Cooling and Heating (Gas, Electric, Water, and Steam)
R-410A
Mod G
LD19506
FORM TPM3-EG1 (518)
Nomenclature
BASE MODEL NUMBER TMAL120–150
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
BASE PRODUCT TYPE NOMINAL CAPACITY APPLICATION REFRIGERANT VOLTAGE DUCT LOCATIONS DESIGN SPECIAL GAS HEAT CAPACITY
L : Scroll
A : Air-Cooled
M : Packaged Rooftop
T : TempMaster
0
2
1
1
1
: 120-ton
0
3
: 130-ton
0
5
: 150-ton
V : VAV or SZVAV
C : Cooling Only
N : Natural Gas Heat
G : Natural Gas Heat Stainless Steel Heat Exchanger
M : Modulating Gas Heat
E : Electric Heat
S : Steam Heat
H : Hot Water Heat
E : R-410A
6 : 460 / 3 / 60
4
8 : 575 / 3 / 60
5
B : Bottom Return
R : Rear Return
S : Side Return
B : Bottom Supply
L : Left Supply
R : Right Supply
N : No Gas Heat
L : Low (375 mbh)
M : Medium (750 mbh)
H : High (1125 mbh)
X : Standard Product, IPU
S : Special Product, IPU
FEATURES AND BENEFITS ................................................................................................................................... 7
APPLICATION DATA ............................................................................................................................................. 14
PHYSICAL DATA ................................................................................................................................................... 19
WEIGHT DATA ....................................................................................................................................................... 21
COOLING PERFORMANCE DATA .......................................................................................................................23
HEATING PERFORMANCE DATA – GAS/ELECTRIC HEAT ............................................................................... 38
SUPPLY FAN DATA ............................................................................................................................................... 39
ELECTRIC HEAT PRESSURE DROPS ................................................................................................................ 42
GAS HEAT PRESSURE DROPS ........................................................................................................................... 42
EXHAUST FAN DATA ............................................................................................................................................ 43
RETURN FAN DATA .............................................................................................................................................. 44
ELECTRICAL DATA .............................................................................................................................................. 45
POWER WIRING: TMAL120–150 ......................................................................................................................... 55
FIELD CONTROL WIRING ................................................................................................................................... 57
GENERAL ARRANGEMENT DRAWING – 120–150 TON MODELS .................................................................. 59
HOT WATER/STEAM COIL CONNECTION LOCATIONS .................................................................................... 65
POWER/CONTROL ENTRY DRAWING – 120–150 TON MODELS ..................................................................... 66
The TempMaster® OmniElite™ Single Package Units –
designed to meet the demands of the market for today and
tomorrow.
Better Economy...
Lower total cost of ownership
• TempMaster provides a standard product offering that meets the latest ASHRAE
90.1 energy efciency requirements.
• Unique compressor staging provides quick response to cooling needs and provides
multiple steps of capacity for high part load efciency.
• Fully modulating gas heat and greater steps of capacity control offer superior offdesign performance while maintaining optimum occupant comfort.
• Accurate ventilation control ensures that no more than the proper amount of ventilation air is utilized. This avoids the energy cost of conditioning excess outside air and
simultaneously monitors all other unit functions for maximized energy efciency.
• Flexible design congurations simplify the design process and allows the TempMas-
ter OmniElite to be applied to virtually any building application.
• Accessibility through double-wall access doors, spacious compartments and sup-
portive oors improves serviceability.
LD07431
The single package unit user interface uses microprocessor logic to optimize operation of the TempMaster OmniElite single package unit.
Better Ecology...
Indoor air quality (IAQ) features for the indoor environment
• A double-sloped stainless steel drain pan with a single drain connection ensures that all condensate is voided from the drain pan. It
is also visible and accessible for periodic inspection and cleaning re-
quired by the ASHRAE 62 IAQ standard.
• Double-wall construction of the roof, oor, doors, and walls prevents insulation bers from entering the conditioned air. The inner liner
also facilitates periodic cleaning of the unit to prevent harmful build-up
of bacteria or contaminants.
• The single package unit control center uses microprocessor
logic to analyze and optimize ventilation decisions and perform de-
mand ventilation, airow compensation, and airow measurement to
maintain the air quality at a healthy level.
TEMPMASTER
5
FORM TPM3-EG1 (518)
10
9
7
Exhaust Air
8
1. Modulating or staged gas heat
11
12
Outside Air
1
2
3
4
5
6
7
LD21646
7. Rain hoods
2. Condenser fans
3. Scroll compressors
4. Condenser
5. Advanced single package unit controller
6. Evaporator coil
FIGURE 1 - STANDARD CABINET ASSEMBLY
6
8. Exhaust/return fan
9. Economizer
10. Filters section
11. Double-wall construction
12. Double width, double inlet (DWDI) airfoil supply
fan
TEMPMASTER
Features and Benefits
AIRFLOW CONFIGURATIONS
Variable Air Volume (VAV) – TempMaster® OmniElite™ units are available for variable air
volume (VAV) applications. Control can be used with a zone sensor or building automation system (BAS). Supply fans are controlled to the supply duct static pressure setpoint,
which can be reset via a BAS, or through a 0–5VDC analog input on the unit controller for
optimized duct static pressure control. The static pressure transducer is provided in the
single package unit, and 5/16-inch or 1/4-inch plastic tubing and static pressure sensor
must be supplied by others and installed approximately 3/4 down the longest duct run.
Single Zone Variable Air Volume (SZVAV) – TempMaster OmniElite units are available
for single zone variable air volume (SZVAV) applications. Control can be used with a zone
sensor or a BAS. Supply fans are controlled based on zone temperature.
COOLING AND HEATING CONFIGURATIONS
FORM TPM3-EG1 (518)
Cooling Only – For applications where no heat is required, or heating is provided else-
where within the building HVAC system, cooling only units include an empty discharge
plenum. Supply duct connections are configurable for bottom, left or right discharge. The
supply air temperature (SAT) sensor is included and factory-installed.
Staged Gas Heat – For applications requiring gas heat for morning warm-up, or other
heating needs, a staged natural gas furnace is available. The furnace is located in the discharge plenum, downstream of the supply fan. The SAT sensor is located across the face
of the supply duct opening in the unit. Furnaces are designed in 375 mbh modules. Three
stages are available for the TMAL120–150. Ignition and safety controls are included and
factory-wired. Units with staged gas heat are ETL listed.
Modulating Gas Heat – For applications requiring gas heat for morning warm-up, supply
air tempering or other heating needs, a modulating natural gas furnace is available for finer
temperature control. The furnace is located in the discharge plenum, downstream of the
supply fan. The SAT sensor is located across the face of the supply duct opening in the unit.
Furnaces are designed in 375 mbh modules in 8:1 turndown increments. Three are available for the TMAL120–150 (8:1, 16:1 or 24:1 turndown). Ignition and safety controls are
included and factory-wired. Units with modulating gas heat are ETL listed.
Electric Resistance Heat – For applications where electric heat is desired, a slip-in electric resistance heat element is available in sizes from 80–250 kW depending on the single
package unit model size. The number of stages varies by size and voltage, but all have a
minimum of two stages of capacity. Units with electric heat are ETL listed.
Hot Water Heat – For applications where hot water is available for heating, a hot water
heating coil is available. A range of coil fin count selections are available to properly size
the heating for the application. Units with hot water heat are ETL listed.
Steam Heat – For applications where steam is available for heating, a steam heating coil
is available. A range of coil fin count selections are available to properly size the heating
for the application. Units with steam heat are ETL listed.
TEMPMASTER
7
FORM TPM3-EG1 (518)
Features and Benefits (Cont'd)
POWER OPTIONS
Single-Point Supply with Terminal Block – This configuration is standard, and includes
three terminals for the incoming 3-phase power and is the standard configuration for the
TempMaster OmniElite product. It includes the enclosure, terminal-block, and interconnecting wiring to the compressors, heater and furnace controls, all fans, etc. In this con-
figuration, code requires that a means of disconnect (not provided) must be installed at
the site within line-of-sight of the equipment.
Single-Point Supply with Non-Fused Disconnect Switch – This option is the same as
the single-point with terminal block option except it includes a unit-mounted through-thedoor manual non-fused disconnect switch with an external, lockable handle (in compliance with Article 440-14 of National Electric Code (NEC)). This option provides a means
to isolate the unit power voltage for servicing. Others must supply separate external fusing
which must comply with the NEC and/or local codes.
Dual-Point Supply with Terminal Block – This option includes enclosure, terminal blocks
circuited to the supply and exhaust fans and control transformer, and a second set of
terminal blocks with interconnecting wiring to the compressors, heat (if applicable), and
condenser.
Convenience Outlet – This options includes a powered 115V GFCI convenience outlet that
can be used for powering tools or lights for servicing. A protective cover plate is included
while not in use. The outlet is located on the bottom left hand corner of the power panel.
CONTROL FEATURES AND OPTIONS
Microprocessor-Based Single Package Unit Controller – All TempMaster OmniElite
units are equipped with a factory-installed, programmed and commissioned unit controller
with all I/O capabilities and control sequences. The controls include all on-board diagnostic,
safety and control features to operate the single package unit. A multimedia card interface
is included for software upgrades and can be used for data logging to simplify equipment
troubleshooting. Communication ports are included as standard with three alarm outputs, a
shutdown contact, remote start/stop input, smoke ventilation controls, analog inputs for SAT
and duct static pressure reset, along with a variety of other capabilities.
Standard Ambient – TMAL120–150 models operate down to 50.0°F as standard.
Low Ambient – This option includes low ambient control of all three refrigerant circuits
down to 0.0°F through the use of suction and discharge pressure transducers, as well as
condenser fan speed using a variable frequency drive (VFD) on the first condenser fan of
each circuit.
Pressure Transducers with Readout Capability– This option includes suction and dis-
charge pressure transducers on each circuit and provides pressure readout of all circuits
at the unit control panel.
Wall-Mount Zone Sensor – A 10 kOhm thermister type III NTC zone sensor for wall
mounting. This zone sensor is for sensing temperature only and does not include any
setpoint adjustment features.
Zone Sensor
COMMUNICATIONS
BACnet® MS/TP (RS-485) Communications – This communication option is standard on
every TempMaster OmniElite unit. Communications to the unit are through a twisted pair,
and the wire terminations are on the primary unit control board. See supplemental information for the available control points and protocol implementation conformance statement (PICS)/BACnet® interoperability building blocks (BIBBs) statements of conformity.
8
TEMPMASTER
FORM TPM3-EG1 (518)
Modbus™ Remote Terminal Unit (RTU) Communications – This communication option
is standard on every TempMaster OmniElite unit and can be used in lieu of the BACnet
communications (only one can be used at a time). See supplemental information for the
available control points.
FILTER OPTIONS
Filter Options – Cleanable, carbon coated MERV 7 or pleated MERV 8 filters in an an-
gled rack are available. For higher filtration requirements, optional rigid filter racks are
available with 12-inch 65% MERV 11 or 95% MERV 14 efficient rigid filters. Two-inch prefilters are included with rigid filter options. The rigid filter rack option is available without
filter media where field-supplied filters are required.
OUTSIDE AIR DAMPER (OA) OPTIONS
Manual Damper – This option includes a manually adjustable outside air (OA) damper. It
is manually adjustable at the unit by setting a mechanical stop between 0–100%.
Two-Position – This OA damper option is controlled to two positions, opened and closed.
Determination of the damper position is based on the occupancy schedule. In the occupied mode, the OA damper is positioned to the manually configured point (set by mechanical stop). In the unoccupied mode, the damper is fully closed.
Modulating Economizer – This option includes modulating OA and return air (RA) dampers that are software interlocked and positioned by fully modulating, solid state damper
actuators. Control of the damper is via a standard ambient OA dry bulb sensor, or optional
single or comparative enthalpy controls.
Airflow Measurement – Optional outside airflow measurement is available on units
equipped with a modulating economizer.
CO2 Sensors – Optional carbon dioxide (CO2 ) sensors for occupied space that operate
demand ventilation control opening OA dampers to ventilate building. The CO2 sensors
can operate in a single or comparative control scheme.
Rain Hoods on Outside Air (OA) Intakes – For all options with OA intake openings, rain
hoods are provided as standard to keep moisture from entering the equipment. The rain
hoods are an integral part of the unit and are rotated into place at the job site.
RELIEF SYSTEM
Barometric Relief – Optional building air exhaust shall be accomplished through baro-
metric relief dampers installed in the return plenum. The dampers will open relative to the
building pressure. The opening pressure shall be adjustable via a spring tension adjustment.
On/Off Powered Exhaust – This option provides simple building pressure control. It can
be controlled via a building pressure signal, or via OA damper control. This option is not available for VAV units.
Modulating Powered Exhaust with Damper Control – This option consists of a constant-speed exhaust fan with a discharge damper that is modulated to control the flow
of exhaust air. The damper control logic is based on the building static pressure setpoint
within the single package unit controller. The static pressure transducer is provided in
the return plenum of the single package unit, and 5/16-inch or 1/4-inch plastic tubing and
static pressure sensor must be supplied by others and installed in a representative location in the building.
TEMPMASTER
9
FORM TPM3-EG1 (518)
Features and Benefits (Cont'd)
Modulating Powered Exhaust with a VFD – This option consists of a VFD to modulate the
speed of the exhaust fan to control the flow of exhaust air. The VFD control logic is based
on the building static pressure setpoint within the single package unit controller. The static
pressure transducer is provided in the return plenum of the single package unit, and 5/16inch or 1/4-inch plastic tubing and static pressure sensor must be supplied by others and
installed in a representative location in the building.
Powered Return Fan with Exhaust – This option uses single width, single inlet (SWSI)
plenum fan(s) to control building pressure. The fan motors are driven by a VFD to maintain
a constant return plenum pressure. An exhaust hood with a modulating control damper
is used to maintain building pressure via the building static pressure. The static pressure
transducer is provided in the return plenum of the single package unit, and 5/16-inch or
1/4-inch plastic tubing and static pressure sensor must be supplied by others and installed
in a representative location in the building. The powered return fan is also available without the exhaust capabilities. For units with no exhaust capabilities, the HVAC system must
provide alternate means of controlling building pressure.
SUPPLY FAN OPTIONS
Double Width, Double Inlet (DWDI) Airfoil Supply Fan – The standard airfoil blade sup-
ply fan is available on all models for higher static conditions. This offers higher efficiency
and lower sound in certain applications.
Fan Skid Isolation – The entire supply fan assembly is isolated from the unit base with
either 1-inch (standard) or 2-inch deflection springs with seismic restraints.
Supply and Exhaust Fan Motors – Premium efficiency open drip-proof (ODP) and premium efficiency total enclosed fan-cooled (TEFC) motors are available all meeting the
Energy Policy Act of 1992 (EPACT).
Supply Fan VFD and Manual Bypass – For VAV applications, VFDs are provided to
modulate air flow. Optional manual bypass can also be provided to allow full airflow in the
event of a VFD failure.
Direct Drive Plenum (DDP) Fan – A direct drive plenum (DDP) supply fan provides outstanding reliability and efficiency, eliminating the possibility of conditioned air supply interruption due to a broken belt and the pollution of conditioned air with belt dust. The supply
fan can be optionally equipped with a piezo ring to precisely measure the amount of air
delivered to the conditioned space. The speed of the supply fan is controlled by a VFD.
EVAPORATOR SECTION
Double Sloped Stainless Steel Drain Pan – The TempMaster OmniElite’s stainless steel
drain pan is factory-mounted and installed on every unit. A condensate drain trap is needed and must be provided and installed in the field by others.
*NOTE:
This is a visual reference only. Actual drain pan pitch will vary.
FIGURE 2 - DRAIN PAN DETAIL
10
LD08022
TEMPMASTER
FORM TPM3-EG1 (518)
Double-Wall Construction – Double-wall construction is the standard construction of the
TempMaster OmniElite and incorporates powder coated pre-fabricated outer panels and
corner post for maximum exterior surface protection.
Factory Shrink-Wrap – All TempMaster OmniElite single package units are shipped from
the factory with factory-fresh shrink-wrap packaging. No longer does the contractor need
to worry about dirt and debris clogging up condenser coils or moisture leaking into the air
handler on the units way to the job site or rigging yard.
Copper Fins – For more extreme climates that aggressively can attack aluminum, copper
tube evaporator coils with copper fins are available. (This is not recommended for units in
areas where they may be exposed to acid rain or environments where ammonia is present.)
CONDENSER FEATURES AND OPTIONS
Scroll Compressors – Reliable, efficient, trouble-free operation is the true measure of
a single package unit’s value. That’s why TempMaster OmniElite single package units
use established scroll compressor technology to deliver dependable, economical performance in a wide range of applications. With the TempMaster OmniElite single package
units, you get the latest generation of compressor enhancements added to the scroll’s
inherent strengths. The simplicity of a hermetic scroll compressor allows the use of fewer
moving parts to minimize breakdown.
Compressor Circuiting – The TempMaster OmniElite is designed so that only two scroll
compressors are in tandem within one refrigeration circuit. This means more reliable com-
pressors, and less equipment down time. With multiple circuits, if a compressor should
ever fail on one circuit, the other circuit/s will remain operational to work to maintain occupied loads. The TempMaster OmniElite system has three circuits in a unit.
Compressor Staging - The TempMaster OmniElite refrigeration system is equipped with
a unique staging algorithm. On first call for cooling the system calculates the amount of
cooling capacity needed by the space and automatically brings on enough cooling capacity to meet this calculated need. Comfort cooling is provided quickly without the lag inherent to staging on additional compressors to meet a high demand. Additionally, due to a
three independent circuit design with two compressors on each circuit, the TempMaster
OmniElite can provide superior granularity in terms of staging, which translates to best in
class part load efficiency or IEER.
Condenser Fan Motors – The condenser fan motors used on the TempMaster OmniElite
unit are totally enclosed air over (TEAO) to provide maximum durability through any season.
Replaceable Core Liquid Line Driers – Liquid line driers are standard on the TempMas-
ter OmniElite single package unit.
Post-Coated Condenser Coil Fins – Technicoat coil-coating process used on condenser
coils for seashore and other corrosive applications (with the exception of strong alkalis,
oxidizers, wet bromide, chlorine, and fluorine in concentrations greater than 100 ppm).
Compressor Sound Blankets – Optional compressor acoustic sound blankets are available for sound sensitive applications.
TEMPMASTER
11
FORM TPM3-EG1 (518)
Features and Benefits (Cont'd)
ROOF CURBS
Full Perimeter Roof Curbs – This option includes a knock-down 14-inch high roof curb
for use with wood nailer (by others). Roof curb supports the entire perimeter of the unit.
Partial Perimeter Roof Curbs – This option includes a knock-down 14-inch high roof
curb for use with wood nailer (by others). Roof curb supports the air handling section with
a separate support under the condenser end.
CABINET FEATURES AND OPTIONS
Double-Wall Access Doors - Full-sized access doors provide easy access into the unit
for routine maintenance and inspection. Solid wall liners encase insulation and prevent
damage and erosion into the airstream.
Diffuser Section – An optional diffuser section is available downstream of the supply
fan in the extended discharge plenum cabinet option. The diffuser section distributes the
airflow from the fan evenly across the downstream filter bank to optimize filter life and
effectiveness. The diffuser design is optimized to provide uniform flow at minimal airside
pressure loss.
Downstream Final Filter Rack – A 90–95% efficient MERV 14, 12-inch rigid filter rack
and filters shall be provided downstream of the supply fan and diffuser segment for hospital applications. A magnahelic pressure gauge is included and visible from the outside of
the unit for servicing and code compliance.
Blank Section – A blank section shall be provided downstream of the supply fan and diffuser section.
ACCESSORIES
Filter Switch – An optional dirty filter alarm can be provided that will provide an alarm
when the filters require cleaning.
Magnahelic Filter Pressure Gauge – On units equipped with downstream filtration, a
magnahelic filter gauge is included and visible on the exterior of the unit. The filter gauge
measures the air pressure drop for through the rigid filter bank to indicate when replace-
ment is required.
12
TEMPMASTER
TMAL120–150 MODEL
section
dust and dirt build-up
• Located in conditioned space
Blower variable frequency
drives (VFDs)
• In ltered air stream to prevent
• Remote keypad in control
Side discharge with heat
structure or curb
• Does not require an elevated
application
• Flexible solution for building
FORM TPM3-EG1 (518)
• Standard low ambient to 0.0°F
• Control to discharge pressure
• Quiet part load operation
Shared-fan design
• Eliminates stratication
• Fewer moving parts
• Solid steel shaft
• Isolated assembly
• Laser aligned and
Single supply fan
balanced
risk of carryover
• Angled coil to reduce
steel drain pan
• Standard stainless
Evaporator
• OA from two sides
• Facilitates mixing
Mixing box
• Induced draft furnace
• Accepts gas pressures down to 4.5-inches
• Six-stage base design
24:1 modulating gas heat
control solution
™
communications
™
ISN ConneXsys
®
MS/TP and Modbus
®
• Multimedia card for updates (no EPROM)
• Multimedia card used for data logging
• Integrated TempMaster
• Standard BACnet
Advanced single package unit controller
centrifugal exhaust fans
• Horizontal return for all congurations
• Double width, double inlet (DWDI)
num return fans
• Variable frequency drive (VFD) options
• Single width, single inlet (SWSI) ple-
Exhaust & return fans
TEMPMASTER
ping to reduce freight
• Single piece shipment
• Collapsible for ship-
Collapsible outside air
(OA) hoods
• Fast and easy setup
13
FORM TPM3-EG1 (518)
Application Data
GENERAL
The TempMaster® OmniElite™ air conditioning units are designed for outdoor installation.
When selecting a site for installation, be guided by the following conditions:
• Unit must be installed on a level surface.
• For the outdoor location of the unit, select a place having a minimum sun exposure
and an adequate supply of fresh air for the condenser.
• Also avoid locations beneath windows or between structures.
• Optional condenser coil protection should be used for seashore locations or other harsh
environments.
• The unit should be installed on a roof that is structurally strong enough to support the
weight of the unit with a minimum of deection. It is recommended that the unit(s) be
installed not more than 15 feet from a main support beam to provide proper structural
support and to minimize the transmission of sound and vibration. Ideally, the center
of gravity should be located over a structural support or building column.
• Location of unit(s) should also be away from building ue stacks or exhaust ventilators to prevent possible reintroduction of contaminated air through the outside air
intakes.
• Be sure the supporting structures will not obstruct the duct, gas or wiring connections.
• Proper service clearance space of 6 feet around the perimeter of the unit, 8 feet on
one side for coil servicing, and 12 feet to any adjacent units is required to eliminate
cross contamination of exhaust and outside air, and for maintenance tasks such as
coil pull and cleaning. No obstructions should be above the condensing unit section.
LOCATION
Of the many factors that can effect the location of equipment, some of the most important
to consider are structural, acoustical and service clearances. Proper attention should be
made at the design stage to ensure proper structural support. In cases where equipment
is being replaced, be aware of building design to ensure support is adequate for the ap-
plication.
The next most important consideration in applying single package units equipment is that
of sound from the equipment. Special care should be made to keep the single package
unit away from sound sensitive areas such as conference rooms, auditoriums and executive offices and any other room that may have potential for tenant occupancy. Possible
locations could be above hallways, mechanical or utility rooms.
Finally, service clearances should be maintained in single package unit design to ensure
safe access to the unit. Unit clearances are designed so that technicians have enough
space between units, building walls, and edges of building to gain access safely. In cases
where space is limited, please call a local TempMaster representative for additional information.
14
TEMPMASTER
FORM TPM3-EG1 (518)
RIGGING
Proper rigging and handling of the equipment is mandatory during unloading and setting
it into position to retain warranty status.
Spreader bars must be used by cranes to prevent damage to the unit casing. All lifting
lugs must be used when lifting the single package unit. Fork lifts will damage the single
package unit and are not recommended.
Care must be taken to keep the unit in the upright position during rigging and to prevent damage to the watertight seams in the unit casing. Avoid unnecessary jarring or rough handling.
UNIT PLACEMENT
• Elevated – Elevated roof curbs or dunnage steel can be used to support the unit in
order to raise it to specic heights. When this type of placement is required, be sure
to keep unit access in mind. Cat walks or other forms of unit access may be required
to one or both sides of the unit, depending on your area of the country and the local
codes that are enforced. Please check with local ofcials to ensure the application
conforms to local codes and regulations.
• Ground Level Locations – It is important that the units be installed on a substantial
base that will not settle, causing strain on the refrigerant lines and sheet metal and
resulting in possible leaks. A one-piece concrete slab with footers extended below
the frost line is highly recommended. Additionally, the slab should be isolated from
the main building foundation to prevent noise and vibration transmission to the building structure.
For ground level installations, precautions should be taken to protect the unit from
tampering by, or injury to, unauthorized persons. Erecting a fence around the unit is
common practice.
• Roof curb – TempMaster offers optional roof curbs designed specically for the
TEMPMASTER
TempMaster OmniElite footprint. These curbs come in full perimeter or open condenser models and are shipped disassembled and require eld assembly and installation. For bottom supply and return openings, the curbs have matching connections
to ease installation. A pipe chase that matches the single package unit pipe chase is
also included in the curb footprint for through-the-curb utility connections.
15
FORM TPM3-EG1 (518)
Application Data (Cont'd)
The curb should be located according to the location recommendations above, and
properly sealed to prevent moisture and air leakage into and out of the duct system.
Flexible collars should be used when connecting the ductwork to prevent unit noise
transmission and vibration into the building.
Ductwork should be supported independently of the unit.
TABLE 1 - SUPPLY AIR DUCT CONN CONFIGURATIONS
SUPPLY AIR
TMAL
120–150
UNIT CONFIGURATION
Cooling onlyXXX
Cool/electric heatX
Cool/gas heatXX
Cool/hydronic heatX
Cooling onlyXXX
Cool/hydronic heatXXX
BOTTOMLEFTRIGHT
STANDARD CABINET
EXTENDED CABINET
TABLE 2 - RETURN AIR DUCT CONNECTION CONFIGURATIONS
RETURN AIR
XX
TMAL
120–150
UNIT CONFIGURATION
No exhaustXX
Barometric
relief damper
Powered exhaust fan (all types)XX
Powered return fanX
BOTTOMFRONT
UNIT ORIENTATION
For applications with multiple single package units located in close proximity on the roof,
the orientation of the unit may be important to reduce the potential for re-entrainment of
outside airflow. Regardless of the outside air and exhaust air openings on a unit, all single
package unit applications can permit recirculation of exhaust air to the return, if applied
improperly.
HORIZONTAL APPLICATIONS
The spectrum of applications for single package units in today’s market is continuing to
grow wider by the day. Flexibility in unit design and construction is a must in today’s mar-
ket in order to ensure safe and sound applications of HVAC equipment. The TempMaster
OmniElite has been designed for specific application of horizontal supply and return airflow taking the guess work out of unit application by building a unit specific to these needs.
If the application calls for horizontal supply and return air, TempMaster can ship it from the
factory as a horizontal unit. This option eliminates the need for field modification of equipment saving time and money. The TempMaster OmniElite can support a left discharge on
all units except electric heat and/or right discharge on all cooling only units and hydronic
heat units with an extended cabinet. Return air can be brought through the front or bottom
return air inlet making the unit specific to building needs.
16
TEMPMASTER
FORM TPM3-EG1 (518)
TOP VIEWSIDE VIEW
LD08045
FRONT
FRONT
NOTE: This diagram is provided as a visual reference of the TempMaster OmniElite discharge air (DA) & return air (RA) openings & locations
for all sizes. Please refer to the dimensional data for exact size & location of panels and openings.
ECONOMIZER
The economizer section is used for ventilation of the conditioned space to maintain indoor
air quality (IAQ), and also to reduce energy consumption by using outside air cooling in lieu
of mechanical cooling. If outside air is appropriate for cooling, but not sufficient for the cooling demand, mechanical cooling will stage on as necessary until the cooling load is met.
Dual (comparative or differential) enthalpy operation is the most accurate and efficient
means of economizer operation. The IPU controller monitors the return and outside air
energy content, and selects the lower of the two for operation.
VARIABLE AIR VOLUME (VAV) SUPPLY AIR PRESSURE CONTROL
Traditional single package unit systems use inlet guide vanes (IGVs) for duct static pressure control. These control supply duct pressure by modulating dampers (introducing losses
and inefficiencies) on the inlet of the fan, open and closed. TempMaster variable frequency
drives (VFDs) offer superior fan speed control and quieter, energy efficient operation.
FIGURE 3 - TRADITIONAL OVERHEAD VARIABLE AIR VOLUME (VAV) AIR
DELIVERY SYSTEM
For variable air volume (VAV) applications, the TempMaster OmniEliteunit uses a VFD
to modulate fan speed and maintain a constant duct static pressure. VFDs offer superior
control over the operation of the unit at part load, and offer the additional benefits of quieter and more efficient operation when compared to IGV.
BUILDING PRESSURE CONTROL SYSTEMS
Building pressure control systems are often necessary when economizers are used to
bring in outside air. Without proper building exhaust, the building may become over pressurized. The pressure control system maintains the proper building pressure by expelling
the appropriate amount of air from the building.
TEMPMASTER
17
FORM TPM3-EG1 (518)
Application Data (Cont'd)
Return fans – For high return static applications, such as buildings with ducted return
systems, a powered return fan may be necessary to maintain building pressure control.
TempMaster offers a powered return fan that is located in the return plenum. This fan
operates coincidentally with the supply fan and draws return air back through the return
ductwork and into a pressurized plenum. A control damper modulates to exhaust air out
of the building and maintain the building pressure. A second control damper modulates
to provide return air from the ductwork to the unit to the single package air mixing section.
The return fan configuration is available in two forms: with and without an exhaust damper.
The option with the exhaust damper provides a means of building exhaust at the unit. In
some applications, the exhaust system is located elsewhere and the single package unit
is not required to provide building exhaust. In these situations, the TempMaster OmniElite
can be offered without the exhaust damper to help reduce installed costs.
Exhaust/relief fans – In this application, a powered exhaust fan may be suitable, however careful consideration of the fan type is necessary. TempMaster offers a centrifugal
powered exhaust fan to perform this function. Some manufacturers use a propeller ex-
haust fan, which cannot handle the static pressure requirements.
For systems with moderate to low return static pressure, an exhaust fan is recommended.
The benefit of the exhaust fan is that it does not run all of the time, and may facilitate com-
pliance with the ASHRAE 90.1 fan motor horsepower requirement.
The exhaust fan operates in parallel with the supply fan. In this arrangement, the supply
fan handles the full static pressure requirements of the system. For normal building pressure control, the exhaust fan operates to draw air from the return plenum and exhaust it
out of the building.
The exhaust fan configuration is available in two forms, modulating and non-modulating.
Modulating is the most common and recommended for the majority of applications, while
non-modulating should be used in only certain circumstances.
In the modulating exhaust system, the volume of airflow exhausted from the building is
proportional to the entering volume of outside air. Control is accomplished via either a discharge damper or a VFD. TempMaster recommends the use of a VFD to reduce energy
consumption, sound levels and improved reliability due to fewer moving parts.
In the non-modulating exhaust system, the exhaust airflow is constant whenever the exhaust fan is operating. This type of control should only be used to either assist a smoke
purge system or when a system requires a constant volume of exhaust airflow.
ACOUSTICAL CONSIDERATIONS
The TempMaster OmniElite unit is designed for lower sound levels than competitive units
by using flexible fan connections, fan spring isolators, double-wall construction, multiple
fan options, and lower speed and horsepower fans. For VAV applications, VFDs are used
instead of inlet guide vanes. Additional sound attenuation can be obtained using compressor sound blankets when necessary.
Even with these equipment design features, the acoustical characteristics of the entire
installation must never be overlooked. Additional steps for the acoustical characteristics
of a single package unit installation should be addressed during the design phase of a
project to avoid costly alterations after the installation of the equipment. During the design
phase of a project, the designing engineer should consider, at a minimum, the impact of
the equipment location, single package unit installation, building structure, and ductwork.
18
TEMPMASTER
FORM TPM3-EG1 (518)
Physical Data
TABLE 3 - PHYSICAL DATA – MODELS 120–150
MODEL SIZE120130150
COMPRESSOR DATA
Quantity/Size (nominal HP)4x15/2x252x15/2x20/2x252X15/2X20/2X32
TypeScrollScrollScroll
Capacity Steps14 steps providing capacity control between 12 and 100%
DOUBLE WIDTH, DOUBLE INLET (DWDI) AIRFOIL SUPPLY FAN AND DRIVE
Quantity 111
Size404040
Motor Size Range (min. to max. HP)10–10010–10010–100
Airow Range (min. to max. CFM)30000–5200032000–5200036000–52000
Static Pressure Range (min. to max. ESP)0–6 inches0–6 inches0–6 inches
DIRECT DRIVE PLENUM (DDP) SUPPLY FAN AND DRIVE
Quantity 222
Size330-100/120330-100/120330-100/120
Motor Size Range (min. to max. HP)10–6010–6010–60
Airow Range (min. to max. CFM)20000–45000/52000 20000–45000/52000 20000–45000/52000
Static Pressure Range (min. to max. ESP)1–8 inches1–8 inches1–8 inches
EXHAUST FAN
Quantity111
TypeDWDI Forward-Curved
Size32–3232–3232–32
Motor Size Range (min. to max. HP)7.5–607.5–607.5–60
Airow Range (min. to max. CFM)0–500000–500000–50000
Static Pressure Range (min. to max. ESP)0–2 inches0–2 inches0–2 inches
RETURN FAN
Quantity Fans/Motors111
TypeSWSI PlenumSWSI PlenumSWSI Plenum
Size445445445
Motor Size Range (min. to max. HP)10–5010–5010–50
Airow Range (min. to max. CFM)0–500000–500000–50000
Static Pressure Range (min. to max. iwg)0–30–30–3
EVAPORATOR COIL
Size (sq. ft.)81.781.781.7
Number Of Rows/Fins Per Inch5 / 105 / 105 / 10
Tube Diameter (inches)1/21/21/2
CONDENSER COIL
Size (sq. ft.)262262262
Number Of Rows/Fins Per Inch1/211/211/21
CONDENSER FANS
Quantity999
TypePropPropProp
Diameter (inches)363636
Power (HP)222
FILTERS - 2-INCH CLEANABLE (PRE-FILTER POSITION)
Quantity36/1236/1236/12
Size (length x width in inches)16x20/20x2016x20/20x2016x20/20x20
Total Filter Face Area (sq. ft.)113.3113.3113.3
1. Electric heat steps and airow range depends on voltage and size. Consult the air pressure drop tables for specic number of steps for a
given voltage.
TABLE 5 - APPROXIMATE BASE OPERATING
WEIGHTS (LBS)
MODEL SIZE120130150
SINGLE PIECE UNIT18,238 18,847 18,938
TWO PIECE UNIT
Air Handler Section12,131 12,325 12,332
Condenser Section6,0966,5106,597
NOTES:
• Weights above are total weight excluding the curb
• Standard cabinet
• Cooling only
• 60 HP supply fan with variable frequency drive (VFD)
• Comparative enthalpy economizer
• Barometric relief exhaust
• Bottom supply and return
• 2-inch pleated lters
• Condenser section wire guards
• Weights represent approximate operating weights and have a
+/- 10% accuracy. To calculate weight for a specic conguration, contact a TempMaster sales representative.
TABLE 6 - COMPONENT WEIGHTS (LBS)
MODEL SIZE120130150
CABINET, AIR HANDLING SECTION
Sheet Metal (Note 1)6,310
Control Panel (Note 2)705
In order to determine the proper exhaust fan motor size, add the return duct static pressure to the appropriate damper pressure drop value in Table 15 on page 40 to get the
total static pressure applied to the exhaust fan. Based on the exhaust fan airflow and total
static pressure, determine the brake horsepower (BHP) and revolutions per minute (RPM)
of the exhaust fan.
TABLE 19 - TMAL120–150: 32-INCH FORWARD-CURVED EXHAUST FAN
NOTE: For performance at operating points not included in these tables, consult your local TempMaster representative.
0.250.500.751.001.251.50
RPMBHPRPMBHPRPMBHPRPMBHPRPMBHPRPMBHP
1.752.002.252.502.753.00
RPMBHPRPMBHPRPMBHPRPMBHPRPMBHPRPMBHP
44
TEMPMASTER
Electrical Data
ELECTRICAL SERVICE SIZING
In order to use the electrical service required for the cooling only TempMaster OmniElite
single package unit, use the appropriate calculations listed below from U.L. 1995. Based
on the configuration of the single package unit, the calculations will yield different minimum circuit ampacity (MCA) and maximum overcurrent protection (MOP).
Using the following load definitions and calculations, determine the correct electrical sizing for your unit. All concurrent load conditions must be considered in the calculations, and
you must use the highest value for any combination of loads.
Load Definitions:
FORM TPM3-EG1 (518)
• LOAD1 is the current of the largest motor – compressor or fan motor.
• LOAD2 is the sum of the remaining motor currents that may run concurrently with
LOAD1.
• LOAD3 is the current of the electric heaters (Note: zero for cooling only units).
• LOAD4 is the sum of any remaining currents greater than or equal to 1.0 amp.
Use the following calculations to determine MCA and MOP for units supplied with a singlepoint power connection:
If the MOP does not equal a standard current rating of an overcurrent protective device,
then the marked maximum rating is to be the next lower standard rating. However, if the
device selected for MOP is less than the MCA, then select the lowest standard maximum
1. Heaters will be sized as follows: 460V heaters rated at 480V,
575V heaters rated at 600V.
120-150 TONS
460V575V
AMPSAMPS
46
TEMPMASTER
Controls
FORM TPM3-EG1 (518)
CONTROL SEQUENCES
FOR VARIABLE AIR VOLUME (VAV)
AND SINGLE ZONE VAV (SZVAV)
GENERAL
The control system for the TempMaster® OmniElite™ single package unit is fully self-contained and based around a single package unit controller. To aid in unit setup, mainte-
nance, and operation, the single package unit controller is equipped with a user interface
that is based around a 4 line x 20 character backlit liquid crystal display (LCD). The LCD
displays plain language text in a menu-driven format to facilitate use.
Based on the unit type (variable air volume (VAV) or single zone VAV (SZVAV)), the TempMaster OmniElite single package units can be operated by a space temperature sensor or
standalone. A field wiring terminal block is provided to facilitate unit setup and installation.
In lieu of the hardwired control options, the single package unit controller can be connected to and operated by a building automation system (BAS).
The IPU controller uses the latest technology and provides complete control for the unit
along with standard BACnet® MS/TP and Modbus™ remote terminal unit (RTU) communications. The IPU controller also has an SD card slot that can be used to capture historic
data on unit operation.
If required, the unit can be equipped with an optional field-installed gateway that allows N2
or Echelon® communications. The E-Link gateway device is field installed and purchased
through the advanced order management system (AOMS).
YK-ELNKE01-0 – E-Link for Echelon
YK-ELNKE00-0 – E-Link for N2
UNOCCUPIED/OCCUPIED SWITCHING
Depending on the application, the unit can be indexed between unoccupied and occupied
modes of operation by one of three methods, hardwired input, internal time clock, or BAS.
A contact-closure input is provided for hardwiring to an external indexing device such as
a central time clock or a manual switch. The unit controller is also equipped with a built-
in 7-day time clock that can be used in lieu of the contact closure input to switch the unit
between unoccupied and occupied modes of operation.
The internal time clock is fully configurable via the user interface and includes holiday
scheduling. In addition to the hardwired input or the internal time clock, the unit can also
be indexed between unoccupied and occupied modes of operation via a BAS command.
GAS HEATING OPERATION
Units supplied with gas heat can be equipped with one, two, or three independently operated burner modules. Each module is fully self-contained furnace with all necessary ignition controls, safeties, and gas valves. The IPU controller determines how the furnaces
are started and stopped and prevents furnace operation if the supply fan airflow is not
sufficient or if the supply air temperature (SAT) is excessively high. If a furnace module
receives a signal to start from the IPU controller, the ignition control engages the furnace
inducer (draft) fan for a 30-second pre-purge cycle. At the end of the 30-second prepurge, the ignition control will stop the furnace and allows the inducer fan to operate for a
30-second post-purge. Each furnace contains a direct spark ignition system and included
safeties for flame and inducer fan verification, high temperature, and flame rollout.
TEMPMASTER
47
FORM TPM3-EG1 (518)
Controls (Cont'd)
HYDRONIC HEAT
If the unit is configured with either of the wet heat options (steam or hot water) the single
package unit controls will modulate the hydronic valve to maintain a supply air (SA) setpoint. In the event temperatures off the hydronic coil are below 34.0°F, the fans will shut
down and the hydronic valve will open 100%. This function is an automatic reset, so as
the temperature rises above 36.0°F, the unit will automatically begin normal operation.
ELECTRIC HEATING OPERATION
For units equipped with electric heaters, the unit can control up to six stages of electric
heat, which are staged on based on heating demand calculated by the IPU controller.
MORNING WARM-UP
Morning warm-up can be initialized by BAS or by the IPU controller if the internal scheduling is used. If the internal scheduling is used, the morning warm-up start time is calculated
through an adaptive algorithm. When morning warm-up is required, the IPU controller
energizes the VAV heat relay, starts the supply fan and qualifies the return air tempera-
ture (RAT) for 5 minutes. The internal heat source (gas, hot water/steam, or electric) is
controlled to maintain the RAT to the return air (RA) heating setpoint, morning warm-up
ends when occupancy occurs (BAS, internal scheduling, or contact closure) or when the
maximum morning warm-up time has expired.
ECONOMIZER OPERATION
The unit can be equipped with one of three types of optional economizers: dry bulb, single
enthalpy, or comparative enthalpy. When the unit controller determines that outside air
is suitable for economizing, the unit controller will control the outside air (OA) damper(s)
open to provide economizer cooling. If economizer cooling alone is insufficient for the
cooling load, the unit controller shall stage up compressors, one at a time, to meet demand.
The control logic for the three types of economizers is as follows:
Dry Bulb Economizer: The dry bulb economizer is the default economizer control
scheme. With the dry bulb economizer, the unit controller monitors the outside air temperature (OAT) only and compares it to a reference temperature setting. Outside air is
deemed suitable for economizing when the OAT is determined to be less than the reference temperature setting. This method of economizing is effective, but it is prone to some
changeover inefficiencies due to the fact that this method is based on sensible temperatures only and does not take outside air moisture content into consideration.
Single Enthalpy Economizer: With the optional single enthalpy economizer, the unit
controller monitors the OA enthalpy in addition to the OAT and compares it to a reference
enthalpy setting and a reference temperature setting. Outside air is deemed suitable for
economizing when the OA enthalpy is determined to be less than the reference enthalpy
setting and the OAT is less than the reference temperature setting. This method of economizing allows the reference temperature setting to be set higher than the dry bulb econo-
mizer and is consequently a more efficient single package unit economizer.
Dual Enthalpy Economizer: With the optional dual enthalpy economizer, the unit controller monitors and compares the OA and RA enthalpies in addition to comparing the OAT to
the reference temperature setting. Outside air is deemed suitable for economizing when
the OA enthalpy is determined to be less than the RA enthalpy and the OAT is less than
the reference temperature setting. This method of economizing is the most accurate and
provides the highest degree of energy efficiency for a single package unit economizer.
48
TEMPMASTER
FORM TPM3-EG1 (518)
VENTILATION CONTROL SEQUENCES
Minimum Outside Air (OA) Damper Position (VAV Units)
With VAV units, there are two minimum OA damper positions: one when the unit is at full
speed and the second when the unit is at approximately half speed. These two points allow the control to linearly reset the position of the OA damper in response to fan speed.
When the unit goes into the occupied mode of operation, the unit controller shall monitor the speed of the supply fan and open the OA damper to a calculated minimum position based on the fan speed. This minimum position shall vary as the speed of the fan
changes. The damper shall remain at this calculated position as long as the unit is in the
occupied mode and the economizer is not suitable for cooling.
Air Measurement Stations
When the unit is equipped with an air measurement station, the unit controller shall control
the OA damper to a measured flow rate through the air measurement station.
When the unit goes into the occupied mode of operation, the unit controller shall control
the OA damper to maintain the minimum airflow setpoint through the air measurement
station. The unit controller shall control the OA damper to this flow rate as long as the unit
is in the occupied mode and the economizer is not suitable for cooling.
Demand Ventilation
If optional carbon dioxide (CO2) sensors are connected to the unit, the unit controller can
reset the minimum OA damper position(s) or minimum flow rate based on demand.
The unit controller shall monitor the CO2 level within the building. If the CO2 level rises
above the CO2 setpoint, the controller will temporarily increase the minimum OA damper
position or minimum OA flow rate to increase ventilation. If the CO2 level drops below the
CO2 setpoint, the controller will decrease the minimum OA damper position or minimum
OA flow rate to decrease ventilation. Demand ventilation shall remain active as long as the
unit is in the occupied mode of operation.
EXHAUST CONTROL SEQUENCES
Barometric
The optional barometric exhaust system consists of a lightweight barometric relief damper
installed on the end of the unit in the RA section. As more outside air is introduced into
the controlled zone due to economizer and ventilation control sequences, the pressure
inside the building rises. As building static pressure increases to overcome any exhaust
duct static pressure, air will be allowed to escape through the barometric relief damper.
Because this type of exhaust is not powered, the amount of air exhausted will be limited
to the static pressure that will need to be overcome.
This optional variable volume powered exhaust system consists of a fixed speed fan configured with a proportionally controlled discharge damper. The unit controller monitors the
pressure inside the building and controls the exhaust damper and the exhaust fan. If the
building pressure rises, the exhaust damper is proportionally controlled open and the exhaust fan is controlled ON. If the building pressure falls, the exhaust damper is proportionally controlled closed and the exhaust fan is controlled OFF. The position of the exhaust
damper in which the exhaust fan is controlled ON and OFF as well as the building pressure
setpoint are user selectable from the user interface.
Powered Variable Volume Exhaust - VFD Controlled
This optional variable volume powered exhaust system consists of an exhaust fan driven
by a variable frequency drive (VFD), which is controlled by the unit controller. The unit
controller monitors the pressure within the building. As the pressure rises, the VFD is
controlled to increase exhaust fan speed. As the pressure falls, the VFD is controlled to
decrease exhaust fan speed. The building pressure setpoint is user selectable from the
user interface. ON/OFF control is maintained the same as exhaust-discharge damper
control stated above.
Return Fan Controlled
This optional variable volume powered return fan system consists of two return fans controlled by one VFD that is controlled by the unit controller. The VFD is controlled to maintain
a slightly positive pressure over the mixing box section to prevent reverse flow. As the return
and/or exhaust air dampers open, the return plenum pressure drops and the fan will speed
up to maintain pressure. When the return and/or exhaust air dampers close, the return plenum pressure increases causing the VFD to slow the fan speed down.
LOW AMBIENT/HEAD PRESSURE CONTROL OPERATION
The unit controller continuously monitors the OAT to determine if mechanical cooling
should be allowed. As a safety, if the OAT falls to or below the low ambient lockout temperature, mechanical cooling is prevented from operating. For units with economizers,
the low ambient lockout temperature is typically low enough that mechanical cooling will
rarely be required. However, for some applications mechanical cooling is required when
the OAT is lower than the low ambient lockout temperature.
For these applications, the unit must be equipped with optional low ambient controls.
For optional low ambient operation, the unit controller monitors the refrigeration system
discharge pressure and takes measures to limit the flow of air across the condenser coil.
With the optional low ambient controls, mechanical cooling is allowed down to an OAT of
0.0°F.
SMOKE PURGE SEQUENCES
General
The controls of the TempMaster OmniElite are designed as standard with a ventilation
override sequence to remove, exhaust, or ventilate smoke, fumes, or other airborne contaminates from the occupied space. This feature offers three selectable operations: purge,
pressurization, and evacuation. The sequence is activated via one of three binary inputs.
A few typical contact closures include smoke detectors, fire alarms, and manual switches.
50
TEMPMASTER
FORM TPM3-EG1 (518)
Purge
Note: All cooling and heating modes are disabled during smoke purge.
Purge shall be used to displace the air inside the space with fresh outside air. When this
sequence is started, the following shall occur:
1. Start the supply fan if not already on. (Note: With VAV units, the fan speed shall be
controlled to maintain the active duct pressure setpoint.)
2. Start the return and exhaust fans if not already on.
3. Set the VFD to 100%.
4. Set the OA damper position to 100% and the exhaust damper to 100%.
Pressurization
Pressurization shall be used to pressurize the building or space in order to force the air
inside the space through the walls to adjacent spaces or outside the building envelope.
When this sequence is started, the following shall occur:
1. Start the supply fan if not already on. (Note: With VAV units, the fan speed shall be
controlled to maintain the active duct pressure setpoint.)
2. Stop the return and exhaust fans if on.
3. Set exhaust/return fan VFD to 0%.
4. Set the OA damper to 100% and the exhaust damper to 0%.
Evacuation
Evacuation shall be used to evacuate (negatively pressurize) the building or space in order to draw air through the walls from adjacent spaces or outside the building envelope.
When this sequence is started, the following shall occur:
1. Stop the supply fan if on.
2. Start the return and exhaust fans if not already on.
3. Set the exhaust/return fan VFD to 100%.
4. Set the OA damper to 0% and the exhaust damper to 100%.
SPECIFIC SEQUENCES (See Installation, Operation, and Maintenance manual (Form
TPM3-NOM1) for further detail)
Variable Air Volume (VAV) Mode
Occupied Cooling – In the occupied cooling mode, the unit controller monitors the RAT
and compares it to the RAT cooling setpoint. The RAT cooling setpoint is entered into the
unit controller through the setpoint key, cooling subsection of the user interface. If the RAT
is equal to or greater than the RAT cooling setpoint plus 0.5°F, the unit controller will place
the unit in the occupied cooling mode. The unit will remain in the occupied cooling mode
until the RAT is equal to or less than the RAT cooling setpoint minus 0.5°F.
TEMPMASTER
51
FORM TPM3-EG1 (518)
ACTIVE COOLING
Variable Air Volume (VAV)
Controls (Cont'd)
Occupied Heating – In the occupied heating mode, the unit controller monitors the RAT
and compares it to the RAT heating setpoint. The RAT heating setpoint is entered into the
unit controller through the setpoints key, heating subsection of the user interface. If the
RAT is equal to or less than the RAT heating setpoint minus 0.5°F, the unit controller will
place the unit in the occupied heating mode. The unit will remain in the occupied heating
mode until the RAT is equal to or greater than the RAT heating setpoint plus 0.5°F.
Unoccupied Cooling – In the unoccupied cooling mode, the unit controller will monitor
the zone temperature and compare it to the unoccupied zone cooling setpoint. The unoccupied zone cooling setpoint is set through the setpoints key, cooling subsection of the
user interface. If the zone temperature is equal to or greater than the unoccupied zone
cooling setpoint temperature plus 0.5°F, the unit controller will place the unit in the unoccupied cooling mode. The unit will remain in the unoccupied cooling mode until the zone
temperature is equal to or less than the unoccupied zone cooling setpoint minus 0.5°F.
Unoccupied Heating – In order for the unoccupied heating mode to function, the night
set back setting must be set to enable. This can be done through the program key, heating
subsection of the user interface. In the unoccupied heating mode, the unit controller will
monitor the zone temperature and compare it to the unoccupied zone heating setpoint.
The unoccupied zone heating setpoint is set through the setpoints key, heating subsec-
tion of the user interface. If zone temperature is equal to or less than the unoccupied zone
heating setpoint minus 0.5°F, the unit controller will place the unit in the unoccupied heating mode. The unit will remain in the unoccupied heating mode until the zone temperature
is equal to or greater than the unoccupied zone heating setpoint plus 0.5°F.
OCCUPIED HEATING
CURRENT RETURN AIR
TEMPERATURE (RAT) IS
MORE THAN THE ACTIVE
HEATING RAT SETPOINT
MINUS 0.5°F. SUPPLY FAN IS
BEING CONTROLLED TO
THE ACTIVE DUCT STATIC
SETPOINT.
NOTES:
1. WHENEVER THE UNIT ENTERS AN ACTIVE COOLING OR HEATING MODE, THE UNIT CONTROLLER WILL UTILIZE AS MANY OR AS FEW STAGES OF COOLING OR
HEATING THAT IT NEEDS TO ACHIEVE AND MAINTAIN THE ACTIVE SUPPLY AIR TEMPERATURE (SAT) SETPOINT.
2. UNIT MODES WILL STAGE DOWN WHEN THE ZONE TEMPERATURE IS 0.5°F UNDER THE SETPOINTS FOR COOLING AND 0.5°F OVER THE SETPOINTS FOR HEATING.
O
C
C
U
P
I
E
D
H
E
A
T
I
N
G
OCCUPIED STANDBY
THERE IS NO DEMAND
FOR HEATING BASED
ON THE ACTIVE RAT
HEATING SETPOINT.
SUPPLY FAN IS BEING
CONTROLLED TO THE
ACTIVE DUCT STATIC
SETPOINT.
R
A
T
S
E
T
P
O
I
N
T
OCCUPIED STANDBY
THERE IS NO DEMAND
FOR COOLING BASED
ON THE ACTIVE RAT
COOLING SETPOINT.
SUPPLY FAN IS BEING
CONTROLLED TO THE
ACTIVE DUCT STATIC
SETPOINT.
O
C
C
U
P
I
E
D
C
O
O
L
I
N
G
OCCUPIED COOLING
CURRENT RAT IS MORE
THAN THE
RAT SETPOINT PLUS 0.5°F.
SUPPLY FAN IS BEING
CONTROLLED TO THE
ACTIVE DUCT STATIC
SETPOINT.
FIGURE 4 - OPERATIONAL MODE: VARIABLE AIR VOLUME (VAV)
52
LD20073
TEMPMASTER
FORM TPM3-EG1 (518)
OCCUPIED HE
Single Zone Variable Air Volume (SZVAV)
NOTES:
1. WHENEVER
NEEDS
2. UNOCCUPIED SEQUENCE WILL
3. UNIT
Single Zone Variable Air Volume (SZVAV) Mode
Units configured for SZVAV operation shall contain a supply fan VFD. The unit shall switch
between cooling mode, heating mode, and standby mode based on zone temperature.
In cooling mode, the supply fan speed shall be varied based on zone temperature. If the
zone temperature gets warmer, the supply fan speed shall increase. Conversely, if the
zone temperature gets cooler, the supply fan speed shall decrease. In heating mode, the
supply fan shall run at full speed. When the zone temperature is satisfied, the unit is neither in cooling mode nor heating mode, and the supply fan shall run at minimum speed.
Control of cooling and heating stages shall operate as described in the following section.
Unit Mode Determination (Hardwired or Communicated) – The unit compares the
analog wired zone temperature or communicated zone temperature input to the occupied
zone cooling, occupied zone heating, unoccupied zone cooling, or unoccupied zone heating setpoints to determine the sub-mode of operation. Figure 5 on page 53 shows what
the unit mode would be based on the difference between the zone temperature and the
zone temperature setpoints.
The only difference between hardwired and communicated is the method the unit controller uses to determine the zone temperature. In the hardwired mode, the input is an analog
input to the control. In the communicated mode, the input is a serial input from a BAS.
ATING HIGH
OCCUPIED HEATING LOW
ZONE TEMPERATURE
IS BETWEEN 0.5°F
AND 1.5°F BELOW
THE ZONE
TEMPERATURE
SETPOINT.
H
E
SUPPLY FAN AT 100%.
A
T
I
N
G
H
I
G
H
THE UNIT ENTERS AN ACTIVE COOLING OR HEATING MODE, THE UNIT CONTROLLER WILL UTILIZE AS MANY OR AS FEW STAGES OF COOLING OR HEATING THAT IT
TO ACHIEVE AND MAINTAIN THE ACTIVE SUPPLY AIR TEMPERATURE (SAT) SETPOINT.
BE THE SAME AS ABOVE EXCEPT THE ZONE TEMPERATURE SETPOINTS USED WILL BE THE UNOCCUPIED SETPOINTS’ VA LUES.
MODES WILL STAGE DOWN WHEN THE ZONE TEMPERATURE IS 0.5°F UNDER THE SETPOINTS FOR COOLING AND 0.5°F OVER THE SETPOINTS FOR HEATING.
ZONE TEMPERATURE
IS MORE THAN 1.5°F
BELOW THE ZONE
TEMPERATURE
SETPOINT.
SUPPLY FAN AT 100%.
FIGURE 5 - OPERATIONAL MODE: SINGLE ZONE VAV (SZVAV)
TEMPMASTER
OCCUPIED STANDBY
THERE IS NO
DEMAND FOR
HEATING BASED ON
THE ACTIVE ZONE
H
TEMPERATURE
E
SETPOINT.
A
T
SUPPLY FAN AT
I
SZVAV MINIMUM
N
SETPOINT.
G
L
O
W
Z
O
OCCUPIED STANDBY
N
THERE IS NO
E
DEMAND FOR
COOLING BASED ON
THE ACTIVE ZONE
S
TEMPERATURE
E
SETPOINT.
T
P
SUPPLY FAN AT
SZVAV MINIMUM
O
SETPOINT.
I
N
T
OCCUPIED COOLING LOW
ZONE TEMPERATURE IS
BETWEEN 0.5°F AND 1.5°F
ABOVE THE ZONE
TEMPERATURE SETPOINT.
SUPPLY FAN AT SZVAV
MINIMUM SETPOINT.
C
O
O
L
I
N
G
L
O
W
OCCUPIED COOLING HIGH
ZONE TEMPERATURE IS
MORE THAN 1.5°F ABOVE
THE ZONE
TEMPERATURE SETPOINT.
SUPPLY FAN SPEED
STARTS TO INCREASE.
SUPPLY FAN AT 100%
C
WHEN THE ZONE TEM-
O
PERATURE IS MORE THAN
O
2.5°F ABOVE THE ZONE
L
TEMPERATURE SETPOINT.
I
N
G
H
I
G
H
LD19888
53
FORM TPM3-EG1 (518)
Controls (Cont'd)
COOLING OPERATION
Zone Sensor Control
If a zone sensor controls the unit, the unit controller shall maintain the zone temperature
setpoint. This setpoint is user selectable at the user interface.
When a zone sensor is used for control, the unit controller will monitor the temperature
within the space and control the unit accordingly. A closed-loop staging algorithm is used
to stage compressors up and down as required to maintain the desired zone temperature
setpoint. If the unit is equipped with an economizer, outside air conditions are continu-
ously monitored by the control to determine if conditions are suitable for economizing. If
conditions are suitable for economizing, the unit controller will modulate the OA damper in
addition to staging compressors up and down to maintain the zone temperature setpoint.
HEATING OPERATION
Zone Sensor Control
If a zone sensor controls the unit, the unit controller shall maintain all zone temperature
setpoints. These setpoints are user selectable at the user interface.
When a zone sensor is used for control, the unit controller will monitor the temperature
within the space and control the unit accordingly. A closed-loop staging algorithm is used
to stage heating steps up and down as required to maintain the desired zone temperature
setpoint. If the unit is equipped with an economizer, outside air conditions are continu-
ously monitored by the control to determine if conditions are suitable for economizing. If
conditions are suitable for economizing, the unit controller will modulate the OA damper in
addition to staging heating steps up and down to maintain the zone temperature setpoint.
TABLE 28 - THREE-PHASE POWER SUPPLY CONDUCTOR SIZE RANGE
120–150 TON UNIT
SUPPLY VOLTAGE
460V
575V
SINGLE POINT
TERMINAL BLOCK
6 AWG thru 500 kcmil
(2 per phase)
6 AWG thru 500 kcmil
(2 per phase)
SINGLE POINT
DISCONNECT
3/0 thru 500 kcmil
(2 per phase)
3/0 thru 500 kcmil
(2 per phase)
DUAL POINT TERMINAL BLOCK
TERMINAL BLOCK 1TERMINAL BLOCK 2
2 AWG thru 300 kcmil
(2 per phase)
2 AWG thru 300 kcmil
(2 per phase)
14 AWG thru 2/0
(1 per phase)
14 AWG thru 2/0
(1 per phase)
54
TEMPMASTER
Power Wiring: TMAL120–150
UNIT POWER SUPPLY WIRING,
STANDARD SINGLE POINT WITH OR WITHOUT DISCONNECT
FORM TPM3-EG1 (518)
NOTES:
1. All eld wiring must be provided through a eld-supplied fused disconnect switch to the unit terminals (or optional molded disconnect
switch).
2. All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.
3. Consult the Installation, Operation, and Maintenance (IOM) manual (TPM3-NOM1) manual or unit nameplate data to determine minimum
circuit ampacities (MCAs) and recommended dual element fuse sizes.
4. MCA is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).
5. Maximum dual element fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22)
6. Use copper conductors only.
7. On units with an optional disconnect switch, the supplied disconnect switch is a Disconnecting Means as dened in the N.E.C. Section
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect
switch is not intended to be a load break device.
FIGURE 6 - SINGLE POINT POWER SUPPLY WIRING
TEMPMASTER
55
FORM TPM3-EG1 (518)
Power Wiring: TMAL120–150 (Cont'd)
UNIT POWER SUPPLY WIRING,
OPTIONAL DUAL POINT
NOTES:
1. All eld wiring must be provided through a eld-supplied fused disconnect switch to the unit terminals (or optional molded disconnect
switch).
2. All electrical wiring must be made in accordance with all N.E.C. and/or local code requirements.
3. Consult the IOM manual (TPM3-NOM1) manual or unit nameplate data to determine minimum circuit ampacities (MCAs) and recommended dual element fuse sizes.
4. MCA is based on U.L. Standard 1995, Section 36.14 (N.E.C. Section 440.34).
5. Maximum dual element fuse size is based on U.L. Standard 1995, Section 36.15 (N.E.C. Section 440.22)
6. Use copper conductors only.
7. On units with an optional disconnect switch, the supplied disconnect switch is a Disconnecting Means as dened in the N.E.C. Section
100, and is intended for isolating the unit from the available power supply to perform maintenance and troubleshooting. This disconnect
switch is not intended to be a load break device.
FIGURE 7 - DUAL POINT POWER SUPPLY WIRING WITH NON-FUSED DISCONNECT
56
TEMPMASTER
Field Control Wiring
Supply Air Temp. Setpoint Reset
25
26
22
DSP- (DUCT STATIC RESET -)
DSP+ (DUCT STATIC RESET +)
+5V (DUCT STATIC SP + 5V )
+5V (SAT SP + 5V)
SHLD - (SHIELD (GND))
ZR - (ZONE TEMP SENSOR -)
ZR + (ZONE TEMP SENSOR +)
SMK3 - (SMOKE PURGE 3)
SMK2 - (SMOKE PURGE 2)
SMK1 - (SMOKE PURGE 1)
OCC - (OCCUPIED/UNOCCUPIED)
SD - (SHUTDOWN)
24V - (24VAC)
24V -
(24VAC)
COM -
(24VAC
COM)
SAT - (SUPPLY AIR TRMP RESET -)
SAT + (SUPPLY AIR TRMP RESET +)
1
or
Duct Pressure Setpoint Reset
Or
Supply Fan Sync Command
FORM TPM3-EG1 (518)
NOTES:
1. Wiring shown indicates typical wiring. Refer to the Installation, Operation, and Maintenance (IOM) manual (Form TPM3-NOM1) for more
detailed wiring methods and options
2. All wiring is Class 2, low voltage.
3. Maximum power available from the 24VAC terminal is 40VA.
4. Use shielded wire where shown.
5. Potentiometer application shown. As an alternative, signal inputs can be driven from an analog output of a third party controller.
*Input resistance is 15 K ohms.
FIGURE 8 - FIELD CONTROL WIRING - INPUTS
TEMPMASTER
LD08184C
57
FORM TPM3-EG1 (518)
Field Control Wiring (Cont'd)
Wiring Notes:
1. Wiring shown indicates typical wiring. Refer to the IOM manual (Form TPM3-NOM1) for more detailed wiring methods and options
2. All wiring is Class 2, low voltage.
3. Maximum power available from the 24VAC terminal is 40VA.
4. Use shielded wire where shown.
5. Relay contacts suitable for pilot duty to 1A from 24VAC to 120VAC.
CURB LAYOUT DRAWING / 120–150 TON STANDARD CABINET
419" O.D.
FORM TPM3-EG1 (518)
143"
109.75"
I.D.
107.75"
47"
I.D.
276.00"
40.5"60"
68.9"
55.6"
I.D.
RETURN
2" TYP
29.94"
I.D.
81.84"
135" O.D.
SUPPLY
23.22"
2" TYP
419"
8"
14"
NOTES:
1. Unit must be installed square and level.
2. Curb conguration for bottom return and bottom supply.
3. These drawings are not intended as construction documents for the eld fabricated roof curbs. TempMaster will not be responsible for the
unit t up, leak integrity, or sound level for installation using eld fabricated roof curbs.
4. The TempMaster® OmniElite™ unit does not have a base pan under the condensing section of the unit. Field fabricated roof curbs must
have a cap on the top of the condensing section of the curb to prevent moisture from entering the space. The cap design must be sloped
away from the supply duct opening to the end of the unit for the drainage of the moisture off of the top of the cap.
5. Depicted above is a full perimeter curb.
FIGURE 10 - GENERAL ARRANGEMENT DRAWING (CON'TD)
TEMPMASTER
63
FORM TPM3-EG1 (518)
General Arrangement Drawing – 120–150 Ton Models (Cont'd)
CURB LAYOUT DRAWING / 120–150 TON EXTENDED CABINET
483" O.D.
143"
I.D.
I.D.
107.75"
109.75"
483"
8"
340"
68.9"40.5"59.5"64.5"47"
I.D.
2" TYP55.6"
29.94"
81.84"
I.D.
135" O.D.
RETURN
23.22"
2" TYP
NOTES:
1. Unit must be installed square and level.
2. Curb conguration for bottom return and bottom supply.
3, These drawings are not intended as construction documents for the eld fabricated roof curbs. TempMaster will not be responsible for the
unit t up, leak integrity, or sound level for installation using eld fabricated roof curbs.
4. The TempMaster® OmniElite™ unit does not have a base pan under the condensing section of the unit. Field fabricated roof curbs must
have a cap on the top of the condensing section of the curb to prevent moisture from entering the space. The cap design must be sloped
away from the supply duct opening to the end of the unit for the drainage of the moisture off of the top of the cap.
1. Location of supply line connection, horizontal from economizer corner post, in direction of airow
2. Location of return line connection, horizontal from economizer corner post, in direction of airow
3. Location of supply line connection, vertical from bottom edge of base rail
4. Location of return line connection, vertical from bottom edge of base rail
5. Location of both supply and return lines, horizontal from outside casing of unit, across direction of airow
MPT = Male Pipe Thread FPS = Female Pipe Sweat
TEMPMASTER
65
FORM TPM3-EG1 (518)
Power/Control Entry Drawing – 120–150 Ton Models
FIGURE 11 - POWER/CONTROL WIRING LOCATION
66
LD19504
TEMPMASTER
Guide Specifications
GENERAL
Scope
The requirements of the General Conditions, Supplementary Conditions, Division 1, and
Drawings apply to all work herein.
Provide microprocessor-controlled, air-cooled, double-wall construction outdoor single
package unit air conditioning product of the scheduled capacities and performance as
shown and indicated on the drawings, including but not limited to:
1. Single-piece single package unit package
2. Charge of refrigerant and oil
3. Electrical power and control connections
4. Supply and return duct connections
FORM TPM3-EG1 (518)
5. Factory start-up
Quality Assurance
All units are tested, rated, or certified, as applicable, in accordance with the following
standards, guidelines, and codes:
1. All units shall meet the latest ASHRAE 90.1 minimum energy efciency ratio (EER).
2. All units shall meet the latest ASHRAE 62 requirements for ventilation and indoor
air quality (IAQ).
3. All units shall be rated in accordance with the ARI Standard 340/360.
4. All units shall be tested to ANSI/UL 1995 and CAN/CSA C22.2 No. 236 standards.
5. Gas heating units shall be designed in conformance with ANSI Z21.47-2006/
CSA2.3-2006 standards and be ETL listed.
6. Units shall be ETL and ETL Canada listed.
Manufacturers: The design shown on the drawing is based upon products of the manu-
facturer scheduled. Alternate equipment manufacturers shall be acceptable if equipment
meets the scheduled performance and complies with these specifications. If equipment
manufactured by manufacturer other than that scheduled is utilized, then the mechanical contractor shall be responsible for coordinating with the general contractor and all
affected subcontractors to ensure proper provisions for installation of the furnished unit.
This coordination shall include, but not be limited to, the following:
1. Structural supports for units.
2. Roof curb transition.
3. Piping size and connection/header locations.
4. Electrical power requirements and wire/conduit and overcurrent protection sizes.
5. All costs incurred to modify the building provisions to accept the furnished units.
TEMPMASTER
67
FORM TPM3-EG1 (518)
Guide Specifications (Cont'd)
Warranty: Manufacturer shall warrant all equipment and material of its manufacture
against defects in workmanship and material for a period of 18 months from date of shipment.
1. The warranty shall include parts only during this period.
2. The warranty shall not include parts associated with routine maintenance, such as
belts, air lters, etc.
Delivery and Handling
Unit shall be delivered to the job site fully assembled, wired, and charged with refrigerant
and oil by the manufacturer.
Unit shall be stored and handled per manufacturer’s instructions.
All handling and storage procedures shall be per manufacturer’s recommendations.
Submittals
Shop Drawings: Shop drawing submittals shall include, but are not limited to, the follow-
type, and size of field connections; and power and control wiring connections.
Product Data: Product data shall include dimensions, weights, capacities, ratings, fan
performance, motor electrical characteristics, and gauges and finishes of materials.
Documentation
1. Fan curves with specied operating point clearly plotted shall be provided.
2. Product data of lter media, lter performance data, lter assembly, and lter frames
shall be provided.
3. Electrical requirements for power supply wiring; including wiring diagrams for inter-
lock and control wiring shall be supplied. Factory and eld-installed wiring shall be
clearly indicated.
4. Operation and maintenance documentation shall be supplied in accordance with
Section 01 78 23 (01830) – Operation and Maintenance Data, including but not
limited to instructions for lubrication, lter replacement, compressor, motor and
drive replacement, coil cleaning, lter maintenance, spare parts lists, and wiring
diagrams.
Warranties
Equipment shall include the manufacturer’s warranty not less than 18 months from the
date of shipment.
Extended parts warranty [optional] shall be included for an additional 1 [5] year.
Extended parts and labor warranty [optional] shall be included for an additional 1 [5] year.
68
TEMPMASTER
FORM TPM3-EG1 (518)
EQUIPMENT
Product Specification
Summary: Completely factory-assembled, unitized construction single [two-piece unit,
consisting of condenser section and air handler section] package air conditioning unit
including a factory-mounted and wired unit controller and sensors, single-point power
connection 460V [/575V] 3-phase, 60Hz power supply, outside air handling section with
return and supply openings, discharge plenum, direct expansion (DX) refrigerant condensing section.
Factory Test: The refrigerant circuit shall be pressure-tested, evacuated, and fully charged
with refrigerant [nitrogen holding charge on two-piece units] and oil. The completed refrigerant circuit shall undergo a factory helium leak test, an automated operational run test,
and quality inspection prior to shipment. The unit controller shall be configured and run
tested at the factory to minimize field setup time. If the unit is not configured and tested,
then the manufacturer shall provide field start-up and testing to ensure that the controller
is functioning properly.
Unit Construction
Base Rail: The unit shall include an integral design base rail with lifting points clearly
marked and visible on the base rail and a 1-1/4-inch female pipe thread (FPT) connection
for condensate drainage. The unit base shall be designed with a recessed curb mounting
location. The recessed curb mounting surface shall provide a continuous surface for field
application of curb gasketing to create a weather-tight seal between the curb and unit.
Casing: Casing shall be complete post and panel construction with exterior skin. All panels, doors, walls, uprights, floor panels, and roofing shall be 1-inch thick, 1-1/2 pound density insulation. Units are specifically designed for outdoor installation. Air handling section
shall be of double-wall construction, including doors, walls, and corner posts.
Roof: The unit roof shall be bowed with the peak in the middle of the unit and sloped
to both sides of the unit for drainage. A drip lip shall run the length of the unit to prevent
water drainage down the side of the unit. Roof and sidewall seams shall be continuously
caulked and covered with formed galvanized seam caps. All panel fasteners shall be secured through standing seams to prevent fastener penetrations that are exposed to the
air stream.
Paint: Exterior painted surfaces are designed to withstand a minimum of 1,000 salt spray
hours when tested in accordance with ASTM B-117.
Markings and Diagrams: All necessary tags and decals to aid in the service and/or indicating caution areas shall be provided. Electrical wiring diagrams shall be attached to the
control panel access door.
Documentation: Installation and maintenance manuals shall be supplied with each unit.
Access Doors: Double-wall access doors shall be provided in the fan, coil, filter, and inlet
sections of the unit on both sides of the unit. Doors shall be double-wall construction with
a solid liner and a minimum thickness of 1-inch. Doors shall be attached to the unit with
piano-type stainless steel hinges. Latches shall be positive-action, creating an airtight
seal between the door and unit. Panels and doors shall be completely gasketed with a
closed-cell, neoprene gasket. Door tiebacks shall be provided for all doors to secure them
while servicing.
TEMPMASTER
69
FORM TPM3-EG1 (518)
Guide Specifications (Cont'd)
Economizer Type
[SELECT NONE OR ONE OF THE FOLLOWING]
1. No Outside Air: The unit has no provisions for outside ventilation air.
2. Manual Outside Air (OA) Damper: A manually adjustable OA damper capable of
admitting 0–25% outside air shall be provided.
3. Two-Position Outside Air (OA) Damper: A two-position OA damper capable of ad-
mitting 0–25% outside air shall be provided. The minimum position shall be manually adjustable from 0–25%. Control shall be based on the occupied mode of the
unit. For occupied mode, the damper shall be open to the minimum position and for
unoccupied, it shall be closed.
4. Modulating Economizer: The economizer segment shall be designed to use out-
side air for cooling and ventilation and provide a means of exhausting air from the
air handling unit. The segment shall consist of parallel acting low-leak dampers.
The return air (RA), OA, and exhaust air (EA) dampers shall be sized for 100% of
nominal unit airow. The EA damper assembly shall have a factory-assembled rain
hood. The rain hood shall have a drip-lip the full width of the hood to channel moisture away from the air being drawn into the unit.
Economizer Leakage
[SELECT ONE OF THE FOLLOWING]
1. Damper assemblies are low-leak design. Damper blades are fabricated from a minimum of 16-gauge galvanized steel. Blade edges are covered with vinyl seals.
2. Damper assemblies have a maximum leakage rate of 10 CFM/sq. ft. at 1-inch water column (w.c.) when tested in accordance with AMCA Standard 500 and have a
longevity of 60,000 damper opening and closing cycles, complying with the requirements of California Title 24.
[SELECT ONE OF THE FOLLOWING TYPES OF BUILDING PRESSURE CONTROL]
1. No Building Exhaust/Relief: The unit has no provisions to exhaust building return air.
2. Barometric Relief Damper: Building air exhaust shall be accomplished through
barometric relief dampers installed in the return plenum. The dampers open relative
to the building pressure. The opening pressure shall be adjustable.
3. On/Off Fan Powered Exhaust: A double width, double inlet (DWDI) Class II for-
ward-curved centrifugal exhaust fan shall be provided to exhaust building return air
to relieve building static pressure. The fans shall be constant volume and operate
based on either a building static pressure or OA damper position.
4. Powered Exhaust with Modulating Discharge Damper: A DWDI Class II forward-
curved centrifugal exhaust fan shall be provided to exhaust building return air to
relieve building static pressure. The fans shall operate at a constant volume and
operate based on building static pressure. Exhaust airow shall be modulated via
a parallel-acting control damper. The EA dampers shall be sized for 100% of the
exhaust airow.
5. Powered Exhaust with Variable Frequency Drive (VFD): A twin DWDI Class II
forward-curved centrifugal exhaust fan shall be provided to exhaust building re-
turn air to relieve building static pressure. Exhaust airow shall be modulated via a
factory installed and commissioned variable frequency drive (VFD) with the same
nameplate horsepower as the supply fan motor.
70
TEMPMASTER
FORM TPM3-EG1 (518)
6. Power Return Fan: A single width, single inlet (SWSI) plenum fan shall be provided
to draw return air from the building to the single package unit. An access door shall
be provided on at least one side of the unit for fan/motor access. The return fan shall
operate to maintain a constant pressure within the return plenum.
7. Power Return Fan with Exhaust: A SWSI plenum fan shall be provided to draw
return air from the building to the single package unit. An access door shall be provided on at least one side of the unit for fan/motor access. The return fan shall operate to maintain a constant pressure within the return plenum. A discharge damper
shall be provided to modulate building exhaust. The damper shall be controlled via
building pressure. The RA damper shall be linked with the OA damper to modulate
volumes of return and outside airows.
[FOR POWERED EXHAUST OR RETURN FAN OPTIONS ABOVE, USE THE FOLLOWING]
1. Fan Motor: Fan motors shall be NEMA design ball-bearing types with electrical
characteristics and horsepower as specied. Motors shall be 1750 RPM, open
drip-proof (ODP) type [total enclosed fan-cooled (TEFC) optional]. [Optional shaft
grounding rings on motors increase motor longevity when applied with a VFD.] The
motor shall be located within the unit on an adjustable base.
2. Mountings: Fan and fan motor shall be internally mounted and isolated on a full
width isolator support channel using 1-inch springs [2-inch springs and seismic restraints optional]. The fan discharge shall be connected to the fan cabinet using a
exible connection to ensure vibration-free operation.
3. Bearings and Drives: Fan bearings shall be self-aligning, pillow block, or anged
type regreaseable ball bearings and shall be designed for an average life (L50) of
at least 200,000 hours. All bearings shall be factory lubricated and equipped with
standard hydraulic grease ttings and lube lines extended to the motor side of the
fan. Fan drives shall be selected for a 1.5 service factor and anti-static belts shall be
furnished. All drives shall be xed pitch. Fan shafts shall be selected to operate well
below the rst critical speed and each shaft shall be factory coated after assembly
with an anti-corrosion coating.
Filter Section
[SELECT A FILTER RACK, FILTER MEDIA, AND SWITCH IF DESIRED]
1. Angled Filter Rack: 2-inch carbon media MERV 7 lters shall be provided in an
angled lter rack.
2. Angled Filter Rack: 2-inch cleanable lters shall be provided in an angled lter
4. Flat Filter Rack: 60–65% efcient MERV 11 rigid lters with a 2-inch high-efciency
5. Flat Filter Rack: 90–95% efcient MERV 14 rigid lters with a 2-inch high-efciency
6. Dirty Filter Alarm: A dirty lter switch shall be provided and wired to the single
TEMPMASTER
pleated pre-lters shall be provided in a at lter rack.
pleated pre-lters shall be provided in a at lter rack.
package unit control panel. Upon closure of the switch, the controller shall display
a dirty lter fault. The setting of the switch can be changed manually to close at a
specied pressure drop across the lters.
71
FORM TPM3-EG1 (518)
Guide Specifications (Cont'd)
Evaporator Section
1. Cooling Coil: Evaporator coils shall be DX type with intertwined circuiting to assure
complete coil face activity during part load operation. Coil tubes shall be 1/2-inch
outside diameter (OD) copper with internally enhanced tubes. Fins shall be enhanced mechanically, expanded to bond with the copper tubes. Coil casing shall be
fabricated from heavy gauge galvanized steel. All coils shall be pressure-tested at
a minimum of 450 psig.
2. Indoor Air Quality (IAQ) Drain Pan: The main coil drain pan shall be double-
sloped of stainless steel construction with a condensate connection through the
base rail of the unit. Clearance between the evaporator coil and the drain pan shall
allow for easy access to the drain pan for cleaning and shall be visible for inspection
without the removal of components.
3. Intermediate Drain Pan: Coils with nned height greater than 48 inches shall have an intermediate drain pan extending the entire nned length of the coil. The intermediate pans shall have drop tubes to guide condensate to the main drain pan.
Supply Fan Section
1. Fan: The fan section shall be equipped with a single DWDI airfoil type wheel for
horizontal discharge. An access door shall be provided on both sides of the unit for
fan/motor access.
a. Mountings: Fan and fan motor shall be internally mounted and isolated on a full
width isolator support channel using 1-inch springs [2-inch springs and seismic
restraints optional]. The fan discharge shall be connected to the fan cabinet using a flexible connection to ensure vibration-free operation.
b. Bearings and Drives: Fan bearings shall be self-aligning, pillow block, or
flanged type regreaseable ball bearings and shall be designed for an average
life (L50) of at least 200,000 hours. All bearings shall be factory lubricated and
equipped with standard hydraulic grease fittings and lube lines extended to the
motor side of the fan. Fan drives shall be selected for a 1.5 service factor and
anti-static belts shall be furnished. All drives shall be fixed pitch. Fan shafts shall
be selected to operate well below the first critical speed and each shaft shall be
factory coated after assembly with an anti-corrosion coating.
c. Optional Variable Frequency Drive (VFD) Manual Bypass: A three contactor
manual bypass shall be provided to permit replacement of the VFD in the event
of a power failure.
2. Direct Drive Plenum (DDP) Supply Fan: The fan section shall be equipped with
two SWSI airfoil plenum wheels. Plenum fans shall be direct drive. An access door
shall be provided on both sides of the unit for fan/motor access.
a. Mountings: Fan and fan motor shall be internally mounted and isolated on a full
width isolator support channel using 1-inch springs [2-inch springs and seismic
restraints optional].
b. Acoustiweir™: Unit shall include a discharge air (DA) sound attenuation barrier.
The passive sound attenuator barrier shall be mounted on the downstream side
of the supply fan and shall block line-of-sight between the fan and the unit discharge opening. If not available, manufacturer must provide a sound attenuator
of at least 3 feet in length.
72
TEMPMASTER
FORM TPM3-EG1 (518)
c. Thrust Restraints: Provide horizontal thrust restraints between air handling
unit casing and fan housing.
d. Supply Fan Airflow Measurement: The SWSI supply fan shall be supplied
with an airflow measurement device. Airflow measurement device shall be capable of measurement accuracy of +/-5%. Airflow measurement ring and transducer shall be supplied for integration into a field-supplied controller.
e. Fan Inlet Screen: Unit shall be provided with a fan inlet screen.
f. Safety Grate: Safety grates capable of supporting a 300 pound center load
shall be provided over bottom supply air (SA) opening.
3. Fan Motor: Fan motors shall be NEMA design ball-bearing types with electrical
characteristics and horsepower as specied. Motors shall be 1750 RPM [1175
RPM], ODP type [TEFC optional]. [Optional shaft grounding rings on motors increase motor longevity when applied with a VFD.] The motor shall be located within
the unit on an adjustable base.
4. Variable Air Volume (VAV) Fan Control: VAV supply fan control shall be accom-
plished by using a VFD matched to the supply fan motor horsepower. The VFD shall
include an integral DC line reactor to reduce harmonic distortion in the incoming
and outgoing power feeds. If a DC line reactor is not provided, an AC line reactor
must be provided. Inlet guide vanes shall not be acceptable. VFD control keypads
shall be located in the control cabinet for accessibility and servicing while the unit
is operating.
Discharge Plenum
[SELECT ONE OF THE FOLLOWING HEAT/NO HEAT CONFIGURATIONS]
1. Cooling Only: The discharge air temperature (DAT) sensor shall be located in the
discharge plenum and be located such that it accurately measures the supply air
temperature (SAT). Walls shall be lined with a solid liner to prevent erosion of the
insulation and separate insulation from the air stream.
2. Staged Gas Heat: The heating section shall include an induced draft furnace in six
stages of heating capacity.
a. Heat Exchanger: The heat exchanger shall be constructed of tubular alumi-
nized steel [stainless steel] with stainless steel flue baffles and flue assembly.
b. Burner and Ignition Control: The burner shall include a direct-driven induced-
draft combustion fan with energy efficient intermittent pilot spark ignition, redundant main gas valves with pressure regulator.
c. Combustion Air Fan: The inducer fan(s) shall maintain a positive flow of air
through each tube to expel the flue gas and to maintain a negative pressure
within the heat exchanger relative to the conditioned space.
d. Safety Devices: A high limit controller with automatic reset to prevent the heat
exchanger from operating at an excessive temperature shall be included. A centrifugal switch on the induced draft fan motor shaft shall prevent ignition until
sufficient airflow is established through the heat exchanger. A rollout switch shall
provide secondary airflow safety protection. The rollout switch shall discontinue
furnace operation if the flue becomes restricted.
TEMPMASTER
73
FORM TPM3-EG1 (518)
Guide Specifications (Cont'd)
e. Flue: The furnace flue shall be shipped loose to protect it from damage during
transit. The flue shall be field-mounted by the installing contractor. The flue outlet shall be located above the unit to help prevent recycling of combustion gases
back through the heat exchanger.
f. Agency Certification: Gas heating sections are both ETL listed to both U.S.
and Canadian safety standards.
3. Modulating Gas Heat: The heating section shall include an induced draft furnace
in 24:1 modulation of heating capacity.
a. Heat Exchanger(s): The heat exchanger(s) shall be constructed of tubular alu-
minized steel [stainless steel] with stainless steel flue baffles and flue assembly.
b. Burner(s) and Ignition Control: The burner(s) shall include a direct-driven in-
duced-draft combustion fan with energy efficient intermittent pilot spark ignition,
redundant main gas valves with pressure regulator.
c. Combustion Air Fan(s): The inducer fan(s) shall maintain a positive flow of
air through each tube to expel the flue gas and to maintain a negative pressure
within the heat exchanger relative to the conditioned space.
d. Safety Devices: A high limit controller with automatic reset to prevent the heat
exchanger from operating at an excessive temperature shall be included. A centrifugal switch on the induced draft fan motor shaft shall prevent ignition until
sufficient airflow is established through the heat exchanger. A rollout switch shall
provide secondary airflow safety protection. The rollout switch shall discontinue
furnace operation if the flue becomes restricted.
e. Flue: The furnace flue shall be shipped loose to protect it from damage during
transit. The flue shall be field-mounted by the installing contractor. The flue outlet shall be located above the unit to help prevent recycling of combustion gases
back through the heat exchanger.
f. Agency Certification: Gas heating sections are both ETL listed to both U.S.
and Canadian safety standards.
4. Electric Heat: An electric slip-in heater is installed within the single package unit
discharge plenum to provide the heating requirements per the schedule shown on
the plans. The electric heater is wired in such a manner as to provide a minimum of
two steps of capacity.
a. Heat Exchanger: The furnace is an industrial grade design using an open coil
made of the highest grade resistance wire containing 80% nickel and 20% chromium. The resistance coils are adequately supported in the air stream using ceramic bushings in the supporting framework. Terminals of the coil are stainless
steel with high temperature ceramic bushings.
b. Safety Devices: The primary high temperature protection is an automatic reset
type thermal cut out. Secondary protection is an automatic reset type thermal
cut out. Secondary protection is a replaceable thermal link.
c. Agency Certification: The operation of the electric heater is an integral part
of the single package units control system. Power connection to the heater is
through the power panel for the unit. Electric heat is ETL listed to both U.S. and
Canadian safety standards.
74
TEMPMASTER
FORM TPM3-EG1 (518)
5. Hot Water Heating Coil: A hot water coil shall be installed in the single package
unit discharge plenum.
a. Construction: The hot water coil shall have 8 [10, 12, 14] fins per inch, 2 tubes
per circuit, and an 2-inch inlet and outlet connection. Primary surface shall be
1/2-inch OD copper tube, staggered in direction of airflow. Connections have
1/4-inch FPT drain plug on each connection. A structural galvanized steel casing shall protect the coil. An intermediate coil support shall be provided. The
coil shall be circuited to provide free draining and venting through one vent and
drain. Freezestat shall be provided to prevent coil freeze-up.
b. Testing: Completed coil, including headers, connections, and return bends
shall be tested with 325 pounds compressed air underwater. Coils shall be designed for operation at 250 psig design working pressure.
6. Steam Heating Coil: A steam heating coil shall be installed in the single package
unit discharge plenum.
a. Construction: The steam coil shall be constructed in the non-freeze style. The
steam coil shall have 6 fins per inch, a 2-inch inlet connection, and 1-1/2-inch
outlet connection. Tubes shall be 1-inch OD seamless copper tubing with a
minimum wall thickness of 0.035-inch and expanded into the fin collars for maximum fin-tube bond. Inner distributing tubes shall be 5/8-inch OD seamless copper tubing with a minimum wall thickness of 1/4-inch. All header connections
shall be of red brass or steel with male pipe threads (MPTs) and silver braze
to headers. Casing shall be galvanized steel. The core shall be pitched in the
direction of the condensate connection for proper drainage. Freezestat shall be
provided to prevent coil freeze-up.
b. Testing: The completed coil, including headers and connections, shall be test-
ed underwater with 325 pounds compressed air to ensure a leak-free coil.
7. Diffuser Section: For applications with an extended discharge plenum with down-
stream ltration or heating, a diffuser section is provided. A diffuser shall be included
to distribute the airow from the fan evenly across the heating coil or lter bank to
optimize coil/lter life and effectiveness. The diffuser shall be sized for 50% free
area and provide adequate upstream and downstream clearance to minimize air-
side pressure drop.
[FOR EXTENDED DISCHARGE PLENUMS, SELECT ONE OF THE FOLLOWING]
1. Downstream Final Filter Rack: A 12-inch rigid lter rack and lters shall be provid-
ed downstream of the supply fan and diffuser segment for hospital applications. The
lter shall be 90–95% efcient MERV 14. A magnahelic pressure gauge shall be
included and visible from the outside of the unit for servicing and code compliance.
2. Blank Section: A blank section shall be provided downstream of the supply fan and
diffuser section.
Condenser Section
1. Condenser Fans: Condenser fans shall be matched up with compressors to op-
timize system control. Condenser fans shall be propeller type, directly driven by
permanently lubricated totally enclosed air over (TEAO) motor.
TEMPMASTER
75
FORM TPM3-EG1 (518)
Guide Specifications (Cont'd)
2. Condenser Coil: Condenser coils shall be all aluminum micro-channel coils or
seamless copper tubes, arranged in staggered rows, mechanically expanded into
the aluminum ns. Coils are congured in a V-bank conguration, with individual at
coils rotated from the vertical plane for protection from hail damage for each con-
densing circuit. Condensing coils shall have a subcooler for more efcient, stable
operation.
3. Compressors: Units shall use industrial-duty hermetic scroll compressors, piped
and charged with oil and POE R-410A refrigerant. Compressors shall have an en-
larged liquid carrying capacity to withstand rugged operating conditions. Compressor frame shall be cast iron, with cast iron xed and orbiting scrolls. Each compres-
sor shall feature a solid state protection module, designed to protect the compressor
from over-temperature and over-current conditions. Compressors shall be vibrationisolated from the unit and installed in an easily accessible area of the unit. All compressor-to-pipe connections shall be brazed to minimize potential for leaks. Each
compressor shall include a replaceable suction screen, discharge line check valve,
and oil sight glass.
4. Compressor Capacity Modulation: Unit shall include six compressors of varying
size to provide 14–100% of cooling during normal operation. The compressor se-
quence of operation shall reduce typical temperature change to less than 2.0°F at
the unit discharge at full design airow. Unit shall not require hot gas bypass and the
inherent energy usage it requires to properly operate the unit. Upon entering cooling mode from other modes, the unit controller will estimate the cooling requirement
and match it closely to the capacity in order to reduce the time required to satisfy
the cooling requirements. After the initial calculation, the unit controller will add or
reduce stage(s) as necessary to establish a balance between the unit capacity and
the space cooling load.
5. Low Ambient: Compressors shall operate down to 0.0°F [optional] by monitor-
ing the refrigeration system discharge pressure and adjusting condenser airow
to maintain the proper head pressure to protect compressor operation. Refrigerant
pressure transducers shall be included and provide the discharge pressure on the
single package unit control display.
6. In-Line Liquid Line Driers [Replaceable Core Liquid Line Driers]: Refrigerant
piping includes check valves, thermal expansion valves with replaceable thermostatic elements, high and low pressure switches, and anti-recycling timing device to
prevent compressor restart for 5 minutes after shutdown.
7. Condenser Wire Grill [Optional Louvered Condenser Enclosure or No Enclo-sure]: The condenser section shall be enclosed by a wire grill [louvered or none]
condenser enclosure on the three exposed sides. Paint nish shall match the color
and salt spray specications of the unit exterior.
8. Compressor Sound Treatment [Optional]: Compressor sound blankets shall be
provided to attenuate radiated sound from the compressors.
9. Service Valves [Optional]: Liquid, suction, and discharge service valves shall be
included to provide a means of isolating the refrigerant charge in the system so that
the refrigeration system may be serviced without removing the charge of the unit.
76
TEMPMASTER
FORM TPM3-EG1 (518)
Controls
1. Enclosure: Unit shall be shipped complete with factory congured, installed, wired,
and tested single package unit controller housed in a rain and dust-tight enclosure
with hinged, latched, and gasket sealed door.
2. Short Circuit Current Rating: Unit shall have a 5,000 amp rating. [Unit shall have
a 65,000 amp rating. Over-current protection must be Class J (eld-provided) to
obtain the 65,000 short circuit current rating (SCCR) rating.] [The unit shall be provided with stand alone 65,000 amp SCCR equipment and ampere interrupting capacity (AIC) rating.]
3. Basic Controls: Control shall include automatic start, stop, operating, and protec-
tion sequences across the range of scheduled conditions and transients. The unit
controller shall provide automatic control of compressor start/stop, energy saver
delay and anti-recycle timers, condenser fans, and unit alarms. Automatic reset
to normal operation after power failure. Software stored in non-volatile memory,
with programmed setpoints retained in lithium battery backed real time clock (RTC)
memory for minimum 5 years. 80-character liquid crystal display (LCD), descriptions, and numeric data in English (or metric) units. The sealed keypad shall include
buttons for setpoints, display, entry, unit options, clock, and an on/off switch.
4. Diagnostics: Upon start-up, the unit controller shall run through a self-diagnostic
check to verify proper operation and sequence loading. The unit controller shall
continually monitor all input and output points on the unit controller and to maintain
proper operation. The unit shall continue to operate in a trouble mode or shut down
as necessary to prevent an unsafe condition for the building occupants or to prevent
damage to the equipment. In the event of a unit shutdown or alarm, the operating
conditions, date, and time shall be stored in the shutdown history to facilitate service
and troubleshooting.
5. Controls and Building Automation System (BAS) Communications
BACnet® MS/TP (RS-485) or Modbus™: The unit shall include BACnet® or Modbus™
communications directly from the unit controller. Equipment that is not native BACnet
at the unit control board shall include any necessary interface or translator device
factory-mounted and wired within the unit. If a field-installed gateway device is re-
quired by the manufacturer, the manufacturer shall include all necessary materials,
equipment, service, and commissioning of the gateway. A control points list, protocol
implementation conformance statement (PICS), and BACnet interoperability building
blocks (BIBBs) statement shall be provided by the manufacturer to facilitate communications programming with the BAS. Programming, establishing communications,
and commissioning shall be the responsibility of the installing controls contractor.
Start-up assistance and support may be purchased from the manufacturer.
Analog inputs: 0–5VDC inputs shall be provided for remote reset of SAT and duct
static pressure.
TEMPMASTER
Binary inputs: Dry (or “wet”) contacts shall be provided for alarm outputs for supply
fan fault, cooling/heating fault, or general/sensor faults. Contacts shall also be provided
for occupied/unoccupied (start/stop) switching; shutdown, smoke purge, exhaust or
pressurization operations; call for cooling or heating; and for morning warm-up.
77
FORM TPM3-EG1 (518)
EXECUTION
Installation
General: Installing contractor shall install unit(s), including components and controls re-
quired for operation, in accordance with unit manufacturer’s written instructions and recommendations. Units shall be installed as specified.
1. Unit(s) specied shall include a protective covering membrane for such equipment being shipped by truck, rail, or ship. The membrane is fully formed around the equipment exterior. The membrane covers the entire top, side, and end panel surface as
to protect the product effectively during shipping and storage, including long term
storage. Storing on the job site shall no longer require the unit(s) to be covered with
a tarp as long as the covering membrane has not been removed.
2. All size or shape equipment including electrical components, especially those not
built with weatherproof enclosures, VFDs, and end devices shall be effectively covered for protection against rain, snow, wind, dirt, sun fading, road salt/chemicals,
rust, and corrosion during shipping cycle. Equipment shall remain clean and dry.
3. Manufacturers of units not having a protective membrane fully formed around the
equipment exterior, covering the entire top, side, and end panel surface area shall be
required to ship equipment covered with a tarp, in crating, or in a closed truck as is
necessary to ensure product protection from road salt/chemicals damage, moisture,
and dirt inltration. Arrangements for long term storage at the job site shall be required.
Location: Locate the single package unit as indicated on drawings, including cleaning
and service maintenance clearance per manufacturer instructions. Adjust and level the
single package unit on support structure.
INSPECTION AND START-UP SUPERVISION
A factory-trained service representative of the manufacturer shall supervise the unit startup and application specific calibration of control components.