Tesla TI2000GPU-24 User Manual

TI2000 GPU-24
!"#$%&'(#)*"'$%+,
!"#$%& '()*#+,-"#& '(./
012&3"(+",45-(+&6$7)/ 8"9&3%#+$":&;<&02=>1 ?@1>A@>BCD201&4E5(" ?@1>A&@>BCD20>&F%G
www.TESLAind.com
WARNING
*******SHOCK HAZARD POTENTIAL*******
IMPROPER USE/FAILURE TO FOLLOW INSTRUCTIONS IN OPERATORS MANUAL CAN RESULT IN UNIT FAILURE AND/OR POSSIBLE INJURY, OR DEATH, BY ELECTRI­CAL SHOCK.
THE TI2000GPU-24 IS A MAINTENANCE FREE, SEALED UNIT
NO REPAIRS ARE AUTHORIZED.
WARRANTY WILL BE VOID IF
UNIT IS TAMPERED WITH.
FOR TECHNICAL SUPPORT CONTACT:
TESLA INDUSTRIES INC. 109 CENTERPOINT BLVD.
CENTERPOINT INDUSTRIAL PARK
NEW CASTLE,DELAWARE 19720
PH.(302)324-8910
FAX (302)324-8912
WARNING
*******SHOCK HAZARD POTENTIAL*******
ATTEMPTS TO OPEN OR ENTER THE INSIDE OF THIS UNIT (BY USING ANY TOOL OR DEVICE; i.e. PROBE, BORESCOPE, etc.) CAN RESULT IN UNIT FAILURE AND/OR POSSIBLE INJURY BY ELECTRICAL SHOCK. THIS UNIT IS MAINTENANCE FREE AND SHALL NOT BE OPENED OR DISASSEMBLED FOR ANY REASON.
***SHIPPING HAZARDS***
“NONE”
“DRY” Non-spillable, POWER CELL (battery), No Free liquids, to leak or toxic gases.
Always protect unit from short circuit.
Return Power cells to Tesla for Recycling.
i
TABLE OF CONTENTS
TITLE Page CHAPTER 1 INTRODUCTION 1-1 CHAPTER 2 UNIT DESCRIPTION AND OPERATION 2-1 Section I Unit 2-1 Section II Description 2-2 CHAPTER 3 OPERATING LIMITS AND RESTRICTIONS 3-1 Section I General 3-1 Section II Operational Restrictions and Safety Limits 3-1 CHAPTER 4 OPERATING PROCEDURES 4-1 Section I Unit Operation 4-1 Section II Operating Procedures 4-2 Section III Functional Check Procedures 4-5 CHAPTER 5 PERFORMANCE DATA 5-1 Section I Introduction 5-1 Section II Data Criteria 5-2 CHAPTER 6 CARE AND MAINTENANCE 6-1 Section I Unit Care 6-1 Section II Maintenance 6-2 INDEX Index 1
LIST OF ILLUSTRATIONS
Figure Title Page 2-1 Dimensions 2-3 2-2 General Details 2-2 2-3 Fuse Setting Procedures 2-4 5-1 Temperature Conversion Chart 5-3 5-2 Discharge Load Curve 5-4 5-3 Maximum Output Current 5-5
ii
CHAPTER 1
INTRODUCTION
1-1. GENERAL
These instructions are for use by the owner/operator. They apply to handling and operation of the TI2000GPU-24 (Turbo Start 2000) ground power unit.
1-2. WARNING, CAUTION, AND NOTE DEFINED
A warning, caution, or note is used to emphasize important and criti­cal instructions as defined for the following conditions:
WARNING
An operating procedure, practice, etc., which,
if not correctly followed, could result in
personal injury or loss of life.
CAUTION
An operating procedure, practice, etc., which,
if not strictly observed, could result in
damage to or destruction of equipment.
NOTE
An operating procedure, condition, etc., which
is essential to highlight.
1-3. DESCRIPTION
This manual contains the complete operating instructions and proce­dures for the TI2000GPU-24 (Turbo Start 2000) ground power unit. The Turbo Start 2000 is intended to provide DC electrical ground power for aircraft flight line and maintenance ground support operations. The unit is designed to provide 24 volt DC electrical power output for aircraft engine starting and 24 or 28.5 volts DC electrical sup­port for ground maintenance, avionics/electrical trouble shooting and testing. The observance of procedures, limitations and performance criteria is essential to ensure peak operating efficiency and to maximize operational capabilities and life of the Turbo Start 2000 ground power unit.
1-1
䩞䩯
1-4. INDEX
The index lists, in alphabetical order, every titled paragraph and figure contained in this manual.
1-5. ABBREVIATIONS AND SYMBOLS
Abbreviations and symbols are used within text, headings and titles. Unless otherwise indicated, the following list of abbreviations and symbols are used in this manual:
LIST OF ABBREVIATIONS AND SYMBOLS Abbreviation Definition
amp Ampere AC Alternating Current C Celsius cont Continuous DC Direct Current F Fahrenheit Ft Feet FWD Forward GPU Ground Power Unit Hr Hour Hz Hertz Kg Kilograms Kw Kilowatts ° Degree LED Light Emitting Diode MAX Maximum MIN Minimum VAC Volts, Alternating Current VDC Volts, Direct Current
Explosion Hazard Potential
Shock Hazard Potential
Guard from moisture
䨻䩡䩭䨻䩤䩩
䩫䩪 䩮䩪䩰䩭
Guard from incorrect power source
Guard from incorrect power source
1-2
1-6. FORMS AND RECORDS
NONE REQUIRED.
1-7. USE OF WORDS SHALL, SHOULD, AND MAY.
Within this technical manual the word “shall” is used to indicate a mandatory requirement for proper operation and warranty purposes. The word “should” is used to indicate a non-mandatory but preferred method of accomplishment. The word “may” is used to indicate an ac­ceptable method of accomplishment.
1-3
CHAPTER 2
UNIT DESCRIPTION AND OPERATION
SECTION I. UNIT
2-1. GENERAL
The TI2000GPU-24 (Turbo Start 2000) (Figure 2-1 and 2-2) is a compact, portable and highly versatile 24/28.5 VDC electrical ground power unit. The unit incor­porates a 120-240 VAC to 28.5 VDC converter, a 24 volt unique (dry) power cell and an internal intelligent 120 to 240 volt AC charger to recharge the power cells. These built-in features give the Turbo Start 2000 self-sufficiency and mobility for short-term operations without AC electrical power or long term operations with AC electrical power. Short term operations rely solely on power cell output and the fast recharge rates that the unit’s internal charger provides from any standard 120 or 240 VAC electrical outlet. Longer term op­erations incorporate the continuous 20 amp output of the 120-240 VAC to 28.5 VDC converter, or a combination of converter and power cell output to provide 24 VDC output. The following are the unit’s four (4) main operational support capabilities:
a. 24 VDC 3000 amp peak power output for engine starting or constant (one hour) rated power output (without a 120-240 VAC power source) for short term trouble shooting and flexible flight line support ground power.
b. 24 VDC constant (one hour) rated power output or variable high load de­mand output (less than one hour) with a 120-240 VAC power source for extended maintenance (hangar) and routine flight line maintenance, ground support power.
c. 28.5 VDC continuous rated (AC to DC converter) power output with a 120­240 VAC power source for hangar and routine flight line maintenance support, and avionics bench testing.
d. Rapid recharge of the unit’s power cells from any 120-240 VAC common power source. This feature eliminates the need for special recharge equip­ment and dedicated maintenance support man-hours.
WARNING
Check fuse holder window to ensure the fuse setting reads either 120 or
240 prior to connecting recharge cord to AC power source.
Fuse setting (120/
240) must match AC power source (hangar wall, flight line AC power) prior to connecting TURBO START for recharging.
(SEE PAGE 2-4 FOR
FUSE SETTING PROCEDURES)
120 VAC Setting 2-1 240 VAC Setting
SECTION II DESCRIPTION
2.2. GENERAL SPECIFICATIONS WEIGHT
UNIT: 111 lbs (50.39 Kg) DC POWER CABLE: 8.5 lbs (3.86 Kg) AC POWER CORD: 0.4 lbs (0.18 Kg)
INPUT POWER AC
TI2000GPU-24: TI2000GPU-24-UNV:
TI25000-U01 NORTH AMERICAN LINE CORD
TI25000-U04 OLD BRITISH LINE CORD
TI25000-U03 EUROPEAN 10A/250V
TI25000-U05 ENGLAND 10A/250V
OUTPUT POWER DC
CONVERTER: 28.5 VDC TO 20 AMPS, 24 VDC 21 AMPS AND ABOVE. POWER CELLS: 24 VDC PEAK OUTPUT: 3000 AMPS
105-125 VAC 60 Hz 6.50 amps max. 210-250 VAC 50/60 Hz 3.25 amps max.
105-125 VAC 60 Hz 6.50 amps max.
210-250 VAC 50/60 Hz 3.25 amps max.
210-250 VAC 50/60 Hz 3.25 amps max.
210-250 VAC 50/60 Hz 3.25 amps max.
POWER CELL
DRY, HIGH RATE DISCHARGE, RECHARGEABLE, MAINTENANCE-FREE
DC POWER CABLE
LENGTH: 8 FT
AIRCRAFT CONNECTOR: 3 PIN RECEPTACLE (MS25488)
2-3
Fuse Setting Procedures
for Switching Voltages or Changing Blown Fuses
1) Grab both tabs on left and right side of the fuse clip. Press tabs inward and pull fuse clip out of housing GENTLY.
TABS
ENLARGEMENT 1
2) Completely pull fuse clip from housing, being careful not to drop the fuses from the fuse clip.
5) Completely remove the white clip from the fuse clip.
3) Note: The fuses are not fastened into the fuse clip, they are lose. Take care to ensure fuses are not dropped or lost.
ENLARGEMENT 2 120 VAC SETTING
ENLARGEMENT 3 240 VAC SETTING
6) Ensure that the proper voltage is selected on the white clip. (See Enlargement 2 & 3)
4) GENTLY pull the white clip from the fuse clip, taking care not to bend any of the tabs. (See enlargement 1)
7) Replace the white clip back into the fuse clip. Take care not to damage the tabs.
8) Completely insert white clip in to fuse clip (GENTLY) until it snaps into place.
9) Insert fuse clip back into fuse housing EVENLY on both sides. DO NOT FORCE, if fuse clip does not go in easy, it means fuses are mis­aligned, realign fuses and insert again.
2-4
10) Snap fuse clip back into the housing (GENTLY). DOUBLE
CHECK VOLTAGE WINDOW PRIOR TO PLUGGING UNIT INTO AC POWER
2-2
CHAPTER 3
OPERATING LIMITS AND RESTRICTIONS
SECTION I. GENERAL
3-1. PURPOSE
Chapter 3 includes all important operating limits and restrictions that must be observed for proper and safe operation of the TI2000GPU­24 (Turbo Start 2000) ground power unit.
3-2. GENERAL
The operating limitations set forth in this chapter are the direct result of design analysis, testing, and operating experience. Com­pliance with these limitations and restrictions will ensure that own­ers/operators obtain maximum continued capability from the Turbo Start 2000 ground power unit.
SECTION II. OPERATIONAL RESTRICTIONS AND SAFETY LIMITS
3-3. POWER CELL RECHARGE LIMITS
Any time the unit’s power cells are fully discharged the unit shall be recharged within 24 hours to prevent performance degradation and ensure maximum life.
CAUTION
Unit’s power cells may be damaged if recharged by NiCad or Lead Acid-
type battery chargers. Power cells should only be charged by either
the TURBO START internal charger and the AC power cord furnished with
the equipment, or when connected aircraft external DC power recep-
tacle.
3-1
3-4. 120-240 VAC CHARGER AND AC TO DC CONVERTER LIMITS
The unit is designed with a single point AC receptacle for external power to operate both the internal charger and converter. The units AC voltage range can be factory set from 105 to 250 VAC at 50 to 60 Hz depending upon customer requirements. The AC power cord provided with the unit is the mechanism that ensures the specified AC power source is properly supplied to the unit (see paragraph 3-5).Use no others
INTERNAL CHARGER: NO LIMIT AC power cord can remain connected when power cells are fully charged. When the power cells are fully charged the unit’s intelligent charger will go to a stand-by mode, monitor the power cells state of charge, and only charge the power cells to ensure they stay at maximum capacity.
*8$5’ )520 ,1&255(&7
32:(5 628 5&(
INTERNAL AC TO DC CONVERTER: LIMITED (see paragraph 3-6, 3-8 and 3-10). AC power cord does not have to be disconnected when con­verter power output is no longer required. Once DC power demand is terminated the unit’s intelligent charger will remain on line to ensure power cells are charged to maximum capacity.
CAUTION
Unit will be damaged if unapproved AC power is applied.
3-5 AC POWER CORD LIMITS
The AC power cord governs which AC power source the unit is set to operate from. The Turbo Start 2000 is supplied with a single cus­tomer specified AC power cord. Some customers may specify a univer­sal AC option (for worldwide mobility), which comes with two (2) power cords, one for 120 VAC 60 Hz and the other for 240 VAC 50 Hz (SEE APPENDIX A). Each power cord is marked accordingly. Below are the following three (3) types of AC power cords available and their limits.
120 VAC 60 Hz power cord (USA): LIMITED TO 105-125 VAC 60 Hz power source only.
120 VAC 60 Hz power cord (Universal): LIMITED TO 105 VAC to 250 VAC 50/60 Hz power source using proper cord set.
240 VAC 50 Hz power cord (European): LIMITED TO 210-250 VAC 50-60 Hz power source only.
FOR MORE INFORMATION ON POWER CORDS SEE APPENDIX A
3-2
乆乗
AC Line Cords
丣义乕丣乌乑
乓乒 乖乒乘乕
Cont. Europe U.K. Old British North American
CAUTION
Unit will be damaged if unapproved AC power is applied by fitting 120 or 240 VAC power cord with any kind of unapproved modification or adapter that changes the specified input power characteristics.
WARNING
********SHOCK HAZARD POTENTIAL*********
Failure to use proper grounding can cause a potential shock hazard! In different countries, the 240 VAC 50 Hz power cord may require the use of a plug adapter to achieve plug style compatibility for 240 VAC 50 Hz operation. Use only adapters with proper grounding mechanism.
3-6. ONE (1) HOUR RATE, 24 VDC CONSTANT OUTPUT
46 amp hour (without AC power connected), power cell output. (see Figure 5-2) 66 amp hours (with AC power connected), both power cell and AC to
DC converter output.
NOTE
If power output is greater than rated amp hour rate, power cell discharge rate will increase correspondingly.
3-7. RATED PEAK OUTPUT (ENGINE STARTING)
3000 peak amps at 25oC (77oF) (See Figure 5-3).
3-3
3-8. CONTINUOUS OUTPUT RATE, 28.5 VDC CONSTANT OUTPUT
20 amp hours (with AC power connected)
NOTE
If current demand exceeds 20 amps, converter output voltage will drop below 28.5 VDC and two or more LED status indicator bars will illumi-
nate. If all LED status indicator bars illuminate, both the con-
verter and power cells are supplying 24 VDC power output (see para-
graph 3-4 and 4-7.4.).
3-9. ENGINE STARTING POWER
Operators should always ensure the unit is charged above 80% prior to ground support engine starting. However, circumstances may exist during use where unit recharge is not readily available and immediate external engine starting power is required. The following provides minimum states of charge necessary to provide ample power for an ef­ficient engine start under specific current load demands.
ENGINE START CURRENT LOAD DEMAND MINIMUM CHARGE 650-850 peak starting amps 40% charged
850-1000 peak starting amps 50% charged 1000-1500 peak starting amps 60% charged 1500-1800 peak starting amps 70% charged 1800-2500 peak starting amps 80% charged 2500-3000 peak starting amps 90% charged
3-10. TEMPERATURE
Temperatures refer to the unit’s cold/heat soaked temperature. A unit’s cold/heat soaked temperature shall be established by the ambi­ent temperature that a unit is exposed to for one (1) hour or more. If unit’s cold/heat soaked temperature exceeds operating temperature range, unit shall be stabilized prior to operation as follows: COLD SOAKED, warmed for a minimum of 3 hours above +10Co (+41oF) or 2 hours above +20Co (+68oF); WARMED SOAKED, cooled for 1 hour below +38Co (+100oF).
Operating range:
without with
AC power -40Co (-40oF) TO +60Co (+140oF)
AC Power -30Co (-22oF) TO +50Co (+124oF)
Storage range:
-60Co (-76oF) TO +60Co (+140oF)
(C0NTINUED ON NEXT PAGE)
3-4
CAUTION
Unit may be damaged if operated when unit’s cold or heat soaked tempera-
ture exceed the specified limit. If unit is operated when cold or heat soaked temperature limit is exceeded, a full functional check should be
accomplished prior to continued use.
NOTE
If unit should overheat, an over-temperature sensor will shut down 120-
240 VAC functions (charger and converter) until unit cools to normal
operating temperatures.
3-11. ENVIRONMENTAL
Operating any electrical equipment in the presence of moisture cre­ates possible safety hazards and/or potential for equipment damage. Every effort has been made, within the scope of existing technology to prevent foreseeable safety hazards and make the Turbo Start 2000 moisture resistant to prevent damage or failure. If the Turbo Start 3000 is exposed to moisture, preventive measures and precautions shall be taken to:
a. prevent accumulation of moisture on AC and DC con­nectors/receptacles
b. minimize moisture entering FWD inlet and AFT out­let cooling fan vent ports
The limits and operational constraints listed below shall apply for the following environmental (weather) conditions:
Heavy or steady rain: OPERATION NOT RECOMMENDED Light rain, drizzle: NO CONVERTER OR CHARGER 120-240 VAC fog, snow or sleet: POWER SHALL BE APPLIED.
Unit inlet and outlet vent ports shall be covered from exposure. Unit shall be kept horizontal.
3-5
WARNING
********SHOCK HAZARD POTENTIAL*********
Severe injury, or Death, from electrical shock is possible when per-
sonnel and/or Turbo Start 2000 are wet during use and when 120-240
VAC power is being supplied to unit.
CAUTION
Damage may occur if unit is operated after exposure to moisture
(rain, drizzle, fog, sleet or snow) or moisture contamination is sus-
pected. DO NOT USE until unit’s exterior and receptacles are dried.
Operation shall be restricted to use
DO NOT CONNECT 120 or 240 VAC power cord until unit has been dried
for a MINIMUM of one (1) hour, prior to use.
Blowing sand or dust: Minimize exposure to sand and dust when 120-240 AC power is used. Unit shall be kept horizontal dur­ing use.
without 120 or 240 power cord
.
3-12. OPERATING POSITION
Without 120-240 VAC power cord: Horizontal or vertical.
Horizontal only
cord is plugged in and exhaust fan is running.
Unit may be damaged if blown over by propeller, rotor or jet wash, or accidentally knocked over. Unit should be kept horizontal during use.
, for propper unit ventilation, when 120-240 VAC line
CAUTION
3-6
CAUTION
Unit damage may occur if inlet and outlet vent ports are obstructed and/or cooling air flow is restricted.
3-13. UNIT OPERATION DURING AIRCRAFT FUELING/DEFUELING
Power output is restricted to 24 VDC power cell output only. DO NOT CONNECT 120 or 240 VAC POWER SUPPLY. 120-240 VAC power (charger or AC-DC converter) functions of unit shall not be oper­ated during any aircraft fuel handling operation.
WARNING
*******FIRE/EXPLOSION HAZARD POTENTIAL********
Severe injury, or Death, may occur from fire or explosion, as a result of electrical sparks produced near fuel vapors.
3-7
CHAPTER 4
OPERATING PROCEDURES
SECTION I. UNIT OPERATION
4-1. GENERAL
Correct operation of the TI2000GPU-24 (Turbo Start 2000) includes both pre-use and operational checks of the unit. Knowledge of the operating limits, restrictions, performance, unit capabilities and functions is fundamental to correct and safe operation. The operator shall ensure compliance with the instructions in this manual that affect operational safety and the warranty of the unit.
4-2. OPERATING LIMITS AND RESTRICTIONS
The minimum, maximum and normal operating ranges result from careful engineering and evaluation of test data. These limitations must be adhered to during all phases of operation. Refer to Chapter 3, Sec­tion II, OPERATING LIMITS AND RESTRICTIONS, for detailed information.
4-3. PERFORMANCE
Refer to Chapter 5, PERFORMANCE DATA to determine the capability of the Turbo Start. Consideration must be given to changes in perfor­mance resulting from variations in ambient temperature, mode of op­eration, state of charge (with or without 120 or 240 VAC power), and aircraft DC bus system inefficiency (voltage drops).
4-1
SECTION II. OPERATING PROCEDURES
4-4. OPERATING PROCEDURES
This section deals with normal procedures, and includes all steps necessary to ensure safe and efficient operation of the TI2000GPU-24 (Turbo Start 3000). As experience is gained with the Turbo Start 3000, the user will be able to maximize the unit’s unique capabili­ties to enhance the flexibility of aircraft maintenance and support operations.
NOTE
When the TURBO START 2000 is not in use, it should plugged into a suitable AC power source to insure operational readi­ness at all times. REMEMBER,when the AC line cord is plugged in, the
unit must be placed in the horizontal position to allow the cooling
fan to operate properly!
4-5. BEFORE OPERATION CHECK
1.
UNIT INTO THE AC POWER SOURCE TO BE USED
cord is plugged in, the unit must be placed in the horizontal posi­tion to allow the cooling fan to operate properly!
blinking green bar at the bottom of the bar graph column.The fan will
CHECK FUSE WINDOW FOR PROPER SETTING (120/240) BEFORE PLUGGING
. REMEMBER,when the AC line
STA TUS
NOTE:
A full charge is indicated by Either a steady lighted green bar or a
also exhibit ratcheting but will not come on when the unit is fully
charged.
always
remain
2. CHECK UNIT FOR EVIDENCE OF DAMAGE - Check for dents, punctures, case distortion or misalignment, cracked or loose connectors, and
that cooling fan is functioning.
4-2
CAUTION
REMEMBER,when the AC line cord is plugged in, the unit must be placed
in the horizontal position to allow the cooling fan to operate prop-
erly!
Unit may overheat if cooling fan fails. Do not operate if cooling
fan fails.(More than one green bar present on bar graph)
3. CHECK DC POWER CABLE/CONNECTORS FOR DAMAGE - Check cable for cuts, chafing or evidence of being crushed. Check connectors for cracks, cuts, distortions, excessive wear, broken/loose fasteners or loose cable attachment.
4-6. 24 VDC GROUND POWER (NO 120 OR 240 VAC POWER SUPPLY) ENGINE STARTING OR DC SYSTEM POWER
1. TRANSPORT UNIT - The Turbo Start 2000 is easily transported using the wheels that are incorparated into the unit. The AXEL EXTENTION kit (included with the unit) ensures that the Turbo Start 2000 is stable. The unit is engineered to be pushed rather than pulled.
2. CONNECT DC POWER CABLE TO UNIT - Ensure power cable connector is fully seated into unit’s connector. Set
the unit down horizontally
ensuring vent ports are un-blocked.
3. CONNECT DC POWER CABLE TO AIRCRAFT - Ensure ground power cable connector is fully seated into aircraft ground power recep-
tacle. DC bus power should come on and aircraft volt meter should indicate 24 VDC to 23.5 VDC (23 VDC minimum).
4. ENGINE STARTING - Check power cable for security and correct installation prior to engine start. Follow ground power engine
starting procedure as specified in aircraft operators manual.
5. REMOVING DC POWER SUPPLY FROM AIRCRAFT
a. Remove DC power cable GPU connector from aircraft. b. Remove DC power cable connector from Turbo Start (if necessary).
4-3
4-7. 24 VDC GROUND POWER (WITH 120/240 VAC POWER) SYSTEM HIGH POWER DE­MAND (21 amps and above) OR ENGINE STARTING.
1. ing the wheels that are incorparated into the unit. The AXEL EXTENTION kit (included with the unit) ensures that the Turbo Start 2000 is stable. The unit is engineered to be pushed rather than pulled.
2.
TING
an approved AC power supply.
ensure unit’s vent ports are free from blockage
5-8 seconds, unit’s LED status indicator will illuminate indicating power cell state of charge. Cooling fan will operate. Ensure LED status indicator and cooling fan are operational prior to continuing to step 3.
3. CONNECT DC POWER CABLE TO UNIT - Ensure power cable connector is fully seated into unit’s receptacle.
4. CONNECT DC POWER CABLE TO AIRCRAFT - Connect to aircraft ground power receptacle. DC bus power should come on and aircraft volt meter should indicate 27.5 VDC to 23.5 VDC (23 VDC minimum). If cur­rent demand is above 20 amps, converter output voltage will drop be­low 28.5 VDC and two or more LED status indicator bars will illumi­nate. At approximately 21 amps of current demand, converter output voltage will be regulated at 24 VDC output and the last (RED) LED status indicator bar will illuminate.
TRANSPORT UNIT - The Turbo Start 2000 is easily transported us-
CONNECT AC POWER CORD TO UNIT (
).- - Ensure 120 or 240 VAC power cord is properly connected to
CHECK FUSE WINDOW FOR PROPER SET-
Unit shall be in horizontal position to
. After approximately
NOTE
When all LED status indicator bars illuminate, both the converter and
power cells are supplying 24 VDC power output for current demands
above 21 amps (see paragraph 3-4).
5. ENGINE STARTING - UNPLUG AC POWER CORD BEFORE STARTING ENGINE WITH TURBO START. (see paragraph 4-6.). Prior to engine
start, ensure power cell charge is sufficient to provide an efficient engine start (see paragraph 3-7).
6. REMOVING DC POWER SUPPLY FROM AIRCRAFT
a. Remove DC power cable GPU connector from aircraft. b. Remove DC power cable connector from Turbo Start
(if necessary).
4-4
4-8 28.5 VDC GROUND POWER (WITH 120/240 VAC POWER) SYSTEM LOW POWER DEMAND (20 amps or less).
1. TRANSPORT UNIT - The Turbo Start 2000 is easily transported us­ing the wheels that are incorparated into the unit. The AXEL EXTENTION kit (included with the unit) ensures that the Turbo Start 2000 is stable. The unit is engineered to be pushed rather than pulled.
2. CONNECT AC POWER CORD TO UNIT (
TING
).- Ensure 120 or 240 VAC power cord is properly connected to an
approved AC power supply.
Unit shall be in horizontal position to
ensure unit’s vent ports are free from blockage
5-8 seconds, unit’s LED status indicator will illuminate indicating power cell state of charge. Cooling fan will operate. Ensure LED status indicator and cooling fan are operational prior to continuing to step 3.
3. CONNECT DC POWER CABLE TO UNIT - Ensure power cable connector is fully seated into unit’s receptacle.
4. CONNECT DC POWER CABLE TO AIRCRAFT - Connect to aircraft ground power receptacle. DC bus power should come on and aircraft volt meter should indicate 28.5 VDC to 27 VDC (26.5 VDC minimum). If air­craft power demand is less than 20 amps converter output will remain at 28.5 VDC (only one GREEN LED status indicator bar will illumi­nate). If aircraft power demand exceeds 20 amps converter voltage output will decrease and two or more LED status indicator bars will illuminate (see paragraph 3-4, and 7-4.4.).
CHECK FUSE WINDOW FOR PROPER SET-
. After approximately
5. REMOVING POWER SUPPLY FROM AIRCRAFT
a. Remove DC power cable GPU connector from aircraft. b. Remove DC power cable connector from Turbo Start (if neces-
sary).
4-9 POWER CELL RECHARGE
1. CONNECT AC POWER CORD TO UNIT -
sition to ensure unit’s vent ports are free from blockage FUSE WINDOW FOR PROPER SETTING
properly connected to an approved AC power supply. After approxi­mately 5-8 seconds, ensure unit’s LED status indicator illuminates
).- Ensure 120 or 240 VAC power cord is
Unit shall be in horizontal po-
. (
CHECK
indicating power cell state of charge and cooling fan is operating.
4-5
CAUTION
Unit may overheat if cooling fan fails.
Do not operate if cooling fan fails.
2. charge indicator should show a single steady or flashing green LED bar when fully charged, the last LED bar. AC power may be left con­nected to unit when power cells are fully charged.
CHECK FOR FULL CHARGE INDICATION - After 2 HR 30 minutes, LED
NOTE
Under a full charge, two things will be observable with the unit. A non-blinking lighted green bar or a blinking green bar at the bottom of the bar graph, both indicate a full charge.Also the fan will dis-
play ratcheting but not come on whe the unit is fully charged.
4-6
SECTION III.
FUNCTIONAL CHECK PROCEDURES
4-10. FUNCTIONAL CHECK PROCEDURES
This section deals with normal functional check procedures, and in­cludes all steps necessary to ensure the Turbo Start 2000 is func­tioning within specific operational parameters prior to operational use. As users gain experience with the Turbo Start 2000, they will incorporate these functional checks as a routine practice.
4-11. REQUIRED EQUIPMENT FOR FUNCTIONAL CHECK.
FLUKE OR EQUIVALENT TYPE DIGITAL MULTIMETER.
4-12. DC FUNCTIONAL CHECK.
1. CHECK UNIT FOR EVIDENCE OF DAMAGE - Check for dents, punctures, case distortion or misalignment, cracked or loose connectors. If no damage is evident proceed to step two.
IF DAMAGE IS EVIDENT contact distributor or manufacturer.
2. ENSURE UNIT IS NOT PLUGGED INTO 120 OR 240 VDC. Unplug AC power if plugged in.
3. CHECK UNIT INTERNAL RESISTANCE (TEST FOR SHORTS) - Better than 10 Megohms. Ensure no short exists.
Negative (-) DC receptacle terminal and unit case. Positive (+) DC receptacle terminal and unit case.
4. CHECK DC VOLTAGE READING AT DC RECEPTACLE TERMINALS. 24 to 25.5 VDC depending on state of charge.
5. PLUG IN 120 OR 240 POWER CORD. (
TING
).-Ensure power unit is connected to a suitable AC power source
(120 USA or 240 European).
6. CHECK UNIT FOR STATE OF CHARGE -
position to ensure unit’s vent ports are free from blockage
approximately 5-8 seconds, unit LED status indicator shall illuminate indicating power cell state of charge. Ensure LED status indicator
CHECK FUSE WINDOW FOR PROPER SET-
Unit shall be in horizontal
. After
and cooling fan are operational. Prior to continuing to step 7, the LED status indicator should show a single green bar (last LED bar) to indicate the unit’s power cells are fully charged. Also under full charge the fan will ratchet but not enable.
4−7
NOTE
Under a full charge, the last green LED bar may blink. This does not
indicate a malfunction. A nonblinking lighted green bar or a blinking
green bar at the bottom of the LED column, both indicate a full
charge.
7. CHECK DC VOLTAGE READING AT DC RECEPTACLE TERMINALS. Ensure power cells are fully charged (see step 6.)
28.5 (+-0.57 VDC) with power cells at full state of charge.
8. FUNCTIONAL CHECK COMPLETE - Unit should remain plugged in to AC power until required for use.
4−8
CHAPTER 5
PERFORMANCE DATA
SECTION 1. INTRODUCTION
5-1. PURPOSE
This chapter provides performance data for the TI2000GPU-24 (Turbo Start 2 000). Continual reference to this information will enable the user to obtain maximum performance, utilization and service life from the Turbo Start. Although maximum performance is not always required, regular referral to this chapter is recommended for the following rea­sons:
a. To generate knowledge of unit’s performance margins to enable the operator to make sound judgment when unexpected conditions or alternate operational requirements are encountered.
b. To enable the user to readily recognize situations requiring maximum performance.
c. To gain experience in accurately estimating the effects of variables for which data is not presented.
d. To help the operator determine if an aircraft system malfunc­tion exists by comparing actual performance with expected perfor­mance.
NOTE
The information provided in this chapter is primarily intended for operational planning and is most useful when planning operations under unfamiliar conditions or environmental extremes. The data may also be
used to establish local operating procedures and to ensure unit’s
operational life is maximized.
5-2. GENERAL
The data presented covers the maximum range of conditions and perfor­mance that can reasonably be expected. In each area of performance, the effects of temperature and DC electrical load demand relating to
the ground power support requirements are presented. Wherever practi­cal, data is presented conservatively. However, NO GENERAL CONSERVATISM HAS BEEN APPLIED. All performance data presented is within the appli­cable limits of the Turbo Start.
5-1
SECTION II
DATA CRITERIA
5-3 DATA BASIS
The type of data used is indicated at the bottom of each performance chart under DATA BASIS. The applicable report and date of the data are also given. The data provided generally are based on one of three categories:
a. obtained on a similar unit type.
b. unit type placed under a controlled test.
c. ics, mathematics, and electrical engineering principles and con­cepts, but not verified by tests.
5-4. SPECIFIC CONDITIONS
The data presented are accurate only for specific conditions listed under the title of each chart or graph. Variables for which data are not presented, but which may affect that phase of performance, are discussed in associated text. Where data are available or reasonable estimates can be made, the amount that each variable affects perfor­mance will be given.
5-5. GENERAL CONDITIONS
In addition to the specific conditions, the following general condi­tions are applicable to the performance data.
Derived From Actual Controlled Testing.
Calculated Data.
Estimated Data
Data based on tests, but not on a similar
. Data based on estimates using rules of phys-
Controlled test data
a. vidual aircraft of the same make and model are known to exist due to variations in DC electrical system efficiency. These differ­ences, however, are considered insignificant and are not individu­ally accounted for.
b.
Variation in Aircraft.
Power demand differences between indi-
Ground Support and Aircraft Instrument Variations.
The data
shown in the performance charts do not account for instrument toler-
ance differences or inaccuracies.
5-6. DEFINITIONS OF ABBREVIATIONS
Unless otherwise indicated, the abbreviations defined in Chapter 1 will be applicable to all charts and graphs in this chapter.
5-2
FIGURE 5-1
OUTPUT VOLTAGE
TI2000GPU-24 OUTPUT VOLTAGE
24
20
16
5-3
12
8
4
0
0
10 20
30
40
50
60
MINUTES
46 AMP CONSTANT CURRENT LOAD
FIGURE 5-2
MAXIMUM OUTPUT CURRENT
3000 2700 2400 2100
1800
1500
AMPS
1200
900 600
300
*
*
*
*
*
*
*
*
*
(+25 C Temp)
*
*
*
(-29 C Temp)
0
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
5-4
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
0
0
0
Calculations based on actual test data at Pratt-Whitney Canada on 30 March 1992.
5
10
15
SECONDS
FIGURE 5-3
20
25
30
5-5
CHAPTER 6
CARE AND MAINTENANCE
SECTION I. UNIT CARE
6-1. GENERAL
Although the TI2000GPU-24 (Turbo Start 2000) has been ruggedized and made weather resistant within the scope of unit’s intended use,
it is essential that good general care be taken to maintain unit in good operating condition and to maximize unit’s operational life.
6-2. AFTER USE - Unit should be protected from the environmental
elements and man made hazards. Ideally unit should be secured in a building or shed. Most importantly, unit shall be fully covered if stored exposed to environmental elements.
1. KEEP UNIT RECEPTACLES AND OUTER CASE CLEAN - wipe with dry cloth.
2. KEEP FOREIGN OBJECTS OUT OF UNIT - Cover unit to prevent foreign objects, water, and dirt from entering vent ports and recep-
tacles.
3. KEEP FROM PROLONGED EXPOSURE TO EXTREMELY DAMP ENVIRONMENTS Cover unit to prevent migration of moisture. If unit is operated in
extremely damp environments unit should be kept in an environmentally controlled building.
4. KEEP UNIT PLUGGED INTO AC POWER SUPPLY WHEN NOT IN USE. (
FUSE WINDOW FOR PROPER SETTING
to ensure unit is always ready for use, unit should remained plugged in to AC power when not in use. NEVER LET DISCHARGED UNIT SIT FOR MORE THAN 24 HOURS WITHOUT FULLY RECHARGING POWER CELLS.
5. PROTECT DC POWER CABLE AND AC POWER CORD FROM DAMAGE - Prevent from being cut, gouged, crushed, dragged or otherwise abused.
). To maximize life of power cells and
CHECK
6-1
SECTION II.
MAINTENANCE
6-3. MAINTENANCE OF UNIT - The Turbo Start 2000 is a maintenance-
free unit, no repairs are authorized. Warranty will be void if unit is tampered with. If unit fails to operate contact Manufactures War­ranty Claim (see unit warranty).
WARRENTY VOID STICKERS
Chapter 7
Push To Test Modification
General Information And Operation
7-1. General
THIS MODIFICATION HAS BECOME STANDARD EQUIPMENT FOR EACH OF OUR UNITS. BOTH MILITARY AND CIVILIAN CLIENTS HAVE FOUND THIS MODIFICA­TION TO BE CRITICAL TO THEIR OPERATION. THE PUSH TO TEST BUTTON IS USED TO INDICATE THE CAPACITY OF THE POWER CELLS WITHOUT APPLYING AC INPUT POWER. IT ALLOWS THE END USER TO CHECK THE STATUS OF THE POWER CELLS. THIS LETS THE OPERATOR KNOW IF THERE IS ENOUGH POWER TO PER­FORM ANOTHER ENGINE START, OR IF THE UNIT HAS TO BE RETURNED TO AC POWER TO ALLOW IT TO RECHARGE.
7-2. OPERATION
1) MAKE SURE THAT YOU WAIT AT LEAST 2 MINUTES AFTER AC POWER IS APPLIED, OR DC POWER IS EXTRACTED FROM THE UNIT, BEFORE YOU DEPRESS THE PUSH TO TEST BUTTON. THIS WILL ENSURE A CORRECT READING.
2) WITHOUT AC POWER INPUT OR DC POWER OUTPUT, SIMPLY DEPRESS THE PUSH TO TEST BUTTON ON THE FACE PLATE AND HOLD FOR APPROXIMATELY 15 SECONDS.
3) AT THIS TIME THE LED BAR GRAPH SHOULD LIGHT UP INDICATING THE STATUS OF THE POWER CELLS.
4) THE FAN SHOULD ALSO OPERATE AT THIS TIME. IF YOU DO NOT HEAR THE FAN RUNNING, STOP DEPRESSING THE BUTTON AND CHECK FOR ANY OBSTRUCTIONS TO THE FAN.
5) NEVER DEPRESS THE PUSH TO TEST BUTTON WHILE THE UNIT IS PLUGGED INTO AC POWER FOR RECHARGE, OR PLUGGED INTO AIRCRAFT FOR DC POWER OUTPUT.
6) NEVER DEPRESS THE PUSH TO TEST BUTTON FOR MORE THAN 30 SECONDS. THIS MAY CAUSE A TEMPERATURE SENSOR TO TEMPORARILY DISRUPT PUSH TO TEST FUNCTION. (IF THIS SENSOR IS TRIPPED, ALLOW TEN MINUTES FOR UNIT TO COOL BEFORE OPERATING PUSH TO TEST BUTTON.)
7-1
ST ATUS
R
Y
G
0
1/2
OK
PARAGRAPH INDEX
120-240 VAC Charger and AC to DC Converter Limits, 3-4 24 VDC Ground Power (NO 120 or 240 VAC Power Supply) Engine Starting
or DC system Power, 4-6 24 VDC Ground Power (With 120/240 VAC Power) System High Power Demand
(21-1500 Amps) or Engine Starting, 4-7
28.5 VDC Ground Power (with 120/240 VAC Power) System Low Power De­mand (20 Amps or less), 4-8
Abbreviations, 1-5 AC Power Cord Limits, 3-5 After Use, 6-2 Appendix A Line Cord Table Before Operation Check, 4-5 Continuous Output Rate, 28.5 VDC Constant Output, 3-8 Data Basis, 5-3 DC Functional Check, 4-12 Definitions of Abbreviations, 5-6 Dimensions, Figure 2-1 Discharge Load Curve, Figure 5-2 Description 1-3 Engine Starting Power, 3-9 Environmental, 3-11 Functional Check Procedures, 4-10 Forms and Records, 1-6 General, Chapter 1, 1-1 General, Chapter 2, 2-1 General, Chapter 3, 3-2 General, Chapter 4, 4-1 General, Chapter 5, 5-2 General, Chapter 6, 6-1
General Conditions, 5-5 General Details, Figure 2-2 General Specifications, 2-2
PARAGRAPH INDEX Index, 1-4 Maintenance of Unit, 6-3 Maximum Output Current, Figure 5-3 One (1) Hour Rate, 24 VDC Constant Output, 3-6 Operating Limits and Restrictions, 4-2 Operating Procedures, 4-4 Operating Position, 3-12 Performance, 4-3 Power Cell Recharge, 4-9 Power Cell Recharge Limits, 3-3 Purpose, Chapter 3, 3-1 Purpose, Chapter 5, 5-1 Rated Peak Output (Engine Starting), 3-7 Required Equipment for Functional Check, 4-11 Specific Conditions, 5-4 Temperature, 3-10 Temperature Conversion Chart, Figure 5-1 Unit Operation During Aircraft Fueling/Defueling, 3-13 Use of Word Shall, Should and May, 1-7 Warning, Caution and Notes Defined, 1-2
APPENDIX A
OPTIONAL LINE CORDS FOR WORLDWIDE OPERATIONS
COUNTRY VOLTS HZ TESLA PART #
Afganistan 220 50 TI25000-004 Old British Line Cord Set Algeria 220 50 TI25000-004 Old British Line Cord Set American Samoa 240 60 TI25000-011 Australian Line Cord Set Angola 220 50 TI25000-100 Europlug Line Cord Set Anguilla (U.K.) 240 50 TI25000-005 United Kingdom Line Cord Set Antigua 230 60 TI25000-005 United Kingdom Line Cord Set Argentina 220 50 TI25000-011 Australian Line Cord Set Aruba 115 60 TI25000-001 North American Line Cord Set Australia 240 50 TI25000-011 Australian Line Cord Set Austria 220 50 TI25000-003 Cont. European Line Cord Set Azores (Portugal) 220 50 TI25000-004 Old British Line Cord Set
Bahamas 120 60 TI25000-001 North American Line Cord Set Bahrain 220 50 TI25000-005 United Kingdom Line Cord Set Bangladesh 220 50 TI25000-004 Old British Line Cord Set Barbados 115 50 TI25000-001 North American Line Cord Set Belguim 220 50 TI25000-003 Cont. European Line Cord Set Belize (Br. Hond.) 110 60 TI25000-001 North American Line Cord Set Benon 220 50 TI25000-004 Old British Line Cord Set Bermuda 120 60 TI25000-005 United Kingdom Line Cord Set Bolivia 220 50 TI25000-003 Cont. European Line Cord Set Botswana 220 50 TI25000-005 United Kingdom Line Cord Set Brazil 110 60 TI25000-001 North American Line Cord Set Bulgaria 220 50 TI25000-003 Cont. European Line Cord Set Burkina Faso 220 50 TI25000-100 Europlug Line Cord Set Burma (Now Myanmar) 230 50 TI25000-005 United Kingdom Line Cord Set Burundi 220 50 TI25000-003 Cont. European Line Cord Set
Cambodia 220 50 TI25000-100 Europlug Line Cord Set Cameroon 230 50 TI25000-003 Cont. European Line Cord Set Canada 120 60 TI25000-001 North American Line Cord Set Canary Islands (Spain) 220 b TI25000-003 Cont. European Line Cord Set Cape Verde, Rep. of 220 50 TI25000-003 Cont. European Line Cord Set Cayman Islands 120 60 TI25000-001 North American Line Cord Set Central African Republic 220 50 TI25000-100 Europlug Line Cord Set Chad 220 50 TI25000-003 Cont. European Line Cord Set Channel Islands 240 50 TI25000-005 United Kingdom Line Cord Set Chile 220 50 TI25000-002 Italian Line Cord Set China, Peoples Republic of 220 50 TI25000-011 Australian Line Cord Set Christmas Island (Australia) 240 50 TI25000-011 Australian Line Cord Set Cocos Islands (Australia) 240 50 TI25000-011 Australian Line Cord Set Columbia 220 60 TI25000-100 Europlug Line Cord Set Congo, Republic of 220 50 TI25000-100 Europlug Line Cord Set Cook Island (New Zealand) 240 50 TI25000-011 Australian Line Cord Set Costa Rica 12 0 60 TI25000-001 North American Line Cord Set Curacao Islands 110 60 TI25000-001 North American Line Cord Set Cyprus 240 50 TI25000-005 United Kingdom Line Cord Set Czech, Republic of 220 50 TI25000-003 Cont. European Line Cord Set
Denmark 220 50 TI25000-300 Denmark Line Cord Set Djibouti, Republic of 22 0 50 TI25000-003 Cont. European Line Cord Set Dominica 230 50 TI25000-005 United Kingdom Line Cord Set Dominican Republic 110 60 TI25000-001 North American Line Cord Set
A-1
APPENDIX A (Cont.)
OPTIONAL LINE CORDS FOR WORLDWIDE OPERATIONS
COUNTRY VOLTS HZ TESLA PART #
Ecuador 120 60 TI25000-001 North American Line Cord Set Egypt 220 50 TI25000-100 Europlug Line Cord Set El Salvador 115 60 TI25000-001 North American Line Cord Set England 240 50 TI25000-005 United Kingdom Line Cord Set Equatorial Guinea 220 50 TI25000-100 Europlug Line Cord Set Estonia 220 50 TI25000-003 Cont. European Line Cord Set Ethiopia 220 50 TI25000-003 Cont. European Line Cord Set
Fiji 240 50 TI25000-011 Australian Line Cord Set Finland 220 50 TI25000-003 Cont. European Line Cord Set France 220 50 TI25000-003 Cont. European Line Cord Set French Guiana 220 50 TI25000-003 Cont. European Line Cord Set
Gabon 220 50 TI25000-003 Cont. European Line Cord Set Gambia 220 50 TI25000-005 United Kingdom Line Cord Set Georgia 220 50 TI25000-003 Cont. European Line Cord Set Germany 220 50 TI25000-003 Cont. European Line Cord Set Ghana 220 50 TI25000-005 United Kingdom Line Cord Set Gibraltar 240 50 TI25000-005 United Kingdom Line Cord Set Greece 220 50 TI25000-003 Cont. European Line Cord Set Greenland (Denmark) 220 50 TI25000-300 Denmark Line Cord Set Grenada 230 50 TI25000-005 United Kingdom Line Cord Set Guadeloupe 220 50 TI25000-003 Cont. European Line Cord Set Guam 110-120 6 0 TI25000-001 North American Line Cord Set Guatemala 120 60 TI25000-001 North American Line Cord Set Guinea 220 50 TI25000-003 Cont. European Line Cord Set Guinea-Bissau 220 50 TI25000-003 Cont. European Line Cord Set Guyana 110 50/60 TI25000-001 North American Line Cord Set
Haiti 110-120 50-60 TI25000-001 North American Line Cord Set Honduras 110 60 TI25000-001 North American Line Cord Set Hong Kong 22 0 50 TI25000-005 United Kingdom Line Cord Set Hungary 220 50 TI25000-003 Cont. European Line Cord Set
Iceland 220 50 TI25000-003 Cont. European Line Cord Set India 220-250 50 TI25000-004 Old British Line Cord Set Indonesia 220 50 TI25000-003 Cont. European Line Cord Set Iran 220 50 TI25000-003 Cont. European Line Cord Set Iraq 220 50 TI25000-005 United Kingdom Line Cord Set Ireland, Republic of 220 5 0 TI25000-005 United Kingdom Line Cord Set Isle of Man 240 5 0 TI25000-005 United Kingdom Line Cord Set Israel 230 50 TI25000-200 Israel Line Cord Set Italy 220 50 TI25000-002 Italy Line Cord Set Ivory Coast 220 5 0 TI25000-100 Europlug Line Cord Set
Jamaica 110 50 TI25000-001 North American Line Cord Set Japan 110 50/60 TI25000-001 North American Line Cord Set Jordan 220 50 TI25000-005 United Kingdom Line Cord Set
Kenya 240 50 TI25000-005 United Kingdom Line Cord Set Korea, South 220 60 TI25000-003 Cont. European Line Cord Set Kuwait 240 50 TI25000-005 United Kingdom Line Cord Set
A-2
APPENDIX A (Cont.)
OPTIONAL LINE CORDS FOR WORLDWIDE OPERATIONS
COUNTRY VOLTS HZ TESLA PART #
Laos 220 50 TI25000-001 North American Line Cord Set Latvia 220 50 TI25000-003 Cont. European Line Cord Set Lebanon 220 50 TI25000-100 Europlug Line Cord Set Lesotho 240 50 TI25000-004 Old British Line Cord Set Liberia 120 60 TI25000-005 United Kingdom Line Cord Set Liechtenstein 220 50 TI25000-006 Switzerland Line Cord Set Lithuania 220 50 TI25000-003 Cont. European Line Cord Set Luxembourg 220 50 TI25000-003 Cont. European Line Cord Set Libya 230 50 TI25000-002 Italy Line Cord Set
Macao 220 50 TI25000-004 Old British Line Cord Set Madagascar 220 50 TI25000-003 Cont. European Line Cord Set Maderia (Portugal) 220 50 TI25000-004 Old British Line Cord Set Majorca 220 50 TI25000-003 Cont. European Line Cord Set Malawi 230 50 TI25000-005 United Kingdom Line Cord Set Malaysia 240 50 TI25000-005 United Kingdom Line Cord Set Maldives 230 50 TI25000-004 Old British Line Cord Set Mali, Republic of 22 0 50 TI25000-003 Cont. European Line Cord Set Malta 240 50 TI25000-005 United Kingdom Line Cord Set Martinique 220 50 TI25000-003 Cont. European Line Cord Set Mauritania 220 50 TI25000-100 Europlug Line Cord Set Mauritius 230 50 TI25000-005 United Kingdom Line Cord Set Mexico 127 60 TI25000-001 North American Line Cord Set Monaco 220 50 TI25000-003 Cont. European Line Cord Set Mongolia 220 50 TI25000-100 Europlug Line Cord Set Montseurrat 230 60 TI25000-005 United Kingdom Line Cord Set Morocco 220 50 TI25000-003 Cont. European Line Cord Set Mozambique 220 50 TI25000-003 Cont. European Line Cord Set
Namibia (W.S. Africa) 220-250 50 TI25000-004 Old British Line Cord Set Nepal 220 50 TI25000-004 Old British Line Cord Set Neth. Antilles 220 50/60 TI25000-003 Cont. European Line Cord Set Netherlands 220 50 TI25000-003 Cont. European Line Cord Set New Caledonia 220 50 TI25000-003 Cont. European Line Cord Set New Zealand 230 50 TI25000-011 Australian Line Cord Set Nicaragua 120 60 TI25000-001 North American Line Cord Set Niger 220 50 TI25000-100 Europlug Line Cord Set Nigeria 230 50 TI25000-005 United Kingdom Line Cord Set Norfolk Islands (Australia) 240 50 TI25000-011 Australian Line Cord Set North Ireland 220 50 TI25000-005 United Kingdom Line Cord Set North Mariana Islands (U.S.) 1 15 60 TI25000-001 North American Line Cord Set Norway 220 50 TI25000-003 Cont. European Line Cord Set
Okinawa 100-120 60 TI25000-001 North American Line Cord Set Oman 240 50 TI25000-005 United Kingdom Line Cord Set
Pakistan 230 50 TI25000-004 Old British Line Cord Set Panama 110 60 TI25000-001 North American Line Cord Set Papua New Guinea 240 50 TI25000-011 Australian Line Cord Set Paraguay 220 50 TI25000-100 Europlug Line Cord Set Peru 110 50/60 TI25000-001 North American Line Cord Set Philippines 115 60 TI25000-001 North American Line Cord Set] Piccairn Islands (U.K.) 240 50 TI25000-004 Old British Line Cord Set Poland 220 50 TI25000-003 Cont. European Line Cord Set Portugal 220 50 TI25000-003 Cont. European Line Cord Set Puerto Rico 120 60 TI25000-001 North American Line Cord Set
Qatar 240 50 TI25000-005 United Kingdom Line Cord Set
A-3
APPENDIX A (Cont.)
OPTIONAL LINE CORDS FOR WORLDWIDE OPERATIONS
COUNTRY VOLTS HZ TESLA PART #
Romania 220 50 TI25000-003 Cont. European Line Cord Set Russia 220 50 TI25000-003 Cont. European Line Cord Set Rwanda 220 50 TI25000-100 Europlug Line Cord Set
Saudia Arabia 220 50/60 TI25000-003 Cont. European Line Cord Set Scotland 220 50 TI25000-005 United Kingdom Line Cord Set Senegal 220 50 TI25000-003 Cont. European Line Cord Set Seychelles 240 50 TI25000-005 United Kingdom Line Cord Set Sierra Leone 230 50 TI25000-005 United Kingdom Line Cord Set Singapore 230 50 TI25000-005 United Kingdom Line Cord Set Slovakia 220 50 TI25000-003 Cont. European Line Cord Set Somalia 220 50 TI25000-003 Cont. European Line Cord Set South Africa 220-250 50 TI25000-004 Old British Line Cord Set Spain 220 50 TI25000-003 Cont. European Line Cord Set Sri Lanka 23 0 50 TI25000-004 Old British Line Cord Set St. Pierre & Miquelon (France) 115 6 0 TI25000-001 North American Line Cord Set St. Kitts & Nevis 230 60 TI25000-005 United Kingdom Line Cord Set St. Lucia 24 0 50 TI25000-005 United Kingdom Line Cord Set St. Vincent 230 50 TI25000-005 United Kingdom Line Cord Set Sudan 240 50 TI25000-005 United Kingdom Line Cord Set Surinam 115 60 TI25000-003 Cont. European Line Cord Set Svalbard (Norway) 220 50 TI25000-003 Cont. European Line Cord Set Swaziland 230 50 TI25000-004 Old British Line Cord Set Sweden 220 50 TI25000-003 Cont. European Line Cord Set Switzerland 220 50 TI25000-006 Switzerland Line Cord Set Syria 220 50 TI25000-100 Europlug Line Cord Set
Tahiti 220 50 TI25000-003 Cont. European Line Cord Set Taiwan 110 60 TI25000-001 North American Line Cord Set Tanzania 230 50 TI25000-005 United Kingdom Line Cord Set Thailand 220 50 TI25000-100 Europlug Line Cord Set Togo 220 50 TI25000-003 Cont. European Line Cord Set Tonga 115 60 TI25000-004 Old British Line Cord Set Trinadad & Tobango 230 6 0 TI25000-005 United Kingdom Line Cord Set Tunisia 220 50 TI25000-100 Europlug Line Cord Set Turkey 220 50 TI25000-003 Cont. European Line Cord Set
Uganda 220 50 TI25000-004 Old British Line Cord Set United Arab Emir. 22 0 50 TI25000-005 United Kingdom Line Cord Set United Kingdom & Ireland 240 5 0 TI25000-005 United Kingdom Line Cord Set United States 120 60 TI25000-001 North American Line Cord Set Uraguay 220 50 TI25000-011 Australian Line Cord Set
Venezuela 120 60 TI25000-001 North American Line Cord Set Vietnam 220 50 TI25000-003 Cont. European Line Cord Set Virgin Islands 120 60 TI25000-001 North American Line Cord Set
Wales 220 50 TI25000-005 United Kingdom Line Cord Set Western Samoa 230 50 TI25000-005 United Kingdom Line Cord Set
Yemen 220 50 TI25000-005 United Kingdom Line Cord Set Yugoslavia 220 50 TI25000-003 Cont. European Line Cord Set
Zaire, Republic of 220 5 0 TI25000-003 Cont. European Line Cord Set Zambia 220 50 TI25000-005 United Kingdom Line Cord Set Zimbabwe 220 50 TI25000-005 United Kingdom Line Cord Set
A-4
APPENDIX A (Cont.)
UNIVERSAL LINE CORD KIT FOR WORLDWIDE OPERATIONS
NOTE: TESLA UNIVERSAL AC LINE CORD KIT, P/N: TI25000-U00, IS FOR UNITS ORIGINALLY BUILT WITH THE UNIVERSAL AC LINE CORD OPTION ONLY. THE AC ADAPTER OPTION IS TESLA P/N TI16000-19 AND MUST BE ORDERED WITH THE ORIGINAL PROCUREMENT OF UNIT(S). UNIT(S) MAY BE RETURNED TO TESLA INDUSTRIES, FOR A NOMINAL COST, AND MODIFIED TO ALLOW OPERATION WITH THE UNIVERSAL AC LINE CORD KIT.
TESLA UNIVERSAL AC LINE CORD KIT, P/N: TI25000-U00, IS COMPRISED OF THE FOLLOWING FOUR PART NUMBERS:
TI25000-U01 NORTH AMERICAN LINE CORD TI25000-U04 OLD BRITISH LINE CORD TI25000-U03 EUROPEAN 10A/250V TI25000-U05 ENGLAND 10A/250V
TESLA REPLACEMENT 8 FOOT DC POWER CORD, P/N: TI2006-501, IS AVAILABLE UPON REQUEST. (CUSTOM LENGTHS ARE ALSO AVAILABLE TO SUIT THE CUSTOM­ERS OPERATIONAL REQUIREMENTS.)
A-5
Loading...