Temp-Cast 2000 Installation Manual

INSTALLATION MANUAL
READ THIS ENTIRE MANUAL
INCLUDING THE WARRANTY SECTION
BEFORE STARTING THE INSTALLATION
TO ENSURE THE SAFE AND
EFFICIENT OPERATION OF THIS
HEATER, SECTION 5 MUST BE
REVIEWED PRIOR TO STARTING
Temp-Cast 2000 Installation Manual February 2010
THE INSTALLATION
2
TABLE OF CONTENTS
SECTION1 – INTRODUCTION
General Information 3 Site Preparation 3 Clearances 3 The Façade 4 Delivery & Handling 4 Tools 4 Additional Materials 4 Combustion Air Supply 5
SECTION 2 – CHIMNEYS & DAMPERS
General Requirements 6 Flue Connections 6 Masonry Chimneys 6 Factory-built Chimneys 7 Base-Exit Dampers 8 Installing the Roof-top Chimney Damper 9
SECTION 3 - STEP-BY STEP ASSEMBLY
Assembly Notes 10 Step-by-Step Installation 11
SECTION 4 - DOOR FRAMES & FACADE
The Door Frame Flange 37 Installing Arched Fire-Box Doors 38 Air Supply Doors 42 Clean-out (Soot) Doors 42 Installing "See-Through" Doors 43 Installing Square Fire-Box Doors 44 Installing Bake Oven Doors 46 The Trim Plate Option 47 Installing the Facade 48 The Masonry Cap 49
SECTION 5 - AVOIDING INSTALLATION ERRORS
SECTION 6 – CERAMIC FIBRE CUTTING PLAN
SECTION 7 –WARRANTY
PAGE #
50
51
53
Temp-Cast 2000 Installation Manual February 2010
Section 1 - Introduction
SECTION 1: INTRODUCTION
GENERAL INFORMATION
The Temp-Cast 2000 is a modular "site-built" fireplace kit. The assembled modules form the "core" of the fireplace, including internal flue passages. The Standard Fireplace package also contains a cast iron fire grate, two soot cleanout doors, refractory joint-sealing mortar, corrugated cardboard spacers, gasket material, and assorted fasteners.
READ THESE INSTRUCTIONS COMPLETELY BEFORE BEGINNING THE INSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY CREATE A FIRE HAZARD, HAMPER THE PERFORMANCE OF THE FIREPLACE AND VOID THE PRODUCT WARRANTY.
IMPORTANT: Review Section 5, "Avoiding Installation Errors" before beginning the installation!
3
CLEARANCES
A minimum clearance of 4" (100mm) from the back and sides of the completed fireplace (i.e. from the masonry facing) to combustible materials is required. The clearance required from the top of the heater is 10" (250mm).
48” (1200mm) clearance is required in front of the door & a non-combustible hearth of 16” (400mm) deep is required, extending 8” either side of the door.( approx. 38” [1m] wide). Also, a clearance of 2" (50mm) is required between the chimney and any combustible construction. (See Fig 1 & 1-1 below.)
SITE PREPARATION
The following instructions detail the assembly of the Temp-Cast 2000 Fireplace, on a properly prepared and supported concrete pad. Support requirements are described in the Temp-Cast Planning Guide, and related Plan Drawings. If you require assistance with the support details for the fireplace or other preparatory work, please contact your dealer or the factory. If you are unsure regarding any aspect of the installation of this product, please contact:
Temp-Cast Enviroheat Ltd, 3409 Yonge St, Bedford Park Postal Outlet, Box 94059 Toronto, Ontario, Canada, M4N 3R1.
Tel: 416-322-5197 Fax: 416-486-3624 Toll-free 1-800-561-8594 Email: staywarm@tempcast.com
Temp-Cast 2000 Installation Manual February 2010
Section 1 - Introduction
If necessary, a metal or masonry convection shield may be placed between your fireplace facade and the combustible structure, reducing clearances by up to 67%. Contact your dealer, local building inspector or the factory for details.
(In new construction, a non-combustible solid masonry wall or metal stud and "cement-board" wall will eliminate concern with clearances.)
FAILURE TO MAINTAIN THE MINIMUM CLEARANCES TO COMBUSTIBLES MAY CREATE A FIRE HAZARD.
THE FACADE
Once the core is assembled, it must be faced with additional suitable heat-storing masonry material, usually installed by a professional mason. (See also Section 4.) Suitable facade materials include brick, rock, fieldstone, or soapstone – concrete block facings are not recommended. (Hollow units must be
filled. If using solid bricks, they should not be perfectly flat on both sides - a depression is needed
to ensure that bricks do not move during thermal expansion.) THE FACADE MUST BE BETWEEN
4" (100mm) & 6” (150mm) OF SOLID MASONRY, STONE OR ROCK. (Substantially thinner facings
may not comply with building codes, due to higher surface temperatures, requiring greater clearances to combustibles. Thicker facings will make the heater slower to respond & more difficult to regulate.)
DELIVERY & HANDLING
The fireplace kit weighs 2800 lbs and is delivered on a wood pallet, covered with plastic. If unloaded by forklift, it should be placed on a level and even surface, so that parts will not fall when the strapping is cut. Unpacking should be done by at least 2 persons, following the unpacking instructions.
As soon as possible after delivery, the fireplace should be unpacked and dry assembled, to become familiar with complete and to check for damage. Visible damage
to the pallet or the contents must be reported immediately to the delivery person and noted on the shipping bill before accepting delivery. Hidden damage or missing parts must be reported to Temp-Cast and to the shipping company within 24 hours.
all the parts, to ensure the delivery is
4
The pieces must be handled with reasonable care to avoid damage, although minor chips to corners and edges are acceptable and do not affect installation or performance. The modules should be stored indoors, in a dry area. When possible, in cold weather, the modules should be left in a heated area for a few days prior to beginning the installation.
TOOLS
The following tools are required to simplify the assembly process:
48" (1.2m) and 12” levels powered cutting tool - options include:
1. 4” grinder with diamond blade
2. circular saw with diamond blade
3. masonry “water” saw or gas concrete saw (less
accurate & convenient on smaller cuts)
1/2" (12.5mm) hammer drill & masonry bits heavy rubber mallet 2" (50mm) margin or pointed trowel 2" packing tape (e.g. “Scotch” tape) black magic marker pencil utility knife bucket, water & sponge measuring tape 20 ft (10m) tie-down or web-clamp, for temporary
support of side channels (Step 18).
ADDITIONAL MATERIALS:
all masonry facing & chimney materials
  Portland cement (to level the base) chimney cleanout for rear connections (see
Section 4)
optional air supply door & frame (for slab-on-grade
installations - refer to Fig 1B)
optional chimney damper 6” or 8” combustion air supply duct (e.g.
galvanized duct - see next section)
Temp-Cast 2000 Installation Manual February 2010
Section 1 - Introduction
COMBUSTION AIR SUPPLY:
The Temp-Cast heater requires an unrestricted air supply for proper combustion and maximum performance. (This section refers to the standard
Temp-Cast “arched” door & air-frame installation. The Temp-Cast “square” door installation is described in a separate
Combustion air can be drawn from outside or inside the house and delivered by way of a 15" x 2" (380mm x 50mm) air intake formed in front of the heater during construction of the concrete floor pad. Air is then directed up behind the facing masonry, and into the hollow door frame through slots on the bottom. The air travels up inside the door frame and feeds the fire from above, creating an "air-wash" across the doors to keep the glass clean. (See Fig. 1a)
If the installation is designed to use inside air from the same room as the heater, (such as in a basement installation ), then an optional "air supply door" must be purchased and installed under the loading doors. This will allow combustion air to be drawn from the room, travel up behind the facade and into the hollow door frame. (Refer to Fig. 1b).
In a basement installation, outside air can still be brought into the fireplace, if ceiling height permits. In this case, a raised hearth can be constructed, and 6" (150mm) of fresh air can be fed into this (A "false" chimney can be used for this fresh air supply.) The air is brought to the front of the heater into a 15" x 2" (380mm x 50mm) masonry slot or custom-fabricated "boot" and treated as a normal outside air installation.
In a "See-Through" fireplace, 8” of combustion air must be supplied and divided equally to both door frames to provide an "air wash" for each door glass. (See Fig. 16)
manual.)
structure.
5
Fig 1a
Temp-Cast 2000 Installation Manual February 2010
Fig 1b
SECTION 2: CHIMNEYS & DAMPERS
GENERAL REQUIREMENTS
Temp-Cast fireplaces require an approved chimney system for safe and satisfactory performance. Code-approved masonry and factory-built chimney systems are both acceptable.
In addition to building code requirements, every chimney system should:
extend straight up from the base of the
fireplace
be at least 18 ft (5.5m) in height  have an access at the base, with a tight-
fitting metal door, for chimney cleaning
have a cross-sectional area of at least 50 sq.
inches (320 sq cm)
NOT BE CONNECTED TO ANOTHER
APPLIANCE OR TO ANY AIR DUCTS
FLUE CONNECTIONS
The chimney connection is made at the bottom of the fireplace, in the first course. The connection can be made on either side of the fireplace or through the back wall, into the cross manifold. (Refer to Fig. # 2). The flue connection can be up to 5 ft. long, creating heated benches & allowing additional flexibility in chimney locations.
For a side connection, the side channel (Part # 30 or 31) is cut to receive the connector. (see step 18.) Make this cut carefully so that a smooth transition from the fireplace to the chimney results, free of of the escaping smoke. Use joint sealing mortar to make it completely smoke tight. The connector piece penetrates the fireplace side channel about 1" (25mm), but care must be taken to ensure that it does not protrude past the inner edge of the side channel. (See Figs. # 3
and 4.)
If the connection is made at the back of the fireplace, the cross manifold (Part #3) is cut to
obstructions to the flow
receive the flue connector. This joint must also be smoke-tight. (See also Section 3,
Step #3.)
MASONRY CHIMNEYS
Due to the thermal mass storage capability of masonry chimneys, we recommend them over factory-built chimneys, provided they are completely inside the home & fitted with a damper.
Masonry chimneys should have carefully aligned flue liners, with joints that are smoke-tight and joined with refractory mortar. The inside surface of the liner should be smooth, with all excess mortar removed. Refractory, clay and UL/ULC listed stainless steel are all acceptable liners.
An access for a chimney cleanout can be cut in the first vertical flue tile. (See Fig #10)
6
Temp-Cast 2000 Installation Manual February 2010
Section 2 – Chimneys & Dampers
7
Fig 3
A 4” grinder with a diamond blade is ideal for cutting accurate & neat holes in the refractory concrete modules.
FACTORY-BUILT CHIMNEYS
We do not recommend exterior chimneys, (see Sec. 4 of the Temp-Cast Planning Guide) but if a
chimney on the outside of the house is unavoidable, then an insulated factory-built (e.g. "HT" or 2100F.) chimney is the better choice.
When a factory-built chimney is started at the floor level, there will not be sufficient space to access the clean-out cap under it. In order to provide a clean out access, one of the following 2 methods is suggested.
Create a masonry connection to the fireplace, with 8" (200mm) round flue tile. Add vertical sections of 8” round flue tile, with a clean-out access built into the first vertical section. Wrap the horizontal tile and the first vertical flue tile with “ceramic wool” blanket & ensure they cannot be dislodged. Continue with flue tile & masonry to the point where the transition to factor-built chimney is wanted – often the masonry is extended to the first ceiling. If a roof-top damper is to be installed, the cable protector for the damper cable must be built into the masonry chimney where it will be accessible for daily use – we recommend at least 6 feet from the floor. Install an anchor plate approved
for the factory-built chimney, on top of the last masonry section - the factory-built chimney continues from this point. (See Fig. 5.) If the factory-built chimney will also be enclosed in masonry, the layout of the first masonry courses must take this into account. (Confirm this
connection method with your local building official.)
Fig 4
Temp-Cast 2000 Installation Manual February 2010
Section 2 – Chimneys & Dampers
8
BASE-EXIT DAMPER/TRANSITION
A Temp-Cast base-exit damper/transition is another method to make a suitable connection from the heater to a factory-built chimney, and also incorporates a damper & cleanout access that is not otherwise possible with factory-built chimneys. (See Fig 6.)
If you use a damper of any kind, be certain to read the cautions regarding carbon monoxide, in the next section.
The following details the installation of the Temp-Cast base-exit damper/transition.
1. At Step 18, position the base-exit
damper/transition, sitting on the concrete slab. Mark where the damper will be installed into the side channel (Part #30 or 31) or rear manifold (Part #3), and cut a 9½” x 9½” opening.
2. Cut the damper rod to length, if
required, to extend beyond the masonry which will enclose the entire assembly.
3. Attach the handle to the rod with the nut
extender and nuts supplied. Check the operation of the damper to become familiar with its operation. (The handle is usually shipped inside the damper.)
4. Attach a strip of ceramic wool to the
outside of the side channel around the damper opening, with high-temperature silicone. Lay a strip of ceramic wool on the bottom edge of the opening and insert the base-exit damper/transition. Insert the damper into the opening and slightly compress the ceramic wool – it may be helpful to temporarily support the damper box until masonry work has been started around it.
5. Cover the damper rod so that it will not
be inadvertently cemented in position during installation of the masonry facing – flexible cardboard or ½” copper pipe (not supplied) may be used for this.
6. With at least 3 metal screws, attach an
approved masonry adapter to the top of the damper assembly & install the first vertical section of factory-built chimney.
7. Enclose the entire damper assembly
with at least 4” of solid masonry, leaving an access for the cleanout. (If the factory-built chimney will also be enclosed, the first masonry courses must take this into account.)
Other methods of connecting factory-built chimneys may also be acceptable. Consult the chimney manufacturer, a certified installer or your local building official.
Fig 6
Temp-Cast 2000 Installation Manual February 2010
Section 2 – Chimneys & Dampers
9
INSTALLING THE ROOF-TOP CHIMNEY DAMPER
An optional “roof-top” chimney damper is recommended to allow the chimney to be closed off when the fire is out. This will let the chimney mass hold additional heat and greatly improve the overall heating efficiency of the system. (Refer to the Temp-Cast Owner's
Manual for proper use of the chimney damper.)
The damper is cemented to the top of the uppermost flue tile of the chimney, and is controlled by a cable through the centre of the chimney. (See Fig. 7) The cable is routed through the side of the flue tile during construction of the chimney and masonry facing.
(Note: Installation of the damper cable is greatly simplified if the protective sleeve and steel cable are installed in the desired area when the chimney is being built. If this has not been done, then a string will have to be fished through the sleeve & secured to the steel cable.) Attach the
cable bracket to the outside of the chimney in a convenient, unobtrusive location, but always out
of the reach of small children.
For 8” round chimneys, including factory-built models, a Round-to-Square adapter and a 13” x 13” damper will be required.
NOTE: When a stainless steel (i.e. “factory­built”) chimney is used, penetrating the steel chimney is not permitted. Alternatives include:
1. Installing a Temp-Cast Base-Exit Damper,
construct a short section of masonry chimney, install an approved masonry adapter part and continue with factory-built chimney through the roof. (See Fig 6.)
2. Starting the installation with a Temp-Cast
Base-Exit Transition, with or without an integral damper. For exposed chimneys, a Temp-Cast Base-Exit Transition/Damper must be used. If the chimney is to be enclosed to the first ceiling or through to the roof, you can use the same Temp-Cast Base Exit Damper/Transition, or obtain an
adapter with a built-in damper, which can be installed with the first section of “factory-built” chimney. This permits a more effective damper, much higher up in the chimney system. In either case, the whole chimney assembly and transition can be enclosed in masonry.
CAUTION: Whenever a full-closure damper is used, care should be taken to ensure that the fire is completely out before the damper is shut. Closing the damper prematurely could cause combustion gases, especially carbon monoxide, to be spilled into the home. Carbon monoxide has the potential to be fatal. We therefore strongly recommend installation of a carbon monoxide alarm, available where smoke alarms are purchased, whenever a damper is used with a Temp-Cast masonry heater.
Temp-Cast 2000 Installation Manual February 2010
Section 3 - Step-By-Step Assembly
SECTION 3: STEP-BY-STEP ASSEMBLY
ASSEMBLY NOTES
1. Dry-assemble the heater upon
delivery, to check the condition of all parts and to familiarize yourself with the modules. (If all of the parts are not numbered, you may find it helpful to do so, using this manual, before taking the unit apart again.)
2. Cutting of flue tiles and fireplace modules should be done outdoors due to the excessive dust created. WEAR
SUITABLE EAR, EYE AND LUNG PROTECTION.
3. A 4” grinder with a diamond blade is best for cutting holes in flue tiles and fireplace modules. Or round holes can be cut as six or eight-sided shapes with a gas, water or circular saw or drilled every inch (25mm) and then cut with a reciprocating saw fitted with a masonry blade. Rounding or beveling the inside edges of the hole in the module creates the least resistance to the flow of smoke and gases, maximizing draft and performance.
(See Fig. 8)
4. When using the ceramic-fibre gasket material, it should only be slightly compressed. Compressing it too much will defeat its purpose as an expansion gasket. (A small amount of refractory mortar can be used to cement the gasket in position.)
5. Refractory casting occasionally leaves behind rough spots or small bumps on the modules. If these rough spots should occur in a joint between 2 modules, they may prevent a tight joint and make installation of subsequent parts more difficult. Remove any such
10
bumps with a rasp or scraping tool before assembling.
6. Refractory mortar should be used
sparingly, applying a small (1/4” to 3/8”) bead between modules. The
finished joint should have a very thin skin of refractory mortar, which is the strongest. (In addition, the parts will
only fit properly if the thinnest possible joint is created.) Apply a small amount
on the outside edges of the part, where indicated by the shaded areas. Do not use a full bed of mortar. Seat the parts completely, using a rubber mallet, so that a little mortar squeezes out. After each course, scrape off and save excess mortar for possible later use. Periodically wipe the modules inside and out with a damp sponge to ensure that excess mortar has not been left behind.
Fig. 8
Temp-Cast 2000 Installation Manual
Section 3 - Step-By-Step Assembly
11
STEP 1: "THERMOTECT" INSULATING BOARD
If an optional insulating board is to be installed, it is installed before starting the Levelling Pad. Cut the board to size as indicated and place it in position. Check that it is square to the concrete floor pad. Ensure that the air intake hole is located immediately in front of the board and centered. (It is also advisable at this point to double check that there will be sufficient clearances to combustible construction around the fireplace.) If you have followed the Temp-Cast Planning Guide, the area around the 6" diameter Ash Drop hole in the concrete pad will be sloped towards the hole for a few inches all around. Cut an appropriately sized hole in the insulating board so that the sloped area around the hole is not obstructed. Lay the board in position as illustrated.
Temp-Cast 2000 Installation Manual
Section 3 - Step-By-Step Assembly
STEP 2: "Dry" assemble (i.e. without mortar) the two halves of the Leveling Pad (Part #1 & #2) on the "Thermotect" board (optional), or on the concrete floor pad, so that the air intake slot is not obstructed and is centered in front of the Leveling Pad. Ensure that the 6" (150mm) diameter ash drop is located within the cut-out section of the base. CHECK THAT THE FLOOR IS REASONABLY LEVEL BEFORE STARTING TO INSTALL THE LEVELLING PAD ­ADDITIONAL MORTAR MAY BE NEEDED TO LEVEL IT AS REQUIRED.
Lay the two halves of the Leveling Pad in a 1/2" (12mm) bed of common mortar, using refractory mortar between them. Using the 48" level, tap the base into the mortar, ensuring that it is level. Before the mortar has set, tap down along the centre-line of the leveling pad, so that the centre of the pad is about 3/16” lower than the sides. (See illustration below.) This centre-line gap will ensure that parts in the upper courses lean in slightly, simplifying installation.
Weights
#1 & 2 - 49 lbs
#1C & 2C - 59 lbs
12
Temp-Cast 2000 Installation Manual
Section 3 - Step-By-Step Assembly
13
STEP 3:
When the Leveling Pad can support weight, dry assemble the first course of modules, including the grate, as in the accompanying drawings, to check for proper fit. This course must be centered
on the Leveling Pad, so that equal space is left on both sides for the heat exchange channels - mark the correct placement with a pencil.
If the chimney is to be connected at the rear of the fireplace, mark the cross manifold (#3) to be cut for the flue connection. Take this part outdoors and cut a hole for the flue connector being used. For flue tile or HT chimney, cut the hole the same size as the inside dimensions of the flue connector. The flue connector or HT adapter will then be mortared or attached to the outside of the cross manifold - Part #3. (Holes for a side connection are discussed at Step 18.)
Once the layout of fireplace and chimney connection, all dimensions and locations of cleanout doors have been confirmed, draw a line on the Leveling Pad to mark the outside edges of the base course. Now remove the modules, (cut the flue hole in #3 if required) and re-assemble, using a small amount of the refractory mortar provided on the bottom edges and between modules. Seat the parts with the rubber mallet, then reach inside the cross manifold and wipe off all excess mortar.
NOTE: once final assembly has been started, the entire core should be assembled in a continuous operation, so that minor adjustments to previous courses can be made before the refractory mortar has set. Place the fire-grate in position, which should fit loosely to allow for expansion. Cover it to keep clean.
Weights
#3 - 61 lbs
#4& #5 - 82 lbs
#6 - 22 lbs
Temp-Cast 2000 Installation Manual
Section 3 - Step-By-Step Assembly
14
STEP 4:
Assemble the second course, parts #7, #8 & #9. A small bead (½”) of refractory mortar is laid on the outside edges where the two parts meet. (The bead can be laid either on the part being laid on or the previous part - whichever is easier.) Note that the parts are numbered in the order that they should be placed. (For a Temp-Cast "See-Through" fireplace, these 3 parts are slightly different,
as in the accompanying illustration.)
Use the rubber mallet to seat the modules. Remove excess mortar and wipe inside and out with a damp sponge as work progresses.
NOTE: When installing the modules on this course and subsequent courses around the firebox opening, take care that the parts are flush at the front of the fireplace. This will produce the most level surface on which to install the door frame later.
Weights
#7 - 52 lbs
#8, #8ST, #9, #9ST - 68
Temp-Cast 2000 Installation Manual
Section 3 - Step-By-Step Assembly
15
STEP 5:
Install Parts# 10, 11, 12 &13, using refractory mortar. Also “butter” the ends of part #10, so there are no gaps on the ends. (Note that parts 11 thru 13 are identical to the previous course.) (In the
"See-Through" fireplace, there is no part #11.)
Seat with the rubber mallet and ensure that joints are tight.
Remember to keep the front edges of the modules aligned and use a 48” level to ensure that the
four sides are plumb.
Leveling the courses is not critical – it is sufficient if the courses are approximately level.
Weights #10 - 12 lbs #11 - 52 lbs
#12 & #13 - 68 lbs
#12ST & #13ST - 68 lbs
Temp-Cast 2000 Installation Manual
Section 3 - Step-By-Step Assembly
STEP 6:
Install the lintel course, parts 14, 15 & 16, in order, using a small (3/8”) bead of refractory mortar on the outside edges of the adjoining parts.
Weights
#14 & #14 ST- 86 lbs
#15 & #16 - 64 lbs
16
Temp-Cast 2000 Installation Manual
Loading...
+ 37 hidden pages