Tempstar N4A3, C4A3, T4A3, NXA6, H4A3 Installation Instructions Manual

...
Page 1
INSTALLATION INSTRUCTIONS
R−410A Split System Air Conditioner
N4A3, C4A3, H4A3, T4A3, NXA6, CXA6, HXA6, TXA6
These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product.
DANGER − Immediate hazards which will result in severe personal injury or death.
WARNING − Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION − Hazards or unsafe practices which may result in minor personal injury or product or
property damage.
NOTE − Used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
WARNING
!
The signal word CAUTION is used throughout this manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures on product labels.
WARNING
CAUTION
TABLE OF CONTENTS
Inspect New Unit 2...............................
Safety Considerations 2...........................
Location 2.......................................
Clearances 2 − 3................................
Unit Support 4...................................
Refrigeration System 5 − 9.......................
Electrical Wiring 10 − 11..........................
Start−up Procedure 12............................
Refrigerant Charge 12 − 15.......................
Sequence of Operation 16.........................
Troubleshooting 16...............................
Maintenance 16..................................
Comfort Alertt Diagnostics Codes 17..............
R−410A Quick Reference Guide 18.................
!
DEATH, PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death.
Installation or repairs made by unqualified per­sons could result in equipment malfunction, property damage, personal injury and/or death.
The information contained in this manual is in­tended for use by a qualified service technician fa­miliar with safety procedures and equipped with the proper tools and test instruments.
Installation must conform with local building codes and with the National Electrical Code NFPA70 current edition or Canadian Electrical Code Part 1 CSA C.22.1.
WARNING
421 01 5103 00 May 2010
Page 2
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
INSPECT NEW UNIT
After uncrating unit, inspect thoroughly for hidden damage. If damage is found, notify the transportation
SAFETY CONSIDERATIONS
Consult a qualified installer, service agency, or the dealer/distributor for information and assistance. The qualified installer must use factory authorized kits and accessories when modifying this product. Refer to the individual instructions packaged with the kit or accessory when installing.
The weight of the product requires careful and proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use a heat sinking material − such as a wet rag − during brazing operations. Keep a fire extinguisher available. Consult local codes and the National Electric Code (NEC) for special requirements.
Improper installation, adjustment, alteration, service or maintenance can void the warranty.
company immediately and file a concealed damage claim.
!
ELECTRICAL SHOCK HAZARD
Failure to turn off the main (remote) electrical dis­connect device could result in personal injury or death.
Before installing, modifying or servicing system, turn OFF the main (remote) electrical disconnect device. There may be more than one disconnect device. Lock out and tag switch with a suitable warning label.
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in proper­ty damage
R−410A systems operate at higher pressures than R−22 systems. When working with R−410A sys­tems, use only service equipment and replace­ment components specifically rated or approved for R−410A service.
WARNING
CAUTION
LOCATION
Check local codes for regulations concerning zoning, noise, platforms, and other issues.
Locate unit away from fresh air intakes, vents, or bedroom windows. Noise may carry into the openings and disturb people inside.
Locate unit in a well drained area, or support unit high enough so that water runoff will not enter the unit.
Locate unit away from areas where heat, lint, or exhaust fumes will be discharged onto unit (as from dryer vents).
CLEARANCES
Nominal minimum clearances are 48 inches (1.2m) above unit for discharge air and 18 inches (457mm) on each side of the coil for intake air. Clearance on any one side of the coil (normally between unit and structure) may be reduced to 6 inches (152mm). Nominal minimum clearances are based on a solid parallel object such as a wall or roof overhang.
The clearance may be reduced for a single object with small surface area, such as the end of a wall, outside corner of a wall, fence section, post, etc. As a general rule, the minimum clearance from the unit should equal the width of the object. For example, a 6 inch (152mm) fence post should be a minimum of 6 inches (152mm) from the unit.
Locate unit away from recessed or confined areas where recirculation of discharge air may occur (refer to CLEARANCES section of this document).
Roof−top installation is acceptable providing the roof will support the unit and provisions are made for water drainage and noise/vibration dampening.
NOTE: Roof mounted units exposed to wind may require wind baffles. Consult the manufacturer for additional information.
Do not install unit under roof overhangs unless gutters are present. A minimum vertical clearance of 48 inches (1.2m) is required to the overhang.
Inside corner locations on single story structures require evaluation. Large overhanging soffits may cause air recirculation in a corner area even though recommended minimum clearances are maintained. As a guide, locate the unit far enough out so that half of the discharge grille is out from under the soffit.
When placing two or more units side−by−side, provide a minimum of 18 inches (457mm) between units.
Provide minimum service clearance of 24 inches (610mm) from control box corner and side service panel.
Refer to Figure 1.
2 421 01 5103 00
Page 3
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
Figure 1 Clearances (various examples)
24”
(610mm)
Service
Wall
6”
(152mm)
18”
(457mm)
Wall
6”
(152mm)
18”
(457mm)
18”
(457mm)
Wall
24”
(610mm)
Service
Wall
6”
(152mm)
18”
(457mm)
Wall
6”
(152mm)
24”
(610mm)
Service
18”
(457mm)
24”
(610mm)
Service
4”
(102mm)
(457mm)
18”
(152mm)
18”
(102mm)
wide fence
Wall
24”
(610mm)
Service
4”
24”
(610mm)
Service
18”
(457mm)
18”
(457mm)
6”
(152mm)
6”
(152mm)
Post
24”
(610mm)
Service
18”
(457mm)
421 01 5103 00 3
Page 4
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
UNIT SUPPORT
NOTE: Unit must be level | 2 degrees {a inch rise or fall
per foot of run (10mm rise or fall per 305 mm of run) }or compressor may not function properly.
A. GROUND LEVEL INSTALLATION
The unit must be level and supported above grade by beams, platform, or a pad. Platform or pad can be of open or solid construction but should be of permanent materials such as concrete, bricks, blocks, steel, or pressure− treated timbers approved for ground contact. Soil conditions must be considered so that the platform or pad does not shift or settle and leave the unit partially supported. Minimum pad dimensions are shown in Figure 2.
If beams or an open platform are used for support, it is recommended that the soil be treated or area be graveled to reduce the growth of grasses and weeds.
To minimize vibration or noise transmission, it is recommended that supports not be in contact with the building structure. However, slabs on grade constructions with an extended pad are normally acceptable.
B. ROOF TOP INSTALLATION
This type of installation is not recommended on wood frame structures where low noise levels are required.
Supporting structure or platform for the unit must be level. If installation is on a flat roof, locate unit minimum 6 inches (152mm) above roof level.
Place the unit over one or more load bearing walls. If there are several units, mount them on platforms that are self−supporting and span several load bearing walls. These suggestions are to minimize noise and vibration transmission through the structure. If the structure is a home or apartment, avoid locating the unit over bedrooms or study.
NOTE: When unit is to be installed on a bonded guaranteed roof, a release must be obtained from the building owner to free the installer from all liabilities.
C. FASTENING UNIT DOWN
If conditions or local codes require the unit be attached in place, remove the knockouts in the base pan and install tie down bolts through the holes (refer to Figure 2).
Contact local distributor for hurricane hold−down details and the P.E. (Professional Engineer) certification, when required.
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in proper­ty damage.
Inadequate unit support may cause excessive vibration, noise, and/or stress on the refrigerant lines, leading to refrigerant line failure.
Figure 2 Tie Down Knockouts
a” (10mm) dia. Tie Down Knockouts In Base Pan (2 places)
A
Base Pan Width
View From Top
Base
Pan
Depth
C
B
Inches (mm)
Base Pan
Width x Depth
@# ~ @#
(584 x 584)
@%n ~ @%n
(652 x 652)
#!8 ~ #!8
(791 x 791)
#$, ~ #$,
(887 x 887)
Tie Down
Knockouts
A B C
&w
(197)$v(113)!*(457)
(z
(230)$v(113)
(z
(230)^2(165)
(z
(230)^2(165)
@!4
(540)
@$s
(625)
@*v
(722)
Minimum
Mounting Pad
Dimensions
@# X~ @#
(584 x 584)
@^ X~ @^
(660 x 660)
#!2 ~ #!2
(800 x 800)
#% ~ #%
(889 x 889)
4 421 01 5103 00
Page 5
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
REFRIGERATION SYSTEM
A. COMPONENT MATCHES
Check to see that the proper system components are in place, especially the indoor coil.
R−410A outdoor units can only be used with R−410A specific indoor coils. If there is a refrigerant mis−match, consult the indoor coil manufacturer to determine if a refrigerant conversion kit is available for the indoor coil.
This outdoor unit is designed for use only with indoor coils that utilize a TXV refrigerant metering device or Piston with Teflon ring metering device. If any other type of metering device is installed on the indoor coil, consult the indoor coil manufacturer to determine if a TXV conversion kit is available.
Installing with TXV
When installing a TXV on an indoor coil, follow the instructions provided with the new TXV.
A typical TXV installation is shown in Figure 3.
Figure 3 Typical TXV Installation
Installing with Indoor Piston − cooling operation.
Check piston size shipped with indoor unit to see if it matches required indoor piston size.
If it does not match, replace indoor piston with correct piston size. (Indoor pistons are shipped with some outdoor models in the accessory bag and are only qualified for Piston fan coils.)
Example fan coils with piston: FEM4P, FSM4P, FSU4P (12 thru 4 ton).
See Figure 4. When changing indoor piston, use a back−up wrench.
Hand tighten hex nut, then tighten with wrench 1/2 turn. Do not exceed 30 ft−lbs.The indoor piston contains a Teflon ring (or seal) which is used to seat against the inside of distributor body, and must be installed properly to ensure proper seating in the direction for cooling operation.
Figure 4 Indoor (cooling) Piston
BRASS
HEX NUT
TEFLON SEAL
TEFLON RING
DISTRIBUTOR
EQUALIZER TUBE
SENSING BULB
TXV
10 O’Clock
7/8
2 O’Clock
SUCTION TUBE
IN. OD & SMALLER
INDOOR
COIL
STRAP
SUCTION TUBE
LIQUID TUBE
SENSING BULB
PISTON
FLOW IN COOLING
PISTON RETAINER
STRAINER
BRASS HEX BODY
L10S017
!
PRODUCT OPERATION HAZARD
Failure to follow this caution may result in improper product operation. If using a TXV in conjunction with a single−phase reciprocat­ing compressor, a compressor start capacitor and relay are required. Consult outdoor unit pre−sale literature for start as­sist kit part number.
CAUTION
421 01 5103 00 5
Page 6
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
B. REFRIGERANT LINE SETS
The refrigerant line set must be properly sized to assure maximum efficiency and proper oil circulation.
Refer to Product Specifications and Long Line Applications Guideline for line set sizing.
NOTE: Total line set length must not exceed 200 feet
(61m). A crankcase heater must be used when the refrigerant
line length exceeds 80 feet (24.4m). If outdoor unit is more than 10 feet (3m) higher than the
indoor coil, refer to the Long Line Applications Guideline for instructions.
When the outdoor unit is higher than the indoor coil, the vertical separation must not exceed 100 feet (30m).
When the outdoor unit is lower than the indoor coil, the vertical separation must not exceed 50 feet (15.2m).
If it is necessary to add refrigerant line in the field, use dehydrated or dry, sealed, deoxidized, copper refrigeration tubing. Do not use copper water pipe.
Do not remove rubber plugs or caps from copper tubing until connections are ready to be made.
Be extra careful when bending refrigeration tubing. Tubing can “kink” easily, and if this occurs, the entire length of tubing must be replaced.
!
WARNING
PERSONAL INJURY HAZARD
Failure to relieve system pressure could result in personal injury and/or death.
Relieve pressure and recover all refrigerant be­fore servicing existing equipment, and before fi­nal unit disposal. Use all service ports and open all flow−control devices, including solenoid valves.
C. ROUTING AND SUSPENDING REFRIGERANT
LINES
Run refrigerant lines as straight and direct as possible, avoiding unnecessary bends and turns. Always insulate the entire suction line. Both lines should be insulated when routed through an attic or when routed through an underground raceway.
When routing refrigerant lines through a foundation or wall, do not allow refrigerant lines to come in direct contact with the building structure. Make openings large enough so that lines can be wrapped with extra insulation. Fill all gaps with RTV caulk. This will prevent noise transmission between the tubing and the foundation or wall.
Along floor or ceiling joists, suspend refrigerant lines so that they do not contact the building structure, water pipes, or ductwork. Use insulated or suspension type hangers. Metal straps must be at least 1” (25mm) wide to avoid cutting into the tube insulation. Keep the liquid and suction lines separate. Refer to Figure 5.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in im­proper product operation.
Do not leave system open to atmosphere any lon­ger than absolutely required for installation. Inter­nal system components − especially refrigerant oils − are extremely susceptible to moisture con­tamination. Keep ends of tubing sealed during installation until the last possible moment.
Figure 5 Routing and Suspending Refrigerant Lines
OUTDOOR WALL INDOOR WALL
CAULK
INSULATION
THROUGH THE WALL SUSPENSION
LIQUID TUBE
SUCTION TUBE
HANGER STRAP
(AROUND SUCTION
TUBE ONLY)
1” (25mm)
MIN
JOIST
INSULATION
SUCTION TUBE
LIQUID TUBE
6 421 01 5103 00
Page 7
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
refrigerant charge sealed in the unit. Leave the service
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in im­proper product operation.
Do not bury more than 36” (1m) of line set under­ground. Refrigerant may migrate to cooler buried section during extended periods of unit shut− down, causing refrigerant slugging and possible compressor damage at start−up. If ANY section of the line set is buried under­ground, provide a minimum 6” (152mm) vertical rise at the service valve.
D. OUTDOOR UNIT HIGHER THAN INDOOR UNIT
Proper oil return to the compressor should be maintained with suction gas velocity. If velocities drop below 1500 fpm (feet per minute), oil return will be decreased. To maintain suction gas velocity, do not upsize vertical suction risers.
E. LIQUID LINE FILTER−DRIER
Outdoor units are shipped with an appropriate filter−drier for installation in the liquid line. Leave the plugs in the tube ends until the filter−drier is installed. The optimal location for the filter−drier is close to the indoor coil. Install the filter−drier with the arrow pointing towards the indoor coil. Refer to Figure 6.
CAUTION
valves closed until all other refrigerant system work is complete or the charge will be lost. Leave the plugs in place until line set tubing is ready to be inserted.
Service valve bodies are brass and tube stubs are copper.
Figure 7 Service Valve
VALVE CORE
G. BRAZING CONNECTIONS NOTE: Remove valve core from schrader port on both
Service Valves BEFORE brazing. This helps prevent overheating and damage to valve seals (refer to Figure 7). Replace valve core when brazing is completed.
!
WARNING
SERVICE VALVE
Figure 6
Filter−Drier (arrow points towards indoor coil)
F. SERVICE VALVES
Service valves are closed and tube stubs are plugged from the factory. Outdoor units are shipped with a
Liquid Line Filter−Drier
Installed at Indoor Coil
38−11 −84
FIRE HAZARD
Failure to remove refrigerant and oil charge be­fore brazing could result in personal injury, death, and/or property damage.
Refrigerant and oil mixture could ignite and burn as it escapes and contacts brazing torch. Make sure the refrigerant charge is properly removed from both the high and low sides of the system be­fore brazing any component or lines.
Clean line set tube ends with emery cloth or steel brush. Remove any grit or debris.
Insert line set tube ends into service valve tube stubs.
Apply heat absorbing paste or heat sink product between service valve and joint. Wrap service valves with a heat sinking material such as a wet cloth.
Braze joints using a Sil−Fos or Phos−copper alloy.
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product dam­age.
Braze with Sil−Fos or Phos−copper alloy on cop­per−to−copper joints and wrap a wet cloth around rear of fitting to prevent damage to TXV.
CAUTION
421 01 5103 00 7
Page 8
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
H. EVACUATING LINE SET AND INDOOR COIL
The unit is shipped with a factory refrigerant charge. The liquid line and suction line service valves have been closed after final testing at the factory. Do not disturb these valves until the line set and indoor coil have been evacuated and leak checked, or the charge in the unit may be lost.
NOTE: Do not use any portion of the factory charge for purging or leak testing. The factory charge is for filling the system only after a complete evacuation and leak check has been performed.
!
CAUTION
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product dam­age.
Never use the outdoor unit compressor as a vacu­um pump. Doing so may damage the compressor.
Line set and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. If deep vacuum equipment is not available, the alternate triple evacuation method may be used by following the specified procedure.
If vacuum must be interrupted during the evacuation procedure, always break vacuum with dry nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum to 500 microns and a vacuum gauge capable of accurately measuring this vacuum level. The deep vacuum method is the most positive way of assuring a system is free of air and water.
Watch the vacuum gauge as the system is pulling down. The response of the gauge is an indicator of the condition of the system (refer to Figure 8).
With no leaks in the system, allow the vacuum pump to run for 30 minutes minimum at the deep vacuum level.
Triple Evacuation Method
The triple evacuation method should only be used when system does not contain any water in liquid form and vacuum pump is only capable of pulling down to 28 inches of mercury (711mm Hg). Refer to Figure 9 and proceed as follows:
1. Pull system down to 28 inches of mercury (711mm Hg) and allow pump to continue operating for an additional 15 minutes.
2. Close manifold valves or valve at vacuum pump and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and fill with nitrogen until system pressure is 2 psig.
4. Close nitrogen valve and allow system to stand for 1 hour. During this time, dry nitrogen will diffuse throughout the system absorbing moisture.
5. Repeat this procedure as indicated in Figure 8.
6. After the final evacuate sequence, confirm there are no leaks in the system. If a leak is found, repeat the entire process after repair is made.
Figure 9 Triple Evacuation Sequence
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
Figure 8
5000
4500
4000
3500
3000
2500
2000
MICRONS
1500
1000
500
Deep Vacuum Gauge Response
and System Conditions
01
246
375
MINUTES
LEAK IN SYSTEM
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
CHARGE SYSTEM
8 421 01 5103 00
Page 9
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
I. OPENING SERVICE VALVES
Outdoor units are shipped with a refrigerant charge sealed in the unit. Opening the service valves releases this charge into the system.
NOTE: Open the Suction service valve first. If the Liquid service valve is opened first, oil from the compressor may be drawn into the indoor coil TXV, restricting refrigerant flow and affecting operation of the system.
Remove Suction service valve cap and insert a hex wrench into the valve stem. Hold the valve body steady with an end−wrench and back out the stem by turning the hex wrench counterclockwise. Turn the stem until it just contacts the rolled lip of the valve body.
After the refrigerant charge has bled into the system, open the Liquid service valve.
NOTE: These are not back−seating valves. It is not necessary to force the stem tightly against the rolled lip.
The service valve cap is a primary seal for the valve and must be properly tightened to prevent leaks. Make sure cap is clean and apply refrigerant oil to threads and sealing surface on inside of cap.
Tighten cap finger tight and then tighten additional 6 of a turn (1 wrench flat) to properly seat the sealing surfaces.
J. GAUGE PORTS
Check for leaks at the schrader ports and tighten valve cores if necessary. Install plastic caps finger tight.
421 01 5103 00 9
Page 10
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
ELECTRICAL WIRING
Wiring Connections
!
ELECTRICAL SHOCK HAZARD
Failure to turn off the main (remote) electrical dis­connect device could result in personal injury or death.
Before installing, modifying or servicing system, turn OFF the main (remote) electrical disconnect device. There may be more than one disconnect device.
The supply voltage must be 208/230 volts (197 volt minimum to 253 volts maximum) 60 Hz single phase.
Outdoor units are approved for use with copper conductors only. Do not use aluminum wire.
Refer to unit rating plate for minimum circuit ampacity and circuit protection requirements.
Grounding
Permanently ground unit in accordance with the National Electrical Code and local codes or ordinances. Use a copper conductor of the correct size from the grounding lug in control box to a grounded connection in the service panel or a properly driven and electrically grounded ground rod.
WARNING
Make all outdoor electrical supply (Line Voltage) connections with raintight conduit and fittings. Most codes require a disconnect switch outdoors within sight of the unit. Consult local codes for special requirements.
Route electrical supply (Line Voltage) wiring through knockout hole in bottom of Control Box. Connect wires to Contactor and Ground Lug according to Wiring Diagram on unit. Refer to Figure 10.
Route thermostat wiring through rubber grommet in bottom of Control Box. Low voltage lead wires are provided in the control box for connection to thermostat wires (use wire nuts). Refer to Wiring Diagram on unit and Figure 11 for low voltage wiring examples.
NOTE: Use No. 18 AWG (American Wire Gage) color−coded, insulated (35 ° C minimum) wire. If thermostat is located more than 100 feet (31 m) from unit as measured along the control voltage wires, use No. 16 AWG color−coded wires to avoid excessive voltage drop.
NOTE: Some models are factory equipped with Comfort Alertt Diagnostics device. If Comfort Alert is used as a field installed option, then a hot bundle must be run for proper connection.
Figure 10 Electrical Supply (Line Voltage) Connections
DISCONNECT
PER NEC AND/OR
LOCAL CODES
CONTACTOR
11
23 or 13
LUG
FIELD POWER
WIRING
FIELD GROUND
WIRING
L1
L2
GROUND
10 421 01 5103 00
Page 11
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
Figure 11 Typical Thermostat Connections
THERMOSTAT FURNACE
24 VAC HOT
24 VAC COM
COOL STAGE 1
INDOOR FAN
THERMOSTAT FAN COIL
24 VAC HOT
24 VAC COM
COOL STAGE 1
INDOOR FAN
R
C
W/W1
Y/Y2
G
R
C
W/W1
Y/Y2
G
R
C
WHEAT STAGE 1
Y
G
R
C
W2HEAT STAGE 1
Y
G
AIR CONDITIONER
C
AIR CONDITIONER
C
THERMOSTAT FAN COIL
24 VAC HOT
24 VAC COM
HEAT STAGE 1
COOL STAGE 1
INDOOR FAN
R
C
W/W1
Y/Y2
G
R
C
W2
Y
G
AC with Comfort Alert
C
Y
421 01 5103 00 11
Page 12
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
START−UP PROCEDURE
1. Set indoor thermostat selector switch to OFF.
2. Turn ON all electrical disconnect devices.
3. If unit has a crankcase heater, energize the heater and wait 24 hours before proceeding.
REFRIGERANT CHARGE
Factory charge amount and desired subcooling are shown on unit rating plate. Charging method is shown on information plate inside unit.
For TXV, use subcooling method. For Piston, use superheat method. To properly check or adjust charge, conditions must be
favorable for subcooling or superheat charging. Favorable conditions exist when the outdoor temperature is between 70_F and 100_F (21_C and 38_C), and the indoor temperature is between 70_F and 80_F (21_C and 27_C). Follow the procedure below.
Unit is factory charged for 15 feet (4.6m) of lineset. Adjust charge by adding or removing 0.6 oz/ft (17 g/mm) of 3/8 liquid line above or below 15 feet (4.6 m) respectively.
For standard refrigerant line lengths 80 feet (24.4m) or less, allow system to operate in cooling mode at least 15 minutes. If conditions are favorable, check system charge by super heat method for fixed metering device and subcooling method for TXV. If any adjustment is necessary, adjust charge slowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system.
4. Set indoor thermostat at desired temperature. Be sure setpoint is below indoor ambient temperature or thermostat will not call for cooling.
5. Set indoor thermostat selector switch to COOL. Operate unit for minimum 15 minutes, then check the system refrigerant charge.
If the indoor temperature is above 80_F (27_C), and the outdoor temperature is in the favorable range, adjust system charge by weight based on line length and allow the indoor temperature to drop to 80_F (27_C) before attempting to check system charge by subcooling method as described above.
If the indoor temperature is below 70_F (21_C), or the outdoor temperature is not in the favorable range, adjust charge for line set length above or below 15 feet (4.6m) only. Charge level should then be appropriate for the system to achieve rated capacity. The charge level could then be checked at another time when the both indoor and outdoor temperatures are in a more favorable range.
NOTE: If line length is beyond 80 feet (24.4m) or greater than 20 feet (6.1m) vertical separation, See Long Line Guideline for special charging requirements.
12 421 01 5103 00
Page 13
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
A. UNITS WITH COOLING MODE TXV
Units installed with cooling mode TXV require charging by the subcooling method.
1. Operate unit a minimum of 15 minutes before checking charge.
2. Measure liquid service valve pressure by attaching an accurate gage to service port.
3. Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liquid line near outdoor coil.
4. Refer to unit rating plate for required subcooling temperature.
5. Refer to Figure 14. Find the point where required subcooling temperature intersects measured liquid service valve pressure.
6. To obtain required subcooling temperature at a specific liquid line pressure, add refrigerant if liquid line temperature is higher than indicated or reclaim refrigerant if temperature is lower. Allow a tolerance of "3_F (|1.7_C).
B. UNITS WITH INDOOR PISTON
Units installed with indoor pistons require charging by the superheat method.
The following procedure is valid when indoor airflow is within "21 percent of its rated CFM.
1. Operate unit a minimum of 15 minutes before checking charge.
2. Measure suction pressure by attaching an accurate gage to suction valve service port.
3. Measure suction temperature by attaching an accurate thermistor type or electronic thermometer to suction line at service valve.
4. Measure outdoor air dry−bulb temperature with thermometer.
5. Measure indoor air (entering indoor coil) wet−bulb temperature with a sling psychrometer.
6. Refer to Figure 12. Find outdoor temperature and evaporator entering air wet−bulb temperature. At this intersection, note superheat. Where a dash (−−) appears on the table, do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighted in, adding or removing 0.6 oz/ft of 3/8 liquid line above or below 15 feet (4.6m) respectively.
7. Refer to Figure 13. Find superheat temperature (from #6 above) and suction pressure. At this intersection, note suction line temperature.
8. If unit has a higher suction line temperature than charted temperature, add refrigerant until charted temperature is reached.
9. If unit has a lower suction line temperature than charted temperature, reclaim refrigerant until charted temperature is reached.
10. When adding refrigerant, charge in liquid form into suction service port using a flow−restricting device.
11. If outdoor air temperature or pressure at suction valve changes, charge to new suction line temperature indicated on chart.
12. Optimum performance will be achieved when the operating charge produces 10_F suction superheat at suction service valve with 95_F (35_C) outdoor ambient and 80_F (27_C) dry bulb (67_F / 19_C) wet bulb) indoor temperature (DOE “A” test conditions) at rated airflow.
421 01 5103 00 13
Page 14
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
Figure 12 Superheat Charging − AC Only
OUTDOOR TEMP (_F)
55 9 12 14 17 20 23 26 29 32 35 37 40 42 45 60 7 10 12 15 18 21 24 27 30 33 35 38 40 43 65
70
75
80
85
90
95
100
105
110
115
*Optimum performance point, 95°F (35°C) outdoor ambient and (80°F / 27°C dry bulb), (67°F / 19°C wet bulb) indoor conditions. (DOE A Test Conditions) Where a dash (--) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in.
Note: Superheat °F is at low-side service port, Allow a tolerance of ± 3°F (± 1.7°C) Note: Indoor dry bulb between 70°F and 80°F (21°C and 27°C)
50 52 54 56 58 60 62 64 67 68 70 72 74 76
—
6 10 13 16 19 21 24 27 30 33 36 38 41
— —
— — —
— — — —
— — — — — —
— — — — — —
— — — — — — —
— — — — — — — —
— — — — — — — —
— — — — — — — — —
— — — — — — — — — —
EVAPORATOR ENTERING AIR TEMPERATURE (_F WB)
7 10 13 16 19 21 24 27 30 33 36 39
6 9 12 15 18 21 24 28 31 34 37
5 8 12 15 18 21 25 28 31 35
8 11 15 19 22 26 30 33
5 9 13 16 20 24 27 31
6 10 14 18 22 25 29
8 12 15 20 23 27
5 9 13 17 22 26
6 11 15 20 25
8 14 18 23
Figure 13 Required Suction−Line Temperature
SUPERHEAT TEMP (_F)
0 35 37 39 41 43 45 47 49 51 2 37 39 41 43 45 47 49 51 53 4 39 41 43 45 47 49 51 53 55 6 41 43 45 47 49 51 53 55 57
8 43 45 47 49 51 53 55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 59 61 63 14 49 51 53 55 57 59 61 63 65 16 51 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69 20 55 57 59 61 63 65 67 69 71 22 57 59 61 63 65 67 69 71 73 24 59 61 63 65 67 69 71 73 75 26 61 63 65 67 69 71 73 75 77 28 63 65 67 69 71 73 75 77 79 30 65 67 69 71 73 75 77 79 81 32 67 69 71 73 75 77 79 81 83 34 69 71 73 75 77 79 81 83 85 36 71 73 75 77 79 81 83 85 87 38 73 75 77 79 81 83 85 87 89 40 75 77 79 81 83 85 87 89 91
107.8 112.2 116.8 121.2 126 130.8 138.8 140.8 145.8
SUCTION PRESSURE AT SERVICE PORT (PSIG)
14 421 01 5103 00
Page 15
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
Figure 14 Rating Plate (required) Subcooling Temperature ° F (° C)
° F (° C) ° F (° C) ° F (° C) ° F (° C) F (° C) F (° C)
Measured Liquid
6 3 8 4 10 6 12 7 14 8 16 9
Pressure (psig)
R−410A Required Liquid Line Temperature ° F (° C)
251 78 26 76 24 74 23 72 22 70 21 68 20 259 80 27 78 26 76 24 74 23 72 22 70 21 266 82 28 80 27 78 26 76 24 74 23 72 22 274 84 29 82 28 80 27 78 26 76 24 74 23 283 86 30 84 29 82 28 80 27 78 26 76 24 291 88 31 86 30 84 29 82 28 80 27 78 26 299 90 32 88 31 86 30 84 29 82 28 80 27 308 92 33 90 32 88 31 86 30 84 29 82 28 317 94 34 92 33 90 32 88 31 86 30 84 29 326 96 36 94 34 92 33 90 32 88 31 86 30 335 98 37 96 36 94 34 92 33 90 32 88 31 345 100 38 98 37 96 36 94 34 92 33 90 32 364 104 40 102 39 100 38 98 37 96 36 94 34 374 106 41 104 40 102 39 100 38 98 37 96 36 384 108 42 106 41 104 40 102 39 100 38 98 37 395 110 43 108 42 106 41 104 40 102 39 100 38 406 112 44 110 43 108 42 106 41 104 40 102 39 416 114 46 112 44 11 0 43 108 42 106 41 104 40 427 116 47 114 46 11 2 44 110 43 108 42 106 41 439 118 48 116 47 11 4 46 112 44 11 0 43 108 42 450 120 49 118 48 11 6 47 114 46 11 2 44 110 43 462 122 50 120 49 118 48 116 47 114 46 11 2 44 474 124 51 122 50 120 49 11 8 48 11 6 47 114 46
421 01 5103 00 15
Page 16
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
SEQUENCE OF OPERATION
With power supplied to indoor and outdoor units, transformer is energized.
On a call for cooling, the thermostat makes circuits R−Y and R−G. Circuit R−Y energizes contactor, starting outdoor fan motor and compressor. Circuit R−G energizes indoor unit blower relay, starting indoor blower motor.
TROUBLESHOOTING
Some models are factory equipped with the Comfort Alertt Diagnostics device in the control box (refer to Figure 15). Comfort Alert provides around−the−clock monitoring for common electrical problems, compressor defects, and broad system faults. If trouble is detected, an alert code is displayed with a flashing LED indicator. Alert codes are listed in Figure 16.
The device is factory wired and requires no modification. Low voltage lead wires are provided in the
control box for connection to thermostat wires (use wire nuts).
The Comfort Alert device operates by monitoring the compressor power leads and the thermostat demand signal (Y terminal).
When thermostat is satisfied, its contacts open, de−energizing contactor and blower relay. Compressor and motors stop.
NOTE: If indoor unit is equipped with a time−delay relay circuit, the blower runs an additional length of time to increase system efficiency.
Figure 15
Comfort Alertt Diagnostics
(some models)
Compressor Wires Pass Through Holes (3)
24 VAC Common
Thermostat Demand
MAINTENANCE
Condensate Drain
During the cooling season, check monthly for free flow of drainage and clean if necessary.
Cleanliness
These tips will help keep the air conditioner looking better and working more efficiently:
1. Free flow of air is essential. Keep fences, shrubs, trash cans, and other obstructions at least 18 inches (457mm) from all coil inlets.
2. Keep the coil free of grass clippings, leaves, weeds, and other debris. NOTE: Coil may occasionally require cleaning with a liquid solution. The coil must be cold when cleaning. Use an alkaline based cleaner only. Cleaning a hot coil or using an acid based cleaner will remove the paint from the fins and may clog the coil.
3. Never use a weather cover over the outdoor unit unless it is a ventilated type or made of breathable fabric that will allow moisture to evaporate rapidly. A cover that holds moisture in the unit will cause more rust build−up and damage than normal exposure to weather.
16 421 01 5103 00
Page 17
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
Figure 16 Comfort Alertt Diagnostics (some models)
Status LED Status LED Description Status LED Troubleshooting Information Green “POWER” Module has power Supply voltage is present at module terminals Red “TRIP” Thermostat demand signal
Y1 is present, but the compressor is not running
1. Compressor protector is open
2. Outdoor unit power disconnect is open
3. Compressor circuit breaker or fuse(s) is open
4. Broken wire or connector is not making contact
5. Low pressure switch open if present in system
6. Compressor contactor has failed open
Yellow “ALERT” Flash Code 1
Long Run Time
Compressor is running extremely long run cycles
1. Low refrigerant charge
2. Evaporator blower is not running
3. Evaporator coil is frozen
4. Faulty metering device
5. Condenser coil is dirty
6. Liquid line restriction (filter drier blocked if present in system)
7. Thermostat is malfunctioning
Yellow “ALERT” Flash Code 2
Yellow “ALERT” Flash Code 3
System Pressure Trip
Discharge or suction pressure out of limits or compressor overloaded
Short Cycling
Compressor is running only briefly
1. High head pressure
2. Condenser coil poor air circulation (dirty, blocked, damaged)
3. Condenser fan is not running
4. Return air duct has substantial leakage
1. If high pressure switch open, go to Flash Code 2 information
2. If low pressure switch open, go to Flash Code 1 information
3. Thermostat demand signal is intermittent
4. Loose wiring at contactor coil
Yellow “ALERT” Flash Code 4
Locked Rotor
1. Run capacitor has failed
2. Low line voltage (contact utility if voltage at disconnect is low)
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
Yellow “ALERT” Flash Code 5
Open Circuit
1. Outdoor unit power disconnect is open
2. Compressor circuit breaker or fuse(s) is open
3. Compressor contactor has failed open
4. High pressure switch is open and requires manual reset
5. Open circuit in compressor supply wiring or connections
6. Unusually long compressor protector reset time due to extreme ambient temperature
7. Compressor windings are damaged
Yellow “ALERT” Flash Code 6
Open Start Circuit
Current only in run circuit
1. Run capacitor has failed
2. Open circuit in compressor start wiring or connections
3. Compressor start winding is damaged
Yellow “ALERT” Flash Code 7 Yellow “ALERT” Flash Code 9
Open Run Circuit
Current only in start circuit
Low Voltage
Control circuit < 17VAC
1. Open circuit in compressor run wiring or connections
2. Compressor run winding is damaged
1. Control circuit transformer is overloaded
2. Low line voltage (contact utility if voltage at disconnect is low)
S Flash Code number corresponds to a number of LED flashes, followed by a pause and then repeated. S TRIP and ALERT LEDs flashing at same time means control circuit voltage is too low for operation.
421 01 5103 00 17
Page 18
INSTALLATION INSTRUCTIONS R−410A Split System Air Conditioner
R−410A QUICK REFERENCE GUIDE
• R−410A refrigerant operates at 50% − 70% higher pressures than R−22. Be sure that servicing equipment and replacement components are designed to operate with R−410A.
• R−410A refrigerant cylinders are rose colored.
• Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
• R−410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the
manifold hose.
• Manifold sets should be 750 psig high−side and 200 psig low−side with 520 psig low−side retard.
• Use hoses with 750 psig service pressure rating.
• Leak detectors should be designed to detect HFC refrigerant.
• R−410A, as with other HFC refrigerants, is only compatible with POE oils.
• Vacuum pumps will not remove moisture from oil.
• Do not use liquid line filter−driers with rated working pressures less than 600 psig.
• Do not install a suction line filter−drier in liquid line.
• POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
• POE oils may cause damage to certain plastics and roofing materials.
• Wrap all filter−driers and service valves with wet cloth when brazing.
• A liquid line filter−drier is required on every unit.
• Do not use with an R−22 TXV.
• If indoor unit is equipped with an R−22 TXV, it must be changed to an R−410A TXV.
• Never open system to atmosphere while it is under a vacuum.
• When system must be opened for service, break vacuum with dry nitrogen and replace all filter−driers.
• Do not vent R−410A into the atmosphere.
• Do not use capillary tube indoor coils.
• Observe all WARNINGS, CAUTIONS, NOTES, and bold text.
18 421 01 5103 00
International Comfort Products, LLC
Lewisburg, TN 37091 USA
Loading...