TEC-9300
Self-Tune Fuzzy / PID Process
Temperature Controller
Serving Industry Since 1972
Agency Approvals: RoHS
TEMPCO Electric Heater Corporation
607 N. Central Avenue • Wood Dale, IL 60191-1452 USA
Tel: 630-350-2252 • Toll Free: 800-323-6859
Fax: 630-350-0232 • E-mail: [email protected]
Web: www.tempco.com
Manual TEC-9300 Revision 9/2016
Page 2
NOTES
Page 3
Warning Symbol
This symbol calls attention to an operating procedure, practice, or
the like which, if not correctly performed or adhered to, could
result in personal injury or damage to or destruction of part or all
of the product and system. Do not proceed beyond a warning symbol until the indicated conditions are fully understood and met.
It is strongly recommended that a process should incorporate a LIMIT CONTROL like TEC-910 which will shut
down the equipment at a preset process condition in order to
preclude possible damage to products or system.
Information in this user’s manual is subject to change without
notice.
levels
** User menu configurable
** Pump control
* Fuzzy plus PID micro-
** Unique * Valuable
* Automatic programming
* Differential control
* Auto-tune function
* Self-tune function
* Sleep mode function
* “Soft-start” ramp and dwell
timer
* Programmable inputs (ther-
mocouple, RTD, mA, VDC)
* Analog input for remote set
point and CT
processor-based control
TEC-9300 Fuzzy Logic plus PID microprocessor-based controller incorporates a bright, easy to read, 4-digit LED display
which indicates the process value. Fuzzy Logic technology
enables a process to reach a predetermined set point in the shortest time, with the minimum of overshoot during power-up or
external load disturbance. The units are housed in a 1/16 DIN
case, measuring 48mm x 48mm with 75mm behind-panel depth.
The units feature three touch keys to select the various control
and input parameters. Using a unique function, you can put up to
five parameters at the front of the user menu by using SEL1 to
SEL5 found in the setup menu. This is particularly useful to
OEM’s as it is easy to configure the menu to suit the specific
application.
TEC-9300 is powered by 11–26VAC/VDC or 90–264VAC
supply, incorporating a 2 amp control relay output and dual 2 amp
alarm relay outputs as standard with a second alarm that can be
configured in the second output for cooling purposes or as a dwell
timer. Alternative output options include SSR drive, triac, 4–
20mA and 0–10 volts. TEC-9300 is fully programmable for
PT100, thermocouple types J, K, T, E, B, R, S, N, L, 0–20mA, 4–
20mA, and voltage signal input, with no need to modify the unit.
The input signals are digitized by using an 18-bit A to D converter. Its fast sampling rate allows the TEC-9300 to control fast
processes such as pressure and flow.
Self-tuning can be used to optimize the control parameters as
soon as undesired control results are observed. Unlike auto-tuning, self-tuning will produce less disturbance to the process during tuning, and can be used at any time.
Digital communications formats RS-485, RS-232 or 4–20mA
retransmission are available as an additional option. These
options allow the TEC-9300 to be integrated with supervisory
control systems and software, or alternatively to drive remote displays, chart recorders, or data loggers.
* Event input for changing
function and set point
* Programmable digital filter
* Hardware lockout and
modules available
* Safety UL/CSA/IEC1010–1
* EMC/CE EN61326
* Front panel sealed to NEMA
4X and IP65
* RS-485, RS-232 communi-
cation
Two different methods can be used to program the TEC-9300.
1. Use the keys on the front panel to program the unit manually;
2. Use a PC with setup software to program the unit via the RS485 or RS-232 COMM port.
PID control has been used and has proven to be an efficient
controlling method by many industries, yet PID has difficulty
dealing with some sophisticated systems such as second and
higher order systems, long time-lag systems, during set point
change and/or load disturbance circumstances, etc. The PID principle is based on a mathematical model which is obtained by tuning the process. Unfortunately, many systems are too complex to
describe precisely in numerical terms. In addition, these systems
may be variable from time to time. In order to overcome the
imperfections of PID control, Fuzzy Technology was introduced.
What is Fuzzy Control? It works like a good driver. Under different speeds and circumstances, he can control a car well based on
previous experience, and does not require knowledge of the kinetic theory of motion. Fuzzy Logic is a linguistic control which is
different from the numerical PID control. It controls the system
by experience and does not need to simulate the system precisely
as a PID controller would.
The function of Fuzzy
Logic is to adjust PID
parameters internally
in order to make
manipulation of output value MV more
flexible and adaptive
to various processes.
The Fuzzy Rule may
work like this:
• If the temperature difference is large, and the temperature rate is large, then
ΔMV is large.
• If the temperature difference is large, and the temperature rate is small, then
ΔMV is small.
PID+Fuzzy Control
has been proven to be
an efficient method to
improve the control
stability as shown by
the comparison curves
at left:
1
Page 6
1–2 Hardware Code
Example
Communications
Alarm 1
Output 2 / Alarm 2
Output 1
Signal Input
Power Input
4: 90 - 264 VAC, 50/60 HZ
5: 11 - 26 VAC or VDC
9: Special Order
1: Standard Input
Input 1 - Universal Input
Thermocouple: J, K, T, E, B,
R, S, N, L
RTD: PT100 DIN, PT100 JIS
Current: 4 - 20mA, 0 - 20 mA.
Voltage: 0 - 1V, 0 - 5V, 1 - 5V,
0 - 10V
Input 2 - CT and Analog Input
***
CT: 0 - 50 Amp. AC Current
Transformer
Analog Input: 4 - 20 mA,
0 - 20mA, 0 - 1V, 0 - 5V,
1 - 5V, 0 - 10V.
Input 3 - Event Input ( EI )
9: Special Order
1: Relay rated 2A/240VAC
2: Pulsed voltage to
drive SSR, 5V/30mA
3: Isolated
4 - 20mA / 0 - 20mA
4: Isolated 1 - 5V / 0 - 5V
5: Isolated 0 - 10V
6: Triac Output
1A / 240VAC, SSR
C: Pulsed voltage to
drive SSR, 14V/40mA
9: Special order
9: Special order
2A / 240VAC
2: Form B Relay
2A / 240VAC
1: Form A Relay
0: None
12
34
5
6
0: None
1: Form A Relay 2A/240VAC
2: Pulsed voltage to
drive SSR, 5V / 30mA
3: Isolated 4 - 20mA / 0 - 20mA
4: Isolated 1 - 5V / 0 - 5V
5: Isolated 0 - 10V
6: Triac Output, 1A / 240VAC, SSR
7: Isolated 20V / 25mA DC
Output Power Supply
8: Isolated 12V / 40 mA DC
Output Power Supply
9: Isolated 5V / 80mA DC
Output Power Supply
TEC-9300-411111
90 - 264 operating voltage
Input: Standard Input
Output 1: Relay
Output 2: Relay
Alarm 1: Form A Relay
RS-485 Communication Interface
Range set by front keyboard
Alternative between RS-232 and EI
Need to order an accessory TEC99999 if
Heater Break detection is required.
TEC-9300-
***
**
*
*
*
*
**
**
*
*
*
C: Pulsed voltage to
drive SSR, 14V/40mA
A: Special order
NOTE: A part number based on the hardware code and any software pre-programming
will be issued at time of order.
Related Products
TEC99001 Smart network adapter for third party software;
converts 255 channels of RS-485 or RS-422 to
RS-232 network
TEC99003 Smart network adapter for connecting the
TEC99013 Programming cable for the TEC-9300
TEC99923 Data Acquisition Software (DAQ Software)
TEC-9300 programming cable to the PCs RS-232
serial port or to a Serial → USB adapter
2
Page 7
1–3 Programming Port and DIP Switch
Front
Panel
Rear
Te rm i na l
Figure 1. Access Hole
Overview
. . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Table 1.1 DIP Switch
Configuration
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
TC, RTD, mV
0-1V, 0-5V, 1-5V, 0-1 0V
0-20 mA, 4-2 0 m A
Input 1
Select
.
All para m e te rs a re U nlocked
Only SP1, SEL1 SEL5 a re u n loc ked
Only SP1 is unlocked
All P arameters a re locked
Lockout
12
34
DIP Switc h
:O N:O F F
Factory Default Setting
*
Access Hole
1
ON DI P
2 3 4
The programming port is used to connect to
the TEC99001 for instant programming
from a computer
is used for off-line automatic setup and testing
procedures only. Do not
attempt to make any connection to these pins
when the unit is being
used for normal control
purposes.
The programming port
the factory, the DIP
switch is set so that TC
and RTD are selected for
input 1 and all parameters
are unlocked, unless
another configuration is
requested.
When the unit leaves
Lockout function is
used to disable the adjustment of parameters as
well as operation of calibration mode. However,
the menu can still be
viewed even under lockout condition.
*SEL1-SEL5 represent
those parameters which
are selected by using
SEL1, SEL2,… SEL5
parameters contained in
the setup menu. The
parameters that have
been selected are then
allocated at the beginning of the user menu.
3
Page 8
1–4 Keys and Displays
Alarm 1 Indicator
Alarm 2 / Output 2 Indicator
Process Value Indicator
Process Unit Indicator
Upper Display,
to display process value,
menu symbol and error
code etc.
Lower Display,
to display set point value,
parameter value or control
output value etc.
3 Silicone Rubber Buttons
for ease of control setup
and set point adjustment.
Set point
Value
Indicator
Output 1
Indicator
A1 A2PV
°F
SV
OUT
For a number with decimal point the
display will be shifted one digit right:
-19999 will be displayed by:
45536 will be displayed by:
-9999 will be displayed by:
How to display a 5-digit number
-199.99 will be displayed by -199.9
4553.6 will be displayed by 4553
For a number without decimal point
the display will be divided into two
alternating phases:
TEC
-9300
Indicates Abstract Characters
AE
I
N
S
X
B
F
J
O
T
Y
C
G
K
P
U
Z
c
H
L
Q
V
?
Dh
M
R
W
=
°C
Figure 1.4 Front Panel Description
Table 1.3 Display Form of Characters
The unit is programmed by using the three keys on the front panel. The available key functions are listed in the following table.
4
Page 9
1–4 Keys and Displays continued…
5
Page 10
1–5 Menu Overview
e
6
Page 11
1–6 System Modes
The controller performs closed loop control in its normal control mode condition. The
controller will maintain its normal control mode when you are operating the user menu,
setup menu, display mode, reloading default values, or applying event input signals.
Under certain conditions, the normal control mode will transfer to an exception mode.
The exception modes include: sleep mode, manual mode, failure mode, calibration
mode, and auto-tuning mode. All of these modes perform in an open loop control except
auto-tuning mode which performs ON-OFF while configuring PID values control. The
mode transfer is governed by the priority conditions. A lower priority mode can not alter
a higher priority mode, as shown in figure 1.6.
System Modes
Sleep mode:
See section 4-11.
Manual mode:
See section 3-23.
Failure mode:
See section 3-17.
Calibration mode:
See chapter 6.
Auto-tuning mode:
See section 3-20.
Normal control mode:
See section 3-24, 3-26, 4-1
Calibration mode, auto-tuning mode, and normal control mode are in the
same priority level. Sleep mode is in the highest priority level.
7
Page 12
1–7 Parameter Description
8
NOTE: For RS-232:
Short J1, Open/Cut J2
Using RS-232 will disable Event Input Function
Page 13
NOTE: Parameter 1N1 continued on next page
9
Page 14
10
NOTE: Parameter O1TY continued on next page
Page 15
11
Page 16
12
Page 17
Note: Calibration menu is for supplier configuration use only.
13
Page 18
14
Page 19
Chapter 2 Installation
Figure 2.1Mounting Dimensions
Figure 2.2 Lead Termination
Figure 2.3 Rear Terminal Connection Diagram
4.5 ~ 7.0 mm
0.18" ~ 0.27"
2.0 mm
0.08" max.
Dangerous voltage capable of causing death can be pres-
ent in this instrument. Before installation or beginning
any troubleshooting procedures, the power to all equipment must
be switched off and isolated. Units suspected of being faulty
must be disconnected and removed to a properly equipped workshop for testing and repair. Component replacement and internal
adjustments must be made by a qualified maintenance person
only.
To minimize the possibility of fire or shock hazards, do
not expose this instrument to rain or excessive moisture.
Do not use this instrument in areas under hazardous con-
ditions such as excessive shock, vibration, dirt, moisture,
corrosive gases, or oil. The ambient temperature of the areas
should not exceed the maximum rating specified in chapter 8.
2–1 Unpacking
Upon receipt of the shipment, remove the unit from the carton
and inspect the unit for shipping damage.
If there is any damage due to transit, report the damage and file
a claim with the carrier.
Write down the model number, serial number, and date code for
future reference when corresponding with our service center.
The serial number (S/N) is labeled on the box and the housing of
the controller .
2–2 Mounting
Make the panel cutout to fit the dimensions shown in figure 2.1.
Remove both mounting clamps and insert the controller into the
panel cutout. Reinstall the mounting clamps. Gently tighten the
screws in the clamp until the controller front panel fits snugly in
the cutout .
2–3 Wiring Precautions
• Before wiring, verify the correct model number and options on
the label. Switch off the power while checking.
• Care must be taken to ensure that the maximum voltage rating
specified on the label is not exceeded.
• It is recommended that the power for these units be protected
by fuses or circuit breakers rated at the minimum value possible.
• All units should be installed in a suitable enclosure to prevent
live parts from being accessible to human hands and metal
tools. Metal enclosures and/or subpanels should be grounded in
accordance with national and local codes.
• All wiring must conform to appropriate standards of good practice and local codes and regulations. Wiring must be suitable
for the voltage, current, and temperature rating of the system.
• Beware not to over-tighten the terminal screws. The torque
should not exceed 1 N-m (8.9 lb-in or 10 KgF-cm).
• Unused control terminals should not be used as jumper points
as they may be internally connected, causing damage to the
unit.
• Verify that the ratings of the output devices and the inputs as
specified are not exceeded.
• Except for thermocouple wiring, all wiring should use stranded
copper conductor with a maximum gage of 14 AWG.
• Electrical power in industrial environments contains a certain
amount of noise in the form of transient voltage and spikes.
This electrical noise can adversely affect the operation of
microprocessor-based controls. For this reason the use of
shielded thermocouple extension wire which connects the sensor to the controller is strongly recommended. This wire is a
twisted-pair construction with foil wrap and drain wire. The
drain wire is to be attached to ground in the control panel only.
15
Page 20
2–4 Power Wiring
The controller is supplied to operate at 11–26VAC/VDC or
90–264VAC. Check that the installation voltage corresponds to
the power rating indicated on the product label before connecting
power to the controller .
This equipment is
designed for installation
in an enclosure which provides
adequate protection against
electrical shock. Metal enclosures must be connected to
earth ground.
Local requirements regarding electrical installation
should be rigidly observed.
Consideration should be given
to prevent unauthorized personnel from gaining access to
the power terminals.
2–5 Sensor Installation Guidelines
Proper sensor installation can eliminate many problems in a
control system. The probe should be placed so that it can detect
any temperature change with minimal thermal lag. In a process
that requires fairly constant heat output, the probe should be
placed close to the heater. In a process where the heat demand is
variable, the probe should be close to the work area. Some experiments with probe location are often required to find the optimum position.
In a liquid process, the addition of a stirrer will help eliminate thermal lag. Since a thermocouple is basically a point
measuring device, placing more than one thermocouple in parallel can provide an average temperature readout and produce
better results in most air-heated processes.
The proper sensor type is also a very important factor in
obtaining precise measurements. The sensor must have the
correct temperature range to meet the process requirements. In
special processes, the sensor might have additional requirements such as leak-proof, anti-vibration, antiseptic, etc.
Standard sensor limits of error are ±4°F (±2°C) or 0.75% of
sensed temperature (half that for special) plus drift caused by
improper protection or an over-temperature occurrence. This
error is far greater than controller error and cannot be corrected on the sensor except by proper selection and replacement .
2–6 Thermocouple Input Wiring
The thermocouple input connections are shown in figure 2.5. The correct type of
thermocouple extension lead-wire or compensating cable must be used for the entire
distance between the controller and the thermocouple, ensuring that the correct
polarity is maintained throughout. Joints in the cable should be avoided, if possible.
If the length of the thermocouple plus the extension wire is too long, it may affect
the temperature measurement. A 400 ohms K type or a 500 ohms J type thermocouple lead resistance will produce approximately 1°C temperature error .
The color codes used on the thermocouple extension leads are shown in table 2.1.
Table 2.1 Thermocouple Cable Color Codes
Thermocouple Cable British American German French
Type Material BS ASTM DIN NFE
T
* blue * blue * brown * blue
J
* black * black * blue * black
Nickel-Chromium
K (Ni-Cr)
Nickel-Aluminum
(Ni-Al)
R Pt-13%Rh, Pt
S Pt-10%Rh, Pt
* green * green * white * green
B
Wire * grey * grey Wire
Copper (Cu)
Constantan (Cu-Ni)
Iron (Fe)
Constantan (Cu-Ni)
Pt-30%Rh
Pt-6%Rh
+ white + blue + red + yellow
– blue – red – brown – blue
+ yellow + white + red + yellow
– blue – red – blue – black
+ brown + yellow + red + yellow
– blue – red – green – purple
* red * yellow * green * yellow
+ white + black + red + yellow
– blue – red – white – green
Use + grey + red Use
Copper – red – grey Copper
* Color of overall sheath
16
Page 21
2–7 RTD Input Wiring
The RTD connections are shown in figure
2.6, with the compensating lead connected to
terminal 12. For two-wire RTD inputs, terminals
12 and 13 should be linked. A three-wire RTD
offers the capability of lead resistance compensation, provided that the three leads are the same
gauge and equal in length.
For the purpose of accuracy, two-wire RTD
should be avoided, if possible. A 0.4 ohm lead
resistance in a two-wire RTD will produce 1°C
temperature error.
2–8 Linear DC Input Wiring
DC linear voltage and linear current connections for input 1 are shown in
figure 2.7 and figure 2.8.
DC linear voltage and linear current connections for input 2 are shown in
figure 2.9 and figure 2.10.
17
Page 22
2–9 CT/Heater Current Input Wiring
Make sure that the total current through TEC99999 does not exceed 100A rms in a 3-Phase system.
18
Page 23
2–10 Event Input wiring
The event input can accept a switch signal as well
as an open collector signal. The event input function (EIFN) is activated when the switch is closed
or an open collector (or a logic signal) is pulled
down.
Also refer to section 4-1 for event input functions.
19
Page 24
2–11 Output 1 Wiring
20
Page 25
2–12 Output 2 Wiring
21
Page 26
2–13, 2–14 Alarm 1 and 2 Wiring
Note: Both Form A and B contacts are available for the alarm 1 relay.
Order the correct form for alarm 1 to suit your needs.
22
Page 27
2–15 RS-485
23
Page 28
2–16 RS-232
Figure 2.20Location of Jumper JP22
Figure 2.21Configuration of RS-232 Cable
Figure 2.19RS-232 Wiring
TEC99014
Note: If the TEC-9300 is configured for RS-232 communication, the EI (event input) is disconnected internally. The unit can
no longer perform event input function (EIFN).
When you connect an RS-232 module (CM94-2) to the connectors on the CPU board (C930), jumper JP22 on the terminal
board (T930) must be modified as following: J1 must be shorted
and J2 must be cut and left open. The location of JP22 is shown
in the diagram below, left (Fig. 2.20).
2–17 Analog Retransmission
If you use a conventional 9-pin RS-232 cable instead of
TEC99014, the cable must be modified according to the circuit diagram above.
24
Page 29
Chapter 3 Programming Basic Functions
This unit provides a useful parameter “FUNC” which can be used
to select the function complexity level before setup. If Basic
Mode (FUNC=BASC) is selected for a simple application, then
the following functions are ignored and deleted from the full
function menu:
3. Output 1: heating or cooling (relay, SSR, SSRD, volt, mA)
4. Output 2: cooling (relay, SSR, SSRD, volt, mA), DC power
supply
5. Alarm 1: relay for deviation, deviation band, process, heater
break, loop break, sensor break, latch, hold, or normal alarm.
6. Alarm 2: relay for deviation, deviation band, process, heater
break, loop break, sensor break, latch, hold, or normal alarm.
7. Dwell timer
3–1 Input 1
Press to enter setup mode. Press to select the desired
parameter. The upper display indicates the parameter symbol,
and the lower display indicates the selection or the value of the
parameter.
IN1: Selects the sensor type and signal type for Input 1.
input 1.
Hidden if: T/C or RTD type is selected for
IN1.
IN1H: Selects the high scale value for Linear type
input 1.
Hidden if: T/C or RTD type is selected for
IN1.
8. Heater break alarm
9. Loop break alarm
10. Sensor break alarm
11. Failure transfer
12. Bumpless transfer
13. PV1 shift
14. Programmable SP1 range
15. Heat-cool control
16. Hardware lockout
17. Self-tune
18. Auto-tune
19. ON-OFF, P, PD, PI,
PID control
20. User-defined menu (SEL)
21. Manual control
22. Display mode
23. Reload default values
24. Isolated DC Power supply
If you don’t need:
1. Second setpoint
2. Second PID
3. Event input
4. Soft start (RAMP)
5. Remote set point
6. Complex process value
7. Output power limit
8. Digital communication
9. Analog retransmission
10. Power shut off
(sleep mode)
11. Digital filter
12. Pump control
13. Remote lockout
…then you can use
basic mode.
How to use IN1L and IN1H:
If 4–20mA is selected for IN1, SL specifies the input signal low
(i.e., 4mA), SH specifies the input signal high (i.e., 20mA), S
specifies the current input signal value, and the conversion
curve of the process value is shown as follows:
Example: If a 4–20mA current loop pressure transducer with
range 0–15 kg/cm≈ is connected to input 1, then per-
form the following setup:
IN1 = 4–20 IN1L = 0.0
IN1U = PU IN1H = 15.0
DP1 = 1 –DP
Of course, you may select another value for DP1 to
alter the resolution.
25
Page 30
3–2 OUT1 and OUT2 Types
O1TY: Selects the signal type for Output 1.
The selection should be consistent with the
output 1 module installed.
The available output 1 signal types are:
RELY: Mechanical relay
SSRD: Pulsed voltage output to drive SSR
SSR: Isolated zero-switching solid-state relay
4–20: 4–20mA linear current output
0–20: 0–20mA linear current output
0–1V: 0–1V linear voltage output
0–5V: 0–5V linear voltage output
1–5V: 1–5V linear voltage output
0–10V: 0–10V linear voltage output
3–3 Configuring User Menu
Most conventional controllers are designed with a fixed order in
which the parameters scroll. The TEC-9300 has the flexibility to
allow you to select those parameters which are most significant
to you and put these parameters at the front of the display
sequence.
SEL1: Selects the most significant parameter for
view and change.
SEL2: Selects the 2nd most significant parameter for
view and change.
SEL3: Selects the 3rd most significant parameter for
view and change.
SEL4: Selects the 4th most significant parameter for
view and change.
SEL5: Selects the 5th most significant parameter for
The selection should be consistent with the
output 2 module installed.
The available output 2 signal types are the same as for
O1TY.
The range for linear current or voltage may not be very accurate.
For 0% output, the value for 4–20mA may be 3.8–4mA; while
for 100% output, the value for 4–20mA may be 20–21mA.
However, this deviation will not degrade the control performance at all.
When using the up and down keys to select the parameters, you
may not see all of the above parameters. The number of visible
parameters is dependent on the setup condition. The hidden
parameters for the specific application are also deleted from the
SEL selection.
OUT1, set PB1 to 0, SP1 is used
to adjust set point value, O1HY
is used to adjust dead band for
ON-OFF control, TIME is used
to adjust the dwell timer (enabled
by selecting TIMR for A1FN or A2FN). Output 1 hysteresis
(O1HY) is enabled in the case of PB1=0. The heat only on-off
control function is shown in the diagram at right:
26
Setup ON-OFF:
OUT1 =
PB1 = 0
Adjust: SP1, O1HY, TIME
(if enabled)
3–4 Heat Only Control continued next page…
Page 31
3–4 Heat Only Control continued…
The ON-OFF control may introduce excessive process oscillation even if hysteresis is minimized to the smallest. If ON-OFF
control is set (i.e., PB1=0), TI1, TD1, CYC1, OFST, CPB and
PL1 will be hidden and have no function to the system. The manual mode, auto-tuning, self-tuning and bumpless transfer will be
disabled too.
Heat only P ( or PD ) control:
Select REVR for OUT1, set TI1 to 0,
SP1 is used to adjust set point value,
TIME is used to adjust the dwell timer
(enabled by selecting TIMR for A1FN
or A2FN). OFST been enabled in case
of TI1=0 is used to adjust the control
offset (manual reset). Adjust CYC1
according to the output 1 type (O1TY).
Generally, CYC1=0.5~2 seconds for
SSRD and SSR, CYC1=10~20 seconds
for relay output. CYC1 is ignored if linear output is selected for O1TY. O1HYis hidden if PB1 is not equal to 0.
Setup P:
OUT1 =
TI1 = 0
CYC1 (if RELAY,
SSRD or SSR is
selected for
O1TY)
Adjust:
SP1, OFST, TIME
(if enabled),
PB1(≠0), TD1
OFST Function: OFST is measured by % with range 0–
100.0%. In the steady state (i.e., process has been stabilized), if
the process value is lower than the set point a definite value, say
5°C, while 20°C is used for PB1, that is lower 25%, then
increase OFST 25%, and vice versa. After adjusting OFST value,
the process value will be varied and eventually coincide with set
point. Using the P control (TI1 set to 0), the auto-tuning and selftuning are disabled. Refer to section 3-21 “manual tuning” for
the adjustment of PB1 and TD1. Manual reset (adjust OFST) is
not practical because the load may
change from time to time and often
need to adjust OFST repeatedly. The
PID control can avoid this situation.
Heat only PID control: Selecting
REVR for OUT1, SP1 is used to adjust
set point value. TIME is used to adjust
the dwell timer (enabled by selecting
TIMR for A1FN or A2FN). PB1 and
TI1 should not be zero. Adjust CYC1
according to the output 1 type (O1TY).
Generally, CYC1=0.5~2 seconds for
SSRD and SSR, CYC1=10~20 seconds
for relay output. CYC1 is ignored if linear output is selected for O1TY. In most
cases, self-tuning can be used to substitute for auto-tuning. See section 3-19. If
self-tuning is not used (select NONE
for SELF), then use auto-tuning for the
new process, or set PB1, TI1, and TD1
with historical values. See section 3-20
for auto-tuning operation. If the control
result is still unsatisfactory, then use
manual tuning to improve control. See
section 3-21 for manual tuning. TEC9300 contains a very clever PID and
Fuzzy algorithm to achieve a very small
overshoot and very quick response to
the process if it is properly tuned.
Setup PID:
OUT1 =
O1TY
CYC1 if RELAY,
SSRD or SSR is
selected for O1TY)
SELF=NONE or
YES
Adjust:
SP1, TIME (if
enabled), PB1(≠0),
TI1(≠0), Td1
Auto-tuning:
Used for new
process during initial tuning
Self-tuning:
Used for a process
any time.
Manual Tuning:
May be used if
self-tuning and
auto-tuning are
inadequate.
3–5 Cool Only Control
ON-OFF control, P (PD) control, and PID control can be used
for cool control. Set OUT1 to
DIRT (direct action). The other
functions for cool only ON-OFF control, cool only P (PD) control and cool only PID control are the same as the descriptions in
section 3-5 for heat only control except that the output variable
(and action) for the cool control is inverse to the heat control,
such as the following diagram shows:
Setup Cool Control:
OUT1 =
Refer to section 3-5, in which similar descriptions for heat only
control can be applied to cool only control.
27
Page 32
3–6 Heat-Cool Control
The heat-cool control can use one of six combinations of control modes. Setup of parameters for each control mode are shown
in the following table.
NOTE: The ON-OFF control may result in excessive overshoot
and undershoot problems in the process. The P (or PD) control
will result in a deviation process value from the set point. It is
recommended to use PID control for the heat-cool control to produce a stable and zero offset process value.
Other Setup Required: O1TY, CYC1, O2TY, CYC2,
A2SP, A2DV
O1TY and O2TY are set in accordance with the types of OUT1
and OUT2 installed. CYC1 and CYC2 are set according to the
output 1 type (O1TY) and output 2 type (O2TY). Generally,
select 0.5~2 seconds for CYC1 if SSRD or SSR is used for
O1TY. Select 10~20 seconds if relay is used for O1TY; CYC1 is
ignored if linear output is used. Similar conditions are applied to
CYC2 selection. If OUT2 is configured for ON-OFF control (by
selecting AL2), OUT2 will act as alarm output, and the process
alarm as well as deviation alarm (see sections 3-8 and 3-9) can
be used. Adjust A2SP to change the set point if process alarm is
used, and adjust SP1 (with preset A2DV) to change the set point
if deviation alarm is used.
Examples:
Heat PID+Cool ON-OFF: Set OUT1=REVR, A1FN or
A2FN=PV1.H, A1FN or A2MD=NORM, A1HY or A2HY=0.1,
PB1≠0, TI1≠0,TD1≠0, and set appropriate values for O1TY and
CYC1.
Heat PID+Cool PID: set OUT1=REVR, OUT2=COOL,
CPB=100, DB=-4.0, PB1≠0, TI1≠0, TD1≠0, and set appropriate
values for O1TY, CYC1, O2TY, CYC2.
If you have no idea about a new process, then use the self-tuning
program to optimize the PID values by selecting YES for SELF
to enable the self-tuning program. See section 3-18 for a description of the self-tuning program. You can use the auto-tuning program for the new process or directly set the appropriate values
for PB1, TI1, and TD1 according to the historical records for the
repeated systems. If the control behavior is still inadequate, then
use manual tuning to improve the control. See section 3-20 for
more information on manual tuning.
CPB Programming: The cooling proportional band is measured
by % of PB with a range of 1~255. Initially set 100% for CPB
and examine the cooling effect. If the cooling action should be
enhanced then decrease CPB, if the cooling action is too strong
then increase CPB. The value of CPB is related to PB and its
value remains unchanged throughout the self-tuning and autotuning procedures.
Adjustment of CPB is related to the cooling media used. If air is
used as the cooling medium, set CPB at 100(%). If oil is used as
the cooling medium, set CPB at 125(%). If water is used as the
cooling medium, set CPB at 250(%).
DB Programming: Adjustment of DB is dependent on the system requirements. If a higher positive value of DB (greater dead
band) is used, unwanted cooling action can be avoided, but an
excessive overshoot over the set point may occur. If a lower negative value of DB (greater overlap) is used, an excessive overshoot over the set point can be minimized, but an unwanted cooling action may occur. It is adjustable in the range -36.0% to
36.0% of PB1 (or PB2 if PB2 is selected). A negative DB value
shows an overlap area over which both outputs are active. A positive DB value shows a dead band
28
Page 33
3–7 Dwell Timer
Alarm 1 or alarm 2 can be configured as dwell timer by selecting TIMR for
A1FN or A2FN, but not both, otherwise Er07 will appear. As the dwell timer is
configured, the parameter TIME is used for dwell time adjustment. The dwell
time is measured in minute ranging from 0 to 6553.5 minutes. Once the process
reaches the set point the dwell timer starts to count from zero until time out.The
timer relay will remain unchanged until time out. The dwell timer operation is
shown as following diagram.
If alarm 1 is configured as dwell timer, A1SP, A1DV, A1HY and A1MD are hidden.
The case is the same for alarm 2.
If alarm 1 is configured as dwell timer, A1SP, A1DV, A1HY and A1MD are hidden.
The case is the same for alarm 2.
Example:
Set A1FN=TIMR or A2FN=TIMR, but not both.
Adjust TIME in minutes
A1MD (if A1FN=TIMR) or A2MD (if A2FN=TIMR) is ignored in this case.
29
Page 34
3–8 Process Alarms
There are at most two independent alarms available by
adjusting OUT2. If AL2 is selected for OUT2, then
OUT2 will perform alarm 2 function. Now NONE can’t
be selected for A2FN, otherwise Er06 will be displayed.
A process alarm sets an absolute trigger level (or temperature). When the process (could be PV1, PV 2, or PV1PV2) exceeds that absolute trigger level, an alarm occurs.
A process alarm is independent from the set point. Adjust
A1FN (Alarm 1 function) in the setup menu. One of
eight functions can be selected for process alarm. These
are: PV1.H, PV1.L, PV2.H, PV2.L, P1.2.H,
P1.2.L, D1.2.H, D1.2.L. When PV1.H or PV1.L is selected, the alarm examines the PV1 value. When PV2.H or
PV2.L is selected, the alarm examines the PV2 value.
When P1.2.H or P1.2.L is selected, the alarm occurs if
the PV1 or PV2 value exceeds the trigger level. When
D1.2.H or D1.2.L is selected, the alarm occurs if the
PV1-PV2 (difference) value exceeds the trigger level.
The trigger level is determined by A1SP (Alarm 1 set
point) and A1HY (Alarm 1 hysteresis value) in User
Menu for alarm 1. The hysteresis value is introduced to
avoid interference action of alarm in a noisy environment. Normally A1HY can be set with a minimum (0.1)
value. A1DV and/or A2DV are hidden if alarm 1 and/or
alarm 2 are set for process alarm.
Normal Alarm: A1MD=NORM
When a normal alarm is selected, the
alarm output is de-energized in the
non-alarm condition and energized in
an alarm condition.
Latching Alarm: A1MD=LTCH
If a latching alarm is selected, once the
alarm output is energized, it will
remain unchanged even if the alarm
condition is cleared. The latching
alarms are disabled when the power is
shut off or if event input is applied
with proper selection of EIFN.
Holding Alarm: A1MD=HOLD
A holding alarm prevents an alarm
from powering up. The alarm is
enabled only when the process reaches
the set point value (may be SP1 or
SP2, see section 4-1 event input).
Afterwards, the alarm performs the
same function as a normal alarm.
2. Apply event input in accordance
with proper selection of EIFN
Latching/Holding Alarm: A1MD=LT.HO
A latching/holding alarm performs both holding and latching function.
Although the descriptions in the examples below are based on alarm 1, the same conditions can be applied to alarm 2.
30
Page 35
3–9 Deviation Alarm
OUT2 can be configured as alarm 2 by selecting AL2. If AL2 is selected for
OUT2, then output 2 will perform alarm 2 function. Now NONE can’t be selected for A2FN, otherwise Er06 will appear. A deviation alarm alerts the user when
the process deviates too far from the set point. The user can enter a positive or
negative deviation value (A1DV, A2DV) for alarm 1 and alarm 2. A hysteresis
value (A1HY or A2HY) can be selected to avoid interference problems in a noisy
environment. Normally, A1HY and A2HY can be set with a minimum (0.1)
value. The trigger level of the alarm moves with the set point.
For alarm 1,
trigger level=SP1+A1DV±A1HY.
For alarm 2,
trigger level=SP1+A2DV±A2HY.
A1SP and/or A2SP are hidden if alarm 1 and/or alarm 2 are set for deviation
alarm. One of four alarm modes can be selected for alarm 1 and alarm 2. These
are: normal alarm, latching alarm, holding alarm and latching/holding alarm. See
section 3-8 for descriptions of these alarm modes.
A deviation band alarm presets two reference levels relative to set point. Two types of
deviation band alarm can be configured for alarm 1 and alarm 2. These are deviation band
high alarm (A1FN or A2FN select DB.HI) and deviation band low alarm (A1FN or A2FN
select DB.LO). A1SP and A1HY are hidden if alarm 1 is selected as a deviation band
alarm. Similarly, A2SP and A2HY are hidden if alarm 2 is selected as a deviation band
alarm. The trigger level for deviation band alarm moves with the set point. For alarm 1,
the trigger level=SP1±A1DV. For alarm 2, the trigger level=SP1±A2DV. One of four
alarm modes can be selected for alarm 1 and alarm 2. These are: normal alarm, latching
alarm, holding alarm and latching/holding alarm. See section 3-8 for descriptions of these
alarm modes.
A current transformer (Part No. TEC99999) should be installed
to detect the heater current if a heater break alarm is required.
The CT signal is sent to input 2, and the PV2 will indicate the
heater current in 0.1amp resolution. The range of the current
transformer is 0 to 50.0amp. For more detailed descriptions
about heater current monitoring, please see section 3-24.
Heater break alarm 1
Setup: IN2=CT
A1FN=PV2.L
A1MD=NORM
A1HY=0.1
Adjust: A1SP
Trigger level: A1SP±A1HY
Heater break alarm 2
Setup: IN2=CT
A2FN=PV2.L
A2MD=NORM
A2HY=0.1
Adjust: A2SP
Trigger level: A2SP±A2HY
Limitations:
1. Linear output can’t use
heater break alarm.
2. CYC1 should use 1 second
or longer to detect heater
current reliably.
3–12 Loop Break Alarm
A1FN selects LB if
alarm 1 is required to act
as a loop break alarm.
Similarly, if alarm 2 is
required to act as a loop
break alarm, then set
OUT2 to AL2 and A1FN
to LB. TIME, A1SP,
A1DV, and A1HY are
hidden if alarm 1 is configured as a loop break
alarm. Similarly, TIME, A2SP, A2DV, and A2HY are hidden if
alarm 2 is configured as a loop break alarm. One of four kinds of
alarm modes can be selected for alarm 1 and alarm 2. These are:
normal alarm, latching alarm, holding alarm and latching/holding alarm. However, the holding mode and latching/holding
mode are not recommended for loop break alarm since loop
break alarm will not perform the holding function even if it is set
for holding or latching/holding mode. See section 3-8 for
descriptions of these alarm modes.
Loop break conditions are detected during a time interval of
2TI1 (double the integral time, but 120 seconds maximum).
Hence the loop break alarm doesn’t respond as quickly as it
occurs. If the process value doesn’t increase (or decrease) while
the control variable MV1 has reached its maximum (or minimum) value within the detecting time interval, a loop break
alarm (if configured) will be activated.
Loop break alarm 1
Setup: A1FN = LB
A1MD = NORM, LTCH
Loop break alarm 2
Setup: OUT2 = AL2
A2FN = LB
A2MD = NORM, LTCH
Example:
A furnace uses two 2KW heaters connected in parallel to warm
up the process. The line voltage is 220V and the rating current
for each heater is 9.09A. If we want to detect any one heater
break, set A1SP=13.0A, A1HY=0.1, A1FN=PV2.L,
A1MD=NORM, then:
Loop break alarm (if configured) occurs when any following
conditions happen:
1. Input sensor is disconnected (or broken).
2. Input sensor is shorted.
3. Input sensor is defective.
4. Input sensor is installed outside (isolated from) the process.
5. Controller fails (A-D converter damaged).
6. Heater (or generally, chiller, valve, pump, motor etc.) breaks
or fails or is uninstalled.
7. Switching device (used to drive heater) is open or shorted.
33
Page 38
3–13 Sensor Break Alarm
Alarm 1 or alarm 2 can be configured as a sensor break alarm by selecting SENB
for A1FN or A2FN. If alarm 2 is required as a sensor break alarm, then
AL2 should be selected for OUT2. The sensor break alarm is activated as soon
as failure mode occurs. Refer to section 3-16 for failure mode conditions. Note
that A-D failure also creates a sensor break alarm. TIME, A1SP, A1DV, and
A1HY are hidden if alarm 1 is configured as a sensor break alarm. Similarly,
TIME, A2SP, A2DV and A2HY are hidden if alarm 2 is configured as a sensor
break alarm. One of four kinds of alarm modes can be selected for sensor break
alarm. These are: normal alarm, latching alarm, holding alarm and
latching/holding alarm. However, the holding alarm and latching/holding alarm
are not recommended for sensor break alarm since sensor break alarm will not
perform the holding function even if it is set for holding or latching/holding
mode. See section 3-8 for the descriptions of these alarm modes.
3–14 SP1 Range
SP1L (SP1 low limit value) and SP1H (SP1 high limit value) in the setup
menu are used to confine the adjustment range of SP1.
Example: A freezer is working in its normal temperature range -10°C to -15°C. In order
to avoid an abnormal set point, SP1L and SP1H are set with the following values:
SP1L=-15°C SP1H=-10°C
Now SP1 can only be adjusted within the range of -10°C to -15°C.
Sensor Break Alarm 1
Setup: A1FN=SENB
A1MD=NORM, LTCH
Hidden: TIME, A1SP, A1DV, A1HY
Sensor Break Alarm 2
Setup: OUT2=AL2
A2FN=SENB
A2MD=NORM, LTCH
Hidden: TIME, A2SP, A2DV, A2HY
Setup: SP1L, SP1H
3–15 PV1 Shift
In certain applications it is desirable to shift the controller display value from its actual value. This can easily be accomplished by
using the PV1 shift function.
Press the “scroll” key to bring up the parameter SHIF. The value you adjust here, either positive or negative, will be added to the actual
value. The SHIF function will alter PV1 only.
Here is an example. A process is equipped with a heater, a sensor, and a subject to be warmed up. Due to the design and position of
the components in the system, the sensor could not be placed any closer to the part. Thermal gradient (different temperature) is common and necessary to an extent in any thermal system for heat to be transferred from one point to another. If the difference between
the sensor and the subject is 35°C, and the desired temperature at the subject to be heated is 200°C, the controlling value or the temperature at the sensor should be 235°C. You should input -35°C so as to subtract 35°C from the actual process display. This in turn
will cause the controller to energize the load and bring the process display up to the set point value.
34
Page 39
3–16 Failure Transfer
The controller will enter failure mode if one of the following conditions occurs:
1. SB1E occurs (due to input 1 sensor break or input 1 current below 1mA if 4–
20mA is selected or input 1 voltage below 0.25V if 1–5V is selected) if PV1, P12, or P2-1 is selected for PVMD or PV1 is selected for SPMD.
2. SB2E occurs (due to input 2 sensor break or input 2 current below 1mA if 4–
20mA is selected or input 2 voltage below 0.25V if 1–5V is selected) if PV2, P12, or P2-1 is selected for PVMD or PV2 is selected for SPMD.
3. ADER occurs if the A-D converter of the controller fails.
Output 1 and output 2 will perform the failure transfer function as one of the fol-
lowing conditions occurs:
1. During power starts (within 2.5 seconds).
2. The controller enters failure mode.
3. The controller enters manual mode.
4. The controller enters calibration mode.
Output 1 failure transfer, if activated, will perform:
1. If output 1 is configured as proportional control (PB1≠0), and BPLS is selected
for O1FT, then output 1 will perform bumpless transfer. Thereafter, the previous
averaging value of MV1 will be used for controlling output 1.
2. If output 1 is configured as proportional control (PB1≠0), and a value of 0 to
100.0% is set for O1FT, then output 1 will perform failure transfer. Thereafter,
the value of O1FT will be used for controlling output 1.
3. If output 1 is configured as ON-OFF control (PB1≠0), then output 1 will be driven OFF if O1FN selects REVR and be driven ON if O1FN selects DIRT.
Failure mode occurs as:
1. SB1E
2. SB2E
3. ADER
Failure Transfer of output
1 and output 2 occurs as:
1. Power start (within 2.5 seconds)
2. Failure mode is activated
3. Manual mode is activated
4. Calibration mode is activated
Failure Transfer of alarm 1
and alarm 2 occurs as:
Failure mode is activated
Failure Transfer Setup:
1. O1FT
2. O2FT
3. A1FT
4. A2FT
Output 2 failure transfer, if activated,
will perform:
1. If OUT2 selects COOL, and BPLS is selected for O1FT, then output 2 will perform bumpless transfer. Thereafter, the previous averaging value of MV2 will be
used for controlling output 2.
2. If OUT2 selects COOL, and a value of 0 to 100.0% is set for O2FT, then output
2 will perform failure transfer. Thereafter, the value of O1FT will be used for
controlling output 2.
Alarm 1 failure transfer is activated as the controller enters failure mode.
Thereafter, alarm 1 will transfer to the ON or OFF state preset by A1FT.
Exception: If A1FN is configured for loop break (LB) alarm or sensor break
(SENB) alarm, alarm 1 will be switched to ON state independent of the setting of
A1FT. If A1FN is configured for dwell timer (TIMR), alarm 1 will not perform
failure transfer.
Alarm 2 failure transfer is activated as the controller enters failure mode.
Thereafter, alarm 2 will transfer to the ON or OFF state preset by A2FT.
Exception: If A2FN is configured for loop break (LB) alarm or sensor break
(SENB) alarm, alarm 2 will be switched to ON state independent of the setting of
A2FT. If A2FN is configured for dwell timer (TIMR), alarm 2 will not perform
failure transfer.
35
Page 40
3–17 Bumpless Transfer
or
Self-tune Menu
The bumpless transfer function is
available for output 1 and output 2
(provided that OUT2 is configured
as COOL).
Bumpless transfer is enabled by
selecting BPLS for O1FT and/or
O2FT and activated as one of the
following cases occurs:
1. Power starts (within 2.5 seconds).
2. The controller enters failure
mode. See section 3-16 for failure
mode descriptions.
3. The controller enters manual
mode. See section 3-22 for manual mode descriptions.
4. The controller enters calibration
mode. See chapter 6 for calibration mode descriptions.
As bumpless transfer is activated, the controller will transfer to
open-loop control and uses the previous averaging value of MV1
and MV2 to continue control.
Bumpless transfer
setup:
1. O1FT = BPLS
2. O2FT = BPLS
Bumpless transfer
occurs as:
1. Power starts (within
2.5 seconds)
2. Failure mode is activated
3. Manual mode is activated
4. Calibration mode is
activated
3–18 Self tuning
Self-tuning, which was designed
using an innovative algorithm, provides an alternate option for tuning
the controller. It is activated when
YES is selected for SELF. When selftuning is working, the controller will
change its working PID values and
compare the process behavior to previous cycles. If the new PID values
achieve better control, then it
changes the next PID values in the
same direction. Otherwise, it changes
the next PID values in the reverse
direction. When an optimal condition is obtained, the optimal
PID values will be stored in PB1, TI1, and TD1, or PB2, TI2, and
TD2, as determined by the event input conditions. See section 4-
1. When self-tuning is completed, the value of SELF will change
from YES to NONE to disable the self-tuning function.
When self-tuning is enabled, the control variables are tuned
slowly so that the disturbance to the process is less than auto-tuning. Usually, self-tuning will perform successfully with no need
to apply additional auto-tuning.
Exceptions: Self-tuning will be disabled as soon as one
of the following conditions occurs:
1. NONE is selected for SELF.
2. The controller is used for on-off control, that is
PB=0.
3. The controller is used for manual reset, that is TI=0.
4. The controller is in a loop break condition.
5. The controller is in failure mode (e.g., sensor break).
6. The controller is in manual control mode.
7. The controller is in sleep mode.
8. The controller is being calibrated.
If self-tuning is enabled, auto-tuning can still be used
any time. Self-tuning will use the auto-tuning results
for its initial values.
When bumpless transfer is configured, the correct control variable is applied immediately as power is recovered, and the disturbance is small. During sensor
breaks, the controller continues to control by using its
previous value. If the load doesn’t change, the process
will remain stable. If the load changes, the process may
run away. Therefore, you should not rely on bumpless
transfer for extended periods of time. For fail safe reasons, an additional alarm should be used to announce to
the operator when the system fails. For example, a sensor break alarm, if configured, will switch to failure state and tell
the operator to use manual control or take proper security action
when the system enters failure mode.
36
Warning:
After the
system fails,
never depend on
bumpless transfer
for a long time, or
it might cause the
system to run
away.
Benefits of self-tuning:
1. Unlike auto-tuning, self-tuning will produce less disturbance to the process.
2. Unlike auto-tuning, self-tuning doesn’t change the
control mode during the tuning period. It always performs PID control.
3. Changing the set point during self-tuning is allowable. Therefore, self-tuning can be used for ramping
set point control as well as remote set point control
where the set point is changed from time to time.
Operation:
The parameter SELF is contained in the setup
menu. Refer to section 1-5 to find SELF for initiating self-tuning.
Page 41
3–19 Auto tuning
The auto-tuning process is performed at the set point.
The process will oscillate around the set point during the
tuning process. Set the set point to a lower value if overshooting
beyond the normal process value is likely to cause damage.
Auto-tuning is applied in cases of:
• Initial setup for a new process
• The set point is changed substantially from the
previous auto-tuning value
• The control result is unsatisfactory
Operation:
1. The system has been installed normally.
2. Use the default values
for PID before tuning.
The default values are: PB1=PB2=18.0°F
TI1=TI2=100 seconds, TD1=TD2=25.0 sec-
onds.
Of course, you can use other reasonable values
for PID before tuning according to your previous experiences. But don’t use a zero value for
PB1 and TI1 or PB2 and TI2, otherwise, the
auto-tuning program will be disabled.
3.Set the set point to a normal operating value or
a lower value if overshooting beyond the normal
process value is likely to cause damage.
4. Press until appears
on the display.
5. Press for at least 3 seconds. The upper
display will begin to flash and the auto-tuning
procedure is beginning.
NOTE: Ramping function, remote set point,
or pump function, if used, will be disabled
once auto-tuning is proceeding.
will be strongly related to the time when the auto-tuning is
applied. Hence, different values will be obtained every time autotuning is completed without pre-tune. It is particularly true when
auto-tuning is applied using cold start and warm start.
If auto-tuning begins near the set point (warm start), the unit
skips the warm-up cycle and enters the waiting cycle. Afterward,
the procedures are the same as described for cold start.
Procedures:
Auto-tuning can be applied either as the process
is warming up (cold start) or when the process
has been in a steady state (warm start). See figure 3.22.
If auto-tuning begins apart from the set point (cold start), the unit
enters warm-up cycle. As the process reaches the set point value,
the unit enters a waiting cycle. The waiting
cycle elapses for a double integral time (TI1 or
TI2, dependent on the selection, see section
4.1), then it enters a learning cycle. The double
integral time is introduced to allow the process
to reach a stable state. Before the learning cycle,
the unit performs a pre-tune function with PID
control. While in the learning cycle, the unit
performs a post-tune function with an ON-OFF control. The
learning cycle is used to test the characteristics of the process.
The data is measured and used to determine the optimal PID values. At the end of the two successive ON-OFF cycles, the PID
values are obtained and automatically stored in the nonvolatile
memory. Once the auto-tuning procedures are completed, the
process display will cease to flash and the unit will revert to PID
control using its new PID values. During the pre-tune stage the
PID values will be modified if any unstable phenomenon which
is caused by incorrect PID values is detected. Without the pretune stage, like other conventional controllers, the tuning result
Pre-tune
function
advantage:
Consistent
tuning results
can be
obtained
Auto-Tuning Error
If auto-tuning fails, an ATER message will appear on the upper
display in the following cases:
• If PB exceeds 9000 (9000 PU, 900.0°F or 500.0°C);
• if TI exceeds 1000 seconds;
• if the set point is changed during the auto-tuning procedure;
• or if the event input state is changed so that the set point
value is changed.
Solutions to
1. Try auto-tuning again.
2. Don’t change the set point value during the auto-tuning
procedure.
3. Don’t change the event input state during the auto-tuning
procedure.
4. Use manual tuning instead of auto-tuning. (See section 3-20)
5. Touch any key to reset message.
37
Page 42
3–20 Manual Tuning
In certain applications (very few), when using both self-tuning and auto-tuning to tune a process proves
inadequate for the control requirements, you can try manual tuning. Connect the controller to the process
and perform the procedures according to the flow chart shown in the following diagram.
If the control performance using auto or selftuning is still unsatisfactory, the following
rules can be applied for further adjustment
of PID values:
Figure 3.25 shows the effects of PID adjustment on process response.
38
Page 43
3–21 Signal Conditioner
DC Power Supply
Three types of isolated DC power supplies are available to supply
an external transmitter or sensor. These are 20V rated at 25mA,
12V rated at 40mA and 5V rated at 80mA. The DC voltage is
delivered to the output 2 terminals.
3–22 Manual Control
Manual control may be used for the following purposes:
1. To test the process characteristics to obtain a step response as
well as an impulse response and use these data for tuning a
controller.
2. To use manual control instead of a closed-loop control if the
sensor fails or the controller’s A-D converter fails. NOTE that
bumpless transfer can not be used for an extended time. See
section 3-17.
3. In certain applications, it is desirable to supply a process with
a constant demand.
Operation:
Press until
(hand control) appears on the display.
Press for 3 seconds, then the upper
display will begin to flash and the lower
display will show . The controller is now in manual control mode.
Press ; the lower display will show
and alternately where indicates output
1 (or heating) control variable value MV1 and indicates
output 2 (or cooling) control variable value MV2. Now you can
use the up and down keys to adjust the percentage values for H or C.
The controller performs open loop control as long as it stays in
manual control mode. The H value is exported to output 1
(OUT1) and C value is exported to output 2 provided that OUT2
is performing cooling function (i.e., OUT2 selects COOL).
MV1=38.4% for
OUT1 (or heating)
MV2=7.63% for
OUT2 (or cooling)
Means
Means
Caution:
To avoid damage, don’t use a DC power supply beyond its
current rating. Purchase one with the correct voltage to suit
your external devices. See the ordering code in section 1-2.
Exception
If OUT1 is configured as ON-OFF control (i.e., PB1=0 if PB1 is
assigned or PB2=0 if PB2 is assigned by event
input), the controller will never perform manual
control mode.
Exiting Manual Control
Press keys the and the controller will
revert to its previous operating mode (may be a
failure mode or normal control mode).
39
Page 44
3–23 Display Mode
PVHIPVLOMV1MV2DVPV1PV2PBTITDCJCTPVRPVRHPVRL
Operation
Press several times until (display)
appears on the display. Then press to enter display mode.
You can select more parameters to view by pressing or
pressing in reverse sequence. The system mode of the
controller and its operation will remain unchanged. When the
controller enters display mode, the upper display will show the
parameter value and the lower display will show the parameter
symbol exceptand
age value for output 1 and shows the percentage value
for output 2 on the lower display while the upper display shows
the current process value.
.
PVHI/PVLO show the historical extreme
(maximum or minimum) values of the
process on the upper display. The historical
extreme values are saved in a nonvolatile
memory even when it is unpowered. Press
for at least 6 seconds to reset both the
historical values PVHI and PVLO and begin
to record new peak process values.
MV1/MV2 show the process value on the
upper display and shows the percentage control value for output 1, while
shows the percentage control value
for output 2.
DV shows the difference value between
process and set point (i.e., PV-SV). This
value is used to control output 1 and output 2.
PV1 shows the process value of input 1 on
the upper display.
PV2 shows the process value of input 2 on
the upper display.
PB shows the current proportional band
value used for control.
TI shows the current integral time used for
control.
TD shows the current derivative time used
for control. Since the controller is performing FUZZY control, the values of PB, TI,
and TD may change from time to time.
CJCT shows the temperature at the cold
junction, measured in °C independent of the
unit used.
PVR Shows the changing rate of the process
in °C (or °F or PU) per minute. It may be
negative if the process is going down.
PVRH/PVRL The maximum and mini-
mum changing rate of the process since
power up, as measured in °C (or °F or PU)
per minute. PVRH is a positive value while
PVRL is a negative value.
NOTE
The controller will never revert to its PV/SV display from display mode unless you press the keys.
shows the percent-
3–24 Heater Current Monitoring
TEC99999, a current transformer, should be equipped to measure the heater current. Select CT
for IN2. The input 2 signal conditioner measures the heater current while the heater is powered
and the current value will
remain unchanged while the
heater is unpowered. The PV2
will indicate the heater current.
For information on how to read
PV2 value, please refer to Table
1.4 under PVMD to use as a
process value or SPMD to use as
a setpoint.
NOTES
If the heater to be measured is
controlled by output 1, then
CYC1 should be set for 1 second or longer and O1TY should
use RELY, SSRD, or SSR.
Similarly, if the heater to be
measured is controlled by output 2, then CYC2 should be set for
1 second or longer and O2TY should use RELY, SSRD, or SSR
to provide an adequate time for the A to D converter to measure
the signal. Since TEC99999 can detect a full-wave AC current
only, a DC or half-wave AC current can’t be measured.
Accessory installed:
CT94-1
Setup
IN2=CT
O1TY or O2TY=RELY,
SSRD or SSR
CYC1 or CYC2≥1 second
Limitations
1. Linear output type can’t
be used.
2. CYC1 (or CYC2) should
be set for 1 second or
longer to detect heater
current reliably.
3. Only full-wave AC current can be detected.
3–25 Reload Default Values
The default values listed in table 1.4 are stored in the memory
when the product leaves the factory. In certain occasions, it is
desirable to retain these values after the parameter values have
been changed. Here is a convenient way to reload the default values.
Operation
Press several times until
appears. Then press .
The upper display will show . Use
the up and down keys to select 0 or 1. If °C
units are required, select 0 for FILE and if
°F units are required, select 1 for FILE.
Then press for at least 3 seconds. The
display will flash for a moment while the default values are
reloaded.
CAUTION
The procedure mentioned above will change the previous setup
data. Before performing it, make sure that it is really required.
FILE 0
°C default file
FILE 1
°F default file
40
Page 45
Chapter 4 Full Function Programming
4–1 Event Input
Refer to section 2-10 for wiring an event input.
The event input accepts a digital type signal. Three types of signal, relay or switch contacts, open collector pull low, and TTL
logic level can be used to switch the event input.
One of ten functions can be chosen by using (EIFN) in
the setup menu.
NONE: Event input no function
If chosen, the event input function is disabled. The controller
will use PB1, TI1, and TD1 for PID control and SP1 (or other
values determined by SPMD) for the set
point.
SP2: If chosen, the SP2 will replace
the role of SP1 for control.
PID2: If chosen, the second PID set
PB2, TI2, and TD2 will be used to
replace PB1, TI1, and TD1 for control.
SP.P2: If chosen, SP2, PB2, TI2, and
TD2 will replace SP1, PB1, TI1, and
TD1 for control.
NOTE: If the second PID set is chosen
during auto-tuning and/or self-tuning
procedures, the new PID values will be
stored in PB2, TI2, and TD2.
RS.A1: Resets alarm 1 as the event
input is activated. However, if the alarm
1 condition is still existent, alarm 1 will
be retriggered when the event input is
released.
RS.A2: Resets alarm 2 as the event
input is activated. However, if the alarm
2 condition is still existent, alarm 2 will
be retriggered when the event input is
released.
R.A1.2: Resets both alarm 1 and alarm
2 as the event input is activated.
However, if alarm 1 and/or alarm 2 are
still existent, alarm 1 and/or alarm 2
will be triggered again when the event
input is released.
RS.A1, RS.A2, and R.A1.2 are particularly suitable to be used for latching
and/or latching/holding alarms.
D.O1: Disables output 1 as the event input is activated. The out-
put 1 control variable MV1 is cleared to zero.
D.O2: Disables output 2 as the event input is activated. The out-
put 2 control variable MV2 is cleared to zero.
D.O1.2: Disables both output 1 and output 2 by clearing MV1
and MV2 values as soon as the event input is activated.
When any of D.O1, D.O2, or D.O1.2 are selected for EIFN,
output 1 and/or output 2 will revert to their normal conditions as
soon as the event input is released.
LOCK: All parameters are locked to prevent them from being
SP2F Function: Defines the format of SP2 value. If ACTU is
selected for SP2F in the
setup menu, the event
input function will use
the SP2 value for its second set point. If DEVI is
selected for SP2F, the
SP1 value will be added to SP2. The sum of SP1 and SP2
(SP1+SP2) will be used by the event input function for the second set point value. In certain applications, it is desirable to
move the second set point value with respect to the value of set
point 1. The DEVI function for SP2 provides a convenient way
to do this.
SP2F=Format of SP2 value
ACTU: SP2 is an actual value
DEVI: SP2 is a deviation value
Modification from RS-232 to event input:
Because of the limited number of pins, pin 14 is used for both
event input and RS-232. If you want to change function of the
TEC-9300 from RS-232 to event input, you must modify jumper
JP22 on the terminal board by opening jumper J1 and shorting
jumper J2. Refer to section 2-16 for the location of jumper JP22.
4–2 Second Set Point
In certain applications it is
desirable to have the set
point change automatically,
without the need to adjust it.
You can apply a signal to the
event input terminals (pin 14
and pin 13). The signal
applied to the event input
may come from a timer, a
PLC, an alarm relay, a manual switch or other devices.
Select SP2 for EIFN, which
is in the setup menu. This is
available only when SP1.2,
MIN.R, or HR.R is used for
SPMD, where MIN.R and
HR.R are used for the ramping function. See section 4-4.
Application 1: A process
is required to be heated to a
higher temperature as soon
as its pressure exceeds a certain limit. Set SPMD=SP1.2,
EIFN=SP2 (or SP.P2 if the second PID is required for the higher
temperature too). The pressure gauge is switched ON as it senses
a higher pressure. Connect the output contacts of the pressure
gauge to the event input. SP1 is set for a normal temperature and
SP2 is set for a higher temperature. Choose ACTU for SP2F.
Application 2: An oven is required to be heated to 300°C
from 8:00AM to 6:00PM. After 6:00PM it should be maintained
at 80°C. Use a programmable 24 hour cycle timer for this purpose. The timer output is used to control the event input. Set
SPMD=SP1.2, and EIFN=SP2 (or SP.P2 if the second PID is
required to be used for the second set point). SP1 is set at 300°C
and SP2 is set at 80°C. Choose ACTU for SP2F. After 6:00PM
the timer output is closed. The event input function will then
select SP2 (=80°C) to control the process.
Refer to section 4-1 for more descriptions about SP2F function.
Apply Signal To
14
Event input +
13
Event input –
Setup
EIFN choose SP2 or SP.P2
Availability
SPMD choose
or
or
Format of SP2 Value
SP2F choose
Actual Value
or Deviation Value
41
Page 46
4–3 Second PID Set
In certain applications the characteristics of a process are strongly related to its process value. The TEC9300 provides two sets of PID values. When the process is changed to
a different set point, the PID values
can be switched to another set to
achieve optimum conditions.
Auto-tuning second PID
The optimal PID values for a
process may vary with its process
value and set point. Hence if a
process is used for a wide range of
set points, dual PID values are necessary to optimize control performance. If the first PID set is selected (event input is not
applied) during auto-tuning procedure, the PID values will be
stored in PB1, TI1, and TD1. Similarly, if the second PID set is
selected (event input is applied while PID2 or SP.P2 is selected
for EIFN) during auto-tuning, the PID values will be stored in
PB2, TI2, and TD2 as soon as auto-tuning is completed.
Apply
Signal To
14
Event input +
13
Event input –
Setup
EIFN choose PID2 or
SP.P2
Application 1: programmed by the set point
Choose SP.P2 for EIFN then both set point and PID values will
be switched to another set simultaneously.
The signal applied to the event input may
come from a timer, a PLC, an alarm relay, a
manual switch or other devices.
EIFN=SP.P2
Application 2: programmed by
the process value
If the process value exceeds a certain limit,
500°C for example, it is desirable to use
another set of PID values to optimize control performance. You can use a process
high alarm to detect the limit of the process
value. Choose PV1H for A1FN, NORM for
A1MD, adjust A1SP to be equal to 500°C,
and choose PID2 for EIFN. If the temperature is higher than 500°C, then alarm 1 is activated. The alarm 1
output is connected to the event input, so the PID values will
change from PB1, TI1, and TD1 to PB2, TI2, and TD2.
Refer to section 5-9 for more details.
EIFN=PID2
Alarm output
controls the
event input
4–4 Ramp and Dwell
Ramp
The ramping function is performed
during power up as well as any
time the set point is changed.
Choose MINR or HRR for SPMD,
and the unit will perform the ramping function. The ramp rate is programmed by using RAMP, which
is found in the user menu.
Example without dwell timer
Select MINR for SPMD, °C for IN1U, 1-DP for DP1, and set
RAMP=10.0. SP1 is set to 200°C initially, then changed to 100°C
30 minutes after power up. The starting temperature is 30°C.
After power up, the process runs like the curve shown below:
separately or in conjunction with a ramp. If A1FN is set for
TIMR, alarm 1 will act as a dwell timer. Similarly, alarm 2 will
act as a dwell timer if A2FN is set for TIMR. The timer is programmed by using TIME which is in the user menu. The timer
starts to count as soon as the process reaches its set point, and
triggers an alarm when it times out. Here is an example.
Example without ramp
Select TIMR for A1FN, °F for IN1U, NODP for DP1, and set
TIME=30.0. SP1 is set to 400°F initially, and corrected to 200°F
before the process reaches 200°F. When the process reaches the
set point (i.e., 200°F), the timer starts to count. The TIME value
can still be corrected without disturbing the timer before time out.
Example: TIME is changed to 40.0, 28 minutes after the process
has reached its set point. The behavior of the process value and
alarm 1 are shown below.
Note: When the ramp function is used, the lower display will
show the current ramping value. However, it will revert to show
the set point value as soon as the up or down key is pressed for
adjustment. The ramping value is initiated as the process value
either at power up or when
RAMP and/or the set point are
changed. Setting RAMP to zero
means no ramp function at all.
Dwell
The dwell timer can be used
42
Once the timer output is energized, it will remain unchanged
until power down or an event input programmed for resetting
the alarm is applied.
Note: TIMR can’t be chosen for A1FN and A2FN simultaneously, or an error code will result.
4–4 Ramp and Dwell, continued next page…
Page 47
4–4 Ramp and Dwell, continued…
Ramp and dwell
A ramp may be accompanied with a dwell timer to control the
process. Here is an example.
Example with ramp and dwell
Select HRR for SPMD, PU for IN1U, 2-DP for DP1, and set
RAMP=60.00. Select TIMR for A2FN and set TIME=20.0. Set
E1 for SP2. When power is applied, the process value starts at
0.00, SP1=30.00, and SP2=40.00. The timer output is used to
control event input.
4–5 Remote Set Point
Selecting PV1 or PV2 for
SPMD will enable the TEC9300 to accept a remote set
point signal. If PV1 is selected
for SPMD, the remote set
point signal is sent to input 1,
and input 2 is used for the
process signal input. If PV2 is selected for SPMD, the remote set
point signal is sent to input 2, and input 1 is used for the process
signal. To achieve this, set the following parameters in the setup
menu.
Case 1: Use Input 2 to accept remote set point
FUNC=FULL
IN2, IN2U, DP2, IN2L, IN2H, are set according to remote sig-
nal.
PVMD=PV1
IN1, IN1U, DP1, are set according to the process signal
IN1L, IN1H if available, are set according to the process signal
Setup
FUNC = FULL
SPMD = PV2, PVMD = PV1
or
SPMD = PV1, PVMD = PV2
4–6 Differential Control
In certain applications it is desirable to control a second process
such that its process value always deviates from the first process by a constant
value. To achieve this, set the following
parameters in the setup menu.
FUNC=FULL
IN1, IN1L, IN1H are set according to input 1 signal
IN2, IN2L, IN2H are set according to input 2 signal
IN1U, DP1, IN2U, DP2, are set according to input 1 and input 2
signal
PVMD=P1-2 or P2-1
SPMD=SP1.2
The response of PV2 will be parallel to PV1 as shown in the fol-
lowing diagram at right
The PV display will indicate PV1-PV2 value if P1-2 is chosen for
PVMD, or PV2-PV1 value if P2-1 is chosen for PVMD. If you
need PV1 or the PV2 to be displayed instead of PV, you can use
the display mode to select PV1 or PV2 to be viewed. See section
3-23.
Setup
PVMD=P1-2
or PVMD=P2-1
SPMD=SP1.2
SPMD=PV2
Case 2: Use Input 1 to accept remote set point
FUNC=FULL
IN1, IN1U, DP1, IN1L, IN1H, are set according to remote sig-
nal.
PVMD=PV2
IN2, IN2U, DP2, are set according to the process signal
IN2L, IN2H if available, are set according to the process signal
SPMD=PV1
Note 1: If PV1 is chosen for both SPMD and PVMD, an
error code will appear. If PV2 is chosen for both
SPMD and PVMD, an error code will appear. In either
case, the TEC-9300 will not control properly.
Note 2: If PV1/PV2 is selected for SPMD, a signal loss will
result in the controller reverting
to manual mode with 0% output.
Error messages
If P1-2 or P2-1 is selected for PVMD, while PV1 or PV2 is
selected for SPMD, an error code will appear.
In this case the signals used for input 1 and input 2 should be the
same unit and the same decimal point, that is, IN1U=IN2U,
DP1=DP2, otherwise an error code will appear.
43
Page 48
4–7 Output Power Limits
In certain systems the heater (or cooler) is overdesigned such that the process is too heavily heated
or cooled. To avoid an excessive overshoot and/or
undershoot you can use the power limit function.
Output 1 power limit PL1 is contained in the user
menu. If output 2 is not used for cooling (that is, COOL is not
selected for OUT2), then PL2 is hidden. If the controller is used
for ON-OFF control, then both PL1 and PL2 are hidden.
Operation:
Press for 3 seconds, then pressseveral times to reach PL1
and PL2. PL1 and PL2 are adjusted by using the up and down
keys with range of 0–100%.
Example:
OUT2=COOL, PB1=10.0°C, CPB=50, PL1=50, PL2=80
Output 1 and output 2 will act as the following curves:
NOTE:
The adjustment range of MV1 (H) and MV2 (C) for manual control and/or failure transfer are not limited by PL1 and PL2.
Menu
PL1
PL2
4–8 Data Communication
Two types of interfaces are available for data communication.
These are the RS-485 and RS232 interfaces. Since RS-485
uses a differential architecture to
drive and sense signal instead of
a single ended architecture
which RS-232 uses, RS-485 is
less sensitive to noise and more
suitable for communication over
longer distances. RS-485 can
communicate without error over
a distance of 1km while RS-232
is not recommended for distances over 20 meters.
Using a PC for data communication is the most economical method. The signal is transmitted and
received through the PC communication port (generally RS-232).
Since a standard PC can’t support an RS-485 port, a network
adapter (such as TEC99001) has to be used to convert RS-485 to
RS-232 for a PC if RS-485 is required for data communication.
Up to 247 RS-485 units can be connected to one RS-232 port;
therefore a PC with four comm ports can communicate with 988
units.
Setup
Enter the setup menu.
Select FULL (full function) for
FUNC.
Select 485 for COMM if RS-485
is required, or 232 if RS-232 is
required. Select RTU (i.e.,
Modbus protocol RTU mode )
for PROT. Set individual
addresses for any units that are
connected to the same port. Set
the baud rate (BAUD), data bit
(DATA), parity bit (PARI) and
stop bit (STOP) so that these values are accordant with the PC
setup conditions.
NOTE: If the TEC-9300 is con-
figured for RS-232 communication, the EI (event input) is disconnected internally. The unit
can no longer perform event
input function (EIFN).
When you attach an RS-232
module (TEC-102-103) to the
connectors on the CPU board,
you also need to modify jumper
JP22 according to section 2-16.
If you use a conventional 9-pin
RS-232 cable instead of CC94-1,
the cable should be modified for
the proper operation of RS-232
communications according to
section 2-16.
RS-485 Benefits:
Long distance
Multiple units
RS-232 Benefits:
Direct connection to a PC
RS-485 Setup
FUNC = FULL
COMM = 485
PROT = RTU
ADDR = Address
BAUD = Baud Rate
DATA = Data Bit Count
PARI = Parity Bit
STOP = Stop Bit Count
RS-485 Terminals
9
TX1
10
TX2
RS-232 Setup
FUNC = FULL
COMM = 232
PROT = RTU
ADDR = Address
BAUD = Baud Rate
DATA = Data Bit Count
PARI = Parity Bit
STOP = Stop Bit Count
RS-232 Terminals
9
TX1
44
10
14
TX2
COM
Page 49
4–9 Analog Retransmission
FILT
Analog retransmission is available for
model number TEC-9300-XXXXXN
where N=3, 4 or 5. See ordering code in
section 1-2.
Setup
Select FULL for FUNC in the setup menu.
Select a correct output signal for COMM
which should be accordant with the
retransmission option used. Five types of
retransmission output are available. These
are: 4–20mA, 0–20mA, 0–5V, 1–5V and
0–10V. There are eight types of parameters
that can be retransmitted according to the
analog function (AOFN) selected. These
are: PV1, PV2, PV1–PV2, PV2–PV1, SV, MV1, MV2 and PV–
SV. Refer to table 1.4 for a complete description. Select a value
for AOLO corresponding to output zero and select a value for
AOHI corresponding to output SPAN.
How to determine output signal:
AOLO and AOHI are set to map to output signal low SL (e.g.,
4mA) and output signal high SH (e.g., 20mA) respectively. The
analog output signal AOS, corresponding to an arbitrary value of
parameter AOV, is determined by the following curve.
Terminals
9
AO+
10
AO–
4–10 Digital Filter
In certain applications the process
value is too unstable to be read. A
programmable low-pass filter
incorporated in the TEC-9300 can
be used to improve this. This is a
first order filter with the time constant specified by the FILT
parameter which is in the setup menu. The default value of FILT
is set at 0.5 seconds before shipping. Adjust FILT to change the
time constant from 0 to 60 seconds. 0 seconds means no filter is
applied to the input signal. The filter is characterized by the following diagram.
Menu
FILT
Filter is used to stabilize
the process display.
Notes:
The setup values used for AOHI and
AOLO must not be equal, otherwise,
incorrect values will occur. However,
AOHI can be set either higher or lower
than AOLO. If AOHI is set higher than
AOLO it could result in a direct conversion. If AOHI is set lower than AOLO it
could result in a reverse conversion.
NOTES
AOHI ≠ AOLO
AOHI > AOLO:
Direct
conversion
AOHI < AOLO:
Reverse
conversion
Example
A control uses a 4–20mA analog output to retransmit the difference value between input 1 and input 2 (PV1–PV2). It is required
that if the difference value is -100, 4mA will be exported, and if
the difference value is 100, 20mA will be exported. Make the following setup for TEC-9300:
IN1U=PU, DP1=NODP, IN2U=PU, DP2=NODP, FUNC=FULL,
COMM=4-20, AOFN=P1-2, AOLO (low side of scale) =-100,
AOHI (high side of scale)=100
Note
The filter is available only for PV1, and is performed for the displayed value only. The controller is designed to use unfiltered signal for control even if the filter is applied. A lagged (filtered) signal, if used for control, may produce an unstable process.
4–11 Sleep Mode
To enter sleep mode:
Set FUNC for FULL to pro-
vide full function.
Select YES for SLEP to enable
sleep mode.
Press for 3 seconds;
the unit will now enter sleep
mode.
During sleep mode:
1. All displays are shut off
except a decimal point which is lit periodically.
2. All outputs and alarms are shut off.
To exit sleep mode:
1. Press to leave the sleep mode.
2. Disconnect the power.
The sleep function can be used in place of a power switch to
reduce the system cost.
Default: SLEP=NONE, sleep mode is disabled.
Note: If sleep mode is not required by your system, NONE
should be selected for SLEP to disable sleep mode.
Sleep mode features:
Shut off display
Shut off outputs
Green power
Replaces power switch
Setup menu
FUNC = FULL
SLEP = YES
45
Page 50
4–12 Pump Control
Pump control function is one of the
unique features of the TEC-9300.
Using this function, the pressure in
a process can be excellently controlled. The pressure in a process is commonly generated by a
pump driven by a variable speed motor. The complete system has
the following characteristics which affect control behavior. 1. The
system is very noisy. 2. The pressure changes very rapidly. 3. The
pump characteristics are ultra nonlinear with respect to its speed.
4. The pump can’t generate any more pressure if its speed is lower
than half of its rating speed. 5. An ordinary pump may slowly lose
pressure even if the valves are completely closed.
Obviously, a conventional controller can’t fulfill the conditions
mentioned above. Only the superior noise rejection capability in
addition to the fast sampling rate possessed by the TEC-9300 can
handle such an application. To achieve this, set the following
parameters in the setup menu:
the set point as soon as the material is demanded again while
the pressure falls below a predetermined value (i.e., SP1+SP2).
Programming guide:
1. Perform auto-tuning to the system under such conditions that
the material (i.e., pressure) is exhausted at typical rate. A typical value for PB1 is about 10Kg/cm≈, TI1 is about 1 second,
TD1 is about 0.2 seconds.
2. If the process oscillates around the set point after auto-tuning,
then increase PB1 until the process can be stabilized at the set
point. The typical value of PB1 is about half to two times the
range of the pressure sensor.
3. Increasing FILT (filter) can further reduce the oscillation
amplitude. But a value of FILT higher than 5 (seconds) is not
recommended. A typical value for FILT is 0.5 or 1.
4. Close the valves and observe whether the controller can shut
off the pump each time. The value of REFC should be adjusted
as little as possible so that the controller can shut off the pump
each time when all the valves are closed. A typical value for
REFC is between 3 and 5.
5. An ordinary pump may slowly lose pressure even if the valves
are completely closed. Adjust SP2 according to the rule that a
more negative value of SP2 will allow the pump to be shut off
for a longer time when the valves are closed. A typical value
for SP2 is about -0.50Kg/cm≈.
An example for pump control is given in section 5-1.
and program the following parameters in the user menu:
REFC = reference constant
SP2 = a negative value added to SP1 to obtain the set point for
the idle state
Since the pump can’t produce
any more pressure at lower
speeds, the pump may not
stop running even if the pressure has reached the set point.
If this happens, the pump will
be overly worn and waste
additional power. To avoid
this, the TEC-9300 provides a
reference constant REFC in
the user menu. If PUMP is selected for SPMD, the controller will
periodically test the process by using this reference constant after
the pressure has reached its set point. If the test shows that the
pressure is still consumed by the process, the controller will continue to supply appropriate power to the pump. If the test shows
that the pressure is not consumed by the process, the controller
will gradually decrease the power to the pump until the pump
stops running. When this happens, the controller enters an idle
state. The idle state will use a lower set point which is obtained
by adding SP2 to SP1 until the pressure falls below this set point.
The idle state is provided for the purpose of preventing the pump
from been restarted too frequently. The value of SP2 should be
negative to ensure that the controller functions correctly.
The pump functions are summarized as follows:
1. If the process is demanding material (i.e., loses pressure), the
controller will precisely control the pressure at the set point.
2. If the process no longer consumes material, the controller will
shut off the pump for as long as possible.
3. The controller will restart the pump to control the pressure at
Pump control features:
1. Minimum oscillation of
pressure
2. Rapidly stabilized
3. Guaranteed pump stop
4. Programmable pump stopping interval
4–13 Remote Lockout
The parameters can be locked to prevent them from being
changed by using either hardware lockout (see section 1-3),
remote lockout, or both. If you
need the parameters to be
locked by using an external
switch (remote lockout function), then connect a switch to
terminals 13 and 14 (see section 2-10), and choose LOCK for EIFN (see section 4-1).
If remote lockout is configured, all parameters will be locked
when the external switch is closed. When the switch is left open,
the lockout condition is determined by internal DIP switch (hardware lockout, see section 1-3).
Hardware lockout: Can be used only during initial setup.
Remote lockout: Can be used any time.
Remote Lockout:
1. Connect external switch
to terminal and .
2. Set LOCK for EIFN
3. Lock all parameters
1413
46
Page 51
Chapter 5 Applications
Figure 5.2
Block Diagram of VPFW SSR
5–1 Pump/Pressure Control
Regulated water supply systems are widely used in residential
areas, water plants, chemical plants, electrical plants, semiconductor plants, etc. By taking advantage of its PUMP function, the
TEC-9300 can be used to create an economical yet versatile solution for these applications. Here is an example:
The water pressure in this example must be controlled at
10Kg/cm≈. To achieve this, the following devices are used for
this example:
Inverter: To supply a variable frequency AC voltage to the
motor.
Motor: A 3-Ø induction motor.
Pump: Any appropriate economical type of pump.
Pressure Sensor: A three-wire or two-wire type of pressure
transducer with a 0–20Kg/cm≈ range.
Pressure Reservoir: Provides smoother pressure for the
system.
TEC-9300: Order a TEC-9300 with standard input, 4–20mA
VPFW SSR is a variable period full wave solid-state relay. It can
provide a zero cross output with superior controllability compared to a conventional SSR with a fixed time base. The block
diagram of VPFW SSR is shown as follows:
NOTES:
1. The VPFW SSR can be used to drive a resistant load and some
types of inductance loads such as relay, contactor, magnetic
switch, solenoid valve, etc. However, it can not drive a motoror capacitance load.
2. Only AC power can supply VPFW SSR, otherwise it will not
operate properly.
Unlike a conventional SSR, the VPFW SSR always gives the output an even number of half cycles (full wave) as shown in the following diagram.
The VPFW switches the load without DC current, minimizing the
harmonic current and stress on the load. This prolongs the load
life.
Since the duty cycle (i.e., output power level) of the control input
is small, the off-period will be extended to keep the output resolution such that the conversion error is minimized. As low as
0.1% timing error can be achieved. Hence, VPFW SSR is particularly suitable for smoother control.
47
Page 52
5–2 Variable Period Full Wave SSR, continued…
The advantages of VPFW SSR, over conventional SSR, are summarized in the following table:
Output 1 and output 2 of the TEC-9300 can be connected to the
VPFW SSR directly provided that a pulsed voltage drive output
is ordered.
5–3 Heat Only Control
An oven is designed to dry the products at 150°C for 30 minutes
and then stay unpowered for another batch. A TEC-9300
equipped with dwell timer is used for this purpose. The system
diagram is shown as follows:
Here is an example:
To achieve this function, set the following parameters in the setup
menu.
Three phase VPFW SSR’s are also available upon request.
48
Page 53
5–4 Cool Only Control
A TEC-9300 is used to control a refrigerator with
the temperature below 0°C. To avoid set point
adjustment beyond the desired range, SP1L is set at
-10°C and SP1H is set at 0°C. Because the temperature is lower than the ambient, a cooling action is
required, so select DIRT for OUT1. Since output 1
is used to drive a magnetic contactor, select RELY
for O1TY. Because a small temperature oscillation
is tolerable, use ON-OFF control to reduce the overall cost. To achieve ON-OFF control, PB1 is set to
zero and O1HY is set at 0.1°C.
5–5 Heat-Cool Control
An injection mold is required to be controlled at
120°C to ensure a consistent quality for the parts. An oil
pipe is buried in the mold. Since plastics are injected at
a higher temperature (e.g., 250°C), the circulation oil
needs to be cooled as its temperature rises. Here is an
example at right:
PID heat-cool is used for the example at right.
To achieve this, set the
following parameters in the setup menu:
FUNC = BASC
IN1 = PT.DN
IN1U = °C
DP1 = 1-DP
OUT1 = REVR
O1TY = RELY
Adjust SP1 to 120.0°C, CPB to 125(%) and
DB to -4.0(%).
Apply auto-tuning at 120°C for a new system
to get optimal PID values. See section 3-19.
Adjustment of CPB is related to the cooling
medium used. If water is used as the cooling
medium instead of oil, the CPB should be set at
250(%). If air is used as the cooling medium
instead of oil, the CPB should be set at 100(%).
Adjustment of DB is dependent on the system
requirements. A more positive value of DB will
prevent unwanted cooling action, but will
increase the temperature overshoot, while a
more negative value of DB will achieve less
temperature overshoot, but will increase
unwanted cooling action.
A chamber is used to test the temperature cycling effect on
personal computers. An external cycle timer is used to control
the event input for switching the set point. The products under
test are required to stay at 60°C for 1 hour and -10°C for 30
minutes. The transition interval between the high and low
temperatures is required to be 5 minutes. Make the following
setup:
The circuit diagram and its temperature profile are shown below:
The TEC-9300 provides a 4–20mA signal to control the speed
of the inverter. SP.P2 is chosen for EIFN in order to create a dual
PID control. You can perform auto-tuning twice at SP1 and SP2
for the initial setup for the dual PID values. Refer to sections
3-19 and 4-3.
Example 2: Programmable bread baking oven
Bread is baked in batches. A ramp is incorporated to control
the thermal gradient to suit for making the bread. A dwell timer is
used to shut off the oven power and announce this to the baker.
The system is configured as shown in the following diagram.
Terminal
87
, use
Form B Relay
50
Order a form B relay for alarm 1. Push the ON switch to start
a batch. The temperature will rise with a ramp rate determined by
the RAMP value. The bread is baked with the set point temperature for a predetermined amount of time which is set in the TIME
value, and then the power is shut off. The temperature profile is
shown in the following figure.
Page 55
5–7 Remote Set
Point
An on-line multiple zone
oven is used to dry paint.
Since heat demand varies at
different positions in the production line, multiple zones
with individual controls
should be used to ensure a
consistent temperature profile. If you order a TEC-9300
with a retransmission unit for
the master controller, and
retransmit its set point to
input 2 on the rest of the
slave controllers, each zone
will be synchronized with the
same temperature. Here is an
example at right:
In certain applications it is desirable to control a second
process so that its process value always deviates from the
first process value by a constant amount. Water tank 1 is
5.12 meters in height, and the level in water tank 2 needs
to be maintained at 1 meter lower than the tank 1 level.
Set the following parameters in the setup menu:
FUNC = FULL
IN1, IN1L, IN1H: According to sensor 1 signal
IN1U = PU
DP1 = 2-DP
IN2, IN2L, IN2H: According to sensor 2 signal
IN2U = PU
DP2 = 2-DP
OUT1 = REVR
O1TY = 4–20
PVMD = P1-2
SPMD = SP1.2
If a voltage signal (such as in the above example) is sent to slave
units, the slave inputs should be connected in parallel. If a current signal (e.g., 4–20mA) is sent to slave units, the slave inputs should be
connected in series. Current retransmission is widely used because it
can transmit over a longer distance without voltage drop.
Note: AOHI and IN2H should be set with values higher than the set
point range used.
Adjust SP (here it is 1.00) to control the difference
between PV1 and PV2. Choose P1-2 for PVMD; the PV
display will show the difference value (PV1-PV2)
between PV1 and PV2, and this value will be stabilized to
the set point (here it is 1.00). If you need PV1 or PV2
instead of PV, you can use the display mode to select PV1
or PV2 for display. See section 3-23. The diagram at right
indicates PV2 instead of PV.
51
Page 56
5–9 Dual Set Point/PID
The TEC-9300 will switch between the two PID sets based on the
process value, the set point, or either of the event inputs. As the
control ramps up to the higher process value, the process characteristics change. When this happens, the original PID values are
no longer valid. To achieve optimal control over the entire range,
a second PID set is used.
Example 1: Single set point/dual PID
A heat treating furnace is used over the range of 400°C to 1200°C.
1. Set the following parameters in the setup menu:
FUNC = FULL
2. Adjust the following parameters in the user menu:
A1SP = 800°C
A1HY = 1.0°C
PL1 = 100(%)
RAMP: According to the process requirement
SP1: According to the process requirement
3. Tune the first PID set at SP1=50°C and tune the second PID set
at SP1=1100°C, or set the proper values for PB1, TI1, TD1,
PB2, TI2, and TD2 directly according to previous records to
eliminate the auto-tuning sequence.
Example 2: Dual set point/PID
A heat treating furnace is required to harden the mold at a high
temperature (1000°C) for 30 minutes, then the mold is cooled
down with a programmable ramp (20°C/minute) to a lower set
point (200°C). Use the dual set point/PID and ramp/dwell functions for this application.
1. Set the following parameters in the setup menu:
FUNC = FULL
A1FN = TIMR
EIFN = SP.P2
PVMD = PV1
SPMD = MINR
2. Adjust the following parameters in the user menu:
TIME = 30.0 (minutes)
RAMP = 20.0 (°C/minute)
SP1 = 1000°C
SP2 = 200°C
PL1 = 100(%)
3. Set the proper values for PB1, TI1, TD1, PB2, TI2, and TD2
directly according to previous records. For a new system, tune
the first PID set at SP1 = 800°C and tune the second PID set at
SP2 = 400°C.
The circuit diagram is the same as shown in figure 5.14. The temperature profile is shown below:
The circuit diagram and its temperature profile are shown as follows:
52
Page 57
5–10 RS-485
A tile making plant has five production
lines. Each production line is equipped
with 16 TEC-9300 units to control the
temperature for the kiln. They want to
program the controllers and monitor the
process from the control room to improve
quality and productivity. A cost-effective
solution for the above application would
be to use 80 TEC-9300 units plus a Smart
Network Adapter (Part Number TEC99003)
and DAQ (Part Number TEC99923) PCbased software for this purpose.
The system is installed as shown in the
following diagram.
Setup
Enter setup mode to configure each TEC-
9300. Choose FULL for FUNC, 485 for
COMM, RTU for PROT, and select a different address (ADDR) for each unit. Use
the same values of BAUD, DATA, PARI,
and STOP for the TEC-9300’s, Smart
Network Adapter and DAQ Software. Also
refer to section 2-15 and section 4-8.
Taking advantage of DAQ software, the
operator can monitor the process on the
PC screen, program the set point as well as
other control parameters such as PID values, download the ramp and soak profile
to the controllers, execute the manual control or trigger auto-tuning, etc., and print
out reports as required. The historical data
can be saved in the floppy drive, hard
drive, or on a CD for permanent storage.
Setup menu
FUNC
COMM
PROT
ADDR
BAUD
DATA
PARI
STOP
53
Page 58
5–11 RS-232
Suppose a chemical experiment is performed in a laboratory
and an engineer wants to find the relationship between the chemical reaction and temperature. He uses a TEC-9300 to control the
temperature of the solution being tested. He is particularly interested in generating a test report containing the relationship
between the concentration and temperature.
For a single unit application, it is adequate to order a TEC9300 with RS-232 communication and DAQ (Part Number
TEC99923) software. Using the DAQ software, the temperature
data can be viewed and stored in a file. The user can program the
temperature as well as other control parameters such as PID values. He can set up the controller, download a ramp and soak profile, execute manual control or auto-tuning procedure, etc. The
results can be printed out or stored in a file for future reference.
Refer to section 2-16 for installation and section 4-8 for setup
procedure.
5–12 Retransmit
An air-conditioned room uses two TEC-9300 units to control
the temperature and humidity. The temperature and humidity
must be recorded on a chart recorder. The preferred ranges for
these two parameters are: 20°C to 30°C and 40% RH to 60% RH.
The recorder inputs accept a 0–5V signal.
To achieve this, set the following parameters in the setup menu.
Do not proceed through this section unless there is a defi-
nite need to recalibrate the controller. If you do recalibrate,
all previous calibration data will be lost. Do not attempt recalibration unless you have the appropriate calibration equipment. If the
calibration data is lost, you will need to return the controller to
your supplier who may charge you a service fee to recalibrate the
controller.
Entering calibration mode will break the control loop. Make
sure that the system is ready to enter calibration mode.
Equipment needed for calibration:
1. A high-accuracy calibrator (Fluke 5520A calibrator
recommended) with the following functions:
0–100mV millivolt source with ±0.005% accuracy
0–10V voltage source with ±0.005% accuracy
0–20mA current source with ±0.005% accuracy
0–300 ohm resistant source with ±0.005% accuracy
2. A test chamber providing 25°C–50°C temperature range
The calibration procedures described in the following section are
step by step manual procedures.
Since it takes 30 minutes to warm up a unit before calibration,
calibrating the units one by one is quite inefficient. An automatic
calibration system for small quantities as well as one for unlimited quantities is available upon request.
Manual calibration procedures
• Perform step 1 to enter calibration mode.
Step 3
Press the scroll key until the display shows
60mV signal to terminals 12 and 13 with the correct polarity.
Press the scroll key for at least 3 seconds. The display will blink
for a moment until a new value is obtained. If the display didn’t
blink or if the obtained value is equal to -199.9 or 199.9, then calibration failed.
• Perform step 4 to calibrate the voltage function (if required) for
input 1.
Send a
.
Step 4
Set the DIP switch for voltage
input. Press the scroll key until the
display shows . Send a
10V signal to terminals 12 and 13
with the correct polarity. Press the scroll key for at least 3 seconds. The display will blink for a moment until a new value is
obtained. If the display didn’t blink or if the obtained value is
equal to -199.9 or 199.9, then calibration failed.
• Perform both steps 5 and 6 to calibrate RTD function (if
required) for input 1.
Step 5
Set the DIP switch for RTD input.
Press the scroll key until the display
shows . Send a 100 ohms signal to terminals 18, 19, and 20 using
to the connection shown below:
Step 1
Set the lockout DIP switch to the unlocked condition (both
switches 3 and 4 are off).
Press both scroll and down keys and release them quickly. The
operation mode menu will appear on the display. Repeat this
operation several times until appears on the display. Press the scroll key for at least 3 seconds. The display will
show and the unit will enter calibration mode. Output 1
and output 2 use their failure transfer values to control.
• Perform step 2 to calibrate zero for the A to D converter and step
3 to calibrate the gain for the A to D converter. The DIP switch
should be set for T/C input.
Step 2
Short terminals 12 and 13, then press
the scroll key for at least 3 seconds.
The display will blink for a moment
until a new value is obtained. If the
display didn’t blink or if the obtained
value is equal to -360 or 360, then calibration failed.
Press the scroll key for at
least 3 seconds. The display will blink for a
moment; if it does not,
calibration failed.
Step 6
Press the scroll key and the display will show
the ohm’s value to 300 ohms. Press the scroll key for at least 3
seconds. The display will blink for a moment while values are
obtained for SR1 and REF1 (last step). If the display didn’t blink
or if any value obtained for SR1 or REF1 is equal to -199.9 or
199.9, then calibration failed.
• Perform step 7 to calibrate mA function (if required) for input 1.
Change
.
Step 7
Set the DIP switch for mA input.
Press the scroll key until the display
shows . Send a 20mA signal
to terminals 12 and 13 with the correct polarity. Press the scroll key for at least 3 seconds. The display will blink for a moment until a new value is obtained. If the
display didn’t blink or if the obtained value is equal to -199.9 or
199.9, then calibration failed.
• Perform step 8 to calibrate voltage as well as CT function (if
required) for input 2.
Manual calibration procedures, continued next page…
55
Page 60
Manual calibration procedures, continued…
Step 8
Press the scroll key until the display shows . Send a 10V
signal to terminals 15 and 16 with the correct polarity. Press the
scroll key for at least 3 seconds. The display will blink for a
moment until a new value is obtained. If the display didn’t blink
or if the obtained value is equal to -199.9 or 199.9, then calibration failed.
• Perform step 9 to calibrate mA function ( if required ) for input
2.
Step 9
Press the scroll key until the display shows . Send a
20mA signal to terminals 15 and 16 with the correct polarity.
Press the scroll key for at least 3 seconds. The display will blink
for a moment until a new value is obtained. If the display didn’t
blink or if the obtained value is equal to -199.9 or 199.9, then
calibration failed.
• Perform step 10 to calibrate offset of cold junction compensation, if required. Set the DIP switch for T/C input.
Step 10
Set up the equipment according to
the following diagram to calibrate
the cold junction compensation.
Note that a K type thermocouple
must be used.
Step 11
Set up the equipment the same as in step 10. The unit under calibration is powered in a still-air room with a temperature of
50±3°C. Allow at least 20 minutes to warm up. The calibrator
source is set at 0.00°C with internal compensation mode.
Perform step 1 as stated above, then press the scroll key until
the display shows
value of 0.0 is obtained. Press the scroll key for at least 3 seconds. The display will blink for a moment until a new value is
obtained. If the display didn’t blink or if the obtained value is
equal to -199.9 or 199.9, then calibration failed. This setup is
performed in a high temperature chamber, therefore it is recommended to use a computer to perform the procedures.
Press the up and down keys until a
.
Step 11N
Perform step 1 as stated above, then press the scroll key until the
display shows . Press the up and down keys until a value
of 0.1 is obtained. Press the scroll key for at least 3 seconds. The
display will blink for a moment until the new value 0.0 is
obtained. Otherwise, calibration failed.
Caution: It is not recommended to use step 11N, since the
cold junction gain is not able to achieve the rated accuracy using
this step.
• Final step
Step 12
Set the DIP switch to your desired position (refer to section 1-3).
The 5520A calibrator is configured for K type thermocouple output with internal compensation. Send a 0.00°C signal to the unit
under calibration. The unit under calibration is powered in a stillair room with a temperature of 25±3°C. Allow at least 20 minutes to warm up. The DIP switch is located at the TC input.
Perform step 1 as stated above, then press the scroll key until the
display shows
of 0.00 is obtained. Press the scroll key at least 3 seconds. The
display will blink for a moment until a new value is obtained. If
the display didn’t blink or if the obtained value is equal to -5.00
or 40.00, then calibration failed.
• Perform step 11 to calibrate the gain of cold junction compensation if required. If a test chamber for calibration is not available, perform step 11N to use a nominal value for the cold junction gain.
Press the up and down keys until a value
.
Automatic calibration procedures
The programming port (see section 2-18) of the TEC-9300 can
be used for automatic calibration.
The equipment required for automatic calibration is available
upon request.
56
Page 61
Chapter 7 Error Codes and Troubleshooting
This procedure requires access to the circuitry of a unit
under live power. Accidental contact with line voltage is
possible. Only qualified personnel should perform these procedures. Potentially lethal voltages are present.
Troubleshooting procedures:
1. If an error message is displayed, refer to table 7.1 to see what
caused it and what action to take to correct the problem.
2. Check each point listed below. Experience has proven that
many control problems are caused by a defective instrument
and not the controller
• Incorrect settings
• Line wires are improperly connected
• No voltage between line terminals
• Incorrect voltage between line terminals
• Connections to terminals are open, missing, or loose
• Thermocouple is open at tip
• Thermocouple lead is broken
• Shorted thermocouple leads
• Short across terminals
• Open or shorted heater circuit
• Open coil in external contactor
• Burned out line fuses
• Burned out relay inside control
• Defective solid-state relays
• Defective line switches
• Burned out contactor
• Defective circuit breakers
3. If the points listed on the above chart have been checked and
the controller still does not function properly, it is recommended that the instrument be returned to the factory for
inspection. Do not attempt to make repairs without a qualified
engineer and proper technical information, as damage may
result. It is also recommended to use adequate packing materials to prevent damage during transportation.
4. Dismantle the controller according to figure 7.1. Refer to table
7.2 for some probable causes and actions.
57
Page 62
58
Page 63
59
Page 64
NOTES
60
Page 65
Chapter 8 Specifications
Power
90–264VAC, 47–63Hz, 15VA, 7W maximum
11–26 VAC/VDC, 15VA, 7W maximum
Input 1 resolution: 18 bits
Sampling rate: 5x/second
Maximum rating: -2VDC minimum, 12VDC maximum
(1 minute for mA input)
Temperature effect: ±1.5uV/°C for all inputs except mA
input ±3.0uV/°C for mA input
Sensor lead resistance effect:
T/C: 0.2uV/ohm
3-wire RTD: 2.6°C/ohm of resistance difference of two leads
2-wire RTD: 2.6°C/ohm of resistance sum of two leads
Common mode rejection ratio (CMRR): 120dB
Normal mode rejection ratio (NMRR): 55dB
Sensor break detection:
Sensor open for TC, RTD, and mV inputs, below 1mA for 4–
20mA input, below 0.25V for 1–5V input, unavailable for
other inputs.
Sensor break responding time:
Within 4 seconds for TC, RTD, and mV inputs, 0.1 second for
4–20mA and 1–5V inputs.
Characteristics:
Input 2
Resolution:
18 bits
Sampling rate: 1.66 times/second
Maximum rating: -2VDC minimum, 12VDC maximum
Temperature effect: ±3.0uV/°C for mA input ±1.5uV/°C
for all other inputs
Common mode rejection ratio (CMRR): 120dB
Sensor break detection: Below 1mA for 4–20mA input,
below 0.25V for 1–5V input,
unavailable for other inputs.
Sensor break responding time: 0.5 seconds
Characteristics:
Input 3 (event input)
Logic low:
-10V minimum, 0.8V maximum.
Logic high: 2V minimum, 10V maximum
External pull-down resistance: 400KΩ maximum
External pull-up resistance: 1.5MΩ minimum
Functions: select second set point and/or PID, reset alarm 1
2A/240 VAC, life cycles 200,000 for resistive
load
Pulsed voltage: source voltage 5V, current limiting resist-
ance 66Ω.
Linear output characteristics:
Linear Output
Resolution:
15 bits
Output regulation: 0.01% for full load change
Output settling time: 0.1 second (stable to 99.9%)
Isolation breakdown voltage: 1000VAC
Temperature effect: ±0.0025% of SPAN/°C
61
Page 66
Triac (SSR) Output
Rating:
1A/240VAC
Inrush Current: 20A for 1 cycle
Min. Load Current: 50mA rms
Max. Off-state Leakage: 3mA rms
Max. On-state Voltage: 1.5V rms
Insulation Resistance: 1000Mohms min. at 500VDC
Dielectric Strength: 2500VAC for 1 minute
DC voltage supply characteristics
(installed at output 2)
Alarm 1/Alarm 2
Alarm 1 relay:
Form A or Form B, max. rating 2A/240VAC,
100,000 life cycles for resistive load.
Alarm 2 relay: Form A, max. rating 2A/240VAC, 200,000 life
Output Regulation: 0.01% for full load change
Output Settling Time: 0.1 sec. (stable to 99.9%)
Isolation Breakdown Voltage: 1000VAC min.
Integral linearity error: ±0.005% of span
Temperature effect: ±0.0025% of span/°C
Saturation low: 0mA (or 0V)
Saturation high: 22.2mA (or 5.55V, 11.1V min.)
Linear output range:
62
0–22.2mA(0–20mA or 4–20mA), 0–5.55V
(0–5V, 1–5V), 0–11.1V (0–10V)
User Interface
Dual 4-digit LED displays:
Upper 0.4" (10mm), lower
0.3" (8mm)
Keypad: 3 keys
Programming port: For automatic setup, calibration, and
testing
Communication port: Connection to PC for supervisory
control
Control Mode
Output 1:
Reverse (heating) or direct (cooling) action
Output 2: PID cooling control, cooling P band 1~255% of PB
ON-OFF: 0.1–100.0(°F) hysteresis control (P band=0)
P or PD: 0–100.0% offset adjustment
PID: Fuzzy logic modified
Proportional band 0.1~900.0°F
Integral time 0–1000 seconds
Derivative time 0–360.0 seconds
Cycle time: 0.1–100.0 seconds
Manual control: Heat (MV1) and cool (MV2)
Auto-tuning: Cold start and warm start
Self-tuning: Select NONE or YES
Failure mode: Auto-transfer to manual mode while sensor
break or A-D converter damage
Sleep mode: Enable or disable
Ramping control: 0–900.0°F/minute or 0–900.0°F/hour
ramp rate
Power limit: 0–100% output 1 and output 2
Pump/pressure control: Sophisticated functions provided
Remote set point: Programmable range for voltage or cur-
rent input
Differential control: Control PV1-PV2 at set point
Protective class: NEMA 4X (IP 65) front panel, indoor
use, IP 20 housing and terminals.
EMC: EN61326
Page 67
Chapter 9 Modbus Communications
This chapter specifies the Modbus Communications protocol as RS-232 or RS-485 interface module
is installed. Only RTU mode is supported. Data is transmitted as eight-bit binary bytes with 1 start
bit, 1 stop bit and optional parity checking (None, Even or Odd). Baud rate may be set to 2400, 4800,
9600, 14400, 19200, 28800 and 38400.
9-1 Functions Supported
Only function 03, 06 and 16 are available for this series of controllers. The message formats for each
function are described as follows:
Slave address (0-255)
Function code (3)
Starting address of register Hi (0) Byte count
Starting address of register Lo Data 1 Hi
(0-79, 128-131) Data 1 Lo
No. of words Hi (0) Data 2 Hi
No. of words Lo (1-79) Data 2 Lo
CRC16 Hi •
CRC16 Lo •
•
•
•
CRC16 Hi
CRC16 Lo
Function 06: Preset Single Register
Query: (from Master) Response: (from slave)
Slave address (0-255)
Function code (6)
Register address Hi (0)
Register address Lo (0-79, 128-131)
Data Hi
Data Lo
CRC16 Hi
CRC16 Lo
Function 16: Preset Multiple Registers
Query: ( from master ) Response: (from slave)
Slave address (0-255)
Function code (16)
Starting address of register Hi (0)
Starting address of register Lo (0-79, 128-131)
No. of words Hi (0)
No. of words Lo (1-79)
Byte count (2-158) CRC16 Hi
Data 1 Hi CRC16 Lo
Data 1 Lo
Data 2 Hi
Data 2 Lo
•
•
•
•
•
CRC16 Hi
CRC16 Lo
63
Page 68
9-2 Exception Responses
If the controller receives a message which contains a corrupted character (parity check error, framing error, etc.), or
if the CRC16 check fails, the controller ignores the message. However, if the controller receives a syntactically correct message which contains an illegal value, it will send an exception response, consisting of five bytes as follows:
slave address +offset function code + exception code + CRC16 Hi +CRC16 Lo
Where the offset function code is obtained by adding the function code with 128 (ie. function 3 becomes H'83), and
the exception code is equal to the value contained in the following table:
Exemption Code Name Cause
1 Bad Function Code Function code is not supported by the controller
2 Illegal data address Register address out of range
a read-only or protected data
3 Illegal data value
Data value out of range or attempt to write
64
Page 69
9-3 Parameter Table
65
Page 70
66
Page 71
67
Page 72
68
Page 73
69
Page 74
70
Page 75
71
Page 76
72
Page 77
73
Page 78
74
Page 79
75
Page 80
P= 100.0
RC 16
07
Lo
9-3 Communication Examples
76
Page 81
A–1 Menu Existence Conditions
77
Page 82
78
Page 83
79
Page 84
A–2 Factory Menu Description
80
Page 85
A–3 Glossary
Absolute zero: The lowest theoretical temperature. At absolute zero, a
body would have no molecular motion of heat energy. Absolute zero is
the zero point on the Rankine and Kelvin scales. (-273.15°C or -
459.67°F)
AC: Alternating Current; an electric current that reverses direction at
regularly occurring intervals.
Accuracy
Calibration accuracy: The potential error of a device compared to
a physical constant or agency standard.
Control accuracy: Maintaining a process at the desired setting. The
errors or combination of errors in the entire system including the sensor, control, power, load and design inefficiencies affect control accuracy.
Display accuracy: The amount of potential error between a measured value and the control’s displayed value.
Set point accuracy: The potential error between a measured value
and the control setting.
Alarm: A control condition or function, indicating that the process is a
predetermined amount above or below the set point.
Alpha (α): The average percent change in resistance per degree of a pure
metal resistance device between 0° and 100°C. Usually designated by the
Greek letter alpha, α with units of ohm/ohm/°C. The common alpha for
a platinum RTD is 0.00385ohm/ohm/°C.
Ambient compensation: The design of an instrument such that
changes in ambient temperature do not affect the readings of the instrument.
Ambient temperature: The average or mean temperature of the surrounding air which comes in contact with the equipment and instruments
under test.
Ampere (amp):A unit used to define the rate of flow of electricity (current) in a circuit; units are one coulomb (6.25 x 10
ond.
Analog indication: A meter with graduated scale and a pointer that
moves to indicate process condition.
Analog output: A voltage or current signal that is a continuous function of the measure parameter.
Analog set point: Potentiometer adjustment of the control setting.
ANSI: American National Standards Institute
Anti-reset windup: This is a feature in a three-mode PID controller
which prevents the integral (auto reset) circuit from functioning when
the temperature is outside the proportional band.
ASME: American Society of Mechanical Engineers.
ASTM: American Society for Testing and Materials.
Automatic reset (Integral): The integral function of a control that
automatically compensates for the difference between the set point and
the actual process temperature. A signal moves the proportional band up
or down to correct for the droop or offset error.
Automatic tuning (of control parameters): A control that calculates the optimum PID parameters with a built-in software algorithm to
eliminate manual tuning efforts.
AWG: American Wire Gauge.
Bandwidth: A symmetrical region around the set point in which propor-
tional control occurs.
Baud rate: In serial communications, the rate of information transfer in
bits per second.
18
electrons) per sec-
Blackbody: A theoretical object that radiates the maximum amount of
energy at a given temperature, and absorbs all the energy incident upon
it. A blackbody is not necessarily black. (The name blackbody was chosen because the color black is defined as the total absorption of light
[energy].)
Boiling point: The temperature at which a substance in the liquid phase
transforms to the gaseous phase; commonly refers to the boiling point of
water which is 100°C (212°F) at sea level.
Btu: British Thermal Unit. The quantity of thermal energy required to
raise one pound of water 1°F at or near its maximum density (39.1°F).
Bumpless transfer: The smooth, automatic transition from automatic
control (closed loop) to manual control (open loop). The control output
is maintained during the transfer.
Burst proportioning: A fast-cycling output form on a time proportioning controller (typically adjustable from .2 to 4 seconds) used in conjunction with a solid state relay to prolong the life of heaters by minimizing
thermal stress.
Calender-van Dusen equation: An equation that defines the resistance-temperature value of any pure metal that takes the form of
R
(1+AT+BT2) for values between the ice point (0°C) and the freez-
T=Ro
ing point of antimony (630.7°C) and the form RT=Ro[1+AT+BT2+C(T-
100)T2] between the oxygen point (-183.0°C) and the ice point (0°C).
Calibration: The process of adjusting an instrument so that the indica-
tion is accurate compared to the actual value.
Calorie: The quantity of thermal energy required to raise one gram of
water 1°C at 15°C.
Cascade: Control in which the output of a secondary or inner control
loop is the set point for a primary or outer loop. The primary loop, in
turn, determines the control action.
CE: A mark that designates compliance with European Union (EU)
requirements for products sold in Europe.
Celsius: (Centigrade) A temperature scale with 0°C defined as the ice
point and 100°C as the boiling point of water at sea level.
cfm: The volumetric flow rate of a liquid or gas in cubic feet per minute.
Chatter: The rapid cycling on and off of a relay in a control process due
to insufficient bandwidth in the controller.
Closed loop control: A control system in which process temperature
changes are detected by a sensor. The feedback from the sensor allows
the control to make adjustments for accurate system regulation.
Cold junction compensation: A temperature sensitive device that
prevents changes in the ambient temperature from affecting the cold
junction of a thermocouple.
Common mode rejection ratio: The ability of an instrument to
reject interference from a common voltage at the input terminals with
relation to ground. Expressed in dB (decibels).
Control loop: The basic control loop of any automatic control system
consists of:
1. variable (process)
2. sensor
3. error detector (of control)
4. control
5. final control element (relay, SSR, SCR)
6. temperature indication
Control mode: The method in which the control restores the system
temperature to set point. On/Off, proportional, and PID are the most
common control modes.
CT: Current Transformer
81
Page 86
Current proportioning: A 4–20 milliamp (typical) current output
which provides a current proportional to the amount of control
required.
Current transformer: A transformer, intended for measuring purposes,
designed to generate a current at its secondary winding which is proportional to the current at the primary winding.
Cycle time: The time, usually expressed in seconds, for a controller to
complete one on/off cycle.
Data logging: Recording a process variable over an extended period of
time.
DC: Direct Current; An electric current flowing in one direction and constant in value.
Dead band: 1. For chart recorders: the minimum change of input signal
required to cause a deflection in the pen position. 2. For temperature controllers: the temperature band where heat is turned off upon rising temperature and turned on upon falling temperature expressed in degrees.
The area where no heating (or cooling) takes place.
Default parameters: The parameters, or programmed instructions,
permanently stored in microprocessor software to provide a data base.
Derivative: (see Rate)
Deviation: The difference between the value of the controlled variable
and the value at which it is being controlled.
Deviation alarm: An offset value that follows the set point. If the set
point is 350°F and the deviation alarm value is +20°F, the alarm value
would be 350°F plus 20°F (or 370°F), See Process alarm.
Dielectric strength: An amount of voltage that an insulating material
can withstand before an electrical breakdown occurs.
Differential: In an on/off control, the temperature difference, expressed
in degrees, between where the control switches off and the control
switches on.
Differential control:A controller can control one process in relation to
the difference of a second process.
DIN: Deutsche Industrial Norms. A German agency that sets engineering
and dimensional standards that now has worldwide recognition.
Drift: A change in a value over a long period due to changes in factors
such as ambient temperature, time, or line voltage.
Droop: In time proportioning controls, the difference in temperature
between the set point and where the system temperature stabilizes.
Corrected by automatic or manual reset.
Dual output: The primary output will regulate the process temperature.
A secondary output will be utilized for process cooling or as an alarm.
Duty cycle: Percentage of “load ON time” relative to total cycle time.
Efficiency: The amount of useful output versus energy input.
Electrical interference: Electrical noise induced upon the signal
wires that obscures the wanted information signal.
Electromagnetic Compatibility (EMC): A system that meets three
requirements: 1. it does not cause interference with other systems, 2. it is
not susceptible to emissions from other systems and 3. it does not cause
interference with itself.
Electromagnetic Interference (EMI): An electrical and magnetic
noise which can be generated when switching inductive devices, lightning, radio wave radiation, electrostatic discharge, etc.
emf: Electromotive force. A rise in (electrical) potential energy. The
principal unit is the volt.
Emissivity: The ratio of energy emitted by an object to the energy emitted by a blackbody at the same temperature. The emissivity of an object
depends upon its material and surface texture; a polished metal surface
can have an emissivity around 0.2, and a piece of wood can have an
emissivity around 0.95.
Endothermic: Absorbs heat. A process is said to be endothermic when
it absorbs heat.
Error: The difference between the correct or desired value and the actual
reading or value taken.
Event input: A programmable On/Off input used to signal peripheral
equipment or a process.
Event output: A programmable On/Off output used to signal peripheral
equipment or a process.
Exothermic: Gives off heat. A process is said to be exothermic when it
releases heat.
Fahrenheit: A temperature scale with 32°F defined as the ice point and
212°F as the boiling point of water at sea level.
Filter: A low pass filter designed to minimize display fluctuations.
Flow rate: speed or velocity of fluid movement.
FM: Factory Mutual Research Corp. An organization which sets indus-
trial safety standards.
FM-approved: An instrument that meets a specific set of specifications
established by Factory Mutual Research Corp.
Form A: Single Pole Single Throw relay that only utilizes the N.O. and
common contacts. These contacts close when the relay coil is energized.
The contacts open when power is removed from the control.
Form B: Single Pole Single Throw relay that only utilizes the N.C. and
common contacts. These contacts will open when the relay coil is energized. The contacts will close when power is removed from the control.
Form C: Single Pole Double Throw. Utilizes the N.O., N.C. and common contacts. The user has the option of wiring for a Form A or Form B
contact. Refer to the Form A and Form B above for more information.
fpm: Flow velocity in feet per minute.
fps: Flow velocity in feet per second.
Freezing point: The temperature at which the substance goes from the
liquid phase to the solid phase.
Frequency: The number or event occurrences or cycles over a specified
period of time.
Fuse: A device that interrupts power in a circuit when an overload
occurs.
Fuzzy logic: An artificial intelligence technique that allows control
decisions to be made upon approximate or incomplete information.
Fuzzy logic is a continuous decision making function that can prevent
initial overshoot and set point differentials.
Gain: The amount of amplification used in an electrical circuit.
GIGA: The prefix for one billion (G).
gph: The volumetric flow rate in gallons per hour.
gpm: The volumetric flow rate in gallons per minute.
Ground: 1. The electrical neutral line having the same potential as the
surrounding earth. 2. The negative side of dc power supply. 3. Reference
point for an electrical system.
Grounded junction: A thermocouple junction in which the sheath and
conductors are welded together forming a completely sealed integrated
junction.
Heat: Thermal energy expressed in Calories, Btu’s or Joules.
Heat of fusion: The amount of energy required to change one pound of
a material from a solid to a liquid without an increase in temperature.
Expressed in Btu/lb.
Heat of vaporization: The amount of energy required to change one
pound of a material from a liquid to a vapor without an increase in temperature. Expressed in Btu/lb.
Heat sink: 1. Thermodynamic. A body which can absorb thermal energy. 2 Practical. A finned piece of metal used to dissipate the heat of solid
state components mounted on it.
Heat transfer: The process of thermal energy flowing from a body of
high energy to a body of low energy. Means of transfer are: conduction,
the two bodies are in contact; convection, a form of conduction where
the two bodies in contact are of different phases, i.e; solid and gas; radiation, all bodies emit infrared radiation
Heat treating: A process for treating metals where heating to a specific
temperature and cooling at a specific rate changes the properties of the
metal.
Hertz (Hz): Unit in which frequency is expressed. Synonymous with
cycles per second.
Hi-Pot test: To apply a high voltage to an electrical conductor to test
the surrounding insulation.
Hysteresis: In ON/OFF control, the temperature change necessary to
change the output from full ON to full OFF.
Hunting: Oscillation or fluctuation of process temperature between set
point and process variable.
IAE: Integrated absolute error
Ice point: The temperature at which pure water freezes. 0°C, 32°F,
273.16K.
IE: Integrated error
Impedance: The total opposition in a circuit to the flow of electrical
current. Measured in ohms and represented by “Z”.
Infrared: Or radiation is the exchange of energy by electromagnetic
waves. The infrared spectrum extends from the deep red end of the visible spectrum to the microwave region of the radio spectrum. The portion
adjacent to the visible spectrum is of importance to heating. Radiant heat
transfer can be very efficient in directing energy from the heat source to
an object.
Integral: (see Automatic Reset).
Interchangeability error: A measurement error that can occur if two
or more probes are used to make the same measurement. It is caused by
a slight variation in characteristics of different probes.
82
Page 87
Intrinsically safe: An instrument which will not produce any spark or
thermal effects under normal or abnormal conditions that will ignite a
specified gas mixture.
IPTS-68: International Practical Temperature Scale of 1968. Fixed
points in thermometry set by the 1968 General Conference of Weights
and Measures.
ISA: Instrument Society of America.
ISE: Integrated squared error
Isolation: Electrical separation
Isothermal: A process or area that maintains a constant temperature.
ITS-90: International Temperature Scale of 1990
Joule: The basic unit of thermal energy. 1 Joule equals 1 ampere passed
through a resistance of 1ohm for 1 second.
Junction: A thermocouple junction is the point at which two alloys are
joined. A typical thermocouple circuit would have a measuring and a reference junction.
Kelvin: The unit of absolute or thermodynamic temperature scale. Zero
Kelvin is absolute zero, where all molecular activity stops. No “°” symbol is used. 0°C=273.15K; 100°C=373.15K.
Kilo: The prefix for one thousand (K).
Kilowatt (kw): 1000 watts or 3412Btu per hour.
Lag: 1. A time delay between the output of a signal and the response of the
instrument to which the signal is sent. 2. A time relationship between two
waveforms where a fixed reference point on one wave occurs after the same
point of the reference wave.
Least Significant Digit (LSD): The digit farthest to the right in a display.
Linearity: The deviation of an instrument’s response from a straight
line.
Load: The electrical demand of a process expressed as power (watts),
current (amps) or resistance (ohms).
Manual reset: The adjustment on a proportional control which shifts
the proportional band in relation to the set point to eliminate droop of
offset errors.
Maximum operating temperature: The maximum temperature at
which an instrument or sensor can be safely operated.
Maximum power rating: The maximum power in watts that a device
can safely handle.
Reference junction: The cold junction in a thermocouple circuit
which is held at a stable known temperature. The standard reference temperature is 0°C (32°F); however, other temperatures can be used.
Relay (mechanical): An electromechanical device that completes or
interrupts a circuit by physically moving electrical contacts into contact
with each other.
Relay (solid state): A solid state switching device which completes or
interrupts a circuit electrically with no moving parts.
Repeatability: The ability of a probe or instrument to give the same
output or reading under repeated identical conditions.
Resistance: The resistance to the flow of electric current measured in
ohms (Ω). For a conductor, resistance is a function of diameter, resistivity (an intrinsic property of the material), and length.
Resolution sensitivity: The amount of temperature change that must
occur before the control actuates. It may be expressed in temperature or
as a percentage of the control’s scale.
Response time (Time constant): The time required by a sensor to
reach 63.2% of a step change in temperature under a specified set of conditions. Five time constants are required for the sensor to stabilize at
99.3% of the step change value.
Retransmit output: Analog output scaled to the process or the set
point value.
RFI: Radio frequency interference.
RS232 or RS485 output signal: A serial interface suitable for con-
nection between a digital control and a personal computer, a host computer, or a printer.
RTD: A temperature sensing probe of finely wound platinum wire that
displays a linear resistance change for a corresponding temperature
change. The resistance increases as the temperature rises. A base resistance of 100ohms at 32°F is the industry (DIN) standard.
Saturation temperature: The boiling temperature of a liquid at the
existing pressure.
SCFM: Volumetric flow rate in cubic feet per minute at 60°F (15°C) and
standard atmospheric pressure.
SCR: Silicone Controlled Rectifier
Secondary standard: A standard of unit measurement derived from a
primary standard.
Sensitivity: The minimum change in input signal to which an instrument can respond.
Set point: Control setting to achieve or maintain temperature.
Sheath thermocouple: A thermocouple made out of mineral-insulated
thermocouple cable which has another metal sheath.
Shield: Material surrounding a conductor(s) to prevent electrostatic or
EMI from external sources.
Slide wire feedback: A potentiometer that varies the resistance to
control a valve position.
Soak: To raise the temperature of a metal object in a heated environment
to produce a metallurgical change.
Soft start: Reduces voltage on initial start-up which reduces power to
the heaters. If heater has accumulated moisture internally during a shut
down, soft start will allow heater to dry before full voltage is applied so
as to extend heater life.
Solid State Relay (SSR): A solid state switching device which completes or breaks a circuit electrically with no moving parts.
Measuring junction: The thermocouple junction referred to as the hot
junction that is used to measure an unknown temperature.
Mechanical relay: An electromechanical device that completes or
breaks a circuit by opening or closing electrical contacts.
Mega: The prefix for one million (M).
Melting point: The temperature at which a substance transforms from
a solid phase to a liquid phase.
Micro: The prefix for one millionth.
Microamp: 10
Micron: 10
-6
amps (one millionth of an amp).
-6
meters (one millionth of a meter).
Microprocessor: The central processing unit (CPU) that performs the
logic operations in a micro-computer system. The microprocessor in a
process or instrument control decodes instructions from the stored program, performs algorithmic and logic functions, and produces signals
and commands.
Milli: The prefix for one thousandth.
Milliamp: 10
Millivolt: 10
-3
amps (one thousandth of an amp).
-3
volts (one thousandth of a volt).
NEC: National Electrical Code
NEMA: National Electrical Manufacturer’s Association
NEMA 4X: A front panel rating designating the control as washdown
capable and corrosion resistant.
NIST: National Institute of Standards and Technology, United States
Department of Commerce.
Noise: Undesirable electrical interference on the signal wires.
Noise suppression: A device used to reduce electrical interference.
Normal-mode rejection ratio: The ability of an instrument to reject
interference, usually of line frequency (50–60Hz), across its input terminals.
NPT: National Pipe Thread.
Offset: The difference in temperature between the set point and the
actual process temperature. Also referred to as droop.
ohm: The unit of electric resistance.
On/off controller: A controller whose action is fully on or fully off.
Open Loop Control: A control system with no sensing feedback.
Overshoot: Excursion of temperature above the set point.
Phase: A time-based relationship between a periodic function and a ref-
erence. In electricity, it is expressed in angular degrees to describe the
voltage or current relationship of two alternating waveforms.
Phase proportioning: A form of temperature control where the power
supplied to the process is controlled by limiting the phase angle of the
line voltage.
PID: Three mode temperature control — proportional, integral, (automatic reset), derivative(rate).
Polarity: In electricity, the quality of having two oppositely charged
poles, one positive and one negative.
Potentiometer: 1. A variable resistor often used to control a circuit. 2.
A balancing bridge used to measure voltage.
Primary standard (NBS): The standard reference units and physical
constants maintained by the National Bureau of Standards upon which
all measurement units in the United States are based.
Process alarm: A fixed alarm or secondary set point value independent of the primary set point. Should a process value exceed this value, an
alarm condition would register.
Process variable: The parameter being controlled or measured such as
temperature, relative humidity, flow, level, pressure, etc.
Proportional band: A temperature band in degrees within which a
control’s proportioning function is active.
83
Page 88
Proportional control mode: When process temperature approaches
set point and enters the proportional band, the output is switched on and
off at the established cycle time. The change in power to the load provides a throttling action which results in less temperature overshoot.
Ramp: A programmed rise or fail in temperature at a constant rate.
Range: An area between two limits in which a measurement or control
action takes place. Typically expressed in upper and lower limits.
Rankine (°R): An absolute temperature scale based upon the Fahrenheit
scale with 180° between the ice point and boiling point of water.
459.69°R=0°F.
Rate (derivative): A control function that measures the rate of increase
or decrease of the system temperature and brings the control into an
accelerated proportioning action. This mode prevents an overshoot condition at initial heat-up and with system disturbances.
Rate time: The interval over which the system temperature is sampled
for the derivative function.
Span: The difference between the upper and lower limits of a range
expressed in the same units as the range.
Specific gravity: The ratio of mass of any material to the mass of the
same volume of pure water at 4°C.
Specific Heat: The ratio of thermal energy required to raise the temperature of a particle 1 degree to the thermal energy required to raise an
equal mass of water 1 degree.
SSR: Solid state relay (see relay, solid state).
Stability: The ability of an instrument or sensor to maintain a constant
output when a constant input is applied.
Surge current: A current of short duration occurring when power is
initially applied to capacitive or resistive loads, usually lasting no more
than several cycles.
Temperature gradient: The range of temperature variations at various
physical locations throughout a thermal system.
Tera: The prefix for one trillion (T).
Thermal expansion: An increase in size due to an increase in temper-
ature expressed in units of an increase in length or increase in size per
degree, i.e., inches/inch/degree C.
Thermal lag: The time delay in the distribution of heat throughout a
thermal system.
Thermal system: A regulated environment consisting of a heat source,
heat transfer medium, sensing device and a process variable control
instrument.
Thermistor: A temperature sensing probe made of a mixture of metal
oxides and encapsulated in epoxy or glass. A large change in resistance is
exhibited proportional to a change in temperature. The resistance usually
decreases as temperature rises.
Thermocouple: A temperature sensing probe consisting of the junction
of two dissimilar metals which has a millivolt output proportional to the
difference in temperature between the “hot” junction and the lead wires
(cold junction).
Thermocouple break protection: Fail-safe operation that assures output shutdown upon an open thermocouple condition.
Thermowell: A closed-end tube designed to protect temperature sensors from harsh environments, high pressure, and flows. They can be
installed into a system by pipe thread or welded flange and are usually
made of corrosion-resistant metal or ceramic material depending upon
the application.
Transducer: A device which converts the parameter being measured
into another form which is its output. For example, a thermocouple transforms heat into a millivolt output.
Transmitter (two-wire): A device which is used to transmit temperature data from either a thermocouple or RTD via a two-wire current loop.
The loop has an external power supply and the transmitter acts as a variable resistor with respect to its input signal.
Triac: A solid state switching device used to switch alternating current
wave forms.
Triple point (water): The thermodynamic state where all three phases,
solid, liquid, and gas may all be present in equilibrium. The triple point
of water is at .01°C.
TTL: Transistor-to-transistor logic. A form of solid state logic which uses
only transistors to form the logic gates.
UL: Underwriters Laboratories, Inc. An independent laboratory that
establishes standards for commercial and industrial products.
Ultraviolet: That portion of the electromagnetic spectrum below blue
light (380 nanometers).
Undershoot: Excursion of temperature below set point.
Ungrounded junction: A thermocouple junction fully insulated from
the sheath.
Viscosity: The inherent resistance of a substance to flow
Volt: The (electrical) potential difference between two points in a circuit.
The fundamental unit is derived as work per unit charge —(V=W/Q).
One volt is the potential difference required to move one coulomb of
charge between two points in a circuit while using one joule of energy.
Voltage: An electrical potential which is measured in volts.
VPFW SSR: A type of Solid State Relay with Variable Period and Full
Wave switching characteristics.
Wattage: A measurement of electrical power. In a resistive circuit,
W=VI (see Ohms Law formulas).
Working standard: A standard of unit measurement calibrated from
either a primary or secondary standard which is used to calibrate other
devices or make comparison measurements.
Zero voltage switching: The making or breaking of a circuit timed
such that the transition occurs when the voltage waveform crosses zero
voltage; typically it is only found in solid state switching devices.
84
Page 89
A–4 Memo
he following table as a master copy for your settings.
85
Page 90
86
Page 91
A–5 Warranty
WARRANTY
Tempco Electric Heater Corporation is pleased to offer suggestions on the use of its products. However, Tempco makes no warranties or representations of any sort regarding the fitness for
use, or the application of its products by the Purchaser. The
selection, application, or use of Tempco products is the
Purchaser's responsibility. No claims will be allowed for any
damages or losses, whether direct, indirect, incidental, special, or
consequential. Specifications are subject to change without
notice. In addition, Tempco reserves the right to make changes–
without notification to the Purchaser–to materials or processing
that do not affect compliance with any applicable specification.
TEC Temperature Controllers are warranted to be free from
defects in material and workmanship for two (2) years after
delivery to the first purchaser for use. Tempco's sole responsibility under this warranty, at Tempco's option, is limited to replacement or repair, free of charge, or refund of purchase price within
the warranty period specified. This warranty does not apply to
damage resulting from transportation, alteration, misuse, or
abuse.
RETURNS
No product returns can be accepted without a completed Return
Material Authorization (RMA) form.
TECHNICAL SUPPORT
Technical questions and troubleshooting help is available from
Tempco. When calling or writing please give as much background information on the application or process as possible.
Note: Information in this manual was deemed correct at the time of printing.
The policy of Tempco is one of continuous development and product
improvement, and we reserve the right to modify specifications and designs
without prior notice. Not responsible for typographical errors.
87
Page 92
Complete Your Thermal Loop System
With Over 100,000 Various Items
Available from Stock
• Electric Heating Elements
• Thermocouples and RTD Assemblies
• SCR Power Controls
• Solid State Relays
• Mechanical Relays
• Videographic Data Recorders
• Temperature Measurement
• Current Indicators
• Thermocouple and Power Lead Wire
• Wiring Accessories
TEMPCO’s Visionary Solutions
The Electric Heating Element, Temperature Controls and