TEKTROL Tek-Flex 4100C Quick Start Manual

Page 1
Quick Start Guide
Tek-Flex 4100C
796 Tek Drive, Crystal Lake, IL 60014 USA
+1 847 857 6076 |+1 847 655 7428 +1 847 655 6147
www.tek-trol.com
Page 2
Quick Start Guide
Quick Start Guide
1. Before You Begin
This guide provides basic guidelines to assist you in quickly getting started. Go to our website to download the full User Guide for detailed installation, maintenance, troubleshooting and safety precautions.
The user must take note of the safety instructions in this operating instructions manual, the country specic installation standards as well as all prevailing safety regulations and accident prevention rules. The instrument must only be operated in a technically awless and reliable condition. The operator is responsible for trouble-free operation of the instrument. During the entire duration of use, the user is obliged to determine the compliance of the required occupational safety measures with the current valid rules and regulations and also take note of new regulations.
2. Unpack
One Tek-Flex 4100C Programmable Two-wire TDR Level Transmitter With Hart & Display
3. Dimensional Drawing
3.84"
(0.32 ft)
0.94"
0.86"
5.37" (0.44 ft)
1½ NPT
2.6"
3 ft. to 60 ft.
796 Tek Drive, Crystal Lake, IL 60014 USA
+1 847 857 6076 |+1 847 655 7428 +1 847 655 6147
5.91"
www.tek-trol.com
Page 3
Technology Solutions
4. Mounting Requirement
Basic Requirement for Installation
Keep in mind that the cable/rod is kept away from obstructions within vessel. The obstructions like: ladders, limit switches, heating spirals, struts and etc. Further more, rope or rods must not intersect the lling streams.
Be cautious during the installation: the level of the measured cable medium must not be in the blanking zone the mounting location must keep a min distance to the vessel wall, the cable or rod is perpendicular to the surface of the measured medium.
Illustration
The reference plane is the thread or ange surface 1 Blanking Zone 2 Length 3 Max. Measurement Range 4 Min. Measurement Range 5 Reference plane
2
4
3
5
100%
0%
Note: The level of the measured medium must not be in either the blanking zone.
The best mounting location for a conical vessel with at top is the centre of the vessel's top, as the eective measurement can reach the bottom of vessel.
1
Tek-Bar 3100
Tek-Flex 4100C
Page 4
Quick Start Guide
Quick Start Guide
Stand Pipe
Avoid installation with socket if possible, otherwise try to minimize the length of socket. In case of long stand pipe, small vessel or medium with low dielectric constant.
h
d
Mounting
1 Wrong: The rod/rope is in/above lling stream, which results in the measurement of lling stream not the target medium. 2 Correct
Note: Sun shield or rain-proof is suggested for outdoor mounting.
1
2
796 Tek Drive, Crystal Lake, IL 60014 USA
+1 847 857 6076 |+1 847 655 7428 +1 847 655 6147
www.tek-trol.com
Page 5
Technology Solutions
Horizontal and Vertical Installation
When mounting outdoors, humid indoors or on cooling/heating vessels, in order to avoid damp seal rings used on cables should be screwed tight, and the cable must be bended downward outside cable entry, as indicated on the diagram below:
5. Power Supply
Power supply and current signal are carried by the same two-wire connection cable. See the Technical Speci­cations of this guide for detailed requirement on power supply.
++-
1
2
1
-
2 Wire
Tek-Bar 3100
Tek-Flex 4100C
Page 6
Quick Start Guide
Quick Start Guide
6. Adjustment Instructions
Use the operation panel of the transmitter to set the conguration parameters such as the zero calibration, cut-o value of low ow and output range of current frequency, etc.
Display/Adjustment Module
dB
120 110 100 90 80 70 60 50 40 30 20 10
0
0.00
2.00 3.00 4.0 0 5.00
LCD
[OK] Keypad
Enter programming mode
Conrm programming options
Conrm modications to parameters
[ ] Keypad
Modify parameter values
Connect with Another Unit Through HART
2 Adjustment Keypad
[ ] Keypad
Choose programming options
Choose the digit of parameters to edit
Display the contents of parameters
[ BK ] Keypad
Programming mode exit
Return to higher menu level
HART to USB Modem
4100C
796 Tek Drive, Crystal Lake, IL 60014 USA
250 ohm Resistance
+1 847 857 6076 |+1 847 655 7428 +1 847 655 6147
www.tek-trol.com
Page 7
HART Handheld Programmer
Adjust 4100C with HART Handheld Programmer
4100C
7. Menu Tree
250 ohm Resistance
HART Handheld Programmer
+
- DC
Technology Solutions
Basic Setting
Display 2
Diagnostics 3
Service 4
Info 5
Min adjustment
1.1
Min adjustment
1.2
Medium 1.3
Fast level change
1.4
Damping 1.5
Mapping curve
1.6
Scaled units 1.7
Scaling 1.8
Sensor length
1.9
Linearity consumer
programme 1.5
Near blanking
1.10
Tek-Bar 3100
Tek-Flex 4100C
Sensor tag
1.11
Page 8
Quick Start Guide
Quick Start Guide
Basic Setting
Display 2
Diagnostics 3
Service 4
Info 5
Display value 2.1
LCD contrast 2.2
Peak values 3.1
Meas status 3.2
Choose curve 3.3
Echo curve 3.4
Simulation 3.5
Echo curve 4.1
Shut o map percent distance scaled height current percent
Distance- min Distance- max
Meas reliability sensor status
Echo curve false echo curve output trend
Curve zoom
Percent Current Distance
Delete Update Create new
X- zoom
Y- zoom
Unzoom
1X 2X 5X 10X
Current output
4.2
Reset 4.13
Units of measurement 4.4
Language 4.5
HART operation mode 4.6
Copy sensor Data 4.7
PIN 4.8
Sensor type serial number
5.1
Output mode Failure mode Min current
Select reset
M (d) ft (d)
Chinese English
Standard Multidrop
Copy from sensor Copy to sensor
Basic reset Factory settings Peak values
Date of manufacture software version 5.2
796 Tek Drive, Crystal Lake, IL 60014 USA
+1 847 857 6076 |+1 847 655 7428 +1 847 655 6147
www.tek-trol.com
Page 9
Technology Solutions
796 Tek Drive
Crystal Lake, IL 60014
USA
Tel: +1 847 857 6076, +1 847 655 7428
Fax : +1 847 655 6147
Email: tektrol@tek-trol.com
www.tek-trol.com
Tek-Flex 4100C
Loading...