- TWIN 2x8 S/W 2x10 S/W 2x12 S/W
Heating output at B 0°C/W 35°C in kW 15,34 18,24 22,56
for brine application
COP at B 0°C/W 35°C 4,02 4,07 4,08
Heating output at B 0°C/W 45°C in kW 14,86 17,68 21,66
Required electr. power at B 0°C/W 35°C in kW 3,82 4,48 5,54
B 5°C/W 45°C in kW 2,84 5,72 7,06
Electrical connection
Maximal current 34,6A 46,1 A 47,0 A
Blocked runner current 76 A 100 A 114 A
Upstream fuse 35 A, D 50 A, D 50 A, D
Fuse for control current 10 A 10 A 10 A
Maximal flow temperature 55 °C 55 °C 55 °C
Minimal heating water quantity 2 800 l/h 3 300 l/h 4.000 l/h
Minimal circulating brine quantity 3
Pressure loss on heating circuit 10 kPa 10 kPa 11 kPa
Pressure loss on collector circuit 14 kPa 15 kPa 17 kPa
Heating flow and return R 1 1/4" A.G. 1 1/4" A.G. 1 1/2" A.G.
Brine inlet and outlet R 1 1/4" A.G. 1 1/4” A.G. 1 1/2" A.G.
Used coolant R 407 C R 407 C R 407 C
Coolant quantity 2x2,0 kg 2x2,1 kg 2x2,6 kg
Compressor oil quantity 2x1,1 lt. 2x1,1 lt. 2x1,85 lt.
Amount of collector circuits 7 9 10
Total pipe length 700 900 1000
Brine quantity (mixture) 245 lt. 315 lt. 350 lt.
Recommended resp. integrated buffer
loading pump
Recommended pump power
Heating output at B 5°C/W 35°C in kW 17,86 21,02 26,70
Heating output at B 5°C/W 45°C in kW 17,12 20,34 25,46
Required electr. power at B 0°C/W 45°C in kW 4,80 5,66 6,88
Required electr. power at B 5°C/W 35°C in kW 3,78 4,48 5,58
Required electr. power at
230V/50 Hz 230V/50 Hz 230V/50Hz
for brine collector up to 40m
.600 kg/h 4 500 kg/h 5 500 kg/h
UPS 25-80 UPS 25-80 UPS 25-80
UPS 25-80 UPS 25-80 UPS 25-80
40 x 2,3 50 x 3,2 50 x 3,2
Note:
For large enough boiler rooms it is enough to have a natural venting with a min. venting opening dimensions,
like listed in the EN 378.
A mechanical venting of the boiler room is only required if the boiler room dimensions are not achieved.
5. Technical Data
Page 3
in line with the EN 14511in line with the EN 14511