Installation manual
Presence detector
compact passage KNX
Table of contents
1. Safety ..................................................47
2. Function and performance characteristics. . . . . . . . . . . . . . . . . . . . . . . 48
3. Fitting and connection ......................................50
4. Start-up procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
5. Setting the Brightness Value ................................. 56
6. Test Operation ............................................ 57
7. Examples ................................................58
8. Technical specications ..................................... 61
9. Warranty declaration .......................................62
10. Troubleshooting .......................................... 63
4747
GB
Thank you for purchasing an Theben HTS presence detector and putting your trust in us.
1. Safety
Familiarise yourself with the compact passage KNX before assembly and start-up by reading this operating instructions.
IMPORTANT!
The unit requires no maintenance. Opening the unit or inserting foreign bodies into it will invalidate the warranty.
Proper use
The presence detector serves exclusively for the purpose contractually ag­reed between the manufacturer and the user. Any other use is regarded as improper. The manufacturer is not responsible for any resulting damage.
4848
2. Function and performance characteristics
The presence detector compact passage KNX detects persons within a corri­dor. Simultaneously, its light sensor measures the brightness in the room and compares it to the pre-set brightness threshold.
Control of one or two lighting groups
Switching mode or constant light control
Semi or fully automatic operation
Presence output with switch-on/off delay time
Surveillance mode with manipulation protection
Brightness value output in Lux
Parallel circuit operation of several detectors (Master-Slave, Master-
Master) without logic component
Mixed light measurement suitable for uorescent lamps (FL/PL/ESL),
halogen/incandescent lamps and LEDs
Mechanical safety locking
Management remote control „Sendo Pro 868 A (optional)
4949
GB
2.1 Switching Mode
The lighting switches on in case of presence and insufcient brightness, and off in case of absence or sufcient brightness
2.2 Constant Light Control Mode
In Constant Light Control mode, the brightness is constantly maintained at th pre-set value. It can be started fully automatically or manually using the push button or remote control. Manually switching off, dimming or changing the settings stops control mode for the duration of the presence.
5050
M'height radial (r) tangential (t) 2,0 m 56 m
2
16m ± 1,5m x 3,5m 56 m
2
16m ± 1,5m x 3,5m
2,5 m 72 m
2
18m ± 1,5m x 4,0m 88 m
2
22m ± 1,5m x 4,0m
3,0 m 90 m
2
20m ± 1,5m x 4,5m 150 m
2
30m ± 1,5m x 4,5m
3,5 m 100 m
2
20m ± 1,5m x 5,0m 150 m
2
30m ± 1,5m x 5,0m
4,0 m 100 m
2
20m ± 2,0m x 5,0m 150 m
2
30m ± 2,0m x 5,0m
4,5 m 100 m
2
20m ± 2,0m x 5,0m 150 m
2
30m ± 2,0m x 5,0m
5,0 m 100 m
2
20m ± 2,5m x 5,0m 150 m
2
30m ± 2,5m x 5,0m
6,0 m 100 m
2
20m ± 2,5m x 5,0m 150 m
2
30m ± 2,5m x 5,0m
3. Fitting and connection
3.1 Presence detection
The ideal mounting height is 2 m – 3,5 m. The sensitivity of the detector decreases with increasing mounting height.
The detection ranges of multiple detectors should overlap in their fringe zone. Ensure the horizontal installation of the detector.
At installation heights between 3.5 and 6 m, the extent and distance between the active and passive zones increase.
5151
GB
Detection range (mounting height 3,0 m)
Please note: because of the virtually horizontal detection of compact passa-
ge to both directions, the detection range of tangential (t) movements of per­sons is different to the range of radial (r) movements towards the detector.
3.2 Light measurement
The detector measures articial light and daylight reected directly
beneath the detector (beam width approx. ± 30°). The mounting loca­tion is used as the reference for the lighting levels.
Switching
Direct light inuences the light measurement. Avoidplacingoorlamps or
suspendedlightingdirectlybelow the detector.
t
15m 12 10 8 6 4 2 0 2 4 6 8 10 12 15
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
2
1
0
1
2
r
Lux
0
3
2
1