PLEASE READ THIS MANUAL
BEFORE INSTALLING AND
USING APPLIANCE
WARNING!
IF THE INFORMATION IN THIS
MANUAL IS NOT FOLLOWED
EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING
PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF
LIFE.
FOR YOUR SAFETY
Installation and service must be
performed by a qualified installer, service agency or the
gas supplier.
supplier from your neighbor's
phone. Follow the gas suppliers
instructions.
• If you cannot reach your gas
supplier call the fire department.
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE
VAPORS AND LIQUIDS IN THE
VICINITY OF THIS OR ANY
OTHER APPLIANCE.
WARNING: Improper installation,
adjustment, alteration, service or
maintenance can cause injury or
property damage. Refer to this
manual. For assistance or additional
information, consult a qualified
installer, service agency or the gas
supplier.
Homeowner's Installation and
Operating Manual
U.S. Patents: 5,669,374; 5,562,088; 6,138,667: Can. Patent: 2,139,684
INSTALLER: DO NOT DISCARD THIS MANUAL - LEAVE FOR HOMEOWNER
77045 2/04 Rev. 28
Temco DV1000/1200/1400DSN/DSP Series
Table of Contents
PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING APPLIANCE.
Thank you and congratulations on your purchase of a Temco Fireplace Products fireplace.
While we have written these instructions as accurately and thoroughly as possible, they may not cover every system,
variation or contingency. Also, questions of interpretation may arise. For more information, solutions to particular
problems or clarifications, contact your local distributor or the manufacturer. See the unit rating plate for whom to
contact.
IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these
instructions may result in a possible fire hazard and will void the warranty.
Installation & Operating Instructions
Important Curing/Burning Instructions................................................................................3
Locating Your Fireplace .....................................................................................................3
This gas appliance should be installed by a qualified installer
in accordance with local building codes and with current CSA-B149.1 Installation codes for Gas Burning Appliances and
Equipment. For U.S.A Installations follow local codes and/or
the current National Fuel Gas Code. ANSI Z223.1/NFPA 54.
FOR SAFE INSTALLATION AND OPERATION
PLEASE NOTE THE FOLLOWING:
1 . This fireplace gives off high temperatures and should be
located out of high traffic areas and away from furniture
and draperies.
2.Children and adults should be alerted to the hazards of
the high surface temperatures of this fireplace and should
stay away to avoid burns or ignition of clothing.
3.Children should be carefully supervised when in the same
room as your fireplace.
4.Under no circumstances should this fireplace be modified.
Parts removed for servicing should be replaced prior to
operating this fireplace again.
5.Installation and any repairs to this fireplace must be
performed by a qualified installer, service agency or gas
supplier. A professional service person should be contacted to inspect this fireplace annually. Make it a practice
to have all of your gas fireplaces checked annually. More
frequent cleaning may be required due to excess lint and
dust from carpeting, bedding material, etc.
6.Control compartments, burners and air passages in this
fireplace should be kept clean and free of dust and lint.
Make sure the gas valve and pilot light are turned off
before you attempt to clean this fireplace.
7.The venting system (chimney) of this fireplace should be
checked at least once a year and if needed your venting
system should be cleaned.
8.Keep the area around your fireplace clear of combustible
materials, gasoline and other flammable vapor and liquids.
This fireplace should not be used as a drying rack for
clothing, nor should Christmas stocking or decorations be
hung in the area of it.
9.Under no circumstances should any solid fuels (wood,
coal, paper or cardboard etc.) be used in this fireplace.
10. For safe operation, the glass door must be closed.
11. Do not use this heater if any part has been under water.
Immediately call a qualified service technician to inspect
the heater and to replace any part of the control system
and any gas control which has been under water.
12. Do not operate appliance unless completely installed as
per installation instructions.
13. This appliance may be used in a bedroom installation.
Install in accordance with local building codes and
regulations.
14. Never use your fireplace as a cooking device.
This appliance may be installed in an aftermarket
permanently located, manufactured home or mobile
home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certified
kit is used.
IMPORTANT:
PLEASE READ THE FOLLOWING CAREFULLY
Remove any plastic from trim parts before turning the
fireplace ON.
It is normal for fireplaces fabricated of steel to give off
some expansion and/or contraction noises during the
start up or cool down cycle. Similar noises are found
with your furnace heat exchanger or car engine. It is
not unusual for your Temco Fireplace Products gas
fireplace to give off some odor the first time it is
burned. This is due to the manufacturing process.
Please ensure that your room is well ventilated
-open all windows.
It is recommended that you burn your fireplace for at
least four (4) hours the first time you use it. If the
optional fan kit has been installed, place the fan switch
in the “OFF” position during this time.
WARNING: When purging the gas line, the glass
front must be removed.
Locating Your Fireplace
LU584-1
Fig. 1 Locate gas fireplace.
A) Flat on wallB) Cross CornerC) As an Island
D) As a room dividerE) Flat on wall cornerF) Exterior wall
The embers supplied with your fireplace are made
from a high grade rock wool and should be
handled carefully. Wash your hands immediately
after touching to avoid irritation. The embers must
be placed correctly in order to function properly.
77045
Island installation is possible as long as the horizontal
portion of the vent system does not exceed maximum
recommended horizontal run as outlined in the venting
chart on Page 10. When you install your fireplace as in
position 'B', 'D' or 'E', (Fig. 1) a minimum of 1” (25mm)
clearance must be maintained from the perpendicular
wall and the front of the appliance.
3
Temco DV1000/1200/1400DSN/DSP Series
Fireplace Dimensions
Rough
Q
Opening
Depth
T
4" (102mm) Dia.
7" (178mm) Dia.
I
C
L
J
S - Rough Opening Width
Bottom Gas Line
Access
O
Q
Gas Line
Access
NOTE: Flex pipe diameters are
4” for inner pipe and 7” for outer
pipe.
1/2" (13mm)
P
J Box
Access
Rough
Opening
Height
B
N
K
L
M
Fig. 2 Fireplace specifications and framing dimensions.
S34¹⁄₂”(876mm)36”(914mm)42”(1067mm)
TRefer to Figure 3 or 4 for Rough Opening Depth
D
R
Framing Dimensions
G
C
H
E
F
K
J Box
Access
N
M
L
Gas
Line
Access
A
4
77045
1” (25mm) Minimum
Air Space Clearance
X
to Combustible
Materials
Vent“X”“X”“X”
System UsedDV1000DV1200 DV1400
TEMCO 4/7 Flex17¹⁄₂”18¹⁄₂”18¹⁄₂”
(445mm) (470mm) (470mm)
TEMCO 4/7 Rigid18¹⁄₂”19¹⁄₂”19¹⁄₂”
(470mm) (495mm) (495mm)
Duravent 4/6-5/8 GS17¹⁄₂”18¹⁄₂”18¹⁄₂”
(445mm) (470mm) (470mm)
Fig. 3 Minimum framing depths with vertical takeoff.
Firestop/Wall Sleeve
Combustible
Construction
Allowed
Standoff
VEF (Vinyl Siding)
or BEF (Brick)
Extension Flange
Vent Terminal
10³⁄₄"
(273mm)
Min.
D
C
Temco DV1000/1200/1400DSN/DSP Series
Framing and Finishing
1. Choose a fireplace location and frame in accordance with the fireplace dimensions specified on
Page 3 of this manual. When using a surround, the
fireplace must be flush to the wall. Also, allowances
must be made for drywall, tile or any other facing
used around the unit.
2. When the appliance is installed directly on carpeting, tile or other combustible material other than
wood flooring, the appliance shall be installed on a
metal or wood platform.
3. Pull out the nail tabs which are located on each side
of the fireplace. Move the fireplace into position and
secure to the floor with screws or nails through the
holes provided in the bottom flanges of the side
casing. After checking unit for squareness, secure
top of fireplace to the framing with screws or nails
using the nailing tabs provided.
4. Cold climate installation recommendation: when
installing this fireplace against a non-insulated
exterior wall or chase, it is recommended that the
outer walls be insulated to conform to applicable
insulation codes. Drywall should be installed around
the unit to prevent insulation from contacting the
body.
NOTE: Never let vapor barrier contact the outer
case of this fireplace or venting.
5. Drywall can be extended flush on the bottom, top
and to the outermost part of the sides of the fireplace.
6. Noncombustible materials such as brick and tile can
be extended across the face of the fireplace. If
brass trim kit is going to be installed, brick and tile
will have to be installed flush with the front of this
appliance.
A
NOTE: Maintain 2” (51mm) minimum clearance to combustibles
above vent and 1” (25mm) to sides and bottom of vent.
ModelABCD
DV1000 15³⁄₈” Min.30¹⁄₈”25³⁄₈”36¹⁄₈”
(391mm) (765mm) (645mm) (918mm)
DV1200 16¹⁄₂” Min.34³⁄₄”30”40³⁄₄”
(419mm) (883mm) (762mm) (1035mm)
DV1400 16¹⁄₂” Min.40³⁄₄”36”46³⁄₄”
(419mm) (1035mm) (914mm) (1188mm)
Fig. 4 Minimum framing dimensions with horizontal venting.
77045
B
2 x 4 or 2 x 6 Framing
Clearance to Combustibles
Top of unit to ceiling* ...............................36” (914mm)
Front of unit to combustibles ................... 36” (914mm)
Appliance
Top (from standoffs)................................0” (0mm)
Side (from standoffs)...............................0” (0mm)
Back (from standoffs) .............................. 0” (0mm)
Top of Elbow ......................................... 2” (51mm)
* Ceiling height is the minimum height of the room ceiling in front of
the fireplace measured from the top front edge of the fireplace.
Combustible Sidewall Clearance
The perpendicular combustible sidewall or mantel
support leg (surround) clearance is 1³⁄₄” (45mm) from
the edge of the recessed door opening.
5
Temco DV1000/1200/1400DSN/DSP Series
Mantels
The height that a combustible mantel is fitted above
the fireplace is dependent on the depth of the mantel.
For the correct mounting height and widths, refer to
Figure 5.
Noncombustible mantels and legs may be installed at
any height and width around the appliance. When
using paint or lacquer, it must be heat resistant to
prevent discoloration.
on a noncombustible mantel unless the noncombustible mantel meets the minimum height and width
requirements for a combustible mantel.
T177
Hearth
A hearth is not mandatory, but is recommended for
aesthetic purposes. We recommend a noncombustible
hearth projecting 12” (305mm) or more in front of the
fireplace.
Although a hearth is not mandatory, (as surface temperatures of combustibles are tested) surface temperatures of flooring (carpeting, tiel, varnish, etc.) may
reach a point where damage to some surfaces may
result.
For example:
• carpeting may buckle and discolor
• vinyl tile may discolor and unglue
• varnishes, waxes, etc. on wood flooring may dis-
color
Drywall
Noncombustible
Facing Material
Overlap of Front Face
Fig. 6 Surround material options.
Combustible Material
Minimum Height from
Top Opening to Mantel
Combustible Material
Above Standoff
Tile, Marble,
etc.
Fireplace
Front
Drywall
Flush Face Installation
(Recommended when
installing optional trim
surroun kits)
2 x 4 Stud
2 x 4 Header
Standoff
Tile,
Marble,
etc.
Optional
Surround
Kits
Fireplace
Front
T178
Surround Material
When using materials around the face of the fireplace,
these materials must be suitable to withstand the
temperatures which they will encounter. Also these
materials must not extend out in front of the face of the
unit, in effect recessing the unit.
If the material used for surround is not flush with the
face of the unit, then the optional surround kits will not
fit properly.
It is recommended that any material used to surround
the face of the fireplace be noncombustible (i.e. ceramic tile, brick, natural stone, etc.). Combustible
materials such as drywall, are permissible.
6
Optional Hearth
Fig. 7 Gas fireplace installation.
T178
Materials such as cultured marble or other synthetic
materials are not recommended as they may discolor,
warp or create odor as a result of exposure to the
temperatures of the front of the fireplace.
77045
Temco DV1000/1200/1400DSN/DSP Series
NOTE: Please remember this appliance produces
heat. All clearances are to combustible material and
are not intended to cover temperatures at which some
materials may discolor, warp or produce odor when
exposed to temperatures which this unit produces.
This gas appliance should be installed by a qualified
installer in accordance with local building codes and
with current CSA-B149.1 installation codes for Gas
Burning Appliances and Equipment in Canada and the
National Fuel Gas Code ANSI Z223.1/NFPA 54 in the
U.S.A.*
1. The gas pipeline can be brought in through the
bottom or the right or the left side of the appliance.
A hole is provided at all locations to allow for the
gas pipe installation and testing of any gas connection.
2. The gas control inlet is 3/8" NPT. Typical installation
layout for rigid pipe is shown on Page 8.
NOTE: All models are equipped with a flex tube
with a shut off valve having a 1/2” NPT inlet. The
flex line with shut off is shipped in the control
valve compartment. Using two wrenches,
tighten the flexible tube at the shut off valve and
at the gas control.
3. When using a flex connector,* use only approved
fittings. When a union is installed, provide easy
access in it’s placement for servicing. Refer to gas
specification for pressure details and ratings.
4. When a vertical section of gas pipe is required for
the installation, a condensation trap is needed. In
Canada see CSA - B149.1 for code details. See
the National Fuel Gas Code ANSI Z223.1/NFPA 54
in the USA.
5. For natural gas, a minimum of 3/8" iron pipe with a
gas supply pressure of 4.5" w.c. (from the gas
meter). Consult with local gas utility and
ANSI223.1/NFPA 54 if any questions arise concerning pipe sizes.
6. Turn the gas supply to 'ON' and check for leaks.
DO NOT USE OPEN FLAME FOR THIS PURPOSE. Use an approved leak testing solution.
7. The appliance and its appliance main gas valve
must be disconnected from the gas supply piping
system during any pressure testing of that system at
test pressures in excess of 1/2psig (3.5 KPa).
8. The appliance must be isolated from the gas supply
piping system by closing its equipment shut off
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than
1/2psig (3.5KPa).
NOTE: The gas line connection may be made of 3/8"
minimum rigid pipe, 3/8” minimum copper pipe or an
approved flex connector. Since some municipalities
have additional local codes, it is always best to consult
your local authorities and the current CSA-B149.1
installation code in Canada or National Fuel Gas Code
ANSI Z223.1/NFPA 54 in the U.S.A.
*Adhere to the following installation requirements in the State
of Massachusetts:
•The installer must be a licensed plumber or gas fitter.
•Flex connectors must be Massachusetts approved,
cannot exceed 36” (914mm) in length, must be a minimum 1/2” dia., and may not penetrate a wall.
1/2” Gas Supply
1/2” NPT x 1/2” Flare
Shut-off Valve
1/2” Flex Line
(from valve)
FP297a
Fig. 8 Typical gas supply installation.
IMPORTANT: Always check for gas leaks with a
soap and water solution. Do not use open flame
for leak testing.
77045
7
Temco DV1000/1200/1400DSN/DSP Series
Sediment Trap
A sediment trap shall be installed as close to the inlet
of the equipment as practicable at the time of equipment installation. The sediment trap shall be either a
tee fitting with a capped nipple in the bottom outlet as
shown below or other device recognized as an effective sediment trap.
Gas Supply Inlet
To
Equipment Inlet
Fig. 9 Sediment trap.
Nipple
Cap
Tee Fitting
3" (76mm)
Min.
T172
General Venting
Thermostatic Fan Kit - Optional
(Part # GDVTFK)
For installation of the optional fan, please refer to the
instructions included in the fan kit.
Electrical Services
Optional fan kits are equipped with a 120V, 60Hz
blower, less than 12 amps.
If electrical supply 120V is being roughed in to provide
for future installation of an optional blower kit, an
approved surface mount, steel electrical box, cover and
strain relief bushing must be installed in the fireplace
(supplied by others).
NOTE: All electric connections are to be made in
accordance with CSA Standard C22.1 - Canadian
Electrical Code part 1 or with the National Electrical
Code, ANSI/NFPA 70 (latest addition) and/or in accordance with local codes.
When locating the vent termination, the minimum vent
clearances must be observed. (Page 9, Fig. 10)
NOTE: Local codes may require different clearances.
It is recommended that the termination not be located
within 24" (305mm) of garden sheds, fences, decks,
utility buildings or other obstructions.
Do not locate termination cap where excessive snow or
ice build up may occur. Be sure to check vent termination area after snow falls and clear to prevent accidental blockage of venting system. When using snow
blowers, make sure snow is not directed towards vent
termination area.
This appliance has a "special vent system". Check with
local codes or in the absence of same, with CSA
B149.1 installation codes in Canada, or the current
National Fuel Gas Code ANSI Z223.1/NFPA 54 in the
USA, regarding special vent termination clearances.
These fireplaces are certified for use with four types of
venting systems
1. Temco 4” x 7” dia. flex vent.
2. Temco TDV series 4” x 7” dia. rigid vent.
3. Simpson Dura-Vent GS series 4” x 6⁵⁄₈” dia. vent.
4. Security Secure Vent series 4” x 6⁵⁄₈” dia. vent.
Review general venting information in this manual, and
information packed with the venting prior to starting the
installation of the fireplace.
• Termination shall not be recessed into a wall or
siding.
• Horizontal sections must maintain a minimum 1/4”
rise per linear foot of horizontal run.
• Combustible clearances from any horizontal vent
pipe area must be 2” (51mm) from top of vent, and
1” (25mm) from sides and bottom.
• Clearance to combustibles from vertical pipe sur-
face is 1” (25mm).
8
77045
Temco DV1000/1200/1400DSN/DSP Series
General Venting Information - Termination Location
INSIDE
CORNER DETAIL
G
V
D
E
V
A
H
N
N
CFM145a
B
V
L
VENT TERMINATION AIR SUPPLY INLET
V
C
Fixed
Fixed
V
Closed
Closed
F
Operable
V
B
B
V
Operable
B
X
B
Fixed
Closed
V
A
V
B
X
J
AREA WHERE TERMINAL IS NOT PERMITTED
Canadian Installations
G
V
M
I
1
K
V
US Installations
G
X
V
A
2
A = Clearance above grade, veranda, porch,12” (30cm)12” (30cm)
deck, or balcony
B = Clearance to window or door that may be12” (30cm) for appliances > 10,000 Btuh9” (23cm) for appliances > 10,000
opened(3kW) and < 100,000 Btuh (30kW)Btuh (3kW) and < 50,000 Btuh
(15kw)
C = Clearance to permanently closed window12” (305mm) recommended to9” (229mm) recommended to
D = Vertical clearance to ventilated soffit located
above the terminal within a horizontal18” (458mm)18” (458mm)
distance of 2 feet (610mm) from the center
line of the terminal
E = Clearance to unventilated soffit12” (305mm); 30” (762mm) min. for vinyl12” (305mm)
clad soffit
F = Clearance to outside cornersee next pagesee next page
G = Clearance to inside corner (see next page)see next pagesee next page
H = Clearance to each inside of center line3’ (91cm) within a height of 15’3’ (91cm) within a height of 15’
extended above meter/regulator assemblyabove the meter/regulator assemblyabove the meter/regulator assy
I = Clearance to service regulator vent outlet3’ (91cm)3’ (91cm)
J = Clearance to nonmechanical air supply inlet 12” (30cm) for appliances > 10,000 Btuh9” (23cm) for appliances > 10,000
to building or the combustion air inlet to any (3kW) and < 100,000 Btuh (30kW)Btuh (3kW) and < 50,000 Buth
other appliances(15Kw)
K = Clearance to a mechanical air supply inlet6’ (1.83m)3’ (91cm) above if within 10’
(3m) horizontally
L = Clearance above paved sidewalk or paved 7’ (2.13m)†7’ (2.13m)†
driveway located on public property
M = Clearance under veranda, porch, deck or18” (46cm)‡18” (46cm)‡
balcony
N = Clearance above a roof shall extend a minimum of 24” (610mm) above the highest point when it passes through the roof
surface, and any other obstruction within a horizontal distance of 18” (450mm).
1 In accordance with the current CSA-B149 Installation Codes
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes
† A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and
serves both dwellings
‡ only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor:
NOTE: 1. Local codes or regulations may require different clearances.
2. The special venting system used on Vermont Castings Direct Vent Stoves are certified as part of the appliance, with
clearances tested and approved by the listing agency.
Fig. 10 Vent termination clearances.
77045
9
Temco DV1000/1200/1400DSN/DSP Series
NOTE: Use only venting systems and components as
certified with the appliance. Use of uncertified vent
systems or components will void the warranty and may
compromise the operation of the fireplace, its systems,
and components as certified with the appliance.
03’
5’10’
15’
MILL-PAC
32’
30’
25’
15’
10’
46"
(1168mm)
(851mm)
5’
33¹⁄₂"
0
*Min. Refer to Chart on Page 5.
Fig. 11 Venting graph.
Top of Vent
2" (51mm)
1" (25mm)
Fig. 12 Vent clearances.
A vent guard should be used
whenever the termination is
*
lower than the specified
minimum or as per local
codes
Combustibles
NOT Allowed in
Shaded Area
1"
(25mm)
T180
4” Dia. Flue
7” Dia.
Intake
Vent
T181
MILL-PAC
NOTE:
Apply sealant “Mill-Pac” to inner pipe and “Mill-Pac” or high
temp silicone sealant to outer pipe. Sealant should be
applied at every joint in the vent system including at the
fireplace and at the vent terminal.
Fig. 13 Apply sealant at every joint in vent system.
Vent Cap
Gas Vent
Lowest Discharge Opening
H
x
12
Roof Pitch
is X/12
H (Min.) - Minimum height
from roof to lowest
discharge opening
T183
Roof PitchH (Min.)
Flat to 6/1212” (305mm)
6/12 to 7/1215” (381mm)
Over 7/12 to 8/1218” (457mm)
Over 8/12 to 16/1224” (610mm)
Over 16/12 to 21/1236” (914mm)
Fig. 14 Vertical termination location.
T182
10
77045
Temco DV1000/1200/1400DSN/DSP Series
Sidewall (General) Venting Information
Vent Opening for Combustible Wall
9³⁄₄"
(248mm)
5⁷⁄₈”
Min.
Fireplace Hearth
(149mm)
4⁷⁄₈”
(124mm)
Rnd.
If length "B" is increased,
length "A" must be decreased
by a corresponding amount
A vent guard should be used
whenever the termination is
lower than the specified
minimum or as per local
codes.
10³⁄₄"
(273mm)
Fireplace Hearth
Opening for Noncombustible Wall
8" Dia.
(203mm)
Fig. 15 Locate vent opening on wall.
2’ (610mm)
Minimum
Minimum
53" (1346mm)
Maximum
28’ (8.5m)
Fig. 16 Horizontal vent run.
33"
(838mm)
Figures 15 and 16 show examples of horizontal termination arrangements using two 90° elbows (Rigid
Vent).
NOTE:
1. A maximum of two 90° elbows are permitted.
2. A minimum of 10’ (3m) vertical from base of unit is
required if two 90° elbows are used.
3. Minimum distance between elbows is 2’ (610mm).
4. Determine the permitted range of horizontal termination arrangement by using chart above and
deducting 3’ (914mm) from the maximum horizontal
distance for the second 90° elbow.
Framing
Detail
12" (305mm)
B
Minimum
A
10’ (3m)
Minimum
VO584-100
T184
Flex Venting
•
Flex vent shall use the spacer springs as included
every foot to ensure proper vent operation.
• The 4” x 7” flex system may be used for all sidewall
applications and vertical venting up to 35’ (10.7m).
• Flex shall be properly supported so there are no
sags in the system. Supports must be used at least
every 24” (610mm) on horizontal section and every
36” (914mm) on vertical. Wire or metal stripping
may be used to support the venting.
• For 4” x 7” flex, the 7” flex has an outside diameter
of 7¹⁄₂” (191mm) and if installed in a chase the
inside diameter of the chase should be 9¹⁄₂”
(241mm) minimum.
• Lengths of co-axial flex may be joined together
using a flex connector kit (GFPVCK) only, maximum
1 kit per installation.
An extension collar is included with side wall cap kits
to simplify the connection of the flex pipe to the fireplace. Refer to Page 13, Figure 22.
ATTENTION: Spacer springs must be installed when
installing flexible venting systems.
Wrap spacer spring around flex flue pipe and overlap
spring ends approximately 2” (610mm). Tie one end
over the other like a shoelace tie, then reverse direction of spring ends. Lift up hooped spring and slide
both spring ends underneath hooped spring. Spring
spacers should be spaced at approximately 12”
(305mm) intervals for the length of pipe system. Once
the springs are placed around the flue pipe, slide the
flue section with spacer springs into the outer flex pipe.
Spacer
Springs
Flex Outer Vent
T185
Fig. 17 Wrap spacer spring around flex flue pipe, overlapping ends.
CAUTION: Care must be taken when
tightening clamps so the flex does not
tear at clamp location.
Flex Flue
77045
11
Temco DV1000/1200/1400DSN/DSP Series
Sidewall (Horizontal) Venting
For side wall (Horizontal) venting, this appliance is
approved for use with a 7" x 4" flexible venting system
with spacers.
Clearance to combustible material from the pipe is 1"
(25mm). Sides and bottom, 2” clearance from the top.
Note: O.D. of pipe is 7¹⁄₂" (191mm).
NOTE: HIGH WIND AREAS All termination caps are
tested and certified for wind conditions up to 40 mph
(64 k/h).
A Vinyl Extension Frame Kit No. VEF is required for all
installations where vinyl siding is used with the HFTK
Kit or HSQ47 Horizontal Vent Termination. If a Vinyl
Extension Frame Kit No. VEF is used, measure to
outside surface of wall without siding and add 2 additional inches (51mm) to the venting length.
A brick extension kit No. BEF is available to extend the
horizontal vent terminal HSQ47 or HFTK kit terminal
beyond the brick surface. If the BEF extension is used,
measure to the outside surface of the framed wall and
add 4 additional inches to the venting length.
Firestop/Wall Sleeve
(Included with HFTK)
GFP74FV3 (3’
(914mm) Flex Pipe
4” x 7” Dia.)
Vent Clamp
(Included
with HFTK)
A
Exterior Wall
VEF (or BEF)
Vinyl (or Brick)
Extension Flange
HFTK Vent
Termination Kit
B
NOTE: Typical terminal height “B” is 48” for model
DV1000, 60” for models DV1200 and DV1400 with
dimension “A” up to 36”. Please refer to minimum
framing dimensions with horizontal venting chart on
Page 5.
Fig. 18 Typical direct vent gas fireplace with horizontal
venting.
T176a
2. Assemble wall thimble with thimble extension flange
to top. Mate thimble to wall plate with the four tabs
provided. Bend tabs over to secure. (Fig. 19)
3. Install the wall thimble assembly through the framed
opening so the firestop plate is on the interior wall.
(Fig. 20) Telescope section should extend all the
way through wall.
Telescope Extension
Flex Vent Offsets
Each installation assumes the use of (1) 45° (bend)
starting off top of unit.
To determine the amount or length of flex vent you
need for a given installation, add the total offset dimension to the total rise needed. Then add 1 ft. (305mm)
for every 45° bend and/or 2’ (610mm) for each 90°
bend.
No more than (4) 90° and (2) 45° offsets are to be used
per installation. Vent terminal cap location should be in
accordance with the Venting Graph chart and the
Vertical Termination Location information.
1. Measure the total wall thickness. Determine whether
or not the thimble extension is needed. If the combustible wall depth is over 5” (127mm), the extension should be used. (Fig. 19)
12
T186
Fig. 19 The telescope extension must be used if wall
thickness is over 5” (127mm).
77045
Loading...
+ 26 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.