Temptek CF Series Instruction Manual

I.O.M. #075 11/05
INSTRUCTION MANUAL • INSTALLATION • OPERATION • MAINTENANCE
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, IN 46142
317-887-0729 fax: 317-881-1277
Service Department fax: 317-885-8683
www.Temptek.com
e-mail: sales@Temptek.com
Page: 2
INSTRUCTION MANUAL
CF Series Portable Chiller
5 - 40 Tons
Air-Cooled & Water-Cooled
COVERING
INSTALLATION
OPERATION
MAINTENANCE
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, IN 46142
317-887-0729 fax: 317-881-1277
Service Department fax: 317-885-8683
www.TempTek.com
e-mail: sales@TempTek.com
CF Series Portable Chillers with CF-1 Instrument
Page: 4
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
TABLE OF CONTENTS
1.0 GENERAL 7
1.1 Introduction 8
1.2 Unit location 8
1.3 Efficiency 8
1.4 Safety 9
1.5 Clean air act 9
1.6 Miscellaneous 9
2.0 INSTALLATION 13
2.1 General 14
2.2 To and From process connections 14
2.3 Water supply connection 15
2.4 Air-cooled condenser 15
2.5 Water-cooled condenser 17
2.6 Electrical connection 18
3.0 OPERATIONS 21
3.1 General 22
3.2 Start up/operations procedure 23
3.3 Instrument/operation 26
3.4 Shut down procedure 30
4.0 TROUBLESHOOTING 31
4.1 Unit Will Not Start 32
4.2 Compressor Hums But Will Not Start 32
4.3 Shuts Off On High Pressure 32
4.4 Shuts Off On Low Pressure 33
4.5 Compressor Shuts Off On Internal Overload 34
4.6 Low Or No Process Pressure Or Water Flow 34
4.7 Cooling Capacity Inadequate 34
4.8 Sensor 35
4.9 Coolant Pump 35
4.10 Crankcase Heater 35
4.11 Chiller Controller 35
5.0 MAINTENANCE 37
5.1 Warranty service procedure 38
5.2 Periodic preventative maintenance 38
5.3 Special maintenance 39
5.4 Solenoid valve service 40
5.5 Pump seal service 42
5.6 Checking the refrigerant charge 45
5.7 Proper cleaning procedure for brazed plate evaporators 45
6.0 COMPONENTS 47
6.1 Water system 48
6.2 Refrigeration system 48
CF Series Portable Chillers with CF-1 Instrument
Page: 5
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
7.0 RELATED DRAWINGS 51
7.1 Mechanical Schematic : Water-Cooled : 5 - 10 Tons 52
7.2 Mechanical Schematic : Water-Cooled : 15 - 40 Tons 53
7.3 Mechanical Schematic : Air-Cooled : 5 - 10 Tons 54
7.4 Mechanical Schematic : Air-Cooled : 15 - 30 Tons 55
7.5 Typical Electrical : Air-Cooled 56
7.6 Typical Electrical : Water-Cooled 57
7.7 Physical Schematic : Air-Cooled : 7.5 - 10 Tons 58
7.8 Physical Schematic : Air-Cooled : 5 Tons 59
7.9 Physical Schematic : Water-Cooled 60
7.10 Duct Schematic for Air-Cooled Chillers 61
8.0 APPENDIX 63
8.1 Operations below 48°F 64
8.2 Water quality control 65
8.3 Inhibited propylene glycol 65
8.4 Sensor current vs temperature 65
8.5 Refrigerant pressure-temperature chart 66
8.6 Chiller capacity and derate chart 67
Page: 6
THIS PAGE INTENTIONALLY BLANK
CF Series Portable Chillers with CF-1 Instrument
1.0 GENERAL
1.1 INTRODUCTION
1.2 UNIT LOCATION
1.3 EFFICIENCY
1.4 SAFETY
1.5 CLEAN AIR ACT
1.6 MISCELLANEOUS
Page: 7
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
CF Series Portable Chillers with CF-1 Instrument
Page: 8
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
1.1 INTRODUCTION
A. This manual covers portable chillers from 5 to 40 tons.
B. When calling for assistance from the Manufacturer’s Service
Department, it is important to know the model and serial number of the particular unit. The model number encodes critical unit information which is helpful in any attempt to troubleshoot operating difficulties. The serial number allows the service team to locate manufacturing and testing records which can have additional information relating to a particular unit.
1.2 UNIT LOCATION
A. For air-cooled and water-cooled models:
1. These units are designed for indoor use only.
2. For most efficient operation, locate the chiller in a clean, dry
and well ventilated environment.
B. For air-cooled models:
1. The unit has an air-cooled refrigerant condenser. For air-
cooled condensers, a motor driven fan (on models from 5 to 15 tons) or a centrifugal blower (on models from 15 to 30 tons) generates air flow through the condenser to remove heat from the refrigerant system. The air cooled condenser on the unit will discharge a maximum of 15,000 BTU’s per hour per ton of cooling.
2. The unit must have a minimum entering air temperature of 60°F and a maximum entering air temperature of 95°F for efficient operation.
3. The unit must have a minimum of two feet clearance at the air intake and six feet at the vertical exhaust air discharge.
4. The unit must
have all enclosure panels in place before operating compressor. Air will not be drawn through the condenser coil if they are not in place. This will cause the compressor to lockout on the high pressure safety fault.
1.3 EFFICIENCY
A. Long term efficiency of operation is largely determined by proper
maintenance of the mechanical parts of the unit and the water quality. The Manufacturer recommends filtering where required to prevent solids from plugging critical parts (pumps, heaters, seals for example). The Manufacturer highly recommends the services of a competent water treatment specialist be obtained and his
CF Series Portable Chillers with CF-1 Instrument
Page: 9
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
recommendations followed. The Manufacturer accepts no responsibility for inefficient operation, or damage caused by foreign materials or failure to use adequate water treatment.
1.4 SAFETY
A. It is important to become thoroughly familiar with this manual and
the operating characteristics of the unit.
B. It is the owner’s responsibility to assure proper operator training,
installation, operation, and maintenance of the unit.
C. Observe all warning and safety placards applied to the chiller.
Failure to observe all warnings can result in serious injury or death to the operator and severe mechanical damage to the unit.
1.5 CLEAN AIR ACT
A. The unit contains HCFC-22 (chlorodifloromethane). This is a class
2 substance.
B. Effective July 1, 1992, it is unlawful for any person in the course of
maintaining, servicing, repairing, or disposing of refrigeration equipment to knowingly vent or otherwise dispose of any class 2 substance used as a refrigerant in the manner which permits such substance to enter the atmosphere.
C. De minimis releases associated with good faith attempts to
recapture, reclaim or recycle such substance shall not be subject to the prohibition set forth in the preceding paragraph.
1.6 MISCELLANEOUS
A. The unit is designed to circulate temperature stabilized fluid through
the process resulting in process temperature control.
B. The ability of the unit to maintain process temperature control is
significantly affected by the method of installation as outline in section 2 of this manual.
C. If the operator has any questions concerning the location and
operation of the unit, contact the The Manufacturer’s Service Department.
CF Series Portable Chillers with CF-1 Instrument
Page: 10
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
Air-Cooled.
Water-Cooled.
Air-Cooled Model.
Pressure Gauges
Cover Panel
Enclosure Panel
Electrical Panel
Enclosure
Casters
Instrument
Caster
Liquid Receiver
Compressor
Liquid Line Solenoid
Refrigerant Site Glass
Fan Motor
Protective Fan Shroud
Air Discharge
Hot Gas Bypass Valve
Pump
Expansion Valve
Insulated Reservoir Tank
CF Series Portable Chillers with CF-1 Instrument
Page: 11
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
Condenser Water-Out
Connection
Reservoir Make-Up
Connection
Condenser Water-In Connection
(optional)
Condenser Water
Regulator Valve
From Process Connection
Reservoir
Optional Reservoir Sight Glass
To Process Connection
Pump
Caster
Condenser
Electrical Panel
Compressor
Refrigerant Sight Glass
Expansion Valve
Make-Up Valve
Water-Cooled Model.
Page: 12
THIS PAGE INTENTIONALLY BLANK
CF Series Portable Chillers with CF-1 Instrument
Page: 13
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
2.0 INSTALLATION
2.1 GENERAL
2.2 TO AND FROM PROCESS CONNECTIONS
2.3 WATER SUPPLY CONNECTION
2.4 AIR COOLED CONDENSER INSTALLATION
2.5 WATER-COOL CONDENSER INSTALLATION
2.6 ELECTRICAL CONNECTION
CF Series Portable Chillers with CF-1 Instrument
Page: 14
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
2.1 GENERAL
A. All process piping materials (such as hose, rigid piping, valves or
filters) used in process water piping circuitry must be rated for 100°F minimum temperature and 100 PSI minimum pressure.
B. All such materials must have the equivalent or larger diameter of
the particular process connection that length of process water piping is connected to.
2.2 TO AND FROM PROCESS CONNECTIONS
A. Connect the ‘TO PROCESS’ to the ‘water in’ manifold on the mold
or process.
B. Connect the ‘FROM PROCESS’ port to the ‘water out’ port on the
process manifold.
C. Process water piping circuitry should be designed to avoid an
excessive use of elbows and/or lengths of pipe or hose. If hose is the material of choice, avoid tight twists or curls and excessive lengths.
D. Valves and filters may be installed in the process water piping
circuitry to facilitate service and maintenance provided that such devices maintain the full inside diameter of the process connection. If installed, all such devices must be open and clean during unit operation.
Air-cooled model shown.
From Process :
Connect to ‘Water Out’
port on process manifold
Water Make-Up : Connect to plant’s city water source.
To Process :
Connect to ‘Water In’ port
on process manifold
CF Series Portable Chillers with CF-1 Instrument
Page: 15
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
2.3 WATER SUPPLY CONNECTION
A. The automatic water supply make-up system continually monitors
the reservoir tank and fills it when needed. Connect as follows:
1. Connect the chiller’s ‘WATER SUPPLY’ port to the plant’s city water source.
2. Minimum water supply pressure requirement is identified on the equipment data plate. This is normally 20 psi.
3. Be certain to use a water supply line equipped with a back flow prevention device to prevent contamination of potable water.
2.4 AIR COOLED CONDENSER
A. Air-cooled condensers require ambient air temperatures between
60°F and 95°F for efficient operation. Operating above 95°F may result in elevated condensing pressures and eventual shut-down on the high pressure safety switch. In such cases, a water assist unit may be necessary for operations. Air temperatures below 60°F may result in below normal condensing pressures and poor condensing. In such cases, a low-ambient damper assembly is required. Check with the Manufacturer’s service department for more information on operating with ambients air temperatures above 95°F or below 60°F.
Water-Cooled model shown.
To Process Connection
From Process Connection
Water Supply Connection
Condenser Water-Out Connection
Condenser Water-In Connection (with optional water regulator valve)
CF Series Portable Chillers with CF-1 Instrument
Page: 16
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
B. Air flow is generated by the motor
mounted fans (figure 2.4A) or centrifugal blowers (figure 2.4B). Air flow is from the outside of the chiller, through the condenser and exhausted through the top of the unit. On centrifugal blowers models, exhaust air can be ducted outside of the plant’s interior environment. Special duct work is required and a HVAC contractor should be consulted for sizing and material specifications. Exhaust air can not be ducted on motor mounted fan models.
C. A free air space of at least two (2)
feet is required at the condenser intake and six (6) feet at the condenser discharge to allow for proper air flow.
D. At full load, the chiller will discharge
approximately 15,000 BTU’s per hour per ton of cooling.
E. On blower units, air discharge
duct work should be sized by a qualified HVAC engineer. Sizing shall be according to rated CFM at the static pressure of .90 inches of water. See figure 2.4C at right.
F. On blower units, a damper
control assembly is required in low ambient temperature areas or when outdoor air make-up is used. The assembly works in conjunction with refrigerant head pressure to regulate air flow to maintain proper refrigerant head pressure when condenser intake air temperature will be less than 60°F. See figure 2.4D to the right.
Figure 2.4A
Typical fan assembly
Figure 2.4B
Typical blower assembly
Figure 2.4C
Figure 2.4D
CF Series Portable Chillers with CF-1 Instrument
Page: 17
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
G. All air cooled units must have all enclosure panels in place before
operating compressor. Air will not be drawn through the condenser coil if they are not in place. This will cause the compressor to lockout on the high pressure safety fault.
2.5 WATER-COOLED CONDENSER
A. Connect the ‘CONDENSER WATER
IN’ port to the plant’s city water
supply or tower system supply.
1. Required consumption from a city water source is 1.5 gpm at 65°F per ton of rated capacity.
2. Required consumption for a tower water source is 3 gpm at 85°F per ton of rated capacity.
B. Connect the chiller’s ‘CONDENSER WATER OUT’ port to the
plant’s drain or tower system return.
1. Note: if dumping to the plant’s open drain, drainage shall be done according to local codes.
C. The pressure differential requirement between the condenser “water
in” and the condenser “water out” lines must be 30 psi for adequate efficiency.
D. The installation of a strainer in the
condenser “water in” line is recommended. This removes solids from the water supply and serves to protect the water saver (regulator) valve.
E. The water saver (regulator) valve
(figure 2.5B) is located in the condenser “water in” line. During winter months, or cold seasons, the valve will throttle the water flow through the condenser. The amount of flow is based on the refrigerant head pressure and the regulator will modulate the valve orifice to maintain 100° - 105°F condensing temperature for best efficiency*.
Figure 2.5A
Typical condenser connections ­30 ton unit
Figure 2.5B
Optional Regulator Valve
* See Temperature-Pressure
chart in Section 8.5 for
refrigerant pressure.
CF Series Portable Chillers with CF-1 Instrument
Page: 18
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
2.5 ELECTRICAL CONNECTION
A. NEMA 1 MODELS
1. Electrical power supply requirements for Nema 1 units are
identified on the equipment data plate. Determine the plant’s voltage supply is the same as the unit’s voltage requirements.
WARNING: Do not connect the unit to a voltage supply not equal to the unit’s voltage requirements as specified on the unit’s data plate. Use of incorrect voltage will void the unit’s warranty and cause a significant hazard that may result in serious personal injury and unit damage.
2. A customer supplied, four conductor cable is required for
connection to a customer supplied fused disconnecting means. The fused disconnecting means shall be sized and installed according to the unit’s power supply requirements and local electrical codes.
3. Connect the four conductor power cable to power entry terminal block on the unit’s electrical panel. Then connect the power cable to the fused disconnect switch.
B. NEMA 12 MODELS
1. NEMA 12 units are constructed with a dust tight electrical
enclosure and branch circuit fusing. Electrical power supply requirements are identified on the equipment data plate. Determine the plant’s voltage supply is the same as the unit’s voltage requirements.
WARNING: Do not connect the unit to a voltage supply source not equal to the unit’s voltage requirements as specified on the unit’s data plate. Use of incorrect voltage will void the unit’s warranty and cause a significant hazard that may result in serious personal injury and unit damage.
2. Appropriate conduit and fittings should be selected which
will maintain the integrity of the cabinet.
3. Supply a power conductor sized according to the unit’s power supply requirements. Connect the power conductor to the unit’s power supply entry terminal block or the fused disconnect switch. Some Nema 12 models may be supplied with an optional disconnect switch. The owner supplied fused disconnecting means shall be sized and installed according to the unit’s power supply requirements and local electrical codes.
C. CONTROL CIRCUIT WIRING
1. The unit’s supplied control circuit is 110 volt, 1 phase, 60
cycle. The control circuit is supplied by the factory installed transformer. An inline control circuit fuse is provided.
CF Series Portable Chillers with CF-1 Instrument
Page: 19
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
D. GENERAL
1. Make certain all ground connections to the unit are properly
affixed.
2. Make certain power conductor, disconnecting means, and fusing are properly sized according to the unit’s power supply requirements.
E. INFORMATION REGARDING ‘PHASING’ OF SCROLL
COMPRESSORS
1. All portable chillers that have pumps, the compressor(s) will
be set in phase with the pump during the testing process at the factory.
2. After installation the phase status must be checked by observing the pump motor shaft on the end of the pump and comparing its rotation to the directional arrow on the motor. In either case, if the phase needs to be altered, it should be done at the main power entry.
Figure 2.5A Typical electrical panel
Refrigerant High Pressure Limit
(protects from excessive condensing pressures)
Refrigerant Low Pressure Limit
(protects from low suction pressures)
Motor Contractor
(supplies voltage to coolant pump motor)
Motor Overload Relay
(protects motor from excessive amperage)
Transformer
(provides different voltages to instrument and other components)
Power Entry
(connect to power cord ­grounding lug on panel)
Compressor Contactor
(supplies voltage to compressor)
Page: 20
THIS PAGE INTENTIONALLY BLANK
CF Series Portable Chillers with CF-1 Instrument
Page: 21
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
3.0 OPERATIONS
3.1 GENERAL
3.2 START UP/OPERATIONS PROCEDURE
3.3 INSTRUMENT
3.4 SHUT DOWN
CF Series Portable Chillers with CF-1 Instrument
Page: 22
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
3.1 GENERAL
A. Failure to follow the factory required operations procedure may
adversely affect the unit’s ability to adequately control process temperature and may create a hazardous operating condition which may result in serious operator injury and/or unit damage.
B. IMPORTANT: if this unit contains a hermetic or semi-hermetic
reciprocating compressor it is equipped with a crankcase heater on the compressor. While the compressor is idle, the crankcase heater prevents freon vapor from migrating to and condensing in the compressor crankcase. If freon is allowed to condense in the crankcase, it can be drawn into the cylinders upon start up. This can cause catastrophic damage to the connecting rods, pistons, and valve plates.
To avoid this, BEFORE THE UNIT IS STARTED, THE POWER
SUPPLY SHOULD BE APPLIED TO THE UNIT FOR AT LEAST 12 HOURS, OR UNTIL THE BOTTOM OF THE COMPRESSOR IS WARM TO THE TOUCH.
If the power has been disconnected more than two hours, the power should be applied for six hours before restarting. Power should be applied to the unit continuously, except for service purposes. The crankcase heater should be checked for proper operation on a regular basis.
UNITS WITH SCROLL COMPRESSORS DO NOT HAVE A CRANKCASE HEATER AND THIS PROCEDURE IS NOT NECESSARY.
C. The OPERATIONS segment of this manual is divided into the
following sections:
3.2 Start up/operations - follow this segment to start the unit after the initial install to the process system or to restart the unit after reinstallation to the same or different process system. This section includes information on system fill, electric motor phasing (pump rotation) and process flow adjustments.
3.3 Chiller Control - follow this segment to start up and operate the chiller control. This section includes information on setpoint selection and adjustment, and feature explanations.
3.4 Shut down procedure - follow this segment to shut down the unit. This segment includes information on system shut down, electrical power supply precautions, and disconnection from system.
CF Series Portable Chillers with CF-1 Instrument
Page: 23
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
3.2 START UP / OPERATION PROCEDURE
A. SYSTEM FILL
1. The unit has an internal reservoir which must be filled and
maintained for proper operation. The unit has a level switch mounted at the proper water level in the reservoir.
2. WATER QUALITY CONTROL. Lack of, as well as, improper water treatment can damage the chilling unit. The services of competent water treatment specialist should be obtained and their recommendations followed. It is the equipment owner’s responsibility to prevent damage from foreign material or inadequate water treatment. See water treatment section in section 8 of this manual for more information.
3. FOR OPTIONAL AUTOMATIC FILL: engage
the water supply to unit. The level switch will activate the make-up solenoid (figure
3.2A), which will open and the water supply will fill the reservoir tank.
4. MANUAL FILL: disconnect the electrical power supply and remove all necessary cover panels to access the reservoir. Add fluid directly to the reservoir. When the pump is first started, as process lines are filled and air is purged, additional fluid may be required to restore the reservoir to the correct level. Verify reservoir level via the coolant sight glass (figure 3.2B).
B. ELECTRIC MOTOR PHASING (PUMP ROTATION)
1. The operator must determine the unit is phased correctly by
visually inspecting the rotation of the pump motor shaft. The procedure is outlined below. Incorrect phasing results in poor operation and eventual damage to the unit.
a. Supply electrical power to the unit. Once the correct
voltage is supplied to the unit, the POWER switch on the unit’s control panel will illuminate. Adjust the
Figure 3.2AMake-up solenoid valve
Figure 3.2B
Typical reservoir sight glass
CF Series Portable Chillers with CF-1 Instrument
Page: 24
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
setpoint to 70°F to prevent the compressor from activating during this procedure.
b. Remove all necessary cover panels to access the
pump motor. Note that the electrical power is
engaged at this point and caution must be observed while the electrical supply is engaged and cabinet panels are removed and opened.
c. Locate the electric
motor (figure 3.2C). The electric motor can be identified when the electrical panel cover is open. The operator must identify the motor shaft inside the electric motor housing. The motor shaft can be seen through the vent slots in the motor housing or by removing the shaft cover.
d. Toggle the
illuminated ON/OFF SWITCH (figure
3.2D). This will quickly cycle the pump motor “on” and then “off”.
e. Observe the motor
shaft. When the ON/OFF SWITCH is on, the motor shaft will rotate. When switched off, the shaft will slowly “coast” to a stop. As the shaft slows, the operator can identify the rotation of the motor shaft. Correct rotation (correct phase) is “clockwise”, when viewed from the rear of the motor. Incorrect rotation is “counter-clockwise” (incorrect phase) when viewed from the rear of the motor. If the shaft does not rotate when the ON/OFF SWITCH is on, the operator must identify the cause as outlined in the troubleshooting and repair section of this manual.
f. If the motor shaft is phased correctly (shaft turns in
a clockwise direction), continue with step C. If the motor shaft is NOT phased correctly (shaft turns in a counter-clockwise direction), correct as outlined in step 2.
Figure 3.2C
Electric motor
Figure 3.2D
Illuminated On/Off switch
CF Series Portable Chillers with CF-1 Instrument
Page: 25
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
2. If the unit is phased incorrectly, the operator must:
a. Disengage the electrical power supply to the unit at
the unit’s disconnect switch. Follow proper lockout procedures before proceeding.
b. Once the electrical power supply is disengaged,
reverse any two power leads of the power cord at the disconnect terminals.
c. Note: reversing any two power leads of the power
cord will correctly phase the power supply to the unit. The operator must reverse the power leads
at the disconnect switch only and
not
at the power entry terminals on the unit’s electrical panel. The unit’s internal electrical system wiring is
phased correctly at the factory and must not be altered in the field.
C. PROCESS FLOW ADJUSTMENTS
1. The operator must determine and set proper water flow rate
for the most efficient and trouble free operation.
a. Water flow rate through the process is determined
by the pressure losses in the process loop. Generally, higher flow rates result in turbulent flow achieving maximum temperature control and lower maintenance. Since the evaporator in most liquid chillers is flow sensitive, the efficiency of operation is directly related to the flow of liquid.
b. Maximum chiller efficiency is obtained at
approximately 2.4 gpm per ton of rated capacity. Low liquid flow can reduce efficiency and in some cases allow ice to develop in the evaporator which can damage the evaporator. Excessive liquid flow will trip the motor overload protection circuit.
2. Switch on the illuminated ON/OFF SWITCH to activate the process pump. Wait a few moments to allow air to be purge from system. Observe the COOLANT pressure gauge for steady readout. Two items the operator for look for are
low
flow
or
excessive flow
conditions.
3.
LOW FLOW:
If a low flow condition is present, be sure all process valves are open. If all process valves are open and a low flow conditions exists, consider the following:
a. To operate under a low flow condition, it is
necessary to install a flow bypass system in the
CF Series Portable Chillers with CF-1 Instrument
Page: 26
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
process circuitry. This will allow a portion of the flow to bypass the process and return directly to the chiller. This keeps the total flow above the cutoff point. Figure 3.2E illustrates a typical bypass loop.
b. Some models may have a factory installed bypass.
Adjust the valve accordingly.
3.3 INSTRUMENT/OPERATION
A. INSTRUMENT START-UP
1. When the correct electrical power and adequate water
supply pressure are supplied to the unit, it is possible to start the unit.
2. Upon power up, the instrument displays “ChF” indicating that the unit is in Fahrenheit temperature mode or “ChC” indicating that it is in Celsius mode. The control then shows the current setpoint for approximately 2 seconds before reverting to the To Process temperature. When power is supplied to the unit, the ON/OFF switch will illuminate.
Figure 3.2E Typical low flow by-pass loop
Figure 3.3A
CF-1 Chiller Control.
CF Series Portable Chillers with CF-1 Instrument
Page: 27
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
3. PRECAUTIONS:
The chiller control is programmed from the factory with a setpoint range of 48° to 90°F. To operate below 48°F, the addition of inhibited propylene glycol and modification of the safety control settings are required. Diligent monitoring of the water/glycol solution is mandatory to prevent freezing of the evaporator. Freezing may cause the evaporator to rupture allowing water and freon to mix which will cause major damage to the refrigeration system.
On R22, R134A and R407C models operating above 70°F and R404A models operating above 60°F requires the addition of a refrigerant crankcase pressure regulating (CPR) valve. The CPR valve is necessary to prevent overloading of the compressor which can cause premature failure. R410A models may be operated up to 80°F without a CPR valve.
Contact your local refrigeration contractor or the factory for further information. The operating range of the chiller control may be changed to 10°F - 90°F by adjusting the Setpoint Lockout (SPL) jumper. Refer to the technical section of this manual for more information.
B. INSTRUMENT OPERATION
1. To start the unit, toggle on the illuminated ON/OFF SWITCH. The chiller control will begin temperature control
operations.
2. To select setpoint temperature, press and hold the UP ARROW or DOWN ARROW keys until the desired set point temperature is displayed in the TEMPERATURE WINDOW. The default range for the setpoint temperature is 48° - 90°F or 9° - 32°C.
3. The setpoint temperature can be displayed by pressing the UP ARROW or DOWN ARROW keys. The setpoint temperature will be displayed for 5 seconds.
4. When the compressor is turned off, the instrument will wait 3 minutes before turning it back on regardless of the To Process temperature or setpoint. If a fault has occurred, the control will attempt to turn the compressor on after 3 minutes powered down. If the fault condition remains, the control will turn the compressor off and retry after 1 minute. This sequence will repeat until the compressor turns on or instrument power is cycled.
CF Series Portable Chillers with CF-1 Instrument
Page: 28
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
5. Under normal conditions (no fault conditions, compressor has been off for three minutes) the instrument will turn on the compressor when the To Process temperature is above the setpoint. The instrument will turn on the hot gas bypass when the To Process temperature is below the setpoint by no more than 3 degrees.
The instrument will turn off the compressor and hot gas bypass when the To Process temperature is 4 degrees or more below the setpoint.
C. INSTRUMENT CONTROLS
1. ILLUMINATED ON/OFF SWITCH: this rocker switch starts
or stops the unit. Electrical power is supplied to the unit when the switch is illuminated.
2. UP ARROW and DOWN ARROW KEYS: depress and hold this push button to increase (UP ARROW) or decrease (DOWN ARROW) the setpoint temperature. If the push button is pressed momentarily the setpoint value is incremented or decremented by one degree. If the push button is held down the setpoint will increase or decrease continously.
3. SETPOINT LOCK OUT JUMPER: this jumper controls whether the user is allowed to reduce the setpoint below 48°F or 9°C. If the jumper is in position 1 (farthest from the SPL label) the user IS NOT ALLOWED to reduce the setpoint below 48°F or 9°C. If the jumper is in position 2 (closest to the SPL label) the user is allowed to reduce the setpoint to 10°F or -11°C.
4. TEMPERATURE DISPLAY JUMPER: if this jumper is in the “F” position, the To Process and Setpoint temperatures are displayed in Fahrenheit. If the jumper is in the “C” position, the To Process and Setpoint temperatures are displayed in Celsius.
5. Probe Calibration: this pot (CALPOT 1) is used to calibrate the probe circuit.
Setpoint Lock Out Jumper Temperature Display Jumper Probe Calibration
Figure 3.3B
CF Series Portable Chillers with CF-1 Instrument
Page: 29
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
D. STATUS LIGHTS
1. COMPRESSOR: illuminates when compressor is turned on.
2. CAPACITY CONTROL: illuminates when capacity control
system is turned on.
3. REFRIGERANT FAULT: illuminates when there is a high pressure or low pressure alarm. Check troubleshooting section of this manual for more details.
High Pressure Alarm. If the chiller control detects a high pressure condition it will immediately turn off the compressor and hot gas bypass.
Low Pressure Alarm. After the compressor is turned on, the control has a 15 second buffer for the low pressure alarm. If a low pressure condition occurs within the first 15 seconds, the control waits the amount of time specified by the “LP TIME” potentiometer before indicating an alarm and turning off the compressor. If the condition is corrected before the time expires, no alarm occurs. If a low pressure condition occurs 15 seconds after the compressor turns on, the instrument waits 20 seconds before indicating an alarm and turning off the compressor.
E. TEMPERATURE DISPLAY
1. A three digit display window indicates the appropriate
temperature. The window also displays the numeric value for the setpoint temperature.
2. The To Process temperature is always displayed unless a button has been pressed. If there is a probe error, the display will show three dashes “---”.
F. PRESSURE GAUGES (OPTIONAL)
1. PROCESS PRESSURE GAUGE: indicates process pump
pressure.
2. REFRIGERANT HEAD PRESSURE GAUGE: indicates refrigerant pressure on the discharge side of the compressor. This is the condensing pressure which is
Figure 3.3C
Low Pressure Potentiometer.
CF Series Portable Chillers with CF-1 Instrument
Page: 30
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
critical to equipment efficiency. Head pressure on water condensed units will vary with ambient temperatures between 190-290 psig.
3. LOW PRESSURE GAUGE: indicates refrigerant pressure on the suction side of the compressor. This pressure will fluctuate with the process temperature.
3.4 SHUT DOWN/DISCONNECT SEQUENCE
A. PRECAUTIONS/WARNINGS
1. The operator must precisely follow all shut down procedures
outlined in this manual. If the operator fails to follow precisely all procedures outlined in this manual, an unsafe condition can develop resulting in damage to the unit or personal injury.
B. UNIT SHUT DOWN
1. To shut down the unit without disconnecting from the process:
a. Move the ON / OFF switch to the off position.
b. Maintain electrical power to the unit at all times
except for service purposes.
2. To shut down the unit and disconnect from the process:
a. Move the ON / OFF switch to the off position.
b. Disengage the electrical supply to the chiller at the
disconnecting device.
c. Disconnect all process lines.
CF Series Portable Chillers with CF-1 Instrument
Page: 31
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
4.0 TROUBLESHOOTING
4.1 UNIT WILL NOT START
4.2 COMPRESSOR HUMS BUT WILL NOT START
4.3 SHUTS OFF ON HIGH PRESSURE
4.4 SHUTS OFF ON LOW PRESSURE
4.5 COMPRESSOR SHUTS OFF ON INTERNAL OVERLOAD
4.6 LOW OR NO PROCESS PRESSURE OR WATER FLOW
4.7 COOLING CAPACITY INADEQUATE
4.8 SENSOR
4.9 PUMPS
4.10 CRANKCASE HEATER
4.11 CHILLER CONTROLLER
CF Series Portable Chillers with CF-1 Instrument
Page: 32
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
4.1 UNIT WILL NOT START
A. Power off. Check main disconnect.
B. Main line open. Check fuses.
C. Loose terminals. Tighten terminals with POWER OFF.
D. Control circuit open. check control voltage fuses and transformer.
4.2 COMPRESSOR HUMS BUT WILL NOT START
A. Contactor. Check contacts and contactor operation.
B. Low voltage. Check voltage at main and at the unit. If voltage is OK
at the main but low at the unit, increase wire size. If low at main, consult your local power company. Voltage must be +/- 10% nameplate rating.
C. No power on one phase of a three phase unit. Check fuses in
control panel and main disconnect. Also check unit wiring, main plant fuse and wiring. If the problem is with the main power supply coming into the plant, call the local power company.
D. Loose terminals. Tighten terminals with POWER OFF.
4.3 SHUTS OFF ON HIGH PRESSURE CONTROL
Note. Refrigerant high pressure will vary with ambient temperature
from minimum of 190 psi to as high as 280 psi. The high pressure switch manually reset when discharge pressure falls to a safe level. The switch is located inside the electrical panel.
A. Air-cooled units:
1. Insufficient condenser air flow. Check condenser filter for
dirt, fins may be plugged with dirt or foreign material. Also, check for proper fan rotation.
Note: all enclosure panels must be attached.
2. Fan motor not operating. Have electrician check fuses
and wiring, motor starter and overloads, and motor. Repair or replace motor if defective.
B. Water-cooled units:
1. Water regulator valve. Adjust condenser water regulator
valve to maintain 100°F to 105°F refrigerant condensing
CF Series Portable Chillers with CF-1 Instrument
Page: 33
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
temperature*. If valve is defective, have valve repaired or replaced by a refrigeration serviceman.
2. Insufficient condenser water flow. Check condenser water pumping system.
3. Condenser water temperature too high. Check cooling tower or proper operation city water temperature.
4. Condenser water tubes scaled. Clean with brushes and chemicals approved by the Advantage Service Department.
C. Improperly set high pressure control. Have refrigeration
serviceman reset or replace the control if defective.
4.4 SHUTS OFF ON LOW PRESSURE CONTROL
Note: The low pressure switch will automatically resets when the pressure
rises above the cut-in pressure. If this does not occur contact the the Manufacturer’s service department for instructions.
The low pressure switch is set to cut-out at 32°F and cut-in at 36°F - 39°F*. If a low pressure condition exists for more than five seconds the compressor will stop and a “L-P” fault will appear in the display window.
After the refrigerant pressure rises above the cut-in pressure, a three minute time delay will occur before the compressor restarts. This will protect the evaporator and compressor from damage should a problem occur in the refrigeration system or if the chiller is operated under circumstances which could cause damage to the refrigeration system.
A. Air-cooled units:
Head pressure too low. Check that entering air
temperature is above 60°F. If below 60°F, find out reason why.
B. Water-cooled units:
Head pressure too low. Adjust condenser water regulating
valve to maintain 100°F - 105°F refrigerant condensing temperature*. Have refrigeration serviceman repair valve or replace if defective.
C. Low refrigerant charge. Check for adequate refrigerant charge
(bubbles or misty sight glass indicates low charge). If charge is low, have system checked for leaks and recharged by a refrigeration serviceman.
* See Temperature-Pressure
chart in Section 8.5 for
refrigerant pressure.
* See Temperature-Pressure
chart in Section 8.5 for
refrigerant pressure.
* See Temperature-Pressure
chart in Section 8.5 for
refrigerant pressure.
CF Series Portable Chillers with CF-1 Instrument
Page: 34
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
D. Improperly set low pressure switch. Have a refrigeration
serviceman reset control or replace if defective.
E. Restriction in the liquid line.
1. Clogged filter drier. Check for pressure or
temperature drop and have drier core replaced by a refrigeration serviceman.
2. Liquid line valve or suction valve on compressor is partially closed. Open fully.
3. Liquid line solenoid not opening fully or leaking during off cycle. have repaired or replaced if
defective by a refrigeration serviceman.
4. Expansion valve plugged or inoperative. Check thermal bulb and capillary tube for damage. Have repaired or replaced if defective by a refrigeration serviceman.
4.5 COMPRESSOR SHUTS OFF ON INTERNAL OVERLOAD
A. Control does not reset. Have compressor windings and internal
solid state safety control checked by a refrigeration serviceman. Have it repaired or replace if defective.
4.6 LOW OR NO PROCESS PRESSURE OR WATER FLOW
A. Valves. Check if water valves are open.
B. Pump. Check pump for correct rotation. Check pump suction for
restriction. Replace motor if defective.
C. Filters. Check filter in the chilled water circuit and clean if
necessary.
D. Pressure switch (or flow switch). Readjust or replace if defective.
E. Fuses and wiring. Have electrician check the fuses and wiring.
4.7 COOLING CAPACITY INADEQUATE
A. Low refrigerant charge. Check for adequate refrigerant charge
(bubbles or misty sight glass indicates low charge). If charge is low, have system checked for leaks and recharged by a refrigeration serviceman.
B. Hot-gas bypass valve stuck open. Have repaired or replace if
defective by a refrigeration serviceman.
CF Series Portable Chillers with CF-1 Instrument
Page: 35
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
C. Expansion valve plugged or inoperative. Check thermal bulb and
capillary tube for damage. Have repaired or replaced if defective by a refrigeration serviceman.
D. Plugged filter. Check filter in chilled water circuit and clean.
E. Air in system. Purge air.
4.8 SENSOR
The sensor is a solid state temperature transducer which converts temperature input to proportional current output. To quickly test for a defective probe, switch connections between the defective probe and a probe known to be working properly. A defective sensor will display a “---” in the display window on the instrument control.
4.9 COOLANT PUMP
A. The centrifugal pump is designed to operate at a specific flow and
pressure at the maximum run load amp draw of the motor. Too much flow can overload the motor and cause the overload circuit to open and stop the pump.
B. If the overload trips, check for electrical shorts, loose wires, or
blown fuses. If these check OK, reset the overload circuit and restart the chiller.
C. Check the amp draw and if overloaded, partially close the from
process line valve until the amp draw drops to the proper level.
4.10 CRANKCASE HEATER
A. If the crankcase heater is not drawing current during the
compressor off cycle, check for a defective crankcase heater, defective fuses or defective interlock on the compressor starter.
B. Scroll compressors do not have crankcase heaters.
4.11 CHILLER CONTROLLER
A. The display is used for all normal set ups, diagnostics, temperature
readout, and operational information. Note: the display is not field repairable. It can be easily removed and replaced if required.
B. The CPU contains the software and various electronic components
which make the instrument work. Note: the CPU is not a field repairable part. It can be easily removed and replaced if a problem arises.
Page: 36
THIS PAGE INTENTIONALLY BLANK
CF Series Portable Chillers with CF-1 Instrument
Page: 37
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
5.0 MAINTENANCE
5.1 WARRANTY SERVICE PROCEDURE
5.2 PERIODIC PREVENTATIVE MAINTENANCE
5.3 SPECIAL MAINTENANCE
5.4 SOLENOID VALVE SERVICE
5.5 PUMP SEAL SERVICE
5.6 CHECKING THE REFRIGERANT CHARGE
5.7 PROPER CLEANING PROCEDURE FOR BRAZED PLATE EVAPORATOR
CF Series Portable Chillers with CF-1 Instrument
Page: 38
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
5.1 WARRANTY SERVICE PROCEDURE
A. In the event of a problem with a chiller that can not be resolved by
normal troubleshooting procedures, the customer is invited to consult the Service Department for assistance. The correct model number and serial number of the chiller must be available. The service department will attempt to isolate the problem and advise repair procedures. Often times, with the customer’s input and with the machine diagnostics, problems can be determined with “over­the-phone” consultation.
B. If the problem is beyond the scope of “over-the-phone” consultation,
and if the warranty status of the machine is valid, the Manufacturer will contact the nearest authorized service contractor and provide authorization to conduct an “on-site” inspection of the unit in order to determine the course of repair. If the chiller is not covered by the warranty, the Manufacturer will advise on the repair and recommend available service contractors.
C. It is of the utmost importance that you provide the correct model
number and serial number of the machine in question. This will allow the Service Department to obtain the correct manufacturing records which will help to properly troubleshoot the problem and obtain the proper replacement parts when they are required. This information is stamped on the data tag that is attached to the electrical enclosure of each machine.
D. The Service Department must be notified prior to any repair or
service of a warranty nature. Warranty claims will not be honored without prior authorization.
5.2 PERIODIC PREVENTATIVE MAINTENANCE
A. Lubricate all motors. Note that some motors are supplied with
sealed bearings.
B. Tighten all wire terminals.
C. Clean and check motor starter and contactor contacts.
D. Check safety switch settings.
E. Clean condenser fins of dust and dirt (air cooled models only).
F. Back flush evaporator.
G. Check glycol/water solution ratio for operating temperature.
H. Check system for leaks.
CF Series Portable Chillers with CF-1 Instrument
Page: 39
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
I. Refrigerant sight glass: check for bubbles when compressor is
operating at 100%. Check the moisture indicator for a color other than green.
J. Clean unit.
5.3 SPECIAL MAINTENANCE
A. Any service of the refrigeration system must be accomplished by a
certified refrigeration technician.
1. Addition of compressor oil.
2. Addition of refrigerant.
3. Repair of a refrigerant leak.
4. Adjustment of super heat.
5. Changing of filter-drier or drier core.
6. Repair of a refrigeration solenoid.
CF Series Portable Chillers with CF-1 Instrument
Page: 40
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
5.4 SOLENOID VALVE SERVICE
A. Units with the optional water
make-up system use a solenoid valve (figure 5.4A) to regulate flow into the reservoir tank. The solenoid valve is controlled by the float switch.
B. Generally, solenoid valves fail due
to poor water quality, low water flow, or defective valve elements.
C. The operator should follow this
procedure to service the make-up solenoid valve:
1. Disengage process operations according to the procedure outlined in section 3.4. The operator must be certain process fluid temperature is under 100°F and pressure is relieved (pressure gauge reads “0”) and water system flow is shut off and all pressure relieved.
2. Disengage main power supply. The operator must verify the proper lockout procedures are followed.
3. Remove or open any access cover panel and set aside to gain access to the cooling solenoid valve.
4. The operator must be certain all water system pressure is relieved.
5. Identify the retaining screw (figure 5.4B) on the solenoid valve coil. Remove the screw. Keeping all electrical connections intact, lift the coil off of the enclosure tube and set aside.
6. Use a pair of channel lock pliers or a pipe wrench to separate the bonnet assembly from the valve body. The plunger is “loose” inside the enclosing tube. Be certain it is retained in the enclosure tube as the bonnet is removed (figure 5.4C).
7. Identify the diaphragm assembly. Gently remove the assembly from the valve body (figure 5.4D).
Coil
Figure 5.4B
Retaining screw
Typical water make-up solenoid valve
Figure 5.4A
CF Series Portable Chillers with CF-1 Instrument
Page: 41
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
8. Identify the mesh screen. Gently removed the mesh screen and clean or replace as necessary.
9. Clean the valve body.
10. Reset the mesh screen into
the valve body.
11. If a new diaphragm assembly was obtained, continue with step 12. If not, disassemble the diaphragm assembly and note component order (figure 5.4E). Clean the valve port, plate, collar and O-ring. Once cleaned, reassemble the diaphragm.
12. Set the reassembled diaphragm assembly or the new assembly back into the valve body. The stem should be facing out of the valve body.
13. Inset the plunger with spring first into the enclosing tube of the top bonnet (figure 5.4F). Holding the plunger in the enclosure tube, set the top bonnet onto the valve body and tighten.
14. Place the coil onto the top bonnet and replace the retaining screw.
15. Open the water supply and drain valves (if installed) to circulate water through the supply and drain manifolds. Check the solenoid valve for leakage. Restart the unit as outlined in section 3.
Figure 5.4F
Plunger
Spring
Top bonnet
Enclosure tube
Top bonnet
Figure 5.4C
Enclosure tube
Plunger
Diaphragm assembly
Figure 5.4D
O-Ring
Diaphragm assembly
Mesh screen
Figure 5.4E
O-Ring
Diaphragm and stem
Collar
Plate
5.5 PUMP SEAL SERVICE
A. The coolant pump seal
is a carbon/niresist shaft seal assembly including a stationary member, rotating member and tension spring (figure 5.5A).
B. The operator can
determine the pump seal is leaking when fluid is identified leaking from the pump case adapter. Generally, a pump seal will leak due to inadequate unit pressure, excessive flow and poor fluid quality.
C. The operator should follow this procedure to replace the pump seal:
1. Disengage process operations according to the procedure
outlined in section 3.4. The operator must be certain process fluid temperature is under 100°F and pressure is relieved (COOLANT pressure gauge reads “0”) and water make-up flow is shut off and all pressure relieved.
2. Disengage main power supply. The operator must verify the proper lockout procedures are followed.
3. Access the pump motor by opening or removing any cover panels as necessary (figure 5.5B).
4. Drain machine. The machine can be drained by using the drain valve located on the pump case. Drain fluid into a suitable container for reuse or disposal according to manufacturer’s instructions (if a glycol solution is used).
5. Locate and remove the three motor wire leads from the motor wiring terminals. The operator should “map” the wire terminal locations to ensure correct rewiring. The power cord should be
CF Series Portable Chillers with CF-1 Instrument
Page: 42
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
Stationary member
Rotating Member
Tension Spring
Figure 5.5A
Pump motor
Figure 5.5B
Pump motor
Figure 5.5C
removed from the motor housing (figure 5.5C).
6. Locate and remove the pump casing bolts. These bolts secure the motor and motor adapter to the pump casing (figure 5.5D).
7. Separate the motor and motor adapter from the pump casing to expose the pump impeller (figure
5.5E). Remove the motor and motor adapter from the unit and place on a workbench to continue the procedure.
8. Locate and remove the dust cap from motor end to expose slotted motor shaft. The motor shaft is free to rotate, but must be secured to remove the impeller. To secure the motor shaft, insert a flat bladed screw driver in slot to hold the shaft stationary (Figure
5.5F).
9. Locate and remove impeller locking screw (Figure
5.5G). Using a socket and ratchet, the impeller retaining screw can be removed. Once the retaining screw is removed, the impeller can be “unthreaded” from the motor shaft to expose the pump seal assembly.
10. Remove all seal parts (Figure 5.5H). Note seal component arrangement to facilitate reassembly.
11. Clean motor shaft and lubricate with a mild soap solution.
CF Series Portable Chillers with CF-1 Instrument
Page: 43
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
Typical pump casing bolt
Figure 5.5D
Motor shaft
Figure 5.5F
Typical impeller
Figure 5.5G
Impeller
Figure 5.5E
CF Series Portable Chillers with CF-1 Instrument
Page: 44
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
12. Install new stationary seal member in pump casing cavity (figure 5.5I). The operator must be certain the stationary seal member is fully squared and seated in cavity.
13. Slide the rotating member onto lubricated pump shaft (figure 5.5J). The operator must be certain not to damage or tear rubber bellows assembly.
14. Place the spring onto the rotating member.
15. Align the impeller, spring and rotating member before reinstalling the impeller (figure 5.5K). The operator must be certain the spring and rotating member are aligned before the impeller is fully tighten and the impeller retaining screw is reinstalled.
16. Clean pump casing, cavities, impeller and O­ring before reassembly.
17. Mate the motor and motor adapter to the pump casing. Reinstall the pump casing bolts.
18. Reconnect the motor power cord and leads.
19. Restore all cover panels as were removed.
E. When the pump seal replacement
procedure is complete, the operator may restart the unit according the section 3.
Stationary member
Figure 5.5I
Stationary member
Figure 5.5J
Seal members
Figure 5.5K
Seal components
Figure 5.5H
CF Series Portable Chillers with CF-1 Instrument
Page: 45
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
5.6 CHECKING THE REFRIGERANT CHARGE
A. All standard chillers are
manufactured with thermostatic expansion valves as the metering device to the evaporator.
B. All standard chillers have a
refrigerant sight glass (figure 5.6A) with a moisture indicator. To check the refrigerant charge under normal operating conditions:
1. Remove the plastic cap covering the sight glass.
2. Start the chiller and allow system pressures and temperatures to stabilize.
3. With the unit operating at 100% capacity (not in the “capacity control” mode) the sight glass should appear clear with no foam or bubbles evident. If foam or bubbles are evident, the chiller has suffered from a loss of refrigerant and should be checked by a qualified refrigeration technician.
4. The “dot” in the middle of the sight glass is the moisture indicator. It should appear green at all times. A white or yellow color indicates moisture has invaded the refrigeration system, which is detrimental to the life of the compressor. The filter-drier should be replaced by a qualified refrigeration technician.
5.7 PROPER CLEANING PROCEDURE FOR BRAZED PLATE EVAPORATORS
A. The brazed plate evaporator is
made of stamped stainless steel plates, furnace brazed together with copper based joints. The complex geometry of the flow passages promotes turbulent flow which gives high efficiency and reduces fouling by mineral deposits. Large solids such as plastic pellets or chunks of mineral deposits will collect at the water inlet port at the evaporator and restrict flow through some of the passages. If this possibility exists, the Manufacturer recommends filters or strainers be added to the “from process” line. If the evaporator becomes fouled there are a couple of methods for cleaning.
Sight Glass
Figure 5.6A
Evaporator
Figure 5.6A
B. To begin, remove the piping to the “water in” port at the evaporator.
Remove any solids that have collected at this point. Then back flush the evaporator to remove any solids that may be trapped between the plates (see back flush procedure below). If there are mineral deposits adhered to the plates, the evaporator must be back flushed with a mild acid solution (5% phosphoric or 5% oxalic acid is recommended.) After cleaning rinse with clear water before returning to service. Continue with step C on the next page.
C. Back flushing procedure:
1. Turn off all power to the machine. For chillers with a
reservoir tank, drain the tank to below the evaporator outlet. For chillers without a reservoir tank, drain total unit.
2. Connect a water supply hose to the evaporator water outlet. If acid cleaning, connect the discharge hose from the acid pump to the evaporator outlet port.
3. Connect a hose to the evaporator water supply port and to an appropriate containment vessel. If acid cleaning, connect the evaporator water inlet port to an acid solution reservoir tank. Dispose of all back flush fluid according to local codes.
4. The cleaning fluid source should have at least 20 psi available. If acid cleaning, follow the instructions supplied with the acid solution carefully.
5. When the procedure is complete, reinstall all water lines to original factory orientation. Restart the unit and check for proper operation.
6. Note: this procedure is not normal maintenance. Maintaining proper water quality and filtration will minimize the need to back flush the evaporator.
CF Series Portable Chillers with CF-1 Instrument
Page: 46
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
BRAZED PLATE HEAT EXCHANGER
(EVAPORATOR)
FREON OUT
FREON IN
ORIGINAL WATER OUT PORT BACKFLUSH WATER IN PORT
(SUPPLY BACKFLUSHING WATER
FLOW TO THIS PORT)
ORIGINAL WATER IN PORT
BACKFLUSH WATER OUT PORT
(ROUTE WATER TO PROPER
SEWER OR DRAIN CONTAINER)
CF Series Portable Chillers with CF-1 Instrument
Page: 47
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
6.0 COMPONENTS
6.1 WATER SYSTEM
6.2 REFRIGERATION SYSTEM
6.1 WATER SYSTEM
A. MOTOR/PUMP ASSEMBLY: the
motor/pump assembly circulates chilled fluid to the process loop. The pump assembly is built of total stainless steel to maintain water quality (figure 6.1A).
6.2 REFRIGERATION SYSTEM
A. COMPRESSOR: hermetic or semi-
hermetic compressors take low pressure/low temperature refrigerant gas and compress the gas into high pressure/high temperature gas (figure 6.2A).
B. AIR COOLED CONDENSER: the
air cooled condenser removes BTU’s from the compressed refrigerant gas. The action causes the gas to “condense” into a liquid state still under high pressure. Air flow across the condenser is achieved via a motor driven fan assembly or centrifugal blower (figure 6.2B).
C. FILTER-DRIER: the filter-drier
removes contaminants and moisture from the liquid refrigerant (figure 6.2C).
D. LIQUID LINE SOLENOID VALVE:
controlled by the instrument, this valve closes when the compressor cycles off to prevent refrigerant liquid from migrating to the evaporator. The valve opens when the compressor cycles on.
E. REFRIGERANT SIGHT GLASS:
the refrigerant sight glass indicates refrigerant charge and moisture content. Refrigerant charge is determined by a clear liquid flow. Bubbles indicate low refrigerant. Moisture content is indicated by the color of the element. Element color is normally green. If the color of the
CF Series Portable Chillers with CF-1 Instrument
Page: 48
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
Hermetic compressor
Semi-hermetic compressor
Figure 6.2A
Pump Motor Assembly
Figure 6.1A
Typical filter-drier
Figure 6.2C
Fans
Blower
Figure 6.2B
element is chartreuse or yellow, the system has been contaminated with moisture. In such case, the filter-drier must be replaced. The replacement of the filter-drier must be completed by a qualified refrigerant service technician (figure 6.2D).
F. EXPANSION VALVE: the
expansion valve throttles flow of refrigerant liquid into the evaporator and creates a pressure drop in the refrigerant system that allows the liquid refrigerant to “boil off” inside the evaporator (figure 6.2E).
G. EVAPORATOR: the evaporator is a
brazed plate heat exchanger where the refrigerant liquid is allowed to evaporate (boil off) to absorb heat (BTU) from the process fluid. As the heat is absorbed, the process fluid is chilled (figure 6.2F).
H. HOT GAS BY-PASS SOLENOID:
the hot gas by-pass solenoid prevents short cycling of the compressor by reducing the capacity by 50% when the process fluid temperature nears the setpoint.
I. HIGH/LOW PRESSURESTATS:
the high/low pressurestats protect the refrigeration system from unsafe operating levels. The high pressure switch is factory set and protects the refrigeration components and personnel from potential damage of injury from excessive high pressure. The high pressure safety must not be altered in the field for any reason. (See section
8.1 for factory settings.) The low pressure switch is factory set to open at 32°F and to close at 36° - 39°F.* The low pressure switch protects the chillers from possible damage due to low operating pressure. The low pressure switch is field adjustable for setpoints below 48°F.
NEVER LOWER THE CUT OUT SETTING WITHOUT ADDING GLYCOL TO THE CIRCULATING SYSTEM. EVAPORATOR DAMAGE WILL RESULT AND WILL NOT BE COVERED BY THE WARRANTY.
CF Series Portable Chillers with CF-1 Instrument
Page: 49
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
Expansion Valve
Figure 6.2E
Refrigerant sight glass
Figure 6.2D
Typical hot gas bypass valve
Figure 6.2H
* See Temperature-Pressure
chart in Section 8.5 for
refrigerant pressure.
CF Series Portable Chillers with CF-1 Instrument
Page: 50
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
J. Liquid receiver: located after the condenser, this component
receives and stores liquid refrigerant leaving the condenser.
K. Service valves: have been provided throughout the system. Only a
qualified refrigeration service technician shall operate these valves.
L. Crankcase heater: insures that freon and compressor crankcase
oil do not mix during the compressor’s “off ” cycles. Power must be applied to the chiller previous to startup.
M. Oil pressure safety switch: protects the compressor from
lubrication failure.
CF Series Portable Chillers with CF-1 Instrument
Page: 51
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
7.0 RELATED DRAWINGS
7.1 MECHANICAL SCHEMATIC : WATER-COOLED : 2 - 10 TONS
7.2 MECHANICAL SCHEMATIC : WATER-COOLED : 15 - 40 TONS
7.3 MECHANICAL SCHEMATIC : AIR-COOLED : 5 - 10 TONS
7.4 MECHANICAL SCHEMATIC : AIR-COOLED : 15 - 30 TONS
7.5 TYPICAL ELECTRICAL : AIR-COOLED
7.6 TYPICAL ELECTRICAL : WATER-COOLED
7.7 PHYSICAL SCHEMATIC : AIR-COOLED : 7.5 - 10 TONS
7.8 PHYSICAL SCHEMATIC : AIR-COOLED : 5 TONS
7.9 PHYSICAL SCHEMATIC : WATER - COOLED :
7.10 DUCT SCHEMATIC FOR AIR-COOLED CHILLERS
CF Series Portable Chillers with CF-1 Instrument
Page: 52
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
7.1 MECHANICAL SCHEMATIC : WATER-COOLED : 2 - 10 TONS
TO PROCESS
PRESSURE GAUGE
WATER REGULATOR VALVE
COOLANT PUMP
TO PROCESS
SENSOR PROBE
TO PROCESS
PORT CONNECTION
MAKE-UP PORT
CONNECTION
MAKE-UP
SOLENOID VALVE
LEVEL SWITCH
FROM PROCESS
PORT CONNECTION
CONDENSER WATER IN
PORT CONNECTION
CONDENSER WATER OUT
PORT CONNECTION
RESERVOIR TANK
EXPANSION VALVE
EVAPORATOR
SERVICE LID AND FILL PORT
REFRIGERANT
SIGHT GLASS
LIQUID LINE
SOLENOID VALVE
FILTER-DRIER
SERVICE VALVE
HOT GAS
BYPASS VALVE
COMPRESSOR
(may be Scroll Hermetic
or Recip Semi-hermetic)
HEAD PRESSURE GAUGE
HIGH PRESSURE
SAFETY SWITCH
SUCTION LINE PRESSURE GAUGE
LOW PRESSURE SAFETY SWITCH
WATER COOLED CONDENSER
CF Series Portable Chillers with CF-1 Instrument
Page: 53
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
7.2 MECHANICAL SCHEMATIC : WATER-COOLED : 15 - 40 TONS
TO PROCESS
PRESSURE GAUGE
WATER REGULATOR VALVE
COOLANT PUMP
TO PROCESS
SENSOR PROBE
TO PROCESS
PORT CONNECTION
MAKE-UP PORT
CONNECTION
MAKE-UP
SOLENOID VALVE
LEVEL SWITCH
FROM PROCESS
PORT CONNECTION
CONDENSER WATER IN
PORT CONNECTION
CONDENSER WATER OUT
PORT CONNECTION
RESERVOIR TANK
EXPANSION VALVE
EVAPORATOR
SERVICE LID AND FILL PORT
REFRIGERANT
SIGHT GLASS
LIQUID LINE
SOLENOID VALVE
FILTER-DRIER
SERVICE VALVE
HOT GAS
BYPASS VALVE
COMPRESSOR
(may be Scroll Hermetic
or Recip Semi-hermetic)
HEAD PRESSURE GAUGE
HIGH PRESSURE
SAFETY SWITCH
SUCTION LINE PRESSURE GAUGE
LOW PRESSURE SAFETY SWITCH
WATER COOLED CONDENSER
CF Series Portable Chillers with CF-1 Instrument
Page: 54
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
7.3 MECHANICAL SCHEMATIC : AIR-COOLED : 2 - 10 TON MODELS
TO PROCESS
PRESSURE GAUGE
AIR-COOLED CONDENSER w/FANS
(5-ton model uses single fan)
COOLANT PUMP
TO PROCESS
SENSOR PROBE
TO PROCESS
PORT CONNECTION
MAKE-UP PORT
CONNECTION
MAKE-UP
SOLENOID VALVE
LEVEL SWITCH
FROM PROCESS
PORT CONNECTION
RESERVOIR TANK
EXPANSION VALVE
EVAPORATOR
SERVICE LID AND FILL PORT
REFRIGERANT
SIGHT GLASS
LIQUID LINE
SOLENOID VALVE
FILTER-DRIER
SERVICE
VALVE
LIQUID LINE
RECEIVER
HOT GAS
BYPASS VALVE
COMPRESSOR
(may be Scroll Hermetic or Recip)
HEAD PRESSURE GAUGE
HIGH PRESSURE SAFETY SWITCH
SUCTION LINE
PRESSURE GAUGE
LOW PRESSURE
SAFETY SWITCH
CF Series Portable Chillers with CF-1 Instrument
Page: 55
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
7.4 MECHANICAL SCHEMATIC : AIR-COOLED : 15 - 30 TON MODELS
TO PROCESS
PRESSURE GAUGE
AIR-COOLED CONDENSER w/blower
COOLANT PUMP
TO PROCESS
SENSOR PROBE
TO PROCESS
PORT CONNECTION
MAKE-UP PORT
CONNECTION
MAKE-UP
SOLENOID VALVE
LEVEL SWITCH
FROM PROCESS
PORT CONNECTION
RESERVOIR TANK
EXPANSION VALVE
EVAPORATOR
SERVICE LID AND FILL PORT
REFRIGERANT
SIGHT GLASS
LIQUID LINE
SOLENOID VALVE
FILTER-DRIER
SERVICE
VALVE
LIQUID LINE
RECEIVER
HOT GAS
BYPASS VALVE
COMPRESSOR
(may be Scroll Hermetic or Recip)
HEAD PRESSURE GAUGE
HIGH PRESSURE SAFETY SWITCH
SUCTION LINE
PRESSURE GAUGE
LOW PRESSURE
SAFETY SWITCH
CF Series Portable Chillers with CF-1 Instrument
Page: 56
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
7.5 TYPICAL ELECTRICAL SCHEMATIC : AIR-COOLED MODELS
UNIT
ON/OFF
22
BLK
WHT
PRIMARY
24 VAC
SECONDARY
120v
BLU/RED
BLU/WHT
RED/RED
RED/RED
5022
23
25
24
27
27
31
23
L1
L2
L3
L4
GROUND
POWER ENTRY
PUMP
M1
1 MOL
M1
COMPRESSOR
M2
M2
110VAC SEC.
TRANSFORMER
GROUND
FU
1
1
2
3 3
2
1
3
1
16
15
14 17
18
19
M3
19
17
FAN MOTOR
LEVEL SWITCH
50
50
M1
1 MOL
S
50
50
23
2323
PUMP MOTOR COIL
SNUBBER
5023
ANTI-DRAIN BACK SOLENOID (OPTIONAL)
S
5020
PRESSURESTAT
HIGH
M2
S
50
50
5030
30
30
COMPRESSOR MOTOR COIL
SNUBBER
LIQUID LINE SOLENOID
S
50
5031
31
SNUBBER
SNUBBER
20
20
20
50
22
22
22
50
HOT GAS SOLENOID
21
POWER ON
WATER MAKE-UP SOLENOID (OPTIONAL)
M4
19
17
FAN MOTOR
(OPTIONAL)
FLOW SWITCH
OPTIONAL
OPTIONAL
STAT
FREEZE-
29 30
JUMPER
28
TO PROCESS PROBE
BLK
ADJUST SETPOINT
* PUSH ONCE TO VIEW SETPOINT * PUSH AND HOLD TO CHANGE SETPOINT
TEMPERATURE
COMPRESSOR
CAPACITY
CONTROL
REFRIGERATION
FAULT
CHILLER CONTROL
MICROPROCESSOR
BLU/YEL
RED/YEL
RED/YEL
PRESSURESTAT
LOW
50
26
31
FAULT INDICATOR
CF Series Portable Chillers with CF-1 Instrument
Page: 57
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
7.6 TYPICAL ELECTRICAL SCHEMATIC : WATER-COOLED MODELS
UNIT
ON/OFF
22
BLK
WHT
PRIMARY
24 VAC
SECONDARY
120v
BLU/RED
BLU/WHT
RED/RED
RED/RED
5022
23
25
24
27
27
31
23
L1
L2
L3
L4
GROUND
POWER ENTRY
PUMP
M1
1 MOL
M1
COMPRESSOR
M2
M2
110VAC SEC.
TRANSFORMER
GROUND
FU
1
1
2
3 3
2
1
3
1
16
15
14 17
18
19
LEVEL SWITCH
50
50
M1
1 MOL
S
50
50
23
2323
PUMP MOTOR COIL
SNUBBER
5023
ANTI-DRAIN BACK SOLENOID (OPTIONAL)
S
5020
PRESSURESTAT
HIGH
M2
S
50
50
5030
30
30
COMPRESSOR MOTOR COIL
SNUBBER
LIQUID LINE SOLENOID
S
50
5031
31
SNUBBER
SNUBBER
20
20
20
50
22
22
22
50
HOT GAS SOLENOID
21
POWER ON
WATER MAKE-UP SOLENOID (OPTIONAL)
FLOW SWITCH
OPTIONAL
OPTIONAL
STAT
FREEZE-
29 30
JUMPER
28
TO PROCESS PROBE
BLK
ADJUST SETPOINT
* PUSH ONCE TO VIEW SETPOINT * PUSH AND HOLD TO CHANGE SETPOINT
TEMPERATURE
COMPRESSOR
CAPACITY
CONTROL
REFRIGERATION
FAULT
CHILLER CONTROL
MICROPROCESSOR
BLU/YEL
RED/YEL
RED/YEL
PRESSURESTAT
LOW
50
26
31
FAULT INDICATOR
23
26
30
27
CF Series Portable Chillers with CF-1 Instrument
Page: 58
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
7.7 PHYSICAL SCHEMATIC : AIR-COOLED : 7.5 - 10 TONS
CF Series Portable Chillers with CF-1 Instrument
Page: 59
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
7.8 PHYSICAL SCHEMATIC : AIR-COOLED : 5 TONS
CF Series Portable Chillers with CF-1 Instrument
Page: 60
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
7.9 PHYSICAL SCHEMATIC : WATER-COOLED
CF Series Portable Chillers with CF-1 Instrument
Page: 61
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
7.10 DUCT SCHEMATIC FOR AIR-COOLED CHILLERS
A. For models equiped with centrifugal blower. Models with equipped
with fans can not be ducted.
13
12
11
10
9
8
7
6
5
4
3
2
1
Item
1 2 3 4 5 6 7 8
9 10 11 12 13
Description Weather cap Screen Flashing to suit Roof curb Plant roof Butterfly with counterbalance Separate duct support from roof Gate control for exhaust air flow Manual chain control Duct to plant heating system Mating collar Chiller air exhaust port Air cooled chiller with blower
NOTE: THIS DRAWING IS FOR
EXPLANATION PURPOSES ONLY,
NOT FOR CONSTRUCTION PURPOSES
Page: 62
THIS PAGE INTENTIONALLY BLANK
CF Series Portable Chillers with CF-1 Instrument
Page: 63
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
8.0 APPENDIX
8.1 OPERATIONS BELOW 48°F
8.2 WATER QUALITY CONTROL
8.3 INHIBITED PROPYLENE GLYCOL
8.4 SENSOR CURRENT VS TEMPERATURE CHART
8.5 REFRIGERANT PRESSURE-TEMPERATURE CHART
8.6 CHILLER CAPACITY AND DERATE CHART
CF Series Portable Chillers with CF-1 Instrument
Page: 64
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
8.1 OPERATIONS BELOW 48°F
A. Chillers supplied with the automatic water supply system, the water
supply connection must be plugged when operating below 48°F or anytime the system utilizes a water/inhibited propylene glycol solution. The system must be manually filled and the mix shall be checked for the proper ratio on a regular basis.
B. Addition of an inhibited propylene glycol solution is required. The
ration shall be according to figure 8.3A. Too much glycol can cause capacity and control problems. Under no circumstances shall an automotive type antifreeze be used in the chilling unit.
C. The freezestat and low pressurestat settings must be field adjusted
according to figure 8.3B.
NEVER LOWER THE CUT OUT SETTING WITHOUT ADDING GLYCOL TO THE CIRCULATING SYSTEM. EVAPORATOR DAMAGE WILL RESULT AND WILL NOT BE COVERED BY THE WARRANTY.
Figure 8.3A & Figure 8.3B
Refrigerant Low Pressure Switch Cut-Out & Cut-In Settings
Operating
Temperature
48° - 70°F
25° - 47°F
10° - 24°F
Operating
Temperature
48° - 70°F
25° - 47°F
10° - 24°F
High Pressure Cut Out (maximum)
Refrigerant
R22
R134A
R407C
R410A
R404A
Glycol
0%
30%
40%
Glycol
0%
30%
40%
Freeze
Point
32°F
10°F
-5°F
Freeze
Point
32°F
10°F
-5°F
Air-Cooled
380#
260#
405#
610#
405#
Cut Out
Cut Out
Temp
32°F
10°F
-5°F
Temp
32°F
10°F
-5°F
Cut In
Temp
36°F - 39°F
15°F - 18°F
0°F - 7°F
Cut In
Temp
36°F - 3°9F
15°F - 1°8F
0°F - 7°F
Water-Cooled
360#
260#
360#
550#
360#
Cut-Out
58#
33#
20#
R404A
Cut-Out
72#
44#
29#
R22
Cut-In
63#
38#
25#
Cut-In
79#
49#
34#
R134A
Cut-Out
Cut-Out
Cut-In
28#
12#
4#
52#
28#
16#
33#
17#
9#
R407C
Cut-In
58#
34#
22#
R410A
Cut-Out
102#
63#
43#
Cut-In
111#
72#
52#
CF Series Portable Chillers with CF-1 Instrument
Page: 65
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
8.2 WATER QUALITY CONTROL
A. Lack of proper water treatment can damage the chilling unit. The
services of a competent water treatment specialist should be obtained and their recommendations followed. It is the equipment owner’s responsibility to prevent damage from foreign material or inadequate water treatment.
B. The two main things to consider for water treatment in chillers are
corrosion and organism growth. Proper chemical treatment can control PH levels and algae growth. An alternative to chemical treatment is the addition of 30% inhibited propylene glycol to the water. This will help prevent organism growth and coat the heat transfer surfaces with corrosion inhibitor.
8.3 INHIBITED PROPYLENE GLYCOL
A. To operate liquid chillers below 48°F, it is necessary to add
inhibited propylene glycol to the circulating system to lower the
freeze point and prevent damage to the cooling system. Inhibited propylene glycol contains corrosion inhibitors which are compatible with most industrial heat transfer surfaces. Inhibited propylene glycol is manufactured by:
• Dow Chemical - “DowFrost” (1-800-258-2436)
• Monsanto “Therminol FS” (1-800-459-2665)
• Advantage Engineering “Thermofluid” (1-317-887-0729)
B. Automotive anti-freeze must never be used in industrial heat transfer
applications. Automotive anti-freeze contains silicate type corrosion inhibitors designed to be compatible with automotive components. In an industrial application, the silicates will form a gel on the heat transfer surface which will result in substantial reduction in cooling capacity and is virtually impossible to remove.
8.4 SENSOR CURRENT VS TEMPERATURE
-20°F = 243.86 A
-10°F = 249.43 A 0°F = 255.00 A
10°F = 260.57 A 20°F = 266.14 A 30°F = 271.71 A 40°F = 277.27 A 50°F = 282.84 A 60°F = 288.41 A 70°F = 293.98 A 80°F = 299.55 A
90°F = 305.12 A 100°F = 310.69 A 110°F = 316.26 A
120°F = 321.82 A 130°F = 327.39 A 140°F = 332.96 A 150°F = 338.53 A 160°F = 344.10 A 170°F = 349.67 A 180°F = 355.24 A 190°F = 360.80 A 200°F = 366.37 A 210°F = 371.64 A 220°F = 377.51 A 230°F = 383.08 A 240°F = 388.65 A 250°F = 394.22 A
Formula:
• 1 u A = (556.8627 x 10 x °F) = (255 x 10)
• °F = (1 u A - 255 x 10) + (556.8627 x 10)
Battery
9 volt
Microammeter
+-+-
Black wireWhite wire
CF Series Portable Chillers with CF-1 Instrument
Page: 66
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
8.5 REFRIGERANT PRESSURE-TEMPERATURE CHART
CF Series Portable Chillers with CF-1 Instrument
Page: 67
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
8.6 CHILLER CAPACITY AND DERATE CHART
60
50
45
40
35
30
25
20
15
10
5
0
-5
*
*
*
*
*
105%
100%
90%
80%
70%
60%
50%
40%
30%
22%
15%
9%
5%
OUTPUT
TEMPERATURE
°F
FULL AVAILABLE % CAPACITY
NOTES:
If operation of the chiller at less than 48°F is required, an inhibited propylene glycol solution is required.
Consult factory for chiller operation below 20°F.
Ambient conditions affect air cooled chiller operation and capacity. Standard rating is at 95°F entering air temperature. For ambient air conditions greater than 95°F, chiller derating will occur. For ambients of 95-105°F, select the next larger capacity chiller. For ambients over 105°F, consult factory.
* These ranges require special options.
Standard chiller rating is at 50°F. For all other temperature settings, output tonnage is altered as follows:
Page: 68
THIS PAGE INTENTIONALLY BLANK
END
© 2009 TEMPTEK, INC.
RE 2 09/09
Loading...