Temprite Industries CMA Installation, Operation And Maintenance Manual

IOMCMA-5
INSTALLATION, OPERATION AND
MAINTENANCE MANUAL FOR CMA MODEL
DIRECT GAS-FIRED HEATERS WITH DDC CONTROLS
ATTENTION: READ THIS MANUAL AND ALL LABELS ATTACHED TO THE UNIT CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THESE UNITS! CHECK UNIT DATA PLATE FOR TYPE OF GAS AND ELECTRICAL SPECIFICATIONS AND MAKE CERTAIN THAT THESE AGREE WITH THOSE AT POINT OF INSTALLATION. RECORD THE UNIT MODEL AND SERIAL No.(s) IN THE SPACE PROVIDED. RETAIN FOR FUTURE REFERENCE.
FOR YOUR SAFETY The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.
POUR VOTRE SÉCURITÉ L'utilisation et l'entreposage d'essence ou d'autres liquides ou produits émettant des vapeurs infl ammables dans des récipients ouverts à proximité de cet appareil est dangereux.
FOR YOUR SAFETY
If you smell gas:
1. Open Windows
2. Don’t touch electrical switches.
3. Extinguish any open fl ame.
c
4. Immediately call your gas supplier.
Si vous sentez une odeur de gaz :
1. Ouvrez les fenêtres.
2. Ne pas actionner d'interrupteur.
3. Éteindre toute fl amme ouverte.
4. Appelez immédiatement votre fournisseur de gaz.
POUR VOTRE SÉCURITÉ
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
AVERTISSEMENT : Une installation défi ciente, de même qu'un mauvais réglage, modifi cation, entretien ou maintenance peuvent occasionner des dommages matéri­els, corporels voire causer la mort. Lire attentivement les instructions d'installation, d'utilisation et d'entretien avant d'installer ou d'intervenir sur cet appareil.
WARNING Install, operate and maintain unit in accordance with manufacturer's instructions to avoid exposure to fuel substances or substances from incomplete combustion which can cause death or serious illness. The state of California has determined that these substances may cause cancer, birth defects, or other reproductive harm.
Installer Please Note: This equipment has been test red and inspected. It has been shipped
free from defects from our factory. However, during shipment and installation, problems such as loose wires, leaks or loose fasteners may occur. It is the installer's responsibility to inspect
and correct any problems that may be found.
INSTALLER'S RESPONSIBILITY
SECTION I - FOREWARD
As is the case with any fi ne piece of equipment, care must be taken to provide the proper attention to the operation and maintenance details of this machine.
This manual of instructions along with the Digital Control System user manual has been prepared in order for you to become well-acquainted with those details, and in doing so, you will be able to give your Direct Gas-Fired System the care and attention which any piece of equipment needs and deserves.
It is the customer and installation personnel responsibility to determine if the unit is equipped with all of the safety devices required for the particular application. Safety considerations include the accessibility of the unit to non-service personnel, the provision of electrical lockout switches, maintenance procedures, and automatic control sequences. Clearly mark all emergency shutoff devices.
*IMPORTANCE NOTICE*
Temprite assumes no responsibility for loss or damage in transit; therefore, you should protect yourself by following these instructions:
Bill Of Lading
Save your bill of lading. It is a contract, and you will need it, provided you have to fi le a loss or damage claim. Remember, claims are outlawed after nine months.
Loss In Transit
Before you sign for this shipment, check against the bill of lading, also the transportation company’s delivery ticket. Make sure that you get the exact total of articles listed. Should the delivery ticket show more or less items than are offered, then the carrier’s agent must mark the difference on your freight bill before you sign.
Visible Damage In Transit
If anything is damaged, accept the shipment only if the carrier’s agent places a notation on your freight bill explaining the nature and extent of damage. Upon inspection of article, make claim to the delivering carrier.
Table of Contents
Section I: Foreword, Table of Contents,
and Important Notice .................................. 2
Section II: General Information .................................... 3
Section III: Installation .................................................4
Section IV: Pre-Start Up .............................................. 8
Section V: Unit Start Up ...............................................9
Section VI: Unit Shut Down ....................................... 11
Section VII: Troubleshooting Guide ........................... 12
Section VIII: Maintenance Schedule
and Lubrication Requirements............... 24
Section IX: Mestek Burner ......................................... 29
Section X: Manifold and Valve Adjustments ..............30
Section XI: Thermistor Curves ...................................31
Section XII: Replacement Parts................................. 32
Section XIII: Recirculating Units ................................ 32
Concealed Damage In Transit
Sometimes transit damage is not noticed until the goods are unpacked. In such cases, notifi cation to the carrier must be made within fi fteen (15) days of receipt of shipment. In such cases, save the packages and packing material, then notify the transportation company at once, and request an inspection. When the inspector calls, have him make out and leave a “concealed” bad order report. He is obliged to give one to you. Insist on it.
Disposition Of Damaged Atticles
Never return damaged articles to us. They are the property of the transportation company when the claim is fi led. They will give you disposition instructions.
Packing
We comply with the packing requirements of the transportation companies, and your bill of lading proved that everything was in good condition when shipped. That bill of lading contract requires them to deliver in perfect condition.
– 2 –
SECTION II - GENERAL INFORMATION
A. Purpose
The purpose of this manual is to present a guide for proper installation, maintenance, and operation of the Direct Gas-Fired System, and supplement, but not to replace, the services of qualifi ed fi eld service person- nel to supervise the initial start-up and adjustment of the unit. Persons without previous experience with large commercial and industrial heating equipment should not attempt the initial adjustment and checkout procedure which is essential before such installations may be considered ready for operation. This manual should be made readily available to all operating per­sonnel as an aid in troubleshooting and proper mainte­nance.
B. Shipping
Base Direct Gas-Fired units are shipped completely assembled where shipping limitations allow. Optional inlet hoods, fi lter and/or damper sections, or other large accessories are assembled and shipped mount­ed and wired whenever possible within limitations of shipping and handling. Any optional accessories shipped separately are shipped as assembled sec­tions. Any wired accessories which have been disas­sembled for separate shipment require no additional conduit or wire for fi eld reassembly. All wire leads will be tagged for ease of reconnection in the fi eld.
If the unit and/or accessories cannot be installed immediately, they should be stored in a clean dry environment. If this is not possible and the unit must be stored outdoors, it should be protected from the weather with tarpaulins or plastic coverings. Do not assume that simply covering a unit will keep insects, dust and condensation out of the unit and critical components. Rotate the fan(s) monthly.
Shipments are made F.O.B. Dallas, Texas by fl at- bed truck. The unit is securely strapped, tied, and blocked to prevent shipping damage. All shipments are checked by an inspector before they are accepted by the carrier. Parts that are shipped unmounted are noted on the bill of lading. These parts, where feasible, are packaged and shipped with the units. Upon receipt of shipment, all units should be checked against the bill of lading to insure all items have been received. All equipment (and any optional accessories) should be checked carefully for physical damage in the presence of the carrier’s representative. If parts are missing or damage has occurred, a claim should be fi led immedi- ately with the carrier.
All Direct Gas-Fired units are given a complete opera­tions test and control circuit checkout before shipment. Copies of the wiring diagram, piping diagram and bill of material are included with each unit shipped. If correspondence with the factory is necessary, please provide the unit model and serial number.
C. Optional Factory Service
Periodic service on any piece of mechanical equip­ment is necessary for effi cient operation. A nationwide service support network is available to provide quick and dependable servicing of make-up air, heating, ventilating, or air handling types of equipment. Factory start-up service is also available which includes the presence of a service engineer to supervise the initial start-up and adjustment of the equipment and provide instructions for the owner’s maintenance personnel in proper operations and maintenance. Consult factory for quotations on start-up or periodic service.
Prior to beginning installation of a unit that has been in storage for weeks or months, the unit and its compo­nents should be closely inspected.
– 3 –
SECTION III - INSTALLATION
FOR CANADIAN INSTALLATIONS ONLY
1. All installations must conform with local building codes, or, in the absence of local codes, with current CAN/CGA-B149-Installation Codes For Gas Burning Appliances and Equipment.
2. All electrical connections must be in accor­dance with Canadian Electrical Code, Part 1, CSA Standard C22.1.
This equipment must be installed and wired in ac­cordance with regulations of the National Board of Fire Underwriters, National Electrical Code, and local governing bodies. The following recommendations are not intended to supplant any requirements of federal, state, or local codes having jurisdiction. Authorities having jurisdiction should be consulted before instal­lations are made. Local codes may require additional safety controls and/or interlocks.
All installations in airplane hangers must be in ac­cordance with current ANSI/NFPA No. 409. All instal­lations in public garages must be in accordance with current NFPA No. 88A and NFPA No. 88B.
CAUTION: Do not install heating system in corrosive or fl ammable atmospheres! Premature failure of, or severe damage to the unit will result!
During transit, unloading and setting of the unit, bolts and nuts may have become loosened, particularly in the pillow block ball bearing assemblies in the fan section. It is recommended that all nuts and set screws be tightened. Turn fan shaft by hand to make certain that blower does not rub against blower housing, and that bearing set screws are tight. If units are not set immediately, cover all openings that might be exposed to the weather.
Open the cover on the electrical control box located on the unit. Inspect all wire terminals and wiring termina­tions to ensure that all connections are tight.
If units are not set immediately, cover all openings that might be exposed to the weather.
Rotate fans monthly.
RIGGING AND MOUNTING DATA - DIRECT FIRED UNITS
SPREADER
BAR
SPREADER
BAR
A
B
B
A
CAUTION: Heating system must not be installed in locations where air for combustion would contain chlorinated, halogenated or acidic vapors. If located in such an environment, premature failure of the unit will occur!
A. Handling the Equipment
The Direct Gas-Fired unit has been designed for rigging and handling through the use of special lifting lugs installed on the sides of each unit. As explained previously, the basic unit is designed for shipping in one piece where shipping limitations allow. Some optional accessories may require fi eld mounting.
The Direct Gas-Fired unit has been designed for rigging and handling through the use of special lifting lugs installed at each corner of unit. When unloading and setting the unit, use the lifting lugs provided or move the equipment on rollers. Hooks, jacks, or chains must not be used around the casing, main control panel or exterior mounted controls.
LIFTING LUGS
PROVIDED IN ONE
OF TWO LOCATIONS
A - USE WHEN LIFTING OVER 3,000 LBS. B - USE WHEN LIFTING UNDER 3,000 LBS.
08/16/07 C000539A
WARNING: To insure that a proper unit lift is made, lift unit approximately 24 inches and verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage.
– 4 –
B. Locating the Unit
Prior to locating the unit, authorities having jurisdic­tion should be consulted before installations are made. Approval permits should be checked against the unit received.
On Direct Gas-Fired units, which recirculate room air, outside ventilation air must be provided in accordance with the information shown on the heater nameplate. All ventilation air to the heater must be ducted directly from the outside. See Section XIII.
If in doubt regarding the application of this appliance, consult the factory.
Use extreme caution in handling the curb. Proper handling and positioning will assure a water-tight curb unit installation.
Re-check approval prints prior to installation. Be sure that there are no obstructions to ducting and that proper planning has been exercised in connection of piping and/or electrical services.
The curb assembly may be bolted or welded to either trusses or roof decking; however, connection to roof trusses is recommended. The curb is designed to carry the weight of the unit. Additional support is required for certain applications.
Locate the unit exactly level. Special attention should be given to the duct, electrical, and fuel connection points. Install duct work with adequate fl exible connec- tions to isolate vibration from the duct work. All duct work should have taped or caulked seams. Duct work should be properly sized so as not to inhibit airfl ow. This information should be cross-checked with the position of support beams and stand pipes to insure that clearance dimensions coincide with those of the unit. The minimum clearance to combustible material must be maintained as listed in Table 1.
Table 1
Minimum clearance to combustible material,
also consult local codes and regulations.
Clearances to Combustible Material
Vertical Units Horizontal Units Front* 39 inches 36 inches Rear 6 inches 6 inches Right 6 inches 6 inches Left 6 inches 6 inches Top 12 inches 12 inches Floor Zero 6 inches *Consider control side as front of unit. **Optimum clearance for shaft removal would be equivalent to cabinet width.
Make a visual inspection to insure no damage has oc­cured to the unit during installation.
Placement of the curb is critical in squareness and leveling. Shims for leveling must be applied to the curb; application of shims to the unit will tend to destroy the sealing effect after installation. Make sure sealing tape is in place before unit is set. Be careful not to allow gaps where two pieces of sealing tape meet. A bubble level must be used in the leveling process. Measure across diagonals to check for squareness. Allowable tolerance is 1/4" difference between diagonal measurements. Double-check approval prints before setting the unit.
Upon completion of setting the curb, apply roofi ng material and fl ashing as required. On outdoor curb mounted installations, fl ash and seal the roof curb to prevent leakage. The cross section of factory provided curb is formed to accept wood nailing strip and insula­tion provided by others.
D. Location of Accessories
Where applicable, standard or optional accessories will be placed inside the fan section of the unit for shipment, and must be removed and installed by the mechanical or electrical contractor.
Remotely located discharge or inlet dampers must be equipped with an end switch and interlocked to insure maximum design opening before starting and running circuits may be energized.
C. Curb Mounted Units
Outdoor units can be supplied with an optional roof curb. The curb greatly facilitates installation thereby reducing installation costs. All connections to the unit: duct, piping, electrical power and control wiring can be made through the roof opening. The curb may be shipped prior to unit shipment. All curbs are shipped un-assembled from the factory.
Field constructed intake accessories should be properly designed to minimize the entry of rain and snow.
Adequate building relief must be provided, so as to not over-pressurize the building, when the heater is operating at its rated capacity. This can be accom­plished by taking into account, through standard engineering methods, the structure’s designed infi ltra- tion rate, by providing properly sized relief openings, by interlocking a powered exhaust system, or by a combination of these methods.
– 5 –
E. Electrical Connections
F. Field Piping
WARNING: Open all disconnect switches and secure in that position before wiring unit. Failure to do so may result in personal injury or death from electrical shock.
WARNING: Controls must be protected from water. Do not allow water to drip on the ignition system.
NOTE: Before installing any wiring, check the unit rating plate for supply power voltage and minimum ampacity.
All electrical connections must conform to the current edition of: ANSI/NFPA No. 70 National Electrical Code and applicable state and local codes; in Canada, to the Canadian Electrical Code, Part 1 CSA Standard C22.1 and applicable provincial and local codes.
Since shipment of unit may require disassembly after factory check and test, reconnection of some electrical devices will be required in the fi eld. Connect electrical wires (supplied in factory furnished conduit) to appro­priate terminals. All leads are tagged to facilitate fi eld connections. See wiring diagram provided with equip­ment. Complete all wiring to any optional accessories as shown on unit bill of material and electrical wiring diagram as required before applying voltage to the unit.
Gas Piping
All gas piping must be in accordance with the require­ments outlined in the National Fuel Gas Code - ANSI Z223.1. It is required that a ground union be installed adjacent to the manifold for easy servicing. A drip leg and/or fi lter should be provided upstream of the unit’s inlet gas connection. An additional shut-off must be located external of the unit’s enclosure. The location of this valve must comply with all local codes. A 1/8 inch N.P.T. plugged tapping, accessible for test gauge con­nection, must be installed immediately upstream of the gas supply connection to the unit.
WARNING: To avoid equipment damage or possible personal injury, disconnect gas piping to this unit until a supply line pressure/leak test has been completed. Connecting the unit before completing the pressure/leak test may damage the unit gas valve and result in a fi re hazard.
DANGER: Never use an open fl ame to detect gas leaks. Explosive conditions may exist which would result in personal injury or death.
On vertical units there is a factory installed “Burner Cleanout” pipe located on the opposite end of the gas piping compartment. This is a clean out to drain any condensate that may have collected in the line burner.
Entry location for all fi eld-installed and control wiring is through the control panel.
If optional disconnect is not furnished with heater, the eld provided disconnect must be of the proper size and voltage. Refer to unit rating plate for minimum circuit ampacity and voltage. The disconnect must be installed in accordance with Article 430 of the current edition of ANSI/NFPA No. 70 National Electrical Code.
Check the supply voltage before energizing the unit. The maximum voltage variation should not exceed ± 10%. Phase voltage unbalance must not exceed 2%.
NOTE: Should any original wire supplied with the heater have to be replaced, it must be replaced with wiring material having a temperature rating of at least 105° C.
REMARQUE : Dans le cas où un quelconque des câbles livrés avec l'unité devait être remplacé, il doit être remplacé avec des câbles prévus pour résister à une chaleur d'au moins 105° C.
WARNING: DO NOT connect supply gas to this pipe.
The gas line should be supported so that no strain is placed on the unit. Pipe compounds which are not soluble to liquid petroleum gases should be used on threaded joints.
Refer to the heater’s rating plate for determining the minimum gas supply pressure for obtaining the maxi­mum gas capacity for which this heater is specifi ed.
Une tuyauterie adéquatement dimensionnée doit être posée jusqu'à l'unité. Veuillez noter que la pression de la tuyauterie d'alimentation en gaz doit correspondre à celle spécifi ée sur la plaque d'identifi cation, lorsque l'unité fonctionne à plein rendement.
Refer to the heater’s rating plate for determining the maximum supply pressure to the heater.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 PSIG.
– 6 –
The appliance must be isolated from the gas supply piping system by closing it’s individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 PSIG.
Correctly sized piping must be run to the unit.
Please note that gas line pressure must be as shown on specifi cation plate when unit is operating at full input. The high-pressure regulator and relief valve should be, if possible, mounted at least 5 to 10 feet upstream from the appliance regulator on the unit (if possible).
Building Pressure Transducer Piping (PT-13)
Pipe the high side to location inside the building that will not be affected by air movement. Pipe the low side to the atmosphere, positioned so it will not be affected by the wind and not exposed to the elements. Be sure that all tubing is clean and clear of any debris before installing tubes on the transducer.
disconnect switch.
2. Field wiring is typically indicated on the wiring diagram as dashed lines. When running any fi eld wiring for control circuit be sure wire is sized for a maximum 10% voltage drop. Check the VA rating of control circuit transformer to determine maximum load.
3.
Mount and wire remote control panel, thermostats, temperature sensors, and any other fi eld installed controls as indicated on the unit control wiring diagram.
4.
Connect all wires to the appropriate fi eld wiring terminals and any shielded or twisted wires as indicated on the unit control diagram.
5. Field wiring shall have a temperature rating of at least 105°C. The minimum size of the supply cable circuit shall be suffi cient for the maximum ampacity of the heater.
L'installation éléctrique d'utilisateur aura une température qui évalue d'au moins 105°C. La minimum de source du circuit de câblage sera suffi sante pour le ampacity maximum de l'appareil
de chauffage.
Flow Station Transducer Piping (PT-15)
Pipe the high side to the upstream connection and low side to the downstream connection of the Airfl ow Station as shown in Drawing # C000643 below. Be sure that all tubing is clean and clear of any debris before installing tubes on the transducer.
G. Field Wiring and Remote Control Installation
1. Connect the power lines to the line side of the power distribution block or optional main
AIRFLOW STATION LAYOUT
HEATER
CASING
RA DAMPER
TUBE CONNECTION
STATIC PRESSURE
NOTE: RUN TUBE CONNECTIONS TO TRANSDUCER (PT-15) IN UNIT CONTROL ENCLOSURE
LOW PRESSURE
SENSING TUBE
H. Locating Temperature Controls
The room or outdoor sensors should be mounted where they will not be subjected to direct impact of the heated air or radiant heat from the sun. It is also recommended that thermostats, especially those with mercury bulb contacts, be mounted on a vibration free surface. The side of building columns away from the heater or interior walls are usually the location best suited for mounting thermostats.
Controls with outdoor sensors require that the outdoor sensor be shielded from direct radiation from the sun. Unit mounted sensors are factory located and mounted.
HIGH PRESSURE TUBE CONNECTION
TOTAL PRESSURE SENSING TUBE
AIRFLOW STATIO N
EXTERIOR INSULATION FIELD PROVIDED WHEN MOUNTED OUTDOORS
– 7 –
BULLET
AMPLIFIER WING (SHEET METAL STRIP)
C000643
SECTION IV - PRE START-UP
Do not attempt start-up without completely reading and understanding this manual, along with the Digital Control Sysem user manual.
A. Pre Start-Up
The owners representative or equipment operator
should be present during start-up to receive instruc­tions on care and adjustments of the equipment.
All equipment has been factory tested, adjusted,
metered and inspected to meet conditions set at the time the order was placed. Only minimal
adjustments should be required. All information
in this service manual is typical. All products are semi-custom and changes may occur.
Suggested Tools and Instruments
Volt/Ohm Meter Thermometer Tachometer Ammeter Manometer (0-10" W.C.) Microammeter Standard Hand Tools D.C. Volt Meter Gas Pressure Gauge (0-35 lbs.) BACview 6
CAUTION: Line side of disconnect may be energized. Follow proper “lockout/tagout” procedures.
NOTE: All servicing and adjustments of the Direct Gas-Fired unit should be performed by a qualifi ed service engineer.
Perform a visual inspection, internally and externally, to make sure no damage has occured and that everything is secure. This inspection is very important and should be completed with greatest care given to detail. A good pre-start inspection will insure against possible unit damage on start-up and will save valuable analysis time.
1. Check that the physical condition of the unit
exterior is acceptable.
2. Check that the insulation inside of unit is properly secured.
3. Remove all shipping blocks, brackets and bolts from supply fan base with optional isolation base.
4. Check all wiring for loose connections and tighten if necessary.
5. Inspect all fan and motor bearings and lubricate if necessary.
CAUTION: DO NOT RUPTURE GREASE SEALS.
6. Inspect pulleys and belts for tightness, tension and alignment. Do not overtighten belts.
7. Check set screws on all bearings, pulleys, fans and couplings for tightness.
8. Check voltage supplied to disconnect switch; the maximum voltage variation should not exceed ± 10%. Phase voltage unbalance must not exceed 2%.
9. Check thermostat(s) for normal operation.
10. Check that system duct work is installed and free from obstructions.
11. Check that fans turn free in housing.
12. Check that the area around the unit is clear of
fl ammable vapors or containers of fl ammable liquids.
13. Check that all piping connections, particularly unions, are tight. Check all gas piping for leaks using a soap bubble solution. The most common types of problems found relative to the gas train itself is foreign material within the gas piping. This will interfere with the proper operation of the gas train components and burner. Purge all air from gas lines per gas codes.
14. Check that all accessories requiring fi eld wiring have been properly installed.
15. Check burner for proper location and alignment.
16. Check that fi lters, fi lter stops, accessories and ship loose items are installed correctly.
17. Check that vent lines (if applicable) are run to atmosphere on gas regulators and pressure switches for indoor units. Vent lines should terminate outside the building, with a turndown elbow and bug screen. Note that some units will use vent limiters and vent lines are not required. If vent lines are even partially plugged, this will interfere with proper venting of pressure control devices. Check that all manual gas shut-off valves are closed.
18.
19. When failure or malfunction of this heater creates a hazard to other fuel burning equipment, (e.g. when the heater provides make-up air to a boiler room), the heater is to be interlocked to open inlet air dampers or other such devices.
20. Motor overload relay setting should match the motor’s nameplate full load amperage.
21. Check that dampers and linkages are free to move, and that linkages are tight.
22. The unit may require that a Return Airfl ow Station be fi eld installed. Be sure all tubing connections are in the correct location as shown in drawing #C000643.
23. Check to ensure all manual reset safety devices have been reset and limits are in the normal operating position.
24. If inlet duct is attached to the heater, a purge timer must be provided and set to purge 4 times the inlet duct volume.
Purge time in seconds = 4 x L x W x H x 60 SCFM L = duct length in feet, W = duct width in feet, H = duct height in feet, SCFM = rating plate air throughput.
Refer to the electrical schematic for the proper circuit placement. Purge timer P/N 65.0711.00.
– 8 –
SECTION V - UNIT START-UP GENERAL
Before attempting to start the heater read and understand the the sequence of operations electrical schematic, ignition module, control components, gas train, burner and the Digital Control System user manual.
WARNING: During installation, testing, servicing and trouble shooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components to perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Make sure all manual gas valves are closed.
Make sure all doors and service panels have been closed or replaced.
Turn main disconnect switch off. Check the incoming line voltage to match unit rating plate rating. If voltage is over ±10% of nameplate rating or phase voltage unbalance is over 2%, notify contractor or power company.
Fans Are Enabled And Disabled By The Following:
MDT And MRT Standard: By rotating the remote “Temperature Setpoint” knob (MP-15).
Clockwise will enable the fans. Counterclockwise will disable the fans.
MRT-PRO With Smart Room Sensor:
To enable the fans and place the unit in the Occupied Mode press the “Manual On” button on the face of the (TS-02) MRT-PRO room sensor. Pressing the “Warmer” button will add 30-minute increments of time for a total of 9-hours of operating time. To disable the fans and place unit in the Unoccupied Mode press and hold down the “Manual On” button. Alternately pressing the “Manual On” button will also decrease the amount of operating time until it reaches zero and turns the fan off.
MRT Expert or VDT Expert With A BACview (KP-01): To enable the fans go to “Unit Modes” and enter [MANUAL], this mode will enable the fans.
To also enable the fans go to “Unit Modes” and enter [AUTO], this mode has four different functions that
control the fans and unit operation. They are a Time Clock, Heating and Cooling Night Setbacks, and signal from an external source to an auxiliary digital input.
To disable the fans go to “Unit Modes” and enter
[OFF].
NOTE: A BACview or PC is required to change Unit Modes. For a more detailed control sequence see the (Digital Control System User Manual).
Turn main disconnect switch on and Enable fans. Damper opens (if applicable). After end switch has proven damper is open, the blower fan turns on. (see operating modes in Digital Control System user manual)
Disable the fans. Check supply blower for proper rotation.
NOTE: To change rotation of the blower, simply interchange any two (2) of the line leads of the motor starter for three (3) phase motors. On single phase motors refer to motor nameplate.
Enable the fans. Check for proper blower rpm. Check that all motor amp draws do not exceed rating plate ratings and overloads are set to motor rating plate amps.
Check all dampers for proper operation, and linkage does not bind, see “Sequence of Operation”, and Digital Control System user manual for damper control modes.
Disable the fans.
NOTE: Before attempting to light the main burner you need to review Section X for proper Manifold and Valve Adjustments. A BACview 6 or PC will be required to change setpoints.
Check the gas supply pressure by replacing the plug tting on the gas line with a pressure gauge having appropriate range, and opening the manual gas valve. Check that the pressure reading is within the specifi ed range on the rating plate.
NOTE: To adjust gas pressure on supply lines where a regulator has been installed (to reduce the inlet pressure to rating plate maximum pressure), remove dust cap of main gas regulator and turn adjusting screw clockwise to increase pressure or counter-clockwise to decrease pressure.
Connect a DC Microammeter between SENSE terminal and fl ame rod sensing wire.
– 9 –
Open fi rst main gas shut-off valve slowly. Reset high- low gas pressure switches (if applicable). Check main gas line for leaks using soap solution.
Heat is Enabled By The Following:
MDT And MRT Standard: To enable the heat, rotate the “Temperature Setpoint” knob (MP-15) clockwise to the desired
setpoint above the actual air temperature. The
o
allowable temperature range is 55
to 90oF.
MRT-PRO With Smart Room Sensor:
To enable the heat, press the “Warmer” or “Cooler” button on the face of the remote MRT-Pro room sensor (TS-02) to the desired room setpoint. Each push of the button changes the temperature setpoint by 1o F. The setpoint can be changed a maximum of + 10oF from the default of 65oF. Changing the heating setpoint
also changes the cooling setpoint.
MRT Expert or VDT Expert With A BACview (KP-01):
To enable the heat for MRT Expert scroll through the “Setpoints” menu in the BACview and enter the desired room Heating Occupied and Unoccupied Setpoints. For VDT Expert enter the desired Heating Discharge Air Setpoint.
Energy Savings Modes: There are 3 Energy Savings Modes that could disable the burner.
NOTE: A BACview or PC is required to change Setpoints. For a more detailed control sequence, see the Digital Control System Users Manual.
Setting Main Flame
CAUTION: You will have approximately three (3) minutes before the unit shuts down on Freezestat (Low Discharge Temperature, if you have disconnected plug wires TS-01 and TS-03). Referred to in Section X.
NOTE: 3 OR 4 TRIALS MAY BE NEEDED TO PURGE AIR FROM GAS LINE.
Install manometer at test port on the last tee of the burner manifold, or MR valve test port.
Slowly open last manual gas shut-off valve.
Enable the fan and burner. Unit will run for 5 seconds before valve opens and burner lights if all safeties and limits are in normal operating mode.
NOTE: This is a direct spark ignition burner. Low fi re may need to be adjusted fi rst in order to light the burner.
Adjust high fi re pressure reading (from manometer) to match Normal Manifold Pressure fi ring rate shown on unit rating plate.
Refer to Valve Adjustment instructions in Section X for setting high and low fi re gas pressure settings.
The high fi re setting must be made before adjusting low fi re. Adjust the high fi re setting according to the Maxitrol Valve Adjustment instructions in Section X. The high fi re setting must not exceed the pressure stated on the rating plate.
When adjusting low fi re, there should be a continuous fl ame along the entire burner length without any blowout spots. Burner must hold in low
re for approximately 10 seconds before modulating up.
Check fl ame signal with burner cycling through full fi ring range.
Cycle burner several times to insure smooth light off. Low fi re may need to be readjusted.
There should be a continuous spark for ten (10) seconds with the last gas cock turned off and the ignition control (RE-02) should lock out.
Check main gas lines for leaks.
Main fl ame is now set. Make sure burner modulates and turn thermostat to the desired setting.
United Technologies Electronic Controls Spark Ignitor (RE-02)
Watch microammeter carefully. Burner must hold in low re for approximately 10 seconds before modulating up. The reading should be at least 0.5 microamps. If the read-ing is too low, slowly turn the low-fi re adjustment on the modulating valve in or out until satisfactory readings are obtained. When adjusting low fi re, there should be a continuous fl ame along the entire burner length without any blowout spots.
– 10 –
Loading...
+ 22 hidden pages