Temptek CF Series Instruction Manual

I.O.M. #075 11/05
INSTRUCTION MANUAL • INSTALLATION • OPERATION • MAINTENANCE
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, IN 46142
317-887-0729 fax: 317-881-1277
Service Department fax: 317-885-8683
www.Temptek.com
e-mail: sales@Temptek.com
Page: 2
INSTRUCTION MANUAL
CF Series Portable Chiller
5 - 40 Tons
Air-Cooled & Water-Cooled
COVERING
INSTALLATION
OPERATION
MAINTENANCE
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, IN 46142
317-887-0729 fax: 317-881-1277
Service Department fax: 317-885-8683
www.TempTek.com
e-mail: sales@TempTek.com
CF Series Portable Chillers with CF-1 Instrument
Page: 4
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
TABLE OF CONTENTS
1.0 GENERAL 7
1.1 Introduction 8
1.2 Unit location 8
1.3 Efficiency 8
1.4 Safety 9
1.5 Clean air act 9
1.6 Miscellaneous 9
2.0 INSTALLATION 13
2.1 General 14
2.2 To and From process connections 14
2.3 Water supply connection 15
2.4 Air-cooled condenser 15
2.5 Water-cooled condenser 17
2.6 Electrical connection 18
3.0 OPERATIONS 21
3.1 General 22
3.2 Start up/operations procedure 23
3.3 Instrument/operation 26
3.4 Shut down procedure 30
4.0 TROUBLESHOOTING 31
4.1 Unit Will Not Start 32
4.2 Compressor Hums But Will Not Start 32
4.3 Shuts Off On High Pressure 32
4.4 Shuts Off On Low Pressure 33
4.5 Compressor Shuts Off On Internal Overload 34
4.6 Low Or No Process Pressure Or Water Flow 34
4.7 Cooling Capacity Inadequate 34
4.8 Sensor 35
4.9 Coolant Pump 35
4.10 Crankcase Heater 35
4.11 Chiller Controller 35
5.0 MAINTENANCE 37
5.1 Warranty service procedure 38
5.2 Periodic preventative maintenance 38
5.3 Special maintenance 39
5.4 Solenoid valve service 40
5.5 Pump seal service 42
5.6 Checking the refrigerant charge 45
5.7 Proper cleaning procedure for brazed plate evaporators 45
6.0 COMPONENTS 47
6.1 Water system 48
6.2 Refrigeration system 48
CF Series Portable Chillers with CF-1 Instrument
Page: 5
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
7.0 RELATED DRAWINGS 51
7.1 Mechanical Schematic : Water-Cooled : 5 - 10 Tons 52
7.2 Mechanical Schematic : Water-Cooled : 15 - 40 Tons 53
7.3 Mechanical Schematic : Air-Cooled : 5 - 10 Tons 54
7.4 Mechanical Schematic : Air-Cooled : 15 - 30 Tons 55
7.5 Typical Electrical : Air-Cooled 56
7.6 Typical Electrical : Water-Cooled 57
7.7 Physical Schematic : Air-Cooled : 7.5 - 10 Tons 58
7.8 Physical Schematic : Air-Cooled : 5 Tons 59
7.9 Physical Schematic : Water-Cooled 60
7.10 Duct Schematic for Air-Cooled Chillers 61
8.0 APPENDIX 63
8.1 Operations below 48°F 64
8.2 Water quality control 65
8.3 Inhibited propylene glycol 65
8.4 Sensor current vs temperature 65
8.5 Refrigerant pressure-temperature chart 66
8.6 Chiller capacity and derate chart 67
Page: 6
THIS PAGE INTENTIONALLY BLANK
CF Series Portable Chillers with CF-1 Instrument
1.0 GENERAL
1.1 INTRODUCTION
1.2 UNIT LOCATION
1.3 EFFICIENCY
1.4 SAFETY
1.5 CLEAN AIR ACT
1.6 MISCELLANEOUS
Page: 7
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
CF Series Portable Chillers with CF-1 Instrument
Page: 8
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
1.1 INTRODUCTION
A. This manual covers portable chillers from 5 to 40 tons.
B. When calling for assistance from the Manufacturer’s Service
Department, it is important to know the model and serial number of the particular unit. The model number encodes critical unit information which is helpful in any attempt to troubleshoot operating difficulties. The serial number allows the service team to locate manufacturing and testing records which can have additional information relating to a particular unit.
1.2 UNIT LOCATION
A. For air-cooled and water-cooled models:
1. These units are designed for indoor use only.
2. For most efficient operation, locate the chiller in a clean, dry
and well ventilated environment.
B. For air-cooled models:
1. The unit has an air-cooled refrigerant condenser. For air-
cooled condensers, a motor driven fan (on models from 5 to 15 tons) or a centrifugal blower (on models from 15 to 30 tons) generates air flow through the condenser to remove heat from the refrigerant system. The air cooled condenser on the unit will discharge a maximum of 15,000 BTU’s per hour per ton of cooling.
2. The unit must have a minimum entering air temperature of 60°F and a maximum entering air temperature of 95°F for efficient operation.
3. The unit must have a minimum of two feet clearance at the air intake and six feet at the vertical exhaust air discharge.
4. The unit must
have all enclosure panels in place before operating compressor. Air will not be drawn through the condenser coil if they are not in place. This will cause the compressor to lockout on the high pressure safety fault.
1.3 EFFICIENCY
A. Long term efficiency of operation is largely determined by proper
maintenance of the mechanical parts of the unit and the water quality. The Manufacturer recommends filtering where required to prevent solids from plugging critical parts (pumps, heaters, seals for example). The Manufacturer highly recommends the services of a competent water treatment specialist be obtained and his
CF Series Portable Chillers with CF-1 Instrument
Page: 9
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
recommendations followed. The Manufacturer accepts no responsibility for inefficient operation, or damage caused by foreign materials or failure to use adequate water treatment.
1.4 SAFETY
A. It is important to become thoroughly familiar with this manual and
the operating characteristics of the unit.
B. It is the owner’s responsibility to assure proper operator training,
installation, operation, and maintenance of the unit.
C. Observe all warning and safety placards applied to the chiller.
Failure to observe all warnings can result in serious injury or death to the operator and severe mechanical damage to the unit.
1.5 CLEAN AIR ACT
A. The unit contains HCFC-22 (chlorodifloromethane). This is a class
2 substance.
B. Effective July 1, 1992, it is unlawful for any person in the course of
maintaining, servicing, repairing, or disposing of refrigeration equipment to knowingly vent or otherwise dispose of any class 2 substance used as a refrigerant in the manner which permits such substance to enter the atmosphere.
C. De minimis releases associated with good faith attempts to
recapture, reclaim or recycle such substance shall not be subject to the prohibition set forth in the preceding paragraph.
1.6 MISCELLANEOUS
A. The unit is designed to circulate temperature stabilized fluid through
the process resulting in process temperature control.
B. The ability of the unit to maintain process temperature control is
significantly affected by the method of installation as outline in section 2 of this manual.
C. If the operator has any questions concerning the location and
operation of the unit, contact the The Manufacturer’s Service Department.
CF Series Portable Chillers with CF-1 Instrument
Page: 10
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
Air-Cooled.
Water-Cooled.
Air-Cooled Model.
Pressure Gauges
Cover Panel
Enclosure Panel
Electrical Panel
Enclosure
Casters
Instrument
Caster
Liquid Receiver
Compressor
Liquid Line Solenoid
Refrigerant Site Glass
Fan Motor
Protective Fan Shroud
Air Discharge
Hot Gas Bypass Valve
Pump
Expansion Valve
Insulated Reservoir Tank
CF Series Portable Chillers with CF-1 Instrument
Page: 11
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
Condenser Water-Out
Connection
Reservoir Make-Up
Connection
Condenser Water-In Connection
(optional)
Condenser Water
Regulator Valve
From Process Connection
Reservoir
Optional Reservoir Sight Glass
To Process Connection
Pump
Caster
Condenser
Electrical Panel
Compressor
Refrigerant Sight Glass
Expansion Valve
Make-Up Valve
Water-Cooled Model.
Page: 12
THIS PAGE INTENTIONALLY BLANK
CF Series Portable Chillers with CF-1 Instrument
Page: 13
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
2.0 INSTALLATION
2.1 GENERAL
2.2 TO AND FROM PROCESS CONNECTIONS
2.3 WATER SUPPLY CONNECTION
2.4 AIR COOLED CONDENSER INSTALLATION
2.5 WATER-COOL CONDENSER INSTALLATION
2.6 ELECTRICAL CONNECTION
CF Series Portable Chillers with CF-1 Instrument
Page: 14
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
2.1 GENERAL
A. All process piping materials (such as hose, rigid piping, valves or
filters) used in process water piping circuitry must be rated for 100°F minimum temperature and 100 PSI minimum pressure.
B. All such materials must have the equivalent or larger diameter of
the particular process connection that length of process water piping is connected to.
2.2 TO AND FROM PROCESS CONNECTIONS
A. Connect the ‘TO PROCESS’ to the ‘water in’ manifold on the mold
or process.
B. Connect the ‘FROM PROCESS’ port to the ‘water out’ port on the
process manifold.
C. Process water piping circuitry should be designed to avoid an
excessive use of elbows and/or lengths of pipe or hose. If hose is the material of choice, avoid tight twists or curls and excessive lengths.
D. Valves and filters may be installed in the process water piping
circuitry to facilitate service and maintenance provided that such devices maintain the full inside diameter of the process connection. If installed, all such devices must be open and clean during unit operation.
Air-cooled model shown.
From Process :
Connect to ‘Water Out’
port on process manifold
Water Make-Up : Connect to plant’s city water source.
To Process :
Connect to ‘Water In’ port
on process manifold
CF Series Portable Chillers with CF-1 Instrument
Page: 15
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
2.3 WATER SUPPLY CONNECTION
A. The automatic water supply make-up system continually monitors
the reservoir tank and fills it when needed. Connect as follows:
1. Connect the chiller’s ‘WATER SUPPLY’ port to the plant’s city water source.
2. Minimum water supply pressure requirement is identified on the equipment data plate. This is normally 20 psi.
3. Be certain to use a water supply line equipped with a back flow prevention device to prevent contamination of potable water.
2.4 AIR COOLED CONDENSER
A. Air-cooled condensers require ambient air temperatures between
60°F and 95°F for efficient operation. Operating above 95°F may result in elevated condensing pressures and eventual shut-down on the high pressure safety switch. In such cases, a water assist unit may be necessary for operations. Air temperatures below 60°F may result in below normal condensing pressures and poor condensing. In such cases, a low-ambient damper assembly is required. Check with the Manufacturer’s service department for more information on operating with ambients air temperatures above 95°F or below 60°F.
Water-Cooled model shown.
To Process Connection
From Process Connection
Water Supply Connection
Condenser Water-Out Connection
Condenser Water-In Connection (with optional water regulator valve)
CF Series Portable Chillers with CF-1 Instrument
Page: 16
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
B. Air flow is generated by the motor
mounted fans (figure 2.4A) or centrifugal blowers (figure 2.4B). Air flow is from the outside of the chiller, through the condenser and exhausted through the top of the unit. On centrifugal blowers models, exhaust air can be ducted outside of the plant’s interior environment. Special duct work is required and a HVAC contractor should be consulted for sizing and material specifications. Exhaust air can not be ducted on motor mounted fan models.
C. A free air space of at least two (2)
feet is required at the condenser intake and six (6) feet at the condenser discharge to allow for proper air flow.
D. At full load, the chiller will discharge
approximately 15,000 BTU’s per hour per ton of cooling.
E. On blower units, air discharge
duct work should be sized by a qualified HVAC engineer. Sizing shall be according to rated CFM at the static pressure of .90 inches of water. See figure 2.4C at right.
F. On blower units, a damper
control assembly is required in low ambient temperature areas or when outdoor air make-up is used. The assembly works in conjunction with refrigerant head pressure to regulate air flow to maintain proper refrigerant head pressure when condenser intake air temperature will be less than 60°F. See figure 2.4D to the right.
Figure 2.4A
Typical fan assembly
Figure 2.4B
Typical blower assembly
Figure 2.4C
Figure 2.4D
CF Series Portable Chillers with CF-1 Instrument
Page: 17
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
G. All air cooled units must have all enclosure panels in place before
operating compressor. Air will not be drawn through the condenser coil if they are not in place. This will cause the compressor to lockout on the high pressure safety fault.
2.5 WATER-COOLED CONDENSER
A. Connect the ‘CONDENSER WATER
IN’ port to the plant’s city water
supply or tower system supply.
1. Required consumption from a city water source is 1.5 gpm at 65°F per ton of rated capacity.
2. Required consumption for a tower water source is 3 gpm at 85°F per ton of rated capacity.
B. Connect the chiller’s ‘CONDENSER WATER OUT’ port to the
plant’s drain or tower system return.
1. Note: if dumping to the plant’s open drain, drainage shall be done according to local codes.
C. The pressure differential requirement between the condenser “water
in” and the condenser “water out” lines must be 30 psi for adequate efficiency.
D. The installation of a strainer in the
condenser “water in” line is recommended. This removes solids from the water supply and serves to protect the water saver (regulator) valve.
E. The water saver (regulator) valve
(figure 2.5B) is located in the condenser “water in” line. During winter months, or cold seasons, the valve will throttle the water flow through the condenser. The amount of flow is based on the refrigerant head pressure and the regulator will modulate the valve orifice to maintain 100° - 105°F condensing temperature for best efficiency*.
Figure 2.5A
Typical condenser connections ­30 ton unit
Figure 2.5B
Optional Regulator Valve
* See Temperature-Pressure
chart in Section 8.5 for
refrigerant pressure.
CF Series Portable Chillers with CF-1 Instrument
Page: 18
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
2.5 ELECTRICAL CONNECTION
A. NEMA 1 MODELS
1. Electrical power supply requirements for Nema 1 units are
identified on the equipment data plate. Determine the plant’s voltage supply is the same as the unit’s voltage requirements.
WARNING: Do not connect the unit to a voltage supply not equal to the unit’s voltage requirements as specified on the unit’s data plate. Use of incorrect voltage will void the unit’s warranty and cause a significant hazard that may result in serious personal injury and unit damage.
2. A customer supplied, four conductor cable is required for
connection to a customer supplied fused disconnecting means. The fused disconnecting means shall be sized and installed according to the unit’s power supply requirements and local electrical codes.
3. Connect the four conductor power cable to power entry terminal block on the unit’s electrical panel. Then connect the power cable to the fused disconnect switch.
B. NEMA 12 MODELS
1. NEMA 12 units are constructed with a dust tight electrical
enclosure and branch circuit fusing. Electrical power supply requirements are identified on the equipment data plate. Determine the plant’s voltage supply is the same as the unit’s voltage requirements.
WARNING: Do not connect the unit to a voltage supply source not equal to the unit’s voltage requirements as specified on the unit’s data plate. Use of incorrect voltage will void the unit’s warranty and cause a significant hazard that may result in serious personal injury and unit damage.
2. Appropriate conduit and fittings should be selected which
will maintain the integrity of the cabinet.
3. Supply a power conductor sized according to the unit’s power supply requirements. Connect the power conductor to the unit’s power supply entry terminal block or the fused disconnect switch. Some Nema 12 models may be supplied with an optional disconnect switch. The owner supplied fused disconnecting means shall be sized and installed according to the unit’s power supply requirements and local electrical codes.
C. CONTROL CIRCUIT WIRING
1. The unit’s supplied control circuit is 110 volt, 1 phase, 60
cycle. The control circuit is supplied by the factory installed transformer. An inline control circuit fuse is provided.
CF Series Portable Chillers with CF-1 Instrument
Page: 19
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
D. GENERAL
1. Make certain all ground connections to the unit are properly
affixed.
2. Make certain power conductor, disconnecting means, and fusing are properly sized according to the unit’s power supply requirements.
E. INFORMATION REGARDING ‘PHASING’ OF SCROLL
COMPRESSORS
1. All portable chillers that have pumps, the compressor(s) will
be set in phase with the pump during the testing process at the factory.
2. After installation the phase status must be checked by observing the pump motor shaft on the end of the pump and comparing its rotation to the directional arrow on the motor. In either case, if the phase needs to be altered, it should be done at the main power entry.
Figure 2.5A Typical electrical panel
Refrigerant High Pressure Limit
(protects from excessive condensing pressures)
Refrigerant Low Pressure Limit
(protects from low suction pressures)
Motor Contractor
(supplies voltage to coolant pump motor)
Motor Overload Relay
(protects motor from excessive amperage)
Transformer
(provides different voltages to instrument and other components)
Power Entry
(connect to power cord ­grounding lug on panel)
Compressor Contactor
(supplies voltage to compressor)
Page: 20
THIS PAGE INTENTIONALLY BLANK
CF Series Portable Chillers with CF-1 Instrument
Page: 21
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Website: www.Temptek.com
Email: service@Temptek.com
3.0 OPERATIONS
3.1 GENERAL
3.2 START UP/OPERATIONS PROCEDURE
3.3 INSTRUMENT
3.4 SHUT DOWN
Loading...
+ 49 hidden pages