Testo 6383 Data sheet

Committing to the future
testo 6383
Differential pressure transmitter in cleanroom-conform panel design
SPECIFICATIONS
testo 6383
The differential pressure transmitter testo 6383 was developed specially for monitoring low differential pressures in the measuring range from 10 Pa to 10 hPa. In cleanroom technology, the maintenance of positive pressure prevents the entry of contaminated air in critical zones. Thanks to an optional internal or external probe from the probe series 6610, the additional recording of humidity and temperature with one instrument is also possible.
Subject to change without notice.
SPECIFICATIONS
testo 6383
• Measurement of differential pressure; optional: humidity and temperature
• Automatic zero-point adjustment guarantees high, temperature-independent accuracy and long-term stability
• Low measurement range up to 10 Pa ensures highest precision at lowest pressures
• Flat housing allows flush surface integration in the cleanroom wall
• Display with multi-language operating menu and optical alarm display
• Ethernet, relay and analog outputs allow optimum integration into individual automation systems
The testo 6383 is particularly outstanding thanks to the automatioc zero-point adjustment which ensures high accuracy and long-term stability.
The integrated self-monitoring and early warning function also guarantees the operator high system availability.
Areas of application:
• Monitoring positive and negative pressure in cleanrooms, operating theatres and isolation rooms
• Optional monitoring of humidity and temperature in cleanrooms
Status 12.02.2010
• Self-monitoring of the transmitter and early warning function guarantee high system availablity
• The P2A software for parameterization, adjustment and analysis saves time and costs in commissioning and maintenance
• Scalability of ±50 percent of the measuring range final value and free scalability within the measuring range
• Configurable alarm management with adjustable response delay and alarm acknowledgement
tteessttoo
AG · Testo-Strasse 1 · D-79853 Lenzkirch · www.testo.com
Page 1/4
DS 6383 EN/msp/A/12.02.2010
Differential pressure transmitter in cleanroom-conform panel design
Technical data
testo 6383
Parameters
ifferential pressure
D
easuring range 0 to 10 Pa
M
Measurement uncertainty* ±0.3% of measurement range final value
electable units Differential pressure in Pa, hPa, kPa,
S
Sensor Piezoresistive sensor
Autom. Zero-point adjustment
verload
O
Parameters
Humidity/temperature optional
Probe
Type
Parameters
Integrated probe
%RH / °C/°F / °Ctd/ °Ftd/ g/kg / gr/lb / g/m3 / gr/ft³ / ppmV / °Cwb
testo 6613 testo 6614 testo 6615 testo 6617
Channel Duct heated Cable trace
/ °Fwb / kJ/kg / mbar / inch H
MMeeaass.. rraannggee
Humidity / trace humidity
Temperature
-20 to +70 °C
-4 to +158 °F
MMeeaassuurreemmeenntt uunncceerrttaaiinnttyy**
Humidity
Integrated probe
±1.0 %RH for 0 to 90 %RH /
±1.4 %RH for 90 to 100 % RH
testo 6613 testo 6614 testo 6615 testo 6617
for deviations from media temp. ±25 °C:±0.02 %RH/K
Dewpoint
Temp. at +25°C /
±0.15 °C / 32.2 °F Pt1000 1/3 Class B
+77°F
Subject to change without notice.
10 to +10 Pa
to 50 Pa
0 0 to 100 Pa 0 to 500 Pa 0 to 10 hPa
­50 to +50 Pa
-
-100 to +100 Pa
-500 to +500 Pa
-10 to +10 hPa
±0.3 Pa Temperature gain drift: 0.02% of
easuring range per Kelvin deviaton
m
rom nominal temperature 22 °C
f
ero point drift: 0% (thanks to cyclic
Z
ero-point adjustment)
z
2
, kg/cm
bar, bar, mmH
m
G, inch H
H
O
2
O
2
PSI, inch
,
via magnetic valve Frequency adjustable: 15 sec, 30 sec, 1 min, 5 min, 10 min
MMeeaassuurriinngg rraannggeeOOvveerrllooaad
d
0 to 10 Pa 20000 Pa
to 50 Pa 20000 Pa
0 0 to 100 Pa 20000 Pa 0 to 500 Pa 20000 Pa
to 10 hPa 200 hPa
0
-10 to 10 Pa 20000 Pa
-50 to 50 Pa 20000 Pa
-100 to 100 Pa 20000 Pa
-500 to 500 Pa 20000 Pa
-10 to 10 hPa 200 hPa
Cable with
humidity
cover elec­trode moni­toring
O / °Ctm (H2O2)/°Ftm (H2O2) / % Vol
2
0 to 100 %RH -60 to +30 °C td 0 to 100 %RH
-40 to +180 °C
-40 to +356 °F
±1.0 %RH for 0
to100 %RH
-40 to +120 °C
-40 to +248 °F
±1 K at
0 °C
td
±2 K at
-40°C
td
±4 K at
-50 °C
td
±0.15 °C/
32.2 °F
Pt100 1/3 Class B
-40 to +180 °C
-40 to +356 °F
±1.2 %RH for 0 to 90 %RH /
±1.6 %RH for 90
to 100 %RH
±0.15 °C/
32.2 °F
Pt1000 1/3 Class
B
Inputs/outputs
nalog outputs
A
uantity Standard: 1;
Q
ith optional humidity probe: 3
w
Output type 0/4 to 20 mA (4-wire) (24 VAC/DC)
0 to 1/5 to 10 V (4-wire) (24 VAC/DC)
Scaling Differential pressure: scalable ±50% of
measuring range final value;
reely scalable within measuring range
f
Meas. cycle 1/sec
esolution 12 bit
R
Max. load max. 500
ther outputs
O
Ethernet Optional
Relay Optional: 4 relays (free allocation to
measurement channels or as collective alarm in operating menu/P2A), up to
50 VAC/3A (NO or NC)
2
Digital Mini-DIN for P2A software
Supply
oltage supply 20 to 30 VAC/DC, 300 mA current
V
consumption, galvanically separate signal and supply line
General technical data
Model
Material Front plate stainless steel, housing
plastic
Dimensions without humidity/temperature:
246 x 161 x 47 mm with humidity/temperature: 396 x 161 x 78 mm
Weight Version without humidity: 0.9 kg;
Version with integrated humidity probe:1.35 kg; version with preparation for external humidity probe: 1.26 kg
Display
Display optional: 3-line LCD with
multi-language operating menu
Resolution
Differential pressure
MMeeaassuurriinngg rraannggee RReessoolluuttiioonn
0 to 10 Pa 0.1 Pa 0 to 50 Pa 0.1 Pa 0 to 100 Pa 0.1 Pa 0 to 500 Pa 0.1 Pa 0 to 10 hPa 0.01 hPa
-10 to 10 Pa 0.1 Pa
-50 to 50 Pa 0.1 Pa
-100 to 100 Pa 0.1 Pa
-500 to 500 Pa 0.1 Pa
-10 to 10 hPa 0.01 hPa
Humidity
Temperature
0.1 %RH
0.01 °C / 0.01 °F
Miscellaneous
Protection class IP 65
Operating conditions
With / without display
Operation temperature -5 to +50 °C / +23 to +122 °F
Storage temperature -20 to +60 °C / -4 to +140 °F
Process temperature -20 to +65 °C / -4 to +149 °F
* Measurement inaccuracy according to GUM. measurement range final value ±0.3 Pa; inaccuracy contribution +0.007 * MW (in %RH). UU
ncertainty in MMeasurement): ISO guideline for the determination of measurement inaccuracy, in order to make measurements comparable worldwide. The following inaccuracies are used for the determination: hysteresis, linearity, reproducibility, long-term stability (only for differential pressure), adjustment site/factory calibration, test site.
FFoorr ddiiffffeerree nnttiiaall pprreessssuurree::
FFoorr hhuummiiddiittyy::
Additional humidity-dependent
GGUUMM(GG
0.5% of
uide to the Expression of
Status 12.02.2010
Page 2/4
DS 6383 EN/msp/A/12.02.2010
tteessttoo
AG · Testo-Strasse 1 · D-79853 Lenzkirch · www.testo.com
+
-
+
-
+
-
+
-
+
-
CH1
CH2 CH3
24V
1
20-30 V AC/DC
0V
Differential pressure transmitter in cleanroom-conform panel design
Technical drawings
161 mm
3 mm
161 mm
3 mm 3 mm
61 mm
1
testo 6383
246 mm
47 mm
Connection plan
396 mm
78 mm
396 mm
47 mm
Subject to change without notice.
tteessttoo
AG · Testo-Strasse 1 · D-79853 Lenzkirch · www.testo.com
Page 3/4
DS 6383 EN/msp/A/12.02.2010 Status 12.02.2010
Differential pressure transmitter in cleanroom-conform panel design
The following options can be specified for the testo 6383:
testo 6383
AXX Messbereich
AXX Measuring range
BXX Analogausgang / Versorgung
BXX Analog display/supply
XX Display
XX Display / menu language
C
C
XX Gehäusefarbe
XX Integrated humidity probe
E
D
XX Einheit
XX Ethernet
F
E
FXX Differential pressure unit (pre-set)
KXX Sprache der Bedienungsanleitung
(für zweisprachige Papier-Bedienungs -
GXX opt. Analog output for humidity probe
nleitung)
a connection (probe series testo 6610) units
pre-set)
(
HXX Relay
IXX Units channel 3 (pre-set, only if opt.
humidity probe connection available)
KXX Instruction manual language
Example:
Order code for transmitter testo 6383 with the following options:
- Measuring range -10 to 10 Pa
- Analog output 4 to 20 mA (4-wire,, 24 VAC/DC)
- with German display
- preparation for external humidity/ temperature probe testo 6610
- with Ethernet module
- Differential pressure unit kg/cm² / min / max
- opt. Analog output for °Ctd / min / max
- without relay
- Unit channel 3 g/m³ / min / max
- Instruction manual language German/English
AXX Measuring range
A01 0 to 10 Pa A02 0 to 50 Pa A03 0 to 100 Pa
04 0 to 500 Pa
A
05 0 to 10 hPa
A
21 -10 to 10 Pa
A A22 -50 to 50 Pa A23 -100 to 100 Pa A24 -500 to 500 Pa A25 -10 to 10 hPa
BXX Analog display / supply
02 0 to 1 V (4-wire, 24 VAC/DC)
B B03 0 to 5 V (4-wire, 24 VAC/DC) B04 0 to 10 V (4-wire, 24 VAC/DC) B05 0 to 20 mA (4-wire, 24 VAC/DC) B06 4 to 20 mA (4-wire, 24 VAC/DC)
XX Display / menu language
C
00 without display
C
02 with display/English
C C03 with display/German C04 with display/French C05 with display/Spanish C06 with display/Italian C07 with display/Japanese
08 with display/Swedish
C
XX Integrated humidity probe
D
D00 no humidity/temperature probe D04 humidity probe integrated in panel D05 preparation for external humidity/
temperature probe testo 6610
EXX Ethernet
E00 without Ethernet module E01 with Ethernet module
FXX Differential pressure unit (pre-set)
F01 Pa / min / max F02 hPa / min / max F03 kPa / min / max F04 mbar / min / max F05 bar / min / max F06 mmH F07 mmH F08 inch HG / min / max F09 kg/cm² / min / max F10 PSI / min / max
O / min / max
2
O / min / max
2
Scaling: 50% of measuring range final value; freely selectable within measuring range
GXX opt. Analog output for humidity probe
connection (probe series testo 6610) units
pre-set)
(
G01 %RH / min / max G02 °C/Min/Max
03 °F/Min/Max
G
04 °Ctd / min / max
G
05 °Ftd / min / max
G G06 g/kg / min / max G07 gr/lb /Min/Max G08 g/m³ / min / max G09 gr/ft³ / min / max
10 ppmV / min / max
G
11 °Cwb / min / max
G G12 °Fwb / min / max G13 kJ/kg / min / max (enthalpy) G14 mbar / min / max (water vapour partial pressure) G15 inch H
16 °Ctm (mixture dewpoint for H
G
17 °Ftm (mixture dewpoint for H
G G18 % Vol
HXX Relay
H00 without relay H01 4 relay outputs, limit value monitoring H02 4 relay outputs, channel 1 limit values and
XX Units channel 3 (pre-set, only if opt. humidity
I
I01 % RH/Min/Max I02 °C/Min/Max I03 °F/Min/Max I04 °Ctd / min / max I05 °Ftd / min / max I06 g/kg / min / max I07 gr/lb /Min/Max I08 g/m³ / min / max I09 gr/ft³ / min / max I10 ppmV / min / max I11 °Cwb / min / max I12 °Fwb / min / max I13 kJ/kg / min / max (enthalpy) I14 mbar / min / max (water vapour partial pressure) I15 inch H
I16 °Ctm (mixture dewpoint for H I17 °Ftm (mixture dewpoint for H I18 % Vol
KXX Instruction manual language
K01 German/English instruction manual K02 French/English instruction manual K03 Spanish/English instruction manual K04 Italian/English instruction manual K05 Dutch/English instruction manual K06 Japanese/English instruction manual K07 Chinese/English instruction manual K08 Swedish/English instruction manual
O / min/ max (water vapour partial
2
pressure)
ollective alarm
c
probe connection available)
O / min/ max (water vapour partial
2
pressure)
2O2
2O2
2O2
2O2
)
)
)
)
0555 6383 A21 B06 C03 D05 E01 F09 G04 H00 I08 K01
only possible when D04 or
05 selected
D
only possible when D04 or D05 selected
Status 12.02.2010
Page 4/4
Subject to change without notice.
tteessttoo
AG · Testo-Strasse 1 · D-79853 Lenzkirch · www.testo.com
DS 6383 EN/msp/A/12.02.2010
testo 6383 / testo 6381 / testo 6351
Committing to the future
Differential Pressure Monitoring in Cleanroom Technology
Highest accuracy and long-term stability with the new transmitters from Testo
Differential pressure measurement in cleanroom applications
2
Input air via HEPA/ULPA filter
Typical exhaust air: (50 - 500
air exchanges / h)
Laminar flow e. g.
0.5 m/s
Outside zone
Critical zone
Normal zone
Whether in cleanrooms, greyrooms, OP theatres or filling systems:
Lowest differential pressures must be maintained between different rooms or zones in order to prevent contaminated air from entering.
For this reason, continuous measurement and regulation of these low differential pressures (according to cleanroom norm ISO 14644: 5 - 20 Pa) is required. Annual proof (against zero potential and against adjacent rooms) of this must be provided according to ISO 14644 .
Functional principle of the automatic zero-point adjustment of the Testo differential pressure transmitter
In hospitals and research laboratories, the pressure difference (negative pressure) prevents the spread of germs and dust
Pressure maintenance in cleanrooms
Cleanroom
Automatic zero-point adjustment guarantees highest, temperature-independent accuracy and long-term stability
The zero-point stability of differential pressure transmitters plays a particularly crucial role at lowest pressures (10 Pa or 50 Pa measurement range). Whereas conventional differential pressure transmitters require manual re­adjustment of the zero point, the new transmitter series from Testo is equipped with an automatic microprocessor-controlled zero-point adjustment. It ensures a low level of temperature-dependency of the pressure sensor, guaranteeing the user high accuracy and long-term stability. In the automatic zero-point adjustment, a magnetic valve causes both sides of the pressure sensor to be exposed to the same pressure a cyclic intervals. This guarantees highest accuracy in cleanroom processes!
Positive pressure in the filling room maintains the hygiene conditions during filling operations in the food and pharamceuticals industry
Defined pressure differences between cleanrooms and adjacent rooms ensure quality
Normal measurement Zero-point adjustment
Overview of differential pressure transmitters from Testo
3
testo 6383
Parameters
Selectable measuring ranges Housing
Area of application:
Usual installation site in cleanroom
Differential pressure Optional: humidity/temperature
testo 6381
Differential pressure Flow velocity Volume flow Optional: Humidity/temperature
testo 6351
Differential pressure Flow velocity Volume flow
10 Pa to 10 hPa 10 Pa to 1000 hPa 50 Pa to 2000 hPa Flat stainless steel housing for
flush wall installation (panel design)
Metal housing Plastic housing
Critical zone: Surface flush installation in cleanroom wall
Normal zone or outside zone
Normal zone or outside zone
Differential pressure monitoring between cleanrooms (optional: simultaneous measurement of temperature and humidity)
Monitoring positive and negative pressure in cleanrooms, operating theatres and isolation rooms
Additional monitoring of humidity and temperature in cleanrooms (optional)
Differential pressure monitoring between cleanrooms (optional: simultaneous measurement of temperature and humidity)
Differential pressure monitoring in filling processes and spray­painting systems
Monitoring drying processes
Differential pressure monitoring
between cleanrooms
Differential pressure monitoring in filling processes in the process industry
Critical air conditioning technology (VAC systems)
Optimizing processes and saving time in commissioning and maintenance
The Testo transmitters are delivered ready to use. For professional application, the following functions are available via the easy-to-use software:
–Parameterization of unit and scale –Sensor adjustment and adjustment of the analog outputs
(humidity: 1-point, 2-point; pressure: n-point)
–Parameterization and adjustment history of all activities of the
P2A software are registered in the PC
An adjustment of the entire signal chain is possible directly at the measurement site thanks to the external interface. This saves time in commissioning and maintenance.
In addition to this, complete parameter files can be stored in the PC. The parameterization of spare transmitters or similar measuring points is thus possible with minimal time expenditure.
Ethernet networking
– Integration of the transmitters into customers’ Ethernet network – Integration of the transmitters into measurement data monitoring systems, e.g. testo Saveris
TM
Using the P2A software, unit and scale can be easily parameterized, for example
Differential pressure transmitters for installation in critical zones
testo 6383 – Overview of features and benefits:
· Measurement of differential pressure, optional:humidity and temperature
· Automatic zero-point adjustment guarantees high, temperature­independent accuracy and long-term stability
· Low measurement range up to 10 Pa ensures highest precision at lowest pressures
· Flat housing allows flush surface integration in the cleanroom wall
4
testo 6383 for differential pressure measurement
testo 6383 with integrated humidity probe
· Combination of differential pressure, humidity, and temperature measurement in one instrument saves investment costs (exchangeable digital humidity probes see page 10)
· Display with multi-language operating menu and optical alarm display
· Ethernet, relay and analog outputs allow optimum integration into individual automation systems
· Self-monitoring of the transmitters guarantees high system availability
· The P2A software for parameterization, adjustment and analysis saves time and costs in commissioning and maintenance
· Scalable measuring range by ±50 percent of the measuring range final value, and free scalability within the measuring range, allow optimum adaptation to the control requirements
Areas of application:
· Monitoring positive and negative pressure in cleanrooms, operating theatres and isolation rooms
· Additional monitoring of humidity and temperature in cleanrooms (optional)
Configuration options testo 6383:
This results in a typical ordering code:
0555 6383 AXX BXX CXX DXX EXX FXX GXX HXX IXX KXX
B02 B03 B04 B05 B06
C00 C02 C03 C04 C05 C06 C07 C08
K01 K02 K03 K04 K05 K06 K07 K08
D00 D04 D05
H00 H01
H02 F01 F02 F03 F04 F05 F06 F07 F08 F09 F10
G01 G02 G03 G04 G05 G06 G07 G08 G09 G10 G11 G12 G13 G14
G15
G16 G17
B02 0 to 1 V (4-wire, 24 VAC/DC) B03 0 to 5 V (4-wire, 24 VAC/DC) B04 0 to 10 V (4-wire, 24 VAC/DC) B05 0 to 20 mA (4-wire, 24 VAC/DC) B06 4 to 20 mA (4-wire, 24 VAC/DC)
without display without operating buttons with display, with operating buttons / English with display, with operating buttons / German with display, with operating buttons / French with display, with operating buttons / Spanish with display, with operating buttons / Italian with display, with operating buttons / Japanese with display, with operating buttons / Swedish
no humidity/temperature probe humidity/temperature probe integrated in panel preparation for external humidity/ temperature probe testo 6610
Pa / min / max hPa / min / max kPa / min / max mbar / min / max bar / min / max mmH
2
O / min / max
mmH
2
O / min / max inch HG / min / max kg/cm² / min / max PSI / min / max
% RH/Min/Max °C/Min/Max °F/Min/Max °C
td
/ min / max
°F
td
/ min / max g/kg / min / max gr/lb /Min/Max g/m³ / min / max gr/ft³ / min / max ppmV / min / max °C
wb
/ min / max
°F
wb
/ min / max kJ/kg /Min/Max (enthalpy) hPa /min/max (water vapour partial pressure) mmH
2
O / min / max (Water vapour partial pressure) °C
tm
(mixture dewpoint for H2O2)
°F
tm
(mixture dewpoint for H2O2)
without relay 4 relay outputs, limit value monitoring 4 relay outputs, channel 1 limit values and collective alarm
German/English instruction manual French/English instruction manual Spanish/English instruction manual Italian/English instruction manual Dutch/English instruction manual Japanese/English instruction manual Chinese/English instruction manual Swedish/English instruction manual
Order no. 0555 6383
A01 Bxx Cxx Dxx Exx Fxx Gxx Hxx Ixx Kxx
E00 E01
without Ethernet module with Ethernet module
Axx Measuring range Bxx Analog display/supply Cxx Display Dxx Integrated humidity probe Exx Ethernet Fxx Differential pressure unit (pre-set) Gxx opt. Analog output for humidity
probe connection testo 6610 / units (pre-set) Hxx Relay Ixx Units channel 3 (pre-set, only if opt. humidity probe connection
available) Kxx IM languages (for bilingual printed IMs)
A01 A02 A03 A04 A05 A21 A22 A23 A24 A25
0 to 10 Pa 0 to 50 Pa 0 to 100 Pa 0 to 500 Pa 0 to 10 hPa
-10 to 10 Pa
-50 to 50 Pa
-100 to 100 Pa
-500 to 500 Pa
-10 to 10 hPa
I01 I02 I03 I04 I05 I06 I07 I08 I09 I10 I11 I12 I13 I14
I15
I16 I17
% RH/Min/Max °C/Min/Max °F/Min/Max °C
td
/ min / max
°F
td
/ min / max g/kg / min / max gr/lb /Min/Max g/m³ / min / max gr/ft³ / min / max ppmV / min / max °C
wb
/ min / max
°F
wb
/ min / max kJ/kg /Min/Max (enthalpy) hPa /min/max (water vapour partial pressure) mmH
2
O / min / max (Water vapour partial pressure) °C
tm
(mixture dewpoint for H2O2)
°F
tm
(mixture dewpoint for H2O2)
Scaling: ±50% of measuring range; freely selectable within measuring range
Only with selection D04 orD05
Only with selection D04 or D05
5
testo 6383 – differential pressure, humidity and temperature
testo 6383
Supply
Display
Differential pressure
Analog outputs
Other outputs
Housing
Miscellaneous
Display
optional: 3-line LCD with multi-language operating menu
Technical data testo 6383
Parameters
Measuring range 0 to 10 Pa
0 to 50 Pa 0 to 100 Pa 0 to 500 Pa 0 to 10 hPa
-10 to +10 Pa
-50 to +50 Pa
-100 to +100 Pa
-500 to +500 Pa
-10 to +10 hPa
Measurement uncertainty*
0.3% of measurement range final value ±0.3 Pa
Meas. cycle 1/sec Resolution 12 bit Scaling Differential pressure: scalable ±50% of
measuring range final value; freely scalable within measuring range
Overload capacity Measuring range Overload
0 to 10 Pa 20000 Pa 0 to to 50 Pa 20000 Pa 0 to
to 100 Pa 20000 Pa
0
to to 500 Pa 20000 Pa
0 to to 10 hPa 200 hPa
-10 to to 10 Pa 20000 Pa
-50 to to 50 Pa 20000 Pa
-100 to
to 100 Pa 20000 Pa
-500
to to 500 Pa 20000 Pa
-10 to to 10 hPa 200 hPa
Inputs/outputs
Output type 0/4 to 20 mA (4-wire) (24 VAC/DC)
0 to 1/5 to 10 V (4-wire) (24 VAC/DC)
Relay Optional: 4 relays (free allocation to
measurement channels or as collective alarm in operating menu/P2A software), up to 250 VAC/3A (NO or NC)
Voltage supply 20 to 30 VAC/DC, 300mA current
consumption, galvanically separate signal and supply line
General technical data
Material Stainless steel housing Dimensions
without humidity/temperature: 246 x 161 x 47 mm with humidity/temperature: 396 x 161 x 78 mm
Resolution pressure Measuring range Resolution
0 to 10 Pa 0.1 Pa 0 to 50 Pa 0.1 Pa 0 to 100 Pa 0.1 Pa 0 to 500 Pa 0.1 Pa 0 to 10 hPa 0.01 hPa
-10 to 10 Pa 0.1 Pa
-50 to 50 Pa 0.1 Pa
-100 to 100 Pa 0.1 Pa
-500 to 500 Pa 0.1 Pa
-10 to 10 hPa 0.01 hPa
Operating temperature (housing) -5 to 50 °C/23 to 122 °F
Storage temperature -20 to 60 °C/-4 to 140 °F
Protection class IP 65
Operating conditions
Selectable units Pa, further pressure units see
configuration options p. 4
Sensor Piezoresistive sensor Autom. Zero-point
adjustment
via magnetic valve, frequency settable: 15 sec, 30 sec, 1 min, 5 min, 10 min
Humidity
Measuring range
Version with integrated probe: 0 to 100 %RH; Version with external probe:dependent on connected probe (see p. 10)
Measurement uncertainty dependent on connected probe (see p. 10)
Selectable units %RH, further calculated humidity
parameters see configuration options p. 4
Sensor Capacitive sensor
Temperature dependency/ coefficient
±0.02 %RH (at temperatures deviating from 25 °C)
Measuring range
dependent on connected probe (see p.
10) Measurement uncertainty 0.15 °C / 32.2 °F Selectable units °C / °F Sensor Pt 1000 1/3 Class B;
Pt 100 1/3 Class B (with probe testo
6615)
Digital output Mini-DIN for P2A software
Ethernet Optional
Temperature
* Measurement inaccuracy according to GUM: ±0,5% of measur ement range final value ±0.3 Pa
GUM (Guide to the Expression of Uncertainty in Measurement): ISO guideline for the determination of measurement inaccuracy, in order to make measurement results internationally comparable. The following inaccuracies are used for the determination: – Hysteresis – Linearity – Reproducibility – Long-term stability – Adjustment site/factory calibration – Test site
Resolution humidity
0.1 %RH
Temperature resolution
0.01 °C / °F
Standard reference
EU guideline 2004/108/EC
Weight Version without humidity:0.9 kg;
Version with integrated humidity probe:
1.350 kg; version with preparation for external humidity probe: 1.260 kg
Load max. 500
Quantity Standard: 1; for humidity/temperature
(optional): 3
6
Differential pressure transmitters for installation in normal zones
testo 6381– Overview of features and
benefits:
· Measurement of differential pressure, flow
velocity, volume flow; optional: humidity and temperature
· Automatic zero-point adjustment guarantees high, temperature-independent accuracy and long-term stability
· Low measurement range up to 10 Pa ensures very high precision at lowest pressures
· The robust metal housing protects from tough ambient conditions
· Combination of differential pressure, humidity, and temperature measurement in one instrument saves investment costs (exchangeable digital humidity probe see page 10)
·
Display with multi-language operating menu and optical alarm display
· Ethernet, relay and analog outputs allow optimum integration into individual automation systems
· Self-monitoring of the transmitters guarantees high system availability
· The P2A software for parameterization, adjustment and analysis saves time and costs in commissioning and maintenance
· Scalable measuring range by ±50 percent of the measuring range final value, and free scalability within the measuring range, allow optimum adaptation to the control requirements
Areas of application:
· Differential pressure monitoring between cleanrooms (optional: simultaneous measurement of ambient temperature and humidity)
· Monitoring drying processes
· Differential pressure monitoring in filling processes and spray-painting systems
Configuration options testo 6381:
This results in a typical ordering code:
0555 6381 AXX BXX CXX DXX EXX FXX GXX HXX IXX KXX
B02 B03 B04 B05 B06
C00 C02 C03 C04 C05 C06 C07 C08
K01 K02 K03 K04 K05 K06 K07 K08
D01 D02 D03
H00 H01 H02
F01 F02 F03 F04 F05 F06 F07 F08 F09 F10 F11 F12 F13 F14 F15 F16
G00
G01 G02 G03 G04 G05 G06 G07 G08 G09 G10 G11 G12 G13 G14
G15
G16 G17
0 to 1 V (4-wire, 24 VAC/DC) 0 to 5 V (4-wire, 24 VAC/DC) 0 to 10 V (4-wire, 24 VAC/DC) 0 to 20 mA (4-wire, 24 VAC/DC) 4 to 20 mA (4-wire, 24 VAC/DC)
without display without operating buttons with display, with operating buttons / English with display, with operating buttons / German with display, with operating buttons / French with display, with operating buttons / Spanish with display, with operating buttons / Italian with display, with operating buttons / Japanese with display, with operating buttons / Swedish
Cable input M16 (relay: M20) Cable entry NPT 1/2“ Cable contact via M-plug connection for signal and supply
Pa / min / max hPa / min / max kPa / min / max mbar / min / max bar / min / max mmH
2
O / min / max
mmH
2
O / min / max inch HG / min / max kg/cm² / min / max PSI / min / max m/s / min / max ft/min / min / max m³/h / min / max l/min / min / max Nm³/h / min / max Nl/min / min / max
without connection possibility for humidity probe testo 6610 % RH/Min/Max °C/Min/Max °F/Min/Max °C
td
/ min / max
°F
td
/ min / max g/kg / min / max gr/lb /Min/Max g/m³ / min / max gr/ft³ / min / max ppmV / min / max °C
wb
/ min / max
°F
wb
/ min / max kJ/kg /Min/Max (enthalpy) hPa /min/max (water vapour partial pressure) mmH
2
O / min / max (Water vapour partial pressure) °C
tm
(mixture dewpoint for H2O2)
°F
tm
(mixture dewpoint for H2O2)
without relay 4 relay outputs, limit value monitoring 4 relay outputs, channel 1 limit values and collective alarm
German/English instruction manual French/English instruction manual Spanish/English instruction manual Italian/English instruction manual Dutch/English instruction manual Japanese/English instruction manual Chinese/English instruction manual Swedish/English instruction manual
Order no. 0555 6381 A01 Bxx Cxx Dxx Exx Fxx Gxx Hxx Ixx Kxx
E00 E01
without Ethernet module with Ethernet module
Axx Measuring range Bxx Analog display/supply Cxx Display Dxx Cable input Exx Ethernet Fxx Differential pressure/flow velocity unit (pre-set) Gxx opt. Analog output for humidity probe
A01 A02 A03 A04 A05 A07 A08 A09 A10 A21 A22 A23 A24 A25 A27 A28 A29 A30
0 to 10 Pa 0 to 50 Pa 0 to 100 Pa 0 to 500 Pa 0 to 10 hPa 0 to 50 hPa 0 to 100 hPa 0 to 500 hPa 0 o 1000 hPa
-10 to 10 Pa
-50 to 50 Pa
-100 to 100 Pa
-500 to 500 Pa
-10 to 10 hPa
-50 to 50 hPa
-100 to 100 hPa
-500 to 500 hPa
-1000 to 1000 hPa
I01 I02 I03 I04 I05 I06 I07 I08 I09 I10 I11 I12 I13 I14
I15
I16 I17
% RH/Min/Max °C/Min/Max °F/Min/Max °C
td
/ min / max
°F
td
/ min / max g/kg / min / max gr/lb /Min/Max g/m³ / min / max gr/ft³ / min / max ppmV / min / max °C
wb
/ min / max
°F
wb
/ min / max kJ/kg /Min/Max (enthalpy) hPa /min/max (water vapour partial pressure) mmH
2
O / min / max (Water vapour partial pressure) °C
tm
(mixture dewpoint for H2O2)
°F
tm
(mixture dewpoint for H2O2)
Scaling ±50% of measuring range; freely selectable within measuring range
only possible when G­Code (from G01) selected)
connection testo 6610 / units (pre-set) Hxx Relay Ixx Units channel 3 (pre-set, only if opt. humidity
probe connection available) Kxx IM languages (for bilingual printed IMs)
with connection possibility testo 6610
7
testo 6381
testo 6381 – differential pressure, humidity and flow velocity
Supply
Display
Differential pressure
Analog outputs
Other outputs
Housing
Miscellaneous
Display optional: 3-line LCD with multi-language
operating menu
Parameters
Measuring range 0 to 10 Pa
0 to 50 Pa 0 to 100 Pa 0 to 500 Pa 0 to 10 hPa 0 to 50 hPa 0 to 100 hPa 0 to 500 hPa 0 to 1000 hPa
-10 to 10 Pa
-50 to 50 Pa
-100 to 100 Pa
-500 to 500 Pa
-10 to 10 hPa
-50 to 50 hPa
-100 to 100 hPa
-500 to 500 hPa
-1000 to 1000 hPa
Measurement uncertainty* 0.5% of measurement range final value ±0.3 Pa
Meas. cycle 1/sec Resolution 12 bit Scaling Differential pressure: scalable ±50% of
measuring range final value; freely scalable within measuring range
Overload capacity Measuring range Overload
0 to 10 Pa 20000 Pa 0 to 50 Pa 20000 Pa 0 to 100 Pa 20000 Pa 0 to 500 Pa 20000 Pa 0 to 10 hPa 200 hPa 0 to 50 hPa 750 hPa 0 to 100 hPa 750 hPa 0 to 500 hPa 2500 hPa 0 to 1000 hPa 2500 hPa
-10 to 10 Pa 20000 Pa
-50 to 50 Pa 20000 Pa
-100 to 100 Pa 20000 Pa
-500 to 500 Pa 20000 Pa
-10 to 10 hPa 200 hPa
-50 to 50 hPa 750 hPa
-100 to 100 hPa 750 hPa
-500 to 500 hPa 2500 hPa
-1000 to 1000 hPa 2500 hPa
Inputs/outputs
Output type 0/4 to 20 mA (4-wire) (24 VAC/DC)
0 to 1/5 to 10 V (4-wire) (24 VAC/DC)
Relay Optional: 4 relays (free allocation to
measurement channels or as collective alarm in operating menu/P2A software), up to 250 VAC/3A (NO or NC)
Voltage supply 20 to 30 VAC/DC, 300 mA current
consumption, galvanically separate signal and supply line
General technical data
Material Metal housing Dimensions 162 x 122 x 77 mm
Resolution pressure Measuring range Resolution
0 to 10 Pa 0.1 Pa 0 to 50 Pa 0.1 Pa 0 to 100 Pa 0.1 Pa 0 to 500 Pa 0.1 Pa 0 to 10 hPa 0.01 hPa 0 to 50 hPa 0.01 hPa 0 to 100 hPa 0.1 hPa 0 to 500 hPa 0.1 hPa 0 to 1000 hPa 1 hPa
-10 to 10 Pa 0.1 Pa
-50 to 50 Pa 0.1 Pa
-100 to 100 Pa 0.1 Pa
-500 to 500 Pa 0.1 Pa
-10 to 10 hPa 0.01 hPa
-50 to 50 hPa 0.01 hPa
-100 to 100 hPa 0.1 hPa
-500 to 500 hPa 0.1 hPa
-1000 to 1000 hPa 1 hPa
Protection class
IP 65
Selectable units Pa, further pressure and flow velocity
units see configuration options p. 6
Sensor Piezoresistive sensor Autom. Zero-point
adjustment
via magnetic valve, frequency settable: 15 sec, 30 sec, 1 min, 5 min, 10 min
Humidity
Measuring range
dependent on connected probe (see p. 10)
Measurement uncertainty dependent on connected probe (see p. 10)
Selectable units %RH, further calculated humidity
parameters see configuration options p. 6
Sensor Capacitive sensor
Temperature dependency/coefficient
±0.02 %RH (at temperatures deviating from 25 °C)
Measuring range
dependent on connected probe (see p.
10)
Measurement uncertainty 0.15 °C / 32.2 °F Selectable units °C / °F Sensor Pt 1000 1/3 Class B;
Pt 100 1/3 Class B (testo 6615)
Digital output Mini-DIN for P2A software
Ethernet Optional with Ethernet module
Temperature
Weight 1,960 kg; optional: Ethernet intermediary
layer 0.610 kg
Operating temperature (housing) -5 to 50 °C/23 to 122 °F
Storage temperature -20 to 60 °C/-4 to 140 °F
Operating conditions
Standard reference
EU guideline 2004/108/EC
Technical data testo 6381
Resolution humidity
0.1 %RH
Temperature resolution
0.01 °C / °F
Load max. 500
Quantity Standard: 1; for humidity/temperature
(optional): 3
* Measurement inaccuracy according to GUM: ±0.8% of measurement range final value ±0.3 Pa
GUM (Guide to the Expression of Uncertainty in Measurement): ISO guideline for the determination of measurement inaccuracy, in order to make measurement results internationally comparable. The following inaccuracies are used for the determination: Hysteresis / Linearity / Reproduceability / Long-term stability / Adjustment site/factory calibration / Test site
8
Differential pressure transmitters for installation in normal zones
Configuration options testo 6351:
testo 6351
Overview of features and
benefits:
· Measurement of differential pressure, flow
velocity and volume flow
· Automatic zero-point adjustment guarantees high, temperature-independent accuracy and long-term stability
· Plastic housing
· Display with multi-language operating
menu and optical alarm display
· Ethernet, relay and analog outputs allow optimum integration into individual automation systems
· Self-monitoring of the transmitters guarantees high system availability
· The P2A software for parameterization, adjustment and analysis saves time and costs in commissioning and maintenance
· Scalable measuring range by ±50 percent
of the measuring range final value, and free scalability within the measuring range, allow optimum adaptation to the control requirements
Areas of application:
· Differential pressure monitoring between cleanrooms
· Differential pressure monitoring in filling processes
· Monitoring differential pressure, volume flow and flow velocities in critical air conditioning technology (VAC systems)
B02 B03 B04 B05 B06
C00 C02 C03 C04 C05 C06 C07 C08
K01 K02 K03 K04 K05 K06 K07 K08
D01 D02 D03
H00 H01 H02
F01 F02 F03 F04 F05 F06 F07 F08 F09 F10 F11 F12 F13 F14 F15 F16
0 to 1 V (4-wire, 24 VAC/DC) 0 to 5 V (4-wire, 24 VAC/DC) 0 to 10V (4-wire, 24 VAC/DC) 0 to 20 mA (4-wire, 24 VAC/DC) 4 to 20 mA (4-wire, 24 VAC/DC)
without display without operating buttons with display, with operating buttons / English with display, with operating buttons / German with display, with operating buttons / French with display, with operating buttons / Spanish with display, with operating buttons / Italian with display, with operating buttons / Japanese with display, with operating buttons / Swedish
Cable input M16 (relay: M20) Cable entry NPT 1/2“ Cable contact via M-plug connection for signal and supply
Pa / min / max hPa / min / max kPa / min / max mbar / min / max bar / min / max mmH
2
O / min / max
mmH
2
O / min / max inch HG / min / max kg/cm² / min / max PSI / min / max m/s / min / max ft/min / min / max m³/h / min / max l/min / min / max Nm³/h / min / max Nl/min / min / max
without relay 4 relay outputs, limit value monitoring 4 relay outputs, channel 1 limit values and collective alarm
German/English instruction manual French/English instruction manual Spanish/English instruction manual Italian/English instruction manual Dutch/English instruction manual Japanese/English instruction manual Chinese/English instruction manual Swedish/English instruction manual
Order no. 0555 6351
A01 Bxx Cxx Dxx Exx Fxx Hxx Ixx
Jxx Kxx
E00 E01
without Ethernet module with Ethernet module
Axx Measuring range Bxx Analog display/supply Cxx Display Dxx Cable input Exx Ethernet
A02 A03 A04 A05 A07 A08 A09 A10 A11 A22 A23 A24 A25 A27 A28 A29 A30 A31
0 to 50 Pa 0 to 100 Pa 0 to 500 Pa 0 to 10 hPa 0 to 50 hPa 0 to 100 hPa 0 to 500 hPa 0 to 1000 hPa 0 to 2000 hPa
-50 to 50Pa
-100 to 100 Pa
-500 to 500 Pa
-10 to 10 hPa
-50 to 50 hPa
-100 to 100 hPa
-500 to 500 hPa
-1000 to 1000 hPa
-2000 to 2000 hPa
Scaling: ±50% of measuring range; freely selectable within measuring range
Fxx Differential pressure/flow velocity unit (pre-set) Hxx Relay Kxx IM languages (for bilingual printed IMs)
This results in a typical ordering code:
0555 6351 AXX BXX CXX DXX EXX FXX HXX IXX KXX
9
testo 6351
testo 6351 – Differential pressure and flow velocity
Supply
Display
Differential pressure
Analog outputs
Other outputs
Housing
Miscellaneous
Display Optional: 3-line LCD with multi-language
operating menu
Parameters
Measuring range 0 to 50 Pa
0 to 100 Pa 0 to 500 Pa 0 to 10 hPa 0 to 50 hPa 0 to 100 hPa 0 to 500 hPa 0 to 1000 hPa 0 to 2000 hPa
-50 to 50 Pa
-100 to 100 Pa
-500 to 500 Pa
-10 to 10 hPa
-50 to 50 hPa
-100 to 100 hPa
-500 to 500 hPa
-1000 to 1000 hPa
-2000 to 2000 hPa
Measurement uncertainty* ±0.8% of measurement range final value
±0.3 Pa
Meas. cycle 1/sec Resolution 12 bit Scaling Differential pressure: scalable ±
50% of measuring range final value; freely scalable within measuring range
Overload capacity Measuring range Overload
0 to 50 Pa 20000 Pa 0 to 100 Pa 20000 Pa 0 to 500 Pa 20000 Pa 0 to 10 hPa 200 hPa 0 to 50 hPa 750 hPa 0 to 100 hPa 750 hPa 0 to 500 hPa 2500 hPa 0 to 1000 hPa 2500 hPa 0 to 2000 hPa 2500 hPa
-50 to 50 Pa 20000 Pa
-100 to 100 Pa 20000 Pa
-500 to 500 Pa 20000 Pa
-10 to 10 hPa 200 hPa
-50 to 50 hPa 750 hPa
-100 to 100 hPa 750 hPa
-500 to 500 hPa 2500 hPa
-1000 to 1000 hPa 2500 hPa
-2000 to 2000 hPa 2500 hPa
Inputs/outputs
Output type 0/4 to 20 mA (4-wire) (24 VAC/DC)
0 to 1/5 to 10 V (4-wire) (24 VAC/DC)
Relay Optional: 4 relays (free allocation to
measurement channels or as collective alarm in operating menu/P2A software), up to 250 VAC/3A (NO or NC)
Voltage supply 20 to 30 VAC/DC, 300mA current
consumption, galvanically separate signal and supply line
General technical data
Material Plastic housing Dimensions 162 x 122 x 77 mm
Resolution pressure Measuring range Resolution
0 to 50 Pa 0.1 Pa 0 to 100 Pa 0.1 Pa 0 to 500 Pa 0.1 Pa 0 to 10 hPa 0.01 hPa 0 to 50 hPa 0.01 hPa 0 to 100 hPa 0.1 hPa 0 to 500 hPa 0.1 hPa 0 to 1000 hPa 1 hPa 0 to 2000 hPa 1 hPa
-50 to 50 Pa 0.1 Pa
-100 to 100 Pa 0.1 Pa
-500 to 500 Pa 0.1 Pa
-10 to 10 hPa 0.01 hPa
-50 to 50 hPa 0.01 hPa
-100 to 100 hPa 0.1 hPa
-500 to 500 hPa 0.1 hPa
-1000 to 1000 hPa 1 hPa
-2000 to 2000 hPa 1 hPa
Protection class
IP 65
Selectable units Pa, further pressure and flow velocity
units see configuration options p. 8
Sensor Piezoresistive sensor Autom. Zero-point
adjustment
via magnetic valve, frequency settable: 15 sec, 30 sec, 1 min, 5 min, 10 min
Digital output Mini-DIN for P2A software
Ethernet Optional with Ethernet module
Weight 0.7 kg; optional: Ethernet intermediary
layer: 0.6 kg
Operating temperature (housing) -5 to 50 °C/23 to 122 °F
Storage temperature -20 to 60 °C/-4 to 140 °F
Operating conditions
Standard reference
EU guideline 2004/108/EC
Load max. 500
Technical data testo 6351
Quantity 1
* Measurement inaccuracy according to GUM: ±0.8% of measurement range final value ±0.3 Pa GUM (Guide to the Expression of Uncertainty in Measurement): ISO guideline for the determination of measurement inaccuracy, in order to make measurement results internationally comparable. The following inaccuracies are used for the determination: – Hysteresis – Linearity – Reproducibility – Long-term stability – Adjustment site/factory calibration – Test site
External probes for testo 6383 and testo 6381 – probe series testo 6610
10
testo 6611* testo 6612 testo 6613 testo 6614 testo 6615 testo 6617
Type Wall
%rF; %RH; °C
tpd
/°F
tpd
; g/m³ / gr/ft³; g/kg / gr/lb; kj/kg; BTU/lb; °Ctw/°Ftw;
hPa; inch H
2O2
; ppm vol %; %vol; °Ctm(H2O2)/ °Ftm(H2O2)
Stainless steel
Sheathed, FEP
ABS plastic
Channel Cable
-30 to +150 °C,
-22 to +302 °F
see trace humidity
0 to 100 %RH
Heated cable
Trace humidity cable (self­adjustment)
Cable with covering electrode monitoring
200 mm 200/500 mm200/300/500/
800 mm
Customized for
duct version
1 to 10 bar (probe tip)
1 bar (probe end)
1 to 16 bar (probe tip)
1 bar (probe end)
1 bar positive
pressure (probe tip)
1 bar (probe end)
Selectable units
0 to 100 %RH
-20 to +70 °C,
-4 to +158 °F
Measuring range
Temperature
Probe shaft Cable Connector
±0.15 °C / 32.2 °F (Pt 1000 1/3 Class B)
Measurement inaccuracy ** (at 25 °C / 77°F)
Indoor climate probe wall installation
Process humidity probe, duct installation
Process humidity probe, flexible installation with cable
Humidity probe for high humiidity applications/for danger of condensation
Humidity probe for trace humidity/pressure dewpoint (with self­adjustment)
Humidity probe with self-monitoring for sensor-damaging media
Probe shaft diameter 12 mm Probe shaft length
Cable length 1/2/5/10 m
Process pressure
1 bar positive pressure (probe tip)
120/200/300/500/
800 mm
±1 K at 0° C
td
±2K at -40° C
td
±4K at -50° C
td
-40 to +180 °C/-40 to +356 °F
-40 to +120 °C,
-40 to +248 °F
-40 to +180 °C /
-40 to +356 °F
±0.15 °C / 32.2 °F
Pt1000 1/3 Class B
±0.15 °C / 32.2 °F
Pt100 1/3 class B
Humidity
±1,0 %RH (0 to 90%); ±1.4 %RH (90 to 100%)
Measurement uncertainty** (25 °C)
0.02 %RH/K
Measurement inaccuracy (for deviations from media temperature of ±25 °C)
Temperature
°C / °FSelectable units
better than 0.2 %RHReproduceability
Trace humidity
-60 to +30 °C
td
/
-76 to +86 °F
td
Measuring range
Measurement uncertainty
Probe
Area of use
Parameters
General technical data
Operating conditions
* Technical data also apply to the integrated humidity probe of the testo 6383. Probe testo 6611 cannot be connected to thetesto 6383.
see trace humidity
±1.0 %RH
(0 to 100%)
±1.2 %RH (0 to 90%); ±1.6 %RH (90 to 100%)
**
DDeetteerrmmiinnaattiioonn ooff hhuummiiddiittyy mmeeaassuurreemmeenntt iinnaaccccuurraaccyy aaccccoorrddiinngg ttoo GGUUMM
GUM (Guide to the Expression of Uncertainty in Measurement): ISO guideline for the determination of measurement inaccuracy, in order to make measurement results internationally comparable. The following inaccuracies are used for the determination: – Hysteresis – Linearity – Reproducibility – Long-term stability – Adjustment site/factory calibration – Test site
Configuration options testo 6610
11
L11 L12 L13 L14 L15 L17
––X––– XXXXXX –XX––– –XXXXX –XX–––
Ordering procedure: Thanks to the digital probe interface, the transmitter and the probe can be ordered separately from each other, see ordering example above.
0555 6610 Lxx Mxx
L11 L12 L13 L14 L15 L17
Probe 6611 (wall version) Probe 6612 (duct version up to 150 °C) Probe 6613 (cable version up to 180 °C) Probe 6614 (heated cable version) Probe 6614 (heated cable version) Probe 6617 (self-monitored cable version)
M01 M02 M03 M04 M06 M07 M08
Sintered stainless steel filter Metal wire protection cap Sintered Teflon filter Open metal protection cap Teflon filter with drip hole Teflon filter with drip hole and condensation protector Filter for H
2O2
atmospheres*
N00 N01 N02 N05 N10 N23
without cable Probe length 1 m Probe length 1 m Probe length 5 m Probe length 10 m Probe length, specially for duct versions
P12 P20 P30 P50 P80
Probe length 300 mm Probe length 200 mm Probe length 300 mm Probe length 500 mm Probe length 800 mm
Nxx Pxx
Ordering example testo 6613 probes
Cable probe, -40 to +180 °C Sintered stainless steel filter Cable length 2 m Probe length 300 mm
0555 6610 L13 / M01 / N02 / P30
specially for high humidity (testo 6614 only)
L11 L12 L13 L14 L15 L17
X––––– ––XXXX ––XXXX ––XXXX ––XXXX –X––––
*
On H2O2processes:
Testo offers a transmitter which can also be used in hydrogen peroxide (H
2O2
) processes - e. g. in sterilization. The sensor is protected with
the help of a special probe (Code M08). In addition, the so-called „mixture dewpoint“ °C
tm
/°Ftmis issued.
Probe
connector
Probe length
Probe length
Probe
Filter
12
Accessories for all transmitters
Mains unit (desktop instrument) 110 to 240 VAC / 24 VDC (350 mA) 0554 1748 Mains unit (top-hat rail mounting) 90 to 264 VAC / 24 VDC (2.5 A) 0554 1749 Process display testo 54-2 AC, two relay outputs (to 250 VAC / 300 VDC, 3A), mains supply 90 to 260 VAC 5400 7553 Process display testo 54-7 AC, two relay outputs (to 250 VAC / 300 VDC, 3A), mains supply 90 to 260 VAC,
with RS485 output for online monitoring and with totalizer display 5400 7555
Ethernet module for installation by the customer (for testo 6351 and testo 6381 only) 0554 6656 Ethernet plug (for testo 6351 and testo 6381 only) 0554 6653 P2A software (parameterization, adjustment, analysis) incl. USB adapter 5546020 Silicon hose ID 4 transparent 0086 0001, by the metre Tygon hose ID 4.8 transparent 0086 0031, by the metre Humidity adjustment set 11.3 / 75.3 %RH (for testo 6381 and testo 6383 only) 0554 0660
Adjustment and extension cable, 10 m (for testo 6381and testo 6383 only) 0554 6610 Pitot tube, length 350 mm, stainless steel (for testo 6351 and testo 6381 only) 0635 2145 Pitot tube, length 1000 mm, stainless steel (for testo 6351 and testo 6381 only) 0635 2345
Ordering data for accessories Order no.
Ethernet module (Intermediary layer)
Ethernet
The Ethernet module is an intermediary layer („sandwich“ design), which can be optionally integrated into the transmitters testo 6681/6351 ex-works. It can also be subsequently easily and quickly retrofitted on site. Two LEDs provide the responsible system operator with information on the status of the voltage supply and the LAN connection.
The cable can be used to carry out an adjustment of a humidity probe from the probe series testo 6610 - either on site or in a laboratory. The cable also serves as an extension between the transmitter and the respective probe.
Advantages of the adjustment
By using an industrial Ethernet plug, IP65 housing protection can be guaranteed, enabling the transmitter to withstand the sometimes rough and demanding conditions in industrial processes.
and extension cable: – Flexible installation and
maintenance of the humidity probe
– Extension of the normal
humdity probe cable by 10 m
– Cable has protection class
IP65
1
Ethernet intermediary layer testo 6381/6351 for installation by customer
2
Adjustment and extension cable for external humidity probes
13
Testo – Your partner for calibration, validation and qualification
testo SaverisTM– Simple, secure and efficient measurement data monitoring
Validation / qualification
The Testo subsidiary testo industrial services (TIS) offers you customized validation and qualification for pharmaceutical projects: – DQ, IQ, OQ, PQ (qualification) – Mapping/distribution measurements (for
optimum probe site determination)
– Customized risk analysis incorporating
GAMP5
– Documentation optionally in Testo or
customer format
More information: www.testo-industrial-services.de
Calibration:
Calibration service in laboratories and on site in numerous countries. Contact your local Testo subsidiary, testo industrial services or Testo’s sales partner in your country.
Calibration and validation/qualification services
The measurement data monitoring system measures pressure, temperature and humidity values in the environment and in processes.
find out more at: www.testo.com/saveris
In industrial processes, exact temperatures, humidity values and pressure relationships play a crucial role.
In a multitude of applications, testo Saveris helps to collect, safely store and present these data wirelessly (analog coupler) or via Ethernet. A selection of alarms that can be used flexibly supports the responsible parties to keep the values in the required range.
Typical applications:
•Monitoring ambient storage and production
conditions
•Monitoring humidity values,
e. g. in air-conditioned cabinets
•Monitoring temperatures,
e. g. during heat treatment or in air­conditioned cabinets
Integrate the new transmitters into testo Saveris
TM
Testo: At your service!
Subject to change without notice.
Please ask for our more information:
Monitoring Instruments for Food Production, Transport and Storage Measurement Engineering for Restaurants, Catering and
Supermarkets Measurement Engineering for Air Conditioning and Ventilation Measurement Engineering for Heating and Installation Measurement Solutions for Emissions, Service and Thermal
Processes Measurement Solutions for Refrigeration Technology Stationary Measurement Solutions for Air Conditioning, Drying,
Cleanrooms and Compressed Air Measurement Solutions for Production, Quality Control and
Maintenance Measurement Solutions for Climate Applications in Industry Reference Measurement Technology for Industry
Measuring Instruments for Temperature Measuring Instruments for Humidity Measuring Instruments for Velocity Measuring Instruments for Pressure and Refrigeration Multi-Function Measuring Instruments Measuring Instruments for Flue Gas and Emissions Measuring Instruments for RPM, Analysis, Current/Voltage Measuring Instruments For Indoor Air Quality, Light And Sound Stationary Measurement Technology Humidity / Differential
Pressure / Temperature / Process Displays Stationary Measurement Technology Compressed Air Humidity /
Compressed Air Consumption
0981 6274/msp/R/Q/08.2009
Loading...