12
Menu 7 - Service
The following options are available in this menu. The arrow along the left edge shows
which menu has been selected.
7.1 Rotation – Setting for the direction of rotation – clockwise or anti-clockwise
opening.
7.2 Manual test – Manual running of the mixing valve motor.
7.3 Control functions – Selection of control function; Room sensor (R),
Room+Outdoor sensor with Room priority (ROr), Outdoor+Room sensor with Outdoor
priority (ROo), Outdoor sensor (O), and only Supply fl ow sensor (S).
7.4 Max/Min//Rem Contr – Setting of max. and min. limits for supply temperature and desired room temperature under external control.
7.5 Display Menu - Setting the menus to be shown/changed.
7.6 Statistics – Shows the history for temperatures for the various sensors.
7.7 Pump/Add.heat – Used in combination with the relay box to start/stop the
circulation pump, heating booster etc. Only shown if relay box is connected
7.8 Alarm – Used to send an alarm, e.g. an SMS if the GSM control is connected, if
a specifi c sensor temperature is exceeded or not reached.
7.10 RF Menu – Used to activate wireless room sensor (WL)
7.11 2 SYST Menu – Used to activate System 2.
7.12 VERSION Menu – Shows software version for the CP.
7.1 Rotation
To select clockwise or anticlockwise motor opening.
7.2 Manual test
Used to test various connected functions manually.
Motor check – Press OK to open or close the motor using the up and down
arrows. If the motor goes the wrong way, the direction of rotation must be changed in
menu 7.1.
Alarm – Press OK to change on or off using the up and down arrows.
Used to send a signal if something is wrong. The setting is carried out in menu 7.8.
In the case of an alarm, connection is made on terminal block 11-12, marked “Alarm”
in the CC.
Relay add. Heat. – Press OK to change on or off using the up and down arrows.
Used with the relay box to start/stop booster heating. Also see 7.7.1.
Relay Circ.pump – Press OK to change on or off using the up and down arrows.
Used with the relay box to start/stop the circulation pump. Also see 7.7.1.
7.3 Control functions
Description of the various control functions can be found in “List”, page 3.
Outdoor sensor is not included in the basic package.
USER GUIDE – R
USER GUIDE – R