Each MEM-32/W and MEM-32/A relay board converts 32 digital outputs from the MetraBus system to SPST relay contact
closures. The MEM-32/W has mercury-wetted contacts rated at 2A. The MEM-32/A has dry contacts rated at 0.5A.
One MetraBus controller can control up to sixteen MEM-32/A or MEM-32/W boards via a single ribbon cable, each
connected by a 50-pin connector.
For more information about the MetraBus system in general and the MEM-32/A and MEM-32W boards specifically, refer to
your MetraBus User’s Guide. The MetraBus User’s Guide also includes programming help for the MEM-32/A and MEM32/W.
Specifications
Relays
MEM-32/AMEM-32/W
Number of relays:3232
Relay type:Form A (SPST)Form A (SPST)
Contact:Dry contactMercury wetted
Position sensitivity:May be mounted in any positionMust be mounted within +30° of vertical
Contact rating:10W at 0.5A or 150VDC/peak VAC (resistive),
Installation Category I
Contact resistance:100mΩ maximum initial50mΩ maximum initial
Contact life:107 operations at rated load107 operations at rated load
Operate time:2 s maximum2ms maximum
50W at 2A or 150VDC/peak VAC (resistive),
Installation Category I
Environmental
Operating temperature range: 0 to 70 °C
Storage temperature range: -40 to +100 °C
Humidity: 0 to 90% non-condensing
Power and Signal Requirements
+5V power: 510mA max. (all relays energized)
+15V power: Not used
Physical
Dimensions: 16in L x 4.75in W (40.6cm L x 12.1cm W)
Safety precautions
The following safety precautions should be observed before using this product and any associated instrumentation. This
product may be used with hazardous voltages.
This product is intended for use by qualified personnel who recognize shock hazards and are familiar with the safety
precautions required to avoid possible injury. Read the operating information carefully before using the product.
PA-611 Rev. A / 9-98
Page 2
General safety definitions
The types of product users are:
Responsible body is the individual or group responsible for the use and maintenance of equipment, and for ensuring that
operators are adequately trained.
Operators use the product for its intended function. They must be trained in electrical safety procedures and proper use of
the instrument. They must be protected from electric shock and contact with hazardous live circuits.
Maintenance personnel perform routine procedures on the product to keep it operating, for example, setting the line
voltage or replacing consumable materials. Maintenance procedures are described in the manual. The procedures explicitly
state if the operator may perform them. Otherwise, they should be performed only by service personnel.
Service personnel are trained to work on live circuits, and perform safe installations and repairs of products. Only properly
trained service personnel may perform installation and service procedures.
If a grounding screw is present, connect it to safety earth ground using the wire recommended in the user
documentation.
The symbol on an instrument indicates that the user should refer to the operating instructions located in the manual.
The WARNING heading in a manual explains dangers that might result in personal injury or death. Always read the
associated information very carefully before performing the indicated procedure.
The CAUTION heading in a manual explains hazards that could damage the instrument. Such damage may invalidate the
warranty.
Installation safety
As described in the International Electrotechnical Commission (IEC) Standard IEC 664, the signal terminals are
Installation Category I and must not be connected to mains, except as noted in the specifications.
When connecting to sources, install protective devices to limit current and voltage to the card.
Operators and maintainers of this product must be protected from electric shock at all times. The responsible body must
ensure that users are prevented access and/or insulated from every connection point. In some cases, connections must be
exposed to potential human contact. Product users in these circumstances must be trained to protect themselves from the
risk of electric shock. If the circuit is capable of operating at or above 1000 volts, no conductive part of the circuit may be
exposed.
Operation safety
Exercise extreme caution when a shock hazard is present. Lethal voltage may be present on cable connector jacks or test
fixtures. The American National Standards Institute (ANSI) states that a shock hazard exists when voltage levels greater
than 30V RMS, 42.4V peak, or 60VDC are present. A good safety practice is to expect that hazardous voltage is present
in any unknown circuit before measuring.
For maximum safety, do not touch the product, test cables, or any other instruments while power is applied to the circuit
under test. ALWAYS remove power from the entire test system and discharge any capacitors before: connecting or
disconnecting cables or jumpers, installing or removing switching cards, or making internal changes, such as installing or
removing jumpers.
Do not touch any object that could provide a current path to the common side of the circuit under test or power line (earth)
ground. Always make measurements with dry hands while standing on a dry, insulated surface capable of withstanding the
voltage being measured.
Do not exceed the maximum signal levels of the instruments and accessories, as defined in the specifications and operating
information, and as shown on the instrument or test fixture panels, or switching card.
If you are using a test fixture, keep the lid closed while power is applied to the device under test. Safe operation requires
the use of a lid interlock.
Instrumentation and accessories shall not be connected to humans.
2
Page 3
Maintenance and service for safety
Inspect the connecting cables, test leads, and jumpers for possible wear, cracks, or breaks before each use.
Before performing any maintenance, disconnect all power sources and test cables.
Cleaning
Keep the connections free of contaminants (such as dirt, oil, etc.) in order to maintain maximum insulation resistance. If the
connections become contaminated, clean them thoroughly with methanol and allow them to dry completely before use.
Installation
WARNINGTo prevent risk of electric shock, always take the following precautions:
As described in the International Electrotechnical Commission (IEC) Standard IEC 664, the signal
terminals are Installation Category I and must not be connected to mains, except as noted in the
specifications.
When connecting to sources, install protective devices to limit current and voltage to the card.
Operators and maintainers of this product must be protected from electric shock at all times. The
responsible body must ensure that users are prevented access and/or insulated from every connection
point. In some cases, connections must be exposed to potential human contact. Product users in these
circumstances must be trained to protect themselves from the risk of electric shock. If the circuit is
capable of operating at or above 1000 volts, no conductive part of the circuit may be exposed.
Setting the board address
Each MEM-32/A or MEM-32/W board requires four unique, consecutive addresses out of 64 addresses available on the
MetraBus. The board address is the lowest numbered address of these four—the base or starting address. The board address
is set with a four pole DIP switch, which is wired so that the address is incremented in multiples of four. The location of the
board address switch is shown in Figure 1.
Board address
switch
Sockets for resistorterminating networks
The board address setting is the sum of the numbers set to ON at the board address switch (i.e., the number 4, 8, 16, or 32
printed above an individual DIP switch pole indicates the number that is added to the address when that pole is turned to
ON). For example, to set a board address of 20, turn switch poles numbered 4 and 16 to ON and turn the other poles to OFF.
See Figure 2.
Mating connector to
MetraBus cable
Figure 1. MEM-32/A or MEM-32/W board layout
32 pairs of relay
output terminals
3
Page 4
32 16 84
ON
■■↑
■■
12 34
Figure 2. Setting a board address of 20
Installing resistor-terminating networks
If only one MEM-32/A or MEM-32/W is installed on the MetraBus cable or if the MEM-32/A or MEM-32/W is the last
board on the cable, then install the resistor-terminating networks provided with your controller card. The resistorterminating networks minimize signal reflection caused by long cable lengths. With the power off, install the resistorterminating networks (14-pin integrated circuits) in the sockets marked RN1 and RN2 immediately above the MetraBus
connector. See Figure 1.
NOTEFor cables of 50 feet or less, resistor-terminating networks are optional and have little effect.
Mounting the board
The MEM-32/W and MEM-32/A boards may be mounted in standard 19” racks or in standard NEMA enclosures. The
MEM-32/W board must be mounted within +30° of vertical for the mercury-wetted relays to work properly. The MEM32/A board may be mounted in any position.
Connecting the board to the MetraBus cable
To connect the board to the MetraBus cable, first remove power from the system, and then plug any unused connector on the
MetraBus cable to the mating connector of the board as shown in Figure 1. The MetraBus cable connector is keyed for your
protection and should plug in easily. Check the keyways for correct alignment prior to plugging in the MetraBus cable.
Connecting I/O signals to the screw terminals
When connecting I/O signals to the screw terminals, note that each pair of relay contacts is independent and is connected
to its own pair of screw terminals, S0, S1, S2…etc. The screw terminals are grouped according to the four port addresses.
You may use wire sizes between 12AWG and 22AWG to make connections to the screw terminals. The screw terminals are
detachable from the board. Therefore, you may wire the connections away from the board, and then plug the wired
connections into the board.
Connecting power to the board
If you are using an MDB-64 Series controller board (non-isolated) and one or two MEM-32/A or MEM-32/W boards are
the only boards connected the MetraBus cable, then no external power is needed. The controller supplies the power.
NOTETo power your MEM-32/A or MEM-32/W from an MDB-64 Series controller board, you must first install fuse
F1 (1A) in the MDB-64.
However, in the following cases, you must connect an MBUS-PWR auxiliary power supply to one of the MetraBus cable
connectors, and you must remove fuse F1 from an MDB-64 controller:
• If you are connecting more than two MEM-32/A or MEM-32/W boards to the MetraBus cable.
• If you are connecting MetraBus boards needing ± 15VDC to the MetraBus cable.
• If you are using an MID-64 controller board (isolated).
See your MetraBus User’s Guide for more information about using an MBUS-PWR auxiliary power supply
CAUTIONIf you are using an MDB-64 Series controller board with an MBUS-PWR auxiliary power supply,
remove fuse F1 from the MDB-64. Failure to remove fuse F1 may damage the MDB-64, the MBUSPWR, or both.
4
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.