ENGINEERING, INSTALLATION AND SERVICE MANUAL
HP-SERIES
Portable Air-Cooled Heat Pump
3700 West Preserve Boulevard Burnsville, MN 55337
Temp-Cool.com | 800.836.7432 | Info@temp-air.com
![](/html/6d/6dc9/6dc9505020c222b604e64b543c4683dceb3dffe6fef405f01e7fe2b303da818d/bg2.png)
FORWARD
This manual provides the user with basic details for the installation and operation of the
TEMP-COOL HP-Series heat pump. It is recommended to read and fully understand the
instructions outlined within this manual, before operating the HP-Series unit.
As with all commercial air conditioning equipment, it is recommended to have the HP-
Series sized and installed by a licensed specifying engineer and contractor, in
accordance with all local and state codes. The length of service received can be
extended by following the installation and preventive maintenance instructions.
NOTICE
In our ongoing process of continuous improvement, the items and procedures described
in this manual are subject to change without notice. Please note model and serial
number of the HP-Series unit before contacting the factory.
TABLE OF CONTENTS
PAGE
GENERAL INFORMATION …................................ 1
PRODUCT DATA AND SPECIFICATIONS............ 2
UNIT DESCRIPTION
Standard Features.................................. 3
Applications / Operation
Cooling Mode.......................... 4
Heating Mode…………………. 5
Electrical Configurations......................... 6
Use of Extension Cords…………………. 7
Condensate............................................ 8
Accessories………................................. 9 - 15
Inspection/Installation............................. 16
Deluxe Electronic Controller.................... 17-19
SERVICE
Replacement Parts Procedure................. 20
Troubleshooting Guide............................. 21
Preventive Maintenance........................... 22
Interior View............................................. 23
DIAGRAMS/SCHEMATIC
Piping Schematic…………………………. 24
Single Phase Wiring Diagrams................. 25 - 27
Three Phase Monitor................................ 28
Three Phase Wiring Diagrams................. 29 - 32
USEFUL INFORMATION ................................... 33
![](/html/6d/6dc9/6dc9505020c222b604e64b543c4683dceb3dffe6fef405f01e7fe2b303da818d/bg3.png)
GENERAL INFORMATION
The TEMP-COOL HP-Series is a portable air-cooled heat pump designed for
permanent or temporary spot cooling or heating applications. The entire unit has been
built in a premium sheet metal cabinet, equipped with heavy-duty casters for mobility.
All HP-Series models come standard with a 10-foot power cord for electrical connection
and added mobility in service. These units direct heated/cooled air to specific areas or
objects through a discharge grille located on the upper-front of the unit, while rejecting
cooled/heated air from the top of the unit. The HP-Series models range in capacities
from 12,000 BTU/HR to 60,000 BTU/HR to satisfy most space cooling or heating
requirements.
The HP-Series is a self-contained unit with the entire system (evaporator and
condenser blower assemblies, electrical and refrigeration components), neatly
arranged in a gray and blue polyester powder coated metal cabinet. When connected
to the proper source of electrical power, the HP-Series is controlled by a solid-state
electronic controller, with numerous options of temperature and airflow controls that will
provide the desired level of comfort when cooling or heating.
A wide variety of accessories and factory installed options are available for the HP-
Series units allowing for improved performance and added versatility.
1
NOMENCLATURE
2O AC H 60 1 2
DELUXE
PORTABLE VOLTAGE
AIR-COOLED PHASE (1 or 3)
HEAT PUMP NOMINAL
CAPACITY
CAPACITY RATING
12..........12,000 BTU/HR
18..........18,000 BTU/HR
24..........24,000 BTU/HR
36..........36,000 BTU/HR
60……...60,000 BTU/HR
![](/html/6d/6dc9/6dc9505020c222b604e64b543c4683dceb3dffe6fef405f01e7fe2b303da818d/bg4.png)
2
SPECIFICATIONS
HP-SERIES
MODEL:
TC-12HP
TC-18HP TC-24HP TC-3612HP TC-3623HP TC-3643HP TC-6021HP TC-6023HP TC-6043HP
Cooling Capacity
11,800
16,800 24,020 36,050 36,050 36,050 60,050 60,050 60,050
Voltage (V/Phase) at 60Hz
115/1
208-230/1 208-230/1 208-230/3 460/3 208-230/1 208-230/3 460/3
Amps
10.4
14.1 14.9 18.1 17.2 8.7 32.0 20.4 14.8
Watts
1180
1670 2700 3620 3620 3620 6000 6000 6000
In Rush Current (Amps)
60
75 68 113 93 60 178 162 87
Plug Type
5-15P
5-20P 6-20P 6-30P L15-30P L16-20P 6-50P L15-30P L16-20P
EER
10.0
10.0 8.9 10.0 10.0 10.0 10.0 10.0 10.0
Compressor HP
1
1 1/2 2 3 3 3 5 5 5
Compressor RLA
9.5
12.3 10.5 13.6 8.8 5.0 27.6 18.1 9.0
Compressor LRA
50
63 48 83 77 35 158 137 62
Evap CFM
400
600 810 1200 1200 1200 1950 1950 1950
Evap Motor HP
1/8
1/8 1/3 1/3 1/3 1/3 1 1 1
Evap Motor Watts
180
210 330 375 375 375 550 550 550
Condenser CFM
580
930 1010 1390 1390 1390 2200 2200 2200
Condenser Motor HP
1/8
1/8 1/3 1 1 1 1 1 1
Condenser Motor Watts
200
280 350 460 460 460 750 750 750
Condensate 5 Gallon Condensate Tank - STANDARD (Pump Optional) Pump -STANDARD (20 ft. Lift)
Sound Level
54
60 65 69 78
R-410A Charge Oz.
18
40
37 66 80
(A) Height with Casters (in.)
36 1/2
45 1/2 50-1/4 52 1/4
(B) Width (in.)
20
24 28
(C) Depth (in.)
25
30 35 39
(D) Height w/o Casters (in.)
32 1/2
40 1/2
45
46
Net Weight (lb.)
180
260 260
365
485 485 515
Shipping Weight (lb.)
200
285 285
405
525 525 555
Shipping Volume (cu. ft.)
19
28 40 48
380
420
Heating Capacity
11,000
15,600 24,020 32,500 32,500 32,500 53,500 53,500 53,500
2
NOTES
1. Dedicated Circuit and Time Delay fuse or circuit breaker are recommended
Cooling Capacity is total BTUH at 80ºDB/67º WB return air, 95 Condenser Air
. Heat
4.
5. Cooling EER is determined at high fan speed, with condenser air ducted into another area
6. Sound Pressure, dB at 5 feet, commercial operation
7. Amps & Watts at 208 Volts (208-230 V Models)
2. º DB
3 ing Capacity is total BTUH at 70ºDB/60º WB indoor, 47º DB/43ºWB Outdoor
CFM with free discharge
* May COOL down to 55º if equipped with hot gas bypass (factory installed)
COOLING AMBIENT* OPERATING RANGE 65º TO 105º
HEATING AMBIENT OPERATING RANGE 40º TO 85º
* Condenser Return Air Plenums
CP-OH1 and CP-OH2 add 13 inches to Dimension “C”
D
B
A
C*
![](/html/6d/6dc9/6dc9505020c222b604e64b543c4683dceb3dffe6fef405f01e7fe2b303da818d/bg5.png)
STANDARD FEATURES
CABINET
The HP-Series Series heat pump has a cabinet that is constructed of 18 gauge steel
with a polyester powder coated finish that will compliment any decor. The cool blue front
compliments any surrounding space, and is insulated with sound-absorbing insulation
for cool, quiet comfort. All units come equipped with handles and premium swivel
casters for portability and convenient set-up.
DELUXE ELECTRONIC CONTROLLER
Each HP-Series unit is equipped with a deluxe electronic controller. When power is
connected to the unit, the thermostat will control the unit to cool/heat a space to the
desired temperature. The thermostat is also capable of controlling the fan to operate
automatically when needed, or continuously.
One additional feature of the Deluxe Electronic Controller is that it will display a
condition alarm “CON”. “CON” displays when a condensate alarm, or a high pressure
reset condition has been met. To protect the compressor from short-cycling, there is a
built-in time delay.
FAN SPEED CONTROL
One of the features of the electronic controller is that the unit supply fan can be
controlled either automatically or manually. In AUTO mode, the indoor blower will adjust
air flow automatically for added comfort and performance. Or, if desired, the controller
can be set to MANUAL fan mode, and the indoor blower will run continuously at one of
six levels of fan speed.
CONDENSATE TANK/PUMP
HP-Series units come equipped with a means for handling the condensate generated
during the cooling/heating process. All units, except the 5-ton models, come equipped
with a condensate tank. The tank can be easily removed from the unit and emptied as
needed.
The TC-60HP models come equipped with an automatic condensate pump. The pump
comes with a 20 foot long vinyl hose that allows for the removal of the condensate water
to a drain. The automatic pump is capable of a 20ft vertical lift, to handle almost any
installation requirement.
FILTERS
All HP-Series units are equipped with washable filters at the air intakes. Electrostatic
mesh air filters located behind the evaporator return air grille serve to filter the air before
it is cooled/heated, and behind the condenser return air grille to prevent dust build-up.
Both filters can be easily removed and cleaned.
HIGH PRESSURE SAFETY SWITCH
Located on the back of the HP-Series unit is a manual re-set high pressure switch, used
for the protection of the compressor. If the condensing pressure exceeds the limit
setting, the switch will cycle the compressor off, while the evaporator fan remains
running. The display will indicate the default setting “CON”. The compressor can then
be re-started, once the condensing pressure has equalized, by depressing the
“RESET” button.
POWER CORDS
All HP-Series units come standard with a power cord for a convenient connection. All
models, except for the 3-phase units and 5-ton units, are equipped with LCDI for added
safety features.
3
![](/html/6d/6dc9/6dc9505020c222b604e64b543c4683dceb3dffe6fef405f01e7fe2b303da818d/bg6.png)
4
APPLICATIONS
COOLING MODE—SPOT COOLER
The HP-Series can be used in an open environment to cool specific objects or "spots".
Spot Cooling is a convenient and economical way to provide air conditioning, where
cooling the entire space is impractical. Cool air is discharged from the unit and is
directed where it is needed. Nozzle kits can be used for directional cooling.
AREA COOLER
When the HP-Series is installed in an open area, the condenser exhaust duct directs the
warm air away from the space, allowing the evaporator air to cool the specific area.
ROOM AIR CONDITIONER
When ducted properly, the HP-Series can be used as a room air conditioner to cool an
enclosed space. Using the condenser return air plenum, additional ceiling kit, and other
accessories, the HP-Series can then operate as a room air conditioner with the
condenser air isolated from the conditioned space.
CONDENSER AIR
INLET
(Back of Unit)
OUTDOOR FAN DISCHARGE
“HOT”
WASHABLE
GRILLE
AND FILTER
ELECTRONIC
CONTROLLER
INDOOR FAN
SUPPLY AIR
“COOL”
HP-SERIES—COOLING MODE
HP-SERIES—COOLING MODE OPERATION / DESCRIPTION
EVAPORATOR
RETURN
![](/html/6d/6dc9/6dc9505020c222b604e64b543c4683dceb3dffe6fef405f01e7fe2b303da818d/bg7.png)
5
APPLICATIONS
HEATING MODE—HEAT PUMP
In HEAT mode, The HP-Series can be used in an open environment to provide heat
to a specific area or "spots". The HP-Series is a heat pump, and the supply air will
feel warm, but not extremely hot to the touch. Nozzle kits can be used for directional
heating.
OUTDOOR FAN DISCHARGE
“COLD”
RETURN AIR
GRILLE
AND FILTER
ELECTRONIC
CONTROLLER
INDOOR FAN
SUPPLY AIR
“HOT”
HP-SERIES—HEATING MODE
OUTDOOR AIR
INLET
(Back of Unit)
HP-SERIES—HEATING MODE OPERATION / DESCRIPTION
INDOOR AIR
![](/html/6d/6dc9/6dc9505020c222b604e64b543c4683dceb3dffe6fef405f01e7fe2b303da818d/bg8.png)
SERVICE CORD
All HP-Series-Series units are equipped with a standard 10-foot long service cord
with plug configurations and receptacle requirements as shown in this chart.
TC-12HP, TC-18HP, TC-24HP and TC-3612HP units come with LCDI (Leakage
Current Detection & Interruption) devices that serve as a means of electrical
protection.
CAUTION
DO NOT USE THE LCDI AS AN ON/OFF SWITCH FOR THE UNIT
All 3-phase models are equipped with locking plugs for added connection reliability.
Refer to the chart below for plug and receptacle details for all HP-Series models.
A DAMAGED LCDI POWER SUPPLY CORD MUST
BE REPLACED WITH A NEW POWER SUPPLY
CORD AND NOT REPAIRED
UNIT/MODEL PLUG CONFIGURATION RECEPTACLE
115 VOLT
TC-12HP
NEMA 5-15R
115 VOLT
TC-18HP
NEMA 5-20R
208-230 VOLT SINGLE PHASE
TC-24HP
NEMA 6-20R
208-230 VOLT SINGLE PHASE
TC-3612HP
NEMA 6-30R
208-230 VOLT SINGLE PHASE
TC-6021HP
NEMA 6-50R
208-230 VOLT 3-PHASE
TC-3623HP
TC-6023HP
NEMA L15-30R
460 VOLT 3-PHASE
TC-3643HP
TC-6043HP
NEMA L16-20R
15A-125 VOLT
NEMA 5-15P
20A-125 VOLT
NEMA 5-20P
20A-250 VOLT
NEMA 6-20P
30A-250 VOLT
NEMA 6-30P
50A-250 VOLT
NEMA 6-50P
30A-250 VOLT
NEMA L15-30P
20A-460 VOLT
NEMA L16-20P
6
ELECTRICAL CONFIGURATION
![](/html/6d/6dc9/6dc9505020c222b604e64b543c4683dceb3dffe6fef405f01e7fe2b303da818d/bg9.png)
USE OF EXTENSION CORDS
CAUTION
FOR MODEL TC-12HP AN EXTENSION CORD CAN BE USED, PROVIDED IT IS
RATED AT LEAST 15 AMPS @ 115 VOLTS WITH GROUNDING-TYPE
ATTACHMENT PLUG AND GROUNDING TYPE CONNECTOR (LOAD FITTING)
FOR MODEL TC-18HP AN EXTENSION CORD CAN BE USED, PROVIDED IT IS
RATED AT LEAST 20 AMPS @ 115 VOLTS WITH GROUNDING-TYPE
ATTACHMENT PLUG AND GROUNDING TYPE CONNECTOR (LOAD FITTING)
FOR MODEL TC-24HP AN EXTENSION CORD CAN BE USED, PROVIDED IT IS
RATED AT LEAST 20 AMPS @ 250 VOLTS WITH GROUNDING-TYPE
ATTACHMENT PLUG AND GROUNDING TYPE CONNECTOR (LOAD FITTING)
FOR MODEL TC-3612HP AN EXTENSION CORD CAN BE USED, PROVIDED IT
IS RATED AT LEAST 30 AMPS @ 250 VOLTS WITH GROUNDING-TYPE
ATTACHMENT PLUG AND GROUNDING TYPE CONNECTOR (LOAD FITTING)
FOR MODEL TC-6021HP AN EXTENSION CORD CAN BE USED, PROVIDED IT
IS RATED AT LEAST 50 AMPS @ 250 VOLTS WITH GROUNDING-TYPE
ATTACHMENT PLUG AND GROUNDING TYPE CONNECTOR (LOAD FITTING)
FOR MODELS TC-3623HP AND TC-6023HP AN EXTENSION CORD CAN BE
USED, PROVIDED IT IS RATED AT LEAST 30 AMPS @ 250 VOLTS, 3 PHASE
FOR MODELS TC-3643HP AND TC-6043 AN EXTENSION CORD CAN BE
USED, PROVIDED IT IS RATED AT LEAST 20 AMPS @ 600 VOLTS, 3 PHASE
SPECIAL NOTICE—THREE PHASE OPERATION
Models TC-3623HP, TC-3643HP, TC-6023HP and TC-6043HP
All three-phase HP-Series models are equipped with a three-phase monitor for added
compressor protection. The phase monitor, located in the control box, has a
multi-color LED that reports status. The monitor protects the compressor from
reverse operation, phase loss, and low voltage situations. Further description of the
three-phase monitor is located in the electrical section of this manual.
NOTICE - DO NOT OPERATE ANY THREE-PHASE UNIT WHILE BYPASSING
THE MONITOR. THIS WILL VOID THE WARRANTY.
7
![](/html/6d/6dc9/6dc9505020c222b604e64b543c4683dceb3dffe6fef405f01e7fe2b303da818d/bga.png)
8
MAXIMUM WATER LEVEL
4” FROM TOP OF TANK
This Side Up
FRONT
CONDENSATE TANK
“FULL” SWITCH
SPRING
CAP
HANDLE
WATER LEVEL
ADJUSTMENT
SCREW
HINGE
CONDENSATE TRAY
TANK LEVEL ADJUSTMENT INSTRUCTIONS
An adjustment screw is provided to vary the cut-off level of
the tank full switch. If less water is desired, turn the adjusting
screw clockwise (CW).
Turning the screw clockwise (CW),
will make the tank easier to remove.
MAXIMUM WATER LEVEL
4” FROM TOP OF TANK
CAUTION
UNPLUG UNIT BEFORE REMOVING
TANK TO ADJUST THE SET SCREW.
CONDENSATE
SUMP
TOP OF TANK
(WHEN PLACED IN UNIT)
SUMP DRAIN HOLE
“CON” WILL BE
DISPLAYED
CONDENSATE
For Models TC-12HP, TC-18HP, TC-24HP and TC-36HP, a 5-gallon polyethylene tank
is provided to collect condensate. The tank is located in the lower front section of the
unit, and can be accessed though the condensate tank door. When the high water level
is reached, a cut-out switch will AUTOMATICALLY cycle off the compressor/condenser
fan.
![](/html/6d/6dc9/6dc9505020c222b604e64b543c4683dceb3dffe6fef405f01e7fe2b303da818d/bgb.png)
CONDENSER
DISCHARGE
CONDENSER
RETURN
NOZZLE KIT
ROUND FLEX-DUCT
(SOLD SEPARATELY)
ROUND FLEX-DUCT
(SOLD SEPARATELY)
EVAPORATOR
RETURN AIR
PLENUM
CONDENSER
RETURN AIR
PLENUM
DISCHARGE DUCT
ADAPTER
CEILING
PANEL
KIT
(CK)
CEILING
PANEL
KIT
(CK-PL)
NOTE - IT IS IMPORTANT TO SPECIFY MODEL NUMBER AND SERIAL
NUMBER WHEN ORDERING ACCESSORIES
HP-Series ACCESSORIES
*NOTE: TC-36HP and TC-60HP come with 16” duct flanges.
DUCT
FLANGE*