TemperZone ISD 840K, ISD 950K Installation & Maintenance

Page 1
ISD 840K, 950K
Ducted Split System Indoor Units
Installation & Maintenance
GENERAL
These ISD indoor units are designed to be coupled with their respective OSA outdoor units. Units must be installed in accordance with all national and local safety codes.
Combinations
One ISD 840K with one OSA 840RKTB One ISD 950K with one OSA 950RKTB
Option
TZT-701 or SAT-2 Thermostat Filters
INSTALLATION Unpacking
The unit's supply air spigot has been secured inside the unit for ease of shipping. Remove the spigot and secure it in place using the existing screws.
Positioning & Mounting
Provide sufficient clearance to the access panels.
Mount on a suitable level platform using vibration isolators. Access to fixing centres beneath the return air spigot can be made via the removeable bungs in the spigot's base.
Condensate Drain
The unit has an internal sloping condensate drain tray. The trap should have a vertical height of at least 100 mm. The drain should have a slope of at least 1 in 50 and must not be piped to a level above the unit drain tray (refer Fig.2).
For long condensate pipe runs, fit a vent pipe near the drain trap. The top of the vent pipe must be at least 100 mm above the ISD unit's drain tray.
It is essential that the drainage system for the evaporator is checked by pouring water in the drain tray and seeing that it discharges at the end of the drain and does not overflow the drain tray.
INDOOR-OUTDOOR UNIT CONNECTIONS
Refer to the relevant OSA Outdoor Unit 'Installation & Maintenance' pamphlet for piping instructions. For wiring connections, refer to the Outdoor Unit wiring diagram.
REFRIGERATION PIPING Pipe Connection Sizes & Type
Liquid : 16 mm OD (
5
/8") sweat
Suction : 35 mm OD (11/8") sweat
The ISD is shipped from the factory with a pressurised holding charge of nitrogen. Immediately before removing any brazed
Fig.1 Dimensions (mm)
Not to Scale
Net Weight ISD 840K 372 kg ISD 950K 383 kg
Fig. 2
NOTE
The manufacturer reserves the right to change specifications at any time without notice or obligation. Certified dimensions available on request.
CORNER LOADS (kg)
MODEL W X Y Z
ISD840K 70 116 116 70
ISD950K 66 137 125 55
OPEN DRAIN
MINIMUM SLOPE 20 mm PER m (1 IN 50)
100 mm MINIMUM
200 mm
APPROX.
'U' TRAP
100 mm
APPROX.
VENT PIPE FOR LONG CONDENSATE DRAIN RUNS
Condensate Drain
PROJECTION
2005
2220 OA
75
75
DRAIN 28 OD
150
60
1320 OA
W
X
Y
Z
REFRIG. CONN’S
1000 MIN. CLEARANCE
1360
MOUNTING CENTRES
105
430
500 MIN. CLEARANCE
REFRIGERANT CONNECTIONS
ELECTRICAL BOX
ACCESS PANEL
FILTER ACCESS EITHER SIDE
VERTICAL
DISCHARGE
MODEL
ELECTRICAL
ACCESS
PANEL
A
B
470
565830
305
470
535
MODEL A B
ISD840K 1070 955
ISD950K 1280 1165
Page 2
pipe connection's seal, reduce holding charge to atmospheric pressure. Warning: failure to do so may cause injury.
Refer to the Outdoor Unit 'Installation & Maintenance' pamphlet for evacuation procedure and piping requirements.
ELECTRICAL WIRING
The electrical supply required (via the Outdoor Unit) is specified on the Outdoor Unit's wiring diagram.
Electrical work must be carried out by a qualified electrician in accordance with local supply authority regulations and the wiring diagram.
In a free blow or low resistance application, beware of exceeding the fan motor's full load amp limit (refer Outdoor Unit's wiring diagram).
To make the indoor fan switch off during de-ice cycle, refer to the Outdoor Unit wiring diagram for the appropriate changes.
INDOOR FAN SPEED
The fan motor is fitted with a factory set adjustable pitch pulley. One revolution of adjustment is equal to 7% change in air volume flow rate.
To change the fan speed loosen the motor mounting plate hold down screws, loosen the pulley grub screws and turn the pulley flange the desired amount. The pulley adjustment is locked by tightening the grub screws in the keyways.
When setting air flows ensure that the pulleys are in alignment. Tension the belt by adjusting the motor mounting plate.
COMMISSIONING
Indoor Unit
1. Check that the thermostat is correctly wired and set at the desired temperature.
2. Check that any air filter (if fitted) is clean.
3. Check that the fan runs freely without vibration.
4. Check the airflow at each air outlet (diffuser) and adjust if necessary.
5. Check condensate drain for free drainage.
6. Run the unit in cooling mode and heating mode.
MAINTENANCE Weekly For First Four Weeks
1. Check air filter (if fitted); vacuum clean as
necessary.
2. Check condensate drain for free
drainage.
Monthly
Check air filter (if fitted); vacuum clean as necessary.
Six Monthly
1. Check condensate drain for free
drainage.
2. Check heat exchanger coil; vacuum or
brush clean as necessary.
3. Check the tightness of the fan, motor
mountings, pullley and belt tension.
4. Check that fan motor is free running.
5. Check tightness of electrical connections.
6. Check air supply at diffuser outlets.
WARNING
This unit is designed for use ONLY with the refrigerant HFC -410A (R410A). The use of other refrigerants is NOT authorised or approved by the manufacturer and may cause operational problems such as poor performance and efficiency, loss of capacity, degradation of materials and refrigerant leaks.
The use of flammable or explosive materials as a refrigerant creates the additional risks of fire and explosion which may result in property damage, personal injury or death.
NOTE
The manufacturer reserves the right to change specifications at any time without notice or obligation. Certified dimensions available on request.
This pamphlet replaces the previous issue no. 3753 dated 08/13. Minor dimension correction.
12/13 Pamphlet No. 3753
© temperzone limited 2013
Loading...