Telular TG-9 User Manual

Telguard® Digital Model TG-9
Digital Cellular Alarm Communicator
Installation and Operating Instructions
Important: Read Before Installing Model TG-9
Screwdriver and appropriate mounting screws
Confirm the presence of all required parts:
1x TG-9 Cellular Alarm Communicator
1x Dipole Antenna
6x End-Of-Line resistors
Before going to the site:
Fill out and submit the Telular TG-9 Digital Cellular Service Activation Form.
Fax the activation form to 678-945-1651 or submit the activation form on the internet at Telular.com
Note: Ensure that you have the correct wiring diagram for the selected TG-9
Operation Profile.
Technical Support: 800-229-2326
M-F 8:00AM – 8:00PM EST
Saturday 9:00 AM – 5:00 PM EST
April 27, 2007
56037002 - 1 - © 2007 Telular Corporation
Device Profile Options
The Telguard TG-9 Profile is stored in the Telular Communications Center and defines how each unit operates. One profile may be used for multiple units. The profile is uploaded to the Telguard TG-9 when it is activated, there is no field programming needed.
Trip and Restore Reporting
The TG-9 is programmed to send trips on all zones (not restorals). The profile can be set so that restores are transmitted. Changes will affect all trip zones.
Profile Options: Report Restoral / Do Not Report Restoral
Zone 1: Trip Input or Bell Input
Zone 1 on the TG-9 can be programmed as a normal trip input (default), or as a Bell Input. Bell input is ANSI standard Fire (3 rings, pause) and Burg (steady on).
Profile Options: Trip Input / Bell Input Note: Do not connect E.O.L. resistor if using bell input. Note: If using Bell input, Bell must be connected per Table 1 on page 5 before
activating. Make sure there are no Bell alarms in progress before activating.
Zone 6: Trip Input or Shunt
Zone 6 on the TG-9 can be used as a shunt (default) or as a normal trip input. When in shunt mode, a switch can be used to enable or disable alarm functions. When the switch is in an “ON or SHORTED” state alarm functions will be disabled.
Profile Options: Shunt / Trip Input
Report Shunt Activity / Do Not Report Shunt Activity
Zones 2 - 5: Trip inputs
Zones 2 - 5 are standard trip inputs.
Swinger Option
The TG-9 can be programmed for a swinger setting. Should a single zone trip more than X times in Y minutes, the system will send no more events for that zone until Z minutes have passed with no trips.
Profile Options: Swinger Option On / Off
Number of Events (1 – 99)
During Time Period (1 – 99 Minutes) Time to Restore (1 – 99 Minutes)
STC Trip Output
The STC trip output is a Normally Closed contact with four modes. Mode 1: It acts as a supervisory output, monitoring for No Cellular Service (NSC), Power Failure (PFC), Failure to Communicate (RFC), Mode 2: It acts as an alarm or bell driver, tripping the alarm system or sounding an alarm bell when a zone or zones on the TG-9 are tripped. Output will time out after 15 minutes.
Mode 3: It acts as an auxiliary output, which will close or open based on incoming signals. Mode 4: the output is disabled
Profile Options: Mode 1 / Mode 2 / Mode 3 / Mode 4
56037002 - 2 - © 2007 Telular Corporation
Loading...
+ 4 hidden pages