Combustible
Gas Detector
INTRODUCTION
This instrument detects combustible gases. It includes a rechargeable battery pack and charger. It is an excellent instrument to use to pinpoint combustible gas, vapor, residue or leaks and verify safety situation of potential hazardous locations.
NGD8800-Manaul-FINAL-031108 3/11/08 2:43 PM Page
SOME APPLICATIONS ARE:
• Gas lines and pipes
• Propane gas refill station
• Fuel in marine bilges
• Exhaust and fuel leaks
• Liquid or gas fired heating systems
• Check manholes for safety
Note: Although the unit will respond to high levels of Carbon Monoxide, it should not be used as a detector for this gas in normal room or working atmospheres. It is used to pinpoint a leak as described in the Operating Instructions.
HOW IT WORKS:
After the automatic warm up, when the sensor of the instrument detects vaporous and gas from combustible compound, the LED signal will light up and change with the increasing tick rate to locate the combustible leaks. This helps the user to take effective measures or actions to clear potential hazard.
FEATURES:
• Leak size indication (Audial and Visible)
• Auto fast warm-up
• Adjustable sensitivity
• Low battery indication
• Rechargeable battery
• Charge protection to prevent overcharge or over current
• Double color LED indicates charge state
• ON/OFF switch
• Sensing tip
• 14" Flexible gooseneck probe - unfasten probe knob to readjust rotation
Includes: Rechargeable battery, charger and hard carry case
NGD8800-Manaul-FINAL-031108 3/11/08 2:43 PM Page
A
Speaker
B
Charge state indicator
C
Leak size indicator-the larger the concentration, the more LED will be lit
D
Sensitivity adjust knob-turn clockwise to increase sensitivity, turn counter clockwise to decrease sensitivity
E
Power indicator-LED blinking indicates low battery. Please turn off the unit and recharge the battery.
F
ON/OFF switch
G
Sensing tip
H
Flex probe-probe knob may be loosened to rotate the probe
I
Battery compartment-unscrew to open battery door and install the battery pack with the contact upwards. Close battery door and fasten the screws.
J
Probe knob
(Figure 1)
NGD8800-Manaul-FINAL-031108 3/11/08 2:43 PM Page
OPERATION INSTRUCTIONS:
1. Turn the unit off and turn the sensitivity knob fully counter
clockwise.
2. Turn the unit on in a non-contaminated atmosphere with the slide
switch, the power indicator will light up. Power indicator shows the battery power is sufficient, it ensures precise detection.
3. After the unit is turned on, it will auto warm-up within 110
seconds, a ticking sound will be heard.
4. Adjust the sensitivity control until the first leak indicator lights up,
and the ticking frequency increases.
5. Approaching known leak source, the leak size indicate lights will
increase with the rapid ticking. Above steps are necessary to ensure the unit is working correctly. Now the unit is ready for use. If the battery power is in sufficient state, but the sensor approaches known leaks without any responses, do not use the instrument, please return for repair.
6. In conjunction with the increased tick rate, the leak size indicator
will light from bottom to top as combustible gas concentration grows.
7. Search the general area of the leak. When a detectable compound
enters the sensor, the tick rate speeds up.
8. If you are searching for a heavy leak source, please lower the
sensitivity in a clear air by turning the adjustable knob (until the leak size indicator turns off).
TO CHARGE BATTERY:
1. During operation, if the power indicator is blinking, it is necessary
to charge the battery.
2. Install the battery into the battery compartment properly, cover
battery door and fasten screws.
3. Turn off the instrument, connect the charger into a power socket of
50-60 Hz and insert the plug into the jack on the bottom of the instrument. A green charge indicator indicates that the battery power is low and still under charge(a new battery needs to be charged for 16 hours before usage)
4. When the charge indicator turns from green to orange the battery
is fully charged. Please take it off the charger.
NGD8800-Manaul-FINAL-031108 3/11/08 2:43 PM Page
Insert the plug into the jack of the instrument
Note: Battery must only be charged or replaced in an area known to be non-hazardous. Make sure the charger plug is completely plugged into the unit.
CAUTION
1. Do not use the instrument in an area of extremely high level of
combustible gas.
2. The gas/vapor of organic solvent might interfere with the function
of the unit. During detection,please eliminate the influence of the organic solvent.
3. In order to ensure correct operation and indication, the unit should
be switched on and warm-up in non-contaminated atmosphere.
4. Charge the unit at least 16 hours before it is used. If it is not used
for a long time, the unit will take a long time to warm up.
5. Do not charge the battery over 24 hours.
SPECIFICATIONS
Detect Item: Combustible gas Sensitivity: Variable, as low as 5ppm (gasoline) Response Time: Instantaneou Warm up time: <110 second (in 25°C, 60%RH Continuous operation time: Up to 2 hours (slightly vary with operation) Low battery indication: 5±0.3V Operation temperature: 0° to 110°F (0° to 52°C) Power supply: 1200mAh, 6V Ni-MH rechargeable battery Weight/Size: 17.4 oz. (492 g); 9.3"x3.4"x1.8" (235 x 86 x 46 cm) Standard accessory: (1) Tool box
(1) Charger: (DC10V AT 240mA LOADING)
(Figure 2)