Ausgangsstrom / output current
Absicherung PRI / fuse PRI
Absicherung SEC / fuse SEC
Schutzklasse / protection class
Schutzgrad /degree of protection
Netzschalter / main switch
230V 50/60Hz
IEC-Dose / socket
1,2A 2,35A
230V
IEC-Dose 4-fach
IEC-socket 4-piece
G 5x20 1,6A/T G 5x20 2,5A/TT
G 5x20 1A/T G 5x20 2A/T
IP20 IP20
2-polig, Einschalt-
Strombegrenzer
with current limiter
230V 50/60Hz
IEC-Dose / socket
230V
IEC-Dose 4-fach
IEC-socket 4-piece
1A 2A
I I
2-polig, Einschalt-
Strombegrenzer
with current limiter
Ableitstrom / discharge current
Prüfspannungen / test voltage:
Ansprechwert
Signalisation
Automatischer Testmodus
Tasten für Quittierung und Test
< 0,3mA < 0,3mA
4kV
2kV
2kV
40° C 40° C
Stahlblechgehäuse
metal housing
(B215xH110XT220) (B215xH110XT220)
6,4kg 7,0kg
CE CE
≤ 53kΩ (±5%)
akustisch und optisch
vorhanden
vorhanden
Stahlblechgehäuse
metal housing
≤ 53kΩ (±5%)
akustisch und optisch
4kV
2kV
2kV
vorhanden
vorhanden
Page 3
ERT 230//230/4W ERT 230//230/6W ERT 230//230/10W
230V 50/60Hz
IEC-Dose / socket
4,8A 6,9A 11A
230V
IEC-Dose 4-fachIEC
-socket 4-piece
4A 6A 10A
G 5x20 4A/TT G 5x20 8A/T G 6,3x32 13A/T
G 5x20 4A/T G 5x20 6,3A/T G 5x20 10A/T
I I I
IP20 IP20 IP20
2-polig, Einschalt-
Strombegrenzer
with current limiter
230V 50/60Hz
IEC-Dose / socket
230V
IEC-Dose 8-fach
IEC-socket 8-piece
2-polig, Einschalt-
Strombegrenzer
with current limiter
230V 50/60Hz
IEC-Dose / socket
IEC-Dose 8-fach
IEC-socket 8-piece
2-polig, Einschalt-
Strombegrenzer
with current limiter
230V
< 0,5mA < 0,5mA < 0,5mA
4KV
2kV
2kV
40° C
Stahlblechgehäuse
metal housing
(B250xH125xT310)
10,4kg 17,2kg 26,9kg
CE CE CE
≤ 53kΩ (±5%)
akustisch und optisch
vorhanden
vorhanden
4kV
2kV
2kV
40° C 40° C
Stahlblechgehäuse
metal housing
(B250xH165xT370) (B250xH165xT370)
≤ 53kΩ (±5%)
akustisch und optisch
vorhanden
vorhanden
akustisch und optisch vorhanden
Stahlblechgehäuse
metal housing
≤ 53kΩ (±5%)
4kV
2kV
2kV
vorhanden
Page 4
D
Der Trenntransformator dient zur galvanischen Trennung medizinischer Geräte vom
Leitungsnetz.
Eine mehrfach-Steckdose bzw. Steckdosenleiste ermöglicht den Anschluß von bis zu
8 Verbrauchern, dabei darf die Gesamtleistung der Verbraucher die Ausgangsleistung des Gerätes gem. Typschild nicht überschreiten.
Es dürfen nur die Geräte, die für den medizinischen Einsatz beabsichtigt sind,
angeschlossen werden. Der Anwender ist verpflichtet, für seinen Anwendungsfall die
Richtlinie 93/42/EWG über Medizinprodukte zu beachten.
Der Anschluß des Gerätes erfolgt an eine Schuko-Steckdose. Für den Potentialausgleich befindet sich am Gerät ein Steckverbinder nach DIN 57107/VDE 0107.
Liefert das Gerät keine Ausgangsspannung, ist zunächst die Ausgangssicherung zu
kontrollieren.
Um eine unzulässige Erwärmung des Gerätes zu vermeiden, darf das Gehäuse nicht
abgedeckt werden.
Zur Gewährleistung der Sicherheit für den Anwender sind Eingriffe in das Gerät
durch den Kunden nicht statthaft.
Bei einer erforderlichen Reparatur ist das Gerät an den Hersteller einzusenden.
Achtung! Bei Schäden, die durch Nichtbeachten der Bedienanleitung
entstehen, erlischt der Garantieanspruch.
Technische Änderungen vorbehalten.
Für Ihre Anfragen, auch zu unserem weiteren Produktionsprogramm, stehen wir
Ihnen gern zur Verfügung.
- Ringkern-Sparstelltransformatoren (Ein- und Dreiphasenausführung)
- Trennstelltransformatoren (Ein- und Dreiphasenausführung)
- Laborsparstelltransformatoren
- Stelltransformatoren mit Motorantrieb
- Elektronische Regler
- Netzregler
- Stellgleichrichter
- Schutzstromgeräte für den kathodischen Korrosionsschutz
- Hochspannungsprüfgeräte
- sowie weitere verschiedene Geräte der Stromversorgungstechnik
Page 5
UK
The isolating transformer acts as a galvanic isolation of medical equipment from the
grid-type-network.
The multifold IEC-output-socket and the multiple socket outlets respectively allow a
connection of up to 8 consumer loads. In doing so the total power of the consumer
loads must not exceed the output power of the equipment according to the label.
Only equipment which is approved for medical use can be connected. For the
application the user is committed to consider guideline 93/42/EWG about medical
products.
The connection of the equipment is carried out by a grounding power socket. For the
potential equalisation there is a connection (cp. DIN 57107 / VDE 0107) at the
equipment.
In case the equipment does not deliver any output voltage the output fuse is to be
checked.
To avoid unallowable heating of the equipment, the casing must not be covered.
Page 6
11A
Prise IEC
230V 50/60Hz
ERT 230/230/10W
230V
10A
Prise IEC quadruple
G 6,3x32 12,5A
I
IP20
G 5x20 10A/T
bipolaire, limiteur
de courant affluant
4kV
2kV
< 0,5mA
2kV
For the warranty of security for users tampering with the equipment by consumers
are prohibited.
In case any repairing is necessary the equipment is to be send to the manufacturer.
Attention! Damages caused by non-observance of the instruction manual the
warranty claim expires.
Subject to technical changes.
We are at you disposal for any enquiries as well as for our further production
program.
- single or three phase regulating toroidal autotransformers
- single or three phase phase isolating regulating transformers
- cased regulating transformers
- regulating transformers with motor drive
- electronic servo control system for motor operated variable toroidal transformers
- line voltage regulators
- regulated rectifier
- cathodic protection rectifiers SG
- high voltage tester
- safety insulation transformers according EN 60601-1
40° C
(L250xH165xP370)
carter de tôle d'acier
CE
28kg
Page 7
F
Type
ERT 230/230/1W
ERT 230/230/2W
ERT 230/230/4W
ERT 115/230/WG
ERT 230/230/6W
branchement de jusqu'à 8 consommateurs. Pendant ce processus la puissance
Courant d'entrée
Sortie
Courant de sortie
Fusible PRI
Fusible SEC
Classe de protection
Degré de protection
Interrupteur du réseau
Entrée
Le transformateur de séparation sert à la séparation galvanique des appareils
médicaux du réseau.
Une prise de courant multiple ou panneau de prise de courant permet le
230V 50/60Hz
Prise IEC
1,2A
230V
Prise IEC quadruple
1A
G 5x20 1,6A/T
G 5x20 1A/T
I
IP20
bipolaire, limiteur
de courant affluant
230V 50/60Hz
Prise IEC
2,35A
230V
Prise IEC quadruple
2A
G 5x20 2,5A/TT
G 5x20 2A/T
I
IP20
bipolaire, limiteur
de courant affluant
230V 50/60Hz
Prise IEC
4,8A
230V
Prise IEC quadruple
4A
G 5x20 4A/TT
G 5x20 4A/T
I
IP20
bipolaire, limiteur
de courant affluant
115V 50/60Hz
commutable à
230V 50/60Hz
Prise IEC
max. 13A
115V <-> 230V
Prise IEC quadruple
SEC 230V: 6A
G 6,3x32 13A/T
G 5x20 6,3A/T
I
IP20
bipolaire, limiteur
de courant affluant
230V 50/60Hz
Prise IEC
6,9A
230V
Prise IEC quadruple
6A
G 5x20 8A/T
G 5x20 6,3A/T
I
IP20
bipolaire, limiteur
de courant affluant
Courant de fuite
Tensions d'essai /
PRI-SEC
Écran PRI
Écran SEC
Température
maximum
de l'entourage
Carter
Dimensions [mm]
Poids net
Agrément
< 0,3mA
4kV
2kV
2kV
40° C
carter de tôle d'acier
(L165xH110XP220)
6kg
CE
< 0,3mA
4kV
2kV
2kV
40° C
carter de tôle d'acier
(L165xH110XP220)
6,6kg
CE
< 0,5mA
4kV
2kV
2kV
40° C
carter de tôle d'acier
(L200xH125xP310)
12,3kg
CE
< 0,5mA
4kV
2kV
2kV
40° C
carter de tôle d'acier
(L250xH165xP370)
18,2kg
CE
< 0,5mA
4kV
2kV
2kV
40° C
carter de tôle d'acier
(L250xH165xP370)
18,2kg
CE
Page 8
totale des consommateurs ne doit pas dépasser la puissance de sortie de l’appareil
selon l’étiquette de type.
Seulement les appareils qui sont projetés pour l'utilisation médicale ont l’autorisation
d’être connectés. L'utilisateur est obligé à faire attention à la ligne générale 93 / 42 /
la CEE sur des produits de médecine pour son cas d'application.
Le port de l'appareil se produit par une prise de courant équipée d’un plot de
sécurité. Pour la compensation de potentiel, un connecteur selon DIN 57107/VDE
0107 se trouve à l'appareil.
Si l'appareil ne livre aucune tension initiale, il faut contrôler le fusible initial tout
d’abord.
Pour éviter un réchauffement inadmissible de l'appareil, le boîtier ne doit pas être
couvert.
A la garantie de la sécurité pour l'utilisateur, des interventions dans l'appareil par le
client ne sont pas admissibles.
Lors d’une réparation nécessaire l'appareil est à envoyer au fabricant.
Attention ! Lors des dégâts qui apparaissent par non-respect du mode d’emploi
s'éteint le droit de garantie. Modifications techniques réservées.
Pour vos demandes, aussi à notre autre programme de production, nous sommes
volontiers à votre disposition.
- Noyau d'anneau – Transformateurs de réglage d’économie (modèle mono et
biphasé)
- Transformateurs de réglage de séparation (modèle mono et biphasé)
- Transformateurs de réglage d’économie pour utilisation en laboratoire
- Transformateurs de réglage avec la stimulation de moteur
- Régulateurs électroniques
- Régulateurs de réseau
- Redresseurs de réglage
- Appareils de courant de protection pour la protection anticorrosive cathodique
- Appareils de contrôle de haute tension
- Ainsi que d'autres appareils différents de la technique d'alimentation en
courant