Tempco tec-220, tec-920 Instruction Manual

Page 1
Instruction Manual
TEC-220 and TEC-920 Auto-Tune Fuzzy / PID Process Temperature Controller
Serving Industry Since 1972
Agency Approvals
TEMPCO Electric Heater Corporation 607 N. Central Avenue • Wood Dale, IL 60191-1452 USA Tel: 630-350-2252 • Toll Free: 800-323-6859 Fax: 630-350-0232 • E-mail: [email protected] Web: www.tempco.com
Manual TEC-220/920 Revision 9/2016
Page 2
NOTES
Page 3
Warning Symbol
This symbol calls attention to an operating procedure, practice, or the like which, if not correctly performed or adhered to, could result in personal injury or damage to or destruction of part or all of the product and system. Do not proceed beyond a warning sym­bol until the indicated conditions are fully understood and met.
Using the Manual
Installers . . . . . . . . . . . . . . . . . . . . . . . . . . . Read Chapter 1, 2
System Designer . . . . . . . . . . . . . . . . . . . . . Read All Chapters
Expert User . . . . . . . . . . . . . . . . . . . . . . . . . Read Page 11
Contents
Page No.
Chapter 1 Overview
1-1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1-2 Ordering Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-3 Programming Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-4 Keys and Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1-5 Menu Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-6 Parameter Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . 5
Chapter 2 Installation
2-1 Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2-2 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2-3 Wiring Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2-4 Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2-5 Sensor Installation Guidelines . . . . . . . . . . . . . . . . . . . 8
2-6 Sensor Input Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2-7 Control Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . 8
2-8 Alarm Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2-9 Data Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 3 Programming
3-1 Lockout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3-2 Signal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3-3 Control Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3-4 Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3-5 Configuring the Display . . . . . . . . . . . . . . . . . . . . . . . 14
3-6 Ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3-7 Dwell Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3-8 PV Shift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3-9 Digital Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3-10 Failure Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3-11 Auto-tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3-12 Manual tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3-13 Manual Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3-14 Data communication. . . . . . . . . . . . . . . . . . . . . . . . . . 17
3-15 Process Variable (PV) Retransmission. . . . . . . . . . . . 17
Chapter 4 Applications
4-1 Heat Only Control With Dwell Timer . . . . . . . . . . . . . 19
4-2 Cool Only Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4-3 Heat-Cool Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Chapter 5 Calibration . . . . . . . . . . . . . . . . . . 21
Chapter 6 Specifications . . . . . . . . . . . . . 23
Chapter 7 Modbus Communications
7-1 Functions Supported . . . . . . . . . . . . . . . . . . . . . . . . . . 25
7-2 Exception Responses . . . . . . . . . . . . . . . . . . . . . . . . . . 26
7-3 Parameter Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
7-4 Data Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7-5 Communication Examples . . . . . . . . . . . . . . . . . . . . . . 29
Appendix
A-1 Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
A-2 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
NOTE:
It is strongly recommended that a process should incorpo­rate a LIMIT CONTROL like TEC-910 which will shut down the equipment at a preset process condition in order to preclude possible damage to products or system.
Information in this user's manual is subject to change without notice.
Copyright © 2010, Tempco Electric Heater Corporation, all rights reserved. No part of this publication may be reproduced, transmitted, transcribed or stored in a retrieval system, or trans­lated into any language in any form by any means without the written permission of Tempco Electric Heater Corporation.
Figures & Tables
Page No.
Figure 1.1 Fuzzy Control Advantage. . . . . . . . . . . . . . . . . . 1
Figure 1.2 Programming Port Overview . . . . . . . . . . . . . . . 2
Figure 1.3 Front Panel Description . . . . . . . . . . . . . . . . . . 3
Figure 1.4 Display in Initial Stage. . . . . . . . . . . . . . . . . . . . 3
Figure 2.1 Mounting Dimensions and Panel Cutout . . . . . . 7
Figure 2.2 Lead Termination for TEC-920 . . . . . . . . . . . . . 7
Figure 2.3 Lead Termination for TEC-220 . . . . . . . . . . . . . 7
Figure 2.4 Rear Terminal Connection for TEC-220 . . . . . . 8
Figure 2.5 Rear Terminal Connection for TEC-920 . . . . . . 8
Figure 2.6 Power Supply Connections . . . . . . . . . . . . . . . . 8
Figure 2.7 Sensor Input Wiring . . . . . . . . . . . . . . . . . . . . . 8
Figure 2.8 Output 1 Relay or Triac (SSR) to
Drive Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 2.9 Output 1 Relay or Triac (SSR) to
Drive Contactor . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 2.10 Output 1 Pulsed Voltage to Drive SSR . . . . . . 9
Figure 2.11 Output 1 Linear Current . . . . . . . . . . . . . . . . . . 9
Figure 2.12 Output 1 Linear Voltage . . . . . . . . . . . . . . . . . . 9
Figure 2.13 Output 2 Relay or Triac (SSR) to
Drive Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 2.14 Output 2 Relay or Triac (SSR) to
Drive Contactor . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 2.15 Output 2 Pulsed Voltage to Drive SSR . . . . . . 9
Figure 2.16 Output 2 Linear Current . . . . . . . . . . . . . . . . . . 9
Figure 2.17 Output 2 Linear Voltage . . . . . . . . . . . . . . . . . 9
Figure 2.18 Alarm Output to Drive Load . . . . . . . . . . . . . 10
Figure 2.19 Alarm Output to Drive Contactor . . . . . . . . . . 10
Figure 2.20 RS-485 Wiring . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 2.21 RS-232 Wiring . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 2.22 Configuration of RS-232 Cable . . . . . . . . . . . 10
Figure 3.1 Conversion Curve for Linear Type
Process Value . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 3.2 Heat Only ON-OFF Control . . . . . . . . . . . . . . . 12
Figure 3.3 Output 2 Deviation High Alarm . . . . . . . . . . . . 13
Figure 3.4 Output 2 Process Low Alarm . . . . . . . . . . . . . . 13
Figure 3.5 RAMP Function . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 3.6 Dwell Timer Function . . . . . . . . . . . . . . . . . . . . 14
Figure 3.7 PV Shift Application . . . . . . . . . . . . . . . . . . . . . 15
Figure 3.8 Filter Characteristics . . . . . . . . . . . . . . . . . . . . . 15
Figure 3.9 Effects of PID Adjustment . . . . . . . . . . . . . . . . 16
Figure 4.1 Heat Control Example. . . . . . . . . . . . . . . . . . . . 19
Figure 4.2 Cooling Control Example . . . . . . . . . . . . . . . . . 19
Figure 4.3 Heat-Cool Control Example . . . . . . . . . . . . . . . 20
Figure 5.1 RTD Calibration . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 5.2 Cold Junction Calibration Setup . . . . . . . . . . . . 22
Table 1.1 Display Form of Characters . . . . . . . . . . . . . . . . 3
Table 3.1 Heat-Cool Control Setup Value . . . . . . . . . . . . . 11
Table 3.2 PID Adjustment Guide . . . . . . . . . . . . . . . . . . . . 16
Table A.1 Error Codes and Corrective Actions . . . . . . . . . 30
Appendix
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Returns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Page 4
NOTES
Page 5
Chapter 1 Overview
1–1 General
Tempco’s TEC-220 and TEC-920 Fuzzy Logic plus PID micro­processor-based controllers incorporate a bright easy to read 4­digit LED display indicating process value or set point. Fuzzy Logic technology enables a process to reach a predetermined set point in the shortest time with a minimum of overshoot during power-up or external load disturbances.
The TEC-220 is a 1/32 DIN size panel mount controller. The TEC-920 is a 1/16 DIN size panel mount controller. These units are powered by 11–26 or 90–250 VDC/VAC 50/60 Hz supply, incorporating a 2 Amp control relay output as a standard. The second output can be used as a cooling control, an alarm or a dwell timer. Either output can use a triac, 5V logic output, linear current or linear voltage to drive an external device. There are six types of alarms or a dwell timer that can be configured for the second output. The units are fully programmable for PT100 RTD and thermocouple types J, K, T, E, B, R, S, N, and L with no need to modify the unit. The input signal is digitized by using an 18­bit A to D converter. Its fast sampling rate allows the unit to con­trol fast processes.
Digital communications RS-485 is available for the TEC-220 or TEC-920. RS-232 is available for the TEC-220 only. These options allow the units to be integrated with supervisory control systems and software.
A programming port is available for automatic configuration, without the need to access the keys on the front panel.
By using proprietary Fuzzy modified PID technology, the con­trol loop will minimize overshoot and undershoot in a short time. The following diagram is a comparison of results with and with­out Fuzzy technology.
High accuracy
This series is manufactured with custom designed ASIC (Application Specific Integrated Circuit) technology which contains an 18-bit A to D converter for high resolution measurement (true 0.1°F resolution for thermocouple and RTD) and a 15-bit D to A converter for linear current or voltage control output. The ASIC technology provides improved operating performance, low cost, enhanced reliability, and higher density.
Fast sampling rate
The sampling rate of the input A to D converter is 5 times/second. The fast sampling rate allows this series to control fast processes.
Fuzzy control
The function of Fuzzy control is to adjust PID parameters from time to time in order to make manipulation of the output value more flexible and adaptive to vari­ous processes. The result is to enable a process to reach a predetermined set point in the shortest time with the mini­mum of overshoot and undershoot during power-up or external load disturbance.
Digital communication
The units are equipped with an optional RS-485 or RS-232 interface cards to pro­vide digital communication. By using the twisted pair wires up to 247 units can be connected together via RS-485 interface to a host computer.
Programming port
A programming port can be used to con­nect the unit to a PC for quick configura­tion.
Auto-tune
The auto-tune function allows the user to simplify initial setup for a new system. An advanced algorithm is used to obtain an optimal set of control parameters for the process, and it can be applied either as the process is warming up (cold start) or when the process is in a steady state (warm start).
Lockout protection
Depending on security requirements, one of four lockout levels can be selected to prevent the unit from being changed without permission.
Bumpless transfer
Bumpless transfer allows the controller to continue to control if the sensor breaks by using its previous value. Hence, the process can be controlled temporarily as if the sensor reading is normal and con­stant.
Soft-start ramp
The ramping function is performed dur­ing power up as well as any time the set point is changed. It can be ramping up or ramping down. The process value will reach the set point at a predetermined constant rate.
Digital filter
A first order low pass filter with a pro­grammable time constant is used to improve the stability of the process value. This is particularly useful in certain applications where the process value is too unstable to be read.
1
Page 6
1–2 Ordering Code
1–3 Programming Port
A special connector can be used to connect the programming port to a PC for automatic configuration.
The programming port is used for off­line automatic setup and testing proce­dures only. Don't attempt to make any connection to these pins when the unit is under power.
Figure 1.2
Programming Port Overview
2
Page 7
1–4 Keys and Displays
R
KEYPAD OPERATION
SCROLL KEY:
This key is used to select a parameter to be viewed or adjusted.
UP KEY:
This key is used to increase the value of the selected parameter.
DOWN KEY:
This key is used to decrease the value of the
selected parameter.
Figure 1.3
Front Panel Description
RESET KEY: for TEC-920,
for TEC-220
This key is used to:
1. Revert the display to show the process value.
2. Reset the latching alarm, once the alarm condi­tion is removed.
3. Stop the manual control mode, auto-tuning mode, and calibration mode.
4. Clear the message of communication error and auto-tuning error.
5. Restart the dwell timer when the dwell timer has timed out.
6. Enter the manual control menu when in failure mode.
ENTER KEY: Press for 5 seconds or longer.
Press for 5 seconds to:
1. Enter setup menu. The display shows .
2. Enter manual control mode — when manual control mode or is selected.
3. Enter auto-tuning mode — when auto-tuning mode (for 220) or AT (for 920) is selected.
4. Perform calibration to a selected parameter dur­ing the calibration procedure.
Press for 6.2 seconds to select calibration mode.
Table 1.1 Display Form of Characters
Displays program code of the instrument for 2.5 seconds.
The diagram at left shows program no. 34, version 16 for the TEC-920.
The program no. is 33 for the TEC-220.
Figure 1.4
Display in Initial Stage
3
Page 8
1–5 Menu Overview
4
Page 9
1–6 Parameter Descriptions
5
Page 10
1–6 Parameter Descriptions, continued…
6
Page 11
Chapter 2 Installation
Dangerous voltages capable of causing death are some-
times present in this instrument. Before installation or beginning any troubleshooting procedures, the power to all equipment must be switched off and isolated. Units suspected of being faulty must be disconnected and removed to a properly equipped workshop for testing and repair. Component replace­ment and internal adjustments must be made by a qualified main­tenance person only.
This instrument is protected by double insulation. To
minimize the possibility of fire or shock hazards do not expose this instrument to rain or excessive moisture.
Do not use this instrument in areas under hazardous con-
ditions such as excessive shock, vibration, dirt, moisture, corrosive gases or oil. The ambient temperature of the area should not exceed the maximum rating specified in chapter 6.
Remove stains from this instrument using a soft, dry
cloth. To avoid deformation or discoloration do not use harsh chemicals, volatile solvent such as thinner or strong deter­gents to clean this instrument.
2–1 Unpacking
Upon receipt of the shipment, remove the unit from the carton and inspect the unit for shipping damage.
2–2 Mounting
Make the panel cutout according to the dimensions shown in Figure 2.1.
Take the mounting clamp away and insert the controller into the panel cutout. Reinstall the mounting clamp.
2–3 Wiring Precautions
• Before wiring, verify the correct model number and options on the label. Switch off the power while checking.
• Care must be taken to ensure that the maximum voltage rating specified on the label is not exceeded.
• It is recommended that the power for these units be protected by fuses or cir­cuit breakers rated at the minimum value possible.
• All units should be installed in a suitable enclosure to prevent live parts from being accessible to human hands and metal tools. Metal enclosures and/or subpanels should be grounded in accordance with national and local codes.
• All wiring must conform to appropriate standards of good practice and local codes and regulations. Wiring must be suitable for the voltage, current, and temperature rating of the system.
• Beware not to over-tighten the terminal screws. The torque should not exceed 1 N-m (8.9 lb-in or 10 KgF-cm).
• Unused control terminals should not be used as jumper points as they may be internally connected, causing damage to the unit.
• Verify that the ratings of the output devices and the inputs as specified are not exceeded.
• Except for thermocouple wiring, all wiring should use stranded copper con­ductor with a maximum gage of 14 AWG.
• Electrical power in industrial environments contains a certain amount of noise in the form of transient voltage and spikes. This electrical noise can adversely affect the operation of microprocessor-based controls. For this reason the use of shielded thermocouple extension wire which connects the sensor to the controller is strongly recommended. This wire is a twisted-pair construction with foil wrap and drain wire. The drain wire is to be attached to ground in the control panel only.
Note: All model TEC-220 controls are supplied with both mounting clamps and mounting screws. The mounting screws have to be used in NEMA 4X appli­cations as they allow the control to be held tighter into the panel. The mounting clamp teeth are released by depressing the ends of the clamp together.
Transit Damage
If there is any damage due to transit, report it and file a claim with the carrier. Write down the model number, serial number, and date code for future ref­erence when corresponding with our service center. The serial number (S/N) is labeled on the box and the housing of the control.
Wiring, continued…
7
Page 12
Wiring, continued…
2–4 Power Wiring
The controller is designed to operate at 11–26VAC/VDC or 90–250VAC. Check that the input voltage corresponds to the power rating indicated on the product label before connecting power to the controller.
2–5 Sensor Installation Guidelines
Proper sensor installation can eliminate many problems in a con­trol system. The probe should be placed so that it can detect any temperature change with minimal thermal lag. In a process that requires fairly constant heat output, the probe should be placed close to the heater. In a process where the heat demand is variable, the probe should be close to the work area. Some experimentation with probe location is often required to find the optimum position.
In a liquid process, the addition of a stirrer will help to eliminate thermal lag. Since the thermocouple is basically a point measur­ing device, placing more than one thermocouple in parallel can provide an average temperature readout and produce better results in most air heated processes. Proper sensor type is also a very important factor in obtaining precise measurements. The sensor must have the correct temperature range to meet the process requirements. In special processes, the sensor might have requirements such as leak-proof, anti-vibration, antiseptic, etc.
Standard sensor limits of error are ±4°F (±2°C) or 0.75% of the sensed temperature (half that for special) plus drift caused by improper protection or an over-temperature occurrence. This error is far greater than controller error and cannot be corrected on the sensor except by proper selection and replacement.
This equipment is designed for installation in an enclosure which provides adequate protection against electric shock. Metal enclosures must be connected to earth ground.
Local requirements regarding electrical installation should be rigidly observed. Consideration should be given to prevent unauthorized personnel from accessing the power terminals.
2–7 Control Output Wiring
2–6 Sensor Input Wiring
8
Page 13
Control Output Wiring, continued…
Load
120V / 240V Mains Supply
SSR
30mA/5V
Pulsed
Volta ge
Internal Circuit
+
5V
0V
33
33
_
+
+
_
5
6
10
9
TEC
220
TEC
920
Figure 2.10 Output 1 Pulsed
Voltage to Drive SSR
_
+
9
Page 14
2–8 Alarm Wiring
2–9 Data Communication
10
If you use a conventional 9-pin RS-232 cable instead of TEC99014, the cable must be modified according to the following circuit diagram.
Page 15
Chapter 3 Programming
Press for 5 seconds and release to enter the setup menu. Press and release to select the desired parameter. The display indicates the parameter symbol. Press or to view or adjust the value of the selected parameter.
3–1 Lockout
There are four security levels that can be selected using the LOCK parameter.
If NONE is selected for LOCK, then no parameter is locked.
If SET is selected for LOCK, then all setup data are locked.
If USER is selected for LOCK, then all setup data as well as
user data (refer to section 1-5) except the set point are locked to prevent them from being changed.
If ALL is selected for LOCK, then all parameters are locked to prevent them from being changed.
How to use Conversion Curve for Process Value:
If 4–20mA is selected for INPT, SL specifies the input signal low (i.e., 4mA), SH specifies the input signal high (i.e., 20mA), S specifies the current input signal value, and the conversion curve of the process value is shown as follows:
3–2 Signal Input
INPT: Selects the sensor type or signal type for signal input.
Range: (thermocouple) Type J, K, T, E, B, R, S, N, L
(RTD) PT.DN, PT.JS (Linear) 4–20 mA, 0–20 mA, 0–60 mA, 0–1V, 0–5V, 1–5V, 0–10V
UNIT: Selects the process unit
Range: °C, °F, PU (process unit). If the unit is set for
neither °C nor °F, then it defaults to PU.
DP: Selects the resolution of process value.
Range: (For T/C and RTD) NO.DP, 1-DP
(For linear) NO.DP, 1-DP, 2-DP, 3-DP
INLO: Selects the low scale value for the linear type input.
INHI: Selects the high scale value for the linear type input.
SL = Setpoint Low Limit SH = Setpoint High Limit
3–3 Control Outputs
There are four kinds of control modes that can be configured as shown in table 3.1.
11
Page 16
Control Outputs, continued…
Heat only ON-OFF control: Select REVR for OUT1. Set PB (Proportional Band) to 0. O1HY is used to adjust dead band for ON-OFF control. The output 1 hysteresis (O1HY) is enabled when PB=0. The heat only on-off control function is shown in the following diagram:
The ON-OFF control may introduce excessive process oscillation even if hysteresis is minimized. If ON-OFF control is set (i.e., PB=0), TI, TD, CYC1, OFST, CYC2, CPB, and DB will be hid­den and have no function in the system. The auto-tuning and bumpless transfer function will be disabled as well.
Heat only P (or PD) control: Select H.TPC or H.L I N for OUT1 and set TI1 and TI2 to 0, OFST is used to adjust the control offset (manual reset). O1HY is hidden if PB is not equal to 0.
OFST function: OFST is measured in % with a range of 0–
100.0%.
In a steady state (i.e. process has stabilized at a temperature), if the process value is lower than the set point by a constant value (we’ll say 5°C) while the PB setting is set for 20°C, we can say the temperature is lower than the setpoint by 25% of the PB set­ting. This can be corrected by increasing the OFST setting to 25%. After adjusting the OFST value, the process value will eventually coincide with set point.
Note that using the P control (TI set to 0), disables auto-tuning.
Refer to Section 3-12 “manual tuning” for the adjustment of P and PD. Manual reset (adjust OFST) is sometimes not practical since the load may change from time to time and OFST may need to be adjusted repeatedly. PID control can avoid this situation.
Heat only PID control: If REVR is selected for OUT1, PB and TI should not be zero. Perform auto-tuning for the new process, or set PB, TI, and TD with historical values. See section 3-11 for auto-tuning operation. If the control result is still unsatisfactory, then use manual tuning to improve control. See section 3-12 for manual tuning. The unit contains an advanced PID and Fuzzy algorithm to create a small overshoot and very quick response to the process if it is properly tuned.
Cool only control: ON-OFF control, P (PD) control, and PID control can be used for cool control. Set OUT1 to DIRT (direct action). The other functions for cool only ON-OFF control, cool only P (PD) control, and cool only PID control are the same as for heat only control except that the output variable (and action) for cool control is inverse to heat control.
NOTE: ON-OFF control may result in excessive overshoot and undershoot problems in the process. P (or PD) control will result in a deviation of process value from the set point. It is recom­mended to use PID control for heat-cool control to produce a sta­ble and zero offset process value.
Other setup required: O1TY, CYC1, O2TY, CYC2, O1FT and O2FT are set in accordance with the types of OUT1 and OUT2 installed. CYC1 and CYC2 are selected according to the output 1 type (O1TY) and output 2 type (O2TY). Generally, select 0.5~2 seconds for CYC1 if SSRD or SSR is used for O1TY; 10~20 sec­onds if relay is used for O1TY and CYC1 is ignored if linear out­put is used. Similar conditions are applied for CYC2 selection.
You can use the auto-tuning program for the new process or directly set the appropriate values for PB, TI, and TD according to historical records for duplicate systems. If the control behavior is still inadequate, then use manual tuning to improve the control. See section 3-12 for manual tuning.
CPB (Cooling Proportional Band) Programming: The cooling proportional band is measured by % of PB with a range of 50-300. Initially set 100% for CPB and examine the cooling effect. If the cooling action should be enhanced, then decrease CPB, if the cooling action is too strong, then increase CPB. The value of CPB is related to PB and its value remains unchanged throughout the auto-tuning procedures.
Adjustment of CPB is related to the cooling medium used. If air is used as the cooling medium, initially set CPB to 100%, then adjust as necessary. If oil is used as the cooling medium, initially set CPB to 125%, then adjust as necessary. If water is used as the cooling medium, initially set CPB to 250%, then adjust as necessary.
DB (Heating-Cooling Dead Band) programming: The adjust­ment of DB is dependent on the system requirements. If a more positive value of DB (greater dead band) is used, an unwanted cooling action can be avoided but an excessive overshoot over the set point will occur. If a more negative value of DB (greater over­lap) is used, an excessive overshoot over the set point can be min­imized, but an unwanted cooling action will occur. It is adjustable in the range -36.0% to 36.0% of PB. A negative DB value shows an overlap area over which both outputs are active. A positive DB value shows a dead band area over which neither output is active.
Output 2 ON-OFF control (alarm function): Output 2 can also be configured with an alarm function. There are six kinds of alarm functions that can be selected for output 2. These are:
DE.HI (deviation high alarm), DE.LO (deviation low alarm), DB.HI (deviation band out of band alarm), DB.LO (deviation
band in band alarm), PV.HI (process high alarm), and PV.LO (process low alarm). Refer to figure 3.3 and figure 3.4 for descriptions of the deviation alarm and the process alarm.
12
Page 17
3.3 & 3.4 Alarm Figures
3–4 Alarm
Output 2 can be set as an alarm output. There are six types of alarm functions and one dwell timer that can be selected, and four kinds of alarm modes (ALMD) are available for each alarm function.
A process alarm sets two absolute trigger levels. When the process value is higher than SP2, a process high alarm (PV.HI) occurs. The alarm is off when the process value is lower than SP2-ALHY. When the process value is lower than SP2, a process low alarm (PV.LO) occurs, and the alarm is off when the process value is higher than SP2+ALHY. A process alarm is independent of the set point.
A deviation alarm alerts the user when the process value deviates too far from the set point. When the process value is higher than SV+SP2, a deviation high alarm (DE.HI) occurs, and the alarm is off when the process value is lower than SV+SP2-ALHY. When the process value is lower than SV+SP2, a deviation low alarm (DE.LO) occurs, and the alarm is off when the process value is higher than SV+SP2+ALHY. The trigger level of the deviation alarm moves with the set point.
A deviation band alarm presets two trigger levels relative to the set point. The two trigger levels are SV+SP2 and SV­SP2 for alarm. When the process value is higher than (SV+SP2) or lower than (SV-SP2), a deviation band high alarm (DB.HI) occurs. When the process value is within the trigger levels, a deviation band low alarm (DB.LO) occurs.
There are four types of alarm modes available for each alarm function. These are: normal alarm, latching alarm, holding alarm and latching/holding alarm. They are described as fol­lows:
Normal alarm: ALMD=NORM
When a normal alarm is selected, the alarm output is de-ener­gized in the non-alarm condition and energized in an alarm condition.
Latching alarm: ALMD=LTCH
If a latching alarm is selected, once the alarm output is ener­gized, it will remain unchanged even if the alarm condition is cleared. The latching alarm is reset when the RESET key is pressed after the alarm condition is removed.
Holding alarm: ALMD=HOLD
A holding alarm prevents an alarm when the control is pow­ering up. The alarm is enabled only when the process reaches the set point value. Afterwards, the alarm performs the same function as a normal alarm.
Latching/holding alarm: ALMD=LT.HO
A latching/holding alarm performs both holding and latching functions. The latching alarm is reset when the RESET key is pressed after the alarm condition is removed.
Alarm failure transfer is activated as the unit enters failure mode. The alarm will go on if ALFT is set for ON and go off if ALFT is set for OFF. The unit will enter failure mode when a sensor break occurs or if the A-D converter of the unit fails.
13
Page 18
3–5 Configuring the Display
The TEC-220 can be configured to display the process value by selecting PV for DISP or to display the set point value by select­ing SP1 for DISP.
If LOCK is set to NONE, OUT2 is set to DEHI, and DISP is set to PV, set SEL1=SHIF, SEL2=ADDR. SEL3=PB, SEL4~SEL8=NONE, then the display scrolling for the TEC-220 will become:
If LOCK is set to NONE, OUT1 is set to REVR, a non-zero value is set for PB and TI, OUT2 is set to COOL, and DISP is set to SP1, set SEL1=INPT, SEL2=PB, SEL3=TI, SEL4~SEL8= NONE, then the display scrolling for the TEC-220 will become:
Example for TEC-920:
Set OUT2=PVLO, LOCK=NONE, SEL1=INPT, SEL2=UNIT, SEL3=DP, SEL4~SEL8=NONE, then the display scrolling for the TEC-920 will become:
Note: When the ramp function is used, the lower display will show the current ramping value. The ramping value is an artifi­cially determined setpoint created and updated by the control to match the ramp rate set by the user. However, it will revert to show the set point value as soon as the up or down key is touched for adjustment. The ramping value is initiated to process value either on power-up or when RR and/or the set point are changed. Setting RR to zero means no ramp function.
3–7 Dwell Timer
Output 2 can be configured as a dwell timer by selecting TIMR for OUT2. As the dwell timer is configured, the parameter SP2 is used for dwell time adjustment. The dwell time is measured in minutes ranging from 0.1 to 4553.6 minutes. Once the process reaches the set point the dwell timer starts to count down to zero (time out). The timer relay will remain unchanged until time out. The dwell timer operation is shown in the following diagram.
After time out, the dwell timer can be restarted by pressing the RESET key.
The timer stops counting during manual control mode, failure mode, the calibration period and the auto-tuning period.
3–6 Ramp
Ramp
The ramping function is performed during power up as well as any time the set point is changed. If MINR or HRR is chosen for RAMP, the unit will perform the ramping function. The ramp rate is programmed by adjusting RR. The ramping function is dis­abled as soon as failure mode, manual control mode, auto-tuning mode or calibration mode is entered.
Example without dwell timer
Select MINR for RAMP, select °C for UNIT, select 1-DP for DP, set RR=10.0. SV is set to 200°C initially, and changed to 100°C 30 minutes after power-up. The starting temperature is 30°C. After power-up, the process runs like the curve shown in Figure 3.5.
14
If output 2 is configured as a dwell timer, ALMD will be hidden.
Page 19
3–8 PV Shift
In certain applications it is desirable to shift the controller display value from its actual value. This can easily be accomplished by using the PV shift function.
The SHIF function will alter PV only.
Here is an Example: A process is equipped with a heater, a sensor, and a subject to be warmed up. Due to the design and position of the components in the system, the sensor could not be placed any closer to the part. Thermal gradient (differing temperatures) is common and necessary to an extent in any ther­mal system for heat to be transferred from one point to another. If the difference between the sensor and the subject is 35°C, and the desired temperature at the subject to be heated is 200°C, the controlling value or the temperature at the sensor should be 235°C. You should enter -35°C to subtract 35°C from the actual process display. This in turn will cause the controller to energize the load and bring the process display up to the set point value.
3–9 Digital Filter
In certain applications, the process value is too unstable to be read due to possible electrical noise. A programmable low-pass filter incorpo­rated in the controller can be used to improve this. It is a first-order filter with the time constant specified by the FILT parameter. The default value of FILT is set at 0.5 seconds before shipping. Adjust FILT to change the time constant from 0 to 60 seconds. 0 seconds means no filter is applied to the input signal. The filter is characterized in Figure 3.8.
Note
The filter is available only for PV, and is performed for the displayed value only. The controller is designed to use unfiltered signal for con­trol even if the filter is applied. A lagged (filtered) signal, if used for control, may produce an unstable process.
3–10 Failure Transfer
The controller will enter failure mode if one of the following conditions occurs:
1. SBER occurs due to input sensor break
or input current below 1mA if 4–20 mA is selected or input voltage below 0.25V if 1–5V is selected.
2. ADER occurs due to the A-D converter
of the controller failing.
Output 1 and output 2 will perform the fail­ure transfer function as the controller enters failure mode.
Output 1 failure transfer, if activated, will perform:
1. If output 1 is configured as proportional control (PB≠ 0), and BPLS is selected for O1FT, then output 1 will perform bumpless transfer. Thereafter, the previ­ous averaging value of MV1 will be used for controlling output 1.
2. If output 1 is configured as proportional control (PB≠ 0), and a value of 0 to
100.0% is set for O1FT, then output 1 will perform failure transfer. Thereafter, the value of O1FT will be used for con­trolling output 1.
3. If output 1 is configured as ON-OFF control (PB=0), then output 1 will be driven OFF if OFF is set for O1FT and will be driven ON if ON is set for O1FT.
Output 2 failure transfer, if activated, will perform:
1. If OUT2 is configured as COOL, and BPLS is selected for O1FT, then output 2 will perform bumpless transfer. Thereafter, the previous averaging value of MV2 will be used for control­ling output 2.
2. If OUT2 is configured as COOL, and a value of 0 to 100.0% is set for O2FT, then output 2 will perform failure trans­fer. Thereafter, the value of O1FT will be used for controlling output 2.
3. If OUT2 is configured as alarm func­tion, and O2FT is set to OFF, then out­put 2 will go off. Otherwise, output 2 will go on if O2FT is set to ON.
15
Page 20
3–11 Auto-tuning
For best results the auto-tuning process should be
performed near the set point. The process will oscil­late around the set point during the tuning process. Set the set point at a lower value if overshooting beyond the normal process value is likely to cause damage.
Auto-tuning is applied in cases of:
• Initial setup for a new process
• The set point is changed substantially from the previous auto-tuning value
• The control result is unsatisfactory
Operation:
1. Do not set a zero value for PB and TI, or the auto-tuning pro­gram will be disabled. The LOCK parameter should also be set at NONE.
2. Set the set point to a normal operating value, or a lower value if overshooting beyond the normal process value is likely to cause damage.
3. Press several times until appears on the display (for TEC-220), or an AT indicator on lower-right of screen is lit (for TEC-920).
4. Press and hold for at least 5 seconds. The AT indicator (for TEC-920) or the display (for TEC-220) will begin to flash indicating the auto-tuning procedure has begun.
NOTE: The ramping function, if used, will be disabled while
auto-tuning is taking place.
Auto-tuning mode is disabled as soon as either failure mode or manual control mode is entered.
Procedures:
Auto-tuning can be applied either as the process is warming up (cold start), or when the process has been in a steady state (warm start). After the auto-tuning procedures are completed, the AT indicator will cease to flash and the unit will revert to PID control using its new PID values. The PID values obtained are stored in the nonvolatile memory.
3–12 Manual Tuning
In certain applications auto-tuning may be inadequate for the control requirements. You can try manual tuning for these applications.
If the control performance using auto-tuning is still unsatisfac­tory, the following rules can be applied for further adjustment of PID values:
Figure 3.9 shows the effects of PID
adjustment on process response.
Auto-Tuning Error
If auto-tuning fails an ATER message will appear on the display in the following cases:
• If PB exceeds 9000 (9000 PU, 900.0°F or 500.0°C),
• if TI exceeds 1000 seconds,
• if the set point is changed during the auto-tuning procedure.
Solutions to
1. Try auto-tuning again.
2. Don't change the set point value during the auto-tuning proce-
dure.
3. Don't set a zero value for PB and TI.
4. Use manual tuning instead of auto-tuning (see section 3-12).
5. Touch RESET key to reset message.
16
Page 21
3–13 Manual Control
R
Operation:
To enable manual control, the LOCK parameter should be set to NONE.
Press several times; (heating output) or (cooling output) will appear on the display. Press and hold for 5 seconds or until the MAN indicator (for TEC-920) or the dis­play (for TEC-220) begins to flash. The controller is now in man­ual control mode. indicates output control variable for output 1, and indicates control variable for output 2. Now you can use the up and down keys to adjust the percentage values for the heating or cooling output.
The controller performs open loop control as long as it stays in manual control mode.
Exit Manual Control
Model TEC-920: Pressing the key will cause the controller to revert to its normal display mode.
Model TEC-220: Press and release the up and down buttons.
3–14 Data Communication
The controllers support RTU mode of Modbus protocol for data communication. Other protocols are not available for this series.
Two types of interface are available for data communication. These are RS-485 and RS-232. Since RS-485 uses a differential architecture to drive and sense signal instead of a single-ended architecture like the one used for RS-232, RS-485 is less sensi­tive to noise and more suitable for communication over a longer distance. RS-485 can communicate without error over a 1km dis­tance while RS-232 is not recommended for a distance of over 60 feet (20 meters).
Using a PC for data communication is the most economical method. The signal is transmitted and received through the PC communication port (generally RS-232). Since a standard PC can't support an RS-485 port, a network adapter (such as TEC99001) has to be used to convert RS-485 to RS-232 for a PC if RS-485 is required for data communication. Up to 247 RS-485 units can be connected to one RS-232 port; therefore a PC with four comm ports can communicate with 988 units.
3–15 Process Variable (PV)
Retransmission
The TEC-220 controller can output (retransmit) a process value via its retransmission terminals RE+ and RE- provided that the retransmission option is ordered. The correct signal type should be selected for COMM parameter to meet the retransmission option installed. RELO and REHI are set to specify the low scale and high scale values of retransmission.
The TEC-920 does not have this feature.
Setup
Enter the setup menu. Select RTU for COMM. Set individual addresses for any units that are connected to the same port. Set the baud rate (BAUD), data bit (DATA), parity bit (PARI) and stop bit (STOP) so that these values are accordant with PC setup conditions.
If you use a conventional 9-pin RS-232 cable instead of TEC99014, the cable should be modified for proper operation of RS-232 communication according to section 2-9 on page 10.
Refer to Chapter 7 for a complete technical description of the Modbus Communications Protocol.
17
Page 22
NOTES
18
Page 23
Chapter 4 Applications
4–1 Heat Only Control with Dwell Timer
An oven is designed to dry products at 150°C for 30 minutes and then stay unpowered for another batch. A TEC-920 equipped with dwell timer is used for this purpose. The system diagram is shown at right:
To achieve this function, set the following parame­ters in the setup menu:
INPT=K_TC UNIT=°C DP=1_DP OUT1=REVR O1TY=RELY CYC1=18.0 O1FT=BPLS OUT2=TIMR O2FT=ON
Auto-tuning is performed at 150°C for a new oven.
4–2 Cool Only Control
A TEC-920 is used to control a refrigerator at temperatures below 0°C. This temperature is lower than the ambient, so a cooling action is required. Select DIRT for OUT1. Since output 1 is used to drive a magnetic contactor, the O1TY should be set for RELY. A small temperature oscillation is tolerable, so use ON-OFF control to reduce the over-all cost. To use ON-OFF control, set PB to zero and O1HY at 0.1°C.
19
Page 24
4–3 Heat-Cool Control
An injection mold is required to be controlled at 120°C to ensure a consistent quality for the parts. An oil pipe is buried in the mold. Since plastics are injected at a higher temperature (e.g., 250°C), the circulation oil needs to be cooled as its temperature rises. Here is an example:
The PID heat-cool operation is used for the above example. To achieve this, set the following parameters in the setup menu:
INPT=PT.DN UNIT=°C DP= 1-DP OUT1=REVR O1TY=RELY CYC1=18.0 (sec.) O1FT=BPLS OUT2=COOL O2TY=4–20 O2FT=BPLS
Set SV at 120.0°C, CPB at 125(%) and DB at -4.0(%).
Apply auto-tuning at 120°C for a new system to get optimal PID values. See section 3-11.
Adjustment of CPB is related to the cooling medium used. If water is used as the cooling medium instead of oil, the CPB should be set at 250(%). If air is used as the cooling medium instead of oil, the CPB should be set at 100(%). The adjustment of DB is dependent on the system requirements. A higher positive value of DB will prevent unwanted cooling action, but will increase the temperature overshoot, while a lower negative value of DB will result in less temperature overshoot, but will increase unwanted cooling action.
20
Page 25
Chapter 5 Calibration
Do not proceed through this section unless there is a def-
inite need to recalibrate the controller. If you recalibrate, all previous calibration data will be lost. Do not attempt recali­bration unless you have the appropriate calibration equipment. If the calibration data is lost, you will need to return the controller to your supplier who may charge you a service fee to recalibrate the controller.
Entering calibration mode will break the control loop.
Make sure that the system is ready to enter calibration mode.
Equipment needed for calibration:
1. A high-accuracy calibrator (Fluke 552A calibrator
recommended) with the following functions: 0–100mV millivolt source with ±0.005% accuracy 0–10V voltage source with ±0.005% accuracy 0–20mA current source with ±0.005% accuracy 0–300 ohm resistant source with ±0.005% accuracy
2. A test chamber providing 25°C–50°C temperature range
3. A switching network (SWU16K, optional for automatic
calibration)
4. A calibration fixture equipped with programming units
(optional for automatic calibration)
The calibration procedure described in the following section is a step-by-step manual procedure.
Manual Calibration Procedures
• Perform step 1 to enter calibration mode.
Step 1.
Set the lock parameter to the unlocked condition (LOCK=NONE).
Press and hold the scroll key until appears on the dis­play, then release the scroll key.
Press the scroll key for 2 seconds, and the display will show
and the unit will enter the calibration mode.
• Perform step 2 to calibrate zero of A to D converter and step 3 to calibrate gain of A to D converter.
Step 2.
Short the thermocouple input terminals, then press the scroll key for at least 5 seconds. The display will blink for a moment until a new value is obtained. If the display didn't blink or if the obtained value is equal to -199.9 or 199.9, then calibration failed.
Step 3.
Press scroll key until the display shows . Send a 60mV signal to the thermocouple input terminals in the correct polarity. Press the scroll key for at least 3 seconds. The display will blink for a moment and a new value is obtained. If the display didn't blink or if the obtained value is equal to -199.9 or 199.9, then the calibration failed.
• Perform both steps 4 and 5 to calibrate RTD function (if required) for input.
Step 4.
Press scroll key until the display shows . Send a 100 ohms signal to the RTD input terminals according to the connec­tion shown below:
Press scroll key for at least 5 seconds. The display will blink for a moment; if it does not this calibration failed.
Step 5.
Press the scroll key and the display will show . Change the ohm's value to 300 ohms. Press the scroll key for at least 5 seconds. The display will blink for a moment and two values will be obtained for RTDH and RTDL (step 4). If the display didn't blink or if any value obtained for RTDH or RTDL is equal to -199.9 or 199.9, then calibration failed.
• Perform step 6 to calibrate offset of cold junction compen­sation, if required.
21
Page 26
Manual Calibration Procedures, continued…
Step 6.
Set up the equipment according to the diagram above for calibrating the cold junction compensation. Note that a K type thermocouple must be used.
The 525A calibrator is configured as K type thermocouple output with internal compensation. Send a 0.00°C signal to the unit under calibration.
The unit under calibration is powered in a still-air room with temperature 25±3°C. Wait at least 20 minutes for warming up. Perform step 1 as stated above, then press the scroll key until the display shows .
Press the scroll key for at least 5 seconds. The display will blink for a moment until a new value is obtained. If the display didn't blink or if the obtained value is equal to –5.00 or 40.00, then calibration failed.
• Perform step 7 to calibrate gain of cold junction compensation if required.
Step 7.
Setup the equipment same as step 6. The unit under calibration is powered in a still-air room with temperature 50 ±3°C. Wait at least 20 minutes for warming up. The calibrator source is set at 0.00°C with internal compen­sation mode.
Perform step as 1 stated above, then press the scroll key until the display shows . Press the scroll key for at least 5 seconds. The display will blink for a moment until a new value is obtained. If the display didn't blink or if the obtained value is equal to –199.9 or 199.9, then calibration failed.
This setup is performed in a high-temperature chamber, therefore it is rec­ommended to use a computer to perform the procedures.
• Input modification and recalibration procedures for a linear voltage or a linear current input:
1. Remove R60(3.3K) and install two 1/4W resistors RA and RB on the
control board with the recommended values specified in the following table.
Low temperature coefficient resistors should be used for RA and RB.
2. Perform step 1 and step 2 to calibrate the linear input zero.
3. Perform step 3 but send a span signal to the input terminals instead of
60mV. The span signal is 1V for 0~1V input, 5V for 0~5V or 1~5V input, 10V for 0~10V input and 20mA for 0~20mA or 4~20mA input.
• Final step
Step 8.
Set the LOCK value to your desired function.
22
Page 27
Chapter 6 Specifications
Power
90–250VAC, 47–63 Hz, 10VA, 5W maximum
11–26VAC/VDC, 10VA, 5W maximum
Input
Resolution: 18 bits Sampling rate: 5 times/second Maximum rating: -2VDC minimum, 12VDC maximum
(1 minute for mA input)
Temperature effect: ±1.5uV/°C for all inputs except mA
input ±3.0uV/°C for mA input
Sensor lead resistance effect:
T/C: 0.2uV/ohm 3-wire RTD: 2.6°C/ohm of resistance difference of two leads 2-wire RTD: 2.6°C/ohm of resistance sum of two leads
Common mode rejection ratio (CMRR): 120dB Normal mode rejection ratio (NMRR): 55dB Sensor break detection:
Sensor open for TC, RTD and mV inputs, Sensor short for RTD input, Below 1mA for 4–20mA input, Below 0.25V for 1–5V input, unavailable for other inputs.
Sensor break responding time:
Within 4 seconds for TC, RTD, and mV inputs, 0.1 second for 4–20mA and 1–5V inputs.
Output 1/Output 2
Relay rating: 2A/240VAC, 200,000 life cycles for
resistive load
Pulsed voltage: Source voltage 5V, current limiting
resistance 66Ω.
Linear Output
Resolution: 15 bits
Output regulation: 0.02% for full load change
Output settling time: 0.1 sec. (stable to 99.9 %)
Isolation breakdown voltage: 1000VAC
Temperature effect: ±0.01% of SPAN/°C
Triac (SSR) Output
Rating: 1A/240 VAC
Inrush current: 20A for 1 cycle
Min. load current: 50mA rms
Max. off-state leakage: 3mA rms
Max. on-state voltage: 1.5VAC rms
Insulation resistance: 1000MΩ min. at 500 VDC
Dielectric strength: 2500VAC for 1 minute
23
Page 28
Specifications, continued…
Output 2 functions: Dwell timer
Deviation high/low alarm Deviation band high/low alarm PV high/low alarm PID cooling control
Alarm modes: Normal, latching, hold, latching/hold.
Dwell timer: 0.1–4553.6 minutes
Data Communication
Interface: RS-232 (1 unit), RS-485 (up to 247 units)
Protocol: Modbus protocol RTU mode
Address: 1–247
Baud rate: 0.3 - 38.4Kbits/sec
Data bits: 7 or 8 bits
Parity bit: None, even or odd
Stop bit: 1 or 2 bits
Communication buffer: 160 bytes
Analog Retransmission
Output Signal: 4-20 mA, 0-20 mA, 0-5V, 1-5V, 0-10V
Resolution: 15 bits
Accuracy: ±0.05% of span ±0.0025%/°C
Load Resistance: 0-500 ohms (for current output)
10K ohms minimum (for voltage output)
Output Regulation: 0.01% for full load change)
Digital Filter
Function: First order
Time constant: 0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 seconds
programmable
Environmental and Physical
Operating temperature: 14°F (-10°C) to 122°F (50°C)
Storage temperature: -40°F (-40°C) to 140°F (60°C)
Humidity: 0 to 90% RH (non-condensing)
Insulation resistance: 20Mohms min. (at 500VDC)
Dielectric strength: 2000VAC, 50/60 Hz for 1 minute
Vibration resistance: 10–55 Hz, 10 m/s≈ for 2 hours
Shock resistance: 200m/s ≈ (20g)
Moldings: Flame retardant polycarbonate
Dimensions:
TEC-220 — 1-3/64" (26.5 mm) H × 2" (50 mm) W
× 4-3/8" (110.5 mm) D
Depth behind panel: 3-7/8" (98 mm)
TEC-920 — 1-7/8" (48 mm) H × 1-7/8" (48 mm) W
× 3-3/4" (94 mm) D
Depth behind panel: 3-3/8" (86 mm)
Weight: TEC-220—.26 lbs. (120 grams)
TEC-920—.31 lbs. (140 grams)
User Interface
Single 4-digit LED display
Keypad: 3 keys for TEC-220, 4 keys for TEC-920
Programming port: For automatic setup, calibration, and
testing
Communication port: Connection to PC for supervisory
control
Control Mode
Output 1: Reverse (heating) or direct (cooling) action
Output 2: PID cooling control, cooling P band 50~300% of
PB, dead band -36.0-36.0% of PB
ON-OFF: 0.1-90.0 (°F) hysteresis control (P band=0)
P or PD: 0–100.0% offset adjustment
PID: Fuzzy logic modified
Proportional band 0.1-900.0°F Integral time 0–1000 seconds Derivative time 0–360.0 seconds
Cycle time: 0.1–90.0 seconds
Manual control: Heat (MV1) and cool (MV2)
Auto-tuning: Cold start and warm start
Failure mode: Auto-transfer to manual mode while sensor
break or A-D converter damage
Ramping control: 0–900.0°F/minute or
0–900.0°F/hour ramp rate
Approval Standards
Safety: UL61010C-1
CSA C22.2 No. 24-93 EN61010-1 (IEC1010-1)
Protective class:
IP65 front panel for TEC-220 IP30 front panel for TEC-920, all indoor use IP20 for terminals and housing with protective cover. All indoor use.
EMC: EN61326
24
Page 29
Chapter 7 Modbus Communications
This chapter specifies the Modbus Communications protocol as RS-232 or RS-485 interface module is installed. Only RTU mode is supported. Data is transmitted as eight-bit binary bytes with 1 start bit, 1 stop bit and optional parity checking (None, Even or Odd). Baud rate may be set to 2400, 4800, 9600, 14400, 19200, 28800 and 38400.
7-1 Functions Supported
Only function 03, 06 and 16 are available for this series of controllers. The message formats for each function are described as follows:
Function 03: Read Holding Registers
Query: (from Master) Response: (from Slave)
Slave address (0-255) Function code (3) Starting address of register Hi (0) Byte count Starting address of register Lo Data 1 Hi
(0-79, 128-131) Data 1 Lo No. of words Hi (0) Data 2 Hi No. of words Lo (1-79) Data 2 Lo CRC16 Hi • CRC16 Lo •
•
•
•
CRC16 Hi
CRC16 Lo
Function 06: Preset Single Register Query: (from Master) Response: (from slave)
Slave address (0-255) Function code (6) Register address Hi (0) Register address Lo (0-79, 128-131) Data Hi Data Lo CRC16 Hi CRC16 Lo
Function 16: Preset Multiple Registers
Query: ( from master ) Response: (from slave)
Slave address (0-255) Function code (16) Starting address of register Hi (0) Starting address of register Lo (0-79, 128-131) No. of words Hi (0) No. of words Lo (1-79) Byte count (2-158) CRC16 Hi Data 1 Hi CRC16 Lo Data 1 Lo Data 2 Hi Data 2 Lo
•
•
•
•
•
CRC16 Hi CRC16 Lo
25
Page 30
7-2 Exception Responses
If the controller receives a message which contains a corrupted character (parity check error, framing error etc.), or if the CRC16 check fails, the controller ignores the message. However, if the controller receives a syntactically correct message which contains an illegal value, it will send an exception response, consisting of five bytes as follows:
slave address +offset function code + exception code + CRC16 Hi +CRC16 Lo
Where the offset function code is obtained by adding the function code with 128 (ie. function 3 becomes H'83), and the exception code is equal to the value contained in the following table:
Exemption Code Name Cause
1 Bad Function Code Function code is not supported by the controller
2 Illegal data address Register address out of range
3 Illegal data value
Data value out of range or attempt to write
a read-only or protected data
7-3 Parameter Table
Register Parameter Parameter Scale Scale Notes
Address Notation Low High
0 SP1 Set Point 1 *4 *4 R/W
1 SP2 Set Point 2 *7 *7 R/W
2 SP3 Set Point 3 *6 *6 R/W
3 LOCK Lock code 0 65535 R/W
4 INPT Input sensor selection 0 65535 R/W
5 UNIT Measuring unit 0 65535 R/W
6 DP Decimal point position 0 65535 R/W
7 INLO Low scale value for linear input *4 *4 R/W
8 INHI High scale value for linear input *4 *4 R/W
9 SP1L Low limit of SP1 *4 *4 R/W
10 SP1H High Limit of SP1 *4 *4 R/W
11 SHIF PV shift value *4 *4 R/W
12 FILT Filter time constant 0 65535 R/W
13 DISP Display form 0 65535 R/W
14 PB P (proportional) band *5 *5 R/W
15 TI Integral time 0 65535 R/W
16 TD Derivative time 0.0 6553.5 R/W
17 OUT1 Output 1 function 0 65535 R/W
18 O1TY Output 1 signal type 0 65535 R/W
19 O1FT Output 1 failure transfer -1999.9 4553.6 R/W
20 O1HY Output 1 ON-OFF hysteresis *5 *5 R/W
21 CYC1 Output 1 cycle time 0.0 6553.5 R/W
22 OFST Offset value for P control 0.0 6553.5 R/W
23 RAMP Ramp function 0 65535 R/W
24 RR Ramp rate *5 *5 R/W
25 OUT2 Output 2 function 0 65535 R/W
26 RELO Retransmission low scale value *4 *4 R/W
27 O2TY Output 2 signal type 0 65535 R/W
28 O2FT Output 2 failure transfer -1999.9 4553.6 R/W
29 O2HY Output 2 ON-OFF hysteresis *5 *5 R/W
30 CYC2 Output 2 cycle time 0.0 6553.5 R/W
31 CPB Cooling P band 0 65535 R/W
32 DB Heating-cooling dead band -1999.9 4553.6 R/W
26
Page 31
Register Parameter Parameter Scale Scale Notes
Address Notation Low High
33 ALFN Alarm Function 0 65535 R/W
34 REHI Retransmission high scale value *4 *4 R/W
35 ALMD Alarm operation mode 0 65535 R/W
36 ALHY Alarm hysteresis *5 *5 R/W
37 ALFT Alarm failure transfer 0 65535 R/W
38 COMM Communication function 0 65535 R/W
39 ADDR Address 0 65535 R/W
40 BAUD Baud rate 0 65535 R/W
41 DATA Data bit count 0 65535 R/W
42 PARI Parity bit 0 65535 R/W
43 STOP Stop bit count 0 65535 R/W
44 SEL1 Selection 1 0 65535 R/W
45 SEL2 Selection 2 0 65535 R/W
46 SEL3 Selection 3 0 65535 R/W
47 SEL4 Selection 4 0 65535 R/W
48 SEL5 Selection 5 0 65535 R/W
49 SEL6 Selection 6 0 65535 R/W
50 SEL7 Selection 7 0 65535 R/W
51 SEL8 Selection 8 0 65535 R/W
52 ADLO mV calibration low coefficient -1999.9 4553.6 R/W
53 ADHI mV calibration high coefficient -1999.9 4553.6 R/W
54 RTDL RTD calibration low coefficient -1999.9 4553.6 R/W
55 RTDH RTD calibration high coefficient -1999.9 4553.6 R/W
56 CJLO Cold junction calibration low coefficient -199.99 455.36 R/W
57 CJHI Cold junction calibration high coefficient -1999.9 4553.6 R/W
58 DATE Date code 0 65535 R/W
59 SRNO Serial number 0 65535 R/W
60 HOUR Working hours of the controller 0 65535 R/W
61 BPL1 Bumpless transfer of OP1 0 65535 R
62 BPL2 Bumpless transfer of OP2 0.00 655.35 R
63 CJCL Cold junction signal low 0.000 65.535 R
64, 128 PV Process value *4 *4 R
65, 129 SV Current set point value *4 *4 R
66 MV1 OP1 control output value 0.00 655.35 Read only unless 130 in manual control
67 MV2 OP2 control output value 0.00 655.35 Read only unless 131 in manual control
68 TIMER Remaining time of dwell timer -1999.9 4553.6 R
69 EROR Error code *1 0 65535 R
70 MODE Operation mode and alarm status *2 0 65535 R
71, 140 PROG Program code *3 0.00 655.35 R
72 CMND Command code 0 65535 R/W
73 JOB1 Job code 0 65535 R/W
74 JOB2 Job code 0 65535 R/W
75 JOB3 Job code 0 65535 R/W
76 CJCT Cold Junction Temperature -199.99 455.36 R
77 Reserved 0 65535 R
78 Reserved 0 65535 R
79 Reserved 0 65535 R
27
Page 32
*1 The error code is shown in the first column of Table A.1 page 30.
*2 Definition for the value of MODE register:
H’000X = Normal mode H’010X = Calibration mode H’020X = Auto-tuning mode H’030X = Manual control mode H’040X = Failure mode
*3 The PROG Code is defined in the following table
Model No. TEC-9100 TEC-8100 TEC-4100 TEC-7100 TEC-220 TEC-920
PROG Code 6.XX 11.XX 12.XX 13.XX 33.XX 34.XX
(xx denotes the software version)
*4 The scale high/low values are defined in the following table for SP1, INLO, INHI, SP1L, SP1H, SHIF, PV, SV, RELO and REHI:
Conditions Non-linear Linear input Linear input Linear input Linear input
input DP = 0 DP = 1 DP = 2 DP = 3
Scale low -1999.9 -19999 -1999.9 -199.99 -19.999
Scale High 4553.6 45536 4553.6 455.36 45.536
*5 The scale high/low values are defined in the following table for PB, O1HY, RR, O2HY, and ALHY:
Conditions Non-linear Linear input Linear input Linear input Linear input
input DP = 0 DP = 1 DP = 2 DP = 3
Scale low 0.0 0 0.0 0.00 0.000
Scale High 6553.5 65535 6553.5 655.35 65.535
H’0X00 = Alarm status is off H’0x01 = Alarm status is on
The alarm status is shown in MV2 instead of MODE for models TEC-220 and TEC-920.
*6 The scale high/low values are defined in the following table for SP3:
Conditions ALFN=1 Non-linear Linear input Linear input Linear input Linear input
(TIMR) input DP = 0 DP = 1 DP = 2 DP = 3
Scale low -1999.9 -1999.9 -19999 -1999.9 -199.99 -19.999
Scale High 4553.6 4553.6 45536 4553.6 455.36 45.536
*7 The scale high/low values are defined in the following table for SP2:
For TEC-220 and TEC-920
Conditions OUT2=1 Non-linear Linear input Linear input Linear input Linear input
(TIMR) input DP = 0 DP = 1 DP = 2 DP = 3
Scale low -1999.9 -1999.9 -19999 -1999.9 -199.99 -19.999
Scale High 4553.6 4553.6 45536 4553.6 455.36 45.536
For TEC-9100, TEC-8100, TEC-7100 and TEC-4100:
Conditions Non-linear Linear input Linear input Linear input Linear input
input DP = 0 DP = 1 DP = 2 DP = 3
Scale low -1999.9 -19999 -1999.9 -199.99 -19.999
Scale High 4553.6 45536 4553.6 455.36 45.536
7-4 Data Conversion
The word data are regarded as unsigned (positive) data in the Modbus message. However, the actual value of the parameter may be a negative value with decimal point. The high/low scale values for each parameter are used for the purpose of such conversion.
Let M = Value of Modbus message A = Actual value of the parameter
SL = Scale low value of the parameter SH = Scale high value of the parameter
28
M =
SH – SL
65535
× (A – SL)
)(
SH – SL
A =
(
65535
× (M + SL)
)
Page 33
7-5 Communication Examples:
R
Example 1: Download the default values via the programming port
The programming port can perform Modbus communications regardless of the incorrect setup values of address, baud, parity, stop bit, etc. It is especially useful during the first time configuration for the controller. The host must be set with 9600 baud rate, 8 data bits, even parity and 1 stop bit. The Modbus message frame with hexadecimal values is shown as follows:
01 10 00 00 00 34 68 4F 19 4E 83 4E 83 00 00
Addr. Func. Starting Addr. No. of words Bytes SP1=25.0 SP2=10.0 Sp3=10.0 LOCK = 0
00 01 00 00 00 01 4D 6D 51 C4 4D 6D 63 21
INPT = 1 UNIT = 0 DP = 1 INLO = -17.8 INHI = 93.3 SP1L = -17.8 SP1H = 537.8
4E 1F 00 02 00 00 00 64 00 64 00 FA 00 00
SHIF = 0.0 FILT = 2 DISP = 0 PB = 10.0 TI = 100 TD = 25.0 OUT1 = 0
00 00 4E 1F 00 01 00 B4 00 FA 00 00 00 00
O1TY = 0 O1FT = 0 O1HY = 0.1 CYC1 = 18.0 OFST = 25.0 RAMP = 0 RR = 0.0
00 02 4E 1F 00 00 4E 1F 00 01 00 B4 00 64
OUT2 = 2 RELO = 0.0 O2TY = 0 O2FT = 0 O2HY = 0.1 CYC2 = 18.0 CPB = 100
4E 1F 00 02 52 07 00 00 00 01 00 00 00 01
DB = 0 ALFN = 2 REHI = 100.0 ALMD = 0 ALHY = 0.1 ALFT = 0 COMM = 1
00 01 00 02 00 01 00 00 00 00 00 02 00 03
ADDR = 1 BAUD = 2 DATA = 1 PARI = 0 STOP = 0 SEL1 = 2 SEL2 = 3
00 04 00 06 00 07 00 08 00 0A 00 11 Hi Lo
SEL3 = 4 SEL4 = 6 SEL5 = 7 SEL6 = 8 SEL7 = 10 SEL8 = 17 CRC16
Example 2: Read PV, SV, MV1 and MV2
Send the following message to the controller via the COMM port or programming port:
03 00
H’80
Addr. Func. Starting Addr. No. of words CRC16
Example 4: Enter Auto-tuning Mode
Query
06 00 H’48 H’68 H’28 Hi Lo
Addr. Func. Register Addr. Data Hi/Lo CRC16
H’40
00 04 Hi Lo
Example 3: Perform Reset Function (same effect as pressing key)
Query
06 00 H’48 H’68 H’25 Hi Lo
Addr. Func. Register Addr. Data Hi/Lo CRC16
Example 5: Enter Manual Control Mode
Query
06 00 H’48 H’68 H’27 Hi Lo
Addr. Func. Register Addr. Data Hi/Lo CRC16
Example 6: Read All Parameters
Query
Example 7: Modify the Calibration Coefficient
Preset the CMND register with 26669 before attempting to change the calibration coefficient.
29
Page 34
A–1 Error Codes
Table A.1 Error Codes and Corrective Actions
30
Page 35
A–2 Warranty
WARRANTY
Tempco Electric Heater Corporation is pleased to offer sugges­tions on the use of its products. However, Tempco makes no war­ranties or representations of any sort regarding the fitness for use, or the application of its products by the Purchaser. The selection, application, or use of Tempco products is the Purchaser's responsibility. No claims will be allowed for any damages or losses, whether direct, indirect, incidental, special, or consequential. Specifications are subject to change without notice. In addition, Tempco reserves the right to make changes– without notification to the Purchaser–to materials or processing that do not affect compliance with any applicable specification. TEC Temperature Controllers are warranted to be free from defects in material and workmanship for two (2) years after delivery to the first purchaser for use. Tempco's sole responsibility under this warranty, at Tempco's option, is limited to replace­ment or repair, free of charge, or refund of purchase price within the warranty period specified. This warranty does not apply to damage resulting from transportation, alteration, misuse, or abuse.
RETURNS
No product returns can be accepted without a completed Return Material Authorization (RMA) form.
TECHNICAL SUPPORT
Technical questions and troubleshooting help is available from Tempco. When calling or writing please give as much back­ground information on the application or process as possible.
E-mail: [email protected] Phone: 630-350-2252
800-323-6859
Note: Information in this manual was deemed correct at the time of printing. The policy of Tempco is one of continuous development and product improvement, and we reserve the right to modify specifications and designs without prior notice. Not responsible for typographical errors.
31
Page 36
Complete Your Thermal Loop System
With Over 100,000 Various Items
Available from Stock
• Electric Heating Elements
• Thermocouples and RTD Assemblies
• SCR Power Controls
• Solid State Relays
• Mechanical Relays
• Videographic Data Recorders
• Temperature Measurement
• Current Indicators
• Thermocouple and Power Lead Wire
• Wiring Accessories
TEMPCO’s Visionary Solutions
The Electric Heating Element, Temperature Controls and
Temperature Sensors Handbook
REQUEST YOUR FREE 960 PAGE COPY TODAY!
Call (800-323-6859) or E-mail ([email protected])
™
Specify Print Edition, CD-ROM or Both
Serving Industry Since 1972
Experience the Advantages of our Diverse and Innovative Products
TEMPCO Electric Heater Corporation 607 N. Central Avenue Wood Dale, IL 60191-1452 USA Tel: 630-350-2252 Fax: 630-350-0232 Web: www.tempco.com
© Copyright 2012 TEHC. All Rights Reserved.
12P200E16
Loading...