Tektronix Series 2260B Multi-Range Programmable DC Power Supplies Programming Manual User manual

Page 1
2260B Series Multi-Range Programmable DC Power Supplies
Programming Manual
077104702 June 2022
tek.com/keithley
*P077104702*
077104702
Page 2
Series 2260B
Multi-Range Programmable DC Power Supplies
PROGRAMMING MANUAL
ISO-9001 CERTIFIED MANUFACTURER
Page 3
This manual contains proprietary information, which is protected by copyright. All rights are reserved. No part of this manual may be photocopied, reproduced or translated to another language without prior written consent.
The information in this manual was correct at the time of printing. However, we continue to improve our products and reserve the rights to change specification, equipment, and maintenance procedures at any time without notice.
Page 4
Table of Contents
Table of Contents
SAFETY INSTRUCTIONS .................................................. 2
GETTING STARTED .......................................................... 6
2260B Series Overview ............................................... 7
Appearance .............................................................. 10
Configuration Settings ............................................. 17
REMOTE CONTROL ....................................................... 23
Interface Configuration ............................................ 24
Socket Server Examples ............................................ 37
Command Syntax ..................................................... 41
Command List .......................................................... 45
Status Register Overview ......................................... 87
Error List .................................................................. 97
APPENDIX .................................................................... 106
2260B Default Settings ........................................... 107
Error Messages & Messages .................................. 109
LED Display Format ............................................... 110
INDEX .......................................................................... 111
1
Page 5
2260B Series Programming Manual
WARNING
Warning: Identifies conditions or practices that could result in injury or loss of life.
CAUTION
Caution: Identifies conditions or practices that could result in damage to the instrument or to other properties.
DANGER High Voltage
Attention Refer to the Manual
Protective Conductor Terminal
Earth (ground) Terminal

SAFETY INSTRUCTIONS

This chapter contains important safety instructions that you must follow during operation and storage. Read the following before any operation to insure your safety and to keep the instrument in the best possible condition.

Safety Symbols

These safety symbols may appear in this manual or on the instrument.
2
Page 6
SAFETY INSTRUCTIONS
Do not dispose electronic equipment as unsorted municipal waste. Please use a separate collection facility or contact the supplier from which this instrument was purchased.
General Guideline
CAUTION
Do not place any heavy object on the
instrument.
Avoid severe impact or rough handling that
leads to damaging the instrument.
Do not discharge static electricity to the
instrument.
Use only mating connectors, not bare wires, for
the terminals.
Do not block the cooling fan opening. Do not disassemble the instrument unless you
are qualified.
(Measurement categories) EN 61010-1:2010 and EN 61010-2-030 specify the measurement categories and their requirements as follows. The 2260B falls under category II.
Measurement category IV is for measurement performed at the
source of low-voltage installation.
Measurement category III is for measurement performed in the
building installation.
Measurement category II is for measurement performed on the
circuits directly connected to the low voltage installation.
0 is for measurements performed on circuits not directly
connected to Mains.
Power Supply
WARNING
To avoid electrical shock connect the protective
grounding conductor of the AC power cord to an earth ground.

Safety Guidelines

3
Page 7
2260B Series Programming Manual
Cleaning the Instrument
Disconnect the power cord before cleaning.
Use a soft cloth dampened in a solution of mild
detergent and water. Do not spray any liquid.
Do not use chemicals containing harsh material
such as benzene, toluene, xylene, and acetone.
Operation Environment
Location: Indoor, no direct sunlight, dust free,
almost non-conductive pollution (Note below)
Relative Humidity: 20%~ 85%
Altitude: < 2000m
Temperature: 0°C to 50°C
(Pollution Degree) EN 61010-1:2010 and EN 61010-2-030 specify the pollution degrees and their requirements as follows. The Instrument falls under degree 2.
Pollution refers to “addition of foreign matter, solid, liquid, or
gaseous (ionized gases), that may produce a reduction of dielectric strength or surface resistivity”.
Pollution degree 1: No pollution or only dry, non-conductive
pollution occurs. The pollution has no influence.
Pollution degree 2: Normally only non-conductive pollution
occurs. Occasionally, however, a temporary conductivity caused by condensation must be expected.
Pollution degree 3: Conductive pollution occurs, or dry, non-
conductive pollution occurs which becomes conductive due to condensation which is expected. In such conditions, equipment is normally protected against exposure to direct sunlight, precipitation, and full wind pressure, but neither temperature nor humidity is controlled.
Storage environment
Disposal
Do not dispose this instrument as unsorted municipal waste. Please use a separate collection facility or contact the supplier from which this instrument was purchased. Please make sure discarded electrical waste is properly recycled to reduce environmental impact.
4
Location: Indoor
Temperature: -15°C to 70°C
Relative Humidity: <90%
Page 8
SAFETY INSTRUCTIONS
Green/ Yellow:
Earth
Blue:
Neutral
Brown:
Live (Phase)

Power cord for the United Kingdom

When using the instrument in the United Kingdom, make sure the power cord meets the following safety instructions.
NOTE: This lead/appliance must only be wired by competent persons
WARNING: THIS APPLIANCE MUST BE EARTHED IMPORTANT: The wires in this lead are coloured in accordance with the following code:
As the colours of the wires in main leads may not correspond with the coloured marking identified in your plug/appliance, proceed as follows:
The wire which is coloured Green & Yellow must be connected to the Earth terminal marked with either the letter E, the earth symbol
or coloured Green/Green & Yellow.
The wire which is coloured Blue must be connected to the terminal which is marked with the letter N or coloured Blue or Black.
The wire which is coloured Brown must be connected to the terminal marked with the letter L or P or coloured Brown or Red.
If in doubt, consult the instructions provided with the equipment or contact the supplier.
This cable/appliance should be protected by a suitably rated and approved HBC mains fuse: refer to the rating information on the equipment and/or user instructions for details. As a guide, a cable of 0.75mm2 should be protected by a 3A or 5A fuse. Larger conductors would normally require 13A types, depending on the connection method used.
Any exposed wiring from a cable, plug or connection that is engaged in a live socket is extremely hazardous. If a cable or plug is deemed hazardous, turn off the mains power and remove the cable, any fuses and fuse assemblies. All hazardous wiring must be immediately destroyed and replaced in accordance to the above standard.
5
Page 9
2260B Series Programming Manual
2260B Series Overview ............................................... 7
Series lineup ......................................................................................... 7
Main Features ...................................................................................... 8
Appearance .............................................................. 10
2260B Front Panel ............................................................................ 10
Rear Panel ........................................................................................... 13
Configuration Settings ............................................. 17
Setting Configuration Settings ........................................................ 17
Configuration Table .......................................................................... 18

GETTING STARTED

This chapter describes the power supply in a nutshell, including its main features and front / rear panel introduction. After going through the overview, please read the theory of operation to become familiar with the operating modes, protection modes and other safety considerations.
6
Page 10
GETTING STARTED
Note
Throughout the user manual, 2260B-30, 2260B-80, 2260B-250 or 2260B-800 will refer to any of the 2260B models with a maximum voltage rating of 30V, 80V, 250V or 800V, respectively.
Model name
Type
Voltage Rating
Current Rating
Power
2260B-30-36
360W models
0~30V
0~36A
360W
2260B-80-13
360W models
0~80V
0~13.5A
360W
2260B-250-4
360W models
0~250V
0~4.5A
360W
2260B-800-1
360W models
0~800V
0~1.44A
360W
2260B-30-72
720W models
0~30V
0~72A
720W
2260B-80-27
720W models
0~80V
0~27A
720W
2260B-250-9
720W models
0~250V
0~9A
720W
2260B-800-2
720W models
0~800V
0~2.88A
720W
2260B-30-108
1080W models
0~30V
0~108A
1080W
2260B-80-40
1080W models
0~80V
0~40.5A
1080W
2260B-250-13
1080W models
0~250V
0~13.5A
1080W
2260B-800-4
1080W models
0~800V
0~4.32A
1080W

2260B Series Overview

Series lineup
The 2260B series consists of 12 models, divided into 3 different model types covering 3 power capacities: 360W models, 720W models and 1080W models.
7
Page 11
2260B Series Programming Manual
360 W models
720 W models
1080 W models
Performance
High performance/power Power efficient switching type power supply Low impact on load devices Fast transient recovery time of 1ms Fast output response time
Features
OVP, OCP and OTP protection Adjustable voltage and current slew rates User adjustable bleeder control to quickly
dissipate the power after shutdown to safe levels.
Extensive remote monitoring and control
options
Support for series* and parallel connections.
*(30, 80 volt models only)
Power on configuration settings. Web server monitoring and control
Apart from the differences in output, each unit differs in size. The 720W and 1080W models are larger than the 360W models to accommodate the increase in power.
Main Features
8
Page 12
GETTING STARTED
Interface
Ethernet port Analog connector for analog voltage and current
monitoring
USB host and device port
9
Page 13
2260B Series Programming Manual
Current knob
Output key
Power
switch
Voltage knob
USB A port
Display
Cover
panel
Function keys
2260B-30-108, 80-40, 250-13, 800-4 (1080W)
2260B-30-36, 80-13, 250-4, 800-1 (360W)
2260B-30-108 1080W

Appearance

2260B Front Panel
2260B-30-72, 80-27, 250-9, 800-2 (720W)
10
Page 14
GETTING STARTED
Function Keys
The Function keys along with the Output key will light up when a key is active.
The Function key is used to configure the power supply.
Set the overcurrent or overvoltage protection levels.
Sets the current and voltage limits.
Used to run customized Test sequence for testing.
Locks or unlocks the panel keys to prevent accidentally changing panel settings.
Toggles the display from viewing V/A V/W or A/W*. *Press the Voltage knob for V/W, press the Current knob for A/W.
Display Indicators
Voltage Slew Rate
Constant Voltage Mode
Remote Control Mode
Alarm on
Delay Output
Constant Current Mode
Current Slew Rate
Power bar Indicates the current power output
as a percentage.
VSR
C V
RMT
ALM
DLY
C C
ISR
20406080100
% W
11
Page 15
2260B Series Programming Manual
Voltage Knob
Sets the voltage.
Current Knob
Sets the current.
Output
Press to turn on the output. The Output key will light up when the output is active.
USB
The USB A port is used to update the firmware. The firmware can only be updated at a service center.
Power Switch
Used to turn the power on/off.
12
Page 16
GETTING STARTED
Output terminal (+)
Fan
Output terminal (-)
USB B port
LAN
AC Input
Sense­terminal
Analog control connector
LAN
100 240V
1000VA MAX.
AC 47 63Hz
SER.NO. LABEL
Sense+ terminal
Chassis ground
2260B-30-108, 80-40 (1080W)
2260B-30-36, 80-13 (360W)
100 240VAC
1500VA MAX.
47 63Hz
LAN
LN
SER.NO. LABEL
AC Input
LAN
100 240V
47 63Hz 500VA MAX.
AC
Rear Panel
2260B-30-72, 80-27 (720W)
13
Page 17
2260B Series Programming Manual
LAN
100 240V
1000VA MAX.
AC 47 63Hz
SER.NO. LABEL
V SN.C. S V
Output terminals +V
Fan
Chassis ground
USB B port
LAN
AC Input
Sense­terminal
Analog control connector
Sense+ terminal
Output terminals -V
2260B-250-13, 800-4 (1080W)
2260B-250-4, 800-1 (360W)
LAN
LN
SER.NO. LABEL
47 63Hz
1500VA MAX.
AC100 240V
V VSN.C. S
AC Input
LAN
100 240V
47 63Hz500VA MAX.
AC
V SN.C. S V
2260B-250-9, 800-2 (720W)
14
Page 18
GETTING STARTED
Analog Control Connector
Standard 26 pin MIL connector (OMRON XG4 IDC plug).
The analog control connector is used to monitor current and voltage output, machine status (OVP, OCP, OTP etc.), and for analog control of the current and voltage output.
Use an OMRON XG5 IDC socket as the mating socket.
Output Terminals (30, 80 volt models)
Positive (+) and negative (-) output terminals.
Chassis ground
Sense (-S) and Sense (+S) terminals.
Output Terminals (250, 800 volt models)
The 250 and 800 volt models use a 9 pin connector and a plug for the output and sense terminal connections. The plug is a MC420-38109Z plug by DECA SwitchLab Inc. This plug is also available separately.
V SN.C. S V
Positive (V+) and negative (V-) output terminals (3 of each).
V SN.C. S V
Chassis ground
V SN.C. S V
Sense (-S) and Sense (+S) terminals.
15
Page 19
2260B Series Programming Manual
USB B port
The USB B port is used for remote control.
Fans
Temperature controlled fans
Ethernet Port
The Ethernet port is used for remote control and digital monitoring from a PC.
Line Voltage Input
360W models: 2260B-30-36/80-13/250-4/ 800-1
720W models: 2260B-30-72/80-27/250-9/ 800-2
Voltage Input: 100~240 VAC
Line frequency: 50Hz/60 Hz
(Automatically switchable)
AC Input voltage range:
85VAC~265VAC
Frequency: 47Hz~63Hz
Line Voltage Input
1080W models: 2260B-30-108/80-40/250-13/800-4
Voltage Input: 100~240 VAC
Line frequency: 50Hz/60 Hz
(Automatically switchable)
LAN
LN
16
Page 20
GETTING STARTED
Background
The normal configuration settings (F-01~F-61, F-88, F-89) are used to configure or view system settings. Use the following operation steps when configuring the interface settings used in the Remote Control chapter on page 23.
Ensure the load is not connected.
Ensure the output is off.
Note
Configuration settings F-90~F-95 cannot be edited in the Normal Function Settings. See the user manual for details.
The F-89 settings can only be viewed, not set.
Steps
1. Press the Function key. The
function key will light up.
2. The display will show F-01
on the top and the configuration setting for F-01 on the bottom.
3. Rotate the Voltage knob to change
the F setting.
Voltage
Range
F-00~ F-61, F-88, F-89

Configuration Settings

Setting Configuration Settings
17
Page 21
2260B Series Programming Manual
4. Use the Current knob to set the
parameter for the chosen F setting.
Current
5. Press the Voltage knob to save the
configuration setting. Conf will be displayed when successful.
Exit
Press the Function key again to exit the configuration settings. The function key light will turn off.
Normal Function Settings
Setting
Setting Range
Output ON delay time
F-01
0.00s~99.99s
Output OFF delay time
F-02
0.00s~99.99s
V-I mode slew rate select
F-03
0 = CV high speed priority 1 = CC high speed priority 2 = CV slew rate priority 3 = CC slew rate priority
Rising voltage slew rate
F-04
0.01V/s~60.00V/s (2260B-30-XX)
0.1V/s~160.0V/s (2260B-80-XX)
0.1V/s~500.0V/s (2260B-250-XX) 1V/s~1600V/s (2260B-800-XX)
Falling voltage slew rate
F-05
0.01V/s~60.00V/s (2260B-30-XX)
0.1V/s~160.0V/s (2260B-80-XX)
0.1V/s~500.0V/s (2260B-250-XX) 1V/s~1600V/s (2260B-800-XX)
Voltage
Configuration Table
Please use the configuration settings listed below when applying the configuration settings.
18
Page 22
GETTING STARTED
Rising current slew rate
F-06
0.01A/s~72.00A/s (2260B-30-36)
0.1A/s~144.0A/s (2260B-30-72)
0.1A/s~216.0A/s (2260B-30-108)
0.01A/s~27.00A/s (2260B-80-13)
0.01A/s~54.00A/s (2260B-80-27)
0.01A/s~81.00A/s (2260B-80-40)
0.001A/s~9.000A/s (2260B-250-4)
0.01A/s~18.00A/s (2260B-250-9)
0.01A/s~27.00A/s (2260B-250-13)
0.001A/s~2.880A/s (2260B-800-1)
0.001A/s~5.760A/s (2260B-800-2)
0.001A/s~8.640A/s (2260B-800-4)
Falling current slew rate
F-07
0.01A/s~72.00A/s (2260B-30-36)
0.1A/s~144.0A/s (2260B-30-72)
0.1A/s~216.0A/s (2260B-30-108)
0.01A/s~27.00A/s (2260B-80-13)
0.01A/s~54.00A/s (2260B-80-27)
0.01A/s~81.00A/s (2260B-80-40)
0.001A/s~9.000A/s (2260B-250-4)
0.01A/s~18.00A/s (2260B-250-9)
0.01A/s~27.00A/s (2260B-250-13)
0.001A/s~2.880A/s (2260B-800-1)
0.001A/s~5.760A/s (2260B-800-2)
0.001A/s~8.640A/s (2260B-800-4)
Internal resistance setting
F-08
0.000~0.833(2260B-30-36)
0.000~0.417 (2260B-30-72)
0.000~0.278 (2260B-30-108)
0.000~5.926 (2260B-80-13)
0.000~2.963 (2260B-80-27)
0.000~1.975 (2260B-80-40)
0.00Ω~55.55Ω (2260B-250-4)
0.00Ω~27.77Ω (2260B-250-9)
0.00Ω~18.51Ω (2260B-250-13)
0.0Ω~555.5Ω (2260B-800-1)
0.0Ω~277.8Ω (2260B-800-2)
0.0Ω~185.1Ω (2260B-800-4)
Bleeder circuit control
F-09
0 = OFF, 1 = ON, 2 = AUTO
Buzzer ON/OFF control
F-10
0 = OFF, 1 = ON
Measurement Average Setting
F-17
0 = Low, 1 = Middle, 2 = High
19
Page 23
2260B Series Programming Manual
Lock Mode
F-19
0 = Panel lock: allow output off 1 = Panel lock: allow output on/off
USB/GPIB settings
Front panel USB State
F-20
0 = Absent, 1 = Mass Storage
Rear panel USB State
F-21
0 = Absent, 2 = USB-CDC, 3 = GPIB­USB adapter
Rear panel USB mode
F-22
0 = Disable, 1 = GPIB-USB adapter, 2 = USB CDC, Auto Detect Speed, 3 = USB CDC, Full Speed Only
GPIB address
F-23
0~30
LAN settings
MAC Address-1
F-30
0x00~0xFF
MAC Address-2
F-31
0x00~0xFF
MAC Address-3
F-32
0x00~0xFF
MAC Address-4
F-33
0x00~0xFF
MAC Address-5
F-34
0x00~0xFF
MAC Address-6
F-35
0x00~0xFF
LAN
F-36
0 = Disable, 1 = Enable
DHCP
F-37
0 = Disable, 1 = Enable
IP Address-1
F-39
0~255
IP Address-2
F-40
0~255
IP Address-3
F-41
0~255
IP Address-4
F-42
0~255
Subnet Mask-1
F-43
0~255
Subnet Mask-2
F-44
0~255
Subnet Mask-3
F-45
0~255
Subnet Mask-4
F-46
0~255
Gateway-1
F-47
0~255
Gateway-2
F-48
0~255
Gateway-3
F-49
0~255
Gateway-4
F-50
0~255
DNS address -1
F-51
0~255
DNS address -2
F-52
0~255
DNS address-3
F-53
0~255
DNS address-4
F-54
0~255
Sockets active
F-57
0 = Disable, 1 = Enable
Web Server active
F-59
0 = Disable, 1 = Enable
Web password active
F-60
0 = Disable, 1 = Enable
Web setting password
F-61
0000~9999
20
Page 24
GETTING STARTED
System Settings
Factory Set Value
F-88
0 = Disable 1 = Return to factory settings
Show Version
F-89
0, 1 = 2260B version 2, 3 = 2260B build year 4, 5 = 2260B build month/day 6, 7 = Keyboard CPLD version 8, 9 = Analog-Control CPLD version A, B = Reserved C, D = Kernel build year E, F = Kernel build month/day
Power On Configuration Settings*
CV Control
F-90
0 = Panel control (local) 1 = External voltage control 2 = External resistance control (Ext-R
10k = Vo, max)
3 = External resistance control (Ext-R
10k = 0)
CC Control
F-91
0 = Panel control (local) 1 = External voltage control 2 = External resistance control (Ext-R
10k = Io,max)
3 = External resistance control
(Ext-R 10k = 0)
Power-ON Output
F-92
0 = OFF at startup 1 = ON at startup T001 ~ T010 = Run Test Sequence TXX at start up
Master/Slave
F-93
0 = Master/Local 1 = Master/Parallel1 2 = Master/Parallel2 3 = Slave/Parallel 4 = Slave/Series (Only 30V, 80V models)
External Out Logic
F-94
0 = High ON, 1 = Low ON
Power Switch trip
F-95
0 = Enable , 1 = Disable
Calibration Settings*
Calibration
F-00
0000 ~ 9999
21
Page 25
2260B Series Programming Manual
*Note
Power On and Calibration settings can only be set during power up.
22
Page 26
REMOTE CONTROL
Interface Configuration ............................................ 24
USB Remote Interface ..................................................................... 24
Configure GPIB Interface ............................................................... 24
Configure Ethernet Connection..................................................... 26
Web Server Configuration ............................................................... 26
Sockets Server Configuration ......................................................... 27
USB Function Check........................................................................ 28
Web Server Remote Control Function Check ............................. 31
Socket Server Function Check ....................................................... 31
Socket Server Examples ............................................ 37
Visual Basic Example ....................................................................... 37
C++ Example .................................................................................... 38
LabVIEW Example .......................................................................... 40
Command Syntax ..................................................... 41
Command List .......................................................... 45
Status Register Overview ......................................... 87
Introduction to the Status Registers .............................................. 87
The Status Registers ......................................................................... 88
Questionable Status Register Group ............................................. 89
Operation Status Register Group ................................................... 91
Standard Event Status Register Group ......................................... 93
Status Byte Register & Service Request Enable Register ........... 95
Error List .................................................................. 97
Command Errors .............................................................................. 97
Execution Errors............................................................................. 101
Device Specific Errors ................................................................... 103
Query Errors .................................................................................... 104

REMOTE CONTROL

This chapter describes basic configuration of IEEE488.2 based remote control.
23
Page 27
2260B Series Programming Manual
USB configuration
PC side connector
Type A, host
2260B side connector
Rear panel Type B, slave
Speed
1.1/2.0 (full speed/high speed)
USB Class
CDC (communications device class)
Panel operation
1. Connect the USB cable to the rear
panel USB B port.
2. Press the Function key to enter the
Normal configuration settings.
Page 7
3. Set the following USB settings:
F-22 = 2
Set the rear panel USB port to USB-CDC.
Configure GPIB
1. Ensure the 2260B is off before proceeding.
2. Connect the USB cable from the rear panel
USB B port on the 2260B to the USB A port on the GPIB to USB adapter.

Interface Configuration

USB Remote Interface
Configure GPIB Interface
To use GPIB, the optional GPIB to USB adapter (2260B-GPIB-USB) must be used. The GPIB to USB adapter must be connected before the 2260B is turned on. Only one GPIB address can be used at a time.
24
Page 28
REMOTE CONTROL
3. Connect a GPIB cable from a GPIB controller to
the GPIB port on the adapter.
From Type B plug
on Power supply
Type A plug
From
computer
GPIB to USB adapter
4. Turn the 2260B on.
5. Press the Function key to enter the
Normal configuration settings.
Page 7
Set the following GPIB settings:
F-22 = 1
Set the rear panel USB port to GPIB-USB
F-23 = 0~30
Set the GPIB address (0~30)
GPIB constraints
Maximum 15 devices altogether, 20m cable
length, 2m between each device
Unique address assigned to each device
At least 2/3 of the devices turned On
No loop or parallel connection
25
Page 29
2260B Series Programming Manual
Ethernet configuration Parameters
MAC Address (display only)
LAN
DHCP
IP Address
Subnet Mask
Gateway
DNS Address
Sockets Active
Web Server Active
Web Password Active
Web set password
0000~9999 (default 0000)
Configuration
This configuration example will configure the 2260B as a web server and use DHCP to automatically assign an IP address to the 2260B.
Steps
1. Connect an Ethernet cable from the
network to the rear panel Ethernet port.
LAN
Configure Ethernet Connection
The Ethernet interface can be configured for a number of different applications. Ethernet can be configured for basic remote control or monitoring using a web server or it can be configured as a socket server.
The 2260B series supports DHCP connections so the instrument can be automatically connected to an existing network or alternatively, network settings can be manually configured.
Web Server Configuration
26
Page 30
REMOTE CONTROL
2. Press the Function key to enter the
Normal configuration settings.
Page 7
Set the following LAN settings:
F-36 = 1
Enable LAN
F-37 = 1
Turn DHCP to enable
F-59 = 1
Turn the web server on
Note
It may be necessary to cycle the power or refresh the web browser to connect to a network.
Configuration
This configuration example will configure the 2260B for web sockets control.
The following configuration settings will manually assign the 2260B an IP address and enable web sockets. By default, the socket port number is 2268 and cannot be configured.
Steps
1. Connect an Ethernet cable from the
network to the rear panel Ethernet port.
2. Press the Function key to enter the
Normal configuration settings.
Page 7
3. Set the following LAN settings:
F-36 = 1
Enable LAN
F-37 = 0
Disable DHCP
F-39 = 172
IP Address part 1 of 4
F-40 = 16
IP Address part 2 of 4
F-41 = 5
IP Address part 3 of 4
F-42 = 133
IP Address part 4 of 4
F-43 = 255
Subnet Mask part 1 of 4
F-44 = 255
Subnet Mask part 2 of 4
LAN
Sockets Server Configuration
27
Page 31
2260B Series Programming Manual
F-45 = 128
Subnet Mask part 3 of 4
F-46 = 0
Subnet Mask part 4 of 4
F-43 = 172
Gateway part 1 of 4
F-44 = 16
Gateway part 2 of 4
F-45 = 21
Gateway part 3 of 4
F-46 = 101
Gateway part 4 of 4
F-57 = 1
Enable Sockets
Note
The socket function is only available for firmware version V1.12 or above. See the user manual to check your firmware version number.
Background
To test the USB functionality, National Instruments Measurement and Automation Explorer can be used. This program is available on the NI website, www.ni.com., via a search for the VISA Run-time Engine page, or
“downloads” at the following URL,
http://www.ni.com/visa/
Requirements
Firmware: V1.12 or above Operating System: Windows XP, 7
Note
The 2260B will appear as a COM port on the PC.
To check the COM port No, see the Device Manager in the PC. For Win 7; Control panel
Hardware and Sound Device Manager.
Functionality check
1. Start the NI Measurement and Automation
Explorer (MAX) program. Using Windows, press:
Start>All Programs>National Instruments>Measurement & Automation
USB Function Check
28
Page 32
REMOTE CONTROL
2. From the Configuration panel access;
My System>Devices and Interfaces
2
3. Select "COM7".
4. Press Open VISA Test Panel.
3
4
Note
The displayed COM port No. may differ with the
29
Page 33
2260B Series Programming Manual
picture shown here. It depends on the virtual COM port number in your system. Here "COM7" is the Virtual COM port assigned to the 2260B.
5. Click the Configuration icon.
6. In the I/O Settings tab, select the Enable
Termination Character check box. Ensure Line Feed - \n is selected as the line feed character.
7. Click Apply Changes.
5
6
7
8. Click the Input/Output icon.
9. Ensure *IDN?\n is selected in the Select or
Enter Command dropdown text box.
10. Click the Query button.
11. The *IDN? query should be returned to the
buffer area:
30
Page 34
REMOTE CONTROL
8
9
11
10
Functionality check
Enter the IP address of the power supply in a web browser after the instrument has been configured as a web server
http:// XXX.XXX.XXX.XXX
The web browser interface appears.
Background
To test the socket server functionality, National Instruments Measurement and Automation Explorer can be used. This program is available on the NI website, www.ni.com., via a search for the VISA Run-time Engine page, or
“downloads” at the following URL,
http://www.ni.com/visa/
Web Server Remote Control Function Check
Socket Server Function Check
31
Page 35
2260B Series Programming Manual
Requirements
Firmware: V1.12 or above Operating System: Windows XP, 7
Functionality check
1. Start the NI Measurement and Automation
Explorer (MAX) program. Using Windows, press:
Start>All Programs>National Instruments>Measurement & Automation
2. From the Configuration panel access;
My System>Devices and Interfaces>Network Devices
3. Click Create New... .
4. Select Visa TCP/IP Resource.
2
3
4
32
Page 36
REMOTE CONTROL
5. Select Manual Entry of Raw Socket from the
popup window.
6. Click Next.
5
6
7. Enter the IP address and the port number of the
2260B. The port number is fixed at 2268.
8. Click the Validate button. A popup box will
appear when successful.
9. Click Next.
33
Page 37
2260B Series Programming Manual
8
9
7
10. Next configure the Alias (name) of the 2260B
connection. In this example the Alias is: PS_DC1
11. Click finish.
10
11
34
Page 38
REMOTE CONTROL
12. The IP address of the 2260B will now appear
under Network Devices in the configuration panel. Select this icon now.
13. Press Open VISA Test Panel.
13
12
14. Click Configuration icon.
15. In the I/O Settings tab, select the Enable
Termination Character check box. Ensure Line Feed - \n is selected as the line feed character.
16. Click Apply Changes.
14
15
16
35
Page 39
2260B Series Programming Manual
17. Click the Input/Output icon.
18. Ensure *IDN?\n is selected in the Select or Enter
Command dropdown text box.
19. Click the Query button.
20. The *IDN? query should be returned to the
buffer area.
17
18
19
20
36
Page 40
REMOTE CONTROL
Background
The following visual basic programming example uses the VISA COM 3.0 Type Library. The example will connect to the 2260B using the IP address of 172.15.5.133 over port 2268. The program will send the *IDN? query to the 2260B, print the return string and then close the connection.

Socket Server Examples

Visual Basic Example
37
Page 41
2260B Series Programming Manual
Background
The following program creates a connection to the 2260B and sets the voltage to 3.3 volts and the current 1.5 amps. The voltage and current reading is then read back and the connection is closed.
Note
Add visa32.lib to the project library when building the following sample program.
C++ Example
38
Page 42
REMOTE CONTROL
39
Page 43
2260B Series Programming Manual
Background
The following picture shows a LabView programming example for the 2260B.
LabVIEW Example
40
Page 44
REMOTE CONTROL
Compatible Standard
IEEE488.2
Partial compatibility
SCPI, 1999
Partial compatibility
Command Structure
SCPI commands follow a tree-like structure, organized into nodes. Each level of the command tree is a node. Each keyword in a SCPI command represents each node in the command tree. Each keyword (node) of a SCPI command is separated by a colon (:).
For example, the diagram below shows an SCPI sub-structure and a command example.
DC
MEASure
SCALar
POWer
VOLTage
CURRent
DC
DC
MEASure:SCALar:CURRent:DC?
Command types
There are a number of different instrument commands and queries. A command sends instructions or data to the unit and a query receives data or status information from the unit.
Command types
Simple
A single command with/without a parameter
Example
*IDN?

Command Syntax

41
Page 45
2260B Series Programming Manual
Query
A query is a simple or compound command followed by a question mark (?). A parameter (data) is returned.
Example
meas:curr:dc?
Compound
Two or more commands on the same command line. Compound commands are separated with either a semi­colon (;) or a semi-colon and a colon (;:).
A semi-colon is used to join two related commands, with the caveat that the last command must begin at the last node of the first command.
A semi-colon and colon are used to combine two commands from different nodes.
Example
meas:volt:dc?;:meas:curr:dc?
42
Page 46
REMOTE CONTROL
Command Forms
Commands and queries have two different forms, long and short. The command syntax is written with the short form of the command in capitals and the remainder (long form) in lower case.
The commands can be written in capitals or lower-case, just so long as the short or long forms are complete. An incomplete command will not be recognized.
Below are examples of correctly written commands.
Long form
STATus:OPERation:NTRansition? STATUS:OPERATION:NTRANSITION? status:operation:ntransition?
Short form
STAT:OPER:NTR? stat:oper:ntr?
Square Brackets
Commands that contain square brackets indicate that the contents are optional. The function of the command is the same with or without the square bracketed items, as shown below.
Both “DISPlay:MENU[:NAME]?” and “DISPlay:MENU?” are both valid forms.
Command Format
1.5,5.2
1 2 3 4 5
APPLY
1. Command header
2. Space
3. Parameter 1
4. Comma (no space
before/after comma)
5. Parameter 2
Parameters
Type
Description
Example
<Boolean>
Boolean logic
0, 1
43
Page 47
2260B Series Programming Manual
<NR1>
integers
0, 1, 2, 3
<NR2>
decimal numbers
0.1, 3.14, 8.5
<NR3>
floating point
4.5e-1, 8.25e+1
<NRf>
any of NR1, 2, 3
1, 1.5, 4.5e-1
<string>
String parameters are any ASCII characters (ASCII: 20H to 7EH) that are enclosed in either single or double quotes. For example: ‘STRING’ or “STRING”.
<block data>
Definitive length arbitrary block data. A single decimal digit followed by data. The decimal digit specifies how many 8-bit data bytes follow.
Message Terminator
LF
Line feed code
44
Page 48
REMOTE CONTROL
Abort Commands
ABORt ...................................................................................... 48
Apply Commands
APPLy ....................................................................................... 48
Display Commands
DISPlay:MENU[:NAME] ..................................................... 49
DISPlay[:WINDow]:TEXT:CLEar ..................................... 50
DISPlay[:WINDow]:TEXT[:DATA] .................................. 50
DISPlay:BLINk ....................................................................... 51
Initiate Commands
INITiate[:IMMediate]:NAME .............................................. 51
Measure Commands
MEASure[:SCALar]:CURRent[:DC] ................................... 52
MEASure[:SCALar]:VOLTage[:DC] ................................... 52
MEASure[:SCALar]:POWer[:DC] ....................................... 52
Output Commands
OUTPut:DELay:ON .............................................................. 53
OUTPut:DELay:OFF ............................................................ 53
OUTPut:MODE ..................................................................... 54
OUTPut[:STATe][:IMMediate] ............................................ 54
OUTPut[:STATe]:TRIGgered .............................................. 54
OUTPut:PROTection:CLEar ............................................... 55
OUTPut:PROTection:TRIPped .......................................... 55
Sense Commands
SENSe:AVERage:COUNt .................................................... 56
Status Commands
STATus:OPERation[:EVENt] ............................................. 57
STATus:OPERation:CONDition ........................................ 57
STATus:OPERation:ENABle .............................................. 57
STATus:OPERation:PTRansition ....................................... 58
STATus:OPERation:NTRansition ...................................... 58
STATus:QUEStionable[:EVENt] ........................................ 58
STATus:QUEStionable:CONDition................................... 59
STATus:QUEStionable:ENABle ......................................... 59
STATus:QUEStionable:PTRansition .................................. 59
STATus:QUEStionable:NTRansition ................................. 59
STATus:PRESet ...................................................................... 60

Command List

45
Page 49
2260B Series Programming Manual
Source Commands
[SOURce:]CURRent[:LEVel][:IMMediate][:AMPLitude] 61 [SOURce:]CURRent[:LEVel]:TRIGgered[:AMPLitude] . 62
[SOURce:]CURRent:PROTection[:LEVel] ........................ 62
[SOURce:]CURRent:PROTection:STATe ......................... 63
[SOURce:]CURRent:SLEW:RISing ..................................... 63
[SOURce:]CURRent:SLEW:FALLing................................. 64
[SOURce:]RESistance[:LEVel][:IMMediate][:AMPLitude]
.................................................................................................... 64
[SOURce:]VOLTage[:LEVel][:IMMediate][:AMPLitude]
.................................................................................................... 65
[SOURce:]VOLTage[:LEVel]:TRIGgered[:AMPLitude] . 65
[SOURce:]VOLTage:PROTection[:LEVel] ....................... 66
[SOURce:]VOLTage:SLEW:RISing .................................... 66
[SOURce:]VOLTage:SLEW:FALLing ................................ 67
Trigger Commands
TRIGger:TRANsient[:IMMediate] ...................................... 68
TRIGger:TRANsient:SOURce ............................................. 68
TRIGger:OUTPut[:IMMediate] ........................................... 69
TRIGger:OUTPut:SOURce .................................................. 69
System Commands
SYSTem:CONFigure:BEEPer[:STATe] ............................. 71
SYSTem:CONFigure:BLEeder[:STATe] ............................ 72
SYSTem:CONFigure:BTRip[:IMMediate] ......................... 72
SYSTem:CONFigure:BTRip:PROTection ......................... 72
SYSTem:CONFigure:CURRent:CONTrol ........................ 73
SYSTem:CONFigure:VOLTage:CONTrol ........................ 73
SYSTem:CONFigure:MSLave .............................................. 74
SYSTem:CONFigure:OUTPut:EXTernal[:MODE] ........ 74
SYSTem:CONFigure:OUTPut:PON[:STATe] ................. 75
SYSTem:COMMunicate:ENABle ........................................ 75
SYSTem:COMMunicate:GPIB[:SELF]:ADDRess ........... 76
SYSTem:COMMunicate:LAN:IPADdress ......................... 77
SYSTem:COMMunicate:LAN:GATEway ......................... 77
SYSTem:COMMunicate:LAN:SMASk ............................... 77
SYSTem:COMMunicate:LAN:MAC ................................... 78
SYSTem:COMMunicate:LAN:DHCP ................................ 78
SYSTem:COMMunicate:LAN:DNS.................................... 78
SYSTem:COMMunicate:LAN:HOSTname ....................... 79
SYSTem:COMMunicate:LAN:WEB:PACTive ................. 79
SYSTem:COMMunicate:LAN:WEB:PASSword ................... 79
SYSTem:COMMunicate:USB:FRONt:STATe .................. 80
SYSTem:COMMunicate:USB:REAR:STATe .................... 80
SYSTem:ERRor ....................................................................... 80
46
Page 50
REMOTE CONTROL
SYSTem:KEYLock:MODE ................................................. 80
SYSTem:KLOCk .................................................................... 81
SYSTem:INFormation ........................................................... 81
SYSTem:PRESet ..................................................................... 82
SYSTem:VERSion .................................................................. 82
Common Commands
*CLS .......................................................................................... 83
*ESE .......................................................................................... 83
*ESR .......................................................................................... 84
*IDN ......................................................................................... 84
*OPC ......................................................................................... 84
*RST .......................................................................................... 85
*SRE .......................................................................................... 85
*STB .......................................................................................... 85
*TRG ......................................................................................... 86
*TST .......................................................................................... 86
*WAI ......................................................................................... 86
47
Page 51
2260B Series Programming Manual
ABORt ...................................................................................... 48
ABORt
Description
The ABORt command will cancel any triggered actions.
Syntax
ABORt
APPLy ....................................................................................... 48
APPLy
Description
The APPLy command is used to set both the voltage and current. The voltage and current will be output as soon as the function is executed if the programmed values are within the accepted range. An execution error will occur if the programmed values are not within accepted ranges.
The Apply command will set the voltage/current values but these values will not be reflected on the display until the Output is On or if the DISPlay:MENU:NAME 3 (set menu) command is used.
Syntax
Query Syntax
APPLy {<voltage>|MIN|MAX}[,{<current>|MIN|MAX}]
APPLy?
Set
Set
Query
Abort Commands
APPLy Commands
48
Page 52
REMOTE CONTROL
Parameter
<voltage>
<NRf> 0% ~ 105% of the rated output voltage.
<current>
<NRf> 0% ~ 105% of the rated output current.
MIN
0 volts/0 amps
MAX
Maxium value for the present range.
Return parameter
<NRf>
Returns the voltage and current.
Example
APPL 5.05,1.1
Sets the voltage and current to 5.05V and 1.1A.
Query Example
APPL?
+5.050, +1.100
Returns voltage (5.05V) and current (1.1A) setting.
DISPlay:MENU[:NAME] ..................................................... 49
DISPlay[:WINDow]:TEXT:CLEar ..................................... 50
DISPlay[:WINDow]:TEXT[:DATA] .................................. 50
DISPlay:BLINk ....................................................................... 51
DISPlay:MENU[:NAME]
Description
The DISPlay MENU command selects a screen menu or queries the current screen menu.
Syntax
Query Sytax
DISPlay:MENU[:NAME] <NR1>
DISPlay:MENU[:NAME]?
Parameter/ Return parameter
<NR1>
Description
0
Measurement-Voltage / Measurement­Current
1
Measurement-Voltage / Measurement-Power
2
Measurement-Power / Measurement-Current
3
Set Menu
4
OVP / OCP Menu
5~99
Not Used.
100~199
F-00~99 Menu.
Set
Query
Display Commands
49
Page 53
2260B Series Programming Manual
Example
DISP:MENU:NAME 0
Sets the display to the Voltage/Current display screen.
DISPlay[:WINDow]:TEXT:CLEar
Description
Clears the text on the main screen from the DISPlay[:WINDow]:TEXT[:DATA] command .
Syntax
DISPlay[:WINDow]:TEXT:CLEar
DISPlay[:WINDow]:TEXT[:DATA]
Description
Sets or queries the data text that will be written to the display. Writing to the display will overwrite data that is currently on the screen. Overwriting a display area with a shorter string may or may not overwrite the screen. The string must be enclosed
in either single or double quotes: ‘STRING’ or “STRING”. Only ASCII characters 20H to 7EH can be used in the <string>. A null string, “”, can also
be used. This is the equivalent of using the DISPlay[:WINDow]:TEXT:CLEar function.
Syntax
Query Syntax
DISPlay[:WINDow]:TEXT[:DATA] <string>
DISPlay[:WINDow]:TEXT[:DATA]?
Parameter/ Return parameter
<string>
ASCII characters 20H to 7EH or a null string, “”, can be used in the string parameter.
Example
DISP:WIND:TEXT:DATA ‘STRING’
Writes STRING to the display.
Query Example
DISP:WIND:TEXT:DATA?
STRING
Returns the text data string on the screen.
Set
Set
Query
50
Page 54
REMOTE CONTROL
DISPlay:BLINk
Description
Turns blink on or off for the display.
Syntax
Query Syntax
DISPlay:BLINk { 0 | 1 | OFF | ON }
DISPlay:BLINk?
Parameter
0
<NR1>Turns blink OFF
OFF
Turns blink OFF
1
<NR1> Turns blink ON
ON
Turns blink ON
Return parameter
0
<NR1>Turns blink OFF
1
<NR1>Turns blink ON
Example
DISP:BLIN 1
Turns blink ON.
INITiate[:IMMediate]:NAME .............................................. 51
INITiate[:IMMediate]:NAME
Description
The INITiate command starts the TRANsient or OUTPut trigger.
Syntax
INITiate[:IMMediate]:NAME {TRANsient|OUTPut}
Parameter TRANSient
Starts the TRANsient trigger.
OUTPut
Starts the OUTPut trigger.
Example
INITiate:NAME TRANient
Starts the TRANSient trigger.
Set
Query
Set
Initiate Commands
51
Page 55
2260B Series Programming Manual
MEASure[:SCALar]:CURRent[:DC] ................................... 52
MEASure[:SCALar]:VOLTage[:DC] ................................... 52
MEASure[:SCALar]:POWer[:DC] ....................................... 52
MEASure[:SCALar]:CURRent[:DC]
Description
Takes a measurement and returns the average output current
Syntax
MEASure[:SCALar]:CURRent[:DC]?
Return parameter
<NRf>
Returns the current in amps.
MEASure[:SCALar]:VOLTage[:DC]
Description
Takes a measurement and returns the average output voltage.
Syntax
MEASure[:SCALar]:VOLTage[:DC]?
Return
<NRf>
Returns the voltage in volts.
MEASure[:SCALar]:POWer[:DC]
Description
Takes a measurement and returns the average output power.
Syntax
MEASure[:SCALar]:POWer[:DC]?
Return
<NRf>
Returns the power measured in watts.
Query
Query
Query
Measure Commands
52
Page 56
REMOTE CONTROL
OUTPut:DELay:ON .............................................................. 53
OUTPut:DELay:OFF ............................................................ 53
OUTPut:MODE ..................................................................... 54
OUTPut[:STATe][:IMMediate] ............................................ 54
OUTPut[:STATe]:TRIGgered .............................................. 54
OUTPut:PROTection:CLEar ............................................... 55
OUTPut:PROTection:TRIPped .......................................... 55
OUTPut:DELay:ON
Description
Sets the Delay Time in seconds for turning the output on. The delay is set to 0.000 by default.
Syntax
Query Syntax
OUTPut:DELay:ON <NRf>
OUTPut:DELay:ON?
Parameter
<NRf>
0.00~99.99 seconds, where 0=no delay.
Return parameter
<NRf>
Returns the delay on time in seconds until the output is turned on.
OUTPut:DELay:OFF
Description
Sets the Delay Time in seconds for turning the output off. The delay is set to 0.000 by default.
Syntax
Return Syntax
OUTPut:DELay:OFF <NRf>
OUTPut:DELay:OFF?
Parameter
<NRf>
0.00~99.99 seconds, where 0=no delay.
Return parameter
<NRf>
Returns the delay off time in seconds until the output is turned off.
Set
Query
Set
Query
Output Commands
53
Page 57
2260B Series Programming Manual
OUTPut:MODE
Description
Sets the 2260B output mode. This is the equivalent to the F-03 (V-I Mode Slew Rate Select) settings.
Syntax
Return Syntax
OUTPut:MODE {<NR1>|CVHS|CCHS|CVLS|CCLS}
OUTPut:MODE?
Parameter
0
CV high speed priority
CVHS
CV high speed priority
1
CC high speed priority
CCHS
CC high speed priority
2
CV slew rate priority
CVLS
CV slew rate priority
3
CC slew rate priority
CCLS
CC slew rate priority
Return parameter
<NR1>
Returns the output mode.
OUTPut[:STATe][:IMMediate]
Description
Turns the output on or off.
Syntax
Query Syntax
OUTPut[:STATe][:IMMediate] { OFF | ON | 0 | 1 }
OUTPut[:STATe][:IMMediate]?
Parameter
0
<NR1> Turns the output off.
OFF
Turns the output off.
1
<NR1> Turns the output on.
ON
Turns the output on.
Return parameter
<NR1>
Returns output status of the instrument.
OUTPut[:STATe]:TRIGgered
Description
Turns the output on or off when a software trigger is generated.
Syntax
Query Syntax
OUTPut[:STATe]:TRIGgered { OFF | ON | 0 | 1 }
OUTPut[:STATe]:TRIGgered?
Set
Query
Set
Query
Set
Query
54
Page 58
REMOTE CONTROL
Parameter
0
<NR1>Turns the output off when a software trigger is generated.
OFF
Turns the output off when a software trigger is generated.
1
<NR1>Turns the output on when a software trigger is generated.
ON
Turns the output on when a software trigger is generated.
Return parameter
<NR1>
Returns output trigger status of the instrument.
OUTPut:PROTection:CLEar
Description
Clears over-voltage, over-current and over­temperature (OVP, OCP, OTP) protection circuits. It also clears the shutdown protection circuit. The AC failure protection cannot be cleared.
Syntax
OUTPut:PROTection:CLEar
OUTPut:PROTection:TRIPped
Description
Returns the state of the protection circuits (OVP, OCP, OTP).
Query Syntax
OUTPut:PROTection:TRIPped?
Return parameter
0
<NR1>Protection circuits are not tripped.
1
<NR1>Protection circuits are tripped.
Set
Query
55
Page 59
2260B Series Programming Manual
SENSe:AVERage:COUNt .................................................... 56
SENSe:AVERage:COUNt
Description
Determines the level of smoothing for the average setting. This is the equivalent to the F-17 function setting.
Syntax
Query Syntax
SENSe:AVERage:COUNt {<NR1>| LOW | MIDDle | HIGH}
SENSe:AVERage:COUNt?
Parameter
0 | LOW
Low level of smoothing.
1 | MIDDle
Middle level of smoothing.
2 | HIGH
High level of smoothing.
Return parameter
<NR1>
Returns the level of smoothing.
0
Low level of smoothing.
1
Middle level of smoothing.
2
High level of smoothing.
Example
SENSe:AVERage:COUNt 1
Sets the level of smoothing to middle.
Set
Query
Sense Commands
56
Page 60
REMOTE CONTROL
STATus:OPERation[:EVENt] ............................................. 57
STATus:OPERation:CONDition ........................................ 57
STATus:OPERation:ENABle .............................................. 57
STATus:OPERation:PTRansition ....................................... 58
STATus:OPERation:NTRansition ...................................... 58
STATus:QUEStionable[:EVENt] ........................................ 58
STATus:QUEStionable:CONDition................................... 59
STATus:QUEStionable:ENABle ......................................... 59
STATus:QUEStionable:PTRansition .................................. 59
STATus:QUEStionable:NTRansition ................................. 59
STATus:PRESet ...................................................................... 60
STATus:OPERation[:EVENt]
Description
Queries the Operation Status Event register and
clears the contents of the register.
Syntax
STATus:OPERation[:EVENt]?
Return
<NR1>
Returns the bit sum of the Operation Status Event register.
STATus:OPERation:CONDition
Description
Queries the Operation Status register. This query will not clear the register.
Syntax
STATus:OPERation:CONDition?
Return
<NR1>
Returns the bit sum of the Operation Condition register.
STATus:OPERation:ENABle
Description
Sets or queries the bit sum of the Operation Status Enable register.
Syntax
Query Syntax
STATus:OPERation:ENABle <NRf>
STATus:OPERation:ENABle?
Query
Query
Set
Query
Status Commands
57
Page 61
2260B Series Programming Manual
Parameter
<NRf>
0~32767
Return parameter
<NR1>
0~32767
STATus:OPERation:PTRansition
Description
Sets or queries the bit sum of the positive transition filter of the Operation Status register.
Syntax
STATus:OPERation:PTRansition <NRf>
STATus:OPERation:PTRansition?
Parameter
<NRf>
0~32767
Return parameter
<NR1>
0~32767
STATus:OPERation:NTRansition
Description
Sets or queries the bit sum of the negative transition filter of the Operation Status register.
Syntax
Query Syntax
STATus:OPERation:NTRansition <NRf>
STATus:OPERation:NTRansition?
Parameter
<NRf>
0~32767
Return parameter
<NR1>
0~32767
STATus:QUEStionable[:EVENt]
Description
Queries the bit sum of the Questionable Status Event register. This query will also clear the contents of the register.
Query Syntax
STATus:QUEStionable[:EVENt]?
Parameter
<NRf>
0~32767
Return parameter
<NR1>
0~32767
Set
Query
Set
Query
Query
58
Page 62
REMOTE CONTROL
STATus:QUEStionable:CONDition
Description
Queries the status (bit sum) of the Questionable Status register. This query will not clear the register.
Query Syntax
STATus:QUEStionable:CONDition?
Parameter
<NRf>
0~32767
Return parameter
<NR1>
0~32767
STATus:QUEStionable:ENABle
Description
Sets or queries the bit sum of the Questionable Status Enable register.
Syntax
Query Syntax
STATus:QUEStionable:ENABle <NRf>
STATus:QUEStionable:ENABle?
Parameter
<NRf>
0~32767
Return parameter
<NR1>
0~32767
STATus:QUEStionable:PTRansition
Description
Sets or queries the bit sum of the positive transition filter of the Questionable Status register.
Syntax
Return Syntax
STATus:QUEStionable:PTRansition <NRf>
STATus:QUEStionable:PTRansition?
Parameter
<NRf>
0~32767
Return parameter
<NR1>
0~32767
STATus:QUEStionable:NTRansition
Description
Sets or queries the negative transition filter of the Questionable Status register.
Syntax
Query Syntax
STATus:QUEStionable:NTRansition <NRf>
STATus:QUEStionable:NTRansition?
Query
Set
Query
Set
Query
Set
Query
59
Page 63
Parameter
<NRf>
0~32767
Return parameter
<NR1>
0~32767
STATus:PRESet
Description
This command resets the ENABle register, the PTRansistion filter and NTRansistion filter on the Operation Status and Questionable Status Registers. The registers/filters will be reset to a default value.
Default Register/Filter Values
Setting
QUEStionable Status Enable
0x0000
QUEStionable Status Positive Transition
0x7FFF
QUEStionable Status Negative Transition
0x0000
Operation Status Enable
0x0000
Operation Status Positive Transition
0x7FFF
Operation Status Negative Transition
0x0000
Summary: The Questionable Status Enable registers and the Operation Status Enable registers are both reset to 0.
The Questionable Status and Operation Status Positive Transition filters are all set high (0x7FFF) and the Negative Transition filters are all set low (0x0000). I.e., only positive transitions will be recognized for the Questionable Status and Operation Status registers.
Syntax
STATus:PRESet
Set
2260B Series Programming Manual
60
Page 64
REMOTE CONTROL
[SOURce:]CURRent[:LEVel][:IMMediate][:AMPLitude]
.................................................................................................... 61
[SOURce:]CURRent[:LEVel]:TRIGgered[:AMPLitude]
.................................................................................................... 62
[SOURce:]CURRent:PROTection[:LEVel] ........................ 62
[SOURce:]CURRent:PROTection:STATe ......................... 63
[SOURce:]CURRent:SLEW:RISing ..................................... 63
[SOURce:]CURRent:SLEW:FALLing ................................ 64
[SOURce:]RESistance[:LEVel][:IMMediate]
[:AMPLitude] ........................................................................... 64
[SOURce:]VOLTage[:LEVel][:IMMediate][:AMPLitude]
.................................................................................................... 65
[SOURce:]VOLTage[:LEVel]:TRIGgered[:AMPLitude]
.................................................................................................... 65
[SOURce:]VOLTage:PROTection[:LEVel] ....................... 66
[SOURce:]VOLTage:SLEW:RISing .................................... 66
[SOURce:]VOLTage:SLEW:FALLing ................................ 67
[SOURce:]CURRent[:LEVel][:IMMediate] [:AMPLitude]
Description
Sets or queries the current level in amps. For externally set current levels (from the analog control connector) the set current level is returned.
Syntax
[SOURce:]CURRent[:LEVel][:IMMediate][:AMPLitude] {<NRf>|MIN|MAX}
Query Syntax
[SOURce:]CURRent[:LEVel][:IMMediate][:AMPLitude]? [MIN|MAX]
Parameter/Return
<NRf>
0~105% of the rated current output level.
MIN
Minimum current level.
MAX
Maximum current level.
Example
SOUR:CURR:LEV:IMM:AMPL? MAX
37.800
Returns the maximum possible current level in amps.
Set
Query
Source Commands
61
Page 65
2260B Series Programming Manual
[SOURce:]CURRent[:LEVel]:TRIGgered [:AMPLitude]
Description
Sets or queries the current level in amps when a software trigger has been generated.
Syntax
[SOURce:]CURRent[:LEVel]:TRIGgered[:AMPLitude] {<NRf>|MIN|MAX}
Query Syntax
[SOURce:]CURRent[:LEVel]:TRIGgered[:AMPLitude]? [MIN|MAX]
Parameter/Return
<NRf>
0%~105% of the rated current output in amps.
MIN
Minimum current level.
MAX
Maximum current level.
Example
SOUR:CURR:LEV:TRIG:AMPL? MAX
37.800
Returns the maximum possible current level in amps.
[SOURce:]CURRent:PROTection[:LEVel]
Description
Sets or queries the OCP (over-current protection) level in amps.
Syntax
[SOURce:]CURRent:PROTection[:LEVel] {<NRf>|MIN|MAX}
Query Syntax
[SOURce:]CURRent:PROTection[:LEVel]? [MIN|MAX]
Parameter/Return
<NRf>
10%~110% of the rated current output level.
MIN
Minimum current level.
MAX
Maximum current level.
Example
SOUR:CURR:PROT:LEV? MIN
+3.600
Returns the minimum possible current level in amps.
Set
Query
Set
Query
62
Page 66
REMOTE CONTROL
[SOURce:]CURRent:PROTection:STATe
Description
Turns OCP (over-current protection) on or off.
Syntax
[SOURce:]CURRent:PROTection:STATe {0|1|OFF|ON}
Query Syntax
[SOURce:]CURRent:PROTection:STATe?
Parameter/Return
0
<NR1> Turns the buzzer off.
OFF
Turns the buzzer off.
1
<NR1> Turns the buzzer on.
ON
Turns the buzzer on.
Return parameter
<Bool>
Returns bleeder resistor status (0 or 1).
Example
SOUR:CURR:PROT:STAT OFF
Turns OCP off.
[SOURce:]CURRent:SLEW:RISing
Description
Sets or queries the rising current slew rate. This is only applicable for CC slew rate priority mode.
Syntax
Query Syntax
[SOURce:]CURRent:SLEW:RISing {<NRf>|MIN|MAX}
[SOURce:]CURRent:SLEW:RISing? [MIN|MAX]
Parameter/Return
<NRf>
0.01A/s~72.00A/s (2260B-30-36)
0.1A/s~144.0A/s (2260B-30-72)
0.1A/s~216.0A/s (2260B-30-108)
0.01A/s~27.00A/s (2260B-80-13)
0.01A/s~54.00A/s (2260B-80-27)
0.01A/s~81.00A/s (2260B-80-40)
0.001A/s~9.000A/s (2260B-250-4)
0.01A/s~18.00A/s (2260B-250-9)
0.01A/s~27.00A/s (2260B-250-13)
0.001A/s~2.880A/s (2260B-800-1)
0.001A/s~5.760A/s (2260B-800-2)
0.001A/s~8.640A/s (2260B-800-4)
MIN
Minimum rising current slew rate.
MAX
Maximum rising current slew rate.
Example
SOUR:CURR:SLEW:RIS 72
Sets the rising current slew rate to 72A/s.
Set
Query
Set
Query
63
Page 67
2260B Series Programming Manual
[SOURce:]CURRent:SLEW:FALLing
Description
Sets or queries the falling current slew rate. This is only applicable for CC slew rate priority mode.
Syntax
[SOURce:]CURRent:SLEW:FALLing {<NRf>|MIN|MAX}
Query Syntax
[SOURce:]CURRent:SLEW:FALLing? [MIN|MAX]
Parameter/Return
NRf
0.01A/s~72.00A/s (2260B-30-36)
0.1A/s~144.0A/s (2260B-30-72)
0.1A/s~216.0A/s (2260B-30-108)
0.01A/s~27.00A/s (2260B-80-13)
0.01A/s~54.00A/s (2260B-80-27)
0.01A/s~81.00A/s (2260B-80-40)
0.001A/s~9.000A/s (2260B-250-4)
0.01A/s~18.00A/s (2260B-250-9)
0.01A/s~27.00A/s (2260B-250-13)
0.001A/s~2.880A/s (2260B-800-1)
0.001A/s~5.760A/s (2260B-800-2)
0.001A/s~8.640A/s (2260B-800-4)
MIN
Minimum falling current slew rate
MAX
Maximum falling current slew rate
Example
SOUR:CURR:SLEW:FALL 1
Sets the falling current slew rate to 1A/s.
[SOURce:]RESistance[:LEVel][:IMMediate] [:AMPLitude]
Description
Sets or queries the internal resistance in ohms.
Syntax
[SOURce:]RESistance[:LEVel][:IMMediate][:AMPLitude] {<NRf>|MIN|DEF|MAX|?}
Query Syntax
[SOURce:]RESistance[:LEVel][:IMMediate][:AMPLitude] ? [MIN|MAX]
Set
Query
Set
Query
64
Page 68
REMOTE CONTROL
Parameter/Return
<NRf>
Resistance in ohms:
0.000Ω~0.833Ω (2260B-30-36)
0.000Ω~0.417Ω (2260B-30-72)
0.000Ω~0.278Ω (2260B-30-108)
0.000Ω~5.926Ω (2260B-80-13)
0.000Ω~2.963Ω (2260B-80-27)
0.000Ω~1.975Ω (2260B-80-40)
0.00Ω~ 55.55Ω (2260B-250-4)
0.00Ω~ 27.77Ω (2260B-250-9)
0.00Ω~ 18.51Ω (2260B-250-13)
0.0Ω~ 555.5Ω (2260B-800-1)
0.0Ω~ 277.8Ω (2260B-800-2)
0.0Ω~ 185.1Ω (2260B-800-4)
MIN
Minimum internal resistance in ohms
MAX
Maximum internal resistance in ohms
Example
SOUR:RES:LEV:IMM:AMPL 0.1
Sets the internal resistance to 100m.
[SOURce:]VOLTage[:LEVel][:IMMediate] [:AMPLitude]
Description
Sets or queries the voltage level in volts.
Syntax
[SOURce:]VOLTage[:LEVel][:IMMediate][:AMPLitude] {<NRf>|MIN|MAX}
Query Syntax
[SOURce:]VOLTage[:LEVel][:IMMediate][:AMPLitude]? [MIN|MAX]
Parameter/Return
<NRf>
0~105% of the rated output voltage in volts.
MIN
Minimum voltage level
MAX
Maximum voltage level
Example
SOUR:VOLT:LEV:IMM:AMPL 10
Sets the voltage level to 10 volts.
[SOURce:]VOLTage[:LEVel]:TRIGgered [:AMPLitude]
Description
Sets or queries the voltage level in volts when a software trigger has been generated.
Set
Query
Set
Query
65
Page 69
2260B Series Programming Manual
Syntax
[SOURce:]VOLTage[:LEVel]:TRIGgered[:AMPLitude] {<NRf>|MIN|MAX}
Query Syntax
[SOURce:]VOLTage[:LEVel]:TRIGgered[:AMPLitude]? [MIN|MAX]
Parameter/Return
<NRf>
0%~105% of the rated voltage output in volts.
MIN
Minimum current level.
MAX
Maximum current level.
Example
SOUR:VOLT:LEV:TRIG:AMPL 10
Sets the voltage level to 10 volts when a software trigger is generated.
[SOURce:]VOLTage:PROTection[:LEVel]
Description
Sets or queries the overvoltage protection level.
Syntax
[SOURce:]VOLTage:PROTection[:LEVel] {<NRf>|MIN|MAX}
Query Syntax
[SOURce:]VOLTage:PROTection[:LEVel]? [MIN|MAX]
Parameter/Return
<NRf>
10%~110% of the rated output voltage in volts.
MIN
Minimum OVP level
MAX
Maximum OVP level
Example
SOUR:VOLT:PROT:LEV MAX
Sets the OVP level to its maximum.
[SOURce:]VOLTage:SLEW:RISing
Description
Sets or queries the rising voltage slew rate. This is only applicable for CV slew rate priority mode.
Syntax
Query Syntax
[SOURce:]VOLTage:SLEW:RISing {<NRf>|MIN|MAX}
[SOURce:]VOLTage:SLEW:RISing? [MIN|MAX]
Parameter/Return
<NRf>
0.01V/s~60V/s (2260B-30-XX)
0.1V/s~160V/s (2260B-80-XX)
0.1V/s~500.0V/s (2260B-250-XX) 1V/s~1600V/s (2260B-800-XX)
MIN
Minimum rising voltage slew rate.
MAX
Maximum rising voltage slew rate.
Set
Query
Set
Query
66
Page 70
REMOTE CONTROL
Example
SOUR:VOLT:SLEW:RIS MAX
Sets the rising voltage slew rate to its maximum.
[SOURce:]VOLTage:SLEW:FALLing
Description
Sets or queries the falling voltage slew rate. This is only applicable for CV slew rate priority mode.
Syntax
[SOURce:]VOLTage:SLEW:FALLing {<NRf>|MIN|MAX}
Query Syntax
[SOURce:]VOLTage:SLEW:FALLing? [MIN|MAX]
Parameter/Return
<NRf>
0.01V/s~60V/s (2260B-30-XX)
0.1V/s~160V/s (2260B-80-XX)
0.1V/s~500.0V/s (2260B-250-XX) 1V/s~1600V/s (2260B-800-XX)
MIN
Minimum voltage falling slew rate.
MAX
Maximum voltage falling slew rate.
Example
SOUR:VOLT:SLEW:FALL MIN
Sets the falling voltage slew rate to its minimum.
Set
Query
67
Page 71
2260B Series Programming Manual
TRIGger:TRANsient[:IMMediate] ...................................... 68
TRIGger:TRANsient:SOURce ............................................. 68
TRIGger:OUTPut[:IMMediate] ........................................... 69
TRIGger:OUTPut:SOURce .................................................. 69
TRIGger:TRANsient[:IMMediate]
Description
Generates a software trigger for the transient trigger system.
Syntax
TRIGger:TRANsient[:IMMediate]
TRIGger:TRANsient:SOURce
Description
Sets or queries the trigger source for the transient system.
Syntax
Query Syntax
TRIGger:TRANsient:SOURce {BUS | IMMediate}
TRIGger:TRANsient:SOURce?
Parameter/Return
BUS
Internal software trigger. Waits for the
*TRG (or IEEE 488.1 “get” group
execute trigger) command to start the trigger.
IMMediate
Starts the trigger immediately. (default)
Set
Set
Query
Trigger Commands
The trigger commands generate and configure software triggers.
This power supply supports the following two trigger functions.
• TRANsient
Specifies the current and voltage settings in advance and uses the
trigger to set them. Please refer to VOLT:TRIG, CURR:TRIG on
page 62 and 69 for details.
• OUTPut
Specifies the output on/ off settings in advance and uses the trigger
to set them. Please refer to OUTP:TRIG on page 69 for details.
68
Page 72
REMOTE CONTROL
Example: Immediate Mode
TRIG:TRAN:SOUR IMM
CURR:TRIG MAX
VOLT:TRIG 5
INIT:NAME TRAN
The current changes to the maximum, and the voltage changes to 5V.
Example: Bus Mode
TRIG:TRAN:SOUR BUS
CURR:TRIG MAX
VOLT:TRIG 5
INIT:NAME TRAN
TRIG:TRAN
The current changes to the maximum, and the voltage changes to 5V.
TRIGger:OUTPut[:IMMediate]
Description
Generates a software trigger for the output trigger system.
Syntax
TRIGger:OUTPut[:IMMediate]
TRIGger:OUTPut:SOURce
Description
Sets or queries the trigger source for the output system.
Syntax
TRIGger:OUTPut:SOURce [BUS | IMMediate]
Query Syntax
TRIGger:OUTPut:SOURce?
Parameter/Return
BUS
Internal software trigger. Waits for the *TRG (or IEEE 488.1 “get” group execute trigger) command to start the trigger.
IMMediate
Starts the trigger immediately. (default)
Set
Set
Query
69
Page 73
2260B Series Programming Manual
Example:
Immediate Mode
TRIG:OUTP:SOUR IMM
OUTP:TRIG 1
INIT:NAME OUTP
The output changes to ON.
Example: Bus Mode
TRIG:OUTP:SOUR BUS
OUTP:TRIG 1
INIT:NAME OUTP
TRIG:OUTP
The output changes to ON.
70
Page 74
REMOTE CONTROL
SYSTem:CONFigure:BEEPer[:STATe] ............................. 71
SYSTem:CONFigure:BLEeder[:STATe] ............................ 72
SYSTem:CONFigure:BTRip[:IMMediate] ......................... 72
SYSTem:CONFigure:BTRip:PROTection......................... 72
SYSTem:CONFigure:CURRent:CONTrol ........................ 73
SYSTem:CONFigure:VOLTage:CONTrol ....................... 73
SYSTem:CONFigure:MSLave .............................................. 74
SYSTem:CONFigure:OUTPut:EXTernal[:MODE] ........ 74
SYSTem:CONFigure:OUTPut:PON[:STATe] ................. 75
SYSTem:COMMunicate:ENABle ....................................... 75
SYSTem:COMMunicate:GPIB[:SELF]:ADDRess ........... 76
SYSTem:COMMunicate:LAN:IPADdress......................... 77
SYSTem:COMMunicate:LAN:GATEway ......................... 77
SYSTem:COMMunicate:LAN:SMASk ............................... 77
SYSTem:COMMunicate:LAN:MAC ................................... 78
SYSTem:COMMunicate:LAN:DHCP ................................ 78
SYSTem:COMMunicate:LAN:DNS ................................... 78
SYSTem:COMMunicate:LAN:HOSTname ....................... 79
SYSTem:COMMunicate:LAN:WEB:PACTive ................. 79
SYSTem:COMMunicate:LAN:WEB:PASSword .............. 79
SYSTem:COMMunicate:USB:FRONt:STATe .................. 80
SYSTem:COMMunicate:USB:REAR:STATe .................... 80
SYSTem:ERRor ...................................................................... 80
SYSTem:KEYLock:MODE ................................................. 80
SYSTem:KLOCk .................................................................... 81
SYSTem:INFormation ........................................................... 81
SYSTem:PRESet ..................................................................... 82
SYSTem:VERSion .................................................................. 82
SYSTem:CONFigure:BEEPer[:STATe]
Description
Sets or queries the buzzer state on/off.
Syntax
Query Syntax
SYSTem:CONFigure:BEEPer[:STATe] {OFF|ON|0|1}
SYSTem:CONFigure:BEEPer[:STATe]?
Set
Query
System Function Command
71
Page 75
2260B Series Programming Manual
Parameter
0
<NR1> Turns the buzzer off.
OFF
Turns the buzzer off.
1
<NR1> Turns the buzzer on.
ON
Turns the buzzer on.
Return parameter
<Boolean>
Returns the buzzer status.
SYSTem:CONFigure:BLEeder[:STATe]
Description
Sets or queries the status of the bleeder resistor.
Syntax
Query Syntax
SYSTem:CONFigure:BLEeder[:STATe] {OFF|ON|AUTO|0|1|2}
SYSTem:CONFigure:BLEeder[:STATe]?
Parameter
0
<NR1> Turns the bleeder resistor off.
OFF
Turns the bleeder resistor off.
1
<NR1> Turns the bleeder resistor on.
ON
Turns the bleeder resistor on.
2
<NR1> Turns on/off the bleeder resistor automatically.
AUTO
The bleeder resistor is automatically turned on when the output is turned on and turned off when the output is turned off.
Return parameter
<Boolean>
Returns bleeder resistor status.
SYSTem:CONFigure:BTRip[:IMMediate]
Description
Trips the power switch trip (circuit breaker) to turn the unit off (shut down the power).
Syntax
SYSTem:CONFigure:BTRip[:IMMediate]
SYSTem:CONFigure:BTRip:PROTection
Description
Enables/Disables the power switch trip (circuit breaker) when the OVP or OCP protection settings are tripped. This setting only applies after power has been cycled.
Set
Query
Set
Set
Query
72
Page 76
REMOTE CONTROL
Syntax
SYSTem:CONFigure:BTRip:PROTection {DISable|ENABle|0|1}
Query Syntax
SYSTem:CONFigure:BTRip:PROTection?
Parameter
0
<NR1> Enables the power switch trip for OVP or OCP.
ENABle
Enables the power switch trip for OVP or OCP.
1
<NR1> Disables the power switch trip for OVP or OCP.
DISable
Disables the power switch trip for OVP or OCP.
Return parameter
<Boolean>
Returns power switch trip setting.
SYSTem:CONFigure:CURRent:CONTrol
Description
Sets or queries the CC control mode (local control (panel), external voltage control, external resistance control). This setting is applied only after the power is cycled.
Syntax
Query Syntax
SYSTem:CONFigure:CURRent:CONTrol { 0 | 1 | 2 | 3 }
SYSTem:CONFigure:CURRent:CONTrol?
Parameter/Return
<NR1>
Description
0
Local (Panel) control
1
External voltage control
2
External resistance control; 10kΩ = Io max, 0kΩ = Io min.
3
External resistance control; 10kΩ = Io min, 0kΩ = Io max.
SYSTem:CONFigure:VOLTage:CONTrol
Description
Sets or queries the CV control mode (local control, external voltage control, external resistance control). This setting is applied only after the power is cycled.
Syntax
Query Syntax
SYSTem:CONFigure:VOLTage:CONTrol { 0 | 1 | 2 | 3 }
SYSTem:CONFigure:VOLTage:CONTrol?
Set
Query
Set
Query
73
Page 77
2260B Series Programming Manual
Parameter/Return
<NR1>
Description
0
Local (Panel) control
1
External voltage control
2
External resistance control; 10kΩ = Vo max, 0kΩ = Vo min.
3
External resistance control; 10kΩ = Vo min, 0kΩ = Vo max.
SYSTem:CONFigure:MSLave
Description
Sets or queries the unit operation mode. This setting is only applied after the power has been cycled.
Syntax
Query Syntax
SYSTem:CONFigure:MSLave { 0 | 1 | 2 | 3 | 4 }
SYSTem:CONFigure:MSLave?
Parameter/Return
<NR1>
Description
0
Master/Local
1
Master/Parallel 1 (2 units)
2
Master/Parallel 2 (3 units)
3
Slave/Parallel
4
Slave/Series
SYSTem:CONFigure:OUTPut:EXTernal [:MODE]
Description
Sets the external logic as active high or active low. This setting is only applied after the power has been cycled.
Syntax
Query Syntax
SYSTem:CONFigure:OUTPut:EXTernal[:MODE]
SYSTem:CONFigure:OUTPut:EXTernal[:MODE]?
Set
Query
Set
Query
74
Page 78
REMOTE CONTROL
Parameter
0
Active high
HIGH
Active high
1
Active low
LOW
Active low
Return Parameter
0
<boolean>Active high
1
<boolean>Active low
SYSTem:CONFigure:OUTPut:PON[:STATe]
Description
Sets the unit to turn the output ON/OFF at power­up. This setting is only applied after the power has been cycled.
Syntax
SYSTem:CONFigure:OUTPut:PON[:STATe] {OFF|ON|0|1}
Query Syntax
SYSTem:CONFigure:OUTPut:PON[:STATe]?
Parameter
0
Output off at power up
OFF
Output off at power up
1
Output on at power up
ON
Output on at power up
Return Parameter
0
Output off at power up
1
Output on at power up
SYSTem:COMMunicate:ENABle
Description
Enables/Disables LAN, GPIB or USB remote interfaces as well as remote services (Sockets, Web Server). This setting is only applied after the power has been cycled.
Syntax
Query Syntax
SYSTem:COMMunicate:ENABle <mode>,<interface>
SYSTem:COMMunicate:ENABle? <interface>
Set
Query
Set
Query
75
Page 79
2260B Series Programming Manual
Parameter
<mode>
OFF
Turns the selected mode off.
0
Turns the selected mode off.
ON
Turns the selected mode on. (Auto detect speed in USB)
1
Turns the selected mode on. (Auto detect speed in USB)
FULL
Full Speed (USB Only)
2
Full Speed (USB Only)
<interface>
GPIB
Select GPIB
USB
Select USB
LAN
Select LAN
SOCKets
Select Sockets
WEB
Select the web server
Return Parameter
0
The selected mode is off.
1
The selected mode is on.
Example-1
SYST:COMM:ENAB 1,USB
Turns the USB interface on.
USB is auto detect speed.
Example-2
SYST:COMM:ENAB 2,USB
Turns the USB interface on.
USB is full speed only..
Query Example
SYST:COMM:ENAB? USB
1
Queries the USB state, returns 1 (USB is on).
SYSTem:COMMunicate:GPIB[:SELF]:ADDR ess
Description
Sets or queries the GPIB address. This setting is only applied after the power has been cycled.
Syntax
Query Syntax
SYSTem:COMMunicate:GPIB[:SELF]:ADDRess <NR1>
SYSTem:COMMunicate:GPIB[:SELF]:ADDRess?
Parameter/Return
<NR1>
0~30
Set
Query
76
Page 80
REMOTE CONTROL
Example
SYST:COMM:GPIB:SELF:ADDR 15
Sets the GPIB address to 15.
SYSTem:COMMunicate:LAN:IPADdress
Description
Sets or queries LAN IP address. This setting is only applied after the power has been cycled.
Syntax
Query Syntax
SYSTem:COMMunicate:LAN:IPADdress <string>
SYSTem:COMMunicate:LAN:IPADdress?
Parameter/Return
<string>
LAN IP address in string format ( “address”) Applicable ASCII characters: 20H to 7EH
Example
SYST:COMM:LAN:IPAD “172.16.5.111 Sets the IP address to 172.16.5.111.
SYSTem:COMMunicate:LAN:GATEway
Description
Sets or queries the Gateway address. This setting is only applied after the power has been cycled.
Syntax
Query Syntax
SYSTem:COMMunicate:LAN:GATEway <string>
SYSTem:COMMunicate:LAN:GATEway?
Parameter/Return
<string>
Gateway address in string format ( “address”) Applicable ASCII characters: 20H to 7EH
Example
SYST:COMM:LAN:GATE “172.16.0.254 Sets the LAN gateway to 172.16.0.254.
SYSTem:COMMunicate:LAN:SMASk
Description
Sets or queries the LAN subnet mask. This setting is only applied after the power has been cycled.
Syntax
Query Syntax
SYSTem:COMMunicate:LAN:SMASk <string>
SYSTem:COMMunicate:LAN:SMASk?
Parameter/Return
<string>
Subnet mask in string format ( “mask”) Applicable ASCII characters: 20H to 7EH
Example
SYST:COMM:LAN:SMASk “255.255.0.0 Sets the LAN mask to 255.255.0.0.
Set
Query
Set
Query
Set
Query
77
Page 81
2260B Series Programming Manual
SYSTem:COMMunicate:LAN:MAC
Description
Returns the unit MAC address as a string. The MAC address cannot be changed.
Query Syntax
SYSTem:COMMunicate:LAN:MAC?
Return parameter
<string>
Returns the MAC address in the following format “FF-FF-FF-FF-FF-FF”
Example
SYST:COMM:LAN:MAC? 02-80-AD-20-31-B1 Returns the MAC address.
SYSTem:COMMunicate:LAN:DHCP
Description
Turns DHCP on/off. Queries the DHCP status. This setting is only applied after the power has been cycled.
Syntax
Query Syntax
SYSTem:COMMunicate:LAN:DHCP {OFF | ON | 0 | 1}
SYSTem:COMMunicate:LAN:DHCP?
Parameter
0
DHCP off
OFF
DHCP off
1
DHCP on
ON
DHCP on
Return parameter
0
<boolean>DHCP off
1
<boolean>DHCP on
SYSTem:COMMunicate:LAN:DNS
Description
Sets or queries the DNS address. This setting is only applied after the power has been cycled.
Syntax
Query Syntax
SYSTem:COMMunicate:LAN:DNS <string>
SYSTem:COMMunicate:LAN:DNS?
Parameter/Return
<string>
DNS in string format ( “mask”) Applicable ASCII characters: 20H to 7EH
Example
SYST:COMM:LAN:DNS “172.16.1.252 Sets the DNS to 172.16.1.252.
Query
Set
Query
Set
Query
78
Page 82
REMOTE CONTROL
SYSTem:COMMunicate:LAN:HOSTname
Description
Queries the host name.
Query Syntax
SYSTem:COMMunicate:LAN:HOSTname?
Return Parameter
<string>
Host name in string format
Query Example
SYST:COMM:LAN:HOST? P-160054 Returns the host name (P-160054).
SYSTem:COMMunicate:LAN:WEB:PACTive
Description
Sets or queries whether the web password is on or off. This setting is only applied after the power has been cycled.
Syntax
Query Syntax
SYSTem:COMMunicate:LAN:WEB:PACTive {OFF | ON | 0 | 1}
SYSTem:COMMunicate:LAN:WEB:PACTive?
Parameter
0
Web password off
OFF
Web password off
1
Web password on
ON
Web password on
Return parameter
0
<boolean> Web password off
1
<boolean> Web password on
SYSTem:COMMunicate:LAN:WEB:PASSword
Description
Sets or queries the web password. This setting is only applied after the power has been cycled.
Syntax
Query Syntax
SYSTem:COMMunicate:LAN:WEB:PASSword <NR1>
SYSTem:COMMunicate:LAN:WEB:PASSword?
Parameter/Return
<NR1>
0 ~ 9999
Example
SYST:COMM:LAN:WEB:PASS 1234
Set the web password as 1234.
Query
Set
Query
Set
Query
79
Page 83
2260B Series Programming Manual
SYSTem:COMMunicate:USB:FRONt:STATe
Description
Queries the front panel USB-A port state.
Query Syntax
SYSTem:COMMunicate:USB:FRONt:STATe?
Return parameter
0
<NR1>Absent
1
<NR1>Mass Storage
SYSTem:COMMunicate:USB:REAR:STATe
Description
Queries the rear panel USB-B port state.
Query Syntax
SYSTem:COMMunicate:USB:REAR:STATe?
Return parameter
0
<NR1>Absent
1
<NR1>USB-CDC
2
<NR1>GPIB-USB
SYSTem:ERRor
Description
Queries the error queue. The last error message is returned and cleared. A maximum of 16 errors are stored in the error queue. Each remote interface I/O session (i.e., GPIB, USB, LAN, etc.) has its own error queue.
Query Syntax
SYSTem:ERRor?
Paramter/Return
<NR1>,<string>
Returns an error code followed by an error message as a string. The string is returned as “string”.
Example
SYSTem:ERRor?
-100, “Command error”
SYSTem:KEYLock:MODE
Set
Query
Description
Sets or queries the key lock mode. This setting is the equivalent of the F-19 function setting.
Syntax
Query Syntax
SYSTem:KEYLock:MODE {0|1}
SYSTem:KEYLock:MODE?
Query
Query
Query
80
Page 84
REMOTE CONTROL
Parameter / Return parameter
0
Panel lock: allow output off.
1
Panel lock: allow output on/off.
SYSTem:KLOCk
Description
Enables or disables the front panel key lock.
Syntax
Query Syntax
SYSTem:KLOCk { OFF | ON | 0 | 1}
SYSTem:KLOCk?
Parameter
0
Panel keys unlocked
OFF
Panel keys unlocked
1
Panel keys locked
ON
Panel keys locked
Return parameter
0
<boolean>Panel keys unlocked
1
<Boolean>Panel keys locked
SYSTem:INFormation
Description
Queries the system information. Returns the machine version, build date, keyboard CPLD version and analog CPLD version.
Query Syntax
SYSTem:INFormation?
Return Parameter
<block data>
Definite length arbitrary block response data.
Query Example
SYST:INF?
#3238MFRS XXXXXX,Model AAAAAA,SN BBBBBB,Firmware-Version 01.00.20120101,Keyboard­CPLD 0x030C,AnalogControl-CPLD 0x0421,Kernel­Buildon May 22 2011,MAC 02-80-ad-20-31-b1
Returns the system information as a block data. (XXXXXX= manufacturer, AAAAAA = model number,
BBBBBB = Serial Number)
Set
Query
Query
81
Page 85
2260B Series Programming Manual
SYSTem:PRESet
Description
Resets all the settings to the factory default settings. See page 107 for details. This command is identical in effect to the *RST command.
Syntax
SYSTem:PRESet
SYSTem:VERSion
Description
Returns the version of the SCPI specifications that the unit complies with.
Query Syntax
SYSTem:VERSion?
Return
<1999.0>
Always returns the SCPI version: 1999.0.
Set
Query
82
Page 86
REMOTE CONTROL
*CLS .......................................................................................... 83
*ESE .......................................................................................... 83
*ESR .......................................................................................... 84
*IDN ......................................................................................... 84
*OPC ......................................................................................... 84
*RST .......................................................................................... 85
*SRE .......................................................................................... 85
*STB .......................................................................................... 85
*TRG ......................................................................................... 86
*TST .......................................................................................... 86
*WAI ......................................................................................... 86
*CLS
Description
The *CLS command clears the Standard Event Status, Operation Status and Questionable Status registers. The corresponding Enable registers in each of the above registers are not cleared.
If a <NL> newline code immediately precedes a *CLS command, the Error Que and the MAV bit in the Status Byte Register is also cleared.
Syntax
*CLS
*ESE
Description
Sets or queries the Standard Event Status Enable register.
Syntax
Query Syntax
*ESE <NR1>
*ESE?
Parameter
<NR1>
0~255
Return parameter
<NR1>
Returns the bit sum of the Standard Event Status Enable register.
Set
Set
Query
IEEE 488.2 Common Commands
83
Page 87
2260B Series Programming Manual
*ESR
Description
Queries the Standard Event Status (Event) register. The Event Status register is cleared after it is read.
Query Syntax
*ESR?
Return parameter
<NR1>
Returns the bit sum of the Standard Event Status (Event) register and clears the register.
*IDN
Description
Queries the manufacturer, model name, serial number, and firmware version of the unit.
Query Syntax
*IDN?
Return parameter
<string>
Returns the instrument identification as a string in the following format:
XXXXXX,AAAAAA,TW123456,01.00.20110101
Manufacturer: XXXXXX
Model number : AAAAAA
Serial number : TW123456 Firmware version : 01.00.20110101
*OPC
Description
The *OPC command sets the OPC bit (bit0) of the Standard Event Status Register when all current commands have been processed.
The *OPC? Query returns 1 when all the outstanding commands have completed.
Syntax
Query Syntax
*OPC
*OPC?
Return parameter
1
Returns 1 when all the outstanding commands have completed.
Query
Query
Set
Query
84
Page 88
REMOTE CONTROL
*RST
Description
Resets all the settings to the factory default settings. See page 107 for details. This command is identical in effect to the SYSTem:PRESet command.
Syntax
*RST
*SRE
Description
Sets or queries the Service Request Enable register. The Service Request Enable register determines which registers of the Status Byte register are able to generate service requests.
Syntax
Query Syntax
*SRE <NR1>
*SRE?
Parameter
<NR1>
0~255
Return parameter
<NR1>
Returns the bit sum of the Service Request Enable register.
*STB
Description
Queries the bit sum of the Status Byte register with MSS (Master summary Status).
Query Syntax
*STB?
Return parameter
<NR1>
Returns the bit sum of the Status Byte register with the MSS bit (bit 6).
Set
Set
Query
Query
85
Page 89
2260B Series Programming Manual
*TRG
Description
The *TRG command is able to generate a “get”
(Group Execute Trigger). If the 2260B cannot accept a trigger at the time of the command, an error message is generated (-211, “Trigger ignored”).
Syntax
*TRG
*TST
Description
Executes a self test.
Query Syntax
*TST?
Return parameter
0
Returns “0” if there are no errors.
<NR1>
Returns an error code <NR1> if there is an error.
*WAI
Description
Prevents any other commands or queries from being executed until all outstanding commands have completed.
Syntax
*WAI
Set
Query
Set
86
Page 90
REMOTE CONTROL
Overview
The status registers are used to determine the status of the power supply. The status registers maintain the status of the protection conditions, operation conditions and instrument errors.
The 2260B Series have a number of register groups:
Questionable Status Register Group
Standard Event Status Register Group
Operation Status Register Group
Status Byte Register
Service Request Enable Register
Service Request Generation
Error Queue
Output Buffer
The next page shows the structure of the Status registers.

Status Register Overview

To program the 2260B power supply effectively, the Status registers need to be understood. This chapter explains in detail how the Status registers are used and how to configure them.
Introduction to the Status Registers
87
Page 91
Condition
OV (Over-Voltage) 0
PTR/NTP Event Enable
OC (Over-Current) 1
Not Used 2
POW (AC Power Off) 3
OT (Over-Temperature) 4
Not Used 5 Not Used 6
Not Used 7 VL (Voltage-Limit) 8 CL (Current-Limit) 9
Not Used 10
SD (Shutdown Alarm) 11
Power-Limit 12
Not Used 13
Not Used 14
Not Used 15
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
Condition
CAL (Calibration mode) 0
PTR/NTP Event Enable
Not Used 1 Not Used 2 Not Used 3 Not Used 4
WTG (Waiting for Trigger)
5 Not Used 6 Not Used 7
CV (Constant Voltage Mode)
8 Not Used 9
CC (Constant Current Mode)
10
OND (Output ON Delay) 11
OFD (Output OFF Delay)
12 Not Used 13 Not Used 14 Not Used 15
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
OPC (Operation Complete)
RQC (Request Control)
QUE (Query Error)
DDE (Device Dependent Error)
EXE (Execution Error)
CME (Command Error)
URQ (User Request)
PON (Power On)
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7
ERR
QUES
MAV ESB MSS
OPER
0 1 2 3 4 5 6 7
Output Buffer
: : :
Error Que
: : :
EnableEvent
Status
Byte
Register
Service
Request
Enable
Register
Questionable Status Register
Operation Status Register
Standard Event Status
Register
2260B Series Programming Manual
The Status Registers
88
Page 92
REMOTE CONTROL
Overview
The Questionable Status Register Group indicates if any protection modes or limits have been tripped.
Condition
OV 0
PTR/NTP Event Enable
OC 1
Not Used 2
POW 3
OT 4 Not Used 5 Not Used 6 Not Used 7
VL 8 CL 9
Not Used 10
SD 11
PL 12 Not Used 13 Not Used 14 Not Used 15
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
Questionable Status Register
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
Logical OR
To Status Byte Register
STATus:QUEStionable:CONDition? STATus:QUEStionable:EVENt?
STATus:QUEStionable:NTRansition <NRf>
STATus:QUEStionable:NTRansition?
STATus:QUEStionable:PTRansition <NRf>
STATus:QUEStionable:PTRansition?
STATus:QUEStionable:ENABle <NRf>
STATus:QUEStionable:ENABle?
Bit Summary
Event
Bit #
Bit Weight
OV (Over-Voltage)
Over voltage protection has been tripped
0
1
OC (Over-Current)
Over current protection has been tripped
1
2 POW (AC Power Off)
AC power switch is off
3
8
Questionable Status Register Group
89
Page 93
2260B Series Programming Manual
OT (Over Temperature)
Over temperature protection has been tripped
4
16 VL (Voltage Limit)
Voltage limit has been reached
8
256 CL (Current Limit)
Current limit has been reached
9
512
SD (Shutdown Alarm)
11
2048
PL (Power-Limit)
12
4096
Condition Register
The Questionable Status Condition Register indicates the status of the power supply. If a bit is set in the Condition register, it indicates that the event is true. Reading the condition register does not change the state of the condition register.
PTR/NTR Filters
The PTR/NTR (Positive/Negative transition) register determines the type of transition conditions that will set the corresponding bit in the Event Registers. Use the Positive transition filter to view events that change from false to positive, and use the negative transition filter to view events that change from positive to negative.
Positive Transition
01
Negative Transition
10
Event Register
The PTR/NTR Register will dictate the type of transition conditions will set the corresponding bits in the Event Register. If the Event Register is read, it will be cleared to 0.
Enable Register
The Enable register determines which Events in the Event Register will be used to set the QUES bit in the Status Byte Register.
90
Page 94
REMOTE CONTROL
Overview
The Operation Status Register Group indicates the operating status of the power supply.
CAL Not Used Not Used Not Used Not Used
WTG Not Used Not Used
CV
Not Used
CC OND OFD
Not Used Not Used Not Used
Condition0PTR/NTP Event Enable
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
Operation Status Register
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
Logical OR
To Status Byte Register
STATus:OPERation:CONDition? STATus:OPERation:EVENt?
STATus:OPERation:NTRansition <NRf>
STATus:OPERation:NTRansition?
STATus:OPERation:PTRansition <NRf>
STATus:OPERation:PTRansition?
STATus:OPERation:ENABle <NRf>
STATus:OPERation:ENABle?
Bit Summary
Event
Bit #
Bit Weight
CAL (Calibration mode)
Indicates if the 2260B is in calibration mode.
0
1
WTG (Waiting for trigger)
Indicates if the 2260B is waiting for a trigger.
5
32
Operation Status Register Group
91
Page 95
2260B Series Programming Manual
CV (Constant voltage mode)
Indicates if the 2260B is in CV mode.
8
256
CC (Constant current mode)
Indicates if the 2260B is in CC mode.
10
1024
OND (Output ON Delay)
Indicates if Output ON delay time is active
11
2048
OFD (Output OFF Delay)
Indicates if Output OFF delay time is active
12
4096
Condition Register
The Operation Status Condition Register indicates the operating status of the power supply. If a bit is set in the Condition register, it indicates that the event is true. Reading the condition register does not change the state of the condition register.
PTR/NTR Filters
The PTR/NTR (Positive/Negative transition) register determines the type of transition conditions that will set the corresponding bit in the Event Registers. Use the Positive transition filter to view events that change from false to positive, and use the negative transition filter to view events that change from positive to negative.
Positive Transition
01
Negative Transition
10
Event Register
The PTR/NTR Register will dictate the type of transition conditions will set the corresponding bits in the Event Register. If the Event Register is read, it will be cleared to 0.
92
Page 96
REMOTE CONTROL
Enable Register
The Enable register determines which registered Events in the Event Register will be used to set the OPER bit in the Status Byte Register.
Overview
The Standard Event Status Register Group indicates if any errors have occurred. The bits of the Event register are set by the error event queue.
OPC RQC QUE DDE
EXE CME URQ PON
Event Enable
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7
Standard Event Status Register
&
&
&
&
&
&
&
&
To Status Byte Register
*ESR?
Logical OR
*ESE <NRf>
*ESE?
Bit Summary
Event
Bit #
Bit Weight
OPC (Operation complete)
The OCP bit is set when all selected pending operations are complete. This bit is set in response to the *OPC command.
0
1
RQC (Request control)
1
2
Standard Event Status Register Group
93
Page 97
2260B Series Programming Manual
QUE (Query Error)
The Query Error bit is set in response to an error reading the Output Queue. This can be caused by trying to read the Output Queue when there is no data present.
2
4
DDE (Device Dependent Error)
Device specific error.
3
8
EXE (Execution Error)
The EXE bit indicates an execution error due to one of the following: illegal command parameter, parameter out of range, invalid parameter, the
command didn’t execute due to
an overriding operation condition.
4
16
CME (Command Error)
The CME bit is set when a syntax error has occurred. The CME bit can also be set when a <GET> command is received within a program message.
5
32
URQ (User Request)
6
64
PON (Power On)
Indicates the power is turned on.
7
128
Event Register
Any bits set in the event register indicate that an error has occurred. Reading the Event register will reset the register to 0.
Enable Register
The Enable register determines which Events in the Event Register will be used to set the ESB bit in the Status Byte Register.
94
Page 98
REMOTE CONTROL
Overview
The Status Byte register consolidates the status events of all the status registers. The Status Byte register can be read with the *STB? query and can be cleared with the *CLS command.
ERR
QUES
MAV ESB MSS
OPER
0 1 2 3 4 5 6 7
Output Buffer
: : :
Error Que
: : :
Status
Byte
Register
0 1 2 3 4 5 6 7
&
&
&
&
&
&
&
*SRE <NRf>
*SRE?
Service
Request
Enable
Register
Logical OR
*STB?
From Operation
Status Register
From
Questionable
Status Register
From Standard
Event Status
Register
Bit Summary
Event
Bit #
Bit Weight
ERR (Error Event/Queue)
If data is present in the Error queue, the ERR bit will be set.
2
4
QUES (Questionable Status Register)
The summary bit for the Questionable Status Register group.
3
8
MAV (Message Available) This is set when there is data in the Output Queue waiting to be read.
4
16
Status Byte Register & Service Request Enable Register
95
Page 99
2260B Series Programming Manual
(ESB) Event Summary Bit. The ESB is the summary bit for the Standard Event Status Register group.
5
32
MSS Bit
The MSS Bit is the summary of the Status Byte Register and Service Request register (bits 1-5,
7). This will be set to 1.
6
64 OPER (Operation Status Register)
OPER bit is the summary bit for the Operation Status Register Group.
7
128
Status Byte Register
Any bits set in the Status byte register acts as a summary register for all the three other status registers and indicates if there is a service request, an error in the Error Queue or data in the Output Queue. Reading the Status Byte register will reset the register to 0.
Service Request Enable Register
The Service Request Enable Register controls which bits in the Status Byte Register are able to generate service requests.
96
Page 100
REMOTE CONTROL
Overview
An <error/event number> in the range [ -199 , ­100 ] indicates that an IEEE 488.2 syntax error
has been detected by the instrument’s parser.
The occurrence of any error in this class shall cause the command error bit (bit 5) in the event status register (IEEE 488.2, section 11.5.1) to be set. One of the following events has occurred:
An IEEE 488.2 syntax error has been detected by
the parser. That is, a controller-to-device message was received which is in violation of the IEEE 488.2 standard. Possible violations include a data element which violates the device listening formats or whose type is unacceptable to the device.
An unrecognized header was received.
Unrecognized headers include incorrect device­specific headers and incorrect or unimplemented IEEE 488.2 common commands.
Events that generate command errors shall not generate execution errors, device-specific errors, or query errors; see the other error definitions in this chapter.

Error List

Command Errors
97
Loading...