Tektronix 7708 User manual

Keithley Instruments
28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595
tek.com/keithley

Model 7708 Multiplexer Module

077144500 / April 2018 *P077144500* 1

Introduction

The Model 7708 40-Channel Differential Multiplexer Plug-In Module with Automatic CJC offers 40 channels of 2-pole or 20 channels of 4-pole multiplexer switching that can be configured as two independent banks of multiplexers. Automatic CJC is provided so that no other accessories are required to make thermocouple measurements. The 7708 is ideal for RTD, thermistor, and thermocouple temperature applications. It is also well suited for mixed-signal measurement applications that require multi-point monitoring, such as environmental stress screening.
Figure 1: Model 7708 40-Channel Differential Multiplexer Module
Item shipped may vary from model pictured here.
Model 7708 Multiplexer Module Instructions for use with DAQ6510
2 077144500 / April 2018
The 7708 includes the following features:
DC and AC voltage measurement ▪ Two-wire or four-wire resistance measurements (automatically pairs switches for four-wire
measurementsn + 20)
Temperature applications (RTD, thermistor, thermocouple) ▪ Built-in cold junction reference ▪ Screw terminal connections
The 7708 can be used with the DAQ6510 data acquisition instrument.
If you are using this switching module with the 2700, 2701, or 2750, please see the Model 7708 40­Channel Differential Multiplexer with Automatic CJC User's Guide, Keithley Instruments document number PA-744.

Connections

Connection and wiring procedures in this document are intended for use by qualified personnel only. Do not perform these procedures unless qualified to do so. Failure to recognize and observe normal safety precautions could result in personal injury or death.
Do not exceed the maximum specifications for the 7708 module. Refer to the specifications provided in the data sheet. Failure to recognize and observe normal safety precautions could result in personal injury or death.
Model 7708 Multiplexer Module Instructions for use with DAQ6510
077144500 / April 2018 3

Wiring procedure

Use the following procedure to make connections to the 7708 module. Make all connections using the correct wire size (up to 20 AWG).
All wiring must be rated for the maximum voltage in the system. For example, if 1000 V is applied to the front terminals of the instrument, the switching module wiring must be rated for 1000 V. Failure to recognize and observe normal safety precautions could result in personal injury or death.
Equipment needed:
Flat-blade screwdriver ▪ Cable ties
To wire the 7708 module:
1. Make sure all power is discharged from the 7708 module.
2. Using a screwdriver, turn the access screw to unlock and open the cover.
Figure 2: Screw terminal access
3. Using a small flat-blade screwdriver, loosen terminal screws and install wires as needed. Channel designations for the screw terminals are shown in the following figure.
Model 7708 Multiplexer Module Instructions for use with DAQ6510
4 077144500 / April 2018
4. Route wire along the cable path and secure with cable ties as shown. The following figure shows connections to channels 1 and 2.
Figure 3: Wire dressing
5. Record the connections in the Connection log (on page 8).
6. Close the cover.
7. Using a screwdriver, press in the access screw and turn to lock the cover.
Model 7708 Multiplexer Module Instructions for use with DAQ6510
077144500 / April 2018 5

Schematic diagram

The simplified schematic diagram of the 7708 is shown in the following figure. The channels are grouped into two banks of 20 channels (40 channels total). Backplane isolation is provided for each bank. Each bank also includes separate cold junction reference points.
The first bank contains channels 1 to 20 and the second bank contains channels 21 to 40. Each channel is wired with separate inputs for HI/LO, providing fully isolated inputs.
Although the 7708 relays are the latching type (relays hold their state even after power has been removed), all relay states are set to open a few seconds after either a power cycle or a reset command is issued.
Connections to DMM functions are provided through the module backplane connector of the instrument. When automatically configured for 4-wire measurements (including 4-wire resistance and RTD temperature),
the channels are paired as shown in the following table. Connect 4-wire sense leads using channels 21 to 40.
CH1 and CH21
CH8 and CH28
CH15 and CH35
CH2 and CH22
CH9 and CH29
CH16 and CH36
CH3 and CH23
CH10 and CH30
CH17 and CH37
CH4 and CH24
CH11 and CH31
CH18 and CH38
CH5 and CH25
CH12 and CH32
CH19 and CH39
CH6 and CH26
CH13 and CH33
CH20 and CH40
CH7 and CH27
CH14 and CH34
The 7708 switching module has 40 channels that can calculate ratio and channel average. The ratio calculation can be done for the DCV function, and the channel average calculation can be done for the DCV and TEMP (thermocouples only) functions. Paired channels are used for ratio and channel average. Channels are paired in the same manner as they are for 4-wire measurements.
Model 7708 Multiplexer Module Instructions for use with DAQ6510
6 077144500 / April 2018
Figure 4: Model 7708 simplified schematic
Channel 41 (2W/4W Configuration), Channel 42 (Sense Isolation), and Channel 43 (Input Isolation) are normally automatically configured by the DAQ6510.
Model 7708 Multiplexer Module Instructions for use with DAQ6510
077144500 / April 2018 7

Typical connections

The following examples show typical wiring connections for the following types of measurements:
Thermocouple ▪ Two-wire resistance and thermistor ▪ Four-wire resistance and RTD ▪ DC or AC voltage

Thermocouple connections

Figure 5: Thermocouple connections

Two-wire resistance and thermistor connections

Figure 6: Two-wire resistance and thermistor connections
Model 7708 Multiplexer Module Instructions for use with DAQ6510
8 077144500 / April 2018

Four-wire resistance and RTD connections

Figure 7: 4-wire resistance and RTD connections

DC or AC voltage connections

Figure 8: Voltage connections - DC or AC
Model 7708 Multiplexer Module Instructions for use with DAQ6510
077144500 / April 2018 9

Connection log

You can use the next table to record your connection information.
Channel
Color
Description
Description
Color
Channel
INPUT H
L
SENSE H
L
CH1 H
H
CH21 L
L
CH2 H
H
CH22 L
L
CH3 H
H
CH23 L
L
CH4 H
H
CH24 L
L
CH5 H
H
CH25 L
L
CH6 H
H
CH26 L
L
CH7 H
H
CH27 L
L
CH8 H
H
CH28 L
L
CH9 H
H
CH29 L
L
CH10 H
H
CH30 L
L
CH11 H
H
CH31 L
L
CH12 H
H
CH32 L
L
CH13 H
H
CH33 L
L
CH14 H
H
CH34 L
L
CH15 H
H
CH35 L
L
CH16 H
H
CH36 L
L
CH17 H
H
CH37 L
L
CH18 H
H
CH38 L
L
CH19 H
H
CH39 L
L
CH20 H
H
CH40 L
L
Loading...
+ 20 hidden pages