subject to changes) Page 18 of 65
Motion detector theLuxa P300 KNX
Low
Medium
High
0..33
34..66
67..100
Code
Meaning
xx.yy
Version of the application as hexadecimal number with dividing point.

4.2.1 General objects

Object 0 "Receive time"
Receives time from bus for setting the internal real time clock.
Object 1 "Send time query"
Object sends time query to bus clock to receive the current time.
Object 2 "Brightness value"
Sends the current brightness value.
Object 3 "Temperature value"
Sends the current temperature value, depending on configuration, in case of a change and/or cyclically.
Object 4 „Dismounting“
Permanently sends cyclical OFF telegrams. The absence of cyclical telegrams might indicate an unauthorised removal of the device.
Object 5 "Sensitivity"
Overwrites the parameter as well as the potentiometer setting for the detection sensitivity of the motion sensor.
Object 116 „Software version“
For diagnostic purposes only.
Sends the software version of the device after reset or download.
Format: Vxx.yy
Example: V00.0A
Updated: Nov-17 (subject to changes) Page 19 of 65
= Version 0.10d
h
Motion detector theLuxa P300 KNX

4.2.2 Objects for motion channels C1-C4

Object 6 „C1 Motion“
Reports a detected movement. Sends a switch telegram. Available only with Type of lighting = Switching.
Object 7 „C1 Dimming“
Sends the configured dimming values (see Dimming parameter page).
Object 8 "Receive C1 brightness threshold"
This object can be used to change the configured brightness threshold of the channel via bus telegram at any time.
Object 9 "Teach in C1 brightness threshold"
After receiving a 1 by the object, the current brightness value is applied as threshold.
Objekt 10 „Receive C1 Alt. brightness threshold"
This object can be used to change the configured alternative brightness threshold of the channel via bus telegram at any time.
Objekt 11 „Teach in C1 Alt. brightness threshold"
After receiving a 1 by the object, the current brightness value is applied as alternative threshold.
Objekt 12 „SELECT C1 Alt. Brightness threshold"
Activates the alternative brightness threshold.
Object 13 „Receive C1 time delay“
This object can be used to change the configured time delay of the channel via bus telegram at any time.
Updated: Nov-17 (subject to changes) Page 20 of 65
Loading...
+ 45 hidden pages