SIOX Climate Controller Module
is a general microprocessor controller
enhanced PLC programmability and
field bus communication. It
two analog outputs and two
ts. Analog input 1 handles voltage /
or thermistor input. Analog input 2
preconnected for thermistor input.
digital inputs, two outputs, two
relays and one alarm relay are
can work standalone or together with
SIOX I/O modules communicating
a common wire pair for climate
energy optimisation and alarm
SIOX Climate Controller with 2 relay outputs, four cable
and built-in NTC thermistor at AI2 for local temperature
SIOX Climate Controller with 3 relay outputs, 3-6 DI, 0-
AO. A 230 V mains transformer is included.
T05-3, SIOX Heat Exchange Controller with 4
SIOX Heat Ex change Controller w ith 4 relays, 5 DI, 2 AI,
2 AO and a Setpoint potentiometer / Mode button.
H:\T05\Man\T05man.wpd/2008-04-07/TF
T05 CLIMATE CONTROLLER MODULE p 2
328/287
.......................................
.................................................
............................................
............................................
Installation and Start-Up
...................................
..........................................
...........................................
...........................................
Analog Output Overrange / Underrange
............................................
.............................................
....................................
...........................................
SIOX Message Transfer for T05
..............................
.........................................
......................................
.......................................
Electrical Specifications
..................................
Environmental Specifications
..............................
Mechanical Specifications
.................................
..............................................
T05 CLIMATE CONTROLLER MODULE p 3
T05 is supplied with 18 V - 35 V DC via the two terminals marked “-/+
on the PC board corresponding to terminals 11/12 in the Block
above. The supply GND terminal is connected directly to the I/O GN D
and the Functional Earthing terminals. Alternatively, a 48 V supply
be connected between terminals 28 (+) and 27 (-), which renders DI6 un-
fuse must be provided on the positive supply with a rating of max
A, Quick Blow. The contacts of the two power relays can carry max 10 A at
230 V AC each, and must be externally fused with max 10 A,
Time Lag (Anti Surge), HRC (High Rupture Capacity) fuses.
T05 CLIMATE CONTROLLER MODULE p 4
can alternatively be powered from 230 V mains v ia a built-in transformer.
connection is shown on next page and must use a separate Pg16 cable
nd and include an external power switch and a fuse of max 10 A. The
of the two digital outputs are, howev er, limited to some 10 mA each by
the transformer capacity.
Installation and Start-Up
T05 is typically wall mounted using the four corner holes. This mounting
does not affect the IP 65 case sealing. Cables must be entered via cable
that are adequately tightened to prohibit the cords from being pushed
out of the unit. The unit is a Class II equipment intended for
Category II. Please follow the instructions described under “Safety
T05 CLIMATE CONTROLLER MODULE p 5
Typically, a two-wire, low capacitance twisted pair is used for the SIOX com-
bus. Shielded cables may be used but unless a correct strategy for
grounding is adopted, it may prove to be of little benefit. The total
resistance of the bus must be low, typically below 2 * 50
a proper supply and the SIOX bus have been connected, the com-
can be tested and operating modes and application PLC program
Unless otherwise requested, the module is preset at the factory to
at 4800 bits/s using address 01. General principles for the SIOX
and communications are described in a separate manual, the "SIOX
Description". Changes in operation modes are brought about by
Setup Strings communicated over the SIOX bus, described on page
are two ways of defining each of the 63 addresses for a T05 module,
through jumpers or by the internal EEPROM in the module. If any combi-
of jumpers except all six installed or all six removed is used at power-up,
the module will choose this jumper combination as the correct address.
= 00 : Illegal, will use EEPROM definition.
= 63 : Illegal, will use EEPROM definition.
= 25 : Valid address (16 + 8 + 1 = 25).
0/ - A5 contribute their values 1, 2, 4, 8, 16 and 32 when
the corresponding jumper is
jumpers installed would generate the invalid address 00, and all jumpers
would be equal to the "reserve" address 63. In this case, the module
checks its internal parameter
address number. Should none be
found, address 63 will be selected.
selected address, either from the jumpers or the EEPROM, is finally saved
and used for all subsequent communications until this
is changed or a new power-up is performed. Changing the RAM
can be done from the master or from the local PLC program in the
but make absolutely certai n to avoid collision with other modules on
T05 CLIMATE CONTROLLER MODULE p 6
special feature is added to help recover "lost" modules, i.e. when an unknown
rate and/or address is selected or the PLC runs a program that erroneously
parameters affecting the communication. To recover such a module,
carry out the following steps:
all address jumpers except for A0 and A1 but
from their normal position. Please refer to the figure below.
power. The module will now communicate at 4800 bits/s using
address 63 with the PLC and any options disabled.
Check and reconfigure the module for proper operation.
Restore correct jumper address.
analog outputs are controlled by values entered in two parameters hex
and provide pos it i ve voltages between 0 V and 10 V at loads up to 5
An individual control flag in parameter
V for either output to suit some types of valves etc.
Analog Output Overrange / Underrange
12-bit AO control range is hex
= 4097 values within 0 - 10
for both AO. AO2, however, being a 10-bit converter will set an output to one
1025 values within 0 to 10 V. This means that typically 4 consecutive 12-bit
- 0/0/0/7, in String Mode or double-byte Data Mode will
generate the same output. (Single-byte Data
Mode permits only 128 different
0/0/0/ - FFFF (or in Double Data Mode hex 2
3FFF) will set the output to zero (or 2 V if this offset is active).
0/0/0/ - 7FFF will set the output to 10 V.