Tek-Bar 3110B is a Smart Differential Pressure Transmitter used for pressure, flow, level
and density measurement of steam and liquids.
The manufacturer is not liable for damage caused by improper or non-designated use.
1.2 Certification
Tek-Bar 3110B has FM approval (Class I Div. I)
1.3 Safety Instructions from the Manufacturer
Disclaimer
The manufacturer will not be held accountable for any damage that happens by using its
product, including, but not limited to direct, indirect, or incidental and consequential
damages.
Any product purchased from the manufacturer is warranted in accordance with the
relevant product documentation and our Terms and Conditions of Sale.
The manufacturer has the right to modify the content of this document, including the
disclaimer, at any time for any reason without prior notice, and will not be answerable
in any way for the possible consequence of such changes.
Product Liability and Warranty
The operator shall bear authority for the suitability of the device for the specific
application. The manufacturer accepts no liability for the consequences of misuse by the
operator. Wrong installation or operation of the devices (systems) will cause the
warranty to be void. The respective Terms and Conditions of Sale, which forms the basis
for the sales contract shall also apply.
Information Concerning the Documentation
To prevent any injury to the operator and damage to the device it is essential to read
the information in this document and read the applicable national standard, and safety
instruction. These operating instructions contain all the information that is required in
various stages, like product identification, incoming acceptance and storage, to
mounting, connection, operation and commissioning through to troubleshooting,
maintenance and disposal.
You must read these instructions carefully prior to installing and commissioning the
device. These instructions are an important part of the product and must be kept for
future reference. Only by observing these instructions, optimum protection of both
personnel and the environment, as well as safe and fault-free operation of the device
can be ensured.
For additional information that are not discussed in this manual, contact the
manufacturer.
Warnings and Symbols Used
The following safety symbol marks are used in this operation manual and on the
instrument.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury. It may also be used to alert against unsafe practices.
NOTE
Indicates that operating the hardware or software in this manner may damage it or
lead to system failure.
If this product is to be stored for a long period of time before installation, take the
following precautions:
•Store your product in the manufacturer’s original packing used for shipping.
•Storage location should conform to the following requirements:
oFree from rain and water
oFree from vibration and impact shock
oAt room temperature with minimal temperature and humidity variation
•Before storing a used flowmeter remove any fluid from the flowmeter line
completely. Properties of the instrument can change when stored outdoors.
1.5 Nameplate
The nameplate lists the order number and other important information, such as design
details and technical data.
NOTE
Check the device nameplate to ensure that the device is delivered according to
your order. Check for the correct supply voltage printed on the nameplate.
This section covers the reference and specification data, as well as ordering information.
2.1 Introduction
Tek-Bar 3110B single crystal silicon pressure transmitter utilizes world’s leading mono
crystal silicon pressure sensor technology and outstanding encapsulation technology. It
can handle the most rigorous industrial applications and it can cope up with extreme
chemical, mechanical and electrical working conditions. Highly accurate and reliable
measurement of level, density and pressure of liquid, gases or steam is possible with TekBar 3110B. The performance accuracy is up to 0.075% of URL. This high-performance
pressure transmitter meticulously designed by Tek-Trol supports HART communication
protocol and IP66 waterproof protection. It is well equipped with several features that
facilitate easy installation, start-up and minimum maintenance.
2.2 Measurement Principle
Tek-Bar 3110B Smart Differential Pressure Transmitter works on mono silicon technology.
The mono silicon pressure sensor is located on the top of the metal body and away from
the process fluid forming mechanical and thermal isolation.
Pressure applied on the diaphragm creates stress on the pair of piezoelectric crystals
causing a change in the voltage resistance. The change in resistance is directly
proportional to applied pressure and is transferred to the transmitter body through lead
wires. The transmitter carries out the further process of signal conditioning.
Built on semiconductor technology, the resistance change due to piezoelectric effect is
notably higher than that exhibited in standard strain gauges. Therefore, the sensitivity of
mono crystal pressure sensors is higher than most of other pressure sensor types.
This section covers instructions on installation and commissioning. Installation of the
device must be carried out by trained, qualified specialists authorized to perform such
works.
CAUTION
• When removing the instrument from hazardous processes, avoid direct contact
with the fluid and the meter
• All installation must comply with local installation requirements and local
electrical code
3.1 Selecting the Installation Location
Prior to product installation, check the model, specifications and installation location for
the transmitter. The transmitter is designed to withstand severe environmental
conditions. However, follow the enlisted precautions while selecting the installation site
to ensure stable and accurate operation for years.
• Ambient Temperature
Avoid locations subjected to significant temperature gradient or wide temperature
variations. If transmitter is exposed to radiant heat from plant’s equipment, then
providing adequate thermal isolation and/or ventilation is desirable.
• Ambient Atmosphere
Avoid corrosive atmosphere while installing the transmitter. If it must be installed in a
corrosive atmosphere, then provide adequate ventilation and take the necessary
measures to prevent intrusion or stagnation of rain water in conduits.
• Shock and Vibration
Although the transmitter is designed to withstand shock and vibrations, it is
recommended to select an installation site with minimum shock and vibration to
avoid device damage and improve measurement accuracy.
3.2 Installation Procedure
This section includes the information regarding installation of the transmitter for safe and
precise functioning. It provides the procedure and instruction for mounting, transmitter
functions, and installation for specific applications.
www.GlobalTestSupply.com
12
Technology Solutions
Instruction Manual
Tek-Bar 3110B
Install Pressure Transmitter
Direct installation or mounting bracket installation may be used depending on the
application and installation site requirement. Various mounting scenarios are illustrated
in sections below.
3.2.1.1 Direct/Bracket Installation
Direct Installation Bracket Installation
3.2.1.2 Mounting Bracket Installation Types
Pipe mounting bent bracket Plate mounting bent bracket Pipe mounting flat bracket
Process Connections
3.2.2.1 Straight Thread Connection
Picture 1 Picture 2
Picture 1: Ensure that the seal of head face gasket is effective by keeping the length of
the pressure transmitter thread longer than the depth of the thread.
Picture 2: Ensure that the seal of root gasket is effective by maintaining the length of
the pressure transmitter thread shorter than the depth of the thread.
Use tapered thread connections to make better seals. Sealing with Teflon tape or
sealant glue results in strong and leak resistant connections.
3.2.2.3 Flange Connection
Choose gasket according to the properties of the process medium and the
temperature range. Pay attention to the bolt balance lock
3.2.2.4 Clamp Connection
Choose gaskets that meet specified standards to avoid excessive clamp locking and
squeezing gasket. Excessive locking of clamp may damage the sensing diaphragm and
cause measuring error.
NOTE
Engage process connection with a minimum of 7 thread connections and tighten
the housing rotation set screw to prevent it from rotating
Mount the transmitter in such a way that the terminal side is easily accessible to the
operator.
LCD Display
Display module is used in field adjustment for parameter settings and site configuration
before starting the measurement process. The local 5-digit LCD displays important
parameters, which can be directly monitored at the measuring point. It enables the
operator to configure the device using the function matrix.
The alignment of the display device can be adjusted vertically or horizontally as per the
requirement of installation location. Unscrew the screws on either sides of the LCD
screen to rotate it 90° clockwise or counter clockwise. The figure below illustrates the
vertical and horizontal arrangement of the display device.
Vertical and horizontal arrangement
Conduit Installation
Improper sealing of connections may damage the transmitter due to excess moisture
accumulation. Mount the transmitter with electrical housing positioned downward so
that the excess of moisture is condensed and drained out from the casing. Secondly,
install wiring with a drip loop and ensure the bottom of the drip loop is mounted lower
than the conduit connections or the transmitter housing to avoid moisture
accumulation in the housing.
NOTE
Conduit thread must be engaged with a minimum of 5 thread connections
3.3 Mounting Requirements
Impulse piping configuration and transmitter position depends on specific measurement
conditions. Follow the procedure below while installing transmitter for liquid, gases or
steam processes.
Liquid Flow Measurement
• Place the taps to the side of the line/pipe to prevent residue deposits on the
transmitter process isolators
• Mount the transmitter beside or below the taps so gases can vent into the process
line
• Mount drain/vent the valve upward to allow gases to vent
the process connection does not exceed the transmitter’s process temperature
NOTE
For steam or other higher temperature processes, ensure that the temperature at
limits.
3.4 Field Adjustment
Perform field adjustments only after installing the transmitter at its final work location
otherwise the set parameters may drift due to jerks while transporting or handling.
Zero Point Adjustment
• For sensor zero trim, ensure that the vessel is empty and there is no input medium
pressure on the diaphragm. The vessel should be applied a normal atmospheric
pressure. If applying external pressure to the transmitter make sure that the display
is sufficiently stabilized (after approximately 10 to 15 seconds), before initiating any
trim function.
• There are 3 ways of making input pressure “Zero”.
➢ Apply a “Zero” pressure source (mandatory for absolute pressure models)
➢ Apply equal pressure on both HP and LP ports (DP models only)
➢ Open equalizing valve of manifolds installed and venting to atmospheric
pressure (applicable for Gauge & DP type models only)
• Sensor zero trim can be performed using an external HHC (Handheld calibrator), PC
or PDA configurator, and/or using Zero/Span local push buttons provided on the
transmitter.
• Using local push buttons set PV=0, refer to section 5.2.1 of this manual for detailed
instructions. If using an external HHT or HART® PC configurator, refer to the user
manual supplied by the third-party supplier.
For high temperature steam measurements, pre-inject more
than half-tube cooling water in the condenser. Once the steam
pipes are stable, gradually open the shut-off valve to start
measurement.
For high temperature steam measurement in a pipeline
by differential pressure transmitter, pre-inject cooling
water into the guided pipe. Once the steam pipes are
stable, slowly open the shut-off valve and start
measuring.
Differential pressure transmitters are commonly used for
micro pressure measurement of hydrostatic pressures
such as filter and equipment leakage tests for improving
accuracy.
For steam flow measurement, up-tilt the guiding
pressure tube by 45°. Ensure that transmitter
installation location is at lower level than that of the
process pipeline. Pre-inject cooling liquid into the
guiding pressure tube. Slowly open the shut-off valve
to start measurement. Periodically open the drain
vent to clear the residual steam from guided pipeline
to improve the measurement accuracy.
For liquid flow measurement, tilt down the guiding
pressure tube by 45°. Ensure that transmitter installation
location is at lower level than that of the process
pipeline. Pre-inject cooling liquid into the guiding
pressure tube. Slowly open the shut-off valve to start
measurement. Periodically open the drain vent to clear
the residual liquid, which will improve the measurement
accuracy.
For liquid flow measurement, up-tilt the guiding pressure tube
by 45°. Ensure that transmitter installation location is at lower
level than that of the process pipeline. Pre-inject cooling liquid
into the guiding pressure tube. Slowly open the shut-off valve
to start measurement. Periodically open the drain vent to clear
the residual gas from the guiding pressure tube, which will
improve the measurement accuracy.
Open container level measurement-single flange level transmitter
Verify the process medium compatibility in case of
open container level measurement. For accurate
measurement, install the transmitter at a location
where liquid level and temperature fluctuations are
minimal.
Use a single flange diaphragm system for sealed
container level measurement. Increase the isolation
tank and multiple shut-off valves. Periodically open
the drain/vent valve to clear off the residual gas and
liquid in the guiding pressure tube for higher
accuracy.
This section covers the all electrical connection requirement. Electrical connection of the
device must be carried out by trained, qualified specialists authorized to perform such
work by the installation site.
WARNING
• Connect all electrical cables when the power is switched off. If the device does
not have switch-off elements, then, overcurrent protection devices, lightning
protection and/or energy isolating devices must be provided by the customer.
• The device must be grounded to a spot in accordance with regulations to
protect personnel against electric shocks.
NOTE
• When using the measuring device in hazardous areas, installation must
comply with the corresponding national standards and regulations and the
Safety Instructions or Installation or Control Drawings.
4.1 Grounding of Measuring Device
• Ensure proper grounding at control cabinet and pressure transmitter.
• Ground terminals are provided on the either sides (inside and outside) of the terminal
box. Either one of these terminals may be used for grounding the transmitter.
• Use shielded twisted pair cable to avoid ground loops.
• Use internal ground terminals for direct grounding.
Use independent linear direct current power supply for pressure transmitter. Large
resistive load results in high pressure drop. Therefore, it is recommended to consider the
resistance across the signal cable, display meter and other equipment to ensure sufficient
voltage is provided to the pressure transmitter for its normal operation.
Standard current signal output: 12-30VDC,
Current signal output with HART: 16.5-55VDC,
Current signal output with intrinsic safety: 12-30VDC,
Modbus-RTU/RS485 signal output: 5VDC/9-30VDC, 0.5-4.5VDC
Voltage signal output: 5 VDC/6-15VDC.
Remove the housing cover on terminal compartment side. Do not remove the cover in
explosive atmospheres when the circuit is live.
Power supply connections:
• Connect power supply ‘+’ terminal to transmitter ‘+’ terminal.
• Connect signal ‘+’ terminal to transmitter ‘-’ terminal.
• Connect signal ‘-’ terminal to power supply ‘-’ terminal.
• Do not connect power signal wiring to the test terminals as it could damage the test
• If the transmitter is situated in dangerous area, use a high quality metallic explosion-
proof tube as a casing for the cable connecting the transmitter to the terminal box.
Connection to the HART Handheld Communicator
A loop resistance for HART Communicator is between 250Ω and 550Ω. Transmitter
operates on 11.9 –45 VDC. Figure below illustrates the connection details for HHT
communicator.
This section covers operation techniques and guidelines along with the configuration and
calibration.
NOTE
Calibrate the instrument according the instructions given in this section, otherwise
it could lead to measurement error.
5.1 Local Operation and Display
Tek-Bar 3110B is available with the optional LCD display. The local display enables user to
read important parameters directly at the measuring point and configure the device using
the function matrix. The display indicates output and diagnostic messages. It features a
two-line display with 5-digit. The first line displays measured value and the second line
displays the engineering units. If LCD display is not available, then use HART for
communication (Refer section 5.4).
5.2 Operation in safe and hazardous area
The internal and external buttons are provided for operation in safe and hazardous
areas respectively.
• While operating in safe area, open the front cover and use internal buttons.
• While operating in hazardous area, slide the nameplate located at the upper side of
the transmitter and use the external buttons.
External buttons for operation in hazardous area
5.3 Configuration
This section provides detailed information of initial setup required for transmitter
functioning.
The device consists of 3 operation key: S, Z and M which are used to set parameters and
perform various operations. The primary function of each key is mentioned as below.
Z: Enter the setting options
S: Modify the parameter value
M: Confirm the set value and enter the next menu
The same keys are used in combination to perform several advanced functions.
Consider the factory setting for pressure measurement is set as follows:
Pressure range: -10 to 100 kPa; Output current display unit: mA
For performing zero-point adjustment and full span pressure adjustment follow the
instructions and display screenshots given in the flow diagram below.
Factory Reset
Achieving the original factory settings at any point of time after the installation of the
transmitter is possible by either of the following methods.
If custom display is not available, then configure transmitter parameter using
communicator. Decimal point position, Upper range value, Lower range value,
Engineering units are configured. See the below flow chart.
This section covers maintenance techniques and guidelines.
WARNING
Explosion can result into a serious injury or death.
• Do not remove the transmitter cover in explosive environments when the
circuit is live.
• After disconnecting power wait for a minute
enclosure to cool down before opening.
• Avoid direct contact with the leads and terminals. High voltage on leads can
cause electrical shock.
• Ensure that the transmitter casings are sealed when the assembly is in
operating condition.
• Only trained and qualified personnel may undertake start-
maintenance activities.
6.1 Hardware Maintenance
Perform maintenance task at regular intervals. Set the maintenance schedule in advance
and maintain a logbook to note maintenance activity details. Maintenance schedule
depends on the system, installation conditions, working medium and rigorousness of the
operation. Consider the system downtime when maintenance cycle is running. Ensure
that it does not affect the system performance.
Maintenance majorly involves sensor cleaning and verifying connections.
Test Terminal
Test Terminal is marked as TEST on the terminal
block. Connect TEST and negative terminal to the
test terminal. Ensure that the voltage across the
receptacles is kept below the diode threshold
voltage so that no current passes through the
diode. Make sure that the resistance of the test
connection does not exceed 10 ohms while
connecting an indicating meter or while taking the
test readings. Note that a resistance of 30 ohms
can cause an error of approximately 10% of actual
value.
The transmitter assembly comes in dual-compartment housing; one contains the
electronic module, and the other contains all wiring terminals and the communication
receptacles. The separate compartment of wiring terminals ensures hassle free handling
while running a routine maintenance cycle.
Module
Terminal
External Cleaning
• Use washing agent that will not damage the instruments.
• Protect the pressure sensing diaphragm from mechanical damage caused by sharp
objects or external pressure.
• Mechanical cleaning of the diaphragm is strictly prohibited.
• Do not point the nozzles to the diaphragm when cleaning by pressure washer.
Depot Repair
Execute following steps before sending the device for depot repair:
• Disconnect the transmitter carefully. Preserve all accessories and cables for
reassembling.
• Remove the harmful residues such as inflammable, poisonous, cancer genic and
radioactive substances.
• Repack the device in original packaging material provided at the time of delivery
and send for repair.
Discard Disposal
It is recommended to pass the instrument to specialized recycling companies rather
than local recycling points.
Check for a minimum of 250 ohms
resistance between the power
Check for an adequate voltage to
the transmitter. The transmitter
Check for intermittent shorts, open
High Output
Sensor Input Failure
Connect
and enter the
Transmitter test mode to isolate a
sensor failure.
Loop Wiring
Check for dirty or defective
terminals, interconnecting pins, or
receptacles.
Power Supply
Check the output voltage of the
7 Troubleshooting
This section provides troubleshooting techniques for most common operating problems.
When device malfunction is suspected despite the absence of any diagnostic messages on
the HHT, inspect following points.
• If measurement signal appears irregular, check whether the process pressure is
within the working range, or the abnormality lies in the measuring system,
installation environment or pressure transmitter. Once diagnosed take
corresponding measures.
• If no signal output or unchanged output signal on corresponding process pressure
changes is observed, then check the power supply polarity, open or short circuit.
Check the parameters like voltage, power and load resistance meet the normal
working requirements. Also, ensure there is no leakage or pressure-impulse line
blockage and shut-off valve is closed.
• If the output signal is large or outside the normal range, check whether the supply
voltage, power consumption, and load resistance meet the normal working
requirements of pressure transmitters. Verify measuring range settings and adjust
the device calibration. Also, ensure there is no leakage, pressure-impulse line
blockage or rapid temperature fluctuations in the installation and shut-off valve is
closed.
7.1 Symptoms and Corrective Measures
Refer to the table below to verify whether the transmitter hardware and process
connections are in good working condition: