Testo 6383 Data sheet

Committing to the future
testo 6383
Differential pressure transmitter in cleanroom-conform panel design
SPECIFICATIONS
testo 6383
The differential pressure transmitter testo 6383 was developed specially for monitoring low differential pressures in the measuring range from 10 Pa to 10 hPa. In cleanroom technology, the maintenance of positive pressure prevents the entry of contaminated air in critical zones. Thanks to an optional internal or external probe from the probe series 6610, the additional recording of humidity and temperature with one instrument is also possible.
Subject to change without notice.
SPECIFICATIONS
testo 6383
• Measurement of differential pressure; optional: humidity and temperature
• Automatic zero-point adjustment guarantees high, temperature-independent accuracy and long-term stability
• Low measurement range up to 10 Pa ensures highest precision at lowest pressures
• Flat housing allows flush surface integration in the cleanroom wall
• Display with multi-language operating menu and optical alarm display
• Ethernet, relay and analog outputs allow optimum integration into individual automation systems
The testo 6383 is particularly outstanding thanks to the automatioc zero-point adjustment which ensures high accuracy and long-term stability.
The integrated self-monitoring and early warning function also guarantees the operator high system availability.
Areas of application:
• Monitoring positive and negative pressure in cleanrooms, operating theatres and isolation rooms
• Optional monitoring of humidity and temperature in cleanrooms
Status 12.02.2010
• Self-monitoring of the transmitter and early warning function guarantee high system availablity
• The P2A software for parameterization, adjustment and analysis saves time and costs in commissioning and maintenance
• Scalability of ±50 percent of the measuring range final value and free scalability within the measuring range
• Configurable alarm management with adjustable response delay and alarm acknowledgement
tteessttoo
AG · Testo-Strasse 1 · D-79853 Lenzkirch · www.testo.com
Page 1/4
DS 6383 EN/msp/A/12.02.2010
Differential pressure transmitter in cleanroom-conform panel design
Technical data
testo 6383
Parameters
ifferential pressure
D
easuring range 0 to 10 Pa
M
Measurement uncertainty* ±0.3% of measurement range final value
electable units Differential pressure in Pa, hPa, kPa,
S
Sensor Piezoresistive sensor
Autom. Zero-point adjustment
verload
O
Parameters
Humidity/temperature optional
Probe
Type
Parameters
Integrated probe
%RH / °C/°F / °Ctd/ °Ftd/ g/kg / gr/lb / g/m3 / gr/ft³ / ppmV / °Cwb
testo 6613 testo 6614 testo 6615 testo 6617
Channel Duct heated Cable trace
/ °Fwb / kJ/kg / mbar / inch H
MMeeaass.. rraannggee
Humidity / trace humidity
Temperature
-20 to +70 °C
-4 to +158 °F
MMeeaassuurreemmeenntt uunncceerrttaaiinnttyy**
Humidity
Integrated probe
±1.0 %RH for 0 to 90 %RH /
±1.4 %RH for 90 to 100 % RH
testo 6613 testo 6614 testo 6615 testo 6617
for deviations from media temp. ±25 °C:±0.02 %RH/K
Dewpoint
Temp. at +25°C /
±0.15 °C / 32.2 °F Pt1000 1/3 Class B
+77°F
Subject to change without notice.
10 to +10 Pa
to 50 Pa
0 0 to 100 Pa 0 to 500 Pa 0 to 10 hPa
­50 to +50 Pa
-
-100 to +100 Pa
-500 to +500 Pa
-10 to +10 hPa
±0.3 Pa Temperature gain drift: 0.02% of
easuring range per Kelvin deviaton
m
rom nominal temperature 22 °C
f
ero point drift: 0% (thanks to cyclic
Z
ero-point adjustment)
z
2
, kg/cm
bar, bar, mmH
m
G, inch H
H
O
2
O
2
PSI, inch
,
via magnetic valve Frequency adjustable: 15 sec, 30 sec, 1 min, 5 min, 10 min
MMeeaassuurriinngg rraannggeeOOvveerrllooaad
d
0 to 10 Pa 20000 Pa
to 50 Pa 20000 Pa
0 0 to 100 Pa 20000 Pa 0 to 500 Pa 20000 Pa
to 10 hPa 200 hPa
0
-10 to 10 Pa 20000 Pa
-50 to 50 Pa 20000 Pa
-100 to 100 Pa 20000 Pa
-500 to 500 Pa 20000 Pa
-10 to 10 hPa 200 hPa
Cable with
humidity
cover elec­trode moni­toring
O / °Ctm (H2O2)/°Ftm (H2O2) / % Vol
2
0 to 100 %RH -60 to +30 °C td 0 to 100 %RH
-40 to +180 °C
-40 to +356 °F
±1.0 %RH for 0
to100 %RH
-40 to +120 °C
-40 to +248 °F
±1 K at
0 °C
td
±2 K at
-40°C
td
±4 K at
-50 °C
td
±0.15 °C/
32.2 °F
Pt100 1/3 Class B
-40 to +180 °C
-40 to +356 °F
±1.2 %RH for 0 to 90 %RH /
±1.6 %RH for 90
to 100 %RH
±0.15 °C/
32.2 °F
Pt1000 1/3 Class
B
Inputs/outputs
nalog outputs
A
uantity Standard: 1;
Q
ith optional humidity probe: 3
w
Output type 0/4 to 20 mA (4-wire) (24 VAC/DC)
0 to 1/5 to 10 V (4-wire) (24 VAC/DC)
Scaling Differential pressure: scalable ±50% of
measuring range final value;
reely scalable within measuring range
f
Meas. cycle 1/sec
esolution 12 bit
R
Max. load max. 500
ther outputs
O
Ethernet Optional
Relay Optional: 4 relays (free allocation to
measurement channels or as collective alarm in operating menu/P2A), up to
50 VAC/3A (NO or NC)
2
Digital Mini-DIN for P2A software
Supply
oltage supply 20 to 30 VAC/DC, 300 mA current
V
consumption, galvanically separate signal and supply line
General technical data
Model
Material Front plate stainless steel, housing
plastic
Dimensions without humidity/temperature:
246 x 161 x 47 mm with humidity/temperature: 396 x 161 x 78 mm
Weight Version without humidity: 0.9 kg;
Version with integrated humidity probe:1.35 kg; version with preparation for external humidity probe: 1.26 kg
Display
Display optional: 3-line LCD with
multi-language operating menu
Resolution
Differential pressure
MMeeaassuurriinngg rraannggee RReessoolluuttiioonn
0 to 10 Pa 0.1 Pa 0 to 50 Pa 0.1 Pa 0 to 100 Pa 0.1 Pa 0 to 500 Pa 0.1 Pa 0 to 10 hPa 0.01 hPa
-10 to 10 Pa 0.1 Pa
-50 to 50 Pa 0.1 Pa
-100 to 100 Pa 0.1 Pa
-500 to 500 Pa 0.1 Pa
-10 to 10 hPa 0.01 hPa
Humidity
Temperature
0.1 %RH
0.01 °C / 0.01 °F
Miscellaneous
Protection class IP 65
Operating conditions
With / without display
Operation temperature -5 to +50 °C / +23 to +122 °F
Storage temperature -20 to +60 °C / -4 to +140 °F
Process temperature -20 to +65 °C / -4 to +149 °F
* Measurement inaccuracy according to GUM. measurement range final value ±0.3 Pa; inaccuracy contribution +0.007 * MW (in %RH). UU
ncertainty in MMeasurement): ISO guideline for the determination of measurement inaccuracy, in order to make measurements comparable worldwide. The following inaccuracies are used for the determination: hysteresis, linearity, reproducibility, long-term stability (only for differential pressure), adjustment site/factory calibration, test site.
FFoorr ddiiffffeerree nnttiiaall pprreessssuurree::
FFoorr hhuummiiddiittyy::
Additional humidity-dependent
GGUUMM(GG
0.5% of
uide to the Expression of
Status 12.02.2010
Page 2/4
DS 6383 EN/msp/A/12.02.2010
tteessttoo
AG · Testo-Strasse 1 · D-79853 Lenzkirch · www.testo.com
+
-
+
-
+
-
+
-
+
-
CH1
CH2 CH3
24V
1
20-30 V AC/DC
0V
Differential pressure transmitter in cleanroom-conform panel design
Technical drawings
161 mm
3 mm
161 mm
3 mm 3 mm
61 mm
1
testo 6383
246 mm
47 mm
Connection plan
396 mm
78 mm
396 mm
47 mm
Subject to change without notice.
tteessttoo
AG · Testo-Strasse 1 · D-79853 Lenzkirch · www.testo.com
Page 3/4
DS 6383 EN/msp/A/12.02.2010 Status 12.02.2010
Differential pressure transmitter in cleanroom-conform panel design
The following options can be specified for the testo 6383:
testo 6383
AXX Messbereich
AXX Measuring range
BXX Analogausgang / Versorgung
BXX Analog display/supply
XX Display
XX Display / menu language
C
C
XX Gehäusefarbe
XX Integrated humidity probe
E
D
XX Einheit
XX Ethernet
F
E
FXX Differential pressure unit (pre-set)
KXX Sprache der Bedienungsanleitung
(für zweisprachige Papier-Bedienungs -
GXX opt. Analog output for humidity probe
nleitung)
a connection (probe series testo 6610) units
pre-set)
(
HXX Relay
IXX Units channel 3 (pre-set, only if opt.
humidity probe connection available)
KXX Instruction manual language
Example:
Order code for transmitter testo 6383 with the following options:
- Measuring range -10 to 10 Pa
- Analog output 4 to 20 mA (4-wire,, 24 VAC/DC)
- with German display
- preparation for external humidity/ temperature probe testo 6610
- with Ethernet module
- Differential pressure unit kg/cm² / min / max
- opt. Analog output for °Ctd / min / max
- without relay
- Unit channel 3 g/m³ / min / max
- Instruction manual language German/English
AXX Measuring range
A01 0 to 10 Pa A02 0 to 50 Pa A03 0 to 100 Pa
04 0 to 500 Pa
A
05 0 to 10 hPa
A
21 -10 to 10 Pa
A A22 -50 to 50 Pa A23 -100 to 100 Pa A24 -500 to 500 Pa A25 -10 to 10 hPa
BXX Analog display / supply
02 0 to 1 V (4-wire, 24 VAC/DC)
B B03 0 to 5 V (4-wire, 24 VAC/DC) B04 0 to 10 V (4-wire, 24 VAC/DC) B05 0 to 20 mA (4-wire, 24 VAC/DC) B06 4 to 20 mA (4-wire, 24 VAC/DC)
XX Display / menu language
C
00 without display
C
02 with display/English
C C03 with display/German C04 with display/French C05 with display/Spanish C06 with display/Italian C07 with display/Japanese
08 with display/Swedish
C
XX Integrated humidity probe
D
D00 no humidity/temperature probe D04 humidity probe integrated in panel D05 preparation for external humidity/
temperature probe testo 6610
EXX Ethernet
E00 without Ethernet module E01 with Ethernet module
FXX Differential pressure unit (pre-set)
F01 Pa / min / max F02 hPa / min / max F03 kPa / min / max F04 mbar / min / max F05 bar / min / max F06 mmH F07 mmH F08 inch HG / min / max F09 kg/cm² / min / max F10 PSI / min / max
O / min / max
2
O / min / max
2
Scaling: 50% of measuring range final value; freely selectable within measuring range
GXX opt. Analog output for humidity probe
connection (probe series testo 6610) units
pre-set)
(
G01 %RH / min / max G02 °C/Min/Max
03 °F/Min/Max
G
04 °Ctd / min / max
G
05 °Ftd / min / max
G G06 g/kg / min / max G07 gr/lb /Min/Max G08 g/m³ / min / max G09 gr/ft³ / min / max
10 ppmV / min / max
G
11 °Cwb / min / max
G G12 °Fwb / min / max G13 kJ/kg / min / max (enthalpy) G14 mbar / min / max (water vapour partial pressure) G15 inch H
16 °Ctm (mixture dewpoint for H
G
17 °Ftm (mixture dewpoint for H
G G18 % Vol
HXX Relay
H00 without relay H01 4 relay outputs, limit value monitoring H02 4 relay outputs, channel 1 limit values and
XX Units channel 3 (pre-set, only if opt. humidity
I
I01 % RH/Min/Max I02 °C/Min/Max I03 °F/Min/Max I04 °Ctd / min / max I05 °Ftd / min / max I06 g/kg / min / max I07 gr/lb /Min/Max I08 g/m³ / min / max I09 gr/ft³ / min / max I10 ppmV / min / max I11 °Cwb / min / max I12 °Fwb / min / max I13 kJ/kg / min / max (enthalpy) I14 mbar / min / max (water vapour partial pressure) I15 inch H
I16 °Ctm (mixture dewpoint for H I17 °Ftm (mixture dewpoint for H I18 % Vol
KXX Instruction manual language
K01 German/English instruction manual K02 French/English instruction manual K03 Spanish/English instruction manual K04 Italian/English instruction manual K05 Dutch/English instruction manual K06 Japanese/English instruction manual K07 Chinese/English instruction manual K08 Swedish/English instruction manual
O / min/ max (water vapour partial
2
pressure)
ollective alarm
c
probe connection available)
O / min/ max (water vapour partial
2
pressure)
2O2
2O2
2O2
2O2
)
)
)
)
0555 6383 A21 B06 C03 D05 E01 F09 G04 H00 I08 K01
only possible when D04 or
05 selected
D
only possible when D04 or D05 selected
Status 12.02.2010
Page 4/4
Subject to change without notice.
tteessttoo
AG · Testo-Strasse 1 · D-79853 Lenzkirch · www.testo.com
DS 6383 EN/msp/A/12.02.2010
testo 6383 / testo 6381 / testo 6351
Committing to the future
Differential Pressure Monitoring in Cleanroom Technology
Highest accuracy and long-term stability with the new transmitters from Testo
Differential pressure measurement in cleanroom applications
2
Input air via HEPA/ULPA filter
Typical exhaust air: (50 - 500
air exchanges / h)
Laminar flow e. g.
0.5 m/s
Outside zone
Critical zone
Normal zone
Whether in cleanrooms, greyrooms, OP theatres or filling systems:
Lowest differential pressures must be maintained between different rooms or zones in order to prevent contaminated air from entering.
For this reason, continuous measurement and regulation of these low differential pressures (according to cleanroom norm ISO 14644: 5 - 20 Pa) is required. Annual proof (against zero potential and against adjacent rooms) of this must be provided according to ISO 14644 .
Functional principle of the automatic zero-point adjustment of the Testo differential pressure transmitter
In hospitals and research laboratories, the pressure difference (negative pressure) prevents the spread of germs and dust
Pressure maintenance in cleanrooms
Cleanroom
Automatic zero-point adjustment guarantees highest, temperature-independent accuracy and long-term stability
The zero-point stability of differential pressure transmitters plays a particularly crucial role at lowest pressures (10 Pa or 50 Pa measurement range). Whereas conventional differential pressure transmitters require manual re­adjustment of the zero point, the new transmitter series from Testo is equipped with an automatic microprocessor-controlled zero-point adjustment. It ensures a low level of temperature-dependency of the pressure sensor, guaranteeing the user high accuracy and long-term stability. In the automatic zero-point adjustment, a magnetic valve causes both sides of the pressure sensor to be exposed to the same pressure a cyclic intervals. This guarantees highest accuracy in cleanroom processes!
Positive pressure in the filling room maintains the hygiene conditions during filling operations in the food and pharamceuticals industry
Defined pressure differences between cleanrooms and adjacent rooms ensure quality
Normal measurement Zero-point adjustment
Loading...
+ 12 hidden pages