country for opening and repairing electrical equipment.
Avoiding personal injury and damage to equipment
> Installation, setting and calibration work must only be carried
out by qualified and authorized personnel!
> Only open the instrument when this is expressly described in
the instruction manual for installation, maintenance or repair
purposes.
> Observe the permissible storage, transport and operating
Pos: 4 /TD/Sicherheit und Umwelt/Sicherheit gewährle isten/ Nicht mit Lösungsmit teln lagern @ 0\mod_1175692375179_79. doc @ 583 @
temperature.
> Do not store the product together with solvents. Do not use any
Pos: 5 /TD/Sicherheit und Umwelt/Sicherheit gewährle isten/ MUF 63xx/ Bei Wartung M UF nicht zur Regelung verwenden @ 3\mod_1234794852377_ 79. doc @ 26318 @
desiccants.
> Do not use the instrument for control purposes at the same time
Pos: 6 /TD/Sicherheit und Umwelt/Sicherheit gewährle isten/ Produkt best immungsgem äß verwenden @ 0\mod_1173781261848_79.doc @ 386 @
as operating or servicing the transmitter.
> Only operate the product properly, for its intended purpose and
within the parameters specified in the technical data. Do not
Any additional work must only be carried out by authorized
personnel. Otherwise testo will not accept any responsibility for the
proper functioning of the instrument after repair and for the validity
of certifications.
Pos: 12 /TD/Sicherheit und Umwelt/Zu diesem Dokument / Verwendung (Standar d) @ 0\mod_1173775068554_79. doc @ 337 @ 5
regulations) or return the product to Testo for disposal.
Use
> Please read this documentation through carefully and
familiarize yourself with the product before putting it to use. Pay
particular attention to the safety instructions and warning advice
in order to prevent injuries and damage to the products.
> Keep this document to hand so that you can refer to it when
necessary.
> Hand this documentation on to any subsequent users of the
Pos: 13 /TD/Sicherheit und Umwelt/Zu diesem Dokument / Symbole und Schreibkonventionen/ Warnhin weis WARNUNG @ 2\m od_1207646966234_79.doc @ 14398 @
Pos: 14 /TD/Sicherheit und Umwelt/Zu diesem Dokument / Symbole und Schreibkonventionen/ Warnhin weis VORSICHT @ 2\ mod_1207651416515_ 79. doc @ 14416 @
Pos: 15 /TD/Sicherheit und Umwelt/Zu diesem Dokument / Symbole und Schreibkonv. Sof tware [ Standard] @ 0\mod_1190203332543_79. doc @ 4883 @ 5
product.
WARNING
Indicates potential serious injuries
CAUTION indicates potential minor injuries
Symbols and writing standards
Representa-
Explanation
tion
Note: Basic or further information.
1. ...
2. ...
Action: more steps, the sequence must be
followed.
> ... Action: a step or an optional step.
- ... Result of an action.
Menu Elements of the program interface.
[OK] Buttons of the program interface.
... | ... Functions/paths within a menu.
“...” Example entries
The testo 6381 transmitter is suitable for the following applications
with Ethernet networking, amongst others:
• Test benches
• Clean rooms
• Filling processes
• Painting systems
• Drying processes
• Monitoring flow velocities or volumetric flow rates in air
conditioning systems
In addition to the signal transmission of the readings to a control
unit via analog outputs, the measurement data can simultaneously
be recorded, documented and visualized via Ethernet.
Furthermore, it is possible to issue an alarm for those responsible
The scope of delivery of the testo 6381 transmitter includes the
following:
• Key cover
• Rear panel bracket
• Ethernet module
• Instruction manual
• Calibration report
• CD-ROM with operating instructions (PDF), configuration files
for Ethernet module and P2A update (this can only be used in
conjunction with the P2A software, which has to be ordered
The specifications are only valid if the positive pressure is
applied at the positive pressure connection.
• 0.5 % of measuring range, additional 0.3 Pa intrinsic error 1
• T
K slope drift
= 0.03 % of measuring range per degree Kelvin of
deviation from nominal temperature 22 °C
• T
K zeroing drift
1
Measuring uncertainty in accordance with GUM: ±0.8 % of measuring range
= 0 %, as zeroing with solenoid valve2
final value ±0.3 Pa.
GUM (Guide to the Expression of Uncertainty in Measurement): ISO guideline for determining the
measuring uncertainty in order to render global measurement results comparable.
The following uncertainties are used during the inquiry:
• Hysteresis
• Linearity
• Reproducibility
• Adjustment area/factory calibration
2
Minor mixtures of the media may occur at the positive and negative pressure
• Test location
side due to the automatic zeroing cycle.
9
4 Transmitter
Pressure measuring range, resolution and overload of
differential pressure
Pressure
measuring range
depending on
version ordered
0 to 50 Pa 0.1 Pa 20,000 Pa
0 to 50 Pa 0.1 Pa 20,000 Pa
0 to 100 Pa 0.1 Pa 20,000 Pa
0 to 500 Pa 0.1 Pa 20,000 Pa
0 to 10 hPa 0.01 hPa 200 hPa
0 to 50 hPa 0.01 hPa 750 hPa
0 to 100 hPa 0.1 hPa 750 hPa
0 to 500 hPa 0.1 hPa 2500 hPa
0 to 1000 hPa 1 hPa 2500 hPa
-10 to 10 Pa 0.1 Pa 20,000 Pa
-50 to 50 Pa 0.1 Pa 20,000 Pa
-100 to 100 Pa 0.1 Pa 20,000 Pa
-500 to 500 Pa 0.1 Pa 20,000 Pa
-10 to 10 hPa 0.01 hPa 200 hPa
-50 to 50 hPa 0.01 hPa 750 hPa
-100 to 100 hPa 0.1 hPa 750 hPa
-500 to 500 hPa 0.1 hPa 2500 hPa
-1000 to 1000 hPa 1 hPa 2500 hPa
Upon delivery and following a factory reset the readings are
shown in the display in the unit that was ordered via the
KMAT option Fxx, see Ordering options for 6381 transmitter
(0555 6381), page 98.
Resolution Overload
10
Meas. cycle
• 1/sec
Interface
• Mini-DIN for P2A software (parameterizing and adjusting
software) and handheld testo 400/650
4 Transmitter
Voltage supply
• 4-wire (separate signal and supply lines): 20 to 30 V AC/DC,
300 mA power consumption
Maximum load
• 4-wire: 500 Ω (power output)
Maximal load
• 4-wire: 10 kΩ (voltage output)
Analog output
• 0 to 1 V ± 1.5 mV (4-wire) or
• 0 to 5 V ± 7.5 mV (4-wire) or
• 0 to 10 V ± 15 mV (4-wire) or
• 0 to 20 mA ± 0.03 mA (4-wire) or
• 4 to 20 mA ± 0.03 mA (4-wire)
Resolution of analog output
• 12 bit
Relay
• 4 relays, 250 V AC/DC, 3 A (optional)
11
4 Transmitter
Display
• 2-line LCD with plain text line (optional)
Operating temperature
• -5 to 50 °C/23 to 122 °F
Storage temperature
• -20 to 60 °C/-4 to +140 °F
Process temperature
• -20 to 65 °C/-4 to 149 °F
Housing, weight
• Metal: 1.960 kg
• Ethernet module: 0.610 kg
Protection class
• IP 65 only if the transmitter is wired properly (closed cable
entries), Ethernet connector and Harting PushPull connector
are inserted and/or sealing plugs are inserted.
12
Directives, standards and tests
• EC Directive: 2004/108/EC
• DIN 14644-4
• EN 61000-6-2 interference immunity
• EN 61000-6-3 interference emission
• EN 61326-1+A1+A2
Ethernet module
• Interface:
◦ 1 x mini-DIN
◦ 1 x RJ45 (Ethernet 10 BaseT/100 BaseTX)
• LED:
2 x green
Warranty
• Duration: 2 years
• Warranty conditions: see website www.testo.com/warranty
This has a floating switch capacity of 250 V AC/3 A. The switching
limits and hysteresis as well as the function as relay for the
collective alarm can be set via the display or the P2A software.
Further features include:
• Function of changeover contacts (NC/NO contacts) freely
selectable
If no relays are available, settings for monitoring limit values
or alarms can still be controlled via the display. The alarm
status will be shown on the display.
Only have the transmitter wired and connected by
authorized personnel with the voltage disconnected.
4 Transmitter
4.2.5. Analog outputs
As analog outputs, the testo 6381 has either
• 1 current output of 0 to 20 mA (4-wire)/4 to 20 mA (4-wire) or
There are three types of min./max. values:
1 The measuring range: The maximum sensor performance is in
this range. Values outside of the measuring range are displayed
via messages, for example. Measuring range, see table
(below).
2 Standard scaling: The output signals are assigned to this
measuring range as standard:
◦ during delivery if no entries are made in the order code
◦ after exchanging the unit, the measuring range recorded in
the instrument is applied as standard.
The transmitter even retains its scaling with the voltage
disconnected.
Measuring range, see table (below).
3 The maximum settings for the manual scaling
◦ The maximum limits can be calculated as follows:
X = difference between MIN. and MAX. value of the
standard scaling
(Max. value of standard) + (50 % of X)
(Min. value of standard) - (50 % of X)
◦ It is thus possible to scale beyond the measuring range, e.g.
for the adjustment of the scaling limits to standard values of
a PLC.
4
in m3/h, l/min, Nm3/h, Nl/min
O, inch
2
3
To prevent fluctuating flow rate values at the zero point (depressurized), the
flow rate values are only calculated as of differential pressures > 0.2 Pa or
> 0.1 % of the respective measuring range (whichever is the greater). With
smaller differential pressures, the flow rate value remains at 0.00 m/s.
0 to 50 Pa -5 to 15 Pa
0 to 50 Pa -25 to 75 Pa
0 to 100 Pa -50 to 150 Pa
0 to 500 Pa -250 to 750 Pa
0 to 10 hPa -5 to 15 hPa
0 to 50 hPa -25 to 75 hPa
0 to 100 hPa -50 to 150 hPa
0 to 500 hPa -250 to 750 hPa
0 to 1000 hPa 500 to 1500 hPa
With the alarm definition, however, the physical measuring
range limits are decisive.
Maximum scaling
4.2.8. Alarm handling
For upper and lower alarm limits, individual alarms as well as
collective alarms can be specified. If the collective alarm function is
activated, an alarm is triggered as soon as the alarm limit of an
alarm is exceeded, if this alarm is assigned to the collective alarm.
The testo 6381 monitors limit values with the help of relays. If a
reading is outside the limit values, a relay to be specified by the
user is switched.
If the reading reverts to more than a specified hysteresis below or
above the limit value, the alarm is cancelled.
17
4 Transmitter
In addition, information about the occurrence of error/status
messages can be provided by means of a collective alarm relay,
see Status, warning and error messages, page 63
If multiple alarm messages are activated at the same time,
the last alarm is shown. If the alarm is cancelled again, the
Only have the transmitter wired and connected by
authorized personnel with the voltage disconnected.
There is the option of twelve terminals for a total of four relays. The
designations NC/C/NO (normally closed contact/root or
pin/normally open contact) are etched on the surface of the board.
4 Transmitter
Relay terminal strip,
item (3) of overview of
terminals
Using PG screw connection
1. Feed connection cables for the relays through opened
M 20 x 1.5 screw connection (item (10) of overview of
terminals).
2. Strip cable ends and clamp on wire end ferrules.
3. Connect relays according to chosen function (NC/NO) (see
diagrams below; relay 1 is shown as an example of a
connection).
Using plug-in connections (optional)
Only insert or disconnect the plug-in connection when the
voltage is disconnected.
4. Clean the connector of the probe line and the coupling of any
foreign matter.
25
4 Transmitter
Do not disconnect the connector of the probe line from the
instrument for extended periods to protect against
contamination.
Connection note
• For the connection, a double-insulated mains cable
(sheathed cable) with a cross-section of at least
1.5 mm² must be used.
• Cable connection (2) may not be routed in a loop within
the tray (1).
• It is recommended that you always tie 3 cores to one
another using a cable tie (3).
• The insulation of the cable must be fed at least 5 mm
(4) into the tray.
26
Use of relay as NC contact (NC = normally closed)
1 Alarm/status light
(example of installation)
2 250 V AC/DC, 3 A
4 Transmitter
The busy light (alarm/status light) is permanently on until
the relay opens or the circuit is interrupted. This circuit can
therefore be used to monitor the functionality of the alarm
circuit, as a cable break, for instance, is indicated by the
busy light going off.
Use of relay as NO contact (NO = normally open)
1 Alarm/status light
(example of installation)
2 250 V AC/DC, 3 A
27
4 Transmitter
The busy light (alarm/status light) only comes on when the
relay is switched (closed). Monitoring the functionality of the
alarm circuit is therefore not possible with this switching
operation.
5. Close M 20 x 1.5 screw connection (item (9) in overview of
As an option, the PG screw connections of the signal and supply
lines can be replaced with plug-in connections that are installed at
the housing, see item 1 and 2. The relay cabling occurs via
standard cable entries and PG screw connections, see item 3 and
4.
28
Plug-in connections for power supply and channels
M12 plug-in connection (5-pin) socket (item 1)
View of the plug-in connections in the installed state from outside
As the testo 6381 has a metal housing, we recommend that the
instrument be earthed. This can be done using the earthing
terminal within the instrument (1) or the earthing terminal outside of
the instrument (2).
Only use the external earthing terminal in dry interiors.
4 Transmitter
Using the earthing terminal within the instrument
1. Guide shielded cable (5) through the cable coupling (x) and fit
cable lug (8). Fix this to the side of the instrument (6) using M 5
screw (3), washer (4) and snap ring (7) on the internal earthing
terminal (1).
2. Place the other cable end on an appropriate functional earth,
e.g. an earthing bar.
Using an earthing terminal outside of the instrument
1. Use PE line (yellow-green) (5) with cable lug (8). Fix this using
M 5 screw (3), washer (4) and snap ring (7) on the external
earthing terminal (2).
2. Place the other cable end on an appropriate functional earth,
e.g. an earthing bar.
In general, the Ethernet module performs two functions:
• a corresponding testo 6381 becomes a Saveris subscriber
• a corresponding testo 6381 can be integrated into any Ethernet
systems
4.3.4.2. Mains connection
33
> Connect the network cable to the transmitter.
The network cable must not be connected directly to the
telephone network (ISDN).
In order to ensure the IP protection class, an RJ 2.5 Harting
PushPull connector must be used.
4 Transmitter
4.3.4.3. LED status displays
Characteristic LED 1 LED 2
Colour green green
Status display for Voltage supply LAN connection
Status: off No voltage supply No LAN connection
Status: lights up Voltage supply present LAN connection
Status: flashes Data transfer
4.3.4.4. testo 6381 as Saveris subscriber
Setting the IP address
✓ Upper part of housing must be removed.
✓ Network cable must be connected to the Saveris base and to
the Ethernet module.
✓ Service plug must be inserted.
The IP address of the transmitter can either be set via the P2A
software (transmitter accessories) or via the configuration menu of
testo Saveris
TM
(testo SaverisTM Ethernet Wizard).
present
34
1. Set the IP address with the P2A software (see Using the
software, page 72) or with the testo Saveris
TM
Ethernet Wizard
(see instruction manual).
2. Disconnect service plug.
3. Disconnect the Ethernet module from the voltage supply.
4. Close instrument (see Closing the instrument, page 32).
Using Saveris
> Start Saveris software (see instruction manual Measurement
data monitoring with testo Saveris)
Ensure that the Saveris software is not already open, for
example in multi-user operation under Windows
®
Vista. If
multiple clients are installed in a network, make sure that no
simultaneous changes are made to the system
configuration by the clients during simultaneous operation
of the clients.
4 Transmitter
1. [Start] | All Programs | Testo |
• Select Saveris Professional Client (full version). The entry is
available if Saveris Professional Client is installed
• Select Saveris Viewer (limited functionality). The entry is
available if Saveris Viewer is installed
- The Testo Saveris software program window is opened with
the Select project dialogue.
If the software will not start, check whether the testo
tdassvcs service is started in the service management of
the operating system and restart it, if needed.
2. Select the
• Only active projects option if the data from a running
project should be opened
• All projects option if the data from a completed project
should be opened.
3. Select the project that is to be opened in the tree structure.
4. Confirm with [OK].
- The Testo Saveris software program window is shown with
Pos: 49 /TD/Erste Schritte/MUF 63xx/Ethernet -spezifisch/I nt egr ation Ethernet -Syst em 635x @ 3\mod_1234881594495_79.doc @ 26521 @ 4555555555
the selected data record in the foreground.
4.3.4.5. Integration into customer's Ethernet system
Precondition
The user should be familiar with the structure of an XML
document. Furthermore, enough knowledge should be
available that this type of document can be downloaded
and decoded via an Internet connection with the aid of a
programming/script language.
35
4 Transmitter
Interface
The communication takes place according to the client/server
principle, whereby the Ethernet module takes on the role of the
server:
The XML interface will be approached via a URL. The URL consists
of the IP address of the Ethernet module, the path for the XML
document and, depending on the URL, with a clearly defined
parameter. If a parameter is missing or an incorrect value is
transferred, the Ethernet module sends back a simple error
message.
Example:
IP address = 254.169.100.100
URL for serialnumber.xml:
http://254.169.100.100/data/getserialnumber
If a parameter is required, a "?" is always in the first place after the
URL, then the parameter is transferred to the common query string
form (name=value).
Example:
IP address = 254.169.100.100
URL for / identification.xml:
http://254.169.100.100/config/getidentification?param=0 (compare
table xml codes)
After calling up the compound URL, if everything was correct, an
XML document is returned. With faulty parameters a simple
HTML answer comes that points out the reason that an XML
answer could not be given.
If an XML document is to be loaded on the server, access is
provided by means of a POST request
Example of an upload via the program wget:
IP address = 254.169.100.100
URL for / usersettings.xml:
Path details of the folder in which
the wget program is located
measurement_valueParent element. Contains the chil d
elements value, unit, resolution
value ReadingNumeric a l , decim al num ber
unitUnitASCII
number_valuesQty.Numeri cal, whole number
38
4 Transmitter
Elements in calibration.xml
XML tag Description Type
calibration_dataBase element. Contains the child
el em ents unit, attenuatio n,
cal_reserved , cal_offset, cal_scale.
unitSe e general elem ents
attenuationDamping (0 - 15)Numeri cal, decimal num ber
cal_offsetOffsetNumeri cal, whole number
cal_scal e Parent e l ement. Contains the child
elemen ts cal_m in sca l e , cal_ m a xscale
cal_minscale Scaling value Numerical, decimal number
cal_maxscale Scaling value Numerical, decimal number
Elements in collectivealarm.xml
XML tag Description Type
colalarmtableBase element. Contains the child
alarm_numbersNumber of alarm messagesNume ri cal, whole number
alarmPare nt ele me nt. Contains the chil d
alarm_eventType of ala rmASCII
alarm_state
el em ents alarm _num be rs, alarm
el em ents alarm _event, al arm_sta te
Status of the alarm
0 = alarm i nactive
1 = alarm active
Numerical, whol e num ber
Elements in firmwaredate.xml
XML tag Description Type
firmware_dateBase element. Contains the child
el em ents ye ar, month, day
yearYearNumeri cal, whole number
mo nth Month Numerical, whole number
day Day Numerical, whole number
Elements in hourscount.xml
XML tag Description Type
hourcountBase element. Contains the child
el em ent hours
hoursS ervice hour co unter in hNum eric al , whol e num ber
39
4 Transmitter
Elements in identification.xml
XML tag Description Type
identBase element. Contains the child
element device_id
device_idTransmitter typeNumeri cal, whole number
Elements in laststatusmessage.xml
XML tag Description Type
mufmsgBase element. Contains the child
el em ents msg, sn, hours
msgStatus m essageASCII
sn Se ri al numbe r ASCII, 8 characters
hours S ervic e hour counter in h Numeri cal, whole number
Elements in onlinevalue.xml
XML tag Description Type
online_valuesBase element. Contains the child
el em ents number_val ues,
measurement_value
number_valuesSe e general elem ents
measurement_value See general elements
Elements in options.xml
XML tag Description Type
optionsBase element. Contains the child
ele m en ts devi ce_ options,
production_options
device_optionsSe e de v i ce_options description Numeri cal, whole number
production_opti ons S ee prod uction_optio ns descriptio n Numerical , whol e num ber
Elements in reldefinition.xml
XML tag Description Type
relay_dataBase element. Contains the child
el em ents relay_channel, rel ay_number,
rel ay_status, sw_point_character,
sw_p oint_val ue, hys teresis_val ue
relay_channelM easurement channel l i nked to the
relay
rel ay_numb er Relay number (0 to 4) Num eric al , whol e num ber
Numeri cal, whole number
40
4 Transmitter
XML tag Description Type
relay_status
sw_point_charact
sw_p oint_value Switch p oint Numeri cal, decimal num ber
hys teresis_value Hysteresis Num eric al , decim al num ber
Status of relay
0 = off
1 = o n
Switch point: Switc h point:
0 = low-li mit mo ni toring
1 = high-lim i t monito ring
Numerical, whol e num ber
Numerical, whol e num ber
Elements in serialnumber.xml
XML tag Description Type
serialnumberBase element. Contains the child
el em ent number
numberSe ri al numberASCII, 8 characte rs
Elements in status.xml
XML tag Description Type
mufstatusBase element. Contains the child
statemsg
staterel
statecounter Counter Numeric al , whol e num ber
ele m en ts st atems g, st a terel ,
statecounter
Status m essage
See statemsg description
Status relay
See staterel description
Numeri cal, whole number
Numerical, whol e num ber
Elements in usersettings.xml
XML tag Description Type
usersettingsBase element. Contains the child
elements (pressure)*6,
(abs_pressure_pa_process)*,
(temperature_c_process)*,
(abs_pressure_pa_norm)*,
(temperature_c_norm)*,
(abs_pressure_pa)*, (area)*,
(correction_factor)*, (pi tot_factor)*,
setting_display, backlight, contrast,
lang uage, disp_msg
pressureAbsolute pressureNum eric al , decim al numbe r
* Chi ld elements are opt io nal
41
4 Transmitter
XML tag Description Type
setting_display
backlight
contrast
language
disp_msg
abs_pressure_pa_process,
temperature_c_process
abs_pressure_pa_norm
humidity_norm
temperature_c_norm
area
correction_factor
p ito t_ fa ctor
Auto OFF background lighting
0 -> b ackground lighting auto off
1 -> b ackground lighting stay s on
Brightnes s of background lighting
0 to 9 (0 = off, 9 = max. )
Displ a y contrast
0 to 9 (0 = m i n., 9 = max.)
Language
0 ->German
1 ->Engli sh
2 ->French
3 ->Spanis h
4 ->Ital i an
5 ->J apane se
6 ->Swedish
Status m essages displ ay
0 = off
1 = o n
Pr ess u re pr oc ess data, absolute
pressure in Pa
Pr ess u re pr oc ess data, pro cess
temperature i n °C
Pre ssure standard da ta, absol ute
pressure in Pa
Pre ssure s tandard data, process
humidity in % RH
Pre ssure s tandard data, process
temperature i n °C
Cross-section of the duct in mm²
Correction factor
Pi tot tube facto r
Numerical, whol e num ber
Numerical, whol e num ber
Numerical, whol e num ber
Numerical, whol e num ber
Numerical, whol e num ber
Numeri cal, decimal num ber
Numeri cal, decimal num ber
Numeri cal, decimal num ber
Numeri cal, decimal num ber
Numeri cal, decimal num ber
Numeri cal, decimal num ber
Numeri cal, decimal num ber
Numeri cal, decimal num ber
Elements in versions.xml
XML tag Description Type
firmware_versionBase element. Contains the child
element version
versionFirm ware v ersio n:ASCII, 6 characte rs
Elements in viewchannels.xml
XML tag Description Type
view_channelsBase element. Contains the child
el em ents number_val ues, view_channel
number_valuesSe e general elem ents
42
4 Transmitter
XML tag Description Type
view_channel Pare nt ele me nt. Contains the chil d
elements channel_info,
me asureme nt_v al ue, me as_status
channel_info Pare nt ele me nt. Contains the chil d
elements connector_info, channel_type
measurement_value See general elements
me as_status Parent ele me nt. Contains the child
el em ents mi n, max, mean
connector_info Channel (transmitter) ASCII
channel_type Parameter details ASCII
min. M i nimum readi ng Numeri cal, decimal num ber
max. Max i m um read i ng Nume ri cal, decimal num ber
me an Mean v al ue Numeri cal, decimal num ber
production_options description
Content of production_options is a double word type number (32
bit). The individual hardware options are bit-coded here.
xxxx xxxx xxxx xxxx xxxx xxx1 2222 3334
1 0=2-wire
1=4-wire
2 free
3 0=4 to 20 mA
1=0 to 20 mA
2=0 to 1 V
3=0 to 5 V
4=0 to 10 V
4 0=1 analog output
device_options description
Content of device_options is a double word type number (32 bit).
The individual instrument options are bit-coded here.
xxxx xxxx xxxx xxxx xxxx xxxx 1222 2345
1 free
2 free
3 free
43
4 Transmitter
xxxx xxxx xxxx xxxx xxxx xxxx 1222 2345
4 0=no relay present
1=relay present
5 0=no display
1=display present
statemsg description
Content of statemsg is a double word type number (32 bit). The
individual status messages are bit-coded here.
If statemsg = 0 there are no new messages.
If statemsg != 0
xxxx xxxx xxxx xxxx xxxx xxxx 1234 5678
1 free
2 free
3 free
4 free
5 free
6 1=transmitter information
7 1=transmitter warning
8 1=transmitter error
44
staterel description
Content of staterel is a double word type number (32 bit). The
individual relay states are bit-coded here.
xxxx xxxx xxxx xxxx xxxx xxxx xxxx x123
1 0=relay 4 is not set
1=relay 4 is set
2 0=relay 3 is not set
1=relay 3 is set
3 0=relay 2 is not set
1=relay 2 is set
4 0=relay 1 is not set
1=relay 1 is set
More information can be found in the download area at
www.testo.com.
The purpose of adjusting the analog outputs is to adjust the signal
chain from the digital signal (within the transmitter) to the analog
outputs. The signal type that was appointed for the transmitter is
adjusted respectively for each channel (e.g. 4 to 20 mA or 0 to 1 V,
etc.).
4 Transmitter
1 Status LED
2. Contact ch. 1+
3. Contact ch. 1-
4. Service interface
Adjusting analog output 1
✓ With testo 6381 with current output: Load of max. 500Ω is
connected to channel 1 (see Plug-in connections for power
supply and channels, page 28)
✓ A precise multimeter (minimum requirement: resolution 6.5
digits, at least 5-times more accurate than the 6381) is
available.
If only a simple multimeter is available, the analog output
must not be adjusted.
✓ The service flap is open.
45
4 Transmitter
1. Connect the inputs of the multimeter with the contacts (2) and
(3) for channel 1.
2. Transfer the reference analog value measured with the
multimeter into the P2A software (see Adjusting the analog
output, page 92) or enter it via the user menu (see Performing
analog adjustment, page 61).
3. Disconnect connections between the multimeter and the
contacts of the testo 6381 and close the service flap.
4.3.5.2. n-point adjustment
With an n-point adjustment, the parameters at the 3-6
measurement points are adjusted to the reference value. The
reference conditions are obtained by using a precise pressure
sensor that should be 5-times more accurate than the transmitter.
1 Positive pressure connection
2. Negative pressure connection
3. Pressure sensor
46
The number of measuring points is set to 3 by the factory
and can only be changed using the P2A software (see n-point adjustment, page 91).
The n-point adjustment must always be carried out to its full
extent and in good time at all selected measurement points.
✓ A precise pressure sensor (5-times more accurate than the
transmitter, e.g. DPC precision pressure sensor from testo
industrial services) is available.
1. Connect the positive output of the pressure sensor (3) to the
positive pressure connection of the transmitter (1) and the
negative output of the pressure sensor (3) to the negative
pressure connection of the transmitter (2).
2. Transfer the reference pressure value created with the pressure
sensor into the P2A software (see n-point adjustment, page 91)
or enter it via the user menu (see Performing analog
adjustment, page 61).
3. Repeat step 2 for all of the measuring points.
4 Transmitter
4. Disconnect connections between the pressure sensor and the
Pos: 54 /TD/Pr odukt verwenden/MUF 63xx/ Zusamm enhang Bedienmenü – Mini DIN Buchse aktiv @ 3\m od_1234454016014_79.doc @ 25213 @ 3
pressure connections of the testo 6381.
4.4.1. Relationship between user menu and mini-DIN
socket is active
The testo 6381 can be parameterized using either the user menu or
the P2A software (see Parameterizing, adjusting and analyzing
software (P2A software) page 69).
The testo 6381 transmitter can only be operated via the
display and keypad if the display option is available.
If the testo 6381 is connected to the P2A software, the user
menu is blocked for the duration of the communication. The
message Service plug is shown in the display of the testo
6381. As soon as the P2A software is disconnected, the
✓ The service flap is opened, see Opening the instrument, page
21.
1. Unscrew screws (3) and remove key frame (2).
2. Insert key cover (1) into service flap and tighten screws (3).
3. Close and screw down the service flap.
4.4.3. Password protection
The user menu can be protected with a four-digit numerical code
(see Editing Main Menu Settings, page 55) so that access to the
user menu is denied to unauthorized persons not familiar with this
numerical code.
If the password protection is not to be used, the numerical code
With the alarm, the relays, available as options, are programmed.
In addition, the alarm statuses are shown on the display (top right)
(even without relays).
53
4 Transmitter
You can choose whether the alarm is to be used to monitor limit
values or as a collective alarm. If an alarm is to be used to monitor
limit values, you can choose between monitoring the minimum or
maximum value and set a limit value and hysteresis for each alarm.
In addition, every alarm can be linked to a clearly visible visual
alarm (display background lighting flashes).
An alarm delay between 0 and 240 seconds can still be assigned to
every alarm used for limit value monitoring so that both the
corresponding relay effect and the visual alarm are delayed. If the
alarm status goes out within the set alarm delay time, neither the
visual alarm nor a relay connection is triggered. .
With an alarm status present, the visual alarm and all relay outputs
can be reset by means of acknowledgement. The triggering of a
new alarm cannot be enabled until after the alarm status goes out.
1. In the Measuring Mode press SET, select Main Menu Alarm
with X or S and confirm selection with SET.
- Four alarms can be parameterized.
2. Select Alarm x with X or S and confirm selection with SET.
54
Using alarm to monitor limit values
NO contact
Monitoring minimum Monitoring maximum
Hysteresis
Limit value Limit value
Hysteresis
NC contact
Monitoring minimum Monitoring maximum
Hysteresis
Limit value Limit value
Hysteresis
3. Select Channel x (e.g. "Channel 1") with X or S and confirm
selection with SET.
4. Select Max control or Min control with X or S (see graphic).
5. Press SET and edit Limit value as well as Hysteresis: Scroll
one digit to the right using X and increase value of digit by 1
using S. Confirm with SET or abort entry with ESC.
6. Select Visual alarm with X or S. Select YES or NO with X or
7. Press SET and edit Alarm delay: Scroll one digit to the right
8. Return to Channel x with ESC.
9. Return to Alarm x with ESC.
10. Change to the other relays using X or S and perform settings
Using alarm as collective alarm or not using it at all
If an alarm is assigned to the collective alarm, the relay is switched
and a visual alarm can be issued via the display as soon as (at
least) one of the warning or error messages of the testo 6381
transmitter becomes active.
✓ Alarm is selected (see previous steps 1 and 2).
1. Use X or S to determine whether Alarm x should be used as a
2. If collective alarm is selected: Select Visual alarm with X or S.
3. Change to another alarm using X or S and perform settings in
4. Return to Main Menu Alarm with ESC.
5. Continue to Main Menu Settings with X or S or return to
using X and increase value of digit by 1 using S (0 to 240
seconds possible). Confirm with SET or abort entry with ESC.
in the same way.
The messages affecting the collective alarm can only be
selected in the P2A software, see Using the software, page
72
Collective alarm or not used. Confirm selection with SET.
Select YES or NO with X or S. Confirm with SET and return to
Alarm x.
the same way.
Measuring Mode with ESC.
4.4.6.3. Editing Main Menu Settings
You can edit instrument settings and other settings.
> In Measuring Mode, press SET, select Main Menu Settings
using X or S and confirm selection with SET.
You can edit settings for:
• Display
• Language
• Code
• Units
55
4 Transmitter
◦ Absolute pressure
◦ Area
◦ Temperature
◦ Standard data
◦ Process data
Editing display settings
You can set the brightness and contrast of the display.
1. Select Display Settings with X or S and confirm selection with
SET.
2. Select Backlight or Contrast with X or S and confirm
selection with SET.
One of the following parameters can now be selected using X or S, after which the selection must be confirmed with SET:
• Backlight
The display illumination is changed.
Edit/select parameter with X or S, confirm with SET or cancel
entry with ESC (the effect of the change in parameter can be
seen during input).
• Contrast
The brightness difference between the display background and
the displayed values is changed.
Edit/select parameter with X or S, confirm with SET or cancel
entry with ESC (the effect of the change in parameter can be
seen during input).
• Backlight 24h on
Select On or Off using X or S and confirm with SET.
Off: The display light switches off automatically if no button was
pressed for 10 seconds.
On: The display light is activated
3. Return to Display Settings with ESC and use
continue to Language.
X or S to
56
Selecting language
You can select the language for the plain text line in the display.
> Press SET, select required language with X or S, confirm
selection with SET and return to Language.
4 Transmitter
Only choose a language that you can understand well.
Select unit
This setting affects the unit of the standard and process data.
1. Press SET, select Change parameters with X or S, confirm
selection with SET or cancel with ESC.
2. Select Change unit with X or S, confirm selection with SET or
cancel with ESC.
3. Select the required variable (absolute
pressure/area/temperature) with X or S, confirm selection with
SET or cancel with ESC.
4. Select the required unit with X or S, confirm selection with SET
or cancel with ESC.
5 Return to Change unit with ESC and continue to Standard
data with X or S.
Editing standard data
Setting individual values for the standard data to calculate the
volumetric flow rate.
1. Select Standard data with X or S, confirm selection with SET
or cancel with ESC.
2. Select the required variable (absolute pressure/temperature)
with X or S, confirm selection with SET or cancel with ESC.
3. Scroll one digit to the right using
X and increase value of digit
by 1 using S. Confirm with SET or abort entry with ESC.
4. Return to Standard data with ESC and useX or S to continue
to Pressure process data.
Editing pressure process data
Setting of the process data for the Pitot tube calculation.
1. Select Pressure process data with X or S and confirm
selection with SET.
2. Select the required variable (absolute
pressure/humidity/temperature/cross-section/Pitot tube
factor/correction factor) with X or S, confirm selection with SET
or cancel with ESC.
3. Scroll one digit to the right using X and increase value of digit
by 1 using S. Confirm with SET or abort entry with ESC.
4. Return to Pressure process data with ESC.
57
4 Transmitter
5. Return to Change parameters with ESC and useX or S to
continue to Code.
Editing code settings
You can set the access code (password).
If a code other than "0000" (factory setting) is set, the
transmitter can only be operated once this code has been
entered via the menu.
1. Select Code with X or S and confirm selection with SET.
2. Scroll one digit to the right using X and increase value of digit
by 1 using S. Confirm with SET or abort entry with ESC.
You can test the functionality of analog and relay outputs. In
addition, you can read off the minimum and maximum values (since
the last voltage supply or reset of the min./max. values).
58
Testing functionality of analog outputs
This function affects the analog outputs directly, not only
the test contacts.
1. In the Measuring Mode press SET, select Main Menu Analysis
with X or S and confirm selection with SET.
- Test Analog Output is shown.
2. Press SET, scroll one digit to the right using X and increase
value of digit by 1 using S. Any analog output value can be
predefined, e.g. for an analog output of 4 to 20 mA, the value
"6.0 mA". Confirm with SET or abort entry with ESC.
3. Accept setting by pressing SET and test with multimeter
(minimum requirement: resolution 6.5 digits, at least 2-times
more accurate than the 6381) as follows:
Analog output 1: Via test contacts under service flap, see
diagram.
4 Transmitter
1 Channel 1
test contacts
2 Service
interface
3 Multimeter
4. Return to Test Analog Output with ESC and useX or S to
continue to Test Relay Output.
Testing functionality of the pressure sensor (Test pressure
sensor)
This function is only required to calibrate the pressure
sensor.
Testing functionality of relay outputs
1. Press SET and choose between Alarm 1, 2, 3, 4 with X or S.
2. Press SET.
The relay can now be tested. You can choose between OFF
and ON using X or S. If ON is chosen, the NO contact is
closed, the NC contact opened. If OFF is chosen, the NC
contact is closed, the NO contact opened.
3. To test, route a measuring cable from the relay terminals (see
Connecting the relay outputs, page 25) out of the transmitter to
a multimeter (resistance measurement) or continuity tester.
4. Return to Test Relay Output with SET (starts relay test) or
ESC (exits the menu without relay test).
Reading off min./max. values of channels
To reset the max./min. values, see Editing Reset main menu, page
63
1. Read off the min./max. values of the channel in succession with
X or S and return to the Main Menu Analysis with ESC.
2. Continue to Main Menu Message with X or S or return to
Measuring Mode with ESC.
Messages can be confirmed/acknowledged, the last messages can
be called up and the display of the messages can be switched on
or off.
Using the P2A software (see Parameterizing, adjusting and
analyzing software (P2A software), page 69) you can
predefine whether messages are to be shown in the
display.
1. In the Measuring Mode press SET, select Main Menu Message
with X or S and confirm selection with SET.
2. Confirm Confirm message using SET.
3. Select Last messages with X or S and confirm with SET.
4. Scroll between the warning and error messages recorded so far
using X or S and return to Last messages using ESC.
5. Select Information with X or S and confirm with SET.
6. Scroll between the status messages recorded so far using X or
S and return to Information using ESC.
7. Continue to Display of message with X or S.
ON: Measurements are shown on the display in Measuring
Mode.
OFF: No messages shown on display.
8. Select ON or OFF with X or S and confirm selection with SET.
9. Return to Main Menu Message with ESC.
1 Operating hours at the
time of message
2 Message code (see
Status, warning and error
messages, page 63).
3 Message text
4 Message number
(example: "4/7" refers to
the fourth of seven
messages)
5 Number of messages
present (example: "4/7"
refers to the fourth of
seven messages)
60
10. Continue to Main Menu Ident with X or S or return to
Measuring Mode with ESC.
An overview of the messages can be found in Status,
4. Press SET. Read off multimeter display and enter this value in
the user menu. Do this by scrolling one digit to the right using X
and increasing the value of digit by 1 using S. Confirm with
SET or abort entry with ESC.
5. Use X or S to select Adj. Point 2.
6. Press SET. Read off multimeter display and enter this value in
the user menu. Do this by scrolling one digit to the right using X
and increasing the value of digit by 1 using S. Confirm with
SET or abort entry with ESC.
7. Use X or S to select Adj. Point 3.
8. Press SET. Read off multimeter display and enter this value in
the user menu. Do this by scrolling one digit to the right using S
and increasing the value of digit by 1 using X. Confirm with
SET or abort entry with ESC.
9. Return to main menu Adjust with ESC.
10. Continue to main menu Reset with X or S or return to
Measuring Mode with ESC.
Performing the pressure adjustment
Also see n-point adjustment, page 46, for instructions on how to
perform the pressure adjustment.
1. In the Measuring Mode press SET, select main menu Adjust
with X or S and confirm selection with SET
.
The pressure adjustment can be performed at 3 to 6
adjustment points.
2. Select Adjust Pressure with X or S and confirm with SET.
3. Use X or S to select Adj. Point 1.
4. Press SET. Read off pressure sensor display and enter this
value in the user menu. Do this by scrolling one digit to the right
using X and increasing the value of digit by 1 using S. Confirm
with SET or abort entry with ESC.
5. Repeat steps 1 to 4 for adjustment points 2 to 6.
6. Return to main menu Adjust with ESC.
7. Continue to main menu Reset with X or S or return to
Measuring Mode with ESC.
62
4.4.6.8. Editing Reset main menu
You can reset the factory settings for the following:
Warning messages show an early warning or a current malfunction
Message Display Cause Remedying of fault
00E00 T ambient high The ambient
00E01 T ambient low The ambient
00809 Pressure too
00E02/00E
05
0081C Alarm 1 Depending on the
0081D Alarm 2 Depending on the
0081E Alarm 3 Depending on the
0081F Alarm 4 Depending on the
Pos: 71 /TD/Pr odukt verwenden/MUF 63xx/ Stat us-War nmeldungen/Fehlermeldung en Messum for mer 635x/6781 @ 3\mod_1236081613819_79. doc @ 27212 @ 3
which may negatively impact measuring.
temperature exceeds
the permissible
temperature for the
transmitter
temperature is below
the permissible
temperature for the
transmitter
The process pressure
high
exceeds the pressure
intended for the
transmitter
Supply voltage
low
The supply voltage is
below the minimum
voltage required for the
transmitter
parameterization of the
relay
parameterization of the
relay
parameterization of the
relay
parameterization of the
relay
Take necessary
measures to lower
ambient temperature,
e.g. through venting or
cooling
Take necessary
measures to raise
ambient temperature,
e.g. through heating
Remove the transmitter
from the process and
take any necessary
measures to lower the
pressure
Take measures to
ensure sufficient
voltage supply
Depending on the
parameterization of the
relay
Depending on the
parameterization of the
relay
Depending on the
parameterization of the
relay
Depending on the
parameterization of the
relay
65
4 Transmitter
4.5.3. Transmitter error messages
Message Display Cause Remedying of fault
01505 Watchdog error Due to a processor
01115 Low adjustment
01116 High adjustment
Pos: 72 /TD/Pr odukt verwenden/MUF 63xx/ Stat us-War nmeldungen/Behandlung von Alarmmeldungen 635x @ 3\mod_1236081852932 _79.doc @ 27252 @ 3
4.5.4. Handling alarm messages
Error messages show a current malfunction.
If the problem occurs
error, the transmitter
performs an automatic
frequently, contact
Testo Service.
restart.
temperature
temperature
Shown on the
display
7
The ambient
temperature is too low
during the pressure
adjustment.
The ambient
temperature is too high
during the pressure
adjustment.
Can be used for
collective alarm8
Take necessary
measures to raise
ambient temperature,
e.g. through heating.
Take necessary
measures to lower
ambient temperature,
e.g. through venting.
Additional
message end9
New limit value x
Scaling changed x
Adjustment DeltaP x
Pressure too high x x
Alarm 1 x
Alarm 2 x
7
If multiple messages/alarms are activated at the same time, only the last
message/alarm is shown. If this is cancelled, the other messages that are still
active are no longer displayed.
8
The message can be assigned the collective alarm function, which means that
the collective alarm is activated as soon as at least one of the messages
assigned to it is activated. The collective alarm can be assigned to each of the 4
optional relays. The collective alarm is then always the same, as it can only be
defined once.
9
The message is shown upon the occurrence of the event causing the message
as well as when closing. Two entries appear in the history in the P2A software:
Message text_start and Message text_end.
66
4 Transmitter
Shown on the
display
7
Can be used for
collective alarm8
Alarm 3 x
Alarm 4 x
Transmitter reset x
Analog adjustment x
T ambient high x x
T ambient low x x
Supply voltage low x x
Watchdog error x
Perform the Confirm message function (acknowledgement of the
alarm via the control keys on the transmitter):
• The message/alarm is no longer shown on the display and the
optical alarm goes out, where applicable. If multiple
messages/alarms are active at the same time, all are reset
simultaneously.
• If at least one message is assigned to the collective alarm, the
collective alarm is reset. If the collective alarm is set on a relay,
the relay is also reset, meaning switched to its neutral position.
4.5.5. Namur fault conditions
If the faults named in the following table occur, the analog outputs
output special values that enable a general fault warning in the
higher-level control system. The values correspond to the "Namur"
Status
message in
the display
0 to
Watchdog
error
Value below
min. scale
Value above
max. scale
industry standard.
Class Display
Analog output
value in the
display
20 mA
Error Previous
21 mA 3.8 mA 1.1 V 5.5 V 11 V
value stops
Underrange Reading 0 mA 3.8 mA 0 V 0 V 0 V
Overrange Reading 20.5 mA 20.5 mA 1.1 V 5.5 V 11 V
4 to
20 mA
Additional
message end9
1 V 5 V 10 V
67
4 Transmitter
Status
message in
the display
Pressure too
Class Display
Analog output
value in the
display
Overrange ooooo · 20.5 mA 20.5 mA 1.1 V 5.5 V 11 V
Convenient "remote monitoring" of the transmitter can be
implemented, for example by using a relay as a collective alarm
(see Editing Main Menu Alarm, page 53) whose messages are
forwarded to a local alarm transmitter (horn, light) or PLC.
4.6.2. Cleaning the instrument
• Only clean the instrument carefully with a moist cloth.
The P2A software is used for the parameterizing, adjustment and
analysis of testo transmitters. The following applies:
• Generally, all newer testo transmitters (as of 2007) are
supported.
• Included with every testo transmitter that is bought new is a CD
that contains a free upgrade of the software, which includes the
device drivers for all transmitters that can be attached at this
time.
• This upgrade can be downloaded at any time via the testo
homepage "www.testo.com/Download/P2A".
The software must only be bought one time, even for owners of
several testo transmitters.
5.1.1. Functions and use
In the P2A software, two different file types are used: The
instrument and the parameter file.
Instrument file
The parameters of a particular transmitter are stored in its so-called
instrument file. Using this file, the parameters can be edited and the
instrument can be tested and adjusted.
Instrument files also contain the respective histories in addition to
the parameter data, i.e. "log books" are kept for the previous
parameterizations, adjustments and messages (see Transmitter
history page 93).
Instrument files are ".cfm" format files.
Parameter file
Parameter files are not tied to a specific individual transmitter and
contain only parameter data/no history data.
If you use various instruments of the same type, you can create
parameter files once (e.g. by saving the appropriate instrument file
as the parameter file) and transmit these onto the other
instruments.
69
5 Parameterizing, adjusting and analyzing software (P2A software)
• Pentium processor of at least 400 MHz or equivalent
• 128 MB RAM
• Graphics resolution of at least 1024 x 768
• Unused hard drive capacity of at least 15 MB
• CD-ROM drive
• USB interface
• At least Internet Explorer 5.0.
Software
The P2A software must be purchased and installed separately from
the transmitter. If it is a new software version, the transmitter is
already supported completely. Older P2A software versions can be
updated via the P2A software upgrade (cf. product CD included
When working with the parameterizing, adjusting and
analyzing software (P2A software), previous knowledge of
Windows
in this instruction manual relates to Windows
®
operating systems is assumed. The description
®
XP.
5 Parameterizing, adjusting and analyzing software (P2A software)
5 Parameterizing, adjusting and analyzing software (P2A software)
Menu Command Explanation
Save as Saves the parameters of an
instrument or parameter file
under a new name.
Edit Copy Copies the parameters of the
marked instrument or parameter
file in the cache.
Paste Pastes the parameters from the
cache in the marked instrument
or parameter file.
View Toolbar
Status bar
? Check instrument
connections
Activates/deactivates the toolbar
or status bar.
Checks the connections to a
connected instrument without the
instrument having to be
activated.
Service A text file with the most important
information on the computer and
the software is opened via
Display service data.
Information Shows the version number of the
P2A software.
2 Toolbar: Shows the Windows-compliant icons for editing.
3 File:
Icon File Explanation
Symbol shows a
transmitter
Instrument
file
Instrument file
Connection to the instrument has
been established.
<Type> <Serial number>.cfm
File name should not be
changed.
Symbol shows a
transmitter with a red
minus sign in the upper
left corner
Instrument
file
Instrument file
Connection to the instrument has
not been established.
73
5 Parameterizing, adjusting and analyzing software (P2A software)
Icon File Explanation
Symbol shows a
transmitter with a white
P for parameter file in
the upper left corner
Parameter
file
<Type> <Serial number>
<Date> <Time>.cfp
File name can be changed.
The name can be selected freely,
but it is recommended that you
retain the reference to the
instrument.
Parameter files are always
marked red; the parameter
values they contain are only
forwarded to the instrument after
being transmitted to the
instrument file.
4 Function buttons: Dialogues on editing and testing the
instrument are opened by means of the buttons.
[Change parameterization] see Changing instrument/parameter
file page 75
[Test/analyze transmitter] see Chapter Analyzing/testing the
transmitter page 86
[Adjusting the transmitter] see Chapter Adjusting the transmitter
page 91
[Transmitter history] see Transmitter history page 93
5 File information:
Status Shown in the window
An instrument file is
selected
A parameter file is
selected
Type, serial number, firmware version of the
instrument.
Type, serial number and firmware version of
instrument for which the parameter file was
created.
Connection status Green = connection is active
Red = connection is inactive
6 Status bar: Shows the current status when editing via the menu
bar.
74
5 Parameterizing, adjusting and analyzing software (P2A software)
Pos: 86 /TD/Pr odukt verwenden/MUF 63xx/ P2A/Ger äte-/Par am et er datei bearbeiten @ 3\mod_1234358080444_7 9. doc @ 24303 @ 34
5.3.2. Editing instrument/parameter file
5.3.2.1. Changing instrument/parameter file
✓ The desired instrument/parameter file is marked.
1. Click on [Change parameterization].
- The Properties of <Instrument type> <Serial number>
dialogue is opened with the Change parameterization register.
If the parameters were transmitted from other parameter files into
the instrument file, a message is shown with which you can
transmit the new parameters to the connected instrument using
[Yes].
> If the parameters should not be transmitted, click on [No].
3. Select storage location and enter the file name.
4. Click on [Save].
- The new parameter file is shown in the file list.
84
5 Parameterizing, adjusting and analyzing software (P2A software)
Only the parameters are saved from an instrument file; the history
data are not adopted.
The original name (Instrument type, Serial number) is
suggested with the current date/time as standard, e.g.
"testo 6381 01234578 061120 1403.cfp".
For a standard installation, the files are saved under
"C:\Documents and Settings\All Users\Shared
Documents\P2A Software". The path can differ depending
Required field: Entry of the value read off at
the multimeter.
Parameterizations, adjustment processes and messages that have
occurred are registered in the transmitter with an operating hours
stamp.
In the history overviews (explained later in more detail), past
processes and events can be made visible.
For parameter changes or adjustments that are performed
directly at the instrument (via the user menu), "Transmitter"
is entered in the User field and only the operating hour is
entered in the Date/time field instead of operating
hour/date/time.
For entries that are performed using the P2A software, the
name of the user logged into Windows appears in the User
field, while the date/time and operating hour are shown in
the Date/time field.
1. Mark the instrument file of the connected instrument.
2. Click on the [Transmitter history] button.
- The Properties of <Instrument type> <Serial number>
dialogue is opened with the Transmitter history register.
3. Click on the required entry in the list to change the display.
93
5 Parameterizing, adjusting and analyzing software (P2A software)
Field Explanation
Operating hours /
date/time
Operating hour/time stamp at which the
change at the instrument was performed.
User Name with which the user is logged into the
operating system.
"Transmitter" entry if the change was
performed at the instrument.
Comments Type of parameter change, e.g. "Unit of
channel 1 from Pa to bar".
94
5 Parameterizing, adjusting and analyzing software (P2A software)
Field Explanation
Selection: Analog adjustments.
Operating hours /
date/time
Operating hour/time stamp at which the
change at the instrument was performed.
User Name with which the user is logged into the
operating system.
"Transmitter" entry if the change was
performed at the instrument.
Unit Unit during the adjustment.
Channel Analog adjustment: Channel 1 to n.
Specification Analog adjustment: Actual value.
Pressure
specification
n-point adjustment: Reference value set at
the pressure sensor.
Multimeter Analog adjustment: Reference value set at
the multimeter.
Offset Analog adjustment: Deviation at time of
adjustment.
95
5 Parameterizing, adjusting and analyzing software (P2A software)
Field Explanation
The table is shown only for error and status messages that were
generated in the transmitter and were transferred and saved there
via the connection to the P2A software.
Operating hour Operating hour at which the message
appeared in the instrument.
Message e.g. "Watchdog error". Due to a processor
error, the transmitter performs an automatic
restart.
Type of message e.g. early warning, status message.
> To print out the history data, click on [Print].
The printing job is automatically sent to the default printer
for the operating system.
Pos: 110 /TD/Übers chrift en/8. Tipps und Hilf e @ 0 \m od_1173789887985_79. doc @ 406 @ 1
4. Click on [OK] or [Cancel] to close the dialogue.
The printout can be edited using [Set up printer …].
96
6 Tips and assistance
Pos: 111 /TD/Übers chrift en/8.1 Fragen und Ant worten @ 0\mod_1177402017078_79.doc @ 1093 @ 2
6.1. Questions and answers
Pos: 112 /TD/Tipps und Hilf e/F r agen und Antworten/ MUF 635x @ 3\mod_1236607627223_79. doc @ 27543 @
Question Possible causes/solution
Connection to instrument
Check connection cable/plug contacts
cannot be established
A message appears on the
display
Malfunction (with and
without display)
See Status, warning and error
messages, page 63
Analysis using the P2A software, see
Analyzing/testing the transmitter, page
86
When does a stable
After approx. 20 seconds
current reading appear?
If we could not answer your question, please contact your dealer or
Testo Customer Service. For contact details see the rear side of
Pos: 113 /TD/Übers chrift en/8.2 Zubehör und Er satzteile @ 0\mod_1177402058734_79. doc @ 1102 @ 2
6.2. Accessories and spare parts
Pos: 114 /TD/Tipps und Hilf e/Z ubehör und Ersat zteile/M UF63xx/Zubehör Er satzt eile MUF 635x @ 3\m od_1235640016819_79.doc @ 26783 @
this document or the web page www.testo.com/service-contact
analyzing) incl. USB adapter
Plug-in connections
Set of M12 plug-in connections (connector
and socket) for power and signal lines
Hoses
Silicone hose ID 4 transparent 0086 0001, sold by
TYGON hose ID 4.8 transparent 0086 0031, sold by
6 Tips and assistance
0554 6020
0554 6682
the metre
the metre
97
6 Tips and assistance
Description Article no.
Pitot tubes
Pitot tube, length 350 mm, stainless steel 0635 2145
Pitot tube, length 1000 mm, stainless steel 0635 2345
Supply
Mains unit (desktop, wall-mounted) 0554 1748
Mains unit (top-hat rail mounting) 0554 1749
External display
Process display for testo 54-2 AC.... 5400 7553
Process display for testo 54-7 AC.... 5400 7555
Calibration
Standard ISO calibration certificate,
transmitter only
Standard DKD calibration certificate,
transmitter only
For a complete list of all accessories and spare parts, please refer
to the product catalogues and brochures or look up our website at:
Pos: 115 /TD/Tipps und Hilf e/Z ubehör und Ersat zteile/M UF63xx/Best elloptionen M UF 6380 @ 3\mod_1234277777760_79. doc @ 24261 @ 3
www.testo.com
0520 1000
0520 1200
6.2.1. Ordering options for 6381 transmitter (0555 6381)
Order code Characteristic
Axx Measuring range
A01 0 to 50 Pa
A02 0 to 50 Pa
A03 0 to 100 Pa
A04 0 to 500 Pa
A05 0 to 10 hPa
A07 0 to 50 hPa
A08 0 to 100 hPa
A09 0 to 500 hPa
A10 0 to 1000 hPa
A21 -10 to 10 Pa
A22 -50 to 50 Pa
98
6 Tips and assistance
Order code Characteristic
A23 -100 to 100 Pa
A24 -500 to 500 Pa
A25 -10 to 10 hPa
A27 -50 to 50 hPa
A28 -100 to 100 hPa
A29 -500 to 500 hPa
A30 -1000 to 1000 hPa
Bxx Analog
output/supply
B02 0 to 1 V (4-wire, 24 V AC/DC)
B03 0 to 5 V (4-wire, 24 V AC/DC)
B04 0 to 10 V (4-wire, 24 V AC/DC)
B05 0 to 20 mA (4-wire, 24 V AC/DC)
B06 4 to 20 mA (4-wire, 24 V AC/DC)
Cxx Display
C00 Without display
C02 With display/English
C03 With display/German
C04 With display/French
C05 With display/Spanish
C06 With display/Italian
C07 With display/Japanese
C08 With display/Swedish
Dxx Cable entry
D01 M16 cable entry (relay: M20)
D02 Cable entry NPT 1/2"
D03 Cable contacting via M plug-in