Tek-Trol 3120B-G4-WP-1-HC-1, 3120B-G3-WP-1-HC-1, 3120B-G1-WP-1-HC-1, 3120B-G6-WP-1-HC-1, 3120B-G2-WP-1-HC-1 User manual

...
Page 1
Technology Solutions
EK-B
T
AR 3120B
Smart Gauge Pressure Transmitters
Instruction Manual
Document Number: IM-3120B
www.GlobalTestSupply.com
Page 2

Table of Contents

Table of Contents ................................................................................................................................. 1
1 Safety Instructions ......................................................................................................... 3
1.1 Intended Use .....................................................................................................................3
1.2 Certification .......................................................................................................................3
1.3 Safety Instructions from the Manufacturer .........................................................................3
Disclaimer ................................................................................................................................ 3
Product Liability and Warranty ............................................................................................... 3
Information Concerning the Documentation .......................................................................... 3
Safety Precautions ................................................................................................................... 4
1.4 Packaging, Transportation, and Storage ..............................................................................5
................................................................................................................................. 5
Transportation......................................................................................................................... 5
Storage .................................................................................................................................... 6
1.5 Nameplate .........................................................................................................................6
2 Product Description ....................................................................................................... 7
2.1 Introduction ......................................................................................................................7
2.2 Measurement Principle ......................................................................................................7
2.3 Specifications .....................................................................................................................8
General Specifications ............................................................................................................. 8
Damping Time ......................................................................................................................... 8
Environmental Conditions ....................................................................................................... 8
Power Supply ........................................................................................................................... 9
Measuring Range Limit for Tek-Bar 3110B.............................................................................. 9
2.4 Dimensional Drawings .......................................................................................................9
2.5 Model Chart..................................................................................................................... 10
3 Installation................................................................................................................... 11
3.1 Selecting the Installation Location .................................................................................... 11
3.2 Installation Procedure ...................................................................................................... 11
Install Pressure Transmitter .................................................................................................. 11
Process Connections ............................................................................................................. 12
Housing Rotation ................................................................................................................... 13
Terminal Side of Transmitter ................................................................................................ 13
LCD Display ............................................................................................................................ 13
Conduit Installation ............................................................................................................... 14
3.3 Mounting Requirements .................................................................................................. 14
Liquid Flow Measurement .................................................................................................... 14
Gas Flow Measurement ........................................................................................................ 15
Steam Flow Measurement .................................................................................................... 15
3.4 Field Adjustment ............................................................................................................. 16
Zero Point Adjustment .......................................................................................................... 16
Full Span Adjustment ............................................................................................................ 16
3.5 Product Usage ................................................................................................................. 16
Pipeline pressure measurement-pressure transmitter ......................................................... 16
Pipeline pressure measurement-differential pressure transmitter ...................................... 16
Steam flow measurement ..................................................................................................... 17
www.GlobalTestSupply.com
Page 3
Liquid flow measurement ..................................................................................................... 17
Air flow measurement........................................................................................................... 17
Open container level measurement-single flange level transmitter .................................... 17
Sealed container level measurement-single flange level transmitter .................................. 17
4 Electrical Connections .................................................................................................. 18
4.1 Grounding of Measuring Device ....................................................................................... 18
4.2 Power Supply Specifications and Connection .................................................................... 18
4.3 Cable Protection System .................................................................................................. 20
Standard Protection System .................................................................................................. 20
Explosion-proof Tube Protection System .............................................................................. 20
Connection to the HART Handheld Communicator .............................................................. 21
5 Operation .................................................................................................................... 22
5.1 Local Operation and Display ............................................................................................. 22
5.2 Operation in safe and hazardous area .............................................................................. 22
5.3 Configuration ................................................................................................................... 22
Key Operation ....................................................................................................................... 23
Factory Reset ......................................................................................................................... 23
Detailed Operating Instructions ............................................................................................ 23
5.4 Handheld Communicator ................................................................................................. 27
6 Maintenance ................................................................................................................ 28
6.1 Hardware Maintenance ................................................................................................... 28
Test Terminal ......................................................................................................................... 28
Disassembling the Electronics Housing ................................................................................. 29
External Cleaning ................................................................................................................... 29
Depot Repair ......................................................................................................................... 29
Discard Disposal .................................................................................................................... 29
7 Troubleshooting ........................................................................................................... 30
7.1 Symptoms and Corrective Measures ................................................................................. 30
7.2 Tek-Bar 3120B Smart Gauge Pressure Transmitter LCD Display error codes ........................ 32
www.GlobalTestSupply.com
Page 4

1 Safety Instructions

1.1 Intended Use

Tek-Bar 3120B is a Smart Gauge Pressure Transmitter used for pressure, flow, level and density measurement of steam and liquids. The manufacturer is not liable for damage caused by improper or non-designated use.

1.2 Certification

Tek-Bar 3120B has FM approval (Class I Div. I)

1.3 Safety Instructions from the Manufacturer

Disclaimer

The manufacturer will not be held accountable for any damage that happens by using its product, including, but not limited to direct, indirect, or incidental and consequential damages. Any product purchased from the manufacturer is warranted in accordance with the relevant product documentation and our Terms and Conditions of Sale. The manufacturer has the right to modify the content of this document, including the disclaimer, at any time for any reason without prior notice, and will not be answerable in any way for the possible consequence of such changes.

Product Liability and Warranty

The operator shall bear authority for the suitability of the device for the specific application. The manufacturer accepts no liability for the consequences of misuse by the operator. Wrong installation or operation of the devices (systems) will cause the warranty to be void. The respective Terms and Conditions of Sale, which forms the basis for the sales contract shall also apply.

Information Concerning the Documentation

To prevent any injury to the operator and damage to the device it is essential to read the information in this document and read the applicable national standard, and safety instruction. These operating instructions contain all the information that is required in various stages, like product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
www.GlobalTestSupply.com
Page 5
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTE
Indicates that operating the hardware or software in this manner may damage it or lead to system failure.

Safety Precautions

You must read these instructions carefully prior to installing and commissioning the device. These instructions are an important part of the product and must be kept for future reference. Only by observing these instructions, optimum protection of both personnel and the environment, as well as safe and fault-free operation of the device can be ensured.
For additional information that are not discussed in this manual, contact the manufacturer.
Warnings and Symbols Used
The following safety symbol marks are used in this operation manual and on the
instrument.
www.GlobalTestSupply.com
Page 6
NOTE
Unpack and check the contents for damages or signs of rough handling. Report damage to the manufacturer immediately. Check the contents against the packing list provided.

1.4 Packaging, Transportation, and Storage

This section contains information regarding packaging, transportation, and storage.

Packaging

The original package consists of
1. Tek-Bar 3120B Smart Gauge Pressure Transmitter
2. Accessories (optional)
3. Documentation

Transportation

Avoid impact shocks to the device and prevent it from getting wet during
Verify local safety regulations, directives, and company procedures with respect to
Transport the product to the installation site using the original manufacturer’s packing
transportation.
hoisting, rigging, and transportation of heavy equipment.
whenever possible.
www.GlobalTestSupply.com
Page 7
NOTE
Check the device nameplate to ensure that the device is delivered according to your order. Check for the correct supply voltage printed on the nameplate.

Storage

If this product is to be stored for a long period of time before installation, take the
following precautions:
Store your product in the manufacturer’s original packing used for shipping.
Storage location should conform to the following requirements:
o Free from rain and water o Free from vibration and impact shock o At room temperature with minimal temperature and humidity variation
Before storing a used flowmeter remove any fluid from the flowmeter line
completely. Properties of the instrument can change when stored outdoors.

1.5 Nameplate

The nameplate lists the order number and other important information, such as design details and technical data.
www.GlobalTestSupply.com
Page 8

2 Product Description

This section covers the reference and specification data, as well as ordering information.

2.1 Introduction

Tek-Bar 3120B single crystal silicon pressure transmitter utilizes world’s leading mono crystal silicon pressure sensor technology and outstanding encapsulation technology. It can handle the most rigorous industrial applications and it can cope up with extreme chemical, mechanical and electrical working conditions. Highly accurate and reliable measurement of level, density and pressure of liquid, gases or steam is possible with Tek-Bar 3120B. The performance accuracy is up to 0.075% of URL. This high-performance pressure transmitter meticulously designed by Tek-Trol supports HART communication protocol and IP66 waterproof protection. It is well equipped with several features that facilitate easy installation, start-up and minimum maintenance.

2.2 Measurement Principle

The Tek-Bar 3120B works on the principle of mono silicon technology. The pressure sensor
of the transmitter is located on the top of the metal body, away from the service fluid. This
enables mechanical and thermal isolation of the sensor from the fluid in service.
When pressure is applied on the diaphragm and the silicon piezoelectric sensor, they
become stressed and undergo a change in voltage resistance. This change in resistance is
directly proportional to the applied pressure, which is transferred to the transmitter body
using lead wires.
Built on semiconductor technology, the resistance change (piezoelectric effect) is notably higher than exhibited in standard strain gauges. Therefore, the sensitivity of mono­crystalline sensors is higher than the sensitivity of most other types.
www.GlobalTestSupply.com
Page 9
Parameter
Description
Pressure Type
Gauge Pressure
Accuracy
±0.075% F.S.
Diaphragm Materials
Hastelloy C
Ranges
5.8 psig to 5800 psig
Stability
±0.2 % URL/5 year
Process Connection
±0.075% F.S.
Wetted material
316LLS
Working Humidity
5 to 100%
Output Signal
Two wire 4to 20mA with Hart®
Mounting Position Effect
Apply to any position. Max value lower than 1.6 w.c.
(400 Pa) can be corrected by zero clearing function
Insulation Resistance
≥20 M Ω at 100 VDC
Process Connection
¼" NPT Female
Approvals
General purpose NEMA 4X or IP66
Weight (excluding Option Items)
3.43 lb (1.55kg) Testing Standard
IEC60770
Parameter
Description

Damping time

0-100s adjustable
Response time
≤0.2 s
Start-up after power off
≤6 s
Parameter
Description
Working temperature
-40 °F to 185 °F (-40 °C to 85 °C),
Storage temperature
-40 °F to 230 °F (-40 °C to 110 °C)
Media temperature
Silicon oil filling: -40 °F to 248 °F (-40 °C to 120 °C)
Working humidity
5-100% RH at 104 °F
Protection class
IP66

2.3 Specifications

General Specifications

Damping Time

Environmental Conditions

www.GlobalTestSupply.com
Page 10
Parameter
Description

Power supply

10.5-55 VDC (Hart: 16.5-55 VDC)
Load resistance
0-2119 Ω for working condition, 250- 600 Ω for HART protocol
Transmission distance
<3281ft Power consumption
≤500 mW at 24 VDC, 20.8 mA
Nominal
Value
Smallest
Calibrated Span
Lower Range Limit
(LRL)
Upper Range Limit
(URL)
Overload
Limit
5.8 psi
8 in.WC
-14.5
5.8 psi
145 psig
36 psi
2 psi
-14.5
36 psi
580 psig
145 psi
7.25 psi
-14.5
145 psi
870 psig
435 psi
22.25 psi
-14.5
435 psi
2175 psig
1450 psi
72.5 psi
-14.5
1450 psi
2900 psig
5800 psi
725 psi
-14.5
5800 psi
11600 psig
Power Supply

Measuring Range Limit for Tek-Bar 3110B

2.4 Dimensional Drawings

www.GlobalTestSupply.com
Page 11
Example
Tek-Bar 3120B-G
3
WP
1
HC
1
BA
Tek-Bar 3120B-G-3-WP-1-HC-1-BA
Series
Tek-Bar 3120B-G
Smart Gauge Pressure Transmitter
1
0 to 5.8 psig (40:1 Turndown, Adj. Range: -14.5 to +5.8 psig)
2
0 to 36 psig (40:1 Turndown, Adj. Range: -14.5 to +36 psig)
3
0 to 145 psig (40:1 Turndown, Adj. Range: -14.5 to +145 psig)
Range Options
4
0 to 435 psig (40:1 Turndown, Adj. Range: -14.5 to +435 psig)
5
0 to 1450 psig (40:1 Turndown, Adj. Range: -14.5 to +1450 psig)
6
0 to 5800 psig ( 8:1 Turndown, Adj. Range: -14.5 to 5800 psig)
Approval Rating
WP
AT
General Purpose NEMA 4X/IP66 ATEX
Process Connections
1
X
½" NPT Male
Diaphragm Seal
Diaphragm Material
HC
Hastelloy C
Electrical Connections
1
½" NPT Female
Options
CC
FC
BA
TAG
Custom Calibration with 5 point Calibration Certificate Factory
Configuration, No Certificate
Stainless Steel Bracket (Angle type) with SST Bolts
Custom Etching of the Name Plate (Must specify on P.O.)

2.5 Model Chart

www.GlobalTestSupply.com
Page 12
CAUTION
When removing the instrument from hazardous processes, avoid direct contact
with the fluid and the meter
All installation must comply with local installation requirements and local
electrical code
3 3 Installation
This section covers instructions on installation and commissioning. Installation of the device must be carried out by trained, qualified specialists authorized to perform such works.

3.1 Selecting the Installation Location

Prior to product installation, check the model, specifications and installation location for the transmitter. The transmitter is designed to withstand severe environmental conditions. However, follow the enlisted precautions while selecting the installation site to ensure stable and accurate operation for years.
Ambient Temperature
Avoid locations subjected to significant temperature gradient or wide temperature variations. If transmitter is exposed to radiant heat from plant’s equipment, then providing adequate thermal isolation and/or ventilation is desirable.
Ambient Atmosphere
Avoid corrosive atmosphere while installing the transmitter. If it must be installed in a corrosive atmosphere, then provide adequate ventilation and take the necessary measures to prevent intrusion or stagnation of rain water in conduits.
Shock and Vibration
Although the transmitter is designed to withstand shock and vibrations, it is recommended to select an installation site with minimum shock and vibration to avoid device damage and improve measurement accuracy.

3.2 Installation Procedure

This section includes the information regarding installation of the transmitter for safe and precise functioning. It provides the procedure and instruction for mounting, transmitter functions, and installation for specific applications.

Install Pressure Transmitter

Direct installation or mounting bracket installation may be used depending on the application and installation site requirement. Various mounting scenarios are illustrated in sections below.
www.GlobalTestSupply.com
Page 13

Process Connections

3.2.2.1 Straight Thread Connection
Picture 1: Ensure that the seal of head face gasket is effective by keeping the length of the pressure transmitter thread longer than the depth of the thread. Picture 2: Ensure that the seal of root gasket is effective by maintaining the length of the pressure transmitter thread shorter than the depth of the thread.
3.2.2.2 Taper Thread Connection
Use tapered thread connections to make better seals. Sealing with Teflon tape or sealant glue results in strong and leak resistant connections.
3.2.2.3 Flange Connection
Picture 1 Picture 2
Choose gasket according to the properties of the process medium and the temperature range. Pay attention to the bolt balance lock
3.2.2.4 Clamp Connection
www.GlobalTestSupply.com
Page 14
NOTE
Engage process connection with a minimum of 7 thread connections and tighten the housing rotation set screw to prevent it from rotating
Choose gaskets that meet specified standards to avoid excessive clamp locking and squeezing gasket. Excessive locking of clamp may damage the sensing diaphragm and cause measuring error.

Housing Rotation

To ensure the visibility of LCD display
Loosen the housing screw
Rotate housing to the desired angle up to 360
Re-tighten the housing screw

Terminal Side of Transmitter

Mount the transmitter in such a way that the terminal side is easily accessible to the operator.

LCD Display

Display module is used in field adjustment for parameter settings and site configuration before starting the measurement process. The local 5-digit LCD displays important parameters, which can be directly monitored at the measuring point. It enables the operator to configure the device using the function matrix.
o
The alignment of the display device can be adjusted vertically or horizontally as per the requirement of installation location. Unscrew the screws on either sides of the LCD screen to rotate it 90° clockwise or counter clockwise. The figure below illustrates the vertical and horizontal arrangement of the display device.
www.GlobalTestSupply.com
Page 15
NOTE
Conduit thread must be engaged with a minimum of 5 thread connections

Conduit Installation

Improper sealing of connections may damage the transmitter due to excess moisture accumulation. Mount the transmitter with electrical housing positioned downward so that the excess of moisture is condensed and drained out from the casing. Secondly, install wiring with a drip loop and ensure the bottom of the drip loop is mounted lower than the conduit connections or the transmitter housing to avoid moisture accumulation in the housing.

3.3 Mounting Requirements

Impulse piping configuration and transmitter position depends on specific measurement conditions. Follow the procedure below while installing transmitter for liquid, gases or steam processes.

Liquid Flow Measurement

Place the taps to the side of the line/pipe to prevent residue deposits on the
transmitter process isolators
Mount the transmitter beside or below the taps so gases can vent into the process
line
Mount drain/vent the valve upward to allow gases to vent
Flow
www.GlobalTestSupply.com
Page 16
NOTE
For steam or other higher temperature processes, ensure that the temperature at the process connection does not exceed the transmitter’s process temperature limits.
Flow
Flow

Gas Flow Measurement

Place the taps in the top or side of the line
Mount the transmitter beside or above the taps so liquid will drain into the process
line

Steam Flow Measurement

Place taps to the side of the line
Mount the transmitter below the taps to ensure that the impulse piping stays filled
with condensate
In steam service above 250°F (121°C), fill impulse lines with water to prevent the
direct steam contact with the transmitter and to ensure accurate measurement at start-up
www.GlobalTestSupply.com
Page 17

3.4 Field Adjustment

Perform field adjustments only after installing the transmitter at its final work location otherwise the set parameters may drift due to jerks while transporting or handling.

Zero Point Adjustment

For sensor zero trim, ensure that the vessel is empty and there is no input medium
pressure on the diaphragm. The vessel should be applied a normal atmospheric pressure. If applying external pressure to the transmitter make sure that the display is sufficiently stabilized (after approximately 10 to 15 seconds), before initiating any trim function.
There are 3 ways of making input pressure “Zero”.
Apply a “Zero” pressure source (mandatory for absolute pressure models) Apply equal pressure on both HP and LP ports (DP models only) Open equalizing valve of manifolds installed and venting to atmospheric
pressure (applicable for Gauge & DP type models only)
Sensor zero trim can be performed using an external HHC (Handheld calibrator), PC
or PDA configurator, and/or using Zero/Span local push buttons provided on the transmitter.
Using local push buttons set PV=0, refer to section 5.2.1 of this manual for detailed
instructions. If using an external HHT or HART® PC configurator, refer to the user manual supplied by the third-party supplier.

Full Span Adjustment

For full span adjustment, ensure that the vessel is filled with process medium to the
maximum level.
Maintain static pressure value within the minimum and maximum pressure range
Using local push buttons set output for lower and upper limit of the full scale i.e.
4mA and 20mA, refer to section 5.2 of this manual for detailed key operations.
The device is now ready for the real-time process measurement.

3.5 Product Usage

Pipeline pressure measurement-pressure transmitter

For high temperature steam measurements, pre-inject more than half-tube cooling water in the condenser. Once the steam pipes are stable, gradually open the shut-off valve to start measurement.

Pipeline pressure measurement-differential pressure transmitter

For high temperature steam measurement in a pipeline by differential pressure transmitter, pre-inject cooling water into the guided pipe. Once the steam pipes are stable, slowly open the shut-off valve and start measuring.
www.GlobalTestSupply.com
Page 18
Differential pressure transmitters are commonly used for micro pressure measurement of hydrostatic pressures such as filter and equipment leakage tests for improving accuracy.

Steam flow measurement

For steam flow measurement, up-tilt the guiding pressure tube by 45°. Ensure that transmitter installation location is at lower level than that of the process pipeline. Pre­inject cooling liquid into the guiding pressure tube. Slowly open the shut-off valve to start measurement. Periodically open the drain vent to clear the residual steam from guided pipeline to improve the measurement accuracy.

Liquid flow measurement

For liquid flow measurement, tilt down the guiding pressure tube by 45°. Ensure that transmitter installation location is at lower level than that of the process pipeline. Pre­inject cooling liquid into the guiding pressure tube. Slowly open the shut-off valve to start measurement. Periodically open the drain vent to clear the residual liquid, which will improve the measurement accuracy.

Air flow measurement

For liquid flow measurement, up-tilt the guiding pressure tube by 45°. Ensure that transmitter installation location is at lower level than that of the process pipeline. Pre­inject cooling liquid into the guiding pressure tube. Slowly open the shut-off valve to start measurement. Periodically open the drain vent to clear the residual gas from the guiding pressure tube, which will improve the measurement accuracy.

Open container level measurement-single flange level transmitter

Verify the process medium compatibility in case of open container level measurement. For accurate measurement, install the transmitter at a location where liquid level and temperature fluctuations are minimal.

Sealed container level measurement-single flange level transmitter

Use a single flange diaphragm system for sealed container level measurement. Increase the isolation tank and multiple shut-off valves. Periodically open the drain/vent valve to clear off the residual gas and liquid in the guiding pressure tube for higher accuracy.
www.GlobalTestSupply.com
Page 19
WARNING
Connect all electrical cables when the power is switched off. If the device does
not have switch-off elements, then, overcurrent protection devices, lightning protection and/or energy isolating devices must be provided by the customer.
The device must be grounded to a spot in accordance with regulations to
protect personnel against electric shocks.
NOTE
When using the measuring device in hazardous areas, installation must
comply with the corresponding national standards and regulations and the Safety Instructions or Installation or Control Drawings.

4 Electrical Connections

This section covers the all electrical connection requirement. Electrical connection of the device must be carried out by trained, qualified specialists authorized to perform such work by the installation site.

4.1 Grounding of Measuring Device

Ensure proper grounding at control cabinet and pressure transmitter.
Ground terminals are provided on the either sides (inside and outside) of the terminal
box. Either one of these terminals may be used for grounding the transmitter.
Use shielded twisted pair cable to avoid ground loops.
Use internal ground terminals for direct grounding.

4.2 Power Supply Specifications and Connection

Use independent linear direct current power supply for pressure transmitter. Large resistive load results in high pressure drop. Therefore, it is recommended to consider the resistance across the signal cable, display meter and other equipment to ensure sufficient voltage is provided to the pressure transmitter for its normal operation.
www.GlobalTestSupply.com
Page 20
Label
Two Wires
Three Wires
Four Wires
+
Power +
Power +
Power +
-
Power -
Power -
Power -
A Signal +
Signal +
B
Signal -
Standard current signal output: 12-30VDC, Current signal output with HART: 16.5-55VDC, Current signal output with intrinsic safety: 12-30VDC, Modbus-RTU/RS485 signal output: 5VDC/9-30VDC, 0.5-4.5VDC Voltage signal output: 5 VDC/6-15VDC.
Remove the housing cover on terminal compartment side. Do not remove the cover in explosive atmospheres when the circuit is live.
Power supply connections:
Connect power supply +’ terminal to transmitter +’ terminal.
Connect signal + terminal to transmitter -’ terminal.
Connect signal - terminal to power supply -’ terminal.
Do not connect power signal wiring to the test terminals as it could damage the test
diode.
Power Supply Connections
www.GlobalTestSupply.com
Page 21

4.3 Cable Protection System

Apply following cable protection measures to protect the connecting cables from various factors that affect negatively on the cable lifetime.

Standard Protection System

To avoid liquid flowing along with the cable into the terminal box, configure a
U-shaped ring between pull box and pressure transmitter as shown in the figure below.
Ensure that the level of U-shaped bottom is maintained below the pressure
transmitter.
Use sufficiently long cable considering the maintenance and repair factors.

Explosion-proof Tube Protection System

If the transmitter is situated in dangerous area, use a high quality metallic explosion-
proof tube as a casing for the cable connecting the transmitter to the terminal box.
www.GlobalTestSupply.com
Page 22

Connection to the HART Handheld Communicator

A loop resistance for HART Communicator is between 250Ω and 550Ω. Transmitter operates on 11.9 –45 VDC. Figure below illustrates the connection details for HHT communicator.
www.GlobalTestSupply.com
Page 23
NOTE
Calibrate the instrument according the instructions given in this section, otherwise it could lead to measurement error.

5 Operation

This section covers operation techniques and guidelines along with the configuration and calibration.

5.1 Local Operation and Display

Tek-Bar 3120B is available with the optional LCD display. The local display enables user to read important parameters directly at the measuring point and configure the device using the function matrix. The display indicates output and diagnostic messages. It features a two-line display with 5-digit. The first line displays measured value and the second line displays the engineering units. If LCD display is not available, then use HART for communication (Refer section 5.4).

5.2 Operation in safe and hazardous area

The internal and external buttons are provided for operation in safe and hazardous areas respectively.
While operating in safe area, open the front cover and use internal buttons.
While operating in hazardous area, slide the nameplate located at the upper side of
the transmitter and use the external buttons.
External buttons for operation in hazardous area

5.3 Configuration

This section provides detailed information of initial setup required for transmitter functioning. The device consists of 3 operation key: S, Z and M which are used to set parameters and perform various operations. The primary function of each key is mentioned as below. Z: Enter the setting options S: Modify the parameter value M: Confirm the set value and enter the next menu The same keys are used in combination to perform several advanced functions.
www.GlobalTestSupply.com
Page 24

Key Operation

Consider the factory setting for pressure measurement is set as follows: Pressure range: -10 to 100 kPa; Output current display unit: mA For performing zero-point adjustment and full span pressure adjustment follow the instructions and display screenshots given in the flow diagram below.

Factory Reset

Achieving the original factory settings at any point of time after the installation of the transmitter is possible by either of the following methods.

Detailed Operating Instructions

Refer the following flow diagrams to configure various parameters. Use parameter table to know the possible range of values and units.

www.GlobalTestSupply.com
Page 25
www.GlobalTestSupply.com
Page 26
www.GlobalTestSupply.com
Page 27
Parameter
Values
Display mode
%
Percentage
pV
Process variable
mA
Current
Units
Use the keys Z() and S() to change the units
kPa
MPa
bar
psi
mmHg
mmH2O
mH2O
inH2O
ftH2O
inHg
mHg
TORR
mbar
g/cm2
Kg/cm2
Pa
ATM
mm
M
Lower and Upper range
-19999-99999 Damping time
0 ~ 100 s
Output signal type
Square root
LINER
Linear
Fault alarm signal
NO
None
H
20.8 mA
L
3.8 mA
Output current
No (none)
3.8000 mA
4.0000 mA
8.0000 mA
12.000 mA
16.000 mA
20.000 mA
20.800 mA
Density
0.0001-99999
Centre distance
0.0001-99999
Coefficient
0.0001-99999
Parameter Table
www.GlobalTestSupply.com
Page 28
Cutting value
0-99.999
Pressure type GAUGE
Gauge, differential
ABSOLUTE
Absolute pressure

5.4 Handheld Communicator

If custom display is not available, then configure transmitter parameter using communicator. Decimal point position, Upper range value, Lower range value, Engineering units are configured. See the below flow chart.
www.GlobalTestSupply.com
Page 29
WARNING
Explosion can result into a serious injury or death.
Do not remove the transmitter cover in explosive environments when the
circuit is live.
After disconnecting power wait for a minute to allow the circuit and enclosure
to cool down before opening.
Avoid direct contact with the leads and terminals. High voltage on leads can
cause electrical shock.
Ensure that the transmitter casings are sealed when the assembly is in
operating condition.
Only trained and qualified personnel may undertake start-up and maintenance
activities.

6 Maintenance

This section covers maintenance techniques and guidelines.

6.1 Hardware Maintenance

Perform maintenance task at regular intervals. Set the maintenance schedule in advance and maintain a logbook to note maintenance activity details. Maintenance schedule depends on the system, installation conditions, working medium and rigorousness of the operation. Consider the system downtime when maintenance cycle is running. Ensure that it does not affect the system performance.
Maintenance majorly involves sensor cleaning and verifying connections.

Test Terminal

Test Terminal is marked as TEST on the terminal block. Connect TEST and negative terminal to the test terminal. Ensure that the voltage across the receptacles is kept below the diode threshold voltage so that no current passes through the diode. Make sure that the resistance of the test connection does not exceed 10 ohms while connecting an indicating meter or while taking the test readings. Note that a resistance of 30 ohms can cause an error of approximately 10% of actual value.
www.GlobalTestSupply.com
Page 30

Disassembling the Electronics Housing

The transmitter assembly comes in dual-compartment housing; one contains the electronic module, and the other contains all wiring terminals and the communication receptacles. The separate compartment of wiring terminals ensures hassle free handling while running a routine maintenance cycle.

External Cleaning

Use washing agent that will not damage the instruments.
Protect the pressure sensing diaphragm from mechanical damage caused by sharp
objects or external pressure.
Mechanical cleaning of the diaphragm is strictly prohibited.
Do not point the nozzles to the diaphragm when cleaning by pressure washer.

Depot Repair

Execute following steps before sending the device for depot repair:
Disconnect the transmitter carefully. Preserve all accessories and cables for
reassembling.
Remove the harmful residues such as inflammable, poisonous, cancer genic and
radioactive substances.
Repack the device in original packaging material provided at the time of delivery
and send for repair.

Discard Disposal

It is recommended to pass the instrument to specialized recycling companies rather than local recycling points.
www.GlobalTestSupply.com
Page 31
Symptom
Potential Source
Corrective Action
No communication between the Transmitter and HART communicator
Loop Wiring
Check for a minimum of 250 ohms resistance between the power supply and HHT.
Check for an adequate voltage to the transmitter. The transmitter always requires 11.9 to 45 VDC.
Check for intermittent shorts, open circuits, and multiple grounds
High Output
Sensor Input Failure
Connect
HHT
and enter the Transmitter test mode to isolate a sensor failure.
Loop Wiring
Check for dirty or defective terminals, interconnecting pins, or receptacles.

7 Troubleshooting

This section provides troubleshooting techniques for most common operating problems.
When device malfunction is suspected despite the absence of any diagnostic messages on the HHT, inspect following points.
If measurement signal appears irregular, check whether the process pressure is
within the working range, or the abnormality lies in the measuring system, installation environment or pressure transmitter. Once diagnosed take corresponding measures.
If no signal output or unchanged output signal on corresponding process pressure
changes is observed, then check the power supply polarity, open or short circuit. Check the parameters like voltage, power and load resistance meet the normal working requirements. Also, ensure there is no leakage or pressure-impulse line blockage and shut-off valve is closed.
If the output signal is large or outside the normal range, check whether the supply
voltage, power consumption, and load resistance meet the normal working requirements of pressure transmitters. Verify measuring range settings and adjust the device calibration. Also, ensure there is no leakage, pressure-impulse line blockage or rapid temperature fluctuations in the installation and shut-off valve is closed.

7.1 Symptoms and Corrective Measures

Refer to the table below to verify whether the transmitter hardware and process connections are in good working condition:
www.GlobalTestSupply.com
Page 32
Power Supply
Check the output voltage of the power supply at the transmitter terminals. It should be 11.9 to 45 VDC in spite of loop scale
Electronics Module
Connect HHT and enter the Transmitter test mode to isolate module failure. Check the sensor limits to ensure calibration adjustments are within the sensor range.
Erratic Output
Loop Wiring
Check the output voltage of the power supply at the transmitter terminals. It should be 11.9 to 45 VDC.
Check for intermittent shorts, open circuits, and multiple grounds.
Check for proper polarity at the signal terminals.
In case measuring electric current while digital communication, output appear around +-0.013mA
Electronics Module
Connect HHT and enter the transmitter test mode to isolate an electronics mode failure.
Low Output or No Output
Sensor Element
Connect HHT and enter the Transmitter test mode to isolate the sensor failure.
Check the PV to see if it is out of range.
Loop Wiring
Check for adequate voltage to the transmitter. The transmitter always requires 11.9 to 45 VDC.
Check for intermittent shorts, open circuits, and multiple grounds.
Check polarity of signal terminal
Check the loop impedance.
Electronics Module
Connect HHT and check the sensor limits to ensure calibration adjustments are within the sensor range.
www.GlobalTestSupply.com
Page 33
Message
Description
ADJ-U
Out of Zero setting value when Zero Adj function using button (upper side)
ADJ-L
Out of Zero setting value when Zero Adj function using button (lower side)
ZERO
Initial message in using the Zero button
SPAN
Initial message in using the Span button
BT-ERR
Button Input Sequence Error
P-LOCK
Button Input Error when Protect Locked
ZT-ERR
Setting Limit (10%) Error when in Zero Trim
-TR-
Zero Trim Complete
ZR-ERR
Setting Limit Error when executing the Zero button function
-TR-
Zero Trim Complete
ZR-ERR
Setting Limit Error when executing the Zero button function
SP-ERR
Setting Limit Error when executing the Span button function
-ZR-
Zero button function Complete
-SP-
Span button function Complete
-ZA-
Zero Adjustment done
-DONE-
Setting Done using button
RNGOVR
Setting Limit error when executing other setting function
LCD_OV
Over figure values for LCD
SCD-ER
Sensor Code Error
F-RST
Flash Setting Data Rese
F-LOCK
While Flash Setting Data Reset, Protect Locked
F-FAIL
Flash Setting Data Reset Failure
-FR-
Flash Reset Done
A-RST
Analog EEPROM Initializing Start
A-STOR
Analog EEPROM Whole Write
A-FAIL
Analog EEPROM Whole Write Failure

7.2 Tek-Bar 3120B Smart Gauge Pressure Transmitter LCD Display error codes

www.GlobalTestSupply.com
Loading...