TempMaster OmniElite Engineering Manual

FORM TPM3-EG1 (518)
TempMaster® OmniElite
SINGLE PACKAGE ROOFTOP UNITS
ENGINEERING GUIDE
Cooling and Heating (Gas, Electric, Water, and Steam)
R-410A
Mod G
LD19506
FORM TPM3-EG1 (518)
Nomenclature
BASE MODEL NUMBER TMAL120–150
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
BASE PRODUCT TYPE NOMINAL CAPACITY APPLICATION REFRIGERANT VOLTAGE DUCT LOCATIONS DESIGN SPECIAL GAS HEAT CAPACITY
L : Scroll
A : Air-Cooled
M : Packaged Rooftop
T : TempMaster
0
2
1 1 1
: 120-ton
0
3
: 130-ton
0
5
: 150-ton
V : VAV or SZVAV
C : Cooling Only N : Natural Gas Heat G : Natural Gas Heat Stainless Steel Heat Exchanger M : Modulating Gas Heat E : Electric Heat S : Steam Heat H : Hot Water Heat
E : R-410A
6 : 460 / 3 / 60
4
8 : 575 / 3 / 60
5
B : Bottom Return R : Rear Return S : Side Return
B : Bottom Supply L : Left Supply R : Right Supply
N : No Gas Heat L : Low (375 mbh) M : Medium (750 mbh) H : High (1125 mbh)
X : Standard Product, IPU S : Special Product, IPU
G
Approvals
2
ASHRAE
90.1
COMPLIANT
TEMPMASTER
FORM TPM3-EG1 (518)
Table of Contents
NOMENCLATURE ................................................................................................................................................... 2
INTRODUCTION ...................................................................................................................................................... 5
FEATURES AND BENEFITS ................................................................................................................................... 7
APPLICATION DATA ............................................................................................................................................. 14
PHYSICAL DATA ................................................................................................................................................... 19
WEIGHT DATA ....................................................................................................................................................... 21
COOLING PERFORMANCE DATA .......................................................................................................................23
HEATING PERFORMANCE DATA – GAS/ELECTRIC HEAT ............................................................................... 38
SUPPLY FAN DATA ............................................................................................................................................... 39
COMPONENT STATIC PRESSURE DROPS ........................................................................................................ 40
ELECTRIC HEAT PRESSURE DROPS ................................................................................................................ 42
GAS HEAT PRESSURE DROPS ........................................................................................................................... 42
EXHAUST FAN DATA ............................................................................................................................................ 43
RETURN FAN DATA .............................................................................................................................................. 44
ELECTRICAL DATA .............................................................................................................................................. 45
CONTROLS ........................................................................................................................................................... 47
POWER WIRING: TMAL120–150 ......................................................................................................................... 55
FIELD CONTROL WIRING ................................................................................................................................... 57
GENERAL ARRANGEMENT DRAWING – 120–150 TON MODELS .................................................................. 59
HOT WATER/STEAM COIL CONNECTION LOCATIONS .................................................................................... 65
POWER/CONTROL ENTRY DRAWING – 120–150 TON MODELS ..................................................................... 66
GUIDE SPECIFICATIONS ..................................................................................................................................... 67
TEMPMASTER
3
FORM TPM3-EG1 (518)
THIS PAGE INTENTIONALLY LEFT BLANK.
4
TEMPMASTER
Introduction
FORM TPM3-EG1 (518)
The TempMaster® OmniElite™ Single Package Units – designed to meet the demands of the market for today and tomorrow.
Better Economy...
Lower total cost of ownership
• TempMaster provides a standard product offering that meets the latest ASHRAE
90.1 energy efciency requirements.
Unique compressor staging provides quick response to cooling needs and provides multiple steps of capacity for high part load efciency.
• Fully modulating gas heat and greater steps of capacity control offer superior off­design performance while maintaining optimum occupant comfort.
• Accurate ventilation control ensures that no more than the proper amount of ventila­tion air is utilized. This avoids the energy cost of conditioning excess outside air and
simultaneously monitors all other unit functions for maximized energy efciency.
Flexible design congurations simplify the design process and allows the TempMas- ter OmniElite to be applied to virtually any building application.
• Accessibility through double-wall access doors, spacious compartments and sup-
portive oors improves serviceability.
LD07431
The single package unit user interface uses micro­processor logic to optimize operation of the Temp­Master OmniElite single package unit.
Better Ecology...
Indoor air quality (IAQ) features for the indoor environment
A double-sloped stainless steel drain pan with a single drain con­nection ensures that all condensate is voided from the drain pan. It is also visible and accessible for periodic inspection and cleaning re-
quired by the ASHRAE 62 IAQ standard.
Double-wall construction of the roof, oor, doors, and walls pre­vents insulation bers from entering the conditioned air. The inner liner
also facilitates periodic cleaning of the unit to prevent harmful build-up of bacteria or contaminants.
The single package unit control center uses microprocessor logic to analyze and optimize ventilation decisions and perform de-
mand ventilation, airow compensation, and airow measurement to maintain the air quality at a healthy level.
TEMPMASTER
5
FORM TPM3-EG1 (518)
10
9
7
Exhaust Air
8
1. Modulating or staged gas heat
11
12
Outside Air
1
2
3
4
5
6
7
LD21646
7. Rain hoods
2. Condenser fans
3. Scroll compressors
4. Condenser
5. Advanced single package unit controller
6. Evaporator coil
FIGURE 1 - STANDARD CABINET ASSEMBLY
6
8. Exhaust/return fan
9. Economizer
10. Filters section
11. Double-wall construction
12. Double width, double inlet (DWDI) airfoil supply fan
TEMPMASTER
Features and Benefits
AIRFLOW CONFIGURATIONS
Variable Air Volume (VAV) – TempMaster® OmniElite™ units are available for variable air
volume (VAV) applications. Control can be used with a zone sensor or building automa­tion system (BAS). Supply fans are controlled to the supply duct static pressure setpoint, which can be reset via a BAS, or through a 0–5VDC analog input on the unit controller for optimized duct static pressure control. The static pressure transducer is provided in the single package unit, and 5/16-inch or 1/4-inch plastic tubing and static pressure sensor must be supplied by others and installed approximately 3/4 down the longest duct run.
Single Zone Variable Air Volume (SZVAV) – TempMaster OmniElite units are available for single zone variable air volume (SZVAV) applications. Control can be used with a zone sensor or a BAS. Supply fans are controlled based on zone temperature.
COOLING AND HEATING CONFIGURATIONS
FORM TPM3-EG1 (518)
Cooling Only – For applications where no heat is required, or heating is provided else- where within the building HVAC system, cooling only units include an empty discharge plenum. Supply duct connections are configurable for bottom, left or right discharge. The supply air temperature (SAT) sensor is included and factory-installed.
Staged Gas Heat For applications requiring gas heat for morning warm-up, or other heating needs, a staged natural gas furnace is available. The furnace is located in the dis­charge plenum, downstream of the supply fan. The SAT sensor is located across the face of the supply duct opening in the unit. Furnaces are designed in 375 mbh modules. Three stages are available for the TMAL120–150. Ignition and safety controls are included and factory-wired. Units with staged gas heat are ETL listed.
Modulating Gas Heat For applications requiring gas heat for morning warm-up, supply air tempering or other heating needs, a modulating natural gas furnace is available for finer temperature control. The furnace is located in the discharge plenum, downstream of the supply fan. The SAT sensor is located across the face of the supply duct opening in the unit. Furnaces are designed in 375 mbh modules in 8:1 turndown increments. Three are avail­able for the TMAL120–150 (8:1, 16:1 or 24:1 turndown). Ignition and safety controls are included and factory-wired. Units with modulating gas heat are ETL listed.
Electric Resistance Heat – For applications where electric heat is desired, a slip-in elec­tric resistance heat element is available in sizes from 80–250 kW depending on the single package unit model size. The number of stages varies by size and voltage, but all have a minimum of two stages of capacity. Units with electric heat are ETL listed.
Hot Water Heat – For applications where hot water is available for heating, a hot water heating coil is available. A range of coil fin count selections are available to properly size the heating for the application. Units with hot water heat are ETL listed.
Steam Heat – For applications where steam is available for heating, a steam heating coil is available. A range of coil fin count selections are available to properly size the heating for the application. Units with steam heat are ETL listed.
TEMPMASTER
7
FORM TPM3-EG1 (518)
Features and Benefits (Cont'd)
POWER OPTIONS
Single-Point Supply with Terminal Block – This configuration is standard, and includes
three terminals for the incoming 3-phase power and is the standard configuration for the TempMaster OmniElite product. It includes the enclosure, terminal-block, and intercon­necting wiring to the compressors, heater and furnace controls, all fans, etc. In this con-
figuration, code requires that a means of disconnect (not provided) must be installed at the site within line-of-sight of the equipment.
Single-Point Supply with Non-Fused Disconnect Switch This option is the same as the single-point with terminal block option except it includes a unit-mounted through-the­door manual non-fused disconnect switch with an external, lockable handle (in compli­ance with Article 440-14 of National Electric Code (NEC)). This option provides a means to isolate the unit power voltage for servicing. Others must supply separate external fusing which must comply with the NEC and/or local codes.
Dual-Point Supply with Terminal Block – This option includes enclosure, terminal blocks circuited to the supply and exhaust fans and control transformer, and a second set of terminal blocks with interconnecting wiring to the compressors, heat (if applicable), and condenser.
Convenience Outlet – This options includes a powered 115V GFCI convenience outlet that can be used for powering tools or lights for servicing. A protective cover plate is included while not in use. The outlet is located on the bottom left hand corner of the power panel.
CONTROL FEATURES AND OPTIONS
Microprocessor-Based Single Package Unit Controller – All TempMaster OmniElite
units are equipped with a factory-installed, programmed and commissioned unit controller with all I/O capabilities and control sequences. The controls include all on-board diagnostic,
safety and control features to operate the single package unit. A multimedia card interface
is included for software upgrades and can be used for data logging to simplify equipment
troubleshooting. Communication ports are included as standard with three alarm outputs, a shutdown contact, remote start/stop input, smoke ventilation controls, analog inputs for SAT and duct static pressure reset, along with a variety of other capabilities.
Standard Ambient – TMAL120–150 models operate down to 50.0°F as standard.
Low Ambient – This option includes low ambient control of all three refrigerant circuits
down to 0.0°F through the use of suction and discharge pressure transducers, as well as
condenser fan speed using a variable frequency drive (VFD) on the first condenser fan of
each circuit.
Pressure Transducers with Readout Capability – This option includes suction and dis- charge pressure transducers on each circuit and provides pressure readout of all circuits at the unit control panel.
Wall-Mount Zone Sensor – A 10 kOhm thermister type III NTC zone sensor for wall mounting. This zone sensor is for sensing temperature only and does not include any setpoint adjustment features.
Zone Sensor
COMMUNICATIONS
BACnet® MS/TP (RS-485) Communications – This communication option is standard on
every TempMaster OmniElite unit. Communications to the unit are through a twisted pair, and the wire terminations are on the primary unit control board. See supplemental infor­mation for the available control points and protocol implementation conformance state­ment (PICS)/BACnet® interoperability building blocks (BIBBs) statements of conformity.
8
TEMPMASTER
FORM TPM3-EG1 (518)
Modbus™ Remote Terminal Unit (RTU) Communications – This communication option is standard on every TempMaster OmniElite unit and can be used in lieu of the BACnet communications (only one can be used at a time). See supplemental information for the available control points.
FILTER OPTIONS
Filter Options – Cleanable, carbon coated MERV 7 or pleated MERV 8 filters in an an-
gled rack are available. For higher filtration requirements, optional rigid filter racks are
available with 12-inch 65% MERV 11 or 95% MERV 14 efficient rigid filters. Two-inch pre­filters are included with rigid filter options. The rigid filter rack option is available without
filter media where field-supplied filters are required.
OUTSIDE AIR DAMPER (OA) OPTIONS
Manual Damper – This option includes a manually adjustable outside air (OA) damper. It
is manually adjustable at the unit by setting a mechanical stop between 0–100%.
Two-Position – This OA damper option is controlled to two positions, opened and closed. Determination of the damper position is based on the occupancy schedule. In the occu­pied mode, the OA damper is positioned to the manually configured point (set by mechani­cal stop). In the unoccupied mode, the damper is fully closed.
Modulating Economizer – This option includes modulating OA and return air (RA) damp­ers that are software interlocked and positioned by fully modulating, solid state damper actuators. Control of the damper is via a standard ambient OA dry bulb sensor, or optional single or comparative enthalpy controls.
Airflow Measurement – Optional outside airflow measurement is available on units
equipped with a modulating economizer.
CO2 Sensors – Optional carbon dioxide (CO2 ) sensors for occupied space that operate demand ventilation control opening OA dampers to ventilate building. The CO2 sensors can operate in a single or comparative control scheme.
Rain Hoods on Outside Air (OA) Intakes – For all options with OA intake openings, rain
hoods are provided as standard to keep moisture from entering the equipment. The rain
hoods are an integral part of the unit and are rotated into place at the job site.
RELIEF SYSTEM
Barometric Relief – Optional building air exhaust shall be accomplished through baro-
metric relief dampers installed in the return plenum. The dampers will open relative to the building pressure. The opening pressure shall be adjustable via a spring tension adjust­ment.
On/Off Powered Exhaust This option provides simple building pressure control. It can be controlled via a building pressure signal, or via OA damper control. This option is not available for VAV units.
Modulating Powered Exhaust with Damper Control – This option consists of a con­stant-speed exhaust fan with a discharge damper that is modulated to control the flow of exhaust air. The damper control logic is based on the building static pressure setpoint within the single package unit controller. The static pressure transducer is provided in the return plenum of the single package unit, and 5/16-inch or 1/4-inch plastic tubing and static pressure sensor must be supplied by others and installed in a representative loca­tion in the building.
TEMPMASTER
9
FORM TPM3-EG1 (518)
Features and Benefits (Cont'd)
Modulating Powered Exhaust with a VFD – This option consists of a VFD to modulate the speed of the exhaust fan to control the flow of exhaust air. The VFD control logic is based on the building static pressure setpoint within the single package unit controller. The static pressure transducer is provided in the return plenum of the single package unit, and 5/16­inch or 1/4-inch plastic tubing and static pressure sensor must be supplied by others and installed in a representative location in the building.
Powered Return Fan with Exhaust – This option uses single width, single inlet (SWSI) plenum fan(s) to control building pressure. The fan motors are driven by a VFD to maintain a constant return plenum pressure. An exhaust hood with a modulating control damper is used to maintain building pressure via the building static pressure. The static pressure transducer is provided in the return plenum of the single package unit, and 5/16-inch or 1/4-inch plastic tubing and static pressure sensor must be supplied by others and installed in a representative location in the building. The powered return fan is also available with­out the exhaust capabilities. For units with no exhaust capabilities, the HVAC system must provide alternate means of controlling building pressure.
SUPPLY FAN OPTIONS
Double Width, Double Inlet (DWDI) Airfoil Supply Fan – The standard airfoil blade sup-
ply fan is available on all models for higher static conditions. This offers higher efficiency and lower sound in certain applications.
Fan Skid Isolation – The entire supply fan assembly is isolated from the unit base with either 1-inch (standard) or 2-inch deflection springs with seismic restraints.
Supply and Exhaust Fan Motors – Premium efficiency open drip-proof (ODP) and pre­mium efficiency total enclosed fan-cooled (TEFC) motors are available all meeting the Energy Policy Act of 1992 (EPACT).
Supply Fan VFD and Manual Bypass – For VAV applications, VFDs are provided to modulate air flow. Optional manual bypass can also be provided to allow full airflow in the event of a VFD failure.
Direct Drive Plenum (DDP) Fan – A direct drive plenum (DDP) supply fan provides out­standing reliability and efficiency, eliminating the possibility of conditioned air supply inter­ruption due to a broken belt and the pollution of conditioned air with belt dust. The supply
fan can be optionally equipped with a piezo ring to precisely measure the amount of air
delivered to the conditioned space. The speed of the supply fan is controlled by a VFD.
EVAPORATOR SECTION
Double Sloped Stainless Steel Drain Pan – The TempMaster OmniElite’s stainless steel
drain pan is factory-mounted and installed on every unit. A condensate drain trap is need­ed and must be provided and installed in the field by others.
*NOTE:
This is a visual reference only. Actual drain pan pitch will vary.
FIGURE 2 - DRAIN PAN DETAIL
10
LD08022
TEMPMASTER
FORM TPM3-EG1 (518)
Double-Wall Construction – Double-wall construction is the standard construction of the TempMaster OmniElite and incorporates powder coated pre-fabricated outer panels and corner post for maximum exterior surface protection.
Factory Shrink-Wrap – All TempMaster OmniElite single package units are shipped from the factory with factory-fresh shrink-wrap packaging. No longer does the contractor need to worry about dirt and debris clogging up condenser coils or moisture leaking into the air handler on the units way to the job site or rigging yard.
Copper Fins – For more extreme climates that aggressively can attack aluminum, copper tube evaporator coils with copper fins are available. (This is not recommended for units in areas where they may be exposed to acid rain or environments where ammonia is present.)
CONDENSER FEATURES AND OPTIONS
Scroll Compressors – Reliable, efficient, trouble-free operation is the true measure of
a single package unit’s value. That’s why TempMaster OmniElite single package units use established scroll compressor technology to deliver dependable, economical perfor­mance in a wide range of applications. With the TempMaster OmniElite single package units, you get the latest generation of compressor enhancements added to the scroll’s inherent strengths. The simplicity of a hermetic scroll compressor allows the use of fewer moving parts to minimize breakdown.
Compressor Circuiting – The TempMaster OmniElite is designed so that only two scroll compressors are in tandem within one refrigeration circuit. This means more reliable com-
pressors, and less equipment down time. With multiple circuits, if a compressor should
ever fail on one circuit, the other circuit/s will remain operational to work to maintain oc­cupied loads. The TempMaster OmniElite system has three circuits in a unit.
Compressor Staging - The TempMaster OmniElite refrigeration system is equipped with a unique staging algorithm. On first call for cooling the system calculates the amount of
cooling capacity needed by the space and automatically brings on enough cooling capac­ity to meet this calculated need. Comfort cooling is provided quickly without the lag inher­ent to staging on additional compressors to meet a high demand. Additionally, due to a three independent circuit design with two compressors on each circuit, the TempMaster OmniElite can provide superior granularity in terms of staging, which translates to best in class part load efficiency or IEER.
Condenser Fan Motors – The condenser fan motors used on the TempMaster OmniElite unit are totally enclosed air over (TEAO) to provide maximum durability through any sea­son.
Replaceable Core Liquid Line Driers – Liquid line driers are standard on the TempMas- ter OmniElite single package unit.
Post-Coated Condenser Coil Fins – Technicoat coil-coating process used on condenser coils for seashore and other corrosive applications (with the exception of strong alkalis, oxidizers, wet bromide, chlorine, and fluorine in concentrations greater than 100 ppm).
Compressor Sound Blankets – Optional compressor acoustic sound blankets are avail­able for sound sensitive applications.
TEMPMASTER
11
FORM TPM3-EG1 (518)
Features and Benefits (Cont'd)
ROOF CURBS
Full Perimeter Roof Curbs – This option includes a knock-down 14-inch high roof curb
for use with wood nailer (by others). Roof curb supports the entire perimeter of the unit.
Partial Perimeter Roof Curbs – This option includes a knock-down 14-inch high roof curb for use with wood nailer (by others). Roof curb supports the air handling section with a separate support under the condenser end.
CABINET FEATURES AND OPTIONS
Double-Wall Access Doors - Full-sized access doors provide easy access into the unit
for routine maintenance and inspection. Solid wall liners encase insulation and prevent damage and erosion into the airstream.
Diffuser Section – An optional diffuser section is available downstream of the supply fan in the extended discharge plenum cabinet option. The diffuser section distributes the airflow from the fan evenly across the downstream filter bank to optimize filter life and effectiveness. The diffuser design is optimized to provide uniform flow at minimal airside pressure loss.
Downstream Final Filter Rack – A 90–95% efficient MERV 14, 12-inch rigid filter rack and filters shall be provided downstream of the supply fan and diffuser segment for hospi­tal applications. A magnahelic pressure gauge is included and visible from the outside of the unit for servicing and code compliance.
Blank Section – A blank section shall be provided downstream of the supply fan and dif­fuser section.
ACCESSORIES
Filter Switch – An optional dirty filter alarm can be provided that will provide an alarm
when the filters require cleaning.
Magnahelic Filter Pressure Gauge – On units equipped with downstream filtration, a
magnahelic filter gauge is included and visible on the exterior of the unit. The filter gauge measures the air pressure drop for through the rigid filter bank to indicate when replace-
ment is required.
12
TEMPMASTER
TMAL120–150 MODEL
section
dust and dirt build-up
• Located in conditioned space
Blower variable frequency
drives (VFDs)
In ltered air stream to prevent
• Remote keypad in control
Side discharge with heat
structure or curb
Does not require an elevated
application
• Flexible solution for building
FORM TPM3-EG1 (518)
• Standard low ambient to 0.0°F
• Control to discharge pressure
Quiet part load operation
Shared-fan design
Eliminates stratication
• Fewer moving parts
• Solid steel shaft
• Isolated assembly
• Laser aligned and
Single supply fan
balanced
risk of carryover
• Angled coil to reduce
steel drain pan
• Standard stainless
Evaporator
• OA from two sides
• Facilitates mixing
Mixing box
• Induced draft furnace
• Accepts gas pressures down to 4.5-inches
• Six-stage base design
24:1 modulating gas heat
control solution
communications
ISN ConneXsys
®
MS/TP and Modbus
®
• Multimedia card for updates (no EPROM)
• Multimedia card used for data logging
• Integrated TempMaster
• Standard BACnet
Advanced single package unit controller
centrifugal exhaust fans
Horizontal return for all congurations
• Double width, double inlet (DWDI)
num return fans
Variable frequency drive (VFD) options
• Single width, single inlet (SWSI) ple-
Exhaust & return fans
TEMPMASTER
ping to reduce freight
• Single piece shipment
• Collapsible for ship-
Collapsible outside air
(OA) hoods
• Fast and easy setup
13
FORM TPM3-EG1 (518)
Application Data
GENERAL
The TempMaster® OmniElite™ air conditioning units are designed for outdoor installation. When selecting a site for installation, be guided by the following conditions:
• Unit must be installed on a level surface.
• For the outdoor location of the unit, select a place having a minimum sun exposure
and an adequate supply of fresh air for the condenser.
• Also avoid locations beneath windows or between structures.
• Optional condenser coil protection should be used for seashore locations or other harsh environments.
• The unit should be installed on a roof that is structurally strong enough to support the
weight of the unit with a minimum of deection. It is recommended that the unit(s) be
installed not more than 15 feet from a main support beam to provide proper structural support and to minimize the transmission of sound and vibration. Ideally, the center of gravity should be located over a structural support or building column.
Location of unit(s) should also be away from building ue stacks or exhaust ventila­tors to prevent possible reintroduction of contaminated air through the outside air intakes.
• Be sure the supporting structures will not obstruct the duct, gas or wiring connec­tions.
• Proper service clearance space of 6 feet around the perimeter of the unit, 8 feet on
one side for coil servicing, and 12 feet to any adjacent units is required to eliminate
cross contamination of exhaust and outside air, and for maintenance tasks such as coil pull and cleaning. No obstructions should be above the condensing unit section.
LOCATION
Of the many factors that can effect the location of equipment, some of the most important
to consider are structural, acoustical and service clearances. Proper attention should be
made at the design stage to ensure proper structural support. In cases where equipment is being replaced, be aware of building design to ensure support is adequate for the ap-
plication.
The next most important consideration in applying single package units equipment is that of sound from the equipment. Special care should be made to keep the single package
unit away from sound sensitive areas such as conference rooms, auditoriums and execu­tive offices and any other room that may have potential for tenant occupancy. Possible locations could be above hallways, mechanical or utility rooms.
Finally, service clearances should be maintained in single package unit design to ensure safe access to the unit. Unit clearances are designed so that technicians have enough space between units, building walls, and edges of building to gain access safely. In cases where space is limited, please call a local TempMaster representative for additional infor­mation.
14
TEMPMASTER
FORM TPM3-EG1 (518)
RIGGING
Proper rigging and handling of the equipment is mandatory during unloading and setting
it into position to retain warranty status.
Spreader bars must be used by cranes to prevent damage to the unit casing. All lifting lugs must be used when lifting the single package unit. Fork lifts will damage the single package unit and are not recommended.
Care must be taken to keep the unit in the upright position during rigging and to prevent dam­age to the watertight seams in the unit casing. Avoid unnecessary jarring or rough handling.
UNIT PLACEMENT
Elevated – Elevated roof curbs or dunnage steel can be used to support the unit in
order to raise it to specic heights. When this type of placement is required, be sure to keep unit access in mind. Cat walks or other forms of unit access may be required
to one or both sides of the unit, depending on your area of the country and the local
codes that are enforced. Please check with local ofcials to ensure the application
conforms to local codes and regulations.
• Ground Level Locations – It is important that the units be installed on a substantial
base that will not settle, causing strain on the refrigerant lines and sheet metal and resulting in possible leaks. A one-piece concrete slab with footers extended below the frost line is highly recommended. Additionally, the slab should be isolated from the main building foundation to prevent noise and vibration transmission to the build­ing structure.
For ground level installations, precautions should be taken to protect the unit from tampering by, or injury to, unauthorized persons. Erecting a fence around the unit is common practice.
• Roof curb – TempMaster offers optional roof curbs designed specically for the
TEMPMASTER
TempMaster OmniElite footprint. These curbs come in full perimeter or open con­denser models and are shipped disassembled and require eld assembly and instal­lation. For bottom supply and return openings, the curbs have matching connections to ease installation. A pipe chase that matches the single package unit pipe chase is also included in the curb footprint for through-the-curb utility connections.
15
FORM TPM3-EG1 (518)
Application Data (Cont'd)
The curb should be located according to the location recommendations above, and properly sealed to prevent moisture and air leakage into and out of the duct system. Flexible collars should be used when connecting the ductwork to prevent unit noise transmission and vibration into the building.
Ductwork should be supported independently of the unit.
TABLE 1 - SUPPLY AIR DUCT CONN CONFIGURATIONS
SUPPLY AIR
TMAL
120–150
UNIT CONFIGURATION
Cooling only X X X
Cool/electric heat X
Cool/gas heat X X
Cool/hydronic heat X
Cooling only X X X
Cool/hydronic heat X X X
BOTTOM LEFT RIGHT
STANDARD CABINET
EXTENDED CABINET
TABLE 2 - RETURN AIR DUCT CONNECTION CONFIGURATIONS
RETURN AIR
X X
TMAL
120–150
UNIT CONFIGURATION
No exhaust X X
Barometric
relief damper
Powered exhaust fan (all types) X X
Powered return fan X
BOTTOM FRONT
UNIT ORIENTATION
For applications with multiple single package units located in close proximity on the roof, the orientation of the unit may be important to reduce the potential for re-entrainment of outside airflow. Regardless of the outside air and exhaust air openings on a unit, all single package unit applications can permit recirculation of exhaust air to the return, if applied improperly.
HORIZONTAL APPLICATIONS
The spectrum of applications for single package units in today’s market is continuing to grow wider by the day. Flexibility in unit design and construction is a must in today’s mar-
ket in order to ensure safe and sound applications of HVAC equipment. The TempMaster
OmniElite has been designed for specific application of horizontal supply and return air­flow taking the guess work out of unit application by building a unit specific to these needs. If the application calls for horizontal supply and return air, TempMaster can ship it from the factory as a horizontal unit. This option eliminates the need for field modification of equip­ment saving time and money. The TempMaster OmniElite can support a left discharge on all units except electric heat and/or right discharge on all cooling only units and hydronic heat units with an extended cabinet. Return air can be brought through the front or bottom return air inlet making the unit specific to building needs.
16
TEMPMASTER
FORM TPM3-EG1 (518)
TOP VIEW SIDE VIEW
LD08045
FRONT
FRONT
NOTE: This diagram is provided as a visual reference of the TempMaster OmniElite discharge air (DA) & return air (RA) openings & locations for all sizes. Please refer to the dimensional data for exact size & location of panels and openings.
ECONOMIZER
The economizer section is used for ventilation of the conditioned space to maintain indoor
air quality (IAQ), and also to reduce energy consumption by using outside air cooling in lieu
of mechanical cooling. If outside air is appropriate for cooling, but not sufficient for the cool­ing demand, mechanical cooling will stage on as necessary until the cooling load is met.
Dual (comparative or differential) enthalpy operation is the most accurate and efficient means of economizer operation. The IPU controller monitors the return and outside air energy content, and selects the lower of the two for operation.
VARIABLE AIR VOLUME (VAV) SUPPLY AIR PRESSURE CONTROL
Traditional single package unit systems use inlet guide vanes (IGVs) for duct static pres­sure control. These control supply duct pressure by modulating dampers (introducing losses
and inefficiencies) on the inlet of the fan, open and closed. TempMaster variable frequency drives (VFDs) offer superior fan speed control and quieter, energy efficient operation.
FIGURE 3 - TRADITIONAL OVERHEAD VARIABLE AIR VOLUME (VAV) AIR DELIVERY SYSTEM
For variable air volume (VAV) applications, the TempMaster OmniElite unit uses a VFD to modulate fan speed and maintain a constant duct static pressure. VFDs offer superior control over the operation of the unit at part load, and offer the additional benefits of qui­eter and more efficient operation when compared to IGV.
BUILDING PRESSURE CONTROL SYSTEMS
Building pressure control systems are often necessary when economizers are used to bring in outside air. Without proper building exhaust, the building may become over pres­surized. The pressure control system maintains the proper building pressure by expelling the appropriate amount of air from the building.
TEMPMASTER
17
FORM TPM3-EG1 (518)
Application Data (Cont'd)
Return fans – For high return static applications, such as buildings with ducted return systems, a powered return fan may be necessary to maintain building pressure control. TempMaster offers a powered return fan that is located in the return plenum. This fan operates coincidentally with the supply fan and draws return air back through the return ductwork and into a pressurized plenum. A control damper modulates to exhaust air out of the building and maintain the building pressure. A second control damper modulates to provide return air from the ductwork to the unit to the single package air mixing section.
The return fan configuration is available in two forms: with and without an exhaust damper. The option with the exhaust damper provides a means of building exhaust at the unit. In some applications, the exhaust system is located elsewhere and the single package unit
is not required to provide building exhaust. In these situations, the TempMaster OmniElite
can be offered without the exhaust damper to help reduce installed costs.
Exhaust/relief fans – In this application, a powered exhaust fan may be suitable, how­ever careful consideration of the fan type is necessary. TempMaster offers a centrifugal powered exhaust fan to perform this function. Some manufacturers use a propeller ex-
haust fan, which cannot handle the static pressure requirements.
For systems with moderate to low return static pressure, an exhaust fan is recommended. The benefit of the exhaust fan is that it does not run all of the time, and may facilitate com-
pliance with the ASHRAE 90.1 fan motor horsepower requirement.
The exhaust fan operates in parallel with the supply fan. In this arrangement, the supply fan handles the full static pressure requirements of the system. For normal building pres­sure control, the exhaust fan operates to draw air from the return plenum and exhaust it out of the building.
The exhaust fan configuration is available in two forms, modulating and non-modulating. Modulating is the most common and recommended for the majority of applications, while non-modulating should be used in only certain circumstances.
In the modulating exhaust system, the volume of airflow exhausted from the building is proportional to the entering volume of outside air. Control is accomplished via either a dis­charge damper or a VFD. TempMaster recommends the use of a VFD to reduce energy consumption, sound levels and improved reliability due to fewer moving parts.
In the non-modulating exhaust system, the exhaust airflow is constant whenever the ex­haust fan is operating. This type of control should only be used to either assist a smoke
purge system or when a system requires a constant volume of exhaust airflow.
ACOUSTICAL CONSIDERATIONS
The TempMaster OmniElite unit is designed for lower sound levels than competitive units by using flexible fan connections, fan spring isolators, double-wall construction, multiple fan options, and lower speed and horsepower fans. For VAV applications, VFDs are used instead of inlet guide vanes. Additional sound attenuation can be obtained using compres­sor sound blankets when necessary.
Even with these equipment design features, the acoustical characteristics of the entire
installation must never be overlooked. Additional steps for the acoustical characteristics of a single package unit installation should be addressed during the design phase of a
project to avoid costly alterations after the installation of the equipment. During the design
phase of a project, the designing engineer should consider, at a minimum, the impact of
the equipment location, single package unit installation, building structure, and ductwork.
18
TEMPMASTER
FORM TPM3-EG1 (518)
Physical Data
TABLE 3 - PHYSICAL DATA – MODELS 120–150
MODEL SIZE 120 130 150 COMPRESSOR DATA
Quantity/Size (nominal HP) 4x15/2x25 2x15/2x20/2x25 2X15/2X20/2X32 Type Scroll Scroll Scroll Capacity Steps 14 steps providing capacity control between 12 and 100%
DOUBLE WIDTH, DOUBLE INLET (DWDI) AIRFOIL SUPPLY FAN AND DRIVE
Quantity 1 1 1 Size 40 40 40 Motor Size Range (min. to max. HP) 10–100 10–100 10–100 Airow Range (min. to max. CFM) 30000–52000 32000–52000 36000–52000 Static Pressure Range (min. to max. ESP) 0–6 inches 0–6 inches 0–6 inches
DIRECT DRIVE PLENUM (DDP) SUPPLY FAN AND DRIVE
Quantity 2 2 2 Size 330-100/120 330-100/120 330-100/120 Motor Size Range (min. to max. HP) 10–60 10–60 10–60 Airow Range (min. to max. CFM) 20000–45000/52000 20000–45000/52000 20000–45000/52000 Static Pressure Range (min. to max. ESP) 1–8 inches 1–8 inches 1–8 inches
EXHAUST FAN
Quantity 1 1 1 Type DWDI Forward-Curved Size 32–32 32–32 32–32 Motor Size Range (min. to max. HP) 7.5–60 7.5–60 7.5–60 Airow Range (min. to max. CFM) 0–50000 0–50000 0–50000 Static Pressure Range (min. to max. ESP) 0–2 inches 0–2 inches 0–2 inches
RETURN FAN
Quantity Fans/Motors 1 1 1 Type SWSI Plenum SWSI Plenum SWSI Plenum Size 445 445 445 Motor Size Range (min. to max. HP) 10–50 10–50 10–50 Airow Range (min. to max. CFM) 0–50000 0–50000 0–50000 Static Pressure Range (min. to max. iwg) 0–3 0–3 0–3
EVAPORATOR COIL
Size (sq. ft.) 81.7 81.7 81.7 Number Of Rows/Fins Per Inch 5 / 10 5 / 10 5 / 10 Tube Diameter (inches) 1/2 1/2 1/2
CONDENSER COIL
Size (sq. ft.) 262 262 262 Number Of Rows/Fins Per Inch 1/21 1/21 1/21
CONDENSER FANS
Quantity 9 9 9 Type Prop Prop Prop Diameter (inches) 36 36 36 Power (HP) 2 2 2
FILTERS - 2-INCH CLEANABLE (PRE-FILTER POSITION)
Quantity 36/12 36/12 36/12 Size (length x width in inches) 16x20/20x20 16x20/20x20 16x20/20x20 Total Filter Face Area (sq. ft.) 113.3 113.3 113.3
FILTERS - 2-INCH PLEATED, 30% EFFICIENT (PRE-FILTER POSITION) (MERV 8)
Quantity 36/12 36/12 36/12 Size (length x width in inches) 16x20/20x20 16x20/20x20 16x20/20x20 Total Filter Face Area (sq. ft.) 113.3 113.3 113.3
TEMPMASTER
19
FORM TPM3-EG1 (518)
Physical Data (Cont'd)
TABLE 3 – PHYSICAL DATA – MODELS 120-150 (CONT'D)
MODEL SIZE 120 130 150 FILTERS - 2-INCH CARBON (PRE-FILTER POSITION) (MERV 7)
Quantity 36/12 36/12 36/12 Size (length x width in inches) 16x20/20x20 16x20/20x20 16x20/20x20 Total Filter Face Area (sq. ft.) 113.3 113.3 113.3
FILTERS - 12-INCH RIGID 65%, 2-INCH 30% PREFILTER (PRE-FILTER POSITION) (MERV 11)
Quantity 7/21 7/21 7/21 Size (length x width in inches) 20x16/20x25 20x16/20x25 20x16/20x25 Total Filter Face Area (sq. ft.) 88.5 88.5 88.5
FILTERS - 12-INCH RIGID 95% (FINAL FILTER POSITION) (MERV 14)
Quantity 5/3/3/4/6/7 5/3/3/4/6/7 5/3/3/4/6/7
12x24,16x20 12x24,16x20 12x24,16x20
Size (length x width in inches)
Total Filter Face Area (sq. ft.) 80.4 80.4 80.4
GAS FURNACE
Staged Furnace Sizes (input/output/stages)
Gas Pressure Range (min. to max. iwg)
Modulating Furnace Sizes (input/output/turndown)
Gas Pressure Range (min. to max. iwg)
ELECTRIC HEATERS
Size Range (min. to max. kW) 80-250 80-250 80-250 Heating steps Minimum steps
MINIMUM OUTSIDE AIR (OA)TEMPERATURE FOR MECHANICAL COOLING LOW AMBIENT OPTION MIN. OA TEMP 0 0 0
1
1
Natural 4.5–10.5 inch w.c. 4.5–10.5 inch w.c. 4.5–10.5 inch w.c.
Propane 11.0–13.0 inch w.c. 11.0–13.0 inch w.c. 11.0–13.0 inch w.c.
Natural 4.5–10.5 inch w.c. 4.5–10.5 inch w.c. 4.5–10.5 inch w.c.
Propane 11.0–13.0 inch w.c. 11.0–13.0 inch w.c. 11.0–13.0 inch w.c.
16x25, 20x20 16x25, 20x20 16x25, 20x20 20x24, 20x25 20x24, 20x25 20x24, 20x25
1125 mbh/900 mbh/6 stages
1125 mbh/900 mbh/24:1 turndown
2-6 2-6 2-6
2 2 2
50 50 50
NOTES
1. Electric heat steps and airow range depends on voltage and size. Consult the air pressure drop tables for specic number of steps for a given voltage.
TABLE 4 - REFRIGERANT CHARGE DATA
120 130 150
REFRIGERANT CHARGE (STD CABINET)
SYS 1 - lb (kg) 41 (18.6) 41 (18.6) 41 (18.6) SYS 2 - lb (kg) 73 (33.1) 82 (37.2) 77 (34.9) SYS 3 - lb (kg) 97 (44.0) 98 (44.4) 106 (48.1)
REFRIGERANT CHARGE (EXTD CABINET)
SYS 1 - lb (kg) 43 (19.5) 43 (19.5) 43 (19.5) SYS 2 - lb (kg) 75 (34.0) 84 (38.1) 79 (35.8) SYS 3 - lb (kg) 100 (45.4) 101 (45.8) 109 (49.4)
20
TEMPMASTER
Weight Data
FORM TPM3-EG1 (518)
TABLE 5 - APPROXIMATE BASE OPERATING WEIGHTS (LBS)
MODEL SIZE 120 130 150 SINGLE PIECE UNIT 18,238 18,847 18,938 TWO PIECE UNIT
Air Handler Section 12,131 12,325 12,332 Condenser Section 6,096 6,510 6,597
NOTES:
• Weights above are total weight excluding the curb
• Standard cabinet
• Cooling only
60 HP supply fan with variable frequency drive (VFD)
• Comparative enthalpy economizer
• Barometric relief exhaust
• Bottom supply and return
2-inch pleated lters
• Condenser section wire guards
• Weights represent approximate operating weights and have a +/- 10% accuracy. To calculate weight for a specic congura­tion, contact a TempMaster sales representative.
TABLE 6 - COMPONENT WEIGHTS (LBS)
MODEL SIZE 120 130 150 CABINET, AIR HANDLING SECTION
Sheet Metal (Note 1) 6,310 Control Panel (Note 2) 705
REFRIGERANT
Refrigerant Charge (R-410A) 210 230 230
COMPRESSORS 826 1,661 1,738 CONDENSER ASSEMBLY
Sheet Metal 2,477 Coils 864 Condenser Fans 90 Condenser Motors 450 Condenser Grills 90 Wire Guards 266 Louvered Panel Guards 432
DWDI AIRFOIL SUPPLY FAN SKID WITHOUT MOTOR (NOTE 3) 1,696 SUPPLY FAN MOTOR DRIVE 80 DUAL DIRECT DRIVE PLENUM (DDP) FAN SKIDS WITHOUT MOTOR
Frame 215T DDP 330-100/120 565/579 Frame 254T DDP 330-100/120 Frame 256T DDP 330-100/120 Frame 284T DDP 330-100/120 Frame 286T DDP 330-100/120 Frame 324T DDP 330-100/120 Frame 326T DDP 330-100/120 Frame 364T DDP 330-100/120 709/722
MOTOR (SUPPLY/EXHAUST/RETURN)
7.5 HP 151 10 HP 165 15 HP 255 20 HP 286 25 HP 379 30 HP 437 40 HP 578 50 HP 700 60 HP 885 75 HP 930 100 HP 1,225
VARIABLE FREQUENCY DRIVE (VFD) (SUPPLY/EXHAUST/RETURN)
5–10 HP 16 15–25 HP 27 30–40 HP 51 50–75 HP 77 100 HP 110
584/597
608/621
692/705
TEMPMASTER
21
FORM TPM3-EG1 (518)
Weight Data (Cont'd)
TABLE 6 – COMPONENT WEIGHTS (LBS) (CONT'D)
MODEL SIZE 120 130 150 EVAPORATOR COILS 921 1,106 1,106 FILTERS
2-inch Cleanable Aluminum 74 2-inch Pleated 40 2-inch Carbon 94 Return Filter - 2-inch Throwaway (Note 4) 30 Return Filter - 12-inch 60–65% (Note 4) 393 Return Filter - 12-inch 90–95% (Note 4) 388 Final Filters 327
ECONOMIZER
Outside Air Dampers 255 Outside Air Hoods 291 Outside Air Filters 103
EXHAUST FAN SKID WITHOUT MOTOR 1,147 RETURN FAN SKID WITHOUT MOTOR 1,574 EXHAUST
No Exhaust - End Panels 332 Exhaust Fan (Damper and Hood) 516 Return Fan (Damper and Hood) 539
HEATING OPTIONS
Electric Heat - 80 kW 660 Electric Heat - 108 kW 680 Electric Heat - 150 kW 700 Electric Heat - 200 kW 720 Electric Heat - 250 kW 740 Gas Heat - 1125 mbh 1,455
Hot Water Coil (2 rows x 14 ns per inch) 417 Steam Coil (1 rows x 10 ns per inch) 534
MISCELLANEOUS
Open Perimeter Curb 684 Enclosed Perimeter Curb 1,110 Airow Measurement Option 45
NOTES:
1. Sheet metal, air handling cabinet cooling only.
2. Includes all options.
3. Motor base is included in fan skid.
4. Filters only. Does not include the lter rack.
Weights represent approximate operating weights and have a +/- 10% accuracy. To calculate weight for a specic conguration, contact a
TempMaster sales representative.
22
TEMPMASTER
Cooling Performance Data
TABLE 7 - COOLING PERFORMANCE DATA* – 120 TON MODEL
AIR ENTERING
EVAPORATOR
COIL
CFM
32000
34500
37000
39500
42000
44500
47000
49500
52000
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
WET
BULB (°F)
75 1778.4 1080.0 1777.1 907.1 1773.2 732.3 71 1660.9 1202.8 1660.9 1031.4 1659.3 855.9 1659.3 674.7 67 1552.6 1325.4 1552.6 1155.3 1550.9 974.7 1550.9 797.9 1550.9 621.1 62 1491.5 1443.6 1425.1 1309.3 1423.2 1126.8 1421.7 951.0 1420.2 775.1 75 1802.4 1124.4 1800.2 935.7 1797.3 745.6 71 1684.4 1258.4 1684.0 1071.4 1682.8 879.6 1682.8 683.4 67 1587.6 1376.3 1586.2 1210.8 1584.9 1013.5 1584.9 822.0 1584.9 630.6 62 1530.6 1488.1 1462.4 1355.8 1461.0 1183.4 1459.9 992.1 1458.7 800.8 75 1826.5 1168.9 1823.4 964.3 1821.4 758.9 71 1707.9 1314.0 1707.0 1111 .4 1706.2 903.3 1706.2 692.2 67 1622.5 1427.2 1619.8 1266.2 1618.9 1052.2 1618.9 846.1 1618.9 640.0 62 1569.7 1532.6 1499.7 1402.3 1498.8 1240.0 1498.0 1033.3 1497.3 826.5 75 1850.5 1213.4 1846.5 992.8 1845.5 772.2 71 1731.4 1369.5 1730.1 1151.3 1729.7 927.0 1729.7 700.9 67 1657.5 1478.0 1653.4 1321.7 1653.0 1091.0 1653.0 870.2 1653.0 649.5 62 1608.8 1577.1 1537.0 1448.8 1536.5 1296.6 1536.2 1074.4 1535.8 852.2 75 1874.6 1257.9 1869.6 1021.4 1869.6 785.5 71 1754.8 1425.1 1753.1 1191.3 1753.1 950.7 1753.1 709.6 67 1692.4 1528.9 1687.0 1377.1 1687.0 1129.7 1687.0 894.3 1687.0 658.9 62 1648.0 1621.6 1574.3 1495.3 1574.3 1353.2 1574.3 1115.6 1574.3 877.9 75 1889.9 1301.0 1886.2 1049.3 1885.6 797.6 71 1770.3 1479.3 1768.2 1229.8 1767.5 972.4 1767.5 717.1 67 1702.0 1551.9 1698.0 1424.0 1698.0 1159.6 1698.0 910.3 1698.0 660.9 62 1679.4 1656.2 1597.8 1528.5 1572.1 1374.8 1571.1 1130.2 1570.1 885.7 75 1905.3 1344.1 1902.8 1077.1 1901.6 809.6 71 1785.8 1533.5 1783.3 1268.3 1781.9 994.0 1781.9 724.5 67 1711.6 1575.0 1708.9 1470.9 1708.9 1189.5 1708.9 926.2 1708.9 662.9 62 1710.8 1690.8 1621.4 1561.6 1569.9 1396.3 1567.9 1144.9 1565.8 893.5 75 1920.6 1387.2 1919.3 1105.0 1917.5 821.7 71 1801.2 1587.6 1798.4 1306.7 1796.3 1015.7 1796.3 731.9 67 1721.2 1598.0 1719.9 1517.7 1719.9 1219.4 1719.9 942.2 1719.9 664.9 62 1742.1 1725.4 1644.9 1594.8 1567.7 1417.9 1564.6 1159.5 1561.6 901.2 75 1935.9 1430.3 1935.9 1132.8 1933.5 833.7 71 1816.7 1641.8 1813.5 1345.2 1810.7 1037.3 1810.7 739.4 67 1730.8 1621.0 1730.8 1564.6 1730.8 1249.3 1730.8 958.1 1730.8 666.9 62 1773.5 1760.0 1668.4 1627.9 1565.5 1439.4 1561.4 1174.2 1557.3 909.0
92.0°F 86.0°F 80.0°F 74.0°F 68.0°F
TMBH SMBH TMBH SMBH TMBH SMBH TMBH SMBH TMBH SMBH
OUTDOOR AMBIENT TEMPERATURE 75.0°F
ENTERING DRY BULB TEMPERATURE
FORM TPM3-EG1 (518)
TEMPMASTER
23
FORM TPM3-EG1 (518)
Cooling Performance Data (Cont'd)
TABLE 7 – COOLING PERFORMANCE DATA* – 120 TON MODEL (CONT’D)
AIR ENTERING
EVAPORATOR
COIL
CFM
32000
34500
37000
39500
42000
44500
47000
49500
52000
* Rated performance is at sea level. Cooling capacities are gross cooling capacity.
WET
BULB (°F)
75 1708.2 1052.4 1706.8 879.6 1702.1 704.6 71 1596.2 1175.4 1595.9 1004.0 1594.2 828.6 1594.2 647.4 67 1489.4 1296.6 1488.0 1126.1 1487.1 945.9 1487.1 769.1 1487.1 592.4 62 1442.9 1407.3 1378.7 1286.1 1377.8 1104.2 1377.0 928.8 1376.3 753.5 75 1731.2 1097.0 1729.6 908.4 1726.0 718.3 71 1618.4 1230.9 1617.9 1044.0 1616.7 852.4 1616.7 656.2 67 1525.2 1346.8 1510.0 1177.0 1509.4 980.0 1509.4 788.7 1509.4 597.4 62 1462.6 1430.7 1414.5 1329.2 1394.3 1151.2 1393.7 960.4 1393.1 769.5 75 1754.2 1141.6 1752.3 937.3 1750.0 732.1 71 1640.6 1286.5 1640.0 1084.1 1639.2 876.2 1639.2 665.1 67 1561.1 1397.0 1532.1 1227.9 1531.7 1014.2 1531.7 808.3 1531.7 602.3 62 1482.4 1454.1 1450.3 1372.3 1410.8 1198.2 1410.4 991.9 1410.0 785.6 75 1777.1 1186.1 1775.1 966.1 1773.9 745.8 71 1662.8 1342.1 1662.1 1124.1 1661.7 900.1 1661.7 674.0 67 1597.0 1447.2 1554.2 1278.8 1554.0 1048.4 1554.0 827.8 1554.0 607.3 62 1502.1 1477.4 1486.1 1415.5 1427.3 1245.3 1427.1 1023.5 1426.9 801.7 75 1800.1 1230.7 1797.8 995.0 1797.8 759.5 71 1685.1 1397.6 1684.2 1164.1 1684.2 923.9 1684.2 682.8 67 1632.9 1497.4 1576.3 1329.7 1576.3 1082.6 1576.3 847.4 1576.3 612.2 62 1521.9 1500.8 1521.9 1458.6 1443.8 1292.3 1443.8 1055.1 1443.8 817.8
75 1813.5 1273.6 1811.5 1022.3 1811.0 771.0
71 1702.5 1439.3 1697.2 1202.2 1696.8 945.2 1696.8 690.0 67 1647.6 1528.4 1593.1 1379.7 1592.8 1115.4 1592.8 866.2 1592.8 617.1 62 1566.3 1548.8 1532.5 1480.0 1472.1 1341.6 1466.1 1088.5 1460.1 835.3 75 1826.8 1316.4 1825.1 1049.6 1824.3 782.5 71 1720.0 1480.9 1710.2 1240.3 1709.4 966.6 1709.4 697.1 67 1662.3 1559.5 1609.9 1429.7 1609.3 1148.2 1609.3 885.0 1609.3 621.9 62 1610.7 1596.8 1543.1 1501.4 1500.5 1391.0 1488.4 1121.9 1476.3 852.8 75 1840.2 1359.2 1838.8 1076.9 1837.5 794.0 71 1737.4 1522.5 1723.2 1278.4 1722.0 987.9 1722.0 704.3 67 1677.0 1590.6 1626.7 1479.7 1625.8 1180.9 1625.8 903.9 1625.8 626.8 62 1655.1 1644.7 1553.7 1522.7 1528.8 1440.3 1510.7 1155.3 1492.6 870.3 75 1853.5 1402.1 1852.4 1104.3 1850.7 805.5 71 1754.8 1564.1 1736.2 1316.5 1734.7 1009.2 1734.7 711.4 67 1691.7 1621.6 1643.5 1529.7 1642.4 1213.7 1642.4 922.7 1642.4 631.7 62 1699.5 1692.7 1564.4 1544.1 1557.1 1489.6 1533.0 1188.7 1508.8 887.8
92.0°F 86.0°F 80.0°F 74.0°F 68.0°F
TMBH SMBH TMBH SMBH TMBH SMBH TMBH SMBH TMBH SMBH
OUTDOOR AMBIENT TEMPERATURE 85.0°F
ENTERING DRY BULB TEMPERATURE
24
TEMPMASTER
Loading...
+ 56 hidden pages