Terra S-TWIN, W-TWIN Technical Information And Assembly Instructions

Technical information
and assembly
instruction
Expenditure July 2008
TERRA-SW-TWIN_230V_installation_jul08-engl.cdr
Expenditure July 2008
TERRA-SW-TWIN_230V_installation_jul08-engl.cdr
heatpump
V
IN
TERRA S/W-TWIN 230V
for
brine- or groundwaterplants
Type Basic
Table of contents
Page
1. General Information
2. Heat pump
3. Heat source systems
4. Brine Horizontal Collector
5. Brine bore - hole system
6. Ground and Surface water systems
7. Advice for the Installation 20
8. Operation 21
9. Faults / Fault removal 22
1 2
2.1 Description 2
2.2 Rang of operation 2
2.3 Delivery content 2
2.4 Accessories 2
2.5 Technical Data- Brine heat pumps 3 Technical Data- Groundwater heat pumps 4
2.6 Operation limits 5
2.7 Technical dimensions 6
2.8 Installation 7
2.9 Hydraulic schematics 8
2.10 Connection ofthe heating side 12
2.11 Electrical scheme 12
2.12 Electrical connection 13
3.1 General information 15
4.1 Description 16
4.2 Rang ofApplication 16
4.3 Delivery Content 16
4.4 Technical Data 17
4.5 Installation schematic 17
5.1 Description
6.1 Description 19
6.2 Range ofApplication 19
6.3 Accessories 19
18
5.2 Rang ofApplication 18
5.3 Delivery Content 18
5.4 Technical Data 18
Changes in technology and Design reserve! IDM-Energiesysteme GmbH,A-9971 Matrei i.O.,
C
(
General information for operation of the heat pump.
Very important information for assem­bling and operation of the heat pump. These informations are to be kept abso­lutely.
General information for assembling the heat pump.
Place for the phone numberof your servi­ce partner.
1. general information
Page 1
With the acquisition of this plant you have decided yourself for a modern and economic heating system
Regular quality controls and improvements, as well as functional tests in the factory, guarantees a technically faultless device.
Read these documents attentively. You will contain important notes and for the sure and economical operation of the plant.
Installation and maintenance can involve dangers by high Plant pressures, high temperatures and volta­ge-carrying Parts andbeing and must be done by ex­perts.
Heat pumps may only be installed by competent ex­perts and put intooperation onlyby a company which is trained by IDM energy systems GmbH
For work on the heat pump all safety data in the cor­responding documents, the sticker at the heat pump itself and all the othersafety regulations haveto been observed.
By transport, never incline the thermal pump more then 15°.
The transportation packing should be removed just after the thermal pump is positioned at the place of in­stallation.
Terra heat pumps are very quiet in operation due to their construction.
Nevertheless it is important that the heating room should be positioned outside of sensitive to noise
living quarter and should be provided with a well clo­sing door closing.
The heat pump isn't setup for the increased need of heat for drying subfloor or carcass.
This must be done by equipment specially designed for this task.
Tip for security:
Transport:
Sound emission:
Drying of subfloor orcarcass:
Service and maintenance:
Aregular maintenance as well as a check and Care of all important plant parts guarantees at last a
safe and thrifty operation of the plant. We recommend acontract formaintenance.
Cleaning:
If required, the Terra heat pump can be cleaned with a damp cloth.The use of cleansers is not recommen­ded.
Correct EC guidelines
Correct harmonized EN
Correct national norms/guidelines
Important safety reference
EC machine guideline (89/392/EEC) EC low voltage guideline (73/23/EEC) EC-EMV guideline (89/366/EEC)
EN378 EN60529 EN292/T1/T2 EN294 EN349 EN60335 1/2-40 EN55014 EN55104
ÖNORM M7755 2 (Austria)
:
The heat pump is filled with refrigerant. This Cryogen is non-poisonous and not combustible.
In case of damage however, refrigerant is could flow out of the plant, and could cause superseding of
oxygen. Due to open fire, toxic disintegration products can ari-
se
By leaving refrigerant (smell)leave theinstallation si­te
immediately leaving and close the door. Contact the customer service. Works at and in the equipment are permitted only for
authorized experts
Reference to disturbances and error messages see Page 20.
2.1 Description
Heat pump with gas inlet cooled scroll-cachet­compressors, with large dimensioned stainless steel heat exchangers as vaporizer, condenser on a ro­bust frame with heat and noise emission insulated ca­sing.
A console with all operational and safety equipment is integrated in the body.
The device is prepared for the operation with a weat­her compensating flow temperature control (acces­sory).
The heat pump is accomplished in compact design and the vaporizer is already built inside the heat pump casing.
2.2 Range of operation
For a monovalent heating of one totwo family homes with geothermal usage, whereby the house should be equipped with a low temperature heating (e.g. un­der floor heating, wall heating or low temperature radi­ators)
2.3 Delivery content
2.4 Accessories
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
Heat pump aggregate with gas inlet cooledscroll­cachet-compressors
stainless steel heat exchanger as condenser stainless steel heat exchanger as vaporizer coolant collector and dryer Thermostatic expansion valve coolant observing window coolant heat exchanger High and low pressure manometer console with all operational and safety equipment Thermorelais to protect the compressor Internal motor protection Robust frame heat and noise emission insulated casing
Plastic brine-horizontal-collector Ø 25 x 2,3mm in loops of 100m each, incl. manifold, connection set and brine circulating pump
Brine-bore-hole Ø 40mm incl. connection set and brine circulating pump
Manifold for brine bore-hole collector
!
5 flexible connection pipes
2. Heat pump for Brine or Groundwater operation
TERRAheat pumps operate with the safety coolant R 407 C, which circulates, if properly installed in a clo­sed circuit and is practically no hazard for the envi­ronment.
As lower the maximal flow temperature is designed as higher is the heat pump effi­ciency
Page 2
- TWIN 2x8 S/W 2x10 S/W 2x12 S/W
Heating output at B 0°C/W 35°C in kW 15,34 18,24 22,56
for brine application
COP at B 0°C/W 35°C 4,02 4,07 4,08
Heating output at B 0°C/W 45°C in kW 14,86 17,68 21,66
Required electr. power at B 0°C/W 35°C in kW 3,82 4,48 5,54
B 5°C/W 45°C in kW 2,84 5,72 7,06
Electrical connection Maximal current 34,6A 46,1 A 47,0 A Blocked runner current 76 A 100 A 114 A Upstream fuse 35 A, D 50 A, D 50 A, D Fuse for control current 10 A 10 A 10 A Maximal flow temperature 55 °C 55 °C 55 °C Minimal heating water quantity 2 800 l/h 3 300 l/h 4.000 l/h Minimal circulating brine quantity 3 Pressure loss on heating circuit 10 kPa 10 kPa 11 kPa Pressure loss on collector circuit 14 kPa 15 kPa 17 kPa Heating flow and return R 1 1/4" A.G. 1 1/4" A.G. 1 1/2" A.G. Brine inlet and outlet R 1 1/4" A.G. 1 1/4” A.G. 1 1/2" A.G. Used coolant R 407 C R 407 C R 407 C Coolant quantity 2x2,0 kg 2x2,1 kg 2x2,6 kg Compressor oil quantity 2x1,1 lt. 2x1,1 lt. 2x1,85 lt. Amount of collector circuits 7 9 10 Total pipe length 700 900 1000 Brine quantity (mixture) 245 lt. 315 lt. 350 lt.
Recommended resp. integrated buffer loading pump
Recommended pump power
Heating output at B 5°C/W 35°C in kW 17,86 21,02 26,70 Heating output at B 5°C/W 45°C in kW 17,12 20,34 25,46
Required electr. power at B 0°C/W 45°C in kW 4,80 5,66 6,88 Required electr. power at B 5°C/W 35°C in kW 3,78 4,48 5,58 Required electr. power at
230V/50 Hz 230V/50 Hz 230V/50Hz
for brine collector up to 40m
.600 kg/h 4 500 kg/h 5 500 kg/h
UPS 25-80 UPS 25-80 UPS 25-80
UPS 25-80 UPS 25-80 UPS 25-80 40 x 2,3 50 x 3,2 50 x 3,2
Note: For large enough boiler rooms it is enough to have a natural venting with a min. venting opening dimensions,
like listed in the EN 378. A mechanical venting of the boiler room is only required if the boiler room dimensions are not achieved.
5. Technical Data
Page 3
in line with the EN 14511in line with the EN 14511
- TWIN 2x8 S/W 2x10 S/W 2x12 S/W
Heating output at W 10°C/W 35°C in kW 20,16 24,00 30,14
COP at W 10°C/W 35°C 10,08 12,00 15,07
for groundwater application
Heating output at W 10°C/W 45°C in kW 20,68 23,04 29,00 Heating output at W 15°C/W 35°C in kW 23,42 27,84 34,76 Heating output at W 15°C/W 45°C in kW 21,88 25,72 32,06
Required electr. power at Required electr. power at W 10°C/W 45 °C in kW 5,02 5,98 7,38 Required electr. power at W 15°C/W 35 °C in kW 4,02 4,78 5,92 Required electr. power at
Electrical connection
A 26,1 A 47 A Blocked runner current 76 A 100 A 114 A Upstream fuse 50 A, D 50 A, D 50 A, D
Maximal flow temperature 55 °C 55 °C 55 °C Minimal heating water quantity 3 500 l/h 4 200 l/h 5 200 l/h Minimal groundwater quantity 3 700 l/h 4 500 l/h 5 500 l/h Pressure loss on heating circuit 15 kPa 17 kPa 19 kPa Pressure loss on collector circuit 16 kPa 18 kPa 18 kPa Heating flow and return R 1 1/4” A.G. 1 1/4" A.G. 1 1/2" A.G. Brine inlet and outlet R 1 1/4” A.G. 1 1/4" A.G. 1 1/2" A.G. Used coolant R 407 C R 407 C R 407 C Coolant quantity 2x2,0 kg 2x2,1 kg 2x2,6 kg Compressor oil quantity 2x1,1 lt. 2x1,1 lt. 2x1,85 lt.
Recommended resp. integrated buffer loading pump
W 10°C/W 35 °C in kW 3,88 2,68 5,88
W 15°C/W 45 °C in kW 5,04 5,94 7,36
Maximal Current 34,6
Sicherung Steuerstrom 10 A 10 A 10 A
230V/50Hz 230V/50Hz 230V/50Hz
UPS 25-80 UPS 25-80 UPS 25-80
Note: For large enough boiler rooms it is enough to have a natural venting with a min. venting opening
dimensions, like listed in the EN 378. A mechanical venting of the boiler room is only required if the boiler room dimensions are not achieved.
Page 4
2.6 Operational limits
Seite 5
TERRA-S resp. TERRA-W heat pumps must be only operated with the heat carrier medium brine or Groundwater. Other heat carrier media are not permitted.
Further it is not allowed to heat other fluids than heating water.
(Heating water quality see page 10) Heat pumps have natural pressure resp. tempe-
rature operation limits. (See illustration)
It is not allowed to operate the TERRAheat pump outside these operational limits.
With groundwater heat pumps the groundwater has to have a certain waterquality,see page18. If one of those values is below or exceeds these li­mits it is not allowed to use the groundwater heat pump with this groundwater.
There are several safety applications integrated to protect the heat pump
A combined high and low pressure manome­ter which can be reset by switching the machi­ne off and backon.
Max. flow temperature limit with will automati­cally reset.
A Thermorelais which can be reset by swit­ching the machine off and back on.
Internal winding protection
With groundwater heat pumps: minimum tem­perature limit for the groundwater return tem­perature and integrated water pressure switch.
Note:
?
?
?
?
?
°C 70
60
50
40
30
20
10
0
flow temperature
Range of application for brine heat pumps
Range of application for groundwater heat
-10010 20 3040°C groundwater inlet temperature
°C 70
60
50
40
30
20
10
0
flow temperature
Minimum groundwater inlet temperature: 7°C!
Also during the winter the groundwater inlet temperature must not drop below 7°C!
-20 -10 0 10 20 30°C brine inlet temperature
2.7 Technical dimensions
Page 6
front sidefront side
right sideright side back sideback side
762
B
A
TERRA 2x8S/W 2x10S/W 2x12S/W
A 750 750 750 B 1160 1160 1160 C 1025 1025 1025 D 465 465 465 E 465 465 465
2 1
3
2 1
3
Legend:
1 flow connection R 1 1/2” (use enclosed connection pipe 1 1/4” or 1 1/2”) 2 Opening for electrical connection with grind voltage 3 return connection 4 Brine resp. groundwater inlets 5 Brine resp. groundwater outlets 6 Opening Ø 50mm for electrical output
R 1 1/2” (use enclosed connection pipe 1 1/4” )
R 1 1/2” (use enclosed connection pipe 1 1/4” )
R 1 1/2” (use enclosed connection pipe 1 1/4” )
For brine heat pumps: see page 3 For groundwater heat pumps: see page4
Dimensions for connections:
or 1 1/2”
or 1 1/2”
or 1 1/2”
C
D
E
210
210
235310
6
4
5
6
4
5
On the backside of the heat pump is a sti­cker with the connecting description loca­ted
Loading...
+ 16 hidden pages