Teseq CDN 3083-S200M User Manual

1
MANUAL HIGH-CURRENT COUPLING/DECOUPLING NETWORK CDN 3083-S200M
USER MANUAL 691-379C
MANUAL HIGH-CURRENT COUPLING/DECOUPLING NETWORK CDN 3083-S200M
USER MANUAL
1 Explanation of the symbols used in this manual 5
2. Safety advice 7
2.1 Safety measures 8
2.2 Installation 8
2.3 Installation of an equipment under test power switch 10
2.3.1 Applicable safety standards 10
2.3.2 Leakage current 11
3. Applications 12 4 Assembling of test rig and the CDN sub-units 15
4.1 Installation of a test rig 16
4.2 Preparation of the CDN 3083-S200M 17
4.2.1 Mounting of the common earth bars 17
4.2.2 Mounting positioning plates 18
4.2.3 Assembly for IEC coupling 20
4.2.4 Assembly for extended IEC coupling 21
4.3 EUT connections 22
4.3.1 EUT power feed 22
4.4 Test conditions 23
5 Coupling modes overview 24
5.1 Phase synchronisation 24
5.2 IEC coupling modes 25
5.3 Extended IEC coupling mode 28 CDN 3083 IEC Coupling Line to Ground 29 CDN 3083 IEC Coupling Line to Line 30 CDN 3083 ANSI Coupling 31
6 Effects on the EUT 32 7 Maintenance 33
8 Technical specications CDN 3083-S200M 34
9 Warranty 37
10 Addresses 39
CONTENTS
5
Please take note of the following explanations of the symbols used in order
to achieve the optimum benet from this manual and to ensure safety during
operation of the equipment.
The following symbol draws your attention to a circumstance where non­observation of the warning could lead to inconvenience or impairment in the performance.
Example:
1 EXPLANATION OF THE SYMBOLS
USED IN THIS MANUAL
This connection must not be confused with the EUT
power input.
The following symbol draws your attention to a circumstance where non­observation of the warning could lead to component damage or danger to the operating personnel.
Example:
Never connect or disconnect the EUT while the test
system is performing a test.
Never connect or disconnect the coupling path while the
test system is performing a test.
6
2 SAFETY ADVICE
Improper or careless handling can be fatal! The instru-
ment must only be used by trained personnel.
These operating instructions form an integral part of the equipment and must be studied carefully before putting the device into use. It needs to be available to the operating personnel at all times. All the safety instructions and advice notes are to be observed.
Keeping responsibility to the instructions and recommendations that follow is imperative.
The safety advice referring to the generators also applies and must be followed when using the instruments together with the CDN 3083-S200M.
Neither Teseq AG, Switzerland nor any of the associated sales organizations accept any responsibility for personal injury or for material or consequential damage that may results through irresponsible or negligent operation of this equipment.
When used with generator NSG 3060 and for EUT voltage
> 440 Vrms do not set pulse repetition rate <20 seconds. The NSG 3060 may be damaged if this is not respected.
7
Lethal danger from high voltages and the risk of radiating
illegal electromagnetic interference.
The CDN 3083-S200M may only be installed and used by
authorised and trained EMC specialists (electrical engi­neers).
The CDN 3083-S200M must only be used for EMC tests
as set down in these operating instructions.
Personnel tted with a heart pacemaker must not
operate the instrument and must not be in the vicinity of the test rig while it is in operation.
Lethal danger from high voltages and the risk of high
levels of electromagnetic radiation being generated.
When the system is used in conjunction with options,
accessories or other equipment the safety instructions concerning those devices must also be observed.
8
2.1. Safety measures
Persons tted with a heart pacemaker must not operate the instrument and
should not be in the vicinity of the test rig when pulses are generated.
The test rig must provide adequate insulation protection for up to 5 kV surge. Particular care should be given to the connections between the CDN 3083­S200M and the equipment under test (EUT).
The EUT may only be tested when placed inside a suitable protective enclosure
which should provide protection against ying fragments, re and electric shock.
The pulse voltage must not be able to nd its way to unearthed metal objects
in the event of the EUT failing.
Only use the instrument in a dry room.
Never leave the instrument unattended when the EUT is switched on.
Regularly check the heat of the CDN using the built in thermometer and switch EUT off if the temperature exceeds 70°C.
Do not open the instrument. Repairs and adjustments must only be carried out
by qualied maintenance personnel.
Do not continue to use the CDN in case of any mechanical damage occur. The CDNs housing and the cables have both insulating and screening function, which can only be assured while the housing is intact. Return the damaged CDN to a Teseq service centre immediately for repair.
2.2 Installation
The test system conforms to protection class 1. Local installation regulations
must be respected to ensure the safe ow of leakage currents.
9 Operation without a protective earth connection is for-
bidden! Therefore it is imperative to screw both earth copper rails to the CDN.
Switch off EUT power before accessing EUT power «in»
or «out» terminals. Use the insulated allen key always when working on the terminals.
Two independent protective earth connections are necessary (for the test system and the EUT). These must be connected back to the local permanent
installation or to a xed, permanent protective earth conductor.
Operate the equipment only in dry surroundings. Any condensation that occurs must be allowed to evaporate before putting the equipment into operation. Do not exceed the permissible ambient temperature or humidity levels. Use only
ofcially approved connectors and accessory items.
It is recommended to connect the CDN 3083-S200M
through a properly rated power switch device, which should be located close to the test setup. In order to ensure an easy and quick acces to the EUT power, same should be clearly and visibly labelled as a device for «EUT power on/off» switching.
The inhouse power distribution needs to be equipped
with a proper circuit breaker and an emergency off
button as per IEC/EN 61010-1.
10
2.3 Installation of an equipment under test power switch
It is recommended to connect the CDN through a properly rated power switch device, which should be located close to the test setup. In order to ensure an easy and quick access to the equipment under test (EUT) power, same should be clearly and visibly labelled as a device for «EUT power on/off» switching.
The in-house power distribution needs to be equipped with a proper circuit breaker and an emergency off button as per IEC/EN 61010-1.
The test setup should only be accessible to trained
personal.
Dimensioning of mains supply and rating of fuse protection of AC or DC power supply must conform with national prescriptions and EUT requirements.
Inappropriate arrangement, mounting, cabling or handling of the device under test or the protective elements can make the protective features that are incor­porated in the concept of the instrument worthless.
2.3.1 Applicable safety standards
Development and manufacture is in compliance with ISO 9001.
The instrument complies with the safety requirements of IEC/EN 61010-1 (safety requirements of electrical equipment for measurement, control and laboratory use).
The interference immunity has been tested in accordance with EN 61326-1.
It is the user’s responsibility to ensure that the test rig does not emit exces­sive electromagnetic interference (EMI) that might affect other items. The test system itself does not produce any excessive radiation; however, the injection of interference pulses into the EUT can result in the device and/or its associated cables starting to radiate EMI. To avoid radiating unwanted interference into the environment, the standards organisations recommend that the test rig be operated in a Faraday cage.
112.3.2 Leakage current
CDN 3083-S200M generates high leakage currents to ground, by specication.
Therefore the EUT power supply connection needs to be free of differential circuit breaker protection.
Local installation regulations must be respected to ensure the safe ow of
leakage currents.
Always rst connect the PE wire to CDN 3083-S200M.
Use only nationally approved connectors and accessory items.
Ensure that a reliable return path for the interference current is provided between the EUT and the coupling/decoupling network.
12
3 APPLICATIONS
The manual coupling network CDN 3083-S200M fullls the requirements called
for in the surge standard IEC/EN 61000-4-5, including the new features concern­ing high currents.
The form factor perfectly suits the demands placed on the instrument in its
working environment. In its basic form, the coupler is made for use on a oor
or for table top placement in an EMC laboratory or in a development workshop. It can be even mounted onto the wall to have free space on the test bench.
High-current couplers may need to be taken to test sites where it is commonly impossible to move large installations in. For convenience, the CDN 3083-S200M can be disassembled in handy parts and can be easily moved to other places.
Injecting surge pulses into power connections always involves a careful weigh-
ing up of partially conicting requirements. On the one hand the power network
has to be protected from the interference signals while the effects of the pulses are concentrated on the equipment under test, yet on the other hand the back
lter must not result in any signicant voltage drop.
In order to keep voltage losses within reasonable limits at increasing current
levels, there are ve different classes of lter inductances dened in IEC 61000-
4-5 Ed. 3, up to 16 A, 16 to 32 A, 32 to 63 A, 63 to 125 A and 125 to 200 A including
specic tolerances for the pulse duration and the peak voltages for each class.
The CDN 3083-S200M conforms to the tolerances of the 125 to 200 A class.
The back lter inductance has been selected to be 0.2 mH.
13
The nominal maximum current rating of 200 A per phase can, during short test periods, be considerably exceeded. The unit will tolerate the frequently encountered inrush currents without complaint and, in extreme cases it can be overstressed until the internal environment has reached the max. temperature of 70°C.
CDN 3083-S200M is delivered with external fans mounted. Supply cables for the fans are part of the delivery. It is recommended to turn on the fans when the CDN 3083-S200M is used in the upper load range (Example: EUT current >100 A), or when environmental temperature is high (>30° C).
Figure 1
14
The coupling network CDN 3083-S200M serves to inject the following standard­ized surge pulses from the surge generator into the mains supply to the device under test:
Voltage surge of up to 6 kV which follows the 1.2/50 µs curve (open-circuit)
Current surge of up to 3 kA which follows the 8/20 µs curve (short circuit
conditions)
The CDN 3083-S200M is designed to be used with an EUT supply of up to 620 Vrms line to line and 400 Vrms line to ground at 200 A.
Coupling surge pulses with higher voltages (up to 8 kV) is in principle possible, but in case the EUT draws low currents the backlter chokes may go in satura­tion due to the higher surge kickback currents and provide no more a good
backltering performance.
Operation is manual, simple and designed to be safe.
The CDN 3083-S200M is tested for safety in compliance with IEC 61010. The rugged connection terminals together with the solid earth line assure a proper connection, this in combination with a rugged housing.
Figure 2: EUT power supply connector
15
4 ASSEMBLING OF TEST RIG AND THE CDN SUB-UNITS
The CDN 3083-S200M contains following parts:
1 Surge decoupling network CDN 3083-S200 N – L1 1 Surge decoupling network CDN 3083-S200 L2 – L3 2 Earth rails 1 Allen key, isolated 1 User manual CDN 3083-S200M
2 Coupling conguration sheets 1 Traceable calibration certicate
Screw set 8 wheels with brakes
Accessories: IEC coupling set
1 INA 3080 Surge coupling unit
Extended IEC coupling set
2 INA 3080 Surge coupling unit 1 Connection cable 0.5 m Fischer/Fischer connector
16
4.1 Installation of a test rig
This section describes the check-up and installation of the CDN 3083-S200M coupling network after delivery and provides a checklist on the functions of
the unit after being transported or after signicant changes of the test rig were
performed.
Installation should only be carried out by qualied personnel.
a) Check the delivery for completeness. b) Check the unit for any signs of transportation damage. Report any damage
found to the carrier immediately. c) Study the manual. d) Set up the surge generator in accordance with the instructions in its manual
but do not, however, switch the instrument on. e) For convenience, place the coupling network close to the generator. f) Connect the protective earth to the terminal. The same protective earth
should also be connected to the earth terminal of the generator. g) Plug the high voltage connectors into the surge generator. h) Connect the INA 3084 synchronisation unit to the generator. i) Connect the EUT supply. j) Switch on the mains power at the generator. k) Choose the appropriate coupling mode. l) Connect the device to be tested according to the relevant safety specica-
tions and with due regard to the magnitude of the pulse voltage selected.
Take the necessary measures to cope with any possible explosion or out-
break of re.
m) Switch on the EUT power supply. n) Operate the generator as instructed in its manual and carry out the required
tests.
It is assumed that the test rig has been set up in accordance with the foregoing notes and that the device to be tested has been connected taking the relevant safety measures into account.
174.2 Preparation of the CDN 3083-S200M
Prepare the test setup according to the chosen standard and put both decou­pling network units, etc. to the place where the CDN shall be used for testing.
4.2.1 Mounting of the common earth rails
Place the two surge decoupling networks in parallel to each other. Looking from the top, make sure that the N-L1 network is below the L2-L3 network.
To enable proper synchronisation, assure that side L1
being placed next to L2!
Use the delivered isolated allen key to screw the copper earth rails on to both ends of the decoupling networks (2 x 2 screws each side per network).
Make sure that the copper rail is properly mounted and
tightened. Use only the delivered screws.
18
Figure 3: Top view on CDN units
Figure 4: Assembly of copper earth rail
After this preparation work, the CDN is stable enough for being turned to its side prior to mounting the wheels at the bottom of the case, if required.
2x
M8 x 16 mm
2x
M8 x 16 mm
2x
M8 x 16 mm
2x
M8 x 16 mm
4.2.2 Mounting positioning plates
Screw the base plates (positioning plates) of the synch unit and of the cou­pling unit, with the knurled screws to the foreseen holes on the outside of the decoupling networks. Connect the synch lines (safety banana connector) to the decoupling units. If CDN 3083-S200M decoupling networks are not placed correctly, the positioning plates can not be screwed on.
19
Figure 5: Location of synchronisation unit and of positioning plate
Figure 6: Synchronisation plate (l.h.) and positioning plate (r.h.)
20
4.2.3 Assembly for IEC coupling
For IEC coupling, add the coupling modules INA 3080 in the middle of the positioning plate and press it slightly down into the positioning holes. Fix the INA by pushing the black quick snap-on knobs down. The CDN 3083-S200M is now ready to use.
Figure 7: Location of IEC coupling module
Figure 8: View of IEC coupling module
214.2.4 Assembly for extended IEC coupling
For extended IEC coupling, add both coupling units INA 3080 on the position­ing plate and press it slightly down into the positioning holes. Fix the INAs by pushing the black quick snap-on knobs down. The CDN 3083-S200M is now ready to use.
Figure 9: Location of extended IEC coupling modules
Figure 10: View of extended IEC coupling modules
Because of the coupling capacitors, the mains voltage
can be present at the HV connectors when the EUT power supply is switched on. The HV connectors must therefore
always be hooked up to the generator before the mains and the EUT power supply are switched on.
22
4.3 EUT connections
The CDN 3083-S200M is equipped with EUT terminals suitable for a max. wire gauge of 110 mm2 AWG 4-4/0 (230 A), torque: max. 20 Nm.
The in-house power distribution needs to be equipped
with a proper circuit breaker and an emergency off
button as per IEC/EN 61010-1.
4.3.1 EUT power feed
The power is fed in via 5-core cable leads.
Do not mismatch the EUT power input of the CDN and the
EUT power output. Use only the delivered isolated allen key to screw the cables to the terminals. Never touch the terminals during the EUT power is on.
EUT power input EUT power output
Figure 11: Identification of EUT power input and output
23
Figure 12: View of EUT power input connection side
4.4 Test conditions
Every test rig must be planned carefully. All the instrumentation should be readily accessible and rigidly positioned.
The whole test assembly should be supplied from the
same mains connection in order to prevent uncontrolled ow of pu ls e curr ent in ot he r pa r t s of th e sy st em . Ins ta ll a ­tion in a Faraday cage ensures that non-associated items and equipment are not disrupted by pulses radiated from the cabling or the device under test. Connections to the EUT must be of low impedance and be made with high contact pressure. Otherwise welding or arcing may occur at the contact points.
24
In the following all possible coupling modes are described.
The following example shows a coupling from L3 to N whereby the generator High output is connected to the INA 3080 surge coupling unit input. One end is
looped, in order to get the recommended 18 μF capacitance required for line to
line coupling according to IEC/EN 61000-4-5. The other pulsed end is connected to L3. The generator low output is directly connected to the N line.
5.1 Phase synchronisation
In the INA 3084 synchronisation unit the input voltage L1 to N is wired out for Sync reference. The approximately 2 meter long cable of INA 3084 needs to be connected to the EUT mains input plug located on the rear side of the NSG 3040.
The phase angle indicated on the display of NSG 3060 is always in relation with the L1-N reference. For coupling settings different from L1 to N coupling, it is up to the user to make the phase angle correction, and enter the required phase angle + phase shifting value.
The value of the phase angle shifting in relation with the selected coupling path
and is installation and wiring dependent. At rst use of the test system it is recommended to make the phase angle setting verication using MD 200 Probe
and to edit a phase angle correction table to be used during further operation.
For synchronisation purpose the cable end of the INA 3084 synchronisation unit needs to go to the EUT power input connection of the generator.
5 COUPLING MODES OVERVIEW
Never run the CDN with a loose end of the coupling unit.
All connectors need to be plugged.
25
Figure 13: Example of IEC coupling L3- N
Alternative connection possibilities are summarized in table 1 hereafter.
5.2 IEC coupling modes
Figure 14: IEC coupling basic configuration
All IEC/EN 61000-4-5 coupling possibilities are listed. For easy understanding, the coupling network INA 3080 input is identied by X1 while the outputs are marked with X2 and X3. Depending on coupling mode selected following con­nections are to be established for:
26
Table 1: Selection of IEC coupling modes
IEC line to line
Generator output
Loop on INA 3080
Decoupling network CDN 3083-S200
High Low L1 L2 L3
L1 – N X1 N X2 to X3 X3
L1 – L2 X1 L2 X2 to X3 X3
L1 – L3 X1 L3 X2 to X3 X3
L2 – N X1 N X3 to X2 X2
L2 – L1 X1 L1 X3 to X2 X2
L2 – L3 X1 L3 X3 to X2 X2
L3 – N X1 N X3 to X2 X2
L3 – L1 X1 L1 X3 to X2 X2
L3 – L2 X1 L2 X3 to X2 X2
Generator output
Loop on INA 3080
Decoupling network CDN 3083-S200
High Low N L1 L2 L3
N – PE X1 PE X2 to X2 X3
L1 – PE X1 PE X2 to X2 X3
L2 – PE X1 PE X3 to X3 X2
L3 – PE X1 PE X3 to X3 X2
IEC line to ground
27
Figure 15: IEC coupling L1-N
Figure 16: IEC coupling L2-N
Figure 17: IEC coupling L2-PE
28
5.3 Extended IEC coupling mode
For extended coupling modes, a second INA 3080 needs to be added on the CDN 3083-S200M.
Figure 18: IEC coupling L1-PE
Figure 19: Extended IEC coupling basic configuration
INA 3084 / 3085
Synchronisation Unit
29
Table 2: Selection of extended IEC coupling modes
Generator output
Loop on INA 3080
Connection from X1 to Y1
Decoupling network CDN 3083-S200M
High
Low N L1 L2 L3
X1 PE –– Yes Y3 Y2 X3 X2
X1 L1 X2 to X3 No X3
X1 L2 X2 to X3 No X2
X1 L3 Y3 to Y2 No Y2
X1 PE Y2 to Y3 No Y3
X1 PE Y3 to Y2 No Y2
X1 PE X2 to X3 No X3
X1 PE X3 to X2 No X2
X1 N Y3 to Y3 Yes Y2 X3 X2
X1 PE Y3 to Y3 Yes Y2 X3 X2
CDN 3083 IEC Coupling Line to Ground
30
CDN 3083 IEC Coupling Line to Line
31CDN 3083 ANSI Coupling
32
6 EFFECTS ON THE EUT
The surge pulse contains considerable energy. When super-imposed on the
mains, a signicant resultant current can occur if the EUT becomes defective.
The effects can be very different, depending on the characteristics of the equip­ment undergoing the test:
No effect Brief faulty operation without permanent damage Reduction of the insulation resistance or similar Quality affected (life expectancy)
Change in the technical specication of the device under test
Flash-over in cables, connectors and equipment Bursting of components Explosion of components Burning of parts caused principally by resultant mains current when mains
superposition mode is used
Damage to equipment, systems or components that are electrically or induc-
tively coupled to the pulse current path
When testing with high energy surge pulses, a test on
a device should never be considered as being damage­free until a subsequent thorough investigation proves that the EUT is still fully intact.
33
Basically there is no need of maintenance and the CDN 3083-S200M does not contain serviceable parts. The housing may be cleaned with a moist cloth with possibly just a trace of detergent liquid. Industrial spirit is also a suitable cleaning agent. Other solvents are not permitted.
Only specialist or trained maintenance personnel may carry out internal work on the instrument. In the event of more service or repair work being necessary, the instrument should be returned to a Teseq service center accompanied by an appropriate description of the problem. The instrument contains no fuses.
7 MAINTENANCE
34
8 TECHNICAL SPECIFICATIONS
CDN 3083–S200M
The CDN 3083-S200M is a 3-phase manual coupling network for surge interfer­ence pulses as per IEC/EN 61000-4-5 and other related standards.
The CDN 3083-S200M base 1 x Surge decoupling network set consists of: CDN 3083-S200 – L1 1 x Surge decoupling network CDN 3083-S200 L2 – L3 2 x Earth rails 1 x Wheel set 1 x Allen key, isolated 1 x User manual CDN 3083-S200M
1 x Test certicate 2 x Coupling conguration sheets
Accessories required either: IEC coupling set 1 x INA 3080 Surge coupling unit or Extended IEC coupling set: 2 x INA 3080 Surge coupling unit 1 x Connection cable
Modula/NSG 3040/CDN 3061: 1 x INA 3084 synchronisation unit for NSG 3040 and Modula 2 x Cable 1 m, with each a Fischer/Fischer plug
Following complementary items are required for phase synchronisation:
35Pulse voltages/current: 6.6 kV/3.3 kA max.
EUT power supply voltage: 620 Vrms line-to-line 400 Vrms line-to-ground 500 VDC, max. Current: 200 Arms or DC max. per line Frequency: DC to 60 Hz Mains decoupling: 0.2 mH ± 10% EUT connection: Screw-terminals, 230 A, up to 110 mm
2
(AWG 4-4/0) Max. temperature: 70°C Coupling modes: Surge differential, lines to PE, common to PE (with optional INA 3080 coupling unit for extended IEC coupling) Dimensions: 850 x 520 x 345 (L x D x H) mm (33.5 x 20.5 x 13.6”) Weight: 80 kg approx. Optional accessories: MD 300 Current measuring probe MD 210 Voltage measuring probe
IEC coupling modes: Line to ground (9 μF) L1 — PE L2 — PE L3 — PE N — PE
Line to line (18 μF) L1 — N L1 — L2 L1 — L3 L2 — N L2 — L3 L3 — N
36
Optional IEC coupling modes (possible only with second INA 3080):
Lines to ground (9 μF) L1+L2 — PE L1+L3 — PE L1+N — PE L2+L3 — PE L2+N — PE L3+ N — PE L1+L2+L3 — PE L1+L2+N — PE L1+L3+N — PE L2+L3+N — PE L1+L2+L3+N — PE
37
9 WARRANTY
Teseq grants a guarantee of 2 years on this instrument, effective from the date of delivery.
During this period, any defective component/part will be repaired or replaced free of charge or, if necessary, the instrument will be replaced by another of equivalent value. The decision regarding the method of reinstating the func­tional capability is at the sole discretion of Teseq.
Excluded from the guarantee are damages or consequential damages caused through negligent operation or use as well as the replacement of parts subject to degradation.
The guarantee is rendered invalid by any intervention by the customer or a non-authorized third party.
The goods are to be returned in the original packing or other equivalent packing suitable for the purpose of the foreseen means of transport. Teseq shall accept no responsibility for damage in transit.
To nd your local partner within Teseq®’s global network, please go to www.teseq.com © December 2018 Teseq®
Specications subject to change without notice. Teseq® is an ISO-registered company. Its products are designed and manufactured under the strict quality and environmental requirements of the ISO 9001. This document has been carefully checked. However, Teseq® does not assume any liability for errors or inaccuracies.
AMETEK CTS
Manufacturer:
Switzerland
EM TEST (Switzerland) GmbH
Sternenhofstrasse 15 4153 Reinach, Schweiz info.conducted.cts@ametek.com
Switzerland
Teseq AG
Sternenhofstrasse 15 4153 Reinach, Schweiz info.conducted.cts@ametek.com
Germany
Teseq GmbH
Landsberger Strasse 255 12623 Berlin, Deutschland info.rf.cts@ametek.com
United Kingdom
Milmega Ltd.
Park Road Ryde, Isle of Wight PO33 2BE, Großbritanien Milmega.sales@ametek.co.uk
USA
IFI – Instruments For Industry
903 South Second Street Ronkonkoma New York 11779, USA sales@i.com
Sales & Service Center
China
AMETEK Commercial Enterprise
(Shanghai) Co. Ltd. Beijing Branch Western Section, 2nd Floor Jing Dong Fang Building (B10) Chaoyang District Beijing, China, 100015 T: +86 10 8526 2111 chinasales@teseq.com
Shanghai Ofce:
Part A1, A4, 2nd oor, Building No. 1 No. 526 Fute 3rd Road East Pilot Free Trade Zone, Shanghai 200131, China T: +86 21 5866 0969
Guangzhou Ofce:
Room 1410-12, Yian Plaza 33 Jian She Liu Ma Road Guangzhou, China T: +86 20 8363 4768
Germany
AMETEK CTS Germany GmbH
Lünener Straße 211 59174 Kamen, Deutschland T: +49 2307 26070-0 info.cts@ametek.de
France
AMETEK SAS
Rond Point de l´Epine des Champs Buroplus, Bat D 78990 Elancourt, France T: +33 (0) 1 30 68 89 0 0 info.france@ametek.com
United Kingdom
Teseq a trading divison of AMETEK (GB) Limited
5 Ashville Way, Molly Millars Lane Wokingham Berkshire RG412PL Great Britain T: +44 845 074 0660 sales.cts@ametek.co.uk
Japan
AMETEK Co. Ltd.
Tokyo of ce 3rd oor, Shiba NBF Tower, 1-1-30 Shiba-Daimon, Minato-ku Tokyo, 105-0012, Japan T: +81 3 6809 2401
Nagoya Ofce
1-329 Kifune Meito-ku Nagoya-shi Aichi-ken, 465- 0058, Japan T +81 52 709 5501 cts-japan.sales@ametek.co.jp
Poland
AMETEK CTS Germany GmbH
ul. Ogrodowa 31/35 00-893 Warszawa, Polen T: +48 518 643 512 infopolska.emtest@ametek.com
Singapore
AMETEK Singapore Pte. Ltd.
No. 43 Changi South Avenue 2 #04-01 Singapore 486164 T: +65 6484 2388 Singaporesales.cts@ametek.com
Taiwan
AMETEK Taiwan Corp. Ltd.
10F-5, No. 120, Sec 2, GongDaoWu Rd., Hsinchu City 30072, Taiwan T: +886 3 57 5099
USA
Teseq Inc. / AMETEK CTS
52 Mayeld Avenue Edison, New Jersey 08837, USA T +1 732 417 0501 For free: +1 888 417 0501 usasales.cts@ametek.com
Loading...