Please be aware that an important notice concerning availability, standard warranty, and use in critical applications of Texas Instruments
SBOS383A − FEBRUAR Y 2007
±1°C Remote and Local TEMPERATURE SENSOR
with N-Factor and Series Resistance Correction
FEATURES
D±1°C REMOTE DIODE SENSOR
D±1°C LOCAL TEMPERATURE SENSOR
DPROGRAMMABLE NON-IDEALITY FACTOR
DSERIES RESISTANCE CANCELLATION
DALERT FUNCTION
DPROGRAMMABLE RESOLUTION: 9 to 12 Bits
DPROGRAMMABLE THRESHOLD LIMITS
DTWO-WIRE/SMBus SERIAL INTERFACE
DMINIMUM AND MAXIMUM TEMPERATURE
DLCD/DLP/LCOS PROJECTORS
DSERVERS
DINDUSTRIAL CONTROLLERS
DCENTRAL OFFICE TELECOM EQUIPMENT
DDESKTOP AND NOTEBOOK COMPUTERS
DSTORAGE AREA NETWORKS (SAN)
DINDUSTRIAL AND MEDICAL
EQUIPMENT
DPROCESSOR/FPGA
TEMPERATURE MONITORING
V+
GND
SCL
SDA
V+
1
5
Conversion Rate
D+
2
3
−
D
8
7
TMP411
N−Factor
Correction
Local
Temperature
Register
Register
Remote
Temperature
Register
DESCRIPTION
The TMP411 is a remote temperature sensor monitor with
a built-in local temperature sensor. The remote
temperature sensor diode-connected transistors are
typically low-cost, NPN- or PNP-type transistors or diodes
that are an integral part of microcontrollers,
microprocessors, or FPGAs.
Remote accuracy is ±1°C for multiple IC manufacturers,
with no calibration needed. The Two-Wire serial interface
accepts SMBus write byte, read byte, send byte, and
receive byte commands to program the alarm thresholds
and to read temperature data.
Features that are included in the TMP411 are: series
resistance cancellation, programmable non-ideality factor,
programmable resolution, programmable threshold limits,
minimum and maximum temperature monitors, wide
remote temperature measurement range (up to +150°C),
diode fault detection, and temperature alert function.
The TMP411 is available in both MSOP-8 and SO-8
(available Q1 2007) packages.
4
THERM
6
ALERT/THERM2
Interrupt
Configuration
Status Regis ter
T
L
Temperature
Comparators
T
R
Bus InterfacePointer Register
Local Temperature Min/Max Register
Remote Temperature Min/Max Register
Consecutive Alert
Configuration Register
Remote Temp High Limit
Remote THERM Limit
Remote TempLow Limit
THERM Hysteresis Register
Local Temp High Limit
Local THE RM Limit
Local Temp Low Limit
Manufacturer IDRegister
Device ID Register
Configuration Register
Resolution Register
semiconductor products and disclaimers thereto appears at the end of this data sheet.
DLP is a registered trademark of Texas Instruments. SMBus is a trademark of Intel Corp.
All other trademarks are the property of their respective owners.
proper handling and installation procedures can cause damage.
ESD damage can range from subtle performance degradation to
complete device failure. Precision integrated circuits may be more
susceptible t o damage because very small parametric changes could
cause the device not to meet its published specifications.
This integrated circuit can be damaged by ESD. Texas
Instruments recommends that all integrated circuits be
handled with appropriate precautions. Failure to observe
ESD Rating:
Human Body Model (HBM)3000V. . . . . . . . . . . . . . . . . . . . . . .
Stresses above these ratings may cause permanent damage.
Exposure to absolute maximum conditions for extended periods
may degrade device reliability. These are stress ratings only , an d
functional operation of the device at these or any other conditions
beyond those specified is not supported.
ORDERING INFORMATION
PRODUCTDESCRIPTIONI2C ADDRESSPACKAGE-LEAD
(1)
PACKAGE
DESIGNATOR
PACKAGE
MARKING
MSOP-8DGK411A
(2)
SO-8
DT411A
MSOP-8DGK411B
(2)
SO-8
(1)
For the most current package and ordering information see the Package Option Addendum at the end of this document, or see the TI web site
at www .ti.com.
(2)
Available Q1 2007.
DT411B
PIN CONFIGURATION
Top ViewMSOP, SO
TMP411
V+
D+
D
THERM
1
2
−
3
4
SCL
8
SDA
7
ALERT/THERM2
6
GND
5
PIN ASSIGNMENTS
PINNAMEDESCRIPTION
1V+Positive supply (2.7V to 5.5V)
2D+
3D−
4THERM
5GNDGround
6ALERT/THERM2
7SDA
8SCL
Positive connection to remote temperature
sensor
Negative connection to remote temperature
sensor
Thermal flag, active low, open-drain;
requires pull-up resistor to V+
Alert (reconfigurable as second thermal
flag), active low, open-drain; requires
pull-up resistor to V+
Serial data line for SMBus, open-drain;
requires pull-up resistor to V+
Serial clock line for SMBus, open-drain;
requires pull-up resistor to V+
2
"#$$
www.ti.com
SBOS383A − FEBRUARY 2007
ELECTRICAL CHARACTERISTICS
At TA = −40°C to +125°C and VS = 2.7V to 5.5V , unless otherwise noted.
TMP411
PARAMETERSCONDITIONS
TEMPERATURE ERROR
Local Temperature SensorTE
Remote Temperature Sensor
vs Supply
Local/RemoteVS = 2.7V to 5.5V±0.2±0.5°C/V
TEMPERATURE MEASUREMENT
Conversion Time (per channel)105115125ms
Resolution
Local Temperature Sensor (programmable)912Bits
Remote Temperature Sensor12Bits
Remote Sensor Source Currents
HighSeries Resistance 3kΩ Max120µA
Medium High60µA
Medium Low12µA
Low6µA
Tested with less than 5Ω effective series resistance and 100pF differential input capacitance.
(1)
LOCAL
TE
REMOTETA
OL
OH
= +15°C to +75°C, TD = −40°C to +150°C, VS = 3.3V±0.0625±1°C
TA = −40°C to +100°C, TD = −40°C to +150°C, VS = 3.3V±1±3°C
TA = −40°C to +125°C, TD = −40°C to +150°C±3±5°C
IH
IL
S
Q
Serial Bus Active, fS = 400kHz, Shutdown Mode90µA
Serial Bus Active, fS = 3.4MHz, Shutdown Mode350µA
TA = −40°C to +125°C±1.25±2.5°C
TA = +15°C to +85°C, VS = 3.3V±0.0625±1°C
I
= 6mA0.150.4V
OUT
V
= V
OUT
S
0.0625 Conversions per Second2830µA
Eight Conversions per Second400475µA
Serial Bus Inactive, Shutdown Mode310µA
MINTYPMAX
2.1V
0.8V
0.11µA
2.75.5V
UNITS
3
"#$$
SBOS383A − FEBRUARY 2007
TYPICAL CHARACTERISTICS
At TA = +25°C and VS = 5.0V , unless otherwise noted.
www.ti.com
REMOTE TEMPERATURE ERROR
3
VS=3.3V
T
REMOTE
C)
2
_
30 Typical Units Shown
η
=1.008
1
0
−
1
−
2
Remote Temperature Error (
−
3
−
50−251251007550250
=+25_C
vs TEMPERATURE
Ambient Temperature, T
A
(_C)
Figure 1.
REMOTE TEMPERATURE ERROR
60
C)
40
_
20
0
−
20
−
40
Remote Temperature Error (
−
60
051015202530
vs LEAKAGE RESISTANCE
R−GND
R−V
S
Leakage Resistance (MΩ)
Figure 3.
LOCAL TEMPERATURE ERROR
3.0
VS=3.3V
2.0
C)
_
1.0
0
−1.0
−2.0
Local Temperature Error (
−3.0
−50125−250255075100
vs TEMPERATURE
50 Units Shown
Ambient Temperature, TA(_C)
Figure 2.
REMOTE TEMPERATURE ERROR vsSERIES RESISTANCE
2.0
1.5
C)
_
1.0
0.5
0
− 0.5
− 1.0
− 1.5
Remote Temperature Error (
− 2.0
(Diode−Connected Transistor, 2N3906 PNP)
VS=2.7V
0350050010001500200025003000
RS(Ω)
Figure 4.
VS=5.5V
REMOTE TEMPERATURE ERROR vsSERIES RESISTANCE
(GND Collector−Connected Transistor, 2N3906 PNP)
2.0
1.5
C)
_
1.0
0.5
0
− 0.5
− 1.0
− 1.5
Remote Temperature Error (
− 2.0
0350050010001500200025003000
VS=2.7V
RS(Ω)
Figure 5.
VS=5.5V
3
C)
2
_
1
0
−
1
−
2
Remote Temperature Error (
−
3
00.51.01.52.02.53.0
REMOTE TEMPERATURE ERROR
vs DIFFERENTIAL CAPACITANCE
Capacitance (nF)
Figure 6.
4
www.ti.com
TYPICAL CHARACTERISTICS (continued)
At TA = +25°C and VS = 5.0V , unless otherwise noted.
"#$$
SBOS383A − FEBRUAR Y 2007
TEMPERATUREERROR
25
20
15
C)
_
10
5
0
−
5
−
10
Temperature Error (
−
15
−
20
−
25
vs POWER−SUPPLY NOISE FREQUENCY
Local 100mVPPNoise
Remote 100mV
Local 250mV
Remote 250mV
051015
Frequency (MHz)
PP
Noise
PP
Noise
Noise
PP
Figure 7.
SHUTDOWN QUIESCENT CURRENT
500
450
400
350
300
A)
µ
250
(
Q
I
200
150
100
50
0
1k10k100k1M10M
vs SCL CLOCK FREQUENCY
VS=5.5V
VS=3.3V
SCLCLockFrequency(Hz)
QUIESCENT CURRENT
500
450
400
350
300
A)
µ
250
(
Q
I
200
150
100
50
0
0.0625 0.1250.250.51248
vs CONVERSION RATE
VS=5.5V
VS=2.7V
Conversion Rate (conversions/sec)
Figure 8.
SHUTDOWN QUIESCENT CURRENT
8
7
6
5
A)
µ
4
(
Q
I
3
2
1
0
vs SUPPLY VOLTAGE
4.53.03.54.05.55.02.5
VS(V)
Figure 9.
Figure 10.
5
"#$$
SBOS383A − FEBRUAR Y 2007
www.ti.com
APPLICATIONS INFORMATION
The TMP411 is a dual-channel digital temperature sensor
that combines a local die temperature measurement
channel and a remote junction temperature measurement
channel in a single MSOP-8 or SO-8 package. The
TMP411 is Two-Wire- and SMBus interface-compatible
and is specified over a temperature range of −40°C to
+125°C. The TMP411 contains multiple registers for
holding configuration information, temperature
measurement results, temperature comparator
maximum/minimum limits, and status information.
User-programmed high and low temperature limits stored
in the TMP401 can be used to monitor local and remote
temperatures to trigger an over/under temperature alarm
+5V
(1)
Transistor−connected configuration
Series Resistance
(2)
R
S
(2)
R
S
:
2
D+
(3)
C
DIFF
3
−
D
1
V+
TMP411
SDA
ALERT/THERM2
0.1µF
SCL
(ALERT
). Additional thermal limits can be programmed
into the TMP411 and used to trigger another flag (THERM
that can be used to initiate a system response to rising
temperatures.
The TMP411 requires only a transistor connected between
D+ and D− for proper remote temperature sensing
operation. The SCL and SDA interface pins require pull-up
resistors as part of the communication bus, while ALERT
and THERM are open-drain outputs that also need pull−up
resistors. ALERT
and THERM may be shared with other
devices if desired for a wired-OR implementation. A 0.1µF
power-supply bypass capacitor is recommended for good
local bypassing. Figure 11 shows a typical configuration
for the TMP411.
Transistor−connected configuration provides better series resistance cancellation.
should be < 1.5kΩin most applications.
S
should be < 1000pF in most applications.
DIFF
Fan Controller
Figure 11. Basic Connections
6
www.ti.com
TEMP
TEMP
"#$$
SBOS383A − FEBRUAR Y 2007
SERIES RESISTANCE CANCELLATION
Series resistance in an application circuit that typically
results from printed circuit board (PCB) trace resistance
and remote line length (see Figure 11) is automatically
cancelled by the TMP411, preventing what would
otherwise result in a temperature offset.
A total of up to 3kΩ of series line resistance is cancelled
by the TMP411, eliminating the need for additional
characterization and temperature offset correction.
See the two Remote Temperature Error vs SeriesResistance typical characteristics curves for details on the
effect of series resistance and power-supply voltage on
sensed remote temperature error.
DIFFERENTIAL INPUT CAPACITANCE
The TMP411 tolerates differential input capacitance of up
to 1000pF with minimal change in temperature error. The
effect of capacitance on sensed remote temperature error
is illustrated in typical characteristic Remote TemperatureError vs Differential Capacitance.
TEMPERATURE MEASUREMENT DATA
Temperature measurement data is taken over a default
range of 0 °C to +127°C for both local and remote locations.
Measurements from −55°C to +150°C can be made both
locally and remotely by reconfiguring the TMP411 for the
extended temperature range. To change the TMP411
configuration from the standard to the extended
temperature range, switch bit 2 (RANGE) of the
Configuration Register from low to high.
for ambient temperatures ranging from −40°C to +125°C.
Parameters in the Absolute Maximum Ratings table must
be observed.
Temperature data resulting from conversions within the
default measurement range is represented in binary form,
as shown in Table 1, Standard Binary column. Note that
any temperature below 0°C results in a data value of zero
(00h). Likewise, temperatures above +127°C result in a
value of 127 (7Fh). The device can be set to measure over
an extended temperature range by changing bit 2 of the
Configuration Register from low to high. The change in
measurement range and data format from standard binary
to extended binary occurs at the next temperature
conversion. For data captured in the extended
temperature range configuration, an offset of 64 (40h) is
added to the standard binary value, as shown in Table 1,
Extended Binary column. This configuration allows
measurement of temperatures below 0°C. Note that binary
values corresponding to temperatures as low as −64°C,
and as high as +191°C are possible; however, most
temperature sensing diodes only measure with the range
of −55°C to +150°C. Additionally, the TMP411 is rated only
NOTE: Whenever changing between standard and
extended temperature ranges, be aware that the
temperatures stored in the temperature limit registers are
NOT automatically reformatted to correspond to the new
temperature range format. These temperature limit values
must be reprogrammed in the appropriate binary or
extended binary format.
Both local and remote temperature data use two bytes for
data storage. The high byte stores the temperature with
1°C resolution. The second or low byte stores the decimal
fraction value of the temperature and allows a higher
measurement resolution; see Table 2. The measurement
resolution for the remote channel is 0.0625°C, and is not
adjustable. The measurement resolution for the local
channel is adjustable; it can be set for 0.5°C, 0.25°C,
0.125°C, or 0.0625°C by setting the RES1 and RES0 bits
of the Resolution Register; see the Resolution Register
section.
7
"#$$
www.ti.com
SBOS383A − FEBRUAR Y 2007
Table 2. Decimal Fraction Temperature Data Format (Local and Remote Temperature Low Bytes)
The TMP411 contains multiple registers for holding
configuration information, temperature measurement
results, temperature comparator maximum/minimum,
limits, and status information. These registers are
described in Figure 12 and Table 3.
POINTER REGISTER
Figure 12 shows the internal register structure of the
TMP411. The 8-bit Pointer Register is used to address a
given data register. The Pointer Register identifies which
of the data registers should respond to a read or write
command on the Two-Wire bus. This register is set with
every write command. A write command must be issued
to set the proper value in the Pointer Register before
executing a read command. Table 3 describes the pointer
address of the registers available in the TMP411. The
power-on reset (POR) value of the Pointer Register is 00h
(0000 0000b).
Pointer Register
Local and Remote Temperature Registers
Local and Remote Limit Registers
THERM Hysteresis Register
Status Register
Configuration Register
Resolution Register
Conversion Rate Register
Consecutive Alert Register
Identification Registers
Local Temperature Min/Max
Remote Temperature Min/Max
NAFCXXX
FENA5501010101Manufacturer ID
FFNA1100010001Device ID
(1)
NA = not applicable; register is write- or read-only.
(2)
X = indeterminate state.
(1)
POWER-ON
(HEX)
00LT11LT10LT9LT8LT7LT6LT5LT4Local Temperature (High Byte)
D7D6D5D4D3D2D1D0
(2)
XXXXXXXSoftware Reset
BIT DESCRIPTIONS
REGISTER DESCRIPTIONS
Remote Temperature
(High Byte)
Local T emperature High Limit
(High Byte)
Local Temperature Low Limit
(High Byte)
Remote Temperature
High Limit (High Byte)
Remote Temperature
Low Limit (High Byte)
Remote Temperature
(Low Byte)
Remote Temperature
High Limit (Low Byte)
Remote Temperature
Low Limit (Low Byte)
Local T emperature High Limit
(Low Byte)
Local Temperature Low Limit
(Low Byte)
Local Temperature Minimum
(High Byte)
Local Temperature Minimum
(Low Byte)
Local Temperature Maximum
(High Byte)
Local Temperature Maximum
(Low Byte)
Remote Temperature Minimum
(High Byte)
Remote Temperature Minimum
(Low Byte)
Remote Temperature
Maximum (High Byte)
Remote Temperature
Maximum (Low Byte)
9
"#$$
SBOS383A − FEBRUARY 2007
www.ti.com
TEMPERATURE REGISTERS
The TMP411 has four 8-bit registers that hold temperature
measurement results. Both the local channel and the
remote channel have a high byte register that contains the
most significant bits (MSBs) of the te m perature ADC result
and a low byte register that contains the least significant
bits (LSBs) of the temperature ADC result. The local
channel high byte address is 00h; the local channel low
byte address is 15h. The remote channel high byte is at
address 01h; the remote channel low byte address is 10h.
These registers are read-only and are updated by the ADC
each time a temperature measurement is completed.
The TMP411 contains circuitry to assure that a low byte
register read command returns data from the same ADC
conversion as the immediately preceding high byte read
command. This assurance remains valid only until another
register is read. For proper operation, the high byte of a
temperature register should be read first. The low byte
register should be read in the next read command. The low
byte register may be left unread if the LSBs are not
needed. Alternatively, the temperature registers may be
read as a 16-bit register by using a single two-byte read
command from address 00h for the local channel result or
from address 01h for the remote channel result. The high
byte will be output first, followed by the low byte. Both bytes
of this read operation will be from the same ADC
conversion. The power-on reset value of both temperature
registers is 00h.
LIMIT REGISTERS
The TMP411 has 11 registers for setting comparator limits
for both the local and remote measurement channels.
These registers have read and write capability. The High
and Low Limit Registers for both channels span two
registers, as do the temperature registers. The local
temperature high limit is set by writing the high byte to
pointer address 0Bh and writing the low byte to pointer
address 16h, or by using a single two-byte write command
(high byte first) to pointer address 0Bh. The local
temperature high limit is obtained by reading the high byte
from pointer address 05h and the low byte from pointer
address 16h. The power-on reset value of the local
temperature high limit is 55h/00h (+85°C in standard
temperature mode; +21°C in extended temperature
mode).
Similarly, the local temperature low limit is set by writing
the high byte to pointer address 0Ch and writing the low
byte to pointer address 17h, or by using a single two-byte
write command to pointer address 0Ch. The local
temperature low limit is read by reading the high byte from
pointer address 06h and the low byte from pointer address
17h, or by using a two-byte read from pointer address 06h.
The power-on reset value of the local temperature low limit
register is 00h/00h (0°C in standard temperature mode;
−64°C in extended mode).
The remote temperature high limit is set by writing the high
byte to pointer address 0Dh and writing the low byte to
pointer address 13h, or by using a two-byte write
command to pointer address 0Dh. The remote
temperature high limit is obtained by reading the high byte
from pointer address 07h and the low byte from pointer
address 13h, or by using a two-byte read command from
pointer address 07h. The power-on reset value of the
Remote Temperature High Limit Register is 55h/00h
(+85°C in standard temperature mode; +21°C in extended
temperature mode).
The remote temperature low limit is set by writing the high
byte to pointer address 0Eh and writing the low byte to
pointer address 14h, or by using a two-byte write to pointer
address 0Eh. The remote temperature low limit is read by
reading the high byte from pointer address 08h and the low
byte from pointer address 14h, or by using a two-byte read
from pointer address 08h. The power-on reset value of the
Remote Temperature Low Limit Register is 00h/00h (0°C
in standard temperature mode; −64°C in extended mode).
The TMP41 1 also has a THERM limit register for both the
local and the remote channels. These registers are eight
bits and allow for THERM limits set to 1°C resolution. The
local channel THERM limit is set by writing to pointer
address 20h. The remote channel THERM limit is set by
writing to pointer address 19h. The local channel THERM
limit is obtained by reading from pointer address 20h; the
remote channel THERM limit is read by reading from
pointer address 19h. The power-on reset value of the
THERM limit registers is 55h (+85°C in standard
temperature mode; +21°C in extended temperature
mode). The THERM limit comparators also have
hysteresis. The hysteresis of both comparators is set by
writing to pointer address 21h. The hysteresis value is
obtained by reading from pointer address 21h. The value
in the Hysteresis Register is an unsigned number (always
positive). The power-on reset value of this register is 0Ah
(+10°C).
Whenever changing between standard and extended
temperature ranges, be aware that the temperatures
stored in the temperature limit registers are NOT
automatically reformatted to correspond to the new
temperature range format. These values must be
reprogrammed in the appropriate binary or extended
binary format.
10
www.ti.com
"#$$
SBOS383A − FEBRUAR Y 2007
STATUS REGISTER
The TMP411 has a Status Register to report the state of
the temperature comparators. Table 4 shows the Status
Register bits. The Status Register is read-only and is read
by reading from pointer address 02h.
The BUSY bit reads as ‘1’ if the ADC is making a
conversion. It reads as ‘0’ if the ADC is not converting.
The OPEN bit reads as ‘1’ if the remote transistor was
detected as open since the last read of the Status Register.
The OPEN status is only detected when the ADC is
attempting to convert a remote temperature.
The RTHRM bit reads as ‘1’ if the remote temperature has
exceeded the remote THERM limit and remains greater
than the remote THERM limit less the value in the shared
Hysteresis Register; see Figure 17.
The LTHRM bit reads as ‘1’ if the local temperature has
exceeded the local THERM limit and remains greater than
the local THERM limit less the value in the shared
Hysteresis Register; see Figure 17.
The LHIGH and RHIGH bit values depend on the state of
the AL/TH bit in the Configuration Register. If the AL/TH bit
is ‘0’, the LHIGH bit reads as ‘1’ if the local high limit was
exceeded since the last clearing of the Status Register.
The RHIGH bit reads as ‘1’ if the remote high limit was
exceeded since the last clearing of the Status Register. If
the AL/TH bit is ‘1’, the remote high limit and the local high
limit are used to implement a THERM2
reads as ‘1’ if the local temperature has exceeded the local
high limit and remains greater than the local high limit less
the value in the Hysteresis Register.
function. LHIGH
The RHIGH bit reads as ‘1’ if the remote temperature has
exceeded the remote high limit and remains greater than
the remote high limit less the value in the Hysteresis
Register.
The LLOW and RLOW bits are not affected by the AL/TH
bit. The LLOW bit reads as ‘1’ if the local low limit was
exceeded since the last clearing of the Status Register.
The RLOW bit reads as ‘1’ if the remote low limit was
exceeded since the last clearing of the Status Register.
The values of the LLOW, RLOW, and OPEN (as well as
LHIGH and RHIGH when AL/TH is ‘0’) are latched and will
read as ‘1’ until the Status Register is read or a device reset
occurs. These bits are cleared by reading the Status
Register, provided that the condition causing the flag to be
set no longer exists. The values of BUSY, LTHRM, and
RTHRM (as well as LHIGH and RHIGH when AL/TH is ‘1’)
are not latched and are not cleared by reading the Status
Register. They always indicate the current state, and are
updated appropriately at the end of the corresponding
ADC conversion. Clearing the Status Register bits does
not clear the state of the ALERT
pin; an SMBus alert
response address command must be used to clear the
ALERT pin.
The TMP411 NORs LHIGH, LLOW, RHIGH, RLOW, and
OPEN, so a status change for any of these flags from ‘0’
to ‘1’ automatically causes the ALERT
applies when the ALERT
/THERM2 pin is configured for
pin to go low (only
ALERT mode).
BIT #D7D6D5D4D3D2D1D0
BIT NAMEBUSYLHIGHLLOWRHIGHRLOWOPENRTHRMLTHRM
POR VALUE0
(1)
The BUSY bit will change to
the TMP411 is converting a temperature reading.
(1)
‘1’ almost immediately (<< 100µs) following power-up, as the TMP411 begins the first temperature conversion. It will be high whenever
Table 4. Status Register Format
STATUS REGISTER (Read = 02h, Write = NA)
0000000
11
"#$$
SBOS383A − FEBRUARY 2007
www.ti.com
CONFIGURATION REGISTER
The Configuration Register sets the temperature range,
controls shutdown mode, and determines how the
ALERT
Register is set by writing to pointer address 09h and read
by reading from pointer address 03h.
The MASK bit (bit 7) enables or disables the ALERT
output if AL/TH = 0. If AL/TH = 1 then the MASK bit has no
effect. If MASK is set to ‘0’, the ALERT
one of the temperature measurement channels exceeds
its high or low limits for the chosen number of consecutive
conversions. If the MASK bit is set to ‘1’, the TMP411
retains the ALERT
go low.
The shutdown (SD) bit (bit 6) enables or disables the
temperature measurement circuitry . I f S D = 0 , the TMP411
converts continuously at the rate set in the conversion rate
register. When SD is set to ‘1’, the TMP411 immediately
stops converting and enters a shutdown mode. When SD
is set to ‘0’ again, the TMP411 resumes continuous
conversions.
The AL/TH bit (bit 5) controls whether the ALERT
functions in ALERT mode or THERM2 mode. If AL/TH = 0,
the ALERT pin operates as an interrupt pin. In this mode,
/THERM2 pin functions. The Configuration
pin
pin goes low when
pin status, but the ALERT pin will not
pin
the ALERT pin goes low after the set number of
consecutive out-of-limit temperature measurements
occur.
If AL/TH = 1, the ALERT
THERM function (THERM2
/THERM2 pin implements a
). In this mode, THERM2
functions similar to the THERM pin except that the local
high limit and remote high limit registers are used for the
thresholds. THERM2 goes low when either RHIGH or
LHIGH is set.
The temperature range is set by configuring bit 2 of the
Configuration Register. Setting this bit low configures the
TMP411 for the standard measurement range (0°C to
+127°C); temperature conversions will be stored in the
standard binary format. Setting bit 2 high configures the
TMP411 for the extended measurement range (−55°C to
+150°C); temperature conversions will be stored in the
extended binary format (see Table 1).
The remaining bits of the Configuration Register are
reserved and must always be set to ‘0’. The power-on reset
value for this register is 00h. Table 5 summarizes the bits
of the Configuration Register.
The RES1 and RES0 bits (resolution bits 1 and 0) of the
Resolution Register set the resolution of the local
temperature measurement channel. Remote temperature
measurement channel resolution is not affected.
Changing the local channel resolution also affects the
conversion time and rate of the TMP411. The Resolution
Register is set by writing to pointer address 1Ah and is
read by reading from pointer address 1Ah. Table 6 shows
the resolution bits for the Resolution Register.
Bits 2 through 4 of the Resolution Register must always be
set to ‘1’. Bits 5 through 7 of the Resolution Register must
always be set to ‘0’. The power-on reset value of this
register is 1Ch.
CONVERSION TIME
(Typical)
power dissipation to be balanced with the temperature
register update rate. Table 7 shows the conversion rate
options and corresponding current consumption.
N-FACTOR CORRECTION REGISTER
The TMP411 allows for a different n-factor value to be used
for converting remote channel measurements to
temperature. The remote channel uses sequential current
excitation to extract a differential V
measurement to determine the temperature of the remote
transistor. Equation 1 relates this voltage and temperature.
V
* V
BE2
BE1
+
nkT
I
2
ǒ
Ǔ
ln
q
I
1
The value n in Equation 1 is a characteristic of the
particular transistor used for the remote channel. The
default value for the TMP411 is n = 1.008. The value in the
N-Factor Correction Register may be used to adjust the
effective n-factor according to Equation 2 and Equation 3.
1.008 @ 300
+
eff
ǒ
300*N
+ 300*
Ǔ
ADJUST
300 @ 1.008
ǒ
n
eff
Ǔ
N
ADJUST
n
voltage
BE
(1)
(2)
(3)
CONVERSION RATE REGISTER
The Conversion Rate Register controls the rate at which
temperature conversions are performed. This register
adjusts the idle time between conversions but not the
conversion timing itself, thereby allowing the TMP411
two’s-complement format, yielding an effective data range
from −128 to +127. The n-correction value may be written
to and read from pointer address 18h. The register
power-on reset value is 00h, thus having no effect unless
written to.
The TMP411 stores the minimum and maximum
temperature measured since power-on, chip-reset, or
minimum and maximum register reset for both the local
and remote channels. The Local Temperature Minimum
Register may be read by reading the high byte from pointer
address 30h and the low byte from pointer address 31h.
The Local Temperature Minimum Register may also be
read by using a two-byte read command from pointer
address 30h. The Local Temperature Minimum Register is
reset at power-on, by executing the chip-reset command,
or by writing any value to any of pointer addresses 30h
through 37h. The reset value for these registers is
FFh/F0h.
power-on by executing the chip reset command, or by
writing any value to any of pointer addresses 30h through
37h. The reset value for these registers is FFh/F0h.
The Remote Temperature Maximum Register may be read
by reading the high byte from pointer address 36h and the
low byte from pointer address 37h. The Remote
Temperature Maximum Register may also be read by
using a two-byte read command from pointer address 36h.
The Remote Temperature Maximum Register is reset at
power-on by executing the chip reset command, or by
writing any value to any of pointer addresses 30h through
37h. The reset value for these registers is 00h/00h.
SOFTWARE RESET
The TMP411 may be reset by writing any value to Pointer
Register FCh. This restores the power-on reset state to all
of the TMP411 registers as well as abort any conversion
in process and clear the ALERT
and THERM pins.
The TMP411 also supports reset via the two-wire general
call address (00000000). The TMP411 acknowledges the
general call address and responds to the second byte. If
the second byte is 00000110, the TMP411 executes a
software reset. The TMP411 takes no action in response
to other values in the second byte.
CONSECUTIVE ALERT REGISTER
The value in the Consecutive Alert Register (address 22h)
determines how many consecutive out-of-limit
measurements must occur on a measurement channel
before the ALERT
register does not affect bits in the Status Register . Values
of one, two, three, or four consecutive conversions can be
selected; one conversion is the default. This function
allows additional filtering for the ALERT
consecutive alert bits are shown in Table 9.
signal is activated. The value in this
pin. The
The Local Temperature Maximum Register may be read
by reading the high byte from pointer address 32h and the
low byte from pointer address 33h. The Local Temperature
Maximum Register may also be read by using a two-byte
read command from pointer address 32h. The Local
Temperature Maximum Register is reset at power-on by
executing the chip reset command, or by writing any value
to any of pointer addresses 30h through 37h. The reset
value for these registers is 00h/00h.
The Remote Temperature Minimum Register may be read
by reading the high byte from pointer address 34h and the
low byte from pointer address 35h. The Remote
Temperature Minimum Register may also be read by using
a two-byte read command from pointer address 34h. The
Remote Temperature Minimum Register is reset at
14
Table 9. Consecutive Alert Register
CONSECUTIVE ALERT REGISTER
(READ = 22h, WRITE = 22h, POR = 80h)
NUMBER OF CONSECUTIVE
C2C1C0
0001
0012
0113
1114
OUT-OF-LIMIT MEASUREMENTS
NOTE: Bit 7 of the Consecutive Alert Register controls the
enable/disable of the timeout function. See the Timeout
Function section for a description of this feature.
www.ti.com
BIT #
D7D6D5D4D3D2D1
D0
"#$$
SBOS383A − FEBRUAR Y 2007
THERM HYSTERESIS REGISTER
The THERM Hysteresis Register stores the hysteresis
value used for the THERM
must be programmed with a value that is less than the
Local Temperature High Limit Register value, Remote
Temperature High Limit Register value, Local THERM
Limit Register value, or Remote THERM Limit Register
value; otherwise, the respective temperature comparator
will not trip on the measured temperature falling edges.
Allowable hysteresis values are shown in Table 10. The
default hysteresis value is 10°C, whether the device is
operating in the standard or extended mode setting.
To address a specific device, a START condition is
initiated. START is indicated by pulling the data line (SDA)
from a high to low logic level while SCL is high. All slaves
on the bus shift in the slave address byte, with the last bit
indicating whether a read or write operation is intended.
During the ninth clock pulse, the slave being addressed
responds to the master by generating an Acknowledge
and pulling SDA low.
Data transfer is then initiated and sent over eight clock
pulses followed by an Acknowledge bit. During data
transfer SDA must remain stable while SCL is high,
because any change in SDA while SCL is high is
interpreted as a control signal.
Once all data has been transferred, the master generates
a STOP condition. STOP is indicated by pulling SDA from
low to high, while SCL is high.
SERIAL INTERFACE
The TMP411 operates only as a slave device on either the
Two-Wire bus or the SMBus. Connections to either bus are
made via the open-drain I/O lines, SDA and SCL. The SDA
and SCL pins feature integrated spike suppression filters
and Schmitt triggers to minimize the effects of input spikes
and bus noise. The TMP411 supports the transmission
protocol for fast (1kHz to 400kHz) and high-speed (1kHz
to 3.4MHz) modes. All data bytes are transmitted MSB
first.
SERIAL BUS ADDRESS
To communicate with the TMP411, the master must first
address slave devices via a slave address byte. The slave
address byte consists of seven address bits, and a
direction bit indicating the intent of executing a read or
write operation. The address of the TMP411 is 4Ch
(1001100b).
BUS OVERVIEW
The TMP411 is SMBus interface-compatible. In SMBus
protocol, the device that initiates the transfer is called a
master, and the devices controlled by the master are
slaves. The bus must be controlled by a master device that
generates the serial clock (SCL), controls the bus access,
and generates the START and STOP conditions.
READ/WRITE OPERATIONS
Accessing a particular register on the TMP411 is
accomplished by writing the appropriate value to the
Pointer Register. The value for the Pointer Register is the
first byte transferred after the slave address byte with the
R/W
bit low. Every write operation to the TMP411 requires
When reading from the TMP411, the last value stored in
the Pointer Register by a write operation is used to
determine which register is read by a read operation. To
change the register pointer for a read operation, a new
value must be written to the Pointer Register. This
transaction is accomplished by issuing a slave address
byte with the R/W
bit low, followed by the Pointer Register
byte. No additional data is required. The master can then
generate a START condition and send the slave address
byte with the R/W
bit high to initiate the read command.
See Figure 15 for details of this sequence. If repeated
reads from the same register are desired, it is not
necessary to continually send the Pointer Register bytes,
because the TMP411 retains the Pointer Register value
until it is changed by the next write operation. Note that
register bytes are sent MSB first, followed by the LSB.
TIMING DIAGRAMS
The TMP411 is Two-Wire and SMBus-compatible.
Figure 13 to Figure 16 describe the various operations on
the TMP411. Bus definitions are given below. Parameters
for Figure 13 are defined in Table 12.
Bus Idle: Both SDA and SCL lines remain high.
Start Data Transfer: A change in the state of the SDA line,
from high to low, while the SCL line is high, defines a
START condition. Each data transfer is initiated with a
START condition.
Stop Data Transfer: A change in the state of the SDA line
from low to high while the SCL line is high defines a STOP
condition. Each data transfer terminates with a repeated
START or STOP condition.
Data Transfer: The number of data bytes transferred
between a START and a STOP condition is not limited and
is determined by the master device. The receiver
acknowledges the transfer of data.
Acknowledge: Each receiving device, when addressed,
is obliged to generate an Acknowledge bit. A device that
acknowledges must pull down the SDA line during the
Acknowledge clock pulse in such a way that the SDA line
is stable low during the high period of the Acknowledge
clock pulse. Setup and hold times must be taken into
account. On a master receive, data transfer termination
can be signaled by the master generating a
Not-Acknowledge on the last byte that has been
transmitted by the slave.
SCL
SDA
t
(LOW)
t
(HDSTA)
t
(BU F )
PSSP
t
R
t
(HDDAT)
t
F
t
(HIGH)t(SUSTA)
t
(SUDAT)
t
(HDSTA)
t
(SUSTO)
Figure 13. Two-Wire Timing Diagram
16
www.ti.com
Table 12. Timing Diagram Definitions for Figure 13
PARAMETERMINMAXMINMAXUNITS
SCL Operating Frequencyf
Bus Free Time Between STOP and START Conditiont
Hold time after repeated START condition.
After this period, the first clock is generated.
Repeated START Condition Setup Timet
STOP Condition Setup Timet
Data Hold Timet
Data Setup Timet
SCL Clock LOW Periodt
SCL Clock HIGH Periodt
Clock/Data Fall Timet
Clock/Data Rise Time
for SCL ≤ 100kHz
(SCL)
(BUF)
t
(HDSTA)
(SUS TA )
(SUS TO)
(HDDA T)
(SUDA T)
(LOW)
(HIGH)
SBOS383A − FEBRUAR Y 2007
0.0010.40.0013.4MHz
600160ns
100100ns
100100ns
100100ns
00ns
10010ns
1300160ns
60060ns
F
t
R
t
R
300160ns
300
160
1000
"#$$
ns
191
SCL
SDA
StartBy
Master
SCL
(Continued)
SDA
(Continued)
NOTE (1): Bit = 0 for TMP411A. Bit = 1 for TMP411B.
1
001100
Frame 1 Two−Wire Slave Address Byte
1
D7
D6 D5 D4 D3 D2 D1 D0
Frame 3 Data Byte 1
Figure 14. Two-Wire Timing Diagram for Write Word Format
In order for the Two-Wire bus to operate at frequencies
above 400kHz, the master device must issue a
High-speed mode (Hs-mode) master code (00001XXX) as
the first byte after a START condition to switch the bus to
high-speed operation. The TMP411 will not acknowledge
this byte, but will switch the input filters on SDA and SCL
and the output filter on SDA to operate in Hs-mode,
allowing transfers at up to 3.4MHz. After the Hs-mode
master code has been issued, the master transmits a
Two-Wire slave address to initiate a data transfer
operation. The bus continues to operate in Hs-mode until
a STOP condition occurs on the bus. Upon receiving the
STOP condition, the TMP411 switches the input and
output filter back to fast-mode operation.
TIMEOUT FUNCTION
When bit 7 of the Consecutive Alert Register is set high,
the TMP411 timeout function is enabled. The TMP411
resets the serial interface if either SCL or SDA are held low
for 30ms (typical) between a START and STOP condition.
If the TMP411 is holding the bus low, it releases the bus
and waits for a START condition. To avoid activating the
timeout function, it is necessary to maintain a
communication speed of at least 1kHz for the SCL
operating frequency. The default state of the timeout
function is enabled (bit 7 = high).
THERM (PIN 4) AND ALERT/THERM2 (PIN 6)
The TMP411 has two pins dedicated to alarm functions,
the THERM
open-drain outputs that each require a pull-up resistor to
V+. These pins can be wire-ORed together with other
alarm pins for system monitoring of multiple sensors. The
THERM
software disabled. The ALERT
an earlier warning interrupt, and can be software disabled,
or masked. The ALERT
and ALERT/THERM2 pins. Both pins are
pin provides a thermal interrupt that cannot be
pin is intended for use as
/THERM2 pin can also be
configured for use as THERM2
, a second THERM pin
(Configuration Register: AL/TH bit = 1). The default setting
configures pin 6 to function as ALERT (AL/TH = 0).
The THERM
pin asserts low when either the measured
local or remote temperature is outside of the temperature
range programmed in the corresponding Local/Remote
THERM Limit Register. The THERM temperature limit
range can be programmed with a wider range than that of
the limit registers, which allows ALERT
earlier warning than THERM
. The THERM alarm resets
to provide an
automatically when the measured temperature returns to
within the THERM temperature limit range minus the
hysteresis value stored in the THERM Hysteresis
Register. The allowable values of hysteresis are shown in
Table 10. The default hysteresis is 10°C. When the
ALERT
/THERM2 pin is configured as a second thermal
alarm (Configuration Register: bit 7 = 0, bit 5 = 1), it
functions the same as THERM
, but uses the temperatures
stored in the Local/Remote Temperature High/Low Limit
Registers to set its comparison range.
When ALERT
/THERM2 (pin 6) is configured as ALERT
(Configuration Register: bit 7 = 0, bit 5 = 0), the pin asserts
low when either the measured local or remote temperature
violates the range limit set by the corresponding
Local/Remote Temperature High/Low Limit Registers.
This alert function can be configured to assert only if the
range is violated a specified number of consecutive times
(1, 2, 3, or 4). The consecutive violation limit is set in the
Consecutive Alert Register. False alerts that occur as a
result of environmental noise can be prevented by
requiring consecutive faults. ALERT
also asserts low if the
remote temperature sensor is open-circuit. When the
MASK function is enabled (Configuration Register:
bit 7 = 1), ALERT
is disabled (that is, masked). ALERT
resets when the master reads the device address, as long
as the condition that caused the alert no longer persists,
and the Status Register has been reset.
Measured
Temperature
THERM
SMBusALERT
ALERT
THERM Limit and ALERT High Limit
ALERT Low Limit and THERM Limit Hysteresis
ReadRead
Time
Read
Figure 17. SMBus Alert Timing Diagram
19
"#$$
SBOS383A − FEBRUAR Y 2007
www.ti.com
SMBUS ALERT FUNCTION
The TMP411 supports the SMBus Alert function. When pin
6 is configured as an alert output, the ALERT
TMP411 may be connected as an SMBus Alert signal.
When a master detects an alert condition on the ALERT
line, the master sends an SMBus Alert command
(00011001) on the bus. If the ALERT
active, the devices will acknowledge the SMBus Alert
command and respond by returning its slave address on
the SDA line. The eighth bit (LSB) of the slave address
byte indicates whether the temperature exceeding one of
the temperature high limit settings or falling below one of
the temperature low limit settings caused the alert
condition. This bit will be high if the temperature is greater
than or equal to one of the temperature high limit settings;
this bit will be low if the temperature is less than one of the
temperature low limit settings. See Figure 16 for details of
this sequence.
If multiple devices on the bus respond to the SMBus Alert
command, arbitration during the slave address portion of
the SMBus Alert command determines which device will
clear its alert status. If the TMP41 1 wins the arbitration, its
ALERT
SMBus Alert command. If the TMP411 loses the
arbitration, the ALERT
pin becomes inactive at the completion of the
pin remains active.
pin of the TMP41 1 is
pin of the
SHUTDOWN MODE (SD)
The TMP411 Shutdown Mode allows the user to save
maximum power by shutting down all device circuitry other
than the serial interface, reducing current consumption to
typically less than 3µA; see typical characteristic curve
Shutdown Quiescent Current vs Supply Voltage.
Shutdown Mode is enabled when the SD bit of the
Configuration Register is high; the device shuts down
once the current conversion is completed. When SD is low ,
the device maintains a continuous conversion state.
SENSOR FAULT
The TMP411 will sense a fault at the D+ input resulting
from incorrect diode connection or an open circuit. The
detection circuitry consists of a voltage comparator that
trips when the voltage at D+ exceeds (V+) − 0.6V (typical).
The comparator output is continuously checked during a
conversion. If a fault is detected, the last valid measured
temperature is used for the temperature measurement
result, the OPEN bit (Status Register, bit 2) is set high, and,
if the alert function is enabled, ALERT
When not using the remote sensor with the TMP411, the
D+ and D− inputs must be connected together to prevent
meaningless fault warnings.
asserts low.
UNDER-VOLTAGE LOCKOUT
The TMP411 senses when the power-supply voltage has
reached a minimum voltage level for the ADC converter to
function. The detection circuitry consists of a voltage
comparator that enables the ADC converter after the
power supply (V+) exceeds 2.45V (typical). The
comparator output is continuously checked during a
conversion. The TMP411 will not perform a temperature
conversion if the power supply is not valid. The last valid
measured temperature is used for the temperature
measurement result.
GENERAL CALL RESET
The TMP411 supports reset via the T wo-Wire General Call
address 00h (0000 0000b). The TMP411 acknowledges
the General Call address and responds to the second byte.
If the second byte is 06h (0000 0110b), the TMP411
executes a software reset. This software reset restores the
power-on reset state to all TMP411 registers, aborts any
conversion in progress, and clears the ALERT
THERM
other values in the second byte.
pins. The TMP41 1 takes no action in response to
and
IDENTIFICATION REGISTERS
The TMP411 allows for the Two-Wire bus controller to
query the device for manufacturer and device IDs to allow
for software identification of the device at the particular
Two-Wire bus address. The manufacturer ID is obtained
by reading from pointer address FEh. The device ID is
obtained by reading from pointer address FFh. The
TMP411 returns 55h for the manufacturer code and 11h for
the device ID. These registers are read-only.
FILTERING
Remote junction temperature sensors are usually
implemented in a noisy environment. Noise is most often
created by fast digital signals, and it can corrupt
measurements. The TMP41 1 has a built-in 65kHz filter on
the inputs of D+ and D− to minimize the effects of noise.
However, a bypass capacitor placed differentially across
the inputs of the remote temperature sensor is
recommended to make the application more robust
against unwanted coupled signals. The value of the
capacitor should be between 100pF and 1nF. Some
applications attain better overall accuracy with additional
series resistance; however, this increased accuracy is
setup-specific. When series resistance is added, the value
should not be greater than 3kΩ.
20
www.ti.com
"#$$
SBOS383A − FEBRUAR Y 2007
REMOTE SENSING
The TMP411 is designed to be used with either discrete
transistors or substrate transistors built into processor
chips and ASICs. Either NPN or PNP transistors can be
used, as long as the base-emitter junction is used as the
remote temperature sense. Either a transistor or diode
connection can also be used; see Figure 11.
Errors in remote temperature sensor readings will be the
consequence of the ideality factor and current excitation
used by the TMP411 versus the manufacturer-specified
operating current for a given transistor. Some
manufacturers specify a high-level and low-level current
for the temperature-sensing substrate transistors. The
TMP411 uses 6µA for I
TMP411 allows for different n-factor values; see the
N-Factor Correction Register section.
The ideality factor (n) is a measured characteristic of a
remote temperature sensor diode as compared to an ideal
diode. The ideality factor for the TMP411 is trimmed to be
1.008. For transistors whose ideality factor does not match
the TMP411, Equation 4 can be used to calculate the
temperature error. Note that for the equation to be used
correctly, actual temperature (°C) must be converted to
Kelvin (°K).
n * 1.008
T
Where:
For n = 1.004 and T(°C) = 100°C:
T
ERR
T
ERR
If a discrete transistor is used as the remote temperature
sensor with the TMP411, the best accuracy can be
achieved by selecting the transistor according to the
following criteria:
1. Base-emitter voltage > 0.25V at 6µA, at the highest
ǒ
+
ERR
n = Ideality factor of remote temperature sensor
T(°C) = actual temperature
T
ERR
Degree delta is the same for °C and °K
+
1.008
= Error in TMP411 reading due to n ≠ 1.008
1.004 * 1.008
ǒ
1.008
+*1.48°C
sensed temperature.
and 120µA for I
LOW
ǒ
Ǔ
273.15 ) Tǒ°C
ǒ
Ǔ
273.15 ) 100°C
. The
HIGH
Ǔ
Ǔ
(4)
Ǔ
(5)
2. Base-emitter voltage < 0.95V at 120µA, at the lowest
sensed temperature.
3. Base resistance < 100Ω.
4. Tight control of V
variations in h
Based on these criteria, two recommended small-signal
transistors are the 2N3904 (NPN) or 2N3906 (PNP).
characteristics indicated by small
BE
(that is, 50 to 150).
FE
MEASUREMENT ACCURACY AND THERMAL
CONSIDERATIONS
The temperature measurement accuracy of the TMP411
depends on the remote and/or local temperature sensor
being at the same temperature as the system point being
monitored. Clearly , i f the temperature sensor is not in good
thermal contact with the part of the system being
monitored, then there will be a delay in the response of the
sensor to a temperature change in the system. For remote
temperature sensing applications using a substrate
transistor (or a small, SOT23 transistor) placed close to the
device being monitored, this delay is usually not a concern.
The local temperature sensor inside the TMP411 monitors
the ambient air around the device. The thermal time
constant for the TMP411 is approximately two seconds.
This constant implies that if the ambient air changes
quickly by 100°C, it would take the TMP411 about 10
seconds (that is, five thermal time constants) to settle to
within 1°C of the final value. In most applications, the
TMP411 package is in electrical and therefore thermal
contact with the printed circuit board (PCB), as well as
subjected to forced airflow. The accuracy of the measured
temperature directly depends on how accurately the PCB
and forced airflow temperatures represent the
temperature that the TMP411 is measuring. Additionally,
the internal power dissipation of the TMP411 can cause
the temperature to rise above the ambient or PCB
temperature. The internal power dissipated as a result of
exciting the remote temperature sensor is negligible
because of the small currents used. For a 5.5V supply and
maximum conversion rate of eight conversions per
second, the TMP411 dissipates 1.82mW (PD
330µA). If both the ALERT
each sinking 1mA, an additional power of 0.8mW is
dissipated (PD
Total power dissipation is then 2.62mW (PD
and, with an q
temperature to rise approximately 0.393°C above the
ambient.
= 1mA × 0.4V + 1mA × 0.4V = 0.8mW).
OUT
JA
/THERM2 and THERM pins are
of 150°C/W, causes the junction
= 5.5V ×
IQ
+ PD
IQ
OUT
)
21
"#$$
SBOS383A − FEBRUAR Y 2007
LAYOUT CONSIDERATIONS
Remote temperature sensing on the TMP411 measures
very small voltages using very low currents; therefore,
noise at the IC inputs must be minimized. Most
applications using the TMP411 will have high digital
content, with several clocks and logic level transitions
creating a noisy environment. Layout should adhere to the
following guidelines:
1. Place the TMP411 as close to the remote junction
sensor as possible.
2. Route the D+ and D− traces next to each other and
shield them from adjacent signals through the use of
ground guard traces, as shown in Figure 18. If a
multilayer PCB is used, bury these traces between
ground or V
noise sources. 5 mil PCB traces are recommended.
3. Minimize additional thermocouple junctions caused
by copper-to-solder connections. If these junctions
are used, make the same number and approximate
locations of copper-to-solder connections in both the
D+ and D− connections to cancel any thermocouple
effects.
4. Use a 0.1µF local bypass capacitor directly between
the V+ and GND of the TMP411, as shown in
Figure 19. Minimize filter capacitance between D+
and D− to 1000pF or less for optimum measurement
performance. This capacitance includes any cable
capacitance between the remote temperature sensor
and TMP411.
5. If the connection between the remote temperature
sensor and the TMP411 is between 8 inches and 12
feet long, use a twisted-wire pair connection. Beyond
this distance (up to 100 feet), use a twisted, shielded
pair with the shield grounded as close to the TMP411
as possible. Leave the remote sensor connection end
of the shield wire open to avoid ground loops and
60Hz pickup.
planes to shield them from extrinsic
DD
(1)
GND
(1)
D+
(1)
−
D
(1)
GND
NOTE: (1) 5 mil traces with 5 mil spacing.
Figure 18. Example Signal Traces
0.1µF Capacitor
V+
PCB Via
1
2
3
4
TMP411
www.ti.com
Ground or V+ layer
on bottom and/or
top, if possible.
GND
PCB Via
8
7
6
5
22
Figure 19. Suggested Bypass Capacitor
Placement
PACKAGE OPTION ADDENDUM
www.ti.com
19-Feb-2007
PACKAGING INFORMATION
Orderable DeviceStatus
(1)
Package
Type
Package
Drawing
Pins Package
Qty
Eco Plan
TMP411ADGKRACTIVEMSOPDGK82500 Green (RoHS &
no Sb/Br)
TMP411ADGKRG4ACTIVEMSOPDGK82500 Green (RoHS &
no Sb/Br)
TMP411ADGKTACTIVEMSOPDGK8250 Green (RoHS &
no Sb/Br)
TMP411ADGKTG4ACTIVEMSOPDGK8250 Green (RoHS &
no Sb/Br)
TMP411BDGKRACTIVEMSOPDGK82500 Green (RoHS &
no Sb/Br)
TMP411BDGKRG4ACTIVEMSOPDGK82500 Green (RoHS &
no Sb/Br)
TMP411BDGKTACTIVEMSOPDGK8250 Green (RoHS &
no Sb/Br)
TMP411BDGKTG4ACTIVEMSOPDGK8250 Green (RoHS &
no Sb/Br)
(1)
The marketing status values are defined as follows:
ACTIVE: Product device recommended for new designs.
LIFEBUY: TI has announced that the device will be discontinued, and a lifetime-buy period is in effect.
NRND: Not recommended for new designs. Device is in production to support existing customers, but TI does not recommend using this part in
a new design.
PREVIEW: Device has been announced but is not in production. Samples may or may not be available.
OBSOLETE: TI has discontinued the production of the device.
(2)
Lead/Ball Finish MSL Peak Temp
CU NIPDAULevel-2-260C-1 YEAR
CU NIPDAULevel-2-260C-1 YEAR
CU NIPDAULevel-2-260C-1 YEAR
CU NIPDAULevel-2-260C-1 YEAR
CU NIPDAULevel-2-260C-1 YEAR
CU NIPDAULevel-2-260C-1 YEAR
CU NIPDAULevel-2-260C-1 YEAR
CU NIPDAULevel-2-260C-1 YEAR
(3)
(2)
Eco Plan - The planned eco-friendly classification: Pb-Free (RoHS), Pb-Free (RoHS Exempt), or Green (RoHS & no Sb/Br) - please check
http://www.ti.com/productcontent for the latest availability information and additional product content details.
TBD: The Pb-Free/Green conversion plan has not been defined.
Pb-Free (RoHS): TI's terms "Lead-Free" or "Pb-Free" mean semiconductor products that are compatible with the current RoHS requirements
for all 6 substances, including the requirement that lead not exceed 0.1% by weight in homogeneous materials. Where designed to be soldered
at high temperatures, TI Pb-Free products are suitable for use in specified lead-free processes.
Pb-Free (RoHS Exempt): This component has a RoHS exemption for either 1) lead-based flip-chip solder bumps used between the die and
package, or 2) lead-based die adhesive used between the die and leadframe. The component is otherwise considered Pb-Free (RoHS
compatible) as defined above.
Green (RoHS & no Sb/Br): TI defines "Green" to mean Pb-Free (RoHS compatible), and free of Bromine (Br) and Antimony (Sb) based flame
retardants (Br or Sb do not exceed 0.1% by weight in homogeneous material)
(3)
MSL, Peak Temp. -- The Moisture Sensitivity Level rating according to the JEDEC industry standard classifications, and peak solder
temperature.
Important Information and Disclaimer:The information provided on this page represents TI's knowledge and belief as of the date that it is
provided. TI bases its knowledge and belief on information provided by third parties, and makes no representation or warranty as to the
accuracy of such information. Efforts are underway to better integrate information from third parties. TI has taken and continues to take
reasonable steps to provide representative and accurate information but may not have conducted destructive testing or chemical analysis on
incoming materials and chemicals. TI and TI suppliers consider certain information to be proprietary, and thus CAS numbers and other limited
information may not be available for release.
In no event shall TI's liability arising out of such information exceed the total purchase price of the TI part(s) at issue in this document sold by TI
to Customer on an annual basis.