Read this manual before working with the product. For personal and system safety, and for optimum
product performance, make sure you thoroughly understand the contents before installing, using, or
maintaining this product.
For technical assistance, contactCustomer Support796 Tek-DriveCrystal Lake, IL 60014USATel: +1 847 857 6076, +1 847 655 7428
No part of this publication may be copied or distributed, transmitted, transcribed, stored in a
retrieval system, or translated into any human or computer language, in any form or by any means,
electronic, mechanical, manual, or otherwise, or disclosed to third parties without the express
written permission. The information contained in this manual is subject to change without notice.
Tek-Thermal 1700B is specially designed for air and N2 applications, such as
compressed air, venting air, aeration, process protection N2, and combustion air.
1.2 Certification
General purpose IP67/NEMA 4X
1.3 Safety Instructions from the Manufacturer
Disclaimer
The manufacturer will not be held accountable for any damage that happens by
using its product, including, but not limited to direct, indirect, or incidental and
consequential damages.
Any product purchased from the manufacturer is warranted in accordance with the
relevant product documentation and our Terms and Conditions of Sale.
The manufacturer has the right to modify the content of this document, including
the disclaimer, at any time for any reason without prior notice, and will not be
answerable in any way for the possible consequence of such changes.
Product Liability and Warranty
The operator shall bear authority for the suitability of the device for the specific
application. The manufacturer accepts no liability for the consequences of misuse by
the operator. Wrong installation or operation of the devices (systems) will cause the
warranty to be void. The respective Terms and Conditions of Sale, which forms the
basis for the sales contract shall also apply.
Information Concerning the Documentation
To prevent any injury to the operator or damage to the device it is essential to read
the information in this document and the applicable national standard safety
instructions. This operating manual contain all the information that is required in
various stages, such as product identification, incoming acceptance and storage,
mounting, connection, operation and commissioning, troubleshooting, maintenance,
and disposal.
You must read these instructions carefully prior to installing and commissioning the
device. These instructions are an important part of the product and must be kept for
future reference. Only by observing these instructions, optimum protection of both
personnel and the environment, as well as safe and fault-free operation of the device
can be ensured.
For additional information that are not discussed in this manual, contact the
manufacturer
Warnings and Symbols Used
The following safety symbol marks are used in this operation manual and on the
instrument.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in
th or serious injury
dea
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result i
n
minor or moderate injury. It may also be used to alert against unsafe practices.
NOTE
Indicates that operating the hardware or software in this manner may damage it or
lead to system failure.
Unpack and check the contents for damages or signs of rough handling. Report
damage to the manufacturer immediately. Check the contents against the packing
list provided.
Transportation
• Avoid impact shocks to the device and prevent it from getting wet during
transportation.
• Verify local safety regulations, directives, and company procedures with respect
to hoisting, rigging, and transportation of heavy equipment.
• Transport the product to the installation site using the original manufacturer’s
packing whenever possible.
Storage
If this product is to be stored for a long period of time before installation, take the
following precautions:
•Store your product in the manufacturer’s original packing used for shipping.
•Storage location should conform to the following requirements:
oFree from rain and water
oFree from vibration and impact shock
oAt room temperature with minimal temperature and humidity
variation
•Before storing a used flowmeter remove any fluid from the flowmeter line
completely. Properties of the instrument can change when stored outdoors.
This section covers the reference and specification data, as well as ordering
information.
2.1 Introduction
Tek-Thermal 1700B Thermal Mass Flowmeters, also known as the thermal dispersion
or immersible mass flowmeters, are the precision instruments to measure mass flow
of fluid flowing in a closed channel like a pipe or duct. Tek-Thermal 1700B is specially
designed for air and nitrogen (N2) applications. It has the more compact design. It has
a small enclosure and thin insertion probe tube. It is used in high-pressure
applications.
2.2 Measuring Principle
The Tek-Thermal 1700B measures the gas mass flow based on Thermal Diffusion
theory. It has two RTD (Resistance temperature Detector) sensors. One sensor
measures the velocity of gas flow (Rh) and the other sensor detects the temperature
shift of gas flow (Rmg). When there are two RTDs in the gas flow, Rh will be heated and
Rmg will sense the temperature difference. As the velocity of gas flow increases, more
heat will dissipate and so the temperature read by Rh will decrease.
Tek-Thermal 1700B Thermal Mass Flowmeter design is based on constant power
measuring method, thus the RTD is heated on a consistent power and will be more
durable and stable. Due to that, Tek-Thermal 1700B has less problem of zero-off
which may cause a function failure of RTD due to overheating the term.
Accuracy ±0.5% of Reading
Maximum Pressure 232 PSI
Temperature of
medium
Power supply 13.5 to 42 VDC or 85 to 265 VAC
Response time 1 second
Output 4 to 20mA and Pulse standard
Communication Modbus RS485 or HART optional
Display Indication Mass flow, Volume flow in normal condition, Total flow,
Ingress Protection IP65
2 to 200 ft/sec or 1 to 100 ft/sec or 3 to 300 ft/sec
This section covers instructions on installation and commissioning. Installation of the
device must be carried out by trained, qualified specialists authorized to perform such
works.
CAUTION
• When re
moving the instrument from hazardous processes, avoid direct
contact with the fluid and the meter
• All installation must comply with local installation requirements and local
electrical code
3.1 Selecting the Installation Location
The flowmeter is designed to withstand the severe environmental conditions.
However, to ensure stable and accurate operation, observe the following precautions
when selecting an installation location.
• Ambient Temperature
Avoid locations subject to wide temperature variations or a significant
temperature gradient. If the location is exposed to radiant heat from plant
equipment’s, provide adequate thermal insulation and/or ventilation.
• Ambient Atmosphere
Avoid installing the transmitter in a corrosive atmosphere. If the transmitter must
be installed in a corrosive atmosphere, there must be adequate ventilation as well
as measures to prevent intrusion or stagnation of rain water in conduits.
• Shock and Vibration
Select an installation site with minimum shock and vibration (although the
transmitter is designed to be relatively resistant to shock and vibration).
1. Use cutting torch or sharp cutting tool to tap into the pipe. The pipe opening must
be at least 0.5 inch (0.04 ft) in diameter (Do not insert sensor probe through a
smaller hole)
2. Remove the burrs from the tap and sharp edges may causes flow profile disturbance
that can affect the accuracy of flowmeter
3. Weld the MNPT ½” socket (Part No.1) on the open hole. The correct insertion depth
places the centreline of the sensor access hole in probe at the pipe line’s centreline
4. Bolt the ½” ball (isolation) valve (Part No.2) with FNPT threads on both ends of the
socket. Seal the thread connection with thread sealant. The lever on the ball valve
should be up when the valve is open.
5. Insert the sensor probe through the ball valve (isolation valve) into the pipe. The
correct insertion depth places the sensor at the pipe’s centreline.
6. Calculate the insertion depth of the sensor probe,
Where,
A=Inner diameter of the pipeline
B=Thickness of the pipe line
C=The distance between the top of the pipeline and the upper end of the nut when
the nut is fixed
7. connect the sleeve (Part No.3) on the meter and the ball valve (isolation valve), seal
the thread connection part with thread sealant. Tighten the nut (Part No.4) with
wrench.
This section covers the all electrical connection requirement. Electrical connection of
the device must be carried out by trained, qualified specialists authorized to perform
such work by the installation site.
• Connect all electrical cables when the power is switched off. If the device does
• The device must be grounded to a spot in accordance with regulations in
WARNING
not have switch-off elements, then, overcurrent protection devices, lightning
protection and/or energy isolating devices must be provided by the customer.
order to protect personnel against electric shocks.
NOTE
• When using the measuring device in hazardous areas, installation must comply
with the corresponding national standards and regulations and the Safety
Instructions or Installation or Control Drawings.
4.1 Grounding of Measuring Device
Tek-Thermal 1700B Thermal Mass Flowmeter the power supply of signal processing
circuit is transferred from outside power supply by an isolation type DC-DC
transmitter with advanced grounding technology. The field frequency interference can
be isolated. The “V” terminal of power supply should not be connected to the ground.
When
Tek-Thermal 1700B is used in the strong interference environment, the shell should be
clean and connect to the earth through the cable, so that interference can be
eliminated.
It has AC and DC power options. Supply power must be 13.5 to 42 VDC and 85 to 265
VAC.
Wiring for 3-Wire Pulse Output
3-wire pulse output requires a power source of 13.5 to 42 VDC. Tek-Thermal 1700B
use a current pulse output with 50% duty ratio. Add resistor between and “V-”,
the resistance should be within 500Ω to 1000Ω, and power consumption should be
no less than 0.5W
This section covers operation techniques and guidelines.
5.1 Local Operation and Display
Tek-Thermal 1700B provide local display and setting, can display several variables on
the local multifunctional LCD display. It has 3 buttons used for configuration. The local
display enables you to read all important parameters directly at the measuring point
and configure the device using the function matrix. The LCD display indicates output.
Tek-Thermal 1700B has three buttons are placed on the top of the display, which are
used as L-R button, used as U-D button, used as Enter button.
• Pressing the L-R button will move the menu selection to the left/right, or the data
entry field to the left/right if updating a menu value
• Pressing the U-D button will move the menu selection up/down, or increment the
data entry field if you are updating a menu value
• Pressing enter button to save the current value
All the “Digital setting” and “Code Setting” of the flowmeter is made through these 3
buttons.
Tek-Thermal 1700B Thermal Mass Flowmeter has a display to indicate temperature,
flow rate, total flow and more parameters.
The LCD display has 2 areas to display the content, the upper row, the lower row.
The upper row displays the flow rate, mass flow, and standard flow rate. Below the
upper row displays the unit of the variable displayed in the upper row.
The lower row displays other variables, such as frequency, pressure, temperature,
density and total flow. And below the lower row displays the unit of the variable
displayed in the lower row.
Tek-Thermal 1700B Multi-Variable version can also display temperature. Users can
switch the parameter displayed on LCD by using the buttons and the next parameter
will be displayed for 30 seconds. Users can also fix the lower row to display a
parameter consistently. You can also set the lower row to display several variables in
circular turn.
Total Flow on Display
The lower row of the flowmeter displays total flow. Tek-Thermal 1700B can display 9
digits left to decimal point and 3 digits right to the decimal point. When more than
six digit displays on LCD, the total flow reading will be displays two times. First
displays the right digits and then displays the left digits. The left digits display with a
mark “x1000”. By using L-R button you can switch the left and the right digits on LCD.
To check the right digits now, press the “L-R button”, the display will be
According to picture, the total flow is 569864.581 kg
• In working mode, press the “Enter” button and “U-D” button at the same time to
entre in the code setting
• In the code setting first row displays the reference number and lower row
displays the content of this parameter
• Use the “L-R” button to move to the next digit and use “U-D” to cycle through
the number. Once the correct value has been entered, hit the “Enter” button to
save current value.
• The C01=02, that is set the pre-heating time to 2 seconds.
• Press the “Enter” button and “U-D” button at the same time to exit the code
• To enter in to the digital setting, press “Enter” and “L-R” button at the same
time.
• The first row displays the reference number of digital setting and lower row
display the content of this parameter
• Use the “L-R” button to move to the next digit and use “U-D” to cycle through
the number. Once the correct value has been entered, hit the “Enter” button to
save the current value
• In below picture, D001=1.60000, Max flow is 1.6 (unit according to another
setting)
• Press the “Enter” button and “U-D” button at the same time to exit the code
setting menu
To set the new password, use “U-D” button to cycle through numbers and “L-R”
button to move to the next digit. The user must have entered the password twice. If
power is off once the password has been entered, hit “Enter” button to save the
current password value.
5.3 Bluetooth Access
How to download the application
• Visit Apple’s application store
• Search “Tek-trol Bluetooth” or “Tek-Bluetooth” to find our app profile
This section covers guidelines for setting up RS485 Modbus communication
6.1 RS485 Modbus
The communication interface should be RS485, the range of Baud rate should be 1200
to 115200. The wiring terminal is “A” and “B”. The communication should comply with
MODBUS-RTU.
The combination of a communication signal: Address code - function code – date
segment – CRC calibration code. The distance between two characters should not be
longer than one character, or it will be considered as the beginning of a new message
or the end of an old message. The message is combined with hexadecimal arrays.
6.2 Address of the Displayed Date
The displayable dates including flow rate, pressure, temperature and total flow, if
the meter is not multi-variable version, then the reading of pressure and
temperature will both be 0. The date of the parameters in above chart can be read
by using function code 03 according to the address above and shifting.
6.3 Address of Code Setting
Register Usage Range Nature Date type
1000 Pre-heating time
(warm up) C01
1001 Density
compensation
C02
1002 Method of pulse
output
1004 Output C05 0 to 2 Read/Write Short
1005 Pulse output
parameter
1006 Damping C07 1 to 16 Read/Write Short
1007 Instrument
number C08
1008 Baud rate C09 1-24Read Short
1009 Unit of time C10 0-2Read/Write Short
1010 Mass unit C11 0-2Read/Write Short
1011 Volume unit C12 0-6Read/Write Short
1012 Pressure unit
TEKMATION LLC reserves the right to change the designs and/or materials of its products without notice. The contents of this publication are the property
Tek-Trol is a fully owned subsidiary of TEKMATION LLC. We oer our customers a comprehensive range of products and solutions
for process, power and oil & gas industries. Tek-Trol provides process measurement and control products for Flow, Level,
Temperature & Pressure Measurement, Control Valves & Analyzer systems. We are present in 15 locations globally and are known
for our knowledge, innovative solutions, reliable products and global presence.