Testo Testo 317-2 Manual

testo 317-2
gas detector
Instruction manual en
General notes
Please read this documentation through carefully and familiarise yourself with the operation of the product before put­ting it to use. Keep this document to hand so that you can refer to it when necessary.
99 Washington Street Melrose, MA 02176
Phone 781-665-1400 Toll Free 1-800-517-8431
Visit us at www.TestEquipmentDepot.com
Operation
Switch-on
Switch detector on in fresh air since the sensor is initialised when switched on
DDeetteeccttoorr ooffff
SSeeggmmeenntt tteesstt
HHeeaattiinngg uupp pphhaassee//SSeellff-tteesstt
RReeaaddyy ttoo ooppeerraattee
Safety Information
Avoid electrical hazards:
Do not measure on or near live parts.
Protect instrument:
Never store instrument together with solvents (e.g. acetone).
Preserving product safety / warranty claims:
Operate the instrument only within the parameters specified in the Technical data.
Operate the instrument properly and according to its intended purpose.
Do not use force. Open the instrument only when this is expressly described in
the documentation for maintenance or service purposes.
Ensure correct disposal:
Disposal of defective rechargeable batteries and spent batter­ies at the collection points provided.
Send the instrument directly to us at the end of its life cycle. We will ensure that it is disposed of in an environmentally friendly manner.
Intended Use
testo 317-2 is a practical gas detector which detects methane (CH
) and propane gas (C3H8).
4
Do not use the testo gas detector as a monitoring instrument for your own personal safety!
Technical Data
Feature Values
Concentration ranges 0 to 20,000ppm CH4, 0 to 10,000 ppm C3H8 Display 8 segment trend display Alarm thresholds 10,000ppm CH4, 20% LEL, 5,000ppm C3H8, 20% LEL Lower response thresholds 100ppm CH4, 50ppm C3H8 Response time t90 <5s Heating-up time 60s Power supply 2 batteries, type micro AAA 1.5 V (LR03) Battery life Approx. 4h Transport/Storage temperature -20 to +50°C Ambient temperature -5 to +45°C Audible signal emitter 85 dB (A) EU directive 89/336/EEC Warranty 2 years
1s
60s
Readiness to operate is indicated by an audible signal.
Detecing leaks
Position the detector such that the sensor opening (orange) is purged by the ambient air in the area under scrutiny. Avoid covering the surface of the sensor.
- The 8 bar symbols change to black according to the concen­trations detected and the frequency of the audible signal rises with increasing gas concentrations.
- If the alarm value is exceeded, a continuous tone is emitted and the alarm symbol ( ) lights up.
Switch-off
RReeaaddyy ttoo ooppeerraattee
DDeetteeccttoorr ooffff
3s
Maintenance and Service
Changing the battery
1
Open battery section
2
Remove spent batteries and replace with new ones. Observe +/-.
3
Close battery section.
Cleaning the detector
The detector housing should be cleaned with a damp cloth (soap water) if dirty. Do not use abrasive cleaning agents or solvents.
Troubleshooting
Problem Possible causes Remedy
lights up in display. Battery life <15min. Change batteries.
Detector cannot be Batteries are spent. Change batteries. switched on.
Error lights up in display. Detector lay for a longer Clean sensor by
period of time in heavily repeatedly switching on contaminated air or the detector, letting it heat up sensor is clogged with and switching it off again dirt. If the Error message still
does not disappear after detector has been switched on several times, switch it off and contact Testo Customer Service or your nearest Testo dealer.
Spare parts
Name Part no
Carrying loop 0516 3181 Carrying loop with belt clip 0516 0317