Temp-O-Matic TMP Multi-Position User Manual

Page 1
Printed on 100% recycled paper 670-000-004/1010
Temp-O-Matic Oil Furnace
TMPMulti-Position (Counterflow / Horizontal)
Contents Page
Read this first!............................................................................2
 Check furnace location..............................................................3
 Prepare furnace and place in position.......................................6
 Connect supply and return ducts...............................................8
 Venting.....................................................................................11
 Connect fuel oil piping.............................................................12
 Wire furnace and burner..........................................................14
 Start-up....................................................................................17
 Checkout procedure................................................................18
 Troubleshooting.......................................................................19
 Service and maintenance........................................................20
 Components and replacement parts........................................ 23
 Dimensions and ratings...........................................................25
 Owner’s information.................................................................27
Hazard definitions
Hazards that will cause severe personal injury, death or substantial property damage.
Hazards that can cause severe personal injury, death or substantial property damage.
Hazards that will or can cause minor personal injury or property damage.
Special instructions on installation, operation or maintenance that are important but not related to personal injury or property damage.
INSTALLER – Read all instructions before installing. Read page 2 first. Follow all instructions in proper order to prevent personal injury or death.
Consider ducting, fuel supply, venting and
installation when determining furnace location.
 Any claims for damage or shortage in shipment
must be filed immediately against the transportation company by the consignee.
Do not store or use gasoline or other flammable liquids or vapors near this furnace or any other appliance.
Ventilate house while operating furnace for the first time. Odors may be emitted for a brief period.
Do not alter this furnace in any way. The manufacturer will not be liable for any damage resulting from changes made in the field to the furnace or its components or from improper installation. Failure to comply could result in severe personal injury, death or substantial property damage.
USER – Please read the following. Failure to comply could result in severe personal injury, death or substantial property damage.
This manual is for use only by your qualified
heating installer / service technician.
Please see the Owner’s information only, on back
page of this manual.
Have the furnace serviced by a qualified service
technician, at least annually.
This manual must only be used by a qualified heating installer / service technician. Furnace and burner must be installed and serviced only by a qualified heating installer / service technician. Failure to comply could result in severe personal injury, death or substantial property damage.
When calling or writing about the furnace – Please indicate furnace model number and serial number from rating label. You may list the serial number and model number in the space provided on the “Installation and service certificate” found on page 18.
KEEP THESE INSTRUCTIONS WITH FURNACE FOR FUTURE REFERENCE.
Page 2
2 670-000-004/1010
READ THIS FIRST!
Failure to adhere to the guidelines below can result in severe personal injury, death or substantial property damage.
Service and maintenance –
 To avoid electric shock, disconnect electrical supply before
performing maintenance.
 To avoid severe burns, allow furnace to cool before performing
maintenance.
 Perform service and maintenance as described in this manual
and the burner manual.
 Do not attempt to make adjustments to the blower or motor while
the furnace is in operation. Disconnect power to the furnace and be sure all parts have stopped moving before attempting adjustments or maintenance.
 The burner must be set up and adjusted using combustion test
instruments. Visual examination of the flame alone cannot determine combustion performance.
Operation -
 Do not use the furnace as a construction heater.  Do not operate any furnace if the heat exchanger is damaged,
corroded or pitted. Toxic flue products could enter the air stream.
 Do not jumper, attempt to by-pass or override any limit control.  Do not block flow of combustion or ventilation air to furnace. Do
not block or obstruct the air openings in the furnace casing.
 Do not store or use combustible materials, gasoline, or other
flammable liquids or vapors in the furnace area.
 Do not operate the furnace if the furnace area will be exposed to
air contaminants as described on page 5.
 Should overheating occur, do not turn off or disconnect electrical
supply to furnace. Instead, shut off the oil supply at a location external to the appliance, if possible.
 Do not use this furnace if any part has been under water. Call a
qualified service technician immediately, to inspect the furnace and to replace any part of the furnace, control system or burner that was submerged in water.
 Do not operate furnace if temperature rise through heat
exchanger exceeds 85
o
F.
 Inspect, clean and replace (if necessary) return air filter
regularly.
 Do not obstruct return air grills or supply air outlets.  Supply only #2 fuel oil to the burner. Never attempt to use
gasoline, a mixture of gasoline and oil, waste fuel, refuse or any other substance in the burner of furnace.
Installation -
 Do not block flow of combustion or ventilation air to furnace. Do
not block or obstruct the air openings in the furnace casing.
 Connect furnace only to a functional vent system in good
condition. Place the furnace to allow proper venting, with the shortest possible venting and minimum number or elbows.
 Always connect and seal a return air duct to the furnace unless
the furnace is located in a large space, such as an unpartitioned basement. Route the return air duct to an adjacent room if no return air manifold is used.
 Install furnace maintaining minimum clearances for service and
separation from combustible surfaces described in this manual. If furnace is installed on a combustible floor, you must use the combustible floor base or provide the minimum clearance from the furnace to the floor as given in this manual.
 Install, start-up, service and maintain burner per instructions in
this manual and the burner manual.
 Verify burner is properly inserted through the combustion
chamber opening.
 Furnace must be installed so that burner and control system
components are protected from dripping, spraying water or rain during operation or service.
 If installing an air conditioning evaporator coil, install the coil
downstream of, or in parallel with, the furnace to prevent condensation on the furnace heat exchanger. If the coil is in parallel, provide means to prevent flow of chilled air into the furnace, including an interlock to prevent simultaneous operation of heating and air conditioning.
Apply the following suggestions to prevent unsatisfactory operation of the furnace.
Installation –
 Be sure to level the furnace, using a spirit level at the front and
one side. If the furnace is not level, oil can drip into the combustion chamber after burner cycling, contaminating the heat exchanger and the burner head.
 Avoid locating return grills in rooms that may contain undesirable
odors.
 Never locate a return air grill closer than approximately 20 feet
from the furnace.
 Locate the furnace near the center of the supply and return duct
systems.
 Always check the size of the ducts on a replacement installation,
particularly if adding air conditioning.
Page 3
TMP Oil FurnacesFurnace Manual
670-000-004/1010 3
1 Check furnace location
Pre-installation checklist
Verify code compliance
Local, state, provincial, and national codes, laws, regulations
and ordinances
NFPA-31, Installation of Oil-Burning Equipment
National Electrical Code
All local codes and/or regulations take precedence over the
instructions in this manual and should be followed accordingly.
TMP furnaces, their burners and controls met safe lighting and other performance criteria when furnace underwent tests specified in Underwriters Laboratories Standard UL727.
Check location and furnace specifications
Use the table below to verify:
Furnace heating capacity
Space is large enough to provide required clearances
Verify the installation will meet the requirements of this manual:
Clearances (page 3)
Combustion/ventilation air openings (pages 4)
Supply air duct (page 8)
Vent system (page 11)
Fuel oil piping (page 12 plus burner manual)
Electrical connection (page 14)
Clearances
Minimum clearance to combustible materials
 Install the furnace, ductwork and vent such that no combustible
surface is closer than listed in Table 1.
Flue pipe clearances must take precedence over jacket clearances (listed below).
Service accessibility clearances
 Provide no less than the minimum clearances given in Table 1 to
ensure the furnace can be properly operated, serviced and maintained.
 Always apply whichever clearance is LARGER – combustible
construction or service accessibility.
Flooring and foundation
Flooring
TMP furnaces are approved for installation on non-combustible floor. If a combustible floor is used, follow these instructions:
Horizontal installation on combustible floor
Always keep the minimum installation clearances of 1 inch between the combustible floor and the furnace sides. Use appropriate leveling legs or optional kit #HFB-1-W.
Counterflow installation on combustible floor
Always keep the minimum installation clearances of 1 inch between the combustible floor and the furnace bottom or air supply plenum. Use appropriate leveling base and spacers or optional kit #CFB­1-W.
Do not install furnace on carpeting even if foundation is used. Fire can result, causing severe personal injury, death or substantial property damage.
Foundation
 Provide a solid brick or minimum 2-inch thick concrete
foundation pad if any of the following is true:
the floor can become flooded.
the furnace mounting area is not level.
Residential garage installations
Take the following special precautions when installing the furnace in a residential garage. If the furnace is located in a residential garage:
Mount the furnace a minimum of 18 inches above the floor
of the garage.
Locate or protect the furnace so it cannot be damaged by a
moving vehicle.
Table 1 Minimum clearances
Location Application Counterflow Horizontal
Furnace 1 " 1 "
Supply plenum, warm air duct within 6ft of furnace 1 " 1 "
Back Furnace 1 " 1 "
Top Furnace casing or plenum 1 " 1 "
Bottom Furnace – combustible floor 1 " 1 "
Front Furnace 24 " 24 "
Flue pipe 18 " 18 "
* Use appropriate leveling legs or optional kit #HFB-1-W; ** Use appropriate leveling base and spacers or optional kit #CFB-1-W.
Sides
Minimum installation clearances from combustible materials (Chimney installation)
***
Page 4
TMP Oil Furnaces – Furnace Manual
4 670-000-004/1010
1 Check furnace location (continued)
Air for combustion and ventilation
Adequate combustion and ventilation air ensures proper combustion and reduces risk of severe personal injury or death from possible flue gas leakage and carbon monoxide emissions.
Do not install exhaust fan in furnace room.
Consider building construction
Older buildings with single-pane windows, minimal weather-stripping and no vapor barrier often provide enough natural infiltration and ventilation without dedicated openings.
New construction or remodeled buildings are most often built tighter. Windows and doors are weather-stripped, vapor barriers are used and openings in walls are caulked. As a result, such tight construction is unlikely to allow proper natural air infiltration and ventilation.
For buildings with tight construction, provide openings directly to outside or to a ventilated crawl space or attic. Size the openings to the same specifications as for the furnace location per the following paragraphs.
Follow state, provincial or local codes when sizing adequate combustion and ventilation air openings. In absence of codes, use the following guidelines when furnace is in a confined room (defined by NFPA 31 as less than 7200 cubic feet per 1 GPH input of all appliances in area. A room 8 ft. high x 30.0 ft. x 30.0 ft. is 7200 cu. ft.).
Provide two permanent openings
Openings locations
One within 12 inches of ceiling, one within 12 inches of floor. Minimum height or length dimension of each rectangular opening should be at least 3 inches.
When inside air is used:
Each opening must freely connect with areas having adequate infiltration from outside. Each opening should be at least 140 sq. in. per 1 GPH input (1 sq. in. per 1000 BTU input) of all fuel-burning appliances plus requirements for any equipment that can pull air from room (including clothes dryer and fireplace).
When outside air is used:
Connect each opening directly, by ducts to the outdoors, or to crawl or attic space that freely connects with outdoors. Size per below:
Through outside wall or vertical ducts – at least 35 sq. in. per 1
GPH input (1 sq. in. per 4000 BTU input) of all fuel burning appliances plus requirements for any equipment that can pull air from room (including clothes dryer and fireplace).
Through horizontal ducts – at least 70 sq. in. per 1 GPH furnace
input (1 sq. in. per 2000 BTU input) of all fuel-burning appliances plus requirements for any equipment that can pull air from room (including clothes dryer and fireplace).
Where ducts are used, they should have the same cross-
sectional area as free area of openings to which they connect. Compensate for louver, grille or screen blockage when calculating free air openings. Refer to the manufacturers’ instructions for details. If unknown, use:
Wood louvers, which provide 20-25% free air.
Metal louvers or grilles, which provide 60-75% free air.
Lock louvers in open position or interlock with equipment to prove open before furnace operation.
Basement installations
When the furnace is located in an unconfined space, such as an unpartitioned basement, adequate air should normally be available without additional openings. An unconfined space is defined as one having no less than 50 cubic feet room volume per 1,000 BTU/h input of all appliances in the space.
If the house is of tight construction, provide air openings to the basement directly from outside or from a ventilated attic. Size the openings as described above under “When outside air is used”.
Closet installations – special NOTICE
Openings in closet doors
Provide TWO openings – one within 6 inches of top of closet door, the other within 6 inches of the bottom of closet door.
EACH opening must be at least 24 inches wide by 12 inches high.
Advise homeowner that the openings to the closet must never be obstructed or blocked in any way. Failure to provide adequate air for combustion and ventilation could result in severe personal injury, death or substantial property damage.
Page 5
TMP Oil FurnacesFurnace Manual
670-000-004/1010 5
1 Check furnace location (continued)
Air contamination
Please review the following information on potential combustion air contamination problems.
See Table 2 for products and areas which may cause contaminated combustion air.
To prevent the potential of severe personal injury or death, check for products or areas listed below before installing the furnace. If any of these contaminants are found:
Remove contaminants permanently.
-OR-
Isolate furnace and provide outside combustion air. See
national, provincial or local codes for further information.
Table 2 Corrosive contaminants and likely locations
Products to avoid
Spray cans containing chloro/fluorocarbons
Permanent wave solutions
Chlorinated waxes/cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
Adhesives used to fasten building products and other similar products
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments
Swimming pools
Metal fabrication plants
Beauty shops
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
Page 6
TMP Oil Furnaces – Furnace Manual
6 670-000-004/1010
2 Prepare furnace and place in position
Inspect & prepare furnace
Remove furnace from carton
Remove the furnace from its shipping carton and inspect thoroughly. Remove access panels to inspect the furnace interior.
Immediately file a claim with the transportation company if you discover concealed damage.
Do not install or attempt to operate the furnace if the heat exchanger, burner or controls have been damaged. Immediately contact your furnace supplier. Operating a damaged furnace could result in severe personal injury, death or substantial property damage.
Prepare burner
Remove the burner from its shipping carton and inspect thoroughly. Read the burner manual and follow instructions for preparing and installing the burner.
Install the correct nozzle for the required firing rate, using the burner manual shipped with the burner. Follow the burner manual instructions for nozzle installation. Verify the correct setting of electrodes after nozzle and burner oil tube assembly are in place.
Openings in walls, floor & ceiling
General
Ensure that the finished door opening to the furnace room is large enough to install and remove the furnace, water heater or any other appliances in the room.
Before placing furnace in a closet or small room, cut all openings required in floor, ceiling or walls for ducts and vent. This will simplify the work and prevent construction dust from entering the furnace heat exchanger.
Verify that all clearances to combustible construction and for service accessibility will be met. The vent must be no closer than 18 inches to any combustible surface unless a type “L” double-wall vent pipe is used or the vent is constructed per the requirements of the NFPA 31. Provide a ventilated thimble per all applicable codes where vent pipe passes through wall or ceiling. Failure to comply could result in severe personal injury, death or substantial property damage.
Duct locations and sizing
Verify that the size of the supply and return duct system is sufficient for the application. The pressure drop through the duct system must not exceed 0.2” water column. The total drop through the duct system and air conditioning condensing coil (if used) must not exceed 0.5” water column.
See suggested duct sizing in this manual. For more detailed sizing information, refer to ACCA Manual D.
Openings …
(continued)
Supply and return ducts
You must install a return air duct, sealed to the furnace, even if no return manifold is used. Cut the required opening for the supply air duct in the floor of the room before placing the furnace.
Verify that the filter will be easily accessible for removal after the furnace is in place.
Install furnace and burner
Place furnace
Place the furnace in the desired location. Measure clearances and verify per page 3 or table 1 of this manual.
Level the furnace using a spirit level on the front and one side.
Inspect combustion chamber
Inspect the combustion chamber. Verify that it is in good condition and correctly positioned inside the heat exchanger. The burner opening in the chamber must align with the burner heat exchanger opening.
The combustion chamber is constructed of ceramic fiber materials. See the WARNING information on page 21 of this manual. Comply with these instructions when handling any ceramic fiber or fiberglass materials. Failure to adhere to these guidelines could result in severe personal injury or death.
Insert burner
Following the burner manual instructions, install the burner and its gasket in the burner opening. Make sure the burner passes through the opening in the combustion chamber and does not protrude more than ¼ inch into the chamber.
Secure the burner in place with the four nuts and washers provided. Wire and pipe fuel to the burner as per the burner manual and this manual.
Burner orientation
For a horizontal installation, you must turn the burner 90o, to the normal orientation. Always keep the motor shaft in horizontal position.
Page 7
TMP Oil FurnacesFurnace Manual
670-000-004/1010 7
2 Prepare furnace and place in position (continued)
Blocked Vent Shut-Off (BVSO) for chimney venting (OPTIONAL)
It is imperative that this device be installed by a qualified agency.
This device is designed to detect the insufficient evacuation of combustion gases in the event of a vent blockage. In such a case the thermal switch will shut down the oil burner. The device will then need to be re-armed MANUALLY.
In the event that the BVSO repetitively shuts down the oil burner, a qualified technician needs to evaluate the cause of this shut down.
Refer to the figures 3 to 5 at section 6, Wiring Diagrams and detailed instructions supplied with the BVSO for the installation and wiring procedures. It is also essential that the BVSO be maintained annually. For more details refer to the instructions supplied with the device itself, as well as the Maintenance Section.
Figure 1
Blocked Vent Shutt-Off device wiring
Installation : Upflow with Vertical exhaust
(Optional)
Figure 2
Blocked Vent Shutt-Off device wiring
Installation : Horizontal flow with vertical exhaust
(Optional)
Page 8
TMP Oil Furnaces – Furnace Manual
8 670-000-004/1010
3 Connect supply and return ducts
Duct sizing
Determine airflow CFM
The temperature rise through the furnace must not exceed 85oF and should be at least 55
o
F for comfort. When calculating airflow,
assume a temperature rise of 70
o
F.
The noticeable temperature change for cooling would be approximately 27-30
o
F. Actual temperature change will be
approximately 18-21
o
F due to humidity of the air.
To calculate the noticeable heat temperature change (T), you can use the formula:
T = BTU/h/(1.1 x CFM) Eq. 3-1
To calculate airflow when you know temperature change (T), you can use:
CFM = BTU/h/(1.1 x T) Eq. 3-2
You can estimate airflow using the following rules of thumb:
Heating: 14 CFM per 1,000 BTU/h output Eq. 3-3 Cooling: 400 CFM per ton air conditioning Eq. 3-4
Determine the required airflow based on whichever is larger – heating mode or air conditioning mode.
Examples:  What would the temperature rise be for a 100,000 BTU/h output
furnace with an airflow rate of 1200 CFM?
Use Equation 3-1 since you know CFM and BTU/h:
T = 100,000/(1.1 x 1200) = 76
o
F
The temperature rise would be 76
o
F.
If the air enters the furnace at 70
o
F, it would leave the
furnace at 70
o
F + 76o F = 146o F.
 What would the airflow be to obtain a 70
o
F rise through a
120,000 BTU/h output furnace?
Use equation 3-2 since you know T and BTU/h:
CFM = 120,000/(1.1 x 70) = 1,558 CFM The airflow would have to be 1,558 CFM to obtain a
temperature rise of 70
o
F.
 Estimate the required airflow for a 75,000 BTU/h output furnace
installed with a 2-ton air conditioning evaporator coil.
Heating mode airflow (use Equation 3-3):
CFM = 75 x 14 = 1,050 CFM
Cooling mode airflow (use Equation 3-4):
CFM = 2 x 400 = 800 CFM The larger number is 1,050 CFM (heating), so the duct
system should be sized for 1,050 CFM.
The supply duct would need to be 16” round or a rectangular
equivalent such as 8” x 25” or 12” x 16”, using Table 4, page 8.
 Estimate the required airflow for the same furnace installed with
a 4-ton air conditioning evaporator coil.
Heating mode airflow is still 1,050 CFM.
Cooling mode airflow (use Equation 3-4):
CFM = 4 x 400 = 1,600 CFM The larger number is 1,600 CFM (cooling), so the duct
system should be sized for 1,600 CFM.
The supply duct would need to be 18” round or a rectangular
equivalent such as 8” x 36” or 12” x 21”, using Table 4, page 9.
Always check the size of existing ducts, particularly if you are adding air conditioning. The air pressure loss through the cooling evaporator coil reduces available airflow. If the ducts are too small as well, the system may not work satisfactorily on either heating or cooling.
Determine duct dimensions
Table 4, page 9, and Table 5, page 10, provide typical round and rectangular duct sizes for rectangular and flat oval galvanized ducts. Do not apply these tables to size ductwork if the total equivalent length of the duct exceeds approximately 100 feet. For longer systems or for ductboard, fiberglass-lined or flexible duct sizing, use the ACCA Manual D or the ACCA duct sizing slide rule. These tables are based on pressure loss of approximately 0.10” water column per 100 feet equivalent length of duct.
Use Table 3 below to size or check sizing of take-offs to supply registers or return grills.
Verify the size and type of registers, diffusers and grills from the manufacturer’s ratings. Do not exceed the recommended flow rate. The pressure drop allowance for each should not exceed approximately 0.05” water column.
Install a return air filter, sized per specifications in Section 12.
Use only a return air filter mounted to the furnace. Do not add additional filters unless the duct system is carefully sized to allow for the additional pressure drop.
Table 3 Suggested maximum flow to runouts
TAKE-OFF SIZE
(Inches)
SUPPLY RETURN
5 Round 60 45
6 Round 100 75
7 Round 140 110
8 Round 210 160
3 ¼ x 8 Stack 70 55
3 ¼ x 10 Stack 100 75
3 ¼ x 14 Stack 140 110
2 ¼ x 12 Stack 70 55
2 ¼ x 14 Stack 90 70
6 Round 55 40
8 Round 120 90
10 Round 200 160
12 Round 320 250
14 Round 480 375
16 Round 660 530
18 Round 880 680
20 Round 1200 900
CFM
Sheet metal or ductboard
Flexible duct (keep bends to minimum)
Page 9
TMP Oil FurnacesFurnace Manual
670-000-004/1010 9
3 Connect supply and return ducts (continued)
Duct sizing (continued)
Table 4 Typical duct sizing for systems not over 100 feet equivalent length – round or rectangular galvanized
Do not apply this table for duct systems over approximately 100 equivalent feet in length. For longer systems or systems using other duct materials, refer to ACCA Manual D. Incorrectly sizing duct systems can result in unsafe or uncomfortable operation.
Round
duct
diameter 4 5 6 7 8 9 10 12 14 16 18 20 22 24 26 28 30
(inches) x x x x x x x x x x x x x x x x x
45
4
444- - - - - - - - - - - - - -
65
5
6544- ------------
100
6
865544- - - - -------
150
7
12 9 7 6 5 5 5 4 4 - -------
200
8
14 11 9 8 7 6 6 5 4 4 -------
250
9
18 13 10 9 8 7 6 6 5 5 4 4 - - - - -
300
9
20 15 12 10 9 8 7 6 6 5 5 4 4 - - - -
400
10
26 19 15 13 11 10 9 8 7 6 6 5 5 5 4 4 -
500
12
32 23 18 15 13 12 11 9 8 7 6 6 6 5 5 5 5
600
12
38 28 22 18 15 13 12 10 9 8 7 7 6 6 6 5 5
700
12
46 32 25 20 17 15 14 11 10 9 8 7 7 7 6 6 6
800
14
52 36 28 23 19 17 15 13 11 10 9 8 8 7 7 6 6
900
14
58 41 31 25 21 19 17 14 12 11 10 9 8 8 7 7 7
1000
16
64 45 34 28 23 20 18 15 13 11 10 9 9 8 8 7 7
1100
16
72 49 38 30 25 22 19 16 14 12 11 10 9 9 8 8 7
1200
16
-5441332724211715131211109 9 8 8
1300
16
-584435292522181614121110109 9 8
1400
18
-634738312724191614131211101099
1500
18
-6851403429252017151412121110109
1600
18
-7254433630272118161413121111109
1700
18
--584538322823191715141312111010
1800
18
--614840342924201716141312111110
1900
20
--645142353125211816151413121111
2000
20
--685344373226221917151413121211
2200
20
---5948413528232018161514131212
2400
22
---6452443830252219171615141312
2600
22
---6956474132272321191716151413
2800
22
----61514434292522201817151514
3000
22
----65544737302623211917161514
3500
24
-----635442342926232119181716
4000
26
-----726147393329262321201918
Typical duct sizing
(For approximately 0.10 inch w.c. in a typical residential installation of galvanized metal duct)
CFM
Rectangular duct equivalent sizes Minimum width
(inches)
for duct heights
(inches)
of :
Page 10
TMP Oil Furnaces – Furnace Manual
10 670-000-004/1010
3 Connect supply and return ducts (continued)
Duct sizing
(continued)
Table 5 Typical duct sizing for systems not over 100 feet equivalent length – round or flat oval galvanized
Do not apply this table for duct systems over approximately 100 equivalent feet in length. For longer systems or systems using other duct materials, refer to ACCA Manual D. Incorrectly sizing duct systems can result in unsafe or uncomfortable operation.
Round
duct
diameter 3 4 5 6 7 8 9 10 12 14 16 18 20
(inches) x x x x x x x x x x x x x
45
4
65- - - - - - - - - - -
65
5
86- - - - - - - - - - -
100
6
11 8 7 - - - - - - - - - -
150
7
16 11 9 8 - - - - - - - - -
200
8
21 15 11 10 8 - - - - - - - -
250
9
26 18 14 11 10 9 - - - - - - -
300
9
30 20 16 13 11 10 - - - - - - -
400
10
40 26 20 16 14 12 11 - - - - - -
500
12
49 32 24 19 16 14 13 12 - - - - -
600
12
59 38 28 22 19 16 15 13 - - - - -
700
12
69 44 32 25 21 18 16 15 13 - - - -
800
14
-5036292420181614- - - -
900
14
-5641322622201815- - - -
1000
16
-634535292422191715- - -
1100
16
-694938312623211816- - -
1200
16
-755341332825221917- - -
1300
16
--5844363026242018---
1400
18
--624738322825211817--
1500
18
--665041343026221918--
1600
18
--715443363128232018--
1700
18
---5746383329242119--
1800
18
---6048403531252220--
1900
20
---635042363226232119-
2000
20
---675344383327242120-
2200
20
---735848413629252321-
2400
22
----635244393227242221
2600
22
----685648423429252322
2800
22
-----6051443630272423
3000
22
-----6454473832282624
3500
24
------63544336322826
4000
26
------71614840353129
Typical duct sizing
(For approximately 0.10 inch w.c. in a typical residential installation of galvanized metal duct)
CFM
Flat oval duct equivalent sizes Minimum width
(inches)
for duct heights
(inches)
of :
Page 11
TMP Oil FurnacesFurnace Manual
670-000-004/1010 11
4 Venting
General venting requirements
Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
Inspect existing chimney before installing furnace. Clean chimney thoroughly. Replace or repair chimney if visual inspection indicates chimney may be unsuitable for use. Insufficient draft can cause flue gas leakage and carbon monoxide emissions. Failure to clean or replace perforated pipe or tile lining and/or patch mortar and joints can cause severe personal injury or death.
Proper draft for these oil furnaces may be achieved using either
a conventional chimney (natural draft) or a power vent (sidewall) system that has been properly designed for use with oil-fired equipment. Power vent manufacturer’s instructions must be followed.
Use vent material approved by local codes for oil-fired burners.
In their absence, refer to:
NFPA 31, Installation of Oil-Burning Equipment. NFPA211, Standard for Chimneys, Fireplaces, Vents and
Solid Fuel Burning Appliances.
In Canada, refer to CSA B139, Installation Code for Oil-
Burning Equipment.
NFPA-211 requires chimney to be lined before connected to
furnace.
To prevent downdrafts, extend chimney at least 3 feet above
highest point where it passes through roof and 2 feet higher than any portion of building within 10 feet. Increase chimney cross­sectional area and height at least 4% per 1,000 feet above sea level.
Provide minimum clearances from vent (flue) pipe to
combustible material:
Single-wall vent – 18 inches minimum Type “L” double-wall vent – 6 inches minimum
Oversized chimneys, outside masonry chimneys and/or derated inputs can result in condensation in chimney.
Connect venting
Long horizontal vent runs, excessive number of tees and elbows, or other obstructions restricting combustion gas flow can result in the possibility of condensation, flue gas leakage and carbon monoxide emissions, which can lead to severe personal injury or death.
 The horizontal vent must slope upwards, away from the furnace,
a minimum of ¼ inch per foot.
 Connection must be made above bottom of chimney to avoid
blockage. Vent pipe must not enter chimney far enough to cause obstruction. Use thimble or slip joint where vent pipe enters chimney to allow removal for cleaning.
 When burner and furnace are properly installed, draft overfire
will be approximately –0.01” to –0.02” w.c. Install barometric
Connect venting (continued)
control in vent, per control manufacturer’s instructions, when excess draft needs to be relieved or to comply with applicable codes and regulations. Use draft gauge to adjust proper opening.
 An induced draft fan for the chimney may be necessary if:
Excessive resistance to flow of combustion gases can be
expected.
Cross-sectional area of chimney is smaller than minimum
recommended.
Chimney height is less than recommended. When using induced draft fan seal all vent joints and
interlock burner with fan operation.
Vent dampers
Do not install a thermal-type vent damper on this furnace. Failure to comply could result in severe personal injury, death or substantial property damage.
If a vent damper is required, use only a motorized one, installed and wired in the furnace according to the vent damper manufacturer’s instructions.
Barometric draft control
Install a barometric control in the vent, per the manufacturer’s instructions, when excess draft needs to be relieved or to comply with applicable codes and regulations. Use draft gauge to adjust proper opening.
 Install a barometric draft control in the vent pipe at least one foot
from the furnace vent connection, preferably in the highest part of the vent pipe before the vent enters the chimney. If headroom does not provide enough clearance to locate the control at least one foot from the vent connection, install an elbow at the furnace and mount the control in an horizontal pipe at least one foot from the elbow. Install an elbow after the control to turn vertically.
 The barometric draft control must be located in the same room
as the furnace to operate correctly.
 Ensure that the barometric draft control is accessible. Adjust the
damper to obtain the correct overfire draft, as described in this manual and the burner manual.
Page 12
TMP Oil Furnaces – Furnace Manual
12 670-000-004/1010
5 Connect fuel oil piping
General oil piping requirements
Location and installation of oil tanks, oil piping and burners must
follow:
NFPA 31, Standard for the Installation of Oil-Burning
Equipment.
In Canada, CSA B139, Installation of Oil-Burning
Equipment.
Local codes and regulations. Information provided with burner and fuel pump.
If any part of the fuel oil tank is above burner level, an anti-
siphon device must be used to prevent the flow of oil in case of an oil line break.
Support oil lines as required by codes.
Make tank connections with swing joints or copper tubing to
prevent breakage in case the tank settles. Make swing joints so they will tighten as tank settles. Non-hardening pipe joint compounds should be used on all threads.
Do not use Teflon tape as an oil pipe sealant. It can cause valves to fail, creating hazards. Use only flare fittings. Do not use compression fittings. Failure to comply could result in severe personal injury, death or substantial property damage from oil leakage and/or fire hazard.
Underground pipe must be run in a casing to prevent oil leaking
into the ground or under the floor. Check local codes for information.
Oil piping connection at burner
Connect oil line to burner using a flare fitting.
Use of any connection other than a flare fitting at the oil connection to the burner could result in a fuel oil leak, with the potential for severe personal injury, death or substantial property damage.
See local codes for appropriate arrangement and piping of filter,
control valves, etc. connecting to oil tank.
Refer to burner manual for oil system requirements. Verify that
suction lift does not exceed stated limit. Where lift exceeds limit for a one-pipe system, use a two-pipe system as directed in burner manual.
Page 13
TMP Oil FurnacesFurnace Manual
670-000-004/1010 13
Notes:
Page 14
TMP Oil Furnaces – Furnace Manual
14 670-000-004/1010
6 Wire furnace & burner
Electric shock hazard. It can cause severe personal injury or death if power source, including the service switch on the furnace, is not disconnected before installation or servicing.
Wire burner
The burner harness is factory-wired to the furnace. Plug the burner harness into the matching burner connector. Refer to the wiring diagrams on pages 15 and 16 for further information.
Install and wire thermostat
Locate the room thermostat on an interior wall in the natural circulating path of room air. Do not locate thermostat so it is exposed to cold air infiltration, drafts from windows or doors, air currents from supply or return air registers, behind obstructions, on a shelf, in a closet, or in a corner.
Ensure the thermostat won’t be exposed to heat from nearby fireplace, radio, television, lamp or rays from the sun. Do not mount thermostat on a wall over a supply or return duct, chimney or vent.
Wire thermostat to furnace and set thermostad anticipator as shown on wiring diagram, pages 15 and 16.
Figure 3
Blocked Vent Shut-Off device wiring (Optional)
 Blocked Vent Shutt-Off device (BVSO)  Electrical kit supplied.  Connect one red wire to limit switch.  Disconnect red wire from limit switch and connect to one red
wire from BVSO.
 Connect the green ground wire to a cabinet screw.
Connect power wiring
All wiring must conform to:
National Electrical Code, ANSI/NFPA 70, latest edition and any
additional national, state or local codes.
In Canada, CSA C22.1 Canadian Electrical Code Part One and
any local codes.
Wiring must be N.E.C. Class 1. If original wire, as supplied with
furnace, must be replaced, type 105
o
C wire or equivalent must be used. Supply wiring to furnace and additional control wiring must be 14 gauge or heavier.
Provide electrical ground at furnace as required by codes.
Connect 120 VAC/60 Hertz, single phase separate electrical line from the main house panel to the power leads in the external junction box as shown on wiring diagrams on pages 15 and 16. Provide a fused disconnect in the power wiring, following all local codes.
Ensure the wire size and type are adequate for the electrical load (see Section 12 and furnace nameplate for value).
Limit control
The furnace is equipped with a fan switch/limit control. This control limits the air leaving the heat exchanger to 200
o
F or less. The fan switch continues fan operation until the air drops to a preset temperature. For most installations, set the blower ON setting at 130
o
F and blower OFF setting at 90oF. If a longer cool down period
is desired, lower the OFF setting.
Counterflow furnaces also contain an automatic reset auxiliary limit control to prevent blower motor and filters from being overheated.
1
2
5 3
4
Page 15
TMP Oil FurnacesFurnace Manual
670-000-004/1010 15
6 Wire furnace & burner (continued)
PLB Oil Furnaces – Furnace Manual
Figure 4 Wiring – TMP furnaces with direct-drive blowers.
DNS-0888 Rev.E
Page 16
TMP Oil Furnaces – Furnace Manual
16 670-000-004/1010
6 Wire furnace & burner (continued)
PLB
Oil Furnaces – Furnace Manual
Figure 5 Wiring – TMP furnaces with direct-drive blowers.
DNS-0907 Rev. C
Page 17
TMP Oil FurnacesFurnace Manual
670-000-004/1010 17
Gasket for overfire pressure reading
7 Start up
Follow information below to prevent severe personal injury, death or substantial property damage:
Do not use gasoline, crankcase drainings or any oil
containing gasoline. See burner manual for proper fuel oil.
Do not attempt to start burner when excess oil has
accumulated, when unit is full of vapor or when combustion chamber is very hot.
Do not start burner unless collector box, venting and
burner mounting plate are secured in place.
Never burn garbage or paper in the furnace.
Never leave combustible material around it.
To start furnace
1. Factory burner adjustment and settings may not be suitable for specific job conditions. Refer to burner manual for burner start up, adjustment and checkout procedures.
2. Set room thermostat to call for heat.
3. Start burner as described in burner manual.
4. The furnace blower will delay for a short time after burner starts, until the Limit/Fan switch senses air temperature above the fan ON setting.
5. Set room thermostat to its lowest setting. Burner should turn off.
6. Furnace blower will continue to run until the Limit/Fan switch senses air temperature below the fan OFF setting.
7. Set the room thermostat to call for heat again. Allow furnace to heat to design temperature. Then adjust burner for correct combustion, using combustion test equipment. Adjust burner for:
Draft: -0.00” to +0.035” water column draft in furnace combustion chamber.
For pressure reading, replace the sight glass by the gasket supply with the appliance.
After the verification, put back in place the sight glass. See Figure 3.
CO
2
: between 10% and 11½ %, with 0 smoke.
To start furnace (continued)
Make final burner adjustments using combustion test equipment to assure proper operation.
8. Check furnace and duct system for proper operation and conditions.
9. Inspect vent system for proper operation.
10. To set Limit/Fan switch:
The blower operates until the air temperature drops below the fan OFF setting. If the air at the supply registers is too warm at blower start up or shutdown, lower the fan OFF and ON settings on the Limit/Fan switch.
To check operation of the limit switch, slide a piece of cardboard into the furnace filter slot. After a few minutes of operation (not more than 5 minutes), the burner should shut off (limit switch open). The blower will operate until the furnace cools down. Remove cardboard when finished.
11. Perform complete test of the burner cad cell control as per the burner manual instructions.
To shut down furnace
1. Set the room thermostat to its lowest setting.
2. Turn off the disconnect switch on the 120-VAC power line to the furnace.
3. If the burner will be shut down for an extended time, tightly close all oil valves.
4. Refer to burner manual for any additional instructions.
Figure 6
DNS-1092 Rev. A
Page 18
TMP Oil Furnaces – Furnace Manual
18 670-000-004/1010
8 Checkout procedure
Furnace selection
.. 1. Heat loss ............................... BTU/h at ............ oF outdoor
design temperature.
.. 2. Furnace model.......................................................................
output .......................... BTU/h.
.. 3. Burner model ........................................................................
nozzle: ............. gph ................
o
type............... .
.. 4. Burner pump pressure ........................................ psig.
Furnace installation
.. 5. Is furnace level?
.. 6. Are return and supply ducts securely attached to furnace?
.. 7. Are fuel filter and fuel lines installed and inspected as per
the burner manual?
.. 8. Are furnace and burner wired as per the wiring diagram?
.. 9. 120 VAC wiring: type ................ size ................ AWG.
Vent and combustion air
..10. Was existing chimney/vent system inspected and found in
proper condition?
.. 11. Was new vent piping installed and sealed as required?
..12. Was vent sizing checked against furnace manual and
codes?
Ductwork
..13. Was duct sizing checked against furnace manual and/or
ACCA Manual D?
.. 14. Were supply and return registers checked for size based on
airflow?
.. 15. Were balancing dampers installed as needed?
..16. Was ductwork sealed and insulated as needed?
Furnace operation
.. 17. Is a / Are clean air filter(s) in place?
.. 18. Was temperature rise through furnace checked (not to
exceed 85
o
F) and blower speed adjusted if necessary?
.. 19. Was thermostat heat anticipator set per wiring diagram?
.. 20. Was burner started and tested per burner manual?
.. 21. Is there proper draft and burner flame? Were final
adjustments made with combustion test equipment?
.. 22. Was air purged from oil piping and piping checked for leaks?
.. 23. Was burner sealed to furnace and nuts tightened? Was
burner harness securely plugged in?
Obtain gas-tight seals at burner flange, cleanout plates and/or flue collector box to prevent possible flue gas leakage and carbon monoxide emissions, leading to severe personal injury or death.
.. 24. Was Limit Control tested per “To start up” in this manual?
.. 25. Was furnace cycled with thermostat? Raise to highest
setting and verify furnace goes through normal start up cycle. Lower to lowest setting and verify furnace goes off.
.. 26. Were several operating cycles observed for proper
operation?
.. 27. Were room thermostat(s) set to desired room temperature?
After installation
.. 28. Was “Installation and service certificate” (below) filled out?
.. 29. Was Owner’s information in this manual reviewed with
owner or maintenance person and the person instructed to keep the manual for future reference?
.. 30. Were all instruction manuals placed near the furnace for
future reference?
Installation and service certificate
Furnace model__________________________________________________ Series _______________________
Serial number_______________________________________Date installed _____________________________
Installation instructions have been followed.
Checkout sequence has been performed. Above information is certified to be correct. Information received and left with owner/maintenance person.
Installer ______________________ ________________________ _____________________
(company) (address) (phone)
________________________________________________ (installers signature)
Page 19
TMP Oil FurnacesFurnace Manual
670-000-004/1010 19
9 Troubleshooting
Check 120 volt supply to furnace. If there is no supply To successfully service the oil furnace, you must voltage, check fuses and service switch. CAUT ION : have these instruments : When testing electrical equipment, always follow smoke tester standard electrical safety procedures.
carbon-dioxide (CO
2
) or oxygen (O2) analyzer draft gauge (scale should read from -.01” w.c. to -.25” w.c.) volt/ OHM/mi lliamper multimeter pressure gauge capable of reading 0-150 lb/sq. inch (for oil only)
Be familiar with these instruments as well as the burner manufacturers recommended settings.
Before beginning these troubleshooting procedures, ALWAYS :
Make sure thermostat is calling for burner operation.
Check oil supply and make sure all valves are open.
Symptom – B urner
Check fuses and make sure service switch is on.
Check for voltage from primary relay to burner motor. Make sure th e primary relay has not locked out on s afety.
Check for line voltage into furnace jun ction box.
Ma ke s ure the t her m ost at i s ca l lin g f or he at a nd that the wiring to th e thermo stat is co rr ect and t ight.
If the primary relay control is not popping out the reset button, measure the milliamperage at the thermostat and set the heat-an ticipator accordingly . A lso check wiring from the thermostat to the burner.
Check the alignment of the cad cell to ass ure it is aimed at the fire.
Ch eck noz zle a nd elec trode po sit ion . Check ig niti on tra nsf orm er ou tpu t
(Reference burner man ufacturers instructions).
Check tube insertion and alignment. Check nozzle and electrode position
(Reference burn er ma nufacture rs instructions).
Replace nozzle. Check pump pressure (varies with
manufacturer and application; see burne
r
manual).
Check overfire draft.
1. Remove CAD cell leadwires from the f -f terminals on the primary safety control, then start burner. Shortly after burner starts, place a temporar y jumpe r between terminals f-f. Connect ohmeter across CAD cell leadwires-resistance should b e under 1,600 ohms.
3. With burner off, check dark cel l resistance acros s CAD cell leadwires. Resistance should be greater than 20,000 ohms. If cell resistances are different from above, reche ck wiring and lo cation of cell , etc. If necessary , rep lace plug-in portion of ce ll.
2. Stop burne r and remove tem porary jumpe r.
Possible correction s :
To check CAD cell operation, use the following procedure :
Burner mo tor does not sta rt.
Unable to achieve clean combustion by setting air adjustments.
Burner short cycles or locks out on primary relay safety.
Symptom – Furnace blower
Check for 120V to the blower motor. If present, replace motor.
Check wiring from Fan and Limit control. See if blower motor will run when it is switched on manually at the thermostat sub-base (if sub­base is installed).
Blower short cycles on limit control.
Return ducts may be undersized.
Possible corrections :
Adjust fan "off" setting at 90
o
and adjust fan
"on" setting setting at 130
o
.
Furnace blower will not start.
Blower cycles on and off after the burner has shut down.
Page 20
TMP Oil Furnaces – Furnace Manual
20 670-000-004/1010
10 Service and maintenance
Follow the “Service and maintenance” procedures given throughout this manual and in component literature shipped with the furnace. Failure to perform the service and maintenance could result in damage to the furnace or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death or substantial property damage.
The furnace should be inspected and started annually, at the beginning of the heating season, only by a qualified service technician. In addition, the maintenance and care of the furnace designated in the table below, and explained on the following pages must be performed to assure maximum furnace efficiency and reliability. Failure to service and maintain the furnace and system could result in equipment failure.
This furnace contains fiberglass and ceramic fiber materials. These materials require special attention. Please refer to the WARNING and guidelines given on page 21. Failure to comply could result in severe personal injury, death or substantial property damage.
Consult with homeowner to see if there were any Check sequence of operation
problems with furnace or system during the prior Check flame characteristics
heating season (or cooling season) Perform combustion checks/tests per burner manual and
Clean, inspect, and lubricate blower motor and wheel furnace manual
Check condition of electrical wiring and tightness of
Check temperature rise
terminals and connectors Check thermostat heat anticipator setting
Clean and inspect heat exchanger and combustion Check safety controls (high-temperature limit switch, flame
chamber
cutoff time, etc.)
Clean and inspect system accessories
Vent system
Clean and inspect flue pipe, chimney/vent, and draft regulator
Fuel oil system
Check oil tank and piping for leaks
Replace oil filter
Oil burner
Clean and inspect oil burner assembly
Bleed system of air (single-pipe system)
Check oil pump pressures
Check combustion air ducts, grilles, etc. (if applicable)
Furnace and air system
Service and maintenance
Service technician annual maintenance/start up
(see following pages and burner manual for instructions)
Check operation
Annual start up
Page 21
TMP Oil FurnacesFurnace Manual
670-000-004/1010 21
Handling ceramic fiber and fiberglass materials
HANDLING OR REMOVAL OR COMBUSTION CHAMBER
The combustion chamber in this product contains ceramic fiber materials. Ceramic fiber can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline silica inhaled in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1)”.
Avoid breathing dust and contact with skin and eyes.
Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA
requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH web site at http://www.cdc.gov/niosh/homepage.html
. NIOSH
approved respirators, manufacturers, and phone numbers are also listed on this web site.
Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
Apply enough water to the combustion chamber lining to prevent airborne dust.
Remove combustion chamber lining from the furnace and place it in a plastic bag for disposal.
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer
thoroughly.
NIOSH stated First Aid.
Eye: Irrigate immediately
Breathing: Fresh air.
HANDLING OR REMOVAL OF FIBERGLASS WOOL – OR – INSTALLATION OF FIBERGLASS WOOL OR COMBUSTION CHAMBER:
This product contains fiberglass jacket insulation and ceramic fiber materials in combustion chamber. Airbone fibers from these materials have been listed by the State of California as a possible cause of cancer through inhalation.
Avoid breathing dust and contact with skin and eyes.
Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA
requirements for fiberglass wool at the time this document was written. Other types of respirators may be needed depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH web site at
http://www.cdc.gov/niosh/homepage.html
. NIOSH approved respirators, manufacturers, and
phone numbers are also listed on this web site.
Wear long-sleeved, loose fitting clothing, gloves, and eye protection.
Operations such as sawing, blowing, tear out, and spraying may generate airbone fiber
concentration requiring additional protection.
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer
thoroughly.
NIOSH stated First Aid.
Eye: Irrigate immediately
Breathing: Fresh air.
Page 22
TMP Oil Furnaces – Furnace Manual
22 670-000-004/1010
10 Service and maintenance (continued)
To lubricate and inspect blower motor
DO NOT lubricated the oil burner motor or the direct drive blower motor as they are permanently lubricated.
Clean blower wheel – Vacuum dust from blower wheel blades and surrounding area.
To clean heat exchanger
The heat exchanger must be cleaned and inspected at least once each year. Operating the furnace with a fouled or leaking heat exchanger could result in severe personal injury, death or substantial property damage.
The combustion chamber contains ceramic fiber materials. Wear a NIOSH-approved respirator while cleaning the furnace and follow WARNING on page 21 for proper handling.
1. Remove the burner and mounting plate.
2. Inspect the heat exchanger using a mirror inserted through the burner opening.
3. Using a brush on a flexible handle, loosen the soot on the inside of the heat exchanger.
4. Remove the soot with a vacuum. Be careful not to damage the combustion chamber while cleaning the heat exchanger.
5. Remove the heat exchanger cleanout covers of flue collector box. Using a brush on a flexible handle, loosen the soot from the heat exchanger surfaces. Remove as much soot as possible using a vacuum.
6. Replace cleanout covers.
7. Inspect combustion chamber and replace with a new one if chamber is damaged in any way.
8. Re-install burner and mounting plate.
Obtain gas-tight seal at burner flange and cleanout plates to prevent possible flue gas leakage and carbon monoxide emissions, leading to severe personal injury or death.
Inspect vent system
Thoroughly inspect the entire vent system at least annually, including horizontal vent pipe and chimney or vertical vent. Ensure vent system is repaired or replaced if necessary before placing furnace in operation.
Oiled-bearing burner motors
The burner may need to be lubricated if motor is equipped with oiling cups. Refer to burner manual for specific instructions. If instructed, apply a few drops only of S.A.E. 20 detergent oil (never use household oils). Do not attempt to “fill up” the oil cup. Over-oiling can damage the motor.
Optional Blocked vent shut off (BVSO) cleaning
For continued safe operation, the Blocked Vent Shut Off System (BVSO) is required to be inspected and maintained annually by a qualified agency.
1. Disconnect the power to the appliance;
2. Remove the two screws holding on the BVSO assembly
cover;
3. Remove the cover;
4. Remove the two screws holding the thermal switch to the
assembly base;
5. Without removing the electrical wires, remove the thermal
switch and remove any build-up from the thermal switch surface;
D Do not dent or scratch the surface of the thermal switch. If the thermal switch is damaged, replacement is required.
6. Clear and remove any build-up or obstruction inside the heat transfer tube;
7. Re-mount the thermal switch to the assembly base;
8. Re-attach the assembly cover with the screws removed in step 2;
9. Re-establish power to the appliance.
Annual start up
Follow information below to prevent severe personal injury, death or substantial property damage:
Do not use gasoline, crankcase drainings or any oil
containing gasoline. See burner manual for proper fuel oil.
Do not attempt to start burner when excess oil has
accumulated, when unit is full or vapor or when combustion chamber is very hot.
Do not start burner unless collector box, vent and
burner mounting door are secured in place.
Never burn garbage or paper in the furnace.
Never leave combustible material around it.
To start furnace
1. Factory burner adjustment and settings may not be suitable for specific job conditions. Refer to burner manual for burner start up, adjustment and checkout procedures.
2. Set room thermostat to call for heat.
3. Refer to burner manual for start up.
4. The furnace blower will delay for a short period after burner starts, until the Limit/Fan switch senses air temperature above the fan ON setting.
5. Set room thermostat to its lowest setting. Burner should turn off.
6. Furnace blower will continue to run until the Limit/Fan switch senses air temperature below the fan OFF setting.
7. Set the room thermostat to call for heat again. Allow furnace to heat to design temperature. Then adjust burner for correct combustion, using combustion test equipment. Adjust burner for:
Draft: -0.01” to –0.02” water column draft in furnace combustion chamber. CO
2
: between 10% and 11 ½ %, with 0 smoke.
Make final burner adjustments using combustion test equipment to ensure proper operation.
8. Check furnace and duct system for proper operation and conditions.
9. Inspect vent system for proper operation.
10. To set Limit/Fan switch:
The blower operates until the air temperature drops below the fan OFF setting. If the air at the supply registers is too warm at blower start up or shut down , lower the fan OFF and ON settings on the Limit/Fan switch.
To check operation of the limit switch, slide a piece of cardboard into the furnace filter slot. After a few minutes of operation (not more than 5 minutes), the burner should shut off (limit switch open). The blower will operate until the furnace cools down. Remove cardboard when finished.
11. Complete testing of the burner cad cell control using the instructions in the burner manual.
Page 23
TMP Oil FurnacesFurnace Manual
670-000-004/1010 23
11 Components and replacement parts
Figure 7 Model TMP furnaces Component locations
B50098 Rev.A
Page 24
TMP Oil Furnaces – Furnace Manual
24 670-000-004/1010
B50098 Rev.B
ITEM DESCRIPTION PART #
1
Com plet e he at ex ch anger ( ite m 2, 3, 4, 5 & 6 incl ude d)
B30776-01
2
Top heat exc han ger
B30542-01
3
Gasket, heat exchanger
B30517
4
Hexa gon al flange nut 3/ 8-16 NC b ras s
F07O001
5
Com bust ion cha mbe r
B30518
6
Bottom heat exchanger
B30757
7
Washer 1 7/16 zinc
F06F015
8
Fro nt fi lter dr awer
B30507-01
9
Gasket, burner
B30534
10
Left side panel assembly (item 11 & 12 included)
B30550-04
11
Left side panel insulation
B30571
12
Left filter support
B30566-01
13
Rea r pan el a sse mbly (i tem 14 & 1 5 in cl uded )
B30549-01
14
Rea r pan el i nsu lat ion
B30572
15
Rea r f ilte r sup por t
B30555-01
16
Rea r B affl e
B30564
17
Divis ion pane l (wi thou t i tem 18)
B30567
18
Blower slide support
B30513
19
Right s ide pa nel as sem bly ( item 20 & 2 1 in clude d)
B30550-03
20
Right s ide pa nel insula tion
B30571
21
Right fi lter su ppor t
B30566-01
22
Upp er fr ont rein force r
B30556-01
23
Blower door assembly (item 24 included)
B30709-04
24
Doo r han dle
Z99F050
25
Cen ter f ron t pan el ass embly (i tem 26 i ncl uded )
B30703-01
26
Cen ter f ron t pan el i nsulatio n
B30570
27A
Fro nt rig ht ba ffle
B30569-01
27B
Fro nt l eft ba ffle
B30569-02
28
Bottom front panel assembly (item 29 included)
B30774-01
29
Bottom front panel insulation
B30773
30
Washer 3/8" AA zinc (for burner)
F06F005
31
Hexa gon al n ut 3/8- 16NC (for burn er)
F07F024
32
Sight glass
Z99F061
33
5" breech plate
B30459
34
Gasket, breech pl ate
B30415-02
35
Burner electrical kit
B30575
36
Cor ner cond uit
B30557
37
Electrical box cover ( without logo )
B40098-01
38
Tra nsfo rme r 12 0/2 4 VAC / 40 VA
L01F009
39
Thermosw itch 160-40F
R02N012
40
Thermosw itch 110-10F
R02N011
41
Rel ay SPDT 24V AC
L01H009
42
Electrical box (without control)
B30797
43
Ter minal str ip, 4 posi tion s
L05F009
44
Blower assembly (45, 47, 50, 51 and 52 included)
B01405-01
45
Blower 100-10T (housing and wheel included)
B03720-04
46
Belly band assembly (band, legs, nut & bolts included)
B01888
47
Mot or as sem bly 1/3 HP (mo tor , be ll ba nd & l egs inc lud ed)
B01890-01
48
Blower electrical kit
B02916
49
Blower side rails
B30433
50
Seal strip 1 1/2" x 13 1/8"
B01291-01
51
Cap aci tor 5 MF
L01I001
52
Cap aci tor hold er
B01024
11 Components and replacement parts (continued)
Model TMP furnaces
Par t n umber Descr ipt io n
CFB-1-W Combustibl e floor base HFB-1-W Horizontal f loor base DFVEST-1- W Counterfl ow vesti bule kit
Opt iona l kit
Page 25
TMP Oil FurnacesFurnace Manual
670-000-004/1010 25
12 Dimensions and ratings
Figure 5 Model TMP dimensional data – ALL DIMENSIONS IN INCHES
Flue pipe
Width Depth Height Width Depth Width Depth diam.
ABCJ KRS
TMP-105 21 21 57 19 3/4 19 3/4 19 3/4 19 3/4 5
Return air
(side)
Model
Furnace casing
Warm air supply
(top)
Maximum heating Filter Electrical Minim um Maximum Ship
temperature rise quantity load ampacity for fuse size weight
(oF)
and size
(amps)
wiring sizing
(amps) (pounds)
TMP-105 55 - 70 (1) 20 X 20 115 - 60 - 1 12.2 13.7 15 202
Model Volt - Hertz - Phase
DNS-0908 Rev. A
(BTU/h) (BTU/h) (GPH) @ 0.25" WC @ 0.50" WC (tons) @ 0.25" WC @ 0.50" WC
70,000 58,000 0.50 81.5 GT10-10 1/3 Med. - Low Med. - Low 3 800 770
88,200 72,500 0.63 81.0 GT10-10 1/3 Med. - Hi Med. - Hi 3 1060 970
105,000 85,200 0.75
80.2 GT10-10 1/3 High High 3 1350 1210
Direct-drive units
TMP-105
Blower speed
Maximum
cooling
capacity
Blower CFM
Installed
nozzle
AFUE
Blower
size
Blower
motor HP
Model
Input Output Firing rate
Page 26
TMP Oil Furnaces – Furnace Manual
26 670-000-004/1010
12 Dimensions and ratings
Model TMP-105, Burners data
Airflow data (CFM)
Pump Com bustion
pressure air adjustment
BTU/h
(PSIG)
(band/shutter)
70,000 0.50 0.50 - 70A 100 F0 Yes 2 3/4 #3383 0 / 4.5
88,200 0.63 0.50 - 70A 155 F0 Yes 2 3/4 #3383 0 / 8
105,000 0.75 0.60 - 70B 155 F0 No 2 3/4 #3383 0 / 7.5
Pump
pressure
BTU/h
(PSIG)
88,200 0.63 0.50 - 60A 155
105,000 0.75 0.60 - 60A 155
Pump
pressure
BTU/h
(PSIG)
70,000 0.50 0.50 - 60A 100
88,200 0.63 0.50 - 60A 155
105,000 0.75 0.60 - 60A 155
TMP-105
Bar # 0.50 / 0.50
Bar # 0.60 - 0.65 / 0.60
Bar # 0.75 / 0.75
CARLIN BURNER - EZ-1 - Tube insertion 5 3/16"
TMP-105
0 / 4
0 / 3
Model
Input
TMP-105
BECKETT BURNER - Model AFG (3450 RPM) - Tube insertion 5 1/8"
Input
Model
Firing ra te
USGPH
Nozzle
(Delavan)
Head
Low firing
rate baffle
Static disc
Combustion
air adjustment
RIELLO BURNER - Model 40-F3 - Tube insertion 5 3/16"
Model
Input Fi ring rate
USGPH
Nozzle
(Delavan)
(Turbulator / Band)
Firing ra te
USGPH
Nozzle
(Delavan)
Combustion
air adjustment
(Bar / Band)
0.1 0.2 0.3 0.4 0.5 0.6 0.7
Med-Low 820 810 795 785 770 760 750
Med-High 1115 1080 1045 1010 970 935 900
High 1435 1380 1325 1270 1210 1155 1100
Notes :
Airflow values in cubic ft per minute (CFM) rounded to neares t 5 CFM.
Data taken with filters in place.
External static pressure
Model Blower speed
TMP-105
Page 27
TMP Oil FurnacesFurnace Manual
670-000-004/1010 27
13 Owner’s information
The furnace must be inspected and started ANNUALLY, at the beginning of the heating season, only by a qualified service technician.
The service technician must perform annual service and maintenance on the furnace to ensure reliable operation. Failure to service and maintain the furnace and system could result in equipment failure, causing severe personal injury, death or substantial property damage.
As the owner, you nee to be aware of the following needs of your furnace. You must inspect and clean or replace the furnace filter monthly, as described below, and perform the other inspection procedures as well. Failure to maintain a clean filter will result in unsatisfactory cycling of the furnace and could lead to a no-heat condition. Failure to perform this maintenance could result in substantial property damage.
Follow all of the procedures below. Failure to comply could result in severe personal injury, death or substantial property damage.
Operating the furnace
1. The furnace should operate automatically on call for heat from the room thermostat.
2. If the furnace oil burner should shut down on flame failure, the burner primary control will lock out. Ask your service technician to show you the correct procedure to reset the primary control button. NEVER push the button more than once in an attempt to start the burner after lockout. Continued lockout of the control means something is wrong with the burner, controls or oil system. The condition must be corrected by a qualified service technician.
Daily inspection
1. Verify there are no combustible materials in the furnace room or near the furnace.
2. Verify the air openings to the furnace room are not obstructed in any way.
3. Verify the furnace seems to be operating normally. Notify your service technician immediately if you notice any abnormal behavior.
Monthly – inspect and clean/replace filter
1. Ask your service technician to show you the correct way to remove and clean your furnace filter. Replace the filter if you are unable to thoroughly clean it.
To shut down furnace
1. Set the room thermostat to its lowest setting.
2. Turn off the disconnect switch in the 120-VAC power line to the furnace.
3. If the burner will be shut down for an extended time, tightly close all oil valves.
4. Refer to burner manual for any additional instructions.
W-T Manufacturing 8201 W. Calumet Rd. •Milwaukee, WI 53223
Page 28
TMP Oil FurnacesFurnace Manual
X40105 Rev. K
Loading...