Unit Specifications .......................................................................................... 2
1-800-836-7432
Warning!
Improper installation, adjustment, alteration, service, or
maintenance can cause injury
or property damage. Please
read instructions before installing, operating or servicing the
TEMP-COOL unit.
Avertissement !
Le fait de modier ou de mal
installer, régler, réparer ou
entretenir cet appareil peut
entraîner des blessures ou des
dommages matériels. On doit
lire attentivement les directives
d’installation, d’utilisation et
d’entretien avant de manipuler
l’unité TEMP-COOL
Rating Information ........................................................................................... 2
This manual is the property
of the owner. Leave with the
unit when set-up and start-up
are complete. TEMP-AIR
Inc. reserves the right to
change design and specications without prior notice.
LxWxH, in.28 x 23 x 4733 x 26 x 4730 x 28 x 5147 x 31 x 6447 x 31 x 6447 x 31 x 64
Weight, net wt/shipping wt, lb.221/279337/375336/395713/775713/775713/775
1
17,30029,60041,00075,90075,90075,900
1. Rating conditions: 95° F at 60% RH
2. Electrical ratings based on UL 484
TEMP-COOL
™
Owner’s Manual
Portable Cooling Systems
INSPECTION
1. Inspect unit on delivery.
2. Compare unit received with description of product
ordered.
3. Report any damage to the delivery carrier.
4. Request a written inspection report from the Claims
Inspector to substantiate claim.
5. File claims with the delivery carrier.
GENERAL DESCRIPTION
TEMP-COOL Portable Cooling Systems are designed
to spot cool industrial, commercial, institutional and
construction sites. Six models provide from 17,300 to
75,900 BTU/hr. of cooling and from 1740 to 7000 watts
of electric heat. Options include discharge nozzles to
direct conditioned air precisely where needed, and exible duct to transfer condenser hot air either outside or to
an adjacent area.
TEMP-COOL Portable Cooling Systems are completely
self-contained and housed within an insulated cabinet.
The units’ exterior is constructed of galvanized steel and
protected with a tough powder-coated, polyester nish.
All models are equipped with standard heavy-duty casters
for portability.
STANDARD FEATURES
Serviceability
Normal maintenance for the TEMP-COOL Portable
Cooling Systems requires a minimum amount of effort. The two air lters that cover the coils can easily be
inspected and replaced by removing the grilles holding
them. The TC-18B through the TC-36B have an internal
condensate tank that must be emptied when full. The tank
is in a rollout drawer mounted on ball bearing drawer
slides. The large TC-60B units have an integral condensate pump, with a condensate tube that must be run to a
drain or container.
All of the other components, which are normally
accessed for troubleshooting or replacement, can be
accessed by removing the side panels or top cover. The
electrical control panels can readily be accessed from the
exterior of the unit through access doors. On the TC-18B
through TC-36B the high head pressure reset switch can
be accessed by opening the condensate tank drawer and
pressing the button located on the back wall of the enclosure. On the TC-60B units the reset button is located
in the cord pocket enclosure, which is accessible from
outside the unit.
High-Pressure Safety Switch
All models feature a manual reset, high-pressure switch.
If the refrigeration circuit exceeds the controls pressure
setting, power to the compressor and other critical components is cutoff to prevent damage to the unit.
Note: Determine the reason for the the trip and correct
the problem before resetting the switch (See the
troubleshooting section for suggestions. Wait four
minutes before attempting to reset.)
Digital Temperature Control System
The digital temperature control system allows the user
to select Cooling or Fan Only operating modes. It also
allows the unit to be started or stopped after a predetermined period. The control also has internal functions
that prevent the cooling coil from freezing, prevent the
compressor from cycling excessively and provide a
heating element cool down function when in the heating
mode. See the section covering the operation of the unit for
additional information on the Digital Temperature Control.
Filters
All units are equipped with removable, disposable,
pleated media lters. Located behind the return air and
condenser intake air grilles, they can be removed for
inspection or replacement by removing the grille.
Condensate Tank
The TC-18B through TC-36B are furnished with a ve
gallon, polyethylene condensate tank located in the
drawer on the lower front of the unit. The tank collects
the moisture that condenses on the cooling coil when the
unit is in operation. When full, a magnetic oat in the
tank closes a magnetic proximity switch located above
the tank inside the unit, turning the unit off and causing
“tF” to be displayed on the front panel of the unit. The
condensate tank must be emptied and reinstalled to allow
further operation.
Note: The unit will not operate unless the tank is
drained periodically. Optional condensate pumps
are available that allow continuous operation,
but require a tube to be run from the pump to a
suitable drain.
3
Condensate Pump
G
X
W
Y
G
G
G
G
X
W
Y
G
G
Due to the large amount of condensate produced by the
TC-60B models, condensate tanks are not furnished or
available on these units. Condensate pumps are furnished
as standard on the TC-60B models, and must be piped to
a suitable drain.
Cord Kit (LCDI) (TC-18B, 24B, 36B)
The LCDI cord kit provides both personal shock as well
as cord arcing and re protection. The LCDI cord kit is
preinstalled and must be replaced with an identical cord
kit, available from Temp-Air, Inc., if damaged or if it fails
to operate properly.
INSTALLATION INSTRUCTIONS:
Before Installing:
Check unit for damage. Air conditioners are inspected at
the factory. If any damage has occurred, save the packaging and le a claim with the delivering carrier within fteen working days. TEMP-COOL units require minimal
installation. The smaller units (TC-18B though TC-36B)
can be plugged into the proper receptacle, and are ready
to run immediately. The larger TC-60B units must be
wired to a plug or power source, and the condensate hose
run to a suitable drain or outdoor location before starting
the unit.
OPTIONAL FEATURES:
See “Accessory” section on page 12 for the correct
accessory part numbers.
Condenser Duct:
Condenser discharge air can be removed from the con-
ditioned space with exible duct. Use 40 feet maximum
for all models. Allow six feet for every 90˚ bend. Do not
exceed 0.10 in. w.c. external static pressure at the condenser.
Ceiling Panel Duct Kit:
A ceiling panel duct kit comes complete with exible
duct and a 2 foot by 2 foot ceiling tile adapter, which allows condenser air to be vented to the plenum area above
a suspended ceiling.
Discharge Nozzle Kit:
A dual-nozzle, discharge air assembly optimizes the abil-
ity to direct cool air precisely where needed. The exible
nozzles are attached to a mounting plate that ts over the
evaporator air grille.
Condensate Pump:
A condensate pump automatically drains from the
condensate pan by removing evaporator coil condensate
water allowing continuous operation. The pump must be
connected to the condensate drain and to the air conditioner’s power supply. A hose must be run from the unit
to a convenient drain or outdoor location.
Condensate pumps are standard on the TC-60B models
and optional on all others.
ModelPlug ConfigurationReceptacle
TC-18B
115V
TC-24B
208-230V
TC-36B
208-230V
W
G
X
G
G
15A/115V
NEMA 5-15P
20A/230V
NEMA 6-20P
30A/230V
NEMA 6-30P
NEMA 5-15P
NEMA 6-20P
NEMA 6-30P
Electrical Supply:
Determine the proper power by checking the unit’s rating plate. For the models from the TC-18B through the
TC-36B use the wall outlets and receptacles shown in the
table above. For the TC-60B, B3 and B4, the units must
be wired to a suitable power supply using the appropriate
cord and circuit protection for the electrical ratings on the
nameplate.
Operating the units at an improper voltage, frequency, or
improper phase orientation (see TC-60B3 and 4 – 3 Phase
Wiring Instructions below) voids the warranty.
Note: Extension cords may be used if rated at a
minimum of 120VAC at 20 amps for the model
TC-18B, 230VAC at 20 amps for the model TC-24B, and 230VAC at 30 amps for the model
TC-36B. All extension cords must have a
functional grounding connector and t the LCDI
cord supplied with the unit.
Extension cords cannot be used on the TC-60B
models.
TEMP-COOL
™
Owner’s Manual
Portable Cooling Systems
TIMERSLEEP
HOURTEMP
HOURTEMP
MODE
COOL
FAN
TC-60B3 and B4 – 3 Phase Wiring Instructions:
Only qualied personnel should install TC-60B units.
Extra care is required on the three phase units, the TC60B3 and TC-60B4, to insure they are connected in phase
with the incoming power. If the unit is not in phase the
condenser fan and compressor operate in reverse and
damage the compressor. If the unit is not in phase with
the power supply, the compressor will make more noise
than normal and the condenser fan will deliver very
little air. The evaporator fan can not be used to check the
phase. It has a single phase motor that operates in the correct direction regardless of the phase sequence.
or outside location. Do not crimp or bend the tubing,
or place it where something might be set on the
tubing restricting its ow. No portion of the
discharge tube should be more than 10 feet above the
level of the pump.
5. Attach any required accessories and ductwork.
6. Plug in or wire the unit to an acceptable power source.
7. When power is applied 06 should appear briey on
the control display and disappear. The unit is now ready for use.
Cooling Operation:
1. Press the POWER BUTTON to start the unit. The evaporator (cooling) fan will start and the current space temperature will be shown on the digital display. The unit will start in the last mode used.
2. Select the Cooling mode by using the MODE button
to step through the three available modes (Cool, Heat
and Fan) until the cooling mode indicator light comes
on. The unit is now in the cooling mode.
If the wiring phase sequence is incorrect, reversing any
two of the three incoming power leads will solve the
problem.
UNIT OPERATION:
Placing the Unit:
1. Locate the unit on a at, level service.
2. Keep entering and leaving air openings free of
obstructions. Maintain at least 18” of clearance between air inlet or outlet and any wall or other
obstruction.
3. For a unit with a condensate tank, check the tank to make sure it is in place and empty.
4. For a unit with condensate pump, make sure the condensate discharge tubing is connected to the outlet
connection of the unit and runs to a suitable drain
3. Press the Up or Down temperature button to see the
current cooling setpoint temperature. Adjust the setpoint temperature to the desired value by pressing
the Up or Down temperature button repeatedly, until
the desired temperature is reached. The display will
ash six times at the new setpoint then the actual
room temperature will be displayed. In the cooling
mode up to ve minutes may lapse between turning
the unit on or resetting the temperature and the compressor starting. This delay is a result of the anti
short cycling program in the thermostat. A green dot
will appear in the lower right hand corner of the temperature display when the compressor is being
energized.
4. The compressor and condenser fan will continue to operate until the space temperature drops to the
setpoint temperature. At that point the compressor
and condenser fan will shut off, but the evaporator
fan will continue to run until the unit is turned off.
Fan Operation:
1. Press the POWER BUTTON to start the unit. The evaporator (cooling) fan will start and the current space temperature will be shown on the digital display. The unit will start in last mode used.
2. Select the Fan mode using the MODE button to step
5
through the two available modes (Cool and
Fan) until the fan mode indicator light comes on. The
unit is now in the Fan mode.
3. Pressing the Up or Down temperature buttons has no
effect on the temperature display, since neither the
cooling nor heating functions are active. The tempera-
ture display displays the current room temperature.
4. To stop the fan, turn the unit off using the power
button.
OTHER FUNCTIONS:
PREVENTIVE MAINTENANCE:
TEMP-COOL air-conditioning units provide high performance and reliability with a minimum amount of maintenance. To prolong the life of the unit and insure a high
level of performance, perform regular maintenance as
described below.
only. Always disconnect the unit from its
power supply when performing any form of service
requiring the removal of grilles or panels.
Timer ON/OFF:
Use the following instructions to turn the unit ON or OFF
after a period of up to 15 hours.
1. To turn the unit ON after a preset period press the TIMER button, while the unit is OFF. The display
will ash ve times showing the current delay time in
hours. If a different time delay is required press the
Up or Down Hour buttons until the desired delay time
is displayed. This number can be any whole number
between 1 and 15 hours. When the desired value is
displayed release the key. The selected value will
ash ve times and go blank, but the TIMER light
will remain on. The unit will start in whatever mode
it was in before the timer was set after the specied
delay time. Once set, the timer function can be cancelled by pressing the TIMER button again.
2. To turn the unit OFF after a delay follow the same
procedure as turning the unit ON after a delay except
start by pressing the TIMER button when the unit is
running. The display will ash the OFF delay time
ve times, then the display will revert back to the
normal temperature display. The timer light will be
on when the OFF delay is active. The delay can be
canceled by pressing the TIMER or turning the
unit OFF.
Sleep:
Press the SLEEP button to raise the setpoint temperature
1˚F when in the cooling mode one hour after the button is
pressed. The unit will run in this mode until it is canceled
by pressing the SLEEP button again or turning the unit
OFF.
Filters:
Dirty lters can restrict airow causing the unit to operate with a reduced efciency. Inspect the lters every six
weeks or more frequently, when operating in a dirty en-
vironment. Replace the lters when dirty with an equivalent lter. Do not attempt to clean the lters or operate
the unit without lters. On the TC-18B through TC-36B,
the lters can be removed by snapping the return air and
condenser air grilles out of the unit by pulling on the
handle at the bottom of the grille. The bottom of the grille
will snap out and the grille can be lowered a few inches
to clear the retaining tabs at the top. The lters are held
in place with plastic clips that can be rotated clear of the
lter. Reverse the procedure for replacing the lters. Pay
attention to the proper direction of air ow indicated on
the new lter.
The TC-60B lters are accessed the same as the smaller
units except the snap-in clamps have been replaced
with screws at the bottom of the grilles that have to be
removed before the grille can be detached. Additional
retainer clips are not used on the larger units. The grille
acts as the lter retainer.
Coil Cleaning:
If the coil becomes dirty it can be cleaned using a vacuum followed by compressed air. Vacuum the face of the
coil where the air enters the coil. Most of the dirt will
be on this side. Use compressed air to blow any remaining dirt out. Work from back to prevent driving the dirt
further into the coil. Keeping clean air lters in place will
greatly reduce the frequency that coils must be cleaned.
Blowers and Blower Motors:
There is nothing that can be serviced on these components other than inspecting the blowers and blower motors to insure they are clean. The blower and motor bear-
TEMP-COOL
™
Owner’s Manual
ings are lubricated and sealed at the factory, and require
no additional lubrication. Dirt on the blower wheels can
be cleaned off with a rag. Dirt should not be a problem if
the air lters are properly maintained and kept in place.
Belt Tension, (TC-60B, 60B3, 60B4 Models only)
The condenser fan on the TC-60B series of air conditioners uses the only blower/motor combination that incorporates V-belts drives. The condition of the belt, along
with its tension and alignment should be checked at least
once a year for proper operation. Replace the belt if it has
cracked or is glazed. Adjust the belt tension for a 3/16”
deection of the belt with 2 pounds of force applied at the
The condenser fan on the TC-60B series of air conditioners utilizes an adjustable sheave on the motor to drive
the blower. The sheave is preset at the factory and should
not be adjusted. However the blower, motor and drives
should periodically be checked for tightness and alignment. Check the setscrews that connect the sheaves and
blower wheel to the shafts to make sure they are secure.
Make sure the setscrews locking down the adjustable
ange on the motor sheave are secure.
Portable Cooling Systems
The factory setting for the drive on the condenser fan
motor is 4 and turns open from the closed position.
7
Loading...
+ 15 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.